Lngineering Product Data

(50Hz/P22)
TH5CST2-03C
Peplace TH5CST2-038
#EILING#ASSETTE
2 Ceiling Cassette(50Hz, R22)
General Description
Thank you very much for your special patronage of LG air conditioners.
LGs "Ceiling Cassette" is a indoor unit which is installed for the significant purpose. The ceiling cassette is
used for the commercial purposes. It can be installed in various places such as restaurants, hotels, offices and
meeting rooms.
This unit has nice outlook and is equipped with many special features. It has four louver for the air circulation in
all directions which in turn can maintain even and wide cooling. In other side it has facility for high elevation pip-
ing (30m), built in drain pump (drain throw 70cm),high ceiling operation,others for facilitating its working.
Noise level of the unit is very low.
In installation field unit is installed in fall ceiling. It has wide capacity range from 18 to 48 kBtu/h.
A lot of information regarding the design & installation of this system is provided in this publication. This new
products series contains data on the same pattern.
Please utilize all the information for conducting your business efficiently.
Make sure the specification, dimension or others technical data are same as provided in enginering data book
before you start the project.
We look forward to your continuing support.
LG Electronics lnc.
Air Conditioning Division
Table of contents
Table of contents Page
1. Models List .............................................................................................................................................................. 4
2. Model Number Nomenclature ....................................................................................................................... 5
3. Feature & Benefts .............................................................................................................................................. 6
4. List of Functions ...................................................................................................................................................
14 5. Specifcations ........................................................................................................................................................
18 6. Dimensional Drawings .....................................................................................................................................
21 7. Wiring Diagrams ................................................................................................................................................
25
8. Refrigerant Cycle Diagrams ........................................................................................................................
26 9. Selection Procedure .........................................................................................................................................
27 10. Performance Data .............................................................................................................................................
33 11. The Coefcient of Capacity Change ....................................................................................................
34
12. Operation range...................................................................................................................................................
35 13. Air Velocity and Temperature Distributions(Reference Data) .............................................................
14. Sound Levels ...................................................................................................................................................... 37
15. Installation .............................................................................................................................................................38
16. Function of Remote Control ....................................................................................................................... 50
LG Airconditioners Product Data
3 2007 Product Data
12
4
1. Models List
1.1 Cooling Only
5.3 18
HT-C186HLA1
HT-C246HLA1
1, 220-240V, 50Hz
R22
Nominal Capacity
,V,Hz
HT-C306HLA0
30
HT-C368DLA0
HT-C488DLA0
kW
kBtu/h
Model Name Refrigerant
3, 380-415V, 50Hz
8.8
36
48
10.5
14.0
7.0 24
Ceiling Cassette(50Hz,R22)
HT-C186HLA0
HT-C246HLA0
Power Supply
Model
2. Model Number Nomenclature
H T C 1 8 6 H L
Development Sequence
Function
A : Basic C : Plasma Air Purifying
E : Elevation Grille F : Elevation Grille + Plasma Air Purifying
Decoration Panel Information
L : Basic Panel
H : TH Chassis D : TD1 Chassis
Chassis Type
Electric Standard (Volts / Freq. / Phase)
6 : 220-240V, 50Hz, 1 8 : 380-415V, 50Hz, 3
Nominal Cooling Capacity
Ex) 18-> 18,000 Btu/h 24-> 24,000 Btu/h
Model Type
C : Cooling Only
A 0
H : Development in Thailand
T : Cassette Type
N : Indoor Type , U : Outdoor Type
2.1 Model Number Nomenclature
5 2007 Product Data
6 Ceiling Cassette(50Hz,R22)
3. Features & Benefits
Energy Saving Gold Fin (Optional)
Heat Exchanger fins are coated with anticorrosive &
hydrophilic layers. It prevents the corrosion of heat
exchanger. Fins remain as new even after long time
of operati on and mai ntai ns effi ci ency of heat
exchanger constant. It also saves power & mainte-
nance Cost.
Compact Design and Easy Installation
Only about 225mm height in the ceiling is sufficient for installation space.
Low Noise with 3-dimensional
turbo fan
The most advanced low-noise design.
The adoption of turbo-fan and round type heat
exchanger provides the quietest operation.
Hygienic and Easy-to-Clean Filter
Washable and anti bacteria filter is adopted.
It is easy to open grille and replace clean filter.
840mm
840mm
225mm
(For TH Chassis)
7 2007 Product Data
3. Features & Benefits
Central Cont rol (Optional)
It enables to control 16 x 8 = 128 units with the help
of 8 controllers. All units can be put on and off from
one central room. For setting the temperature, fan
speed and other sub functions, access the sespec-
ture LCD wired remote controller of each unit.
Cooling & Fan Operation( for cooling on ly)
LG Ceiling Cassette air conditioner provides cooling & fan operation. In the cooling mode, it cools the air with
an operation range of 18~30C. In the fan operation mode, only indoor fan at the selected speed will run, out-
door fan and compressor will be off.
Wired Remote Cont rol (Accessory)
It can control all the functions of the unit. You can
check/set temperature, change operation mode, set
timer & also diagnose the error of the unit. It also
has the option of weekly program.
Auto Resta rt Operation
When there is electricity failure the unit shuts off and after resumption of the power, unit will start in the same
mode as prior to the power failure. Memorized condition are on / off condition, operating mode (cooling/heat-
ing), set temperature and fan speed.The unit will memorize the above conditions and start with same memo-
rized condition.
Two Thermistor Cont rol (Accessory)
There may be a significant difference between the temperature taken at the installed product and indoor tem-
perature. Two thermistor control provides option to control temperature by referring any of the two tempera-
tures. With the help of the slide switch at the back of the LCD wired remote controller, selection of the desired
thermistor for controlling the unit can be done. One thermistor is in the Indoor unit & the other one is in the
LCD wired remote.
Main
PCB
Controller
# 1
Controller
# 2
Controller
# 8
M
1
Sub
1
M
2
Sub
2
M
16
Sub
16
M
17
Sub
17
M
18
Sub
18
M
128
Sub
128
Timer
Program
Hour
Cancel 2ndF
Week Holiday
Set/Clr
Min
RESET
PLASMA
ZONE 1 2 3 4
Operation unit No Func
Humidify JET
SLo
AUTO
AUTO SWING OPERATION FAN SPEED
Program set
SUB FUNCTION SET TEMP
Room Temp
HI
MED
LO
Heater
Defrost
Filter
Preheat
Out door
Time
Timer
On
Set no. Time
Off
01 03 05 07 09 11 13 15 17 19 21 23
2ndF
8 Ceiling Cassette(50Hz,R22)
3. Features & Benefits
Ceiling Board Drain Pan
Maximum 700mm
Drain Pump
Flexible drain hose
Pipe fixture
Slope 1/50~1/100
Hard Tube(ex.PVC)
+
+
+
+
Polluted Air Purified fresh Air
+4.8KV discharge
Ionizer Photo-Catalyst Coated Mesh
Dust particles
Odour
Dust electrode discharge
Odour molecule
Generating plasma
Plasma Air Purifying System (Optional)
The PLASMA Air Purifying Function not only removes micro-
scopic contaminants and dust, but also removes house
mites, pollen, and pet fur helps to prevent allergic diseases
like asthma.
High Head Drain Pump(700mm)
Built-in Drain Pump drains out water automatically.
A standard drain-head height of up to 700 mm is possible, creating the ideal solution for perfect water drainage.
High Ceiling Operation (Accessory)
According to the height of the installation, it provides vari-
ability of indoor fan motor rpm. If the height of installation
is low then you can adjust low rpm of indoor fan motor.
On the other hand if the height of the installation is high
you can adjust high rpm of indoor fan motor. Selection of
speed can be done by slide switch at the back of the LCD
wired remote.
Installation on the
normal-height ceiling
installation on the
higher ceiling
2007 Product Data 9
Child Lo ck Function (Accessory)
It prevents the children or others from tampering
with the control buttons. Unit can be controlled by
the wireless remote controller. This can be easily set
by pressing timer key & Min key simultaneously.
After child lock is set, pressing any key will display
CL on the LCD for 3 seconds and all the keys will be
ineffective.
Jet Cool
In this mode quick and fast cooling is done. Cold
and high velocity air is supplied to the room till the
indoor temperature reaches 18 C.
Swirl Swing (Accessory)
It is the function for comfort cooling/heating operation.
The diagonal two louvers are opened the
more larger than the other louvers.
After one minute, it is opposite.
Group Cont rol (Accessory)
It enables to control up to 16 units with the help of
one wired remote controller.All the units will follow
same setting of temperature & other sub functions.
1 2 16 ........
........

Vane 2 Swirl Swing(New) 4- Open(Conventional)
Swirl Swing(New) 4- Open(Conventional)
2.4% 4.8% 100% Improved
Comparison of Air Flow Types
Comparison of Floor
Temp. Distribution(20 C)
Vane 1 Close Open Open
Open
Open
Open
Close Close Open
Vane 3 Close Open Close Close Open
Open Open Close Close Open Vane 2
Open Open
Time
Close Close Open Vane 4
Vane 1
Vane 3
Vane 2
Time
Vane 4
Vane 3
Vane 4
Vane 1
3. Features & Benefits
Timer
Program
Hour
Cancel 2ndF
Week Holiday
Set/Clr
Min
RESET
PLASMA
ZONE 1 2 3 4
Operation unit No Func
Humidify JET
SLo
AUTO
AUTO SWING OPERATION FAN SPEED
Program set
SUB FUNCTION SET TEMP
RoomTemp
HI
MED
LO
Heater
Defrost
Filter
Preheat
Out door
Time
Timer
On
Set no. Time
Off
01 03 05 07 09 11 13 15 17 19 21 23
2ndF
CHILD LOCK Display
ZONE 1 2 3 4
Operation unit No Func
Humidify JET
SLo
AUTO
AUTO SWING OPERATION FAN SPEED
Program set
SUB FUNCTION SET TEMP
RoomTemp HI
MED
LO
Heater
Defrost
Filter
Preheat
Out door
Time
Timer
On
Set no. Time
Off
01 03 05 07 09 11 13 15 17 19 21 23
2ndF
o
10
Ceiling Cassette(50Hz,R22)
3. Features & Benefits
Space Control (Accessory)
Vanes angle can be controlled by pair, considering its
installation environment.
For example direct drafts can be annoying, leading
to discomfort and reduced productivity vane control
helps to eliminate this problem.
Easily controlled by wired remote control.
Air Flow can be controlled easily regarding any
space environment.
+2C
+1C
+0.5C
Setting Temp.
COMP
Cooling Cooling Heating
on
Set
Mode
Set
Mode
Set
Mode
Set
Mode
Low/
Stop
Low/
Stop
Set
Mode
off
Low Low Low Stop
off off off off off on on on on
CYCLE
Indoor
FAN
-0.5C
-1C
-2C
Inside Temp
11 2007 Product Data
Time Delay Safety Function
It delays restarting of the compressor by three min-
utes thereby preventing damage to the compressor.
Long Refrigerant Piping
LG Ceiling Cassette air conditioners can cover up to
30 m length and 15 m height. It provides flexibility of
installation and keep the building in a good outlook.
Zero Standby Power
Due to SMPS (Switching Modulation Power Supply)
technology, there is almost zero power consumption
in the standby mode.
15m
30m
5~6W
0.5W
3. Features & Benefits
Category Function
HTNC186HLA0 HTNC246HLA0
HTNC306HLA0 HTNC368DLA0 HTNC488DLA0
Ai r sup p ly out let 4 4 4 4 4
Ai rflow d i rect i on cont rol(left & ri ght ) - - - - -
Ai rflow d i rect i on cont rol(up & d own Aut o Aut o Aut o Aut o Aut o
Aut o swi ng(left & ri ght ) - - - - -
4/ 5
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -



Wi red remot e cont roller(for h ot el use)
Wi reless remot e cont roller(si mp le)
General cent ral cont roller (Non LGAP)
Dry cont act




Ind i vi d ual
cont rol
CAC
net work
funct i on
Speci al
funct i on ki t
Ai r flow
Ai r puri fyi ng
Inst allat i on
Reli abi li t y
Conveni ence
HTNC186HLA1 HTNC246HLA1
Aut o swi ng(up & down)
12 Ceiling Cassette (50Hz,R22)
4. List of Functions
Ai rflow st ep s(fan/cool)
Chaos wind
Vane Control
Jet cool(Power wi nd )
Swi rl wi nd
Aut o rest art op erat i on
Elect ro t hermost at
CTIE
PDI(power d i st ri but i on i nd i cat or)
PI 485
Z one cont rol
Simple central control (LGAP)
Wi reless LCD remot e cont rol
Si mp le wi red remot e cont roller
Delux e wi red remot e cont roller
St and ard wi red remot e cont roller
Two t hermi st or cont rol
Ti mer(weekly)
Ti mer(on/off)
Sleep mod e
Group cont rol
Forced op erat i on
Chi ld lock
Aut o operat i on(art i fi ci al i nt elli gence)
Aut o cleani ng
Aut o changeover
Soft d ry op erat i on
Self d i agnosi s
Hot st art
Deod ori zi ng fi lt er
Plasma ai r p uri fi er
Prefi lt er(washable / ant i -fungus)
Drai n p ump
E.S.P. cont rol
Elect ri c heat er(op erat i on)
High Ceiling Operation











Accessory Acc e ssory Acc e ssory Ac cessory Ac cessory
Accessory Acc essory Ac cessory Ac cessory Acc e ssory
Accessory Acc e ssory Acc essory Ac cessory Ac c essory
Others

Option Option Option Option Option
Accessory Ac cessory Ac c essory Ac ce ssory Acc essory
Accessory Ac cessory Acc essory Ac ce ssory Acce ssory
Zero Stand by Power
Accessory
O : Applied, X : Not applied, - : No relation
* Option : Model name & price are different according to options, and assembled in factory with main unit
* Accessory : Installed at field, ordered and purchased separately by the corresponding model name,
Note:
supplied separate package.
Accessory Accessory Accessory Accessory
Accessory Accessory Accessory Accessory Accessory
Accessory Accessory Accessory Accessory Accessory



Option Option Option Option Option
Option Option Option Option Option
Option Option Option Option Option
Accessory Accessory Accessory Accessory Accessory
( ) 3/4 4/ 5 ( ) 3/4 4/ 5 ( ) 3/4 4/ 5 ( ) 3/4 4/ 5 ( ) 3/4 (wired remote)
(auto wind)
Category Function
HTUC 186HLA0 HTUC 246HLA0
HTUC 306HLA0 HTUC 368DLA0 HTUC 488DLA0
Defrost/Deicing
High pressure switch - - - - -
Phase protection
- - - - -
Reliability
HTUC 186HLA1 HTUC 246HLA1
Restart delay(3-minutes)
13 2007 Product Data
4. List of Functions
Self diagnosis
Soft start
Test function
Thermistor
Low ambient operation
Auto operation(Artificial intelligence)
Auto restart operation
Network soluation(LGAP)
PDI(Power Distribution Indicator)
PI485

CAC network
function
Convenience
Special
function kit
Others
Low pressure switch
- - - - -
- - - - -



- - - - -

- - - - -
- - - - -
- - - - -
- - - - -
O : Applied, X : Not applied, - : No relation
* Option : Model name & price are different according to options, and assembled in factory with main unit
* Accessory : Installed at field, ordered and purchased separately by the corresponding model name,
supplied separate package
- - - - -
14 Ceiling Cassette(50Hz,R22)
5. Specifications
/ V / Hz 1 / 220 240 / 50
kW 5.3 5.3 7 7
Btu/h 18,000 18,000 24,000 24,000
kW - - - -
Btu/h - - - -
Current Nominal Running Current A 0.3
Induction Induction Induction Induction
Turbo Fan Turbo Fan Turbo Fan Turbo Fan
100
CMM 15 / 12 / 10 15 / 12 / 10 17 / 15 / 13 17 / 15 / 13
cfm 350 300 260 / / / / / / / /
External Static Pres s ure mmAq - - - -
Capacitor F / Vac
Direct Direct Direct Direct
Coil
Body mm(inch)
Decorative Panel mm(inch)
Body kg (lbs ) 26(57) 26(57) 26(57) 26(57)
Decorative Panel kg (lbs )
Long Life Filter
dB(A)+3 32 / 28 / 25 32 / 28 / 25 35 / 33 / 30 35 / 33 / 30
Liquid mm (inch) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4)
Gas mm (inch) 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8)
Drain (ID) mm 32 32 32 32
l/h 1.9 1.9 2.4 2.4
Fus e Fus e Fus e Fus e
Thermis tor Thermis tor Thermis tor Thermis tor
R22 R22 R22 R22
Capillary Tube Capillary Tube Capillary Tube Capillary Tube
Single Single Single Single
No.mm
2
3 x 2.5 (4 0.75) 3 x 2.5 (4 0.75) 3 x 2.5 (4 0.75) 3 x 2.5 (4 0.75)
Ceiling Cessette Type
Air Filter
Referigerant
Fan
Air Flow Rate
(H / M / L)
Cooling Capacity
Heating Capacity
Connectable Outdoor Unit
Power and Trans mis s ion Interunit Cable
Sound Level (H / M / L)
Dehumidification Rate
Safety Devices
Temperature Sens or
Piping Connections
Referigerant Control
Dimens ions (W x H x D)
Net Weight
Power Supply
Motor Type
Motor Output(W) x No. of Unit
Fan Type
Drive
Row Column FPI
1 / 220 240 / 50 1 / 220 240 / 50 1 / 220 240 / 50
HTNC186HLA0 HTNC186HLA1 HTNC246HLA0 HTNC246HLA1
Indoor Unit Type
Model
Model No : H TNC186HLA0, HTNC186HLA1, HTNC246HLA0, HTNC246HLA1
0.3 0.3 0.3
100 100 100
Note :
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27 (80.6 ) DB/19 (66.2 ) WB
- Outdoor Temperature 35 (95 ) DB/24 (75.2 ) WB
Heating: - Indoor Temperature 20 (68 ) DB/15 (59 ) WB
- Outdoor Temperature 7 (44.6 ) DB/6 (42.8 ) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
Long Life Filter Long Life Filter Long Life Filter
5(11) 5(11) 5(11) 5(11)
950*950*30(37.4*37.4*1.2)
840*840*225(33.1*33.1*8.9) 840*840*225(33.1*33.1*8.9) 840*840*225(33.1*33.1*8.9) 840*840*225(33.1*33.1*8.9)
950*950*30(37.4*37.4*1.2) 950*950*30(37.4*37.4*1.2) 950*950*30(37.4*37.4*1.2)
350 300 260 390 360 320 390 360 320
- - - -
2Rx9Cx18FPI 2Rx9Cx18FPI 2Rx9Cx18FPI 2Rx9Cx18FPI
15 2007 Product Data
5. Specifications
HT NC306HL A0 HT NC368DL A0 HT NC488DL A0
/ V / Hz 1 / 220 240 / 50 3 / 380 415 / 50 3 / 380 415 / 50
kW 8. 8 10. 5 14
Btu/h 30, 000 36, 000 48, 000
kW - - -
Btu/h - - -
C urrent Nominal R unning Current A 0. 3 0. 4 0. 4
I nduction I nduction I nduction
T urbo Fan T urbo Fan T urbo Fan
100 124 124
CMM 22 / 19 / 16 27 / 22 / 20 35 / 30 / 27
cfm 490 460 420 / / / / / /
External Static Pressure mmAq - - -
Capacitor F / Vac
Direct Direct Direct
C oil
Body mm( inch)
Decorative Panel mm( inch)
Body kg ( lbs )
Decorative Panel kg ( lbs )
dB( A) +3 41 / 39 / 37 42 / 37 / 36 48 / 45 / 42
Liquid mm ( inch)
Gas mm ( inch)
Drain (ID) mm 32 32 32
l/h 3 2. 9 4. 6
Fus e Fus e Fus e
T hermis tor T hermis tor T hermis tor
R 22 R 22 R 22

S ingle S ingle S ingle
No. mm
2

Dimens ions ( W x H x D)
Net W eight
P ower S upply
Motor Type
Motor Output( W) x No. of Unit
F an T ype
Drive
R ow Column F PI
C onnectable Outdoor Unit
P ower and T rans mis s ion I nterunit C able
S ound Level ( H / M / L)
Dehumidification R ate
S afety Devices
T emperature S ens or
Piping C onnections
R eferigerant C ontrol
Ceiling Cas s ette Type
Air F ilter
Model
R eferigerant
F an Air Flow Rate ( H / M / L)
Indoor Unit Type
C ooling C apacity
Heating C apacity
Model No : HTNC306HLA0,HTNC368DLA0,HTNC488DLA0
Note :
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27 (80.6 ) DB/19 (66.2 ) WB
- Outdoor Temperature 35 (95 ) DB/24 (75.2 ) WB
Heating: - Indoor Temperature 20 (68 ) DB/15 (59 ) WB
- Outdoor Temperature 7 (44.6 ) DB/6 (42.8 ) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
840*840*225(33.1*33.1*8.9) 840*840*225(33.1*33.1*8.9) 840*840*225(33.1*33.1*8.9)
950*950*30(37.4*37.4*1.2) 950*950*30(37.4*37.4*1.2) 950*950*30(37.4*37.4*1.2)
Long Life Filter Long Life Filter Long Life Filter
5(11) 5(11) 5(11)
510 460 420 630 580 500
- - -
2Rx9Cx18FPI 2Rx12Cx19FPI
2Rx12Cx19FPI
Ceiling Cassette(50Hz,R22)
5. Specifications
HTUC186HLA0 HTUC186HLA1 HTUC246HLA0 HTUC246HLA1
kW 5.3 5.3 7 7
Btu/h 18,000 18,000 24,000 24,000
kW - - -
Btu/h - - -
Cooling kW - - - -
Heating kW - - - -
- - - -
Cooling A 7.75 7.75 12 11
Heating A - - - -
Starting Current Cooling/Heating A 30 30 40 40
/ V / Hz 1/220~240/50 1/220~240/50 1/220~240/50 1/220~240/50
No.mm 3 x 2.5 3 x 2.5 3 x 2.5 3 x 2.5
Power and Transmission Cable
(Outdoor to ndoor or Outdoor to BD)
No. mm - - -
Dimensions W x H x D mm(inch) 870*655*320(34.2*25.8*12.6) 870*655*320(34.2*25.8*12.6) 870*655*320(34.2*25.8*12.6) 870*655*320(34.2*25.8*12.6)
57(125) 51(112) 62(136) 62(136)
1 1 1 1
Rotary Rotary Rotary Rotary
QP325PBA QJ292PBA QP407PAB QP407PAB
One Phase One Phase One Phase One Phase
Oil charge volume cc 700 450 700 700
High efficiency High efficiency High efficiency High efficiency
- - - -
- - - -
- - - -
Oil charge volume cc - - - -
- - - -
- - - -
- - - -
- - - -
Oil charge volume cc - - - -
- - - -
Cycle A Charge (at 7.5m) g(oz) 1,360(48) 1,100 (39) 1,440(51) 1,520(54)
Cycle B Charge (at 7.5m) g(oz) - - -
R22 R22 R22 R22
Capillary Tube Capillary Tube Capillary Tube Capillary Tube
g/m(oz/ft) 25(2.90) 25(2.90) 30(3.47) 30(3.47)
(2R 30C 21) 1 (2R 30C 21) 1 (2R 28C 18) 1 (2R 28C 18) 1
- - - -
Capacitor / Vac 6/370 6/370 6/370 6/370
Direct Direct Direct Direct
Side Side Side Side
Air Flow RateNo. of Fan CMM(cfm) 51(1810) x 1 51(1810) x 1 51(1810) x 1 51(1810) x 1
Sound Level(H/L) Sound Pressure dB(A)+3 62/- 66/- 67/- 67/-
Liquid(Cycle A) mm(inch) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4)
Gas(Cycle A) mm(inch) 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8)
Liquid(Cycle B) mm(inch) - - - -
Gas(Cycle B) mm(inch) - - - -
High Pressure Gas mm(inch) - - - -
Total Piping m 30
Main Piping m - - - -
Total Branch Piping m - - - -
Each Branch Piping m - - - -
Outdoor Unit~ndoor Unit m 7 7 7 7
ndoor Unit~ndoor Unit m - - - -
Cooling
o
C(
o
F) -21 43(69.8~109.4) -21 43(69.8~109.4) -21 43(69.8~109.4) -21 43(69.8~109.4)
Heating
o
C(
o
F) - - - -
Outdoor Unit Type Ceiling Cas s ette Type
No. mm 4 0.75(ncluding Earth) 4 0.75(ncluding Earth) 4 0.75(ncluding Earth) 4 0.75(ncluding Earth)
Piping Connections
Max. nterunit
Piping Length
Max. Elevation
Difference
Operation Range
(Outdoor)
Heat Exchanger
(Rows x Column x FP) No.
Defrosting Method
Fan
Drive
Discharge Direction(Side/Top)
Refrigerant
Type
Control
Additional Refrigerant Charge
Compressor (#3)
Type
Qty x Model
Motor type
Oil type
Compressor (#2)
Type
Qty x Model
Motor type
Oil type
Max. Number of Connectable ndoor Units
Compressor (#1)
Type
Qty x Model
Motor type
Oil Type
Power Supply Cable(Outdoor)
Power and Transmission Cable(BD to ndoor)
Net Weight
Nominal nput
(MinRatingMax)
Testing Combination
Running Current(Rating)
Power Supply
Outdoor unit
Nominal Capacity
(MinRatingMax)
Cooling
Heating
Model No : HTUC186HLA0,HTUC186HLA1,HTUC246HLA0,HTUC246HLA1
Note :
1. Capacities are based on the following conditions:
Cooling: - ndoor Temperature 27 (80.6 ) DB/19 (66.2 ) WB
- Outdoor Temperature 35 (95 ) DB/24 (75.2 ) WB
Heating: - ndoor Temperature 20 (68 ) DB/15 (59 ) WB
- Outdoor Temperature 7 (44.6 ) DB/6 (42.8 ) WB
Piping Length - nterconnecting Piping Length 7.5m
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
30 30 30
17 2007 Product Data
5. Specifications
HTUC306HLA0 HTUC368DLA0 HTUC488DLA0
kW 8.8 10.5 14
Btu/h 30,000 36,000 48,000
kW - - -
Btu/h - - -
Cooling kW - - -
Heating kW - - -
- - -
Cooling A 15 6 8.5
Heating A - - -
Starting Current Cooling/Heating A 68 55 58
/ V / Hz 1/220~240/50 3/380~415/50 3/380~415/50
No. mm 3 2.5 4 4 4 4
Power and Transmission Cable
(Outdoor to Indoor or Outdoor to BD)
No. mm - - -
Dimensions W x H x D mm(inch) 870 * 800 * 320(34.2*31.4*12.6) 900 * 1160 * 370(35.4*45.7*14.6) 900 * 1160 * 370(35.4*45.7*14.6)
73(160) 81(179) 87(192)
1 1 1
Rotary Scroll Scroll
NHT52VBAT SQ042YAA SB061YAA
One Phase Three Phase Three Phase
Oil charge volume cc 1300 1300 1,650
High efficiency High efficiency High efficiency
- - -
- - -
- - -
Oil charge volume cc - - -
- - -
- - -
- - -
- - -
Oil charge volume cc - - -
- - -
Cycle A Charge (at 7.5m) g(oz) 2,000(71) 2,000(71) 2,600(92)
Cycle B Charge (at 7.5m) g(oz) - - -
R22 R22 R22
Capillary Tube Capillary Tube Capillary Tube
g/m(oz/ft) 40(4.62) 40(4.62) 60(6.94)
(2R 36C 18) 1 (1R 22C 17) 2 (2R 26C 18) 2
- - -
Capacitor GG /Vac 6/470 6/400 6/400
Direct Direct Direct
Side Side Side
Air Flow RateNo. of Fan CMM(cfm) 51(1810) x 1 104 (3673) x 2 104 (3673) x 2
Sound Level(H/L) Sound Pressure dB(A)+3 58/- 67/- 71/-
Liquid(Cycle A) mm(inch) 6.35(1/4) 6.35(1/4) 9.52(3/8)
Gas(Cycle A) mm(inch) 15.88(5/8) 15.88(5/8) 19.05(3/4)
Liquid(Cycle B) mm(inch) - - -
Gas(Cycle B) mm(inch) - - -
High Pressure Gas mm(inch) - - -
Total Piping m 30 30 30
Main Piping m - - -
Total Branch Piping m - - -
Each Branch Piping m - - -
Outdoor Unit~Indoor Unit m 7 15 15
Indoor Unit~Indoor Unit m - - -
Cooling
o
C(
o
F) -21 GG43(69.8~109.4) -21 GG43(69.8~109.4) -21 GG43(69.8~109.4)
Heating
o
C(
o
F) - - -
4 0.75(Including Earth) 4 0.75(Including Earth) 4 0.75(Including Earth)
Ceiling Cas s ette Type Outdoor Unit Type
Piping Connections
Max. Interunit
Piping Length
Max. Elevation
Difference
Operation Range
(Outdoor)
Heat Exchanger
(Rows x Column x FPI) No.
Defrosting Method
Fan
Drive
Discharge Direction(Side/Top)
Refrigerant
Type
Control
Additional Refrigerant Charge
Compressor (#3)
Type
Qty x Model
Motor type
Oil type
Compressor (#2)
Type
Qty x Model
Motor type
Oil type
Compressor (#1)
Type
Qty x Model
Motor type
Oil Type
Power and Transmission Cable(BD to Indoor)
Net Weight
Max. Number of Connectable Indoor Units
No. mm
Testing Combination
Running Current(Rating)
Power Supply
Power Supply Cable(Outdoor)
Nominal Capacity
(MinGG RatingGG Max)
Cooling
Heating
Nominal Input
(MinGG RatingGG Max)
Outdoor unit
Model No : HTUC368DLA0,HTUC488DLA0
Note :
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27 (80.6 ) DB/19 (66.2 ) WB
- Outdoor Temperature 35 (95 ) DB/24 (75.2 ) WB
Heating: - Indoor Temperature 20 (68 ) DB/15 (59 ) WB
- Outdoor Temperature 7 (44.6 ) DB/6 (42.8 ) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
6.1 Indoor Units
18
Ceiling Cassette (50Hz,R22)
6. Dimensional Dr awings
L1
0
4
8
1
L
3
L 4
L
0
9
0
9
2
L
0
3
5
8
7
840
678
40
110 110
950
950
Unit:mm
840 Unit si ze
e
z
i
s
t
i
n
U
0
4
8
)
t
l
o
b
g
n
i
g
n
a
H
(
2
7
6
5
.
1
0
1
5
.
1
0
1
)
g
n
i
n
e
p
o
g
n
i
l
i
e
C
(
5
7
8
875 (Ceiling opening)
785(Hanging bolt) 45 45
4
1
2
3
950
0
5
9
6
0
3
5
L
(unit : mm)
L1 L3 L2 L4
Dimension
Model
HTNC186HLA0
225
288
70.4
140
139.8
210.5
84
152
Number Nam e
1 Liquid pipe connectio n 6.35
2 Gas pipe connectio n
HTNC186HLA0,
HTNC186HLA1
3 Drain pipe connection
4 Power supply connection
5 Air discharge grille
6 Air suction grille
Descripition
HTNC246HLA0,
HTNC246HLA1
HTNC306HLA0
HTNC368DLA0 HTNC488DLA0
6.35 6.35 6.35 9.52
12.70 15.88 15.88 15.88 19.05
- - - - -
- - - - -
- - - - -
- - - - -
(unit : mm)
Model No : HTNC186LA0, HTNC186LA1, HTNC246HLA0, HTNC246LA1, HTNC306HLA0
5
HTNC186HLA1
HTNC246HLA0
HTNC246HLA1
HTNC306HLA0
HTNC368DLA0
HTNC488DLA0
L5
47
52
19 2007 Product Data
Air discharge grille
W
6.2 Outdoor Units
W mm
H mm
D mm
L1 mm
L2 mm
L3 mm
L4 mm
L5 mm
L6 mm
L7 mm
L8 mm
L9 mm
L10 mm
L11 mm
mm
6.35
mm
15.88
HTUC306HLA0
Model
Dimensions
870 870 870
655 655 800
320 320 320
370 370 370
25 25 25
340 340 340
775 775 775
25 25 25
546 546 546
162 162 162
162 162 162
54 54 54
74.5 74.5 74.5
79 79 79
HTUC186HLA0 HTUC246HLA0
6.35 6.35
15.88 12.70
Model No : HTUC186LA0, HTUC186LA1, HTUC246HLA0,
(30k)
(18k,24k)
6. Dimensional Drawings
HTUC246LA1, HTUC306HLA0
HTUC186HLA1 HTUC246HLA1
20 Ceiling Cassette(50Hz,R22)
L6 L7 L8 L9
4
L
H
1
1
L
0
1
L
5
L
W
D
1
L
2
L
3
L
Gas side
3-way valve
Control cover
Liquid side
3-way valve
4-hole for anchor bolts
W mm
H mm
D mm
L1 mm
L2 mm
L3 mm
L4 mm
L5 mm
L6 mm
L7 mm
L8 mm
L10 mm
L11 mm
mm
mm
Mdel
Dimensions
HTUC368DLA0 HTUC488DLA0
900
1,165
370
460
45
410
1,135
30
550
175
175
112
120
83
900
1,165
370
460
45
410
1,135
30
550
175
175
112
120
83
6.35 9.52
15.88 19.05
6. Dimensional Drawings
L9 mm
Model : HTUC368DLA0, HTUC488DLA0
21 2007 Product Data
7. Wiring Diagrams
Model No : HTNC186HLA0, HTNC186HLA1,
CONNECTOR NUMBER LOCATION
CN-POWER AC POWER SUPPLY
CN-MOTOR BLDC FAN MOTOR OUTPUT
CN-D/PUMP DRAIN PUMP OUTPUT
CN-DISP DISPLAY
CN-FLOAT FLOAT SWITCH INPUT
CN-REMO REMOTE CONTROL
CN-GRILLE ELEVATION TWILLE
CN-CC CENTRAL CONTROL
CN-PIPE1 DISCHARGE PIPE SENSOR
CN-ROOM ROOM SENSOR
CN-HVB AIR CLEANER
CN-VANE1 STEP MOTOR
CN-VANE2 STEP MOTOR
HTNC306HLA0
7.1 Indoor Wiring Diagrams
HTNC246HLA0, HTNC246HLA1,
Option
22 Ceiling Cassette(50Hz,R22)
7. Wiring Di agrams
Model No : H TNC368DLA0, HTNC488DLA0
CONNECTOR NUMBER LOCATION
CN-POWER AC POWER SUPPLY
CN-MOTOR BLDC FAN MOTOR OUTPUT
CN-D/PUMP DRAIN PUMP OUTPUT
CN-DISP DISPLAY
CN-FLOAT FLOAT SWITCH INPUT
CN-REMO REMOTE CONTROL
CN-GRILLE ELEVATION TWILLE
CN-CC CENTRAL CONTROL
CN-PIPE1 DISCHARGE PIPE SENSOR
CN-ROOM ROOM SENSOR
CN-HVB AIR CLEANER
CN-VANE1 STEP MOTOR
CN-VANE2 STEP MOTOR
Option
Notes:
CM
BR
WH
COMPRESSOR
BROWN
WHITE
BL
OR
YL
BLUE
ORANGE
YELLOW
BK
RD
GN/YL
BLACK
RED
GREEN/YELLOW
7.2 Outdoor Wiring Diagrams
Model No : HTUC186HLA0, HTUC186HLA1,
Model No : HTUC306HLA0
7. Wiring Diagrams
HTUC246HLA0, HTUC246HLA1
23 2007 Product Data
Notes:
CM
BR
WH
COMPRESSOR
BROWN
WHITE
BL
OR
YL
BLUE
ORANGE
YELLOW
BK
RD
GN/YL
BLACK
RED
GREEN/YELLOW
Model No : HTUC368DLA0, HTUC488DLA0
(U)
(V)
(W)
24
7. Wiring Di agrams
Ceiling Cassette(50Hz,R22)
25 2007 Product Data
8. Refrigerant Cycle Diagrams
INDOOR UNIT OUTDOOR UNIT
INDOOR
COIL
OUTDOOR
COIL
COMPRESSOR
GAS SIDE
LIQUID SIDE CAPILLARY TUBE
Model No: HT-C186HLA0 , HT-C186HLA1, HT-C246HLA0
HT-C368DLA0, HT-C488HLA0
CAPILLARY TUBE
COOLING
15.88
Field Piping
Model
Gas(mm) Liquid(mm)
HT-C186HLA0,HT-C186HLA1
HT-C246HLA0,HT-C246HLA1
HT-C306HLA0
HT-C368DLA0
HT-C488DLA0
15.88
15.88
19.05
12.70
6.35
6.35
6.35
6.35
9.52
Refrigerant pipe connection part diameter
,HT-C246DLA1, HT-C306HLA0
26 Ceiling Cassette(50Hz,R22)
Step 1. Determine cooling load requirements at design conditions.
Required load conditions:
Required cooling capacity (TC).............................. 21,000 Btu/h
Sensible capacity (SHC) ........................................ 17,000 Btu/h
Temperature air entering Outdoor Unit ................. 95F
Temperature air entering Indoor Unit ..................... 80F DB/67F WB
DB dry bulb temperature
WB wet bulb temperature
Step 2. Select unit based on required cooling capacity.
Based on Total Cooling Capacity, choose suitable model from the specification table.
The model with net cooling capacity of 24,000 Btu/h is selected.
The system is HT-C246HLA0.
Verify the unit performance at the given conditions in accordance with step 3.
Step 3. Determine if system selected satisfies cooling requirements.
Enter cooling capacities table on page 31 at high speed and 95F outdoor entering air temperature
with 80F DB/67F WB indoor entering air temperature.
Total cooling capacity = 23,000 Btu/h, Sensible capacity=19,300 Btu/h
To find capacity at intermediate conditions not in the table ;
Interpolation should be used when design conditions are between two numbers that are in the
capacity table.
Extra-polation is not recommended.
If the interconnecting piping length is more than 7.5 m ;
Find the capacity(%) at that particular interconnecting piping length from the coefficient of capacity
change graph, on page 33. .
Multiply coefficient factor with Total Cooling Capacity & Sensible Capacity.
Ex: At 30m interconnecting piping length, from coefficient of capacity change graph,
coeffienct factor is 0.915.
Total Cooling Capacity =
Capacity (%) x Total Cooling Capacity
=
91.5x23,000
= 21,045 Btu/h
100 100
Sensible Capacity =
Capacity (%) x Sensible Capacity
=
91.5x19,300
= 17,660 Btu/h
100 100
9. Selection Procedure
27
2007 Product Data
10. Performance Data
Outdoor DB ()
Indoor WB ()
Indoor DB () TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
5.1 4.6 1.53 5.6 3.5 1.58 6.0 1.5 1.61 4.9 4.6 1.69 5.4 3.5 1.74 5.8 1.6 1.78 4.7 4.5 1.81 5.2 3.4 1.87 5.6 1.5 1.90
5.3 5.2 1.53 5.7 4.3 1.58 6.0 2.8 1.61 5.1 5.1 1.69 5.5 4.4 1.75 5.8 2.9 1.78 4.9 4.9 1.81 5.3 4.3 1.87 5.6 2.8 1.91
5.5 5.5 1.54 5.8 5.2 1.59 6.0 3.9 1.62 5.3 5.3 1.70 5.6 5.3 1.75 5.8
4.0
1.79 5.1 5.1 1.82 5.4 5.2 1.88 5.6 3.9 1.91
5.7 5.7 1.54 5.9 5.8 1.59 6.0 4.8 1.62 5.5 5.5 1.70 5.6 5.6 1.76 5.8 4.9 1.79 5.3 5.3 1.82 5.4 5.4 1.88 5.6 4.7 1.92
16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
29.4 35.0 40.6
23.9
26.7
29.4
32.2
Model No : HT-C186HLA0
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
4.5 4.4 1.91 4.9 3.3 1.97 5.3 1.5 2.01 4.1 4.1 2.00 4.6 3.2 2.06 4.9 1.4 2.10
4.6 4.6 1.92 5.0 4.2 1.98 5.3 2.7 2.01 4.3 4.3 2.00 4.6 4.0 2.07 4.9 2.6 2.11
4.8 4.8 1.92 5.1 5.0 1.98 5.3 3.8 2.02 4.5 4.5 2.01 4.7 4.7 2.07 4.9 3.6 2.11
5.0 5.0 1.93 5.1 5.1 1.99 5.3 4.6 2.03 4.6 4.6 2.02 4.8 4.8 2.08 4.9 4.4 2.12
19.4 22.8 16.1 19.4 22.8 16.1
51.7 46.1
Model No :
Outdoor DB ()
Indoor WB ()
Indoor DB () TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
4.8 4.6 1.40 5.4 3.5 1.44 5.8 1.5 1.47 4.7 4.7 1.55 5.2 3.5 1.60 5.6 1.6 1.62 4.5 4.5 1.66 5.0 3.4 1.71 5.4 1.5 1.74
5.1 5.1 1.40 5.5 4.3 1.45 5.8 2.8 1.47 4.9 4.9 1.55 5.3 4.4 1.60 5.6 2.9 1.63 4.7 4.7 1.66 5.1 4.3 1.71 5.4 2.8 1.74
5.2 5.2 1.41 5.5 5.2 1.45 5.7 3.9 1.48 5.1 5.1 1.56 5.3 5.3 1.60 5.5 4.0 1.63 4.9 4.9 1.67 5.2 5.2 1.72 5.4 3.9 1.75
5.4 5.4 1.41 5.6 5.6 1.46 5.7 4.8 1.48 5.2 5.2 1.56 5.4 5.4 1.61 5.5 4.9 1.64 5.0 5.0 1.67 5.2 5.2 1.72 5.3 4.8 1.75
29.4
32.2
29.4 35.0 40.6
16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
23.9
26.7
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
4.3 4.3 1.75 4.7 3.3 1.81 5.1 1.5 1.84 3.9 3.9 1.83 4.4 3.2 1.89 4.7 1.4 1.92
4.4 4.4 1.76 4.8 4.2 1.81 5.1 2.7 1.84 4.1 4.1 1.84 4.4 4.0 1.89 4.7 2.6 1.93
4.6 4.6 1.76 4.9 4.9 1.82 5.1 3.8 1.85 4.3 4.3 1.84 4.5 4.5 1.90 4.7 3.6 1.93
4.8 4.8 1.77 4.9 4.9 1.82 5.0 4.6 1.86 4.4 4.4 1.85 4.6 4.6 1.90 4.6 4.4 1.94
46.1 51.7
16.1 19.4 22.8 16.1 19.4 22.8
Model No : HT-C186HLA1
1. All capacites are net, evaporator fan motor heat is deducted.
2. DB=Dry Bulb Temperature( C), WB=Wet Bulb Temperature( C)
) W k : t i n U ( y t i c a p a c t a e h e l b i s n e S = C H S . 4
) W k : t i n U ( y t i c a p a c g n i l o o c l a t o T = C T . 3
5. PI=Power Input(Comp.+ indoor fan motor+outdoor fan motor) (kW)
Notes:
Cooling Capacity(SI Unit)
28 Ceiling Cassette(50Hz, R22)
10. Performance Data

Model No : HT-C246HLA1
Model No : HT-C306HLA0
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
5.5 5.5 2.66 6.0 4.3 2.74 6.5 1.9 2.79 5.1 5.1 2.78 5.6 4.1 2.87 6.0 1.8 2.92
5.7 5.7 2.67 6.1 5.4 2.75 6.5 3.5 2.80 5.3 5.3 2.79 5.7 5.1 2.88 6.0 3.4 2.93
5.9 5.9 2.67 6.2 6.2 2.76 6.5 4.9 2.81 5.5 5.5 2.80 5.8 5.8 2.88 6.0 4.6 2.94
6.1 6.1 2.68 6.3 6.3 2.77 6.4 5.9 2.82 5.7 5.7 2.80 5.8 5.8 2.89 6.0 5.7 2.95
22.8 16.1 19.4 22.8 16.1 19.4
46.1 51.7
Outdoor DB ()
Indoor WB ()
Indoor DB () TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
6.9 6.2 2.19 7.7 4.7 2.25 8.2 2.1 2.30 6.7 6.3 2.42 7.4 4.8 2.49 8.0 2.1 2.54 6.5 6.1 2.59 7.1 4.6 2.67 7.7 2.0 2.72
7.2 7.1 2.19 7.8 5.8 2.26 8.3 3.8 2.30 7.0 7.0 2.42 7.5 6.0 2.50 8.0 3.9 2.55 6.7 6.7 2.59 7.3 5.8 2.68 7.7 3.8 2.73
7.5 7.5 2.20 7.9 7.0 2.27 8.2 5.3 2.31 7.2 7.2 2.43 7.6 7.2 2.51 7.9 5.4 2.55 7.0 7.0 2.60 7.4 7.0 2.68 7.7 5.3 2.73
7.8 7.8 2.21 8.0 7.8 2.28 8.2 6.4 2.32 7.5 7.5 2.44 7.7 7.7 2.52 7.9 6.6 2.56 7.2 7.2 2.61 7.5 7.5 2.69 7.6 6.4 2.74
29.4
32.2
23.9
26.7
16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
29.4 35.0 40.6
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
6.1 6.0 2.73 6.7 4.5 2.82 7.2 2.0 2.87 5.6 5.6 2.86 6.2 4.3 2.95 6.7 1.9 3.00
6.4 6.4 2.74 6.9 5.6 2.83 7.3 3.7 2.88 5.9 5.9 2.87 6.4 5.4 2.96 6.7 3.5 3.01
6.6 6.6 2.75 7.0 6.8 2.84 7.2 5.1 2.89 6.1 6.1 2.88 6.4 6.4 2.97 6.7 4.9 3.02
6.8 6.8 2.76 7.0 7.0 2.85 7.2 6.2 2.90 6.3 6.3 2.88 6.5 6.5 2.98 6.7 5.9 3.03
19.4 22.8 16.1 19.4 22.8 16.1
51.7 46.1
Outdoor DB ()
Indoor WB ()
Indoor DB () TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
6.2 5.9 2.12 6.9 4.4 2.19 7.4 2.0 2.23 6.0 6.0 2.35 6.6 4.5 2.42 7.1 2.0 2.47 5.8 5.8 2.51 6.4 4.4 2.59 6.9 1.9 2.64
6.5 6.5 2.13 7.0 5.6 2.20 7.4 3.6 2.24 6.3 6.3 2.36 6.7 5.7 2.43 7.1 3.7 2.48 6.0 6.0 2.52 6.5 5.5 2.60 6.9 3.6 2.65
6.7 6.7 2.14 7.1 6.7 2.20 7.4 5.0 2.25 6.5 6.5 2.36 6.8 6.8 2.44 7.1 5.1 2.48 6.3 6.3 2.53 6.6 6.6 2.61 6.9 5.0 2.66
6.9 6.9 2.14 7.2 7.2 2.21 7.3 6.1 2.25 6.7 6.7 2.37 6.9 6.9 2.44 7.1 6.2 2.49 6.5 6.5 2.54 6.7 6.7 2.62 6.8 6.1 2.67
23.9
26.7
29.4
32.2
19.4 22.8
40.6
16.1 19.4 22.8 16.1 19.4 22.8 16.1
29.4 35.0
Outdoor DB ()
Indoor WB ()
Indoor DB () TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
8.4 7.0 2.78 9.3 5.3 2.87 10.0 2.3 2.92 8.1 7.2 3.08 9.0 5.4 3.17 9.7 2.4 3.23 7.9 7.0 3.29 8.7 5.3 3.40 9.3 2.3 3.46
8.8 8.1 2.79 9.5 6.7 2.88 10.0 4.4 2.93 8.5 8.2 3.08 9.2 6.8 3.18 9.7 4.4 3.24 8.2 8.0 3.30 8.8 6.6 3.41 9.4 4.3 3.47
9.1 8.8 2.80 9.6 8.0 2.89 10.0 6.0 2.94 8.8 8.8 3.09 9.3 8.2 3.19 9.7 6.1 3.25 8.5 8.5 3.31 9.0 8.0 3.42 9.3 6.0 3.48
9.4 9.3 2.81 9.7 8.9 2.90 10.0 7.3 2.95 9.1 9.1 3.10 9.4 9.1 3.20 9.6 7.5 3.26 8.8 8.8 3.32 9.1 8.8 3.43 9.3 7.3 3.49
29.4
32.2
23.9
26.7
16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
29.4 35.0 40.6
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
7.4 6.8 3.48 8.2 5.1 3.59 8.8 2.3 3.66 6.9 6.5 3.64 7.6 4.9 3.75 8.2 2.2 3.82
7.7 7.7 3.49 8.4 6.4 3.60 8.8 4.2 3.67 7.2 7.2 3.65 7.7 6.1 3.76 8.2 4.0 3.83
8.0 8.0 3.50 8.5 7.8 3.61 8.8 5.8 3.68 7.4 7.4 3.66 7.8 7.4 3.78 8.2 5.6 3.85
8.3 8.3 3.51 8.6 8.6 3.62 8.7 7.1 3.69 7.7 7.7 3.67 7.9 7.9 3.79 8.1 6.8 3.86
19.4 22.8 16.1 19.4 22.8 16.1
51.7 46.1
Model No : HT-C246HLA0
Cooling Capacity(SI Unit)
29 2007 Product Data
10. Performance Data
Model No : HT-C488DLA0
Model No : HT-C368DLA0
Outdoor DB ( )
Indoor WB ( )
Indoor DB () TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
9.9 9.1 2.98 10.9 6.9 3.08 11.8 3.0 3.13 9.6 9.2 3.30 10.6 7.0 3.40 11.4 3.1 3.46 9.2 9.0 3.53 10.2 6.8 3.64 11.0 3.0 3.71
10.3 10.3 2.99 11.1 8.6 3.08 11.8 5.6 3.14 10.0 10.0 3.31 10.8 8.8 3.41 11.4 5.7 3.47 9.6 9.6 3.54 10.4 8.5 3.65 11.0 5.6 3.72
10.7 10.7 3.00 11.3 10.4 3.09 11.7 7.8 3.15 10.3 10.3 3.32 10.9 10.6 3.42 11.3 7.9 3.48 10.0 10.0 3.55 10.5 10.3 3.66 10.9 7.7 3.73
11.1 11.1 3.01 11.4 11.4 3.10 11.7 9.5 3.16 10.7 10.7 3.33 11.0 11.0 3.43 11.3 9.7 3.49 10.3 10.3 3.56 10.6 10.6 3.67 10.9 9.4 3.74
16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
23.9
26.7
29.4
32.2
29.4 35.0 40.6
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
8.7 8.7 3.73 9.6 6.6 3.85 10.3 2.9 3.92 8.1 8.1 3.90 8.9 6.3 4.02 9.6 2.8 4.10
9.1 9.1 3.74 9.8 8.3 3.86 10.3 5.4 3.93 8.4 8.4 3.91 9.1 7.9 4.03 9.6 5.2 4.11
9.4 9.4 3.75 9.9 9.9 3.87 10.3 7.5 3.94 8.7 8.7 3.92 9.2 9.2 4.05 9.6 7.2 4.12
9.7 9.7 3.76 10.0 10.0 3.88 10.3 9.2 3.95 9.0 9.0 3.93 9.3 9.3 4.06 9.5 8.8 4.13
22.8 16.1
51.7
19.4 22.8 16.1 19.4
46.1
Outdoor DB ()
Indoor WB ()
Indoor DB () TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
13.0 11.2 4.60 14.3 8.5 4.74 15.4 3.7 4.83 12.5 11.4 5.08 13.8 8.6 5.24 14.9 3.8 5.34 12.1 11.1 5.44 13.3 8.4 5.61 14.3 3.7 5.72
13.5 12.9 4.61 14.6 10.6 4.76 15.4 7.0 4.85 13.0 13.0 5.10 14.1 10.8 5.26 14.9 7.1 5.36 12.6 12.6 5.46 13.6 10.6 5.63 14.3 6.9 5.73
14.0 14.0 4.63 14.8 12.8 4.77 15.4 9.6 4.86 13.5 13.5 5.11 14.3 13.0 5.28 14.8 9.8 5.37 13.1 13.1 5.47 13.8 12.7 5.65 14.3 9.6 5.75
14.5 14.5 4.64 14.9 14.2 4.79 15.3 11.7 4.88 14.0 14.0 5.13 14.4 14.4 5.29 14.7 11.9 5.39 13.5 13.5 5.49 13.9 13.9 5.66 14.2 11.6 5.77
26.7
29.4
32.2
23.9
22.8 19.4 22.8 16.1 19.4 16.1 19.4 22.8 16.1
29.4 35.0 40.6
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
11.4 10.8 5.75 12.6 8.2 5.93 13.5 3.6 6.05 10.5 10.3 6.02 11.7 7.8 6.20 12.5 3.5 6.32
11.9 11.9 5.77 12.8 10.3 5.95 13.5 6.7 6.06 11.0 11.0 6.03 11.9 9.8 6.22 12.5 6.4 6.34
12.3 12.3 5.79 13.0 12.4 5.97 13.5 9.3 6.08 11.4 11.4 6.05 12.0 11.8 6.24 12.5 8.9 6.36
12.7 12.7 5.81 13.1 13.1 5.99 13.4 11.3 6.10 11.8 11.8 6.07 12.2 12.2 6.26 12.4 10.8 6.38
16.1 19.4 22.8 16.1 19.4 22.8
46.1 51.7
1. All capacites are net, evaporator fan motor heat is deducted.
2. DB=Dry Bulb Temperature( C), WB=Wet Bulb Temperature( C)
) W k : t i n U ( y t i c a p a c t a e h e l b i s n e S = C H S . 4
) W k : t i n U ( y t i c a p a c g n i l o o c l a t o T = C T . 3
5. PI=Power Input(Comp.+ indoor fan motor+outdoor fan motor) (kW)
Notes:
Cooling Capacity(SI Unit)
30
Ceiling Cassette (50Hz,R22)
10. Performance Data
Cooling Capacity(English Units)
Model No : HT-C186HLA1

Indoor DB ( F)
Model No : HT-C186HLA0
Notes: 1. All capacites are net, evaporator fan motor heat is deducted.

F ), WB=Wet Bulb Temperature( F)
3. TC=Total cooling capacity(Unit:1,000Btu/h)
5. PI=Power Input(Comp.+ indoor fan motor+outdoor fan motor) (kW)
4. SHC=Sensible heat capacity(Unit:1,000Btu/h)
2. DB=Dry Bulb Temperature(
PI PI PI PI PI PI PI PI PI






Outdoor DB ( F)

Indoor WB ( F)

PI PI PI PI PI PI





Outdoor DB ( F)

Indoor WB ( F)

Indoor DB ( F)
PI PI PI PI PI PI PI PI PI





Indoor WB ( F)

Outdoor DB ( F)

Indoor DB ( F)

PI PI PI PI PI PI





Outdoor DB ( F)

Indoor WB ( F)

Indoor DB ( F)

31 2007 Product Data


10. Performance Data
Model No : HT-C246HLA0

Model No : HT-C246HLA1
PI PI PI PI PI PI PI PI PI




Outdoor DB ( F)
Indoor WB ( F)
Indoor DB ( F)

PI PI PI PI PI PI




Outdoor DB ( F)

Indoor WB ( F)
Indoor DB ( F)

Model No : HT-C306HLA0
PI PI PI PI PI PI PI PI PI





Outdoor DB ( F)
Indoor WB ( F)
Indoor DB ( F)

PI PI PI PI PI PI




Outdoor DB ( F)
Indoor WB ( F)
Indoor DB ( F)

PI PI PI PI PI PI PI PI PI





PI PI PI PI PI PI





Outdoor DB ( F)
Outdoor DB ( F)
Indoor WB ( F)
Indoor WB ( F)
Indoor DB ( F)
Indoor DB ( F)

Cooling Capacity(English Units)


32 Ceiling Cassette (50Hz,R22)
10. Performance Data
Model No : HT-C488DLA0
Notes: 1. All capacites are net, evaporator fan motor heat is deducted.

F ), WB=Wet Bulb Temperature( F)
3. TC=Total cooling capacity(Unit:1,000Btu/h)
5. PI=Power Input(Comp.+ indoor fan motor+outdoor fan motor) (kW)
4. SHC=Sensible heat capacity(Unit:1,000Btu/h)
2. DB=Dry Bulb Temperature(
Model No : HT-C368DLA0
PI PI PI PI PI PI PI PI PI





PI PI PI PI PI PI





PI PI PI PI PI PI PI PI PI





PI PI PI PI PI PI





Outdoor DB ( F)
Indoor WB ( F)
Indoor DB ( F)

Outdoor DB ( F)
Indoor WB ( F)
Indoor DB ( F)

Outdoor DB ( F)
Indoor WB ( F)
Indoor DB ( F)

Outdoor DB ( F)
Indoor WB ( F)
Indoor DB ( F)

Cooling Capacity(English Units)


Model No : HT-C186HLA0, HT-C186HLA1,HT-C246HLA0,HT-C246DLA1,HT-C306HLA0
Notes:
* Equivalent pipe length = Actual pipe length + number of bend x 0.3
* Refer to the specification for the maximum pipe length of each model.
Cooling(24k)
Cooling(18k)
Models
18k 24k
25 30
Additional
Refrigerant
70
75
80
85
90
95
100
7.5 30
Total Pi pe Length(m)
y
t
i
c
a
p
a
C
%
(
)
Cooling(48k)
Cooling(36k)
Cooling(30k)
30k 36k 48k
40 40 60
20 10
Cooling Capacity
(g/m)
2007 Product Data 33
11. The Coefficient of Capacity Change
HT-C368DLA0,HT-C488DLA0
34 Ceiling Cassette (50Hz,R22)
12. Operation Range
24(75.2)
35 2007 Product Data
Discharge angle : 45

Air velocity [m/s]


13. Air Velocity and temperature Distributions(Reference Data)
Ceiling Cassette 4 -way TD1 chassis (36kBtu/h) Models
2.7m
2m
1m
0m
4m 3m 2m 1m 0m 1m 2m 3m 4m
2.0 2.0
1.5 1.5
1.0 1.0
0.5 0.5

Air velocity [m/s]


Discharge angle : 40
2.7m
2m
1m
0m
4m 3m 3m 2m 2m 1m 0m 1m 4m
2.0 2.0
1.5 1.5
1.0 1.0
0.5 0.5
Ceiling Cassette 4 -way TH chassis (18kBtu/h) Models
36 Ceiling Cassette (50Hz,R22)
13. Air Velocity and temperature Distribution
Temperature [ C]
Ceiling Cassette 4 -way TH chassis (18kBtu/h) Models
2.7m
2m
1m
0m
4m 3m 3m 2m 2m 1m 0m 1m 4m
18 18
20 20
22 22
24 24
Discharge angle:45
u
Ceiling Cassette 4 -way TD1 chassis
(36kBtu/h) Models
2.7m
2m
1m
0m
4m 3m 2m 1m 0m 1m 2m 3m 4m
20 20
22 22
24 24
Temperature [

C]
Discharge angle:40
u
37
2007 Product Data
Overall
Sound Pressure Level
Notes:
- Sound measured at 1.5m away from
the center of the unit.
- Data is valid at free field condition
- Data is valid at nominal operation condition
- Reference accoustic pressure OdB = 20 Pa
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
- The operating conditions are assumed to be standard.
Model
HT-C186HLA0(1)
HT-C246HLA0(1)
Sound Levels(dBA)
H M L
32
35
28
33
25
30
1.5m
Ceiling
Octave Band Center Frequency (Hz)
0
2
e
r
B
d
(
l
e
v
e
L
e
r
u
s
s
e
r
P
d
n
u
o
S
)
a
P
Octave Band Center Frequency (Hz)
0
2
e
r
B
d
(
l
e
v
e
L
e
r
u
s
s
e
r
P
d
n
u
o
S
)
a
P
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
NC-15
NC-70
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
NC-15
NC-70
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
39
37
37
36
42
HT-C368DLA0
HT-C488DLA0
41
42
48 45
HT-C306HLA0
HT-C368DLA0
Octave Band Center Frequency (Hz)
0
2
e
r
B
d
(
l
e
v
e
L
e
r
u
s
s
e
r
P
d
n
u
o
S
)
a
P
10 20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
NC-15
NC-70
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
Octave Band Center Frequency (Hz)
0
2
e
r
B
d
(
l
e
v
e
L
e
r
u
s
s
e
r
P
d
n
u
o
S
)
a
P
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
NC-15
NC-70
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
Octave Band Center Frequency (Hz)
0
2
e
r
B
d
(
l
e
v
e
L
e
r
u
s
s
e
r
P
d
n
u
o
S
)
a
P
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
NC-15
NC-70
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
HT-C246HLA0(1) HT-C186HLA0(1)
14. Sound Levels
HT-C306DLA0
HT-C488DLA0
38 Ceiling Cassette(50Hz, R22)
15. Installation
15.1 Select the best location
15.1.1 Indoor Unit
t There should not be any heat source or steam near
the unit.
t There should not be any obstacles to the air circula-
tion.
t There should be easy provision of condensate drain.
t Taking into account the noise prevention criteria,
spot the installation location.
t Keep proper distance of the unit from ceiling, fence,
walls & other obstacles as shown figure.
t The indoor unit must have the maintenance space
around.
Above fgure means minimum value. Please keep these
value at least.
If H is 2700~3200mm: High ceiling operation control requied
If H is ~2700: Normal operation
NOTE
1500 or more
1
5
0
0

o
r

m
o
r
e
1500 or more
1
5
0
0

o
r

m
o
r
e
Unit:mm
Unit:mm
Ceiling
False ceiling
False ceiling
20 or more
1
5
0
0
o
r

m
o
r
e
1500 or
more
H
1500 or
more
Floor
t In case of the multi fow type, use the high humidity kit.
Otherwise the dew drops can be seen on the unit body.
t Refrigerant piping: Increase the piping insulation
thickness upto 20mm or more.
t Others: Inside the ceiling near th air tight seal places
(no escape of the humidity)
In case of multiple indoor cassette units
(recommended)
Refrigerant piping
Grill for ventilation
Above 1500mm
Indoor unit
Lighting
Ventilator
Indoor unit
Above 2000mm
Above 3000mm
39
2007 Product Data
15. Installation
15.1.2 Outdoor Unit
t If a roof is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the
condenser is not restricted.
t Do not place animals and plants in the path of the warm air.
t Take the air conditioner weight into account and select a place where noise and vibration are minimum.
t Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
t Rooftop Installations : If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the
roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop
mounting.
15.2 Settlement of outdoor unit
t Anchor the outdoor unit with a bolt and nut(10mm)
tightly and horizontally on a concrete or rigid mount.
t When installing on the wall, roof or rooftop, anchor
the mounting base securely with a nail or wire
assuming the influence of wind and earthquake.
t In the case when the vibration of the unit is con-
veyed to the hose, secure the unit with an anti-vibra-
tion rubber.
Bolt
Tubing connection
More than
30cm
f
o
o
r
n
u
S
r
o
e
c
n
e
F
s
e
l
c
a
t
s
b
o
More than 70cm
More than 50cm
More than
30cm
More than
30cm
More than
30cm
r
o
e
c
n
e
F
s
e
l
c
a
t
s
b
o
More than 70cm
More than 50cm
More than
30cm
More than
30cm
f
o
o
r
n
u
S
More than 50cm
(Service space)
40 Ceiling Cassette (50Hz, R22)
1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion
on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunc-
tion or inefficient performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it
needs additional anticorrosion treatment on the heat exchanger.
1. If you cant meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment.
2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water.
15.3 Installation guide at the seaside
15.3.1 Selecting the location(Outdoor Unit)
1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided.
Install the outdoor unit on the opposite side of the sea wind direction.
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
3) Select a well-drained place.
the sea wind from the sea.
the outdoor unit.
between outdoor unit and the windbreak for easy
air flow.
Sea wind Sea wind
Sea wind
Windbreak
CAUTION
15. Installation
41 2007 Product Data
15.4 Ceiling Opening dimensions and hanging bolt location
t The dimensions of the paper model for installing are
the same as those of the ceiling opening dimensions.
Unit:mm
840 Unit size
e
z
i
s
t
i
n
U
0
4
8
)
tl
o
b
g
ni
g
n
a
H
(
2
7
6
)
g
n
i
n
e
p
o
g
n
i
l
i
e
C
(
0
7
8
870 (Ceiling opening)
785(Hanging bolt)
TH,TD1 Chassis
t
Ceiling board
t Select and mark the position for fixing bolts and piping hole.
t Decide the position for fixing bolts slightly tilted to the drain direc-
tion after considering the direction of drain hose.
t Drill the hole for anchor bolt on the wall.
Level gauge
Ceiling t This air-conditioner uses a drain pump.
t Install the unit horizontally using a level gauge.
t During the installation, care should be taken not to
damage electric wires.
CAUTION
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table
Air conditioner
Take enough
distance
NOTE:
t Avoid the following installation location.
1. Such places as restaurants and kitchen where con-
siderable amount of oil steam and flour is generat-
ed.
These may cause heat exchange efficiency reduc-
tion, or water drops, drain pump mal-function.
In these cases, take the following actions;
t Make sure that ventilation fan is enough to cover all
noxious gases from this place.
t Ensure enough distance from the cooking room to
install the air conditioner in such a place where it
may not suck oily steam.
2. Avoid installng air conditioner in such places where
cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.
15. Installation
42 Ceiling Cassette(50Hz, R22)
15. Installation
Wall
m
m
7
~
5
Indoor Outdoor
Set screw of
paper model (4 pieces)
Paper model
for installation
Ceiling board
m
m
0
5
1
Adjust the same height
Ceiling board
Ceiling
Flat washer for M10
(accessory)
Keep the length of the bolt
from the bracket to 40mm
Open the ceiling board
along the outer edge of the
paper model
Flat washer for M10
(accessory)
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
Air Conditioner body
t The following parts are local purchasing.
Hanging Bolt - W 3/8 or M10
Nut - W 3/8 or M10
Spring Washer - M10
Plate Washer - M10
t Drill the piping hole on the wall slightly tilted to the
outdoor side using a 70 hole-core drill.
t Tighten the nut and bolt to prevent unit from
falling off.
CAUTION
15.5 The Indoor Unit Installation
43
2007 Product Data
15.6 Wiring Connection
The power cord connected to the outdoor unit
should be complied with the following specifications
(Rubber insulation, type H05RN-F approved by HAR
or SAA).
If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer or its service agent.
The connecting cable connected to the indoor and
outdoor unit should be complied with the following
specifications (Rubber insulation, type H05RN-F
approved by HAR or SAA).
CAUTION
m
m
5
.
8
m
m
0
2
L
Y /
N
G
m
m
5
.
7
m
m
0
2
L
Y /
N
G
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
2
(18k/24k/30k)
Make sure that the screws of the terminal are free from looseness.
WARNING
1. All wiring must comply with LOCAL REGULATIONS.
2. Select a power source that is capable of supplying the current as required by the air conditioner.
3. Feed the power source to the unit via a distribution switch board designed for this purpose.
4. The terminal screws inside the control box may be loose due to vibration during transport.
Check the screws for loose connection.
(Running the air conditioner with loose connection can overload and damage electrical components.)
5. Always ground the air conditioner with a grounding wire and connector to meet the LOCAL REGULATION.
Terminal Block in Indoor
1(L) 2(N) 3 4
Connected to indoor unit
1(L) 2(N) 3(L) 4(N) 5 6 7 8
outdoor unit
Main
Terminal Block in Indoor
1(L) 2(N) 3 4
Connected to indoor unit
outdoor unit
Main
1(R) 2(S) 3(T) 4(N ) 6(L) 7(N) 8 9
3 ,380V ,50HZ
1 ,220V , 50Hz

Capacity 1 Phase 3 Phase


18k/24k/30k
Btu/h
36kBtu/h
2.5mm
2
-
4 mm
2
4 mm
2
-
-
AREA 1.25mm
2
(36k/48k)
15. Installation
48kBtu/h
44 Ceiling Cassette(50Hz,R22)
15. Installation
1. Form the piping according to its routing. Avoid bending
and bending back the same piping point more than three
times. (This will result in hardening the pipe.)
2. After deforming the piping, align centers of the union
ftting of the indoor unit and the piping, and tighten them
frmly with wrenches.
3. Connect pipe to the service valve or ball valve which is
located below the outdoor unit.
4. After completing the piping connection, be sure to check
if there is gas leakage in indoor and outdoor connection.
After completing the piping connection, execute vacuum
drying for the connecting piping and the indoor unit.
The vacuum drying must be carried out using the service
ports of both the liquid and gas side valves.
Out door
uni t
Liquid side
Flare connection
Flare connection
Gas side
Indoor
unit
15.7 Piping Connection
15.8 Vacuum drying
Model Liquid side piping Gas side piping
30kBtu/h
6.35mm 15.88mm
36kBtu/h
9.52mm
19.05mm 48kBtu/h
24kBtu/h
18kBtu/h
6.35mm
12.70mm
45 2007 Product Data
15. Installation
15.9 Installation of Decoration Panel
1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by
amount 10mm in length.)
The fixing screws (hexagon M5 screw) are included the indoor unit box.
2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.)
3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so
that the screws reach the key hole edge.
4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws)
5. Connect the louver motor connector and display connector.
6. After tightening these screws, install the air inlet grille (including the air filter).
The decoration panel has its installation
direction.
Before installing the decoration panel,
always remove the paper template.
Decoration panel fixing screws
(hexagon M5 screws)
Temporally fitting at 2 places
(Tightening about 10mm)
Control box cover
Piping side
Inlet Grille Inlet Grille
Inlet Grille Louver motor
Decoration panel fixing screws
(Hexagon M5 screw)
Air conditioner unit
Decoration panel
Key holes
Display
Lead wire for
louver motor and
display
CAUTION
Install certainly the decoration
panel.
Cool air leakage causes sweating.
Water drops fall.
Air conditioner
unit
Ceiling
board
Decoration panel
Decoration
panel
Fit the insulator (this part) and
be careful for cool air leakage
Good example
Air
Cool air leakage
(no good)
Bad example
Ceiling
board
Air conditioner unit
46 Ceiling Cassette(50Hz, R22)
15. Installation
15.11 Drain Pipe Work
Drain pipe gradient and support
1) - The drain pipe must be ftted at a gradient of at least 1/100.
- The drain pipe should be as short as possible and free from airlocks.
2) Suspension bolts should be used to support long stretches of drain pipe in order to ensure that a gradient
of 1/100 is maintained.(PVC pipe should not be bent)
Spacing of supports for horizontal piping
3) The length of pipe laid horizontally should be kept a minimum.
Class Nominal diameter Spacing
Rigid PVC pipe 25~40mm 1.0m or less
Indoor unit
Gradient of at least 1 / 100
(1cm/ 1m)
t Drain piping must have down-slope (1/50 to 1/100): be sure
not to provide up-and-down slope to prevent reversal flow.
t During drain piping connection, be careful not to exert extra
force on the drain port on the indoor unit.
t The outside diameter of the drain connection on the indoor
unit is 32mm.
t Be sure to install heat insulation on the drain piping.
Piping material: Polyvinyl chloride pipe VP-25
and pipe fittings
Heat insulation material: Polyethylene foam with
thickness more than 8 mm.
Maintenance
drain port
Upward
routing
not allowed
Pipe clamp
Indoor unit
1/50~1/100
MAX 700mm
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
t Connect the main drain pipe to the exterior
and leave it provisionally until the test
comes to an end.
t Feed water to the flexible drain hose and
check the piping for leakage.
t Be sure to check the drain pump for normal
operating and noise when electrical wiring is
complete.
t When the test is complete, connect the flexi-
ble drain hose to the drain port on the
indoor unit.
Drain test
Feed water
Drain Pump
Drain pan
Flexible drain hose
(accessory)
Main
drain pipe
Glue the joint
Drain
port
Drain hose connection
Use the clip (accessory)
47 2007 Product Data
15. Installation
CAUTION
The supplied flexible drain hose should not be curved,
neither screwed. The curved or screwed hose may
cause a leakage of water.
1/50~1/100
MAX 700mm
Flexible drain hose Flexible drain hose
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the
circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which
the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If
they are loose, it could give rise to burn-out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
t Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a
overload protection device.
t Proper starting power is not given to the compressor.
CAUTION
Grouped drain piping
1) It is standard work practice to make connections to the main pipe from above. The pipe coming down from
the combination should be as large as possible.
2) The pipe work should be kept as short as possible and the number of indoor units per group kept to a
minimum.
Face the vent pipe mouth downward to keep
foreign matter from penetrating the system
Vent pipe
Face piping
downward
48
Ceiling Cassette(50Hz,R22)
15. Installation
15.12 Optional Operation (For wire remote)
1) Two Thermistor System
(1) Open the rear cover of the wired remote-controller to set the mode.
(2) Select one of three selectable modes as follows.
t Position 1:
The room temperature is controlled by the thermistor of the main body.
t Position 2:
The room themperature is controlled by the thermistor of the wired remote-controller, control the
temperature according to the position of wired remote-controller.
t Position 3:
The room temperature is controlled by lower temperature between the temperature of main body and of
remote-controller sensor.
(3) Move the slide switch to set position.
(4) Close the rear cover and check if it works normally.
TH
R14H
SW TH
REMO
MAIN
2TH
OP7
R18H
R17H
OP6
LO
STAND
SW HIGH
HI R03S
0
7
0
C
S
4
0
R
S
2
0
R
R01S
OP3 OP2 OP1
R19H
R11H
R13H R12H OP5R16H OP4
R15H
CO1H
REMO
Room Temp. sensor
2TH
MAIN
Position 2
Position 1
Position 3
Slide switch for ceiling height
Slide switch for 2 Thermistor
t Select the position after counselling with a customer.
t In case of cooling mode, room temperature is controlled by the main body sensor.
t To control the room temperature by a wired remote controller, install controller(room temp. sensor) to
sense the temperature more accurately.
t Maunfactured in the position 3.
CAUTION
49
2007 Product Data
15. Installation
2) Adjusting air volume to the height of ceiling
You can choose the RPM(or air volume) of indoor motor according to the height of ceiling to supply the
comfortable atmosphere to consumers.
Procedure
1. Choose the selectable position in the table after measuring the height of ceiling.
2. In the case of changing the height as "high" or "low", open the rear cover of the wired remote-controller.
3. Move the slide switch to the set position.
4. Close the rear cover and check if it works nomally.
TH
R14H
SW TH
REMO
MAIN
2TH
OP7
R18H
R17H
OP6
LO
STAND
SW HIGH
HI R03S
0
7
0
C
S
4
0
R
S
2
0
R
R01S
OP3 OP2 OP1
R19H
R11H
R13H R12H OP5R16H OP4
R15H
CO1H
Lo
Hi
STAND
Slide switch for ceiling height
Slide switch for 2 Thermistor
Standard
(Default)
Low ceiling
High Ceiling
Ceiling height Mode of slide switch Change of air volume Remark
more than 3.3m High Ceiling Increasing
2.7~3.3m Standard -
less than 2.7m Low Ceiling Decreasing
Maunfactured in stan-
dard mode
3) Group Control(Optional Wiring)
t Be careful not to exchange the color of wires.
t The maximum length of connecting wire should be below 200m(25) on connecting each units.
t Use a wire more than 0.5mm
2
CAUTION
It operates maximum 16 Units by only one Wired Remote Controller, and each Unit starts sequentially to pre-
vent overcurrent.
Wiring design
Operation unit
ZONE 1 2 3 4
Humidify JET
AUTO
AUTO SWING OPERATION FAN SPEED
Program set
SUB FUNCTION SET TEMP
Room Temp HI
MED
LO
Heater
Defrost
Filter
Preheat
Out door
Time
Timer
On
Set no. Time
Off
01 03 05 07 09 11 13 15 17 19 21 23
Indoor Unit 1
Terminal(Local Supply)
Block
Terminal(Local Supply)
Block
Terminal(Local Supply)
Block
Main PCB
#1
Main PCB
#2
Main PCB
#16
Wired Remote Controller
Indoor Unit 2
Main PCB
Indoor Unit 16
Connector
RED(12V)
YL(SIGNAL)
BR(GND)
RED(12V)
YL(SIGNAL)
BR(GND)
YL(SIGNAL)
BR(GND)
Connecting Cable(Local Supply)
Connector Connector
....
....
YL(SIGNAL)
BR(GND)
YL(SIGNAL)
BR(GND)
YL(SIGNAL)
BR(GND)
Remote
Controller
PCB
Single
Group S/W GR
t Using the supplied Wired Remote Controller, wire
them like above.
t Move S/W GR to "Group" position.
t Check the line color of the wire.
50
Ceiling Cassette(50Hz,R22)
16.1 Wired LCD Remote Control
Cooling Model
1 Operation indication screen
Displays the operation conditions.
2 Swirl button

3 2ndF button
16. Function of Remote Control
Name and Function of Remote Control
.
Used to select swirl cool mode.
4 Timer set/cancel /Program/Week
Holiday/Hour/Min/SET/Clr/Ventilator
5 Set temperature button
Used to set the temperature when required.
6 ON/OFF button
Operation starts when this button is pressed
and stops when the button is pressed again.
7 Fan operation
Used to circulate room air without cooling or heating.
8 Operation mode selection button
Used to select the operation mode.
9 Fan speed button
Used to set the disired fan speed.
10 Horizontal/Vertical air flow direction button
11
Room temperature/filtersign
release button
Used to check the room temperature and
release the filter in Second Function Mode.
12 Plasma/Heater button
Used plasma and saved power in Second Function.
13 Time reset button
Reset Used to set the current time and clear
the setting time.
14 Operation lamp
Timer
Program
Hour
Cancel 2ndF
Week Holiday
Set/Clr
Min
RESET
PLASMA
ZONE 1 2 3 4
Operation unit No Func
Humidify JET
SLo
AUTO
AUTO SWING OPERATION FAN SPEED
Program set
SUB FUNCTION SET TEMP
Room Temp
HI
MED
LO
Heater
Defrost
Filter
Preheat
Out door
Time
Timer
On
Set no. Time
Off
01 03 05 07 09 11 13 15 17 19 21 23
2ndF
1
2
5
6
7
8
9
10
11
12
13
3
4
14
51
2007 Product Data
16. Function of Remote Cont rol
Thi s air-conditioner is equipped with wired remote controller basically . But if you want to be availabl e with
wireles s remote controller, you pay for it.
ON OFF
CANCEL
AUTO CLEAN
SET
1
3
5
4
9
10
12
14
16
7
2
8
13
15
11
6
Flip-up door
(opened)
Signal transmitter
17
Controls
The controls will look like the following.
1.START/STOP BUTTON
Operation starts when this button is pressed
and stops when the button is pressed again.
2. OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
3. ROOM TEMPERATURE SETTING
BUTTONS
Used to select the room temperature.
4. INDOOR FAN SPEED SELECTOR
Used to select fan speed in four steps
low, medium, high and CHAOS.
5. JET COOL
Used to start or stop the speed cooling.(speed
cooling operates super high fan speed in
cooling mode.)
6. CHAOS SWING BUTTON
Used to stop or start louver movement and
set the desired up/down airfow direction.
7. ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping
operation.
8. TIME SETTING BUTTONS
Used to adjust the time.
9. TIMER SET/CANCEL BUTTON
Used to set the timer when the desired time
is obtained and to cancel the Timer
operation.
10. SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
11. AIR CIRCULATION BUTTON
Used to circulate the room air without
cooling or heating.
12. ROOM TEMPERATURE CHECKING
BUTTON
Used to check the room temperature.
13. NEO PLASMA(OPTIONAL)
Used to start or stop the
plasma-purifcation function.
14. HORIZONTAL AIRFLOW DIRECTION
CONTROL BUTTON (OPTIONAL)
Used to set the desired horizontal airfow
direction.
15. RESET BUTTON
Used prior to resetting time.
16. 2nd F Button
Used prior to using modes printed in blue
at the bottom of buttons.
17. AUTO CLEAN (OPTIONAL)
Used to set Auto Clean mode.
CAUTION:of handling the Remote Controller
t Aim at the signal receiver on the wired remote controller so as to operate.
t The remote control signal can be received at a distance of up to about 7m.
t Be sure that there are no obstructions between the remote controller and the signal receptor.
t Do not drop or throw the remote controller.
t Do not place the remote controller in a location exposed to direct sunlight, or near the heating unit, or any other
heat source.
t Block a strong light over the signal receptor with a curtain or etc. so as to prevent the abnormal operation. (ex:elec-
tronic quick start, ELBA, inverter type fluorescent lamp)
16.2.Wireless Remote Controller
Name and Function of Remote Cont roller
.
Rayong Office:
The air conditioners manufactured by LG
have received ISO9001 certificate for
quality assurance and ISO14001
certificate for environmental
management system.
P/No.:MFL32271301
November/2007