You are on page 1of 31

UNIT

Raceway and Box Calculations

INTRODUCTION TO UNIT 5RACEWAY AND BOX CALCULATIONS


Anyone whos ever pulled wire into a conduit understands the reason for maximum limits on the wire fill for raceways. Trying to pull too many conductors into a raceway can damage the conductor insulation due to the friction and mechanical abuse. Weve all heard a joke about tying a wire-pulling rope onto the hitch of the service truck and locking in the hubs. At least, we hope this is a joke and not an accurate recounting of an installation. Chapter 9, Table 1 provides the maximum limits the Code recognizes for wire fill in terms of a percentage of the raceways interior crosssectional area. This unit explains those limits and provides instruction regarding the use of the associated tables in Chapter 9 to calculate conductor fill. How to use the tables in Annex C when all of the conductors in the raceway are the same size (total cross-sectional area including insulation) is also covered. Wireway abuse results from disregarding the limits on the radius of bends required for making transitions into and out of the wireway, and the number of conductors and splices allowed. There are specific rules in the NEC to help plan wireway installations that are in compliance and much easier to work with. The Code provides a limit to the number of conductors allowed in outlet boxes, based on Table 314.16(A). This limit is often joked about as being the maximum number of conductors that can be installed in the outlet box while using the persuasion of your hammer handle. This method doesnt follow the NECs guidance set forth in 314.16(B). In this unit, youll learn how to properly calculate the maximum number of conductors and conductor equivalents to be installed in an outlet box. Be sure to read this material carefully so youll understand what the Code means by conductor equivalents. An explanation of the sizing requirements of 314.28(A)(1) and (2) for larger pull boxes, junction boxes, and conduit bodies which enclose conductors 4 AWG and larger, rounds out the information provided here in Unit 5.

PART ARACEWAY FILL


Introduction
Raceways must be large enough to avoid damaging the insulation when conductors are pulled into the raceway. Chapter 9 and Annex C of the NEC are the primary references for determining allowable conductor fill in raceways. For the most common condition, where multiple conductors of the same size are installed together in a raceway, the maximum number of conductors permitted can be determined from the tables in Annex C. For situations where conductors of different sizes are mixed together in a raceway, Chapter 9 contains the information necessary to calculate the required raceway size. Because different conductor types (THW, TW, THHN, and so forth) have different thicknesses of insulation, the number and size of conductors permitted in a given raceway often depend on the conductor type used.

Authors Comment: This unit is based on the use of solidly grounded ac systems, 600V or less, using 90C insulated copper conductors sized to 75C terminals unless otherwise specified.

5.1 Understanding the NEC, Chapter 9 Tables


Table 1Conductor Percent Fill
The maximum percentage of allowable conductor fill is listed in Chapter 9, Table 1. Its based on common conditions where the length of the conductor and number of raceway bends are within reasonable limits [Chapter 9, Table 1, Note 1]. Figure51

Mike Holt Enterprises, Inc. www.MikeHolt.com 888.NEC.CODE (632.2633)

121

Unit 5

Raceway and Box Calculations

Table C.3(A)Compact conductors in flexible metal conduit (FMC) Table C.4Conductors and fixture wires in intermediate metal conduit (IMC) Table C.4(A)Compact conductors in intermediate metal conduit (IMC) Table C.5Conductors and fixture wires in liquidtight flexible nonmetallic conduit (gray type) (LFNC-B) Table C.5(A)Compact conductors in liquidtight flexible nonmetallic conduit (gray type) (LFNC-B) Table C.6Conductors and fixture wires in liquidtight flexible nonmetallic conduit (orange type) (LFNC-A) Table C.6(A)Compact conductors in liquidtight flexible nonmetallic conduit (orange type) (LFNC-A) Figure51 Authors Comment: The annex doesnt have a table for LFNC of the black type (LFNC-C). Table C.7Conductors and fixture wires in liquidtight flexible metal conduit (LFMC) Table C.7(A)Compact conductors in liquidtight flexible metal conduit (LFMC) Table C.8Conductors and fixture wires in rigid metal conduit (RMC) Table C.8(A)Compact conductors in rigid metal conduit (RMC) Table C.9Conductors and fixture wires in rigid PVC conduit, Schedule 80 Table C.9(A)Compact conductors in rigid PVC conduit, Schedule 80 Table C.10Conductors and fixture wires in rigid PVC conduit, Schedule 40 Table C.10(A)Compact conductors in rigid PVC conduit, Schedule 40 Table C.11Conductors and fixture wires in Type A, rigid PVC conduit Table C.11(A)Compact conductors in Type A, rigid PVC conduit Table C.12Conductors and fixture wires in Type EB, PVC conduit Table C.12(A)Compact conductors in Type EB, PVC conduit

Notes to Tables, Note 1Conductors all the Same Size


When all conductors in a conduit or tubing are the same size (total cross-sectional area including insulation), the number of conductors permitted in a raceway can be determined by simply looking at the tables located in Annex CRaceway Fill Tables for Conductors and Fixture Wires of the Same Size.

Table 1 of Chapter 9, Maximum Percent Conductor Fill


Number of Conductors 1 conductor 2 conductors 3 or more conductors Raceway 24 inches or less Percent Fill Permitted 53% fill 31% fill 40% fill 60% fill, Note 4

Tables C.1 through C.12(a) are based on maximum percent fill as listed in Chapter 9, Table 1. Table C.1Conductors and fixture wires in electrical metallic tubing (EMT) Table C.1(A)Compact conductors in electrical metallic tubing (EMT) Table C.2Conductors and fixture wires in electrical nonmetallic tubing (ENT) Table C.2(A)Compact conductors in electrical nonmetallic tubing (ENT) Table C.3Conductors and fixture wires in flexible metal conduit (FMC)

122

Mike Holts Illustrated Guide to Electrical Exam Preparation 2011 Edition

Raceway and Box Calculations

Unit 5

c Annex CTable C.1EMT


Question: How many 14 RHH conductors (without cover) can be installed in trade size 1 EMT? Figure52 (a) 13 (b) 16 (c) 19 (d) 25

Answer: (b) 16 conductors [Annex C, Table C.1] Note 2 at the end of Annex C, Table C.1 indicates that an asterisk (*) with conductor insulation types RHH*, RHW*, and RHW-2* means that these types dont have an outer covering. Insulation types RHH, RHW, and RHW-2 (without the asterisk) do have an outer cover. This is a cover (which may be a fibrous material) that increases the dimensions of the conductor more than the thin nylon cover encountered with conductors such as THHN. Question: How many 8 THHN conductors can be installed in a trade size 3/4 EMT? Figure53 (a) 3 (b) 5 (c) 6 (d) 8 Figure53

c Annex CTable C.2ACompact Conductors in ENT


Question: How many 6 XHHW compact conductors can be installed in trade size 1 ENT? Figure54 (a) 6 (b) 10 (c) 13 (d) 16

Answer: (c) 6 conductors [Annex C, Table C.1]

Answer: (b) 10 conductors [Annex C, Table C.2A] Compact stranding is the result of a manufacturing process where the standard conductor is compressed to the extent that the voids between the strands of wires are virtually eliminated [Annex C, Table C.1(a) footnote]. Unless the question specifically states compact conductors, assume that the conductors arent the compact type.

Figure52

Figure54

Mike Holt Enterprises, Inc. www.MikeHolt.com 888.NEC.CODE (632.2633)

123

Unit 5

Raceway and Box Calculations

c Annex CTable C.3FMC


Question: If trade size 1 FMC has three THHN conductors (not compact), whats the largest conductor permitted to be installed? Figure55 (a) 1 THHN (b) 1/0 THHN (c) 2/0 THHN (d) 3/0 THHN

c Annex CTable C.7Fixture Wire in LFMC


Question: How many 18 TFFN conductors can be installed in trade size LFMC? Figure56 (a) 14 conductors (c) 30 conductors (b) 26 conductors (d) 39 conductors

Answer: (a) 1 THHN [Annex C, Table C.3] Its common to see conductors with a dual insulation rating, such as THHN/THWN. This type of conductor can be used in a dry location at the THHN 90C ampacity, or if used in a wet location, the THWN ampacity rating of the 75C column of Table 310.15(B)(16) for THWN insulation types must be adhered to.

Answer: (d) 39 conductors [Annex C, Table C.7]

Figure56

c Annex CTable C.9PVC Schedule 80


Figure55 Question: Whats the smallest trade size PVC Schedule 80 raceway that can be used for the installation of a single 3/0 THHN as a grounding electrode conductor? Figure57 (a) Trade size (c) Trade size 1 (b) Trade size (d) Trade size 1

c Annex CTable C.4IMC


Question: How many 4/0 RHH conductors with an outer cover can be installed in trade size 2 IMC? Note: RHH insulation with an outer cover has no asterisk (*). (a) 1 conductor (c) 3 conductors (b) 2 conductors (d) 4 conductors

Answer: (b) Trade size 3/4 [Annex C, Table C.9] Question: If trade size 2 PVC Schedule 80 has three THHN compact conductors, whats the largest conductor permitted to be installed? (a) 1/0 THHN (c) 250 kcmil THHN (b) 4/0 THHN (d) 300 kcmil THHN

Answer: (c) 3 conductors [Annex C, Table C.4]

Answer: (d) 300 kcmil THHN [Annex C, Table C.9(A)]

124

Mike Holts Illustrated Guide to Electrical Exam Preparation 2011 Edition

Raceway and Box Calculations

Unit 5

c Annex CTable C.10(a)Compact Conductors in PVC Schedule 40


Question: If a trade size 2 PVC Schedule 40 raceway has three THHN compact conductors, whats the largest conductor permitted to be installed? (a) 1/0 THHN (c) 350 kcmil THHN (b) 4/0 THHN (d) 750 kcmil THHN

Answer: (c) 350 kcmil THHN [Annex C, Table C.10(A)]

Notes to Tables, Note 2Used for Physical Protection


Figure57 The percentages listed in Table 1 apply only to complete raceway systems and arent intended to apply to sections of raceways used to protect wiring from physical damage. Figure59

c Annex CTable C.10PVC Schedule 40


Question: Whats the smallest trade size PVC Schedule 40 raceway that can be used for the installation of four 1/0 THHN conductors? Figure58 (a) Trade size3/4 (c) Trade size 1 1/2 (b) Trade size 1 (d) Trade size 2

Answer: (c) Trade size 1 [Annex C, Table C.10]

Figure59

Notes to Tables, Note 3Equipment Grounding Conductors


When equipment grounding and bonding conductors are installed in a raceway, the actual area of the conductor must be used to calculate raceway fill, Figure510 . Chapter 9, Table 5 can be used to determine the cross-sectional area of insulated conductors and Chapter 9, Table 8 can be used to determine the cross-sectional area of bare conductors (see Chapter 9, Notes to Tables, Note 8).

Figure58

Mike Holt Enterprises, Inc. www.MikeHolt.com 888.NEC.CODE (632.2633)

125

Unit 5

Raceway and Box Calculations

Figure510

Figure512 Question: What Is the total are occupied in a raceway for the following cables? 4 Category 5 plenum cables, dia = 0.167 in. 2 fiber cables, 24 strand, dia = 0.438 in. 3 fiber cables, 12 strand, dia = 0.25 in. (a) 0.0254 (b) 0.1203 (c) 0.5363 (d) 0.9578

Notes to Tables, Note 4Raceways not Exceeding 24 Inches


When a raceway doesnt exceed 24 in. in length, its permitted to be filled to 60 percent of its total cross-sectional area as identified in Table 4 of Chapter 9. Figure511

Answer: (c) 0.5363 sq in. 4 Cat 5 plenum cables, diameter = 0.167 in. r = d/2 r = 0.167/2 = 0.0835 in. Area = 3.14 x r2 Area = 3.14 x 0.0835 in. x 0.0835 in. Area = 0.0219 sq in. x 4 = 0.0876 sq in. 3 fiber cables, 12 strand, dia = 0.25 in. r = d/2 r = 0.25/2 = 0.125 in. Area = 3.14 x r2 Area = 3.14 x 0.125 in. x 0.125 in. Area = 0.0491 sq in. x 3 = 0.1473 sq in. 2 fiber cables, 24 strand, diameter = 0.438 in. r = d/2 r = 0.438/2 = 0.219 in. Area = 3.14 x r2 Area = 3.14 x 0.219 in. x 0.219 in. Area = 0.1507 sq in. x 2 = 0.3014 sq in. Cat 5 12- strand 24-strand 0.0876 sq in. 0.1473 sq in. 0.3014 sq in. 0.5363 sq in.

Figure511

Notes to Tables, Note 5Multiconductor Cables


For multiconductor cables, the actual cross-sectional area of the cable is to be used for raceway sizing. The cross sectional area of a circle is calculated by taking 3.14 x the square of the radius of the circle. Figure512

126

Mike Holts Illustrated Guide to Electrical Exam Preparation 2011 Edition

Raceway and Box Calculations


Notes to Tables, Note 6Different Size Conductors
Use Table 4 and Table 5 when sizing raceways for conductors of different sizes. Table 4 provides the cross-sectional area of raceways, while Tables 5 and 5A give the cross-sectional areas of conductors. This is also the method to use when doing calculations for raceways of 24 in. and shorter, as Annex C doesnt account for the 60 percent fill allowance provided by Table 4. Figure513

Unit 5

Figure514

Notes to Tables, Note 8Bare Conductors


The dimensions for bare conductors are listed in Chapter 9, Table 8. Figure515

Figure513

Notes to Tables, Note 7Rounding


When the calculated number of conductors (all of the same size including insulation) results in 0.80 or more, the next higher whole number of conductors can be used. Question: How many 8 THHN conductors can be installed in a trade size 3/4 EMT? Figure514 (a) 3 (b) 5 (c) 6 (d) 8 Figure515

Answer: (c) 6 conductors 8 THHN = 0.0366 sq in [Chapter 9 Table 5] 3/4 EMT 40% fill = 0.213 sq in. [Chapter 9 Table 4] 0.213 sq in./0.0366 sq in. = 5.82 conductors we are allowed to use 6 conductors per Chapter 9 Notes to Tables, Note 7 When the calculated number of conductors, all of the same size including insulation results in 0.80 or more, the next higher number of conductors can be used [Chapter 9, Notes to Tables, Note 7]

Notes to Tables, Note 9


A multiconductor cable or flexible cord is treated as a single conductor for calculating percentage conduit fill area. For cables with elliptical cross sections, the cross-sectional area is based on using the major diameter of the ellipse as the circle diameter.

Mike Holt Enterprises, Inc. www.MikeHolt.com 888.NEC.CODE (632.2633)

127

Unit 5

Raceway and Box Calculations

c NM cable in EMT Example


Question: What size EMT is needed for one 12-2 w/G NM cable that measures 716 on the major diameter? Figure516 (a) Trade size (c) Trade size 1 Answer: (a) Trade size Area = 3.14 x r 2 D = 716 in. D = 0.4375 in. R = D/2 R = 0.4375 in./2 R = 0.22 in. Area = 3.14 x 0.22 in. x 0.22 in. Area = 0.1520 sq in. Use the one wire column (53%) of Chapter 9, Table 4 for EMT: Trade size EMT provides 0.161 sq in., which is larger than 0.1520 sq in. and will meet the minimum requirement. (b) Trade size (d) Trade size 1

c Raceway Cross-Sectional Area Example 1


Question: Whats the cross-sectional area of permitted conductor fill for a trade size 1 EMT raceway 30 inches long that contains four conductors? Figure517 (a) 0.346 sq in. (c) 2.067 sq in. (b) 1.013 sq in. (d) 3.356 sq in.

Answer: (a) 0.346 sq in. [Chapter 9, Notes to Tables, Note 4 and Table 4, 40% column]

Figure517

c Raceway Cross-Sectional Area Example 2


Question: Whats the cross-sectional area of permitted conductor fill for a trade size 2 EMT raceway thats 20 inches long? Figure518 (a) 1.342 sq in. (c) 2.067 sq in. Figure516 (b) 2.013 sq in. (d) 3.356 sq in.

Notes to TablesRaceway Cross-Sectional Area


The sixth column of this table (Total Area 100%) gives the total crosssectional area in square inches of the raceway. There are also 31% (2 wires), 40% (3 or more wires), 53% (1 wire), and 60% (nipple) crosssectional area columns based on the number of conductors in accordance with Chapter 9, Table 1.

Answer: (b) 2.013 sq in. Reminder: For a raceway 24 in. and shorter, use the 60% column [Chapter 9, Notes to Tables, Note 4 and Table 4, 60% column]

128

Mike Holts Illustrated Guide to Electrical Exam Preparation 2011 Edition

Raceway and Box Calculations

Unit 5

Table 5Dimensions of Insulated Conductors and Fixture Wires


Chapter 9, Table 5 lists the cross-sectional area of insulated conductors and fixture wires (see Table 51).

c Table 5THHN
Question: Whats the cross-sectional area for one 10 THHN conductor? Figure519 (a) 0.0097 sq in. (c) 0.0211 sq in. Answer: (c) 0.0211 sq in. Figure518 (b) 0.0172 sq in. (d) 0.0278 sq in.

c Raceway Cross-Sectional Area Example 3


Question: Whats the cross-sectional area of permitted conductor fill for a trade size 2 EMT raceway 30 inches long that contains four conductors? See Figure518. (a) 1.342 sq in. (c) 2.067 sq in. (b) 2.013 sq in. (d) 3.356 sq in.

Answer: (a) 1.342 sq in. [Chapter 9, Table 1 and Table 4, 40% column]

c Raceway Cross-Sectional Area Example 4


Question: Whats the minimum size EMT raceway required for three conductors with a wire fill of 0.25 sq in.? (a) Trade size (c) Trade size 1 Answer: (b) Trade size 1 (b) Trade size 1 (d) Trade size 1 Figure519

c Table 5RHW With an Outer Cover


Question: Whats the cross-sectional area for one 10 RHW conductor with an outer cover? (a) 0.0172 sq in. (c) 0.0278 sq in. Answer: (d) 0.0437 sq in. (b) 0.0206 sq in. (d) 0.0437 sq in.

c Raceway Cross-Sectional Area Example 5


Question: Whats the minimum size Schedule 80 PVC raceway required for three conductors with a wire fill of 0.35 sq in.? (a) Trade size (c) Trade size 1 Answer: (c) Trade size 1 (b) Trade size 1 (d) Trade size 1

Mike Holt Enterprises, Inc. www.MikeHolt.com 888.NEC.CODE (632.2633)

129

Unit 5

Raceway and Box Calculations

Table 51: Commonly Used Conductor Cross-Sectional Area


RHH/RHW With Cover Column 1 Column 2 Size AWG/kcmil 14 12 10 8 6 4 3 2 1 0 00 000 0000 Column 3 RHH/RHW Without Cover TW or THW Chapter 9, Table 5 Column 4 Column 5 Column 6 THHN THWN XHHW BARE Stranded Conductors Chapter 9 Table 8

Approximate Cross-Sectional Area Square Inches 0.0293 0.0209 0.0139 0.0097 0.0139 0.004 0.0353 0.0260 0.0181 0.0133 0.0181 0.006 0.0437 0.0835 0.1041 0.1333 0.1521 0.1750 0.2660 0.0333 0.0556 0.0726 0.0973 0.1134 0.1333 0.1901 0.0243 0.0437 0.0726 0.0973 0.1134 0.1333 0.1901 0.0211 0.0366 0.0507 0.0824 0.0973 0.1158 0.1562 0.0243 0.0437 0.0590 0.0814 0.0962 0.1146 0.1534 0.011 0.017 0.027 0.042 0.053 0.067 0.087

0.3039 0.2223 0.2223 0.1855 0.1825 0.109 0.3505 0.2624 0.2624 0.2233 0.2190 0.137 0.4072 0.4754 0.3117 0.3718 0.3117 0.3718 0.2679 0.3237 0.2642 0.3197 0.173 0.219

c Table 5RHH Without an Outer Cover


Question: Whats the cross-sectional area for one 10 RHH without an outer cover? (a) 0.0117 sq in. (c) 0.0278 sq in. Answer: (d) 0.0333 sq in. The note at the end of Table 5 states that conductor Types RHH, RHW, and RHW-2 without outer coverings are identified on the table with an asterisk (*). (b) 0.0252 sq in. (d) 0.0333 sq in.

Table 5ADimensions of Compact Insulated Conductors


Chapter 9, Table 5A, lists the cross-sectional areas for compact copper and aluminum building wires. These conductors use specially shaped strands so that the overall size of the conductor is more compact. The outer covering is marked as a compact conductor.

c Table 5THHN Compact Conductors


Question: Whats the cross-sectional area for one 1 THHN compact conductor? (a) 0.0117 sq in. (c) 0.2733 sq in. Answer: (b) 0.1352 sq in. (b) 0.1352 sq in. (d) 0.5216 sq in.

Authors Comment: The difference in the insulation thickness between RHH and THHN can be determined from Table 310.104(A) Conductor Applications and Insulations. You will find that 10 RHH has an insulation thickness of 45 mils while 10 THHN has an insulation thickness of 20 mils.

130

Mike Holts Illustrated Guide to Electrical Exam Preparation 2011 Edition

Raceway and Box Calculations 5.2 Raceway Calculations

Unit 5

c Table 5Compact Conductors


Question: Whats the cross-sectional area for one 4/0 XHHW compact conductor? (a) 0.0117 sq in. (c) 0.2733 sq in. Answer: (c) 0.2733 sq in. (b) 0.1352 sq in. (d) 0.5216 sq in.

Annex CTables 1 through 12 cant be used to determine raceway sizing when conductors of different sizes are installed in the same raceway. When this situation is encountered, use the following steps to determine the raceway size and nipple size: Step 1: Determine the cross-sectional area (in square inches) for each conductor from Chapter 9, Table 5 for insulated conductors and from Chapter 9, Table 8 for bare conductors. Step 2: Determine the total cross-sectional area for all conductors. Step 3: Size the raceway according to the percent fill as listed in Chapter 9, Table 1. Chapter 9, Table 4 includes the various types of raceways with columns representing the allowable percentage fills; such as 40 percent for three or more conductors, and 60 percent for raceways 24 in. or less in length. Be careful when selecting the raceway from Chapter 9, Table 4 as this table is divided up into numerous tables for each raceway type, and you must choose the correct section of the table for the type of raceway for which youre performing the calculations.

Table 8Conductor Properties


Chapter 9, Table 8 contains conductor properties such as the crosssectional area in circular mils, the number of strands per conductor, the cross-sectional area in square inches for bare conductors, and the direct-current resistance at 75C for both copper and aluminum conductors.

c Bare ConductorCross-Sectional Area


Question: Whats the cross-sectional area for one 10 AWG bare stranded conductor? Figure520 (a) 0.008 sq in. (c) 0.038 sq in. (b) 0.011 sq in. (d) a or b

c Raceway Size
Question: Whats the minimum size Schedule 40 PVC raceway required for three 500 kcmil THHN conductors, one 250 kcmil THHN conductor, and one 3 THHN conductor. Figure521 (a) Trade size 2 (c) Trade size 3 Answer: (c) Trade size 3 Step 1: Determine the cross-sectional area of the conductors [Chapter 9, Table 5]. 500 THHN 0.7073 sq in. x 3 wires = 2.1219 sq in. 250 THHN 0.3970 sq in. x 1 wire = 0.3970 sq in. 3 THHN 0.0973 sq in. x 1 wire = 0.0973 sq in. Step 2: Total cross-sectional area of all conductors = 2.6162 sq in. Step 3: Size the conduit at 40 percent fill [Chapter 9, Table 1] using Chapter 9, Table 4 (be sure to select the table for PVC Schedule 40). Trade size 3 Schedule 40 PVC has an allowable cross-sectional area of 2.907 sq in. for over two conductors in the 40 percent column. (b) Trade size 2 (d) Trade size 3

Answer: (b) 0.011 sq in. [Chapter 9, Table 8]

Figure520

Mike Holt Enterprises, Inc. www.MikeHolt.com 888.NEC.CODE (632.2633)

131

Unit 5

Raceway and Box Calculations

Figure521

Figure522

c Raceway 24 in. or Less in Length


Question: What size RMC 24 in. or less in length is required for three 3/0 THHN conductors, one 1 THHN conductor, and one 6 THHN conductor? Figure522 (a) Trade size (c) Trade size 1 Answer: (c) Trade size 1 Step 1: Determine the cross-sectional area of the conductors [Chapter 9, Table 5]. 3/0 THHN 0.2679 sq in. x 3 wires = 0.8037 sq in. 1 THHN 0.1562 sq in. x 1 wire = 0.1562 sq in. 6 THHN 0.0507 sq in. x 1 wire = 0.0507 sq in. Step 2: Total cross-sectional area of the conductors = 1.0106 sq in. Step 3: Size the conduit at 60 percent fill [Chapter 9, Table 1, Note 4] using Chapter 9, Table 4. Trade size 1 nipple = 0.0916 sq in., too small Trade size 1 nipple = 1.243 sq in., just right Trade size 2 nipple = 2.045 sq in., larger than required (b) Trade size 1 (d) Trade size 2

5.3 Wireways
Wireways are commonly used where access to the conductors within the raceway is required to make terminations, splices, or taps to several devices at a single location. Their high cost precludes their use for other than short distances, except in some commercial or industrial occupancies where the wiring is frequently revised. Authors Comment: Both metal wireways [376] and nonmetallic wireways [378] are often called troughs or gutters in the field. Gutters are not really the same thing as a wireway, and are covered by Article 366. Gutters are typically part of a factory fabricated switchgear, and the product installed in the field is a wireway.

DefinitionMetal Wireway [376.2]


A sheet metal raceway with hinged or removable covers for housing and protecting electric conductors and cable, and in which conductors are placed after the wireway has been installed. Figure523

ConductorsMaximum Size [376.21]


The maximum size conductor permitted in a wireway must not be larger than that for which the wireway is designed.

132

Mike Holts Illustrated Guide to Electrical Exam Preparation 2011 Edition

Raceway and Box Calculations

Unit 5

c Wireway Cross-Sectional Area


Question: Whats the cross-sectional area of a 6 in. x 6 in. wireway? (a) 6 sq in. (b) 16 sq in. (c) 36 sq in. (d) 66 sq in.

Answer: (c) 36 sq in. The cross-sectional area is found by multiplying height by depth: 6 in. x 6 in. = 36 sq in.

c Wireway Allowable Conductor Fill Area


Question: Whats the maximum allowable conductor fill in square inches for a 6 in. x 6 in. wireway? Figure523 (a) 5 sq in. (b) 6.50 sq in. (c) 7.20 sq in. (d) 8.90 sq in.

Number of Conductors and Ampacity [376.22]


(a) Number of Conductors. The maximum number of conductors permitted in a wireway is limited to 20 percent of the cross-sectional area of the wireway. Figure524

Answer: (c) 7.20 sq in. 36 sq in. x 0.20 = 7.20 sq in. [376.22(A)]

c Wireway Conductor Fill


Question: Whats the maximum number of 500 kcmil THHN conductors that can be installed in a 6 in. x 6 in. wireway? Figure525 (a) 4 Answer: (c) 10 36 sq in. x 0.20 = 7.20 sq in. [376.22(A)] 500 kcmil THHN = 0.7073 sq in. [Chapter 9, Table 5] Maximum Allowable Area/Area per Conductor = Number of Conductors 7.20 sq in./0.7073 sq in. = 10.17 conductors 10 conductors can be installed. Note: Conductor ampacity adjustment for bundling isnt required because there are fewer than 30 current-carrying conductors [376.22(B)]. (b) 6 (c) 10 (d) 20

Figure524

Mike Holt Enterprises, Inc. www.MikeHolt.com 888.NEC.CODE (632.2633)

133

Unit 5

Raceway and Box Calculations

Figure525

Figure526

c Wireway Conductor Fill


Question: What size wireway is required for three 500 kcmil THHN, one 250 kcmil THHN, and four 4/0 THHN conductors? (a) 4 in. x 4 in. (c) 8 in. x 8 in. Answer: (b) 6 in. x 6 in. Find the conductor area [Chapter 9, Table 5] 500 kcmil THHN = 0.7073 sq in. x 3 = 2.1219 sq in. 250 kcmil THHN = 0.3970 sq in. 4/0 THHN = 0.3237 sq in. x 4 =1.2948 sq in. Total Conductor Area = 3.8137 sq in. The wireway must not be filled to over 20 percent of its crosssectional area [376.22(A)]. Twenty percent is equal to one-fifth, so we can multiply the required conductor area by five to find the minimum square inch area required. Conductor Area x 5 = Required Wireway Minimum Area 3.8137 sq in. x 5 = 19.07 sq in. A 6 in. x 6 in. wireway has a cross-sectional area of 36 sq in. and will be large enough. Figure527 Sizing for Conductor Bending Radius. Where conductors are bent within a metal wireway, the wireway must be sized to meet the bending radius requirements contained in Table 312.6(A), based on one wire per terminal [367.23(A)]. Figure528 (b) 6 in. x 6 in. (d) 10 in. x 10 in.

Wireway Splices and Taps. Splices and taps must not fill more than 75 percent of the wiring space at any cross section [376.56]. Figure526 and 527

134

Mike Holts Illustrated Guide to Electrical Exam Preparation 2011 Edition

Raceway and Box Calculations

Unit 5

Figure528

Figure529

5.4 Tips for Raceway Calculations


Tip 1: Tip 2: Tip 3: Take your time. Use a ruler or a straightedge when using tables, and highlight key words and important sections. Watch out for different types of raceways and conductor insulations, particularly RHH/RHW with or without an outer cover. Watch for the difference between conductors and compact conductors.

5.5 Sizing BoxConductors All the Same Size [Table 314.16(A)]


When all of the conductors in an outlet box are the same size (insulation doesnt matter), Table 314.16(A) can be used to: (1) Determine the number of conductors permitted in the outlet box, or (2) Determine the size outlet box required for the given number of conductors. Authors Comment: If the outlet box contains switches, receptacles, luminaire studs, luminaire hickeys, manufactured cable clamps, or equipment grounding conductors, then we must make an allowance for these items, which is not reflected in Table 314.16(A) .

Tip 4:

PART BOUTLET BOX FILL CALCULATIONS [314.16]


Introduction
Boxes must be of sufficient size to provide free space for all conductors. An outlet box is generally used for the attachment of devices and luminaires and has a specific amount of space (volume) for conductors, devices, and fittings. The volume taken up by conductors, devices, and fittings in a box must not exceed the box fill capacity. The volume of a box is the total volume of its assembled parts, including plaster rings, industrial raised covers, and extension rings. The total volume includes only those parts that are marked with their volumes in cubic inches [314.16(A)] or included in Table 314.16(A) of the NEC. Figure529

c Outlet Box Size


Question: Whats the minimum depth for a 4 in. square outlet box which contains six 12 THHN conductors and three 12 THW conductors? Figure530 (a) 4 x 1 in. square (c) 4 x 218 in. square Answer: (b) 4 x 1 in. square Table 314.16(a) permits nine 12 AWG conductors; the insulation type isnt a factor when calculating box fill. (b) 4 x 1 in. square (d) 4 x 218 in. with extension

Mike Holt Enterprises, Inc. www.MikeHolt.com 888.NEC.CODE (632.2633)

135

Unit 5

Raceway and Box Calculations

Figure530

Figure531 (1) Conductor Volume. Each unbroken conductor that runs through a box and each conductor that terminates in a box is counted as a single conductor volume in accordance with Table 314.16(B). Each loop or coil of unbroken conductor having a length of at least twice the minimum length required for free conductors in 300.14 must be counted as two conductor volumes. Conductors that originate and terminate within the box, such as pigtails, arent counted at all. Figures532 and 533

c Number of Conductors in an Outlet Box


Question: Using Table 314.16(A), how many 14 THHN conductors are permitted in a 4 x 1 in. round box? (a) 7 conductors (c) 10 conductors Answer: (a) 7 conductors (b) 9 conductors (d) 11 conductors

5.6 Conductor Equivalents


Box Fill Calculations [314.16(B)].
The calculated conductor volume determined by (1) through (5) and Table 314.16(B) are added together to determine the total volume of the conductors, devices, and fittings. Raceway and cable fittings, including locknuts and bushings, arent counted for box fill calculations. Figure531

Table 314.16(B) Volume Allowance Required per Conductor


Conductor AWG 18 16 14 12 10 8 6 Volume cu in. 1.50 1.75 2.00 2.25 2.50 3.00 5.00

Figure532

136

Mike Holts Illustrated Guide to Electrical Exam Preparation 2011 Edition

Raceway and Box Calculations

Unit 5

(2) Cable Clamp Volume. One or more internal cable clamps count as a single conductor volume in accordance with Table 314.16(B), based on the largest conductor that enters the box. Cable connectors that have their clamping mechanism outside the box arent counted. Figure535

Figure533 Authors Comment: According to 300.14, at least 6 in. of free conductor, measured from the point in the box where the conductors enter the enclosure, must be left at each outlet, junction, and switch point for splices or terminations of luminaires or devices. Exception: Equipment grounding conductors, and up to four 16 AWG and smaller fixture wires, can be omitted from box fill calculations if they enter the box from a domed luminaire or similar canopy, such as a ceiling paddle fan canopy. Figure534

Figure535

(3) Support Fitting Volume. Each luminaire stud or luminaire hickey counts as a single conductor volume in accordance with Table 314.16(B), based on the largest conductor that enters the box. Figure536

Figure534 Figure536

Mike Holt Enterprises, Inc. www.MikeHolt.com 888.NEC.CODE (632.2633)

137

Unit 5

Raceway and Box Calculations

(4) Device Yoke Volume. Each single gang device yoke (regardless of the ampere rating of the device) counts as two conductor volumes based on the largest conductor that terminates on the device in accordance with Table 314.16(B). Figure537

Figure538 (5) Equipment Grounding Conductor Volume. All equipment grounding conductors in a box count as a single conductor volume in accordance with Table 314.16(B), based on the largest equipment grounding conductor that enters the box. Insulated equipment grounding conductors for receptacles having insulated grounding terminals (isolated ground receptacles) [250.146(D)] count as a single conductor volume in accordance with Table 314.16(B). Figure539

Figure537

Each multigang device yoke counts as two conductor volumes for each gang based on the largest conductor that terminates on the device in accordance with Table 314.16(B). Figure538 Authors Comment: A device thats too wide for mounting in a single gang box is counted based on the number of gangs required for the device.

Question: If a range receptacle that requires 2 gangs for mounting is fed by three 6 AWG conductors In a raceway system where the raceway is the equipment grounding conductor, and a 1.30 cu in. plaster ring is installed on a metal 4 11/16 square box, how deep must the box be? (a) 1 in. (c) 2 18 in. (b) 1 in. (d) none of these is deep enough Figure539

Answer: (c) 2 18 in. 6 AWG = 5.00 cu in. [Table 314.16(B)] 5.00 cu in. x 7 = 35.00 cu in. 4 11/16 sq x 2 1/8 deep box = 42.00 cu in. [Table 314.16(A)] 42.00 + 1.30 cu in. = 43.30 cu in.

What Isnt Counted


Wire connectors, cable connectors, raceway fittings, and conductors that originate and terminate within the outlet box (such as equipment bonding jumpers and pigtails) arent counted for box fill calculations [314.16(A)].

138

Mike Holts Illustrated Guide to Electrical Exam Preparation 2011 Edition

Raceway and Box Calculations

Unit 5
Step 1: Determine the number and size of conductor equivalents in the box. Step 2: Determine the volume of the conductor equivalents from Table 314.16(B). Step 3: Size the box by using Table 314.16(A).

c Number of Conductors
Question: Whats the total number of conductors used for the box fill calculations in Figure540? (a) 5 conductors (c) 9 conductors Answer: (d) 11 conductors Switch and conductors Receptacles and conductors Equipment grounding conductor Cable clamps Total

(b) 7 conductors (d) 11 conductors

5 14 AWG 4 14 AWG 1 14 AWG + 1 14 AWG 11 14 AWG

c Example: Calculating Different Size Conductors


Question: Whats the minimum depth 4 in. square outlet box required for one 14/3 w/G Type NM cable that terminates on a 3-way switch, and one 12/2 w/G Type NM cable that terminates on a receptacle? The box has internally installed cable clamps. Figure541 (a) 4 x 1 in. square (c) 4 x 218 in. square Answer: (c) 4 x 2 18 in. square Step 1: Determine the number of each size conductor. 14 AWG 14/3 NM = Switch Total 12 AWG 12/2 NM Cable clamp Receptacle Equipment grounding conductor Total 3 14 AWG + 2 14 AWG 5 14 AWG 2 12 AWG 1 12 AWG 2 12 AWG + 1 12 AWG 6 12 AWG (b) 4 x 1 in. square (d) any of these

two conductors for the device and three conductors terminating two conductors for the device and two conductors terminating

Each 14 AWG counts as 2 cu in. [Table 314.16(B)]. 11 conductors x 2 cu in. = 22 cu in. If the cubic inch volume of the mud ring isnt stamped on it, or given in the problem, we cant include it in the box volume. Without knowing the mud ring volume, a 4 in. square by 2 18 in. deep box is the minimum required for this example.

All equipment grounding conductors count as one conductor, based on the largest equipment grounding conductor entering the box [314.16(B)(5)]. Step 2: Determine the volume of the conductors [Table 314.16(B)]. 14 AWG 2 cu in. x 5 conductors 12 AWG 2.25 cu in. x 6 conductors Total Volume Total Volume 2 cu in. each 10 cu in. 2.25 cu in. each 13.50 cu in. 10 cu in. + 13.50 cu in. 23.50 cu in.

Figure540

5.7 Outlet Box Sizing [314.16(B)]


To determine the size of the outlet box when the conductors are of different sizes (insulation isnt a factor), follow these steps:

Step 3: Select the outlet box from Table 314.16(A). 4 x 218 in. square, 30.30 cu in. meets the minimum cu in. requirements

Mike Holt Enterprises, Inc. www.MikeHolt.com 888.NEC.CODE (632.2633)

139

Unit 5

Raceway and Box Calculations

Figure541

c Domed Fixture Canopy [314.16(B)(1) Ex]


Question: A round 4 x in. box has a total volume of 7 cu in. and has factory-installed internal cable clamps. Can this pancake box be used with a lighting luminaire that has a domed canopy? The branch-circuit wiring is 14/2 w/G NM cable, and the luminaire has two 16 AWG fixture wires and one 16 AWG ground wire. Figure542 (a) Yes Answer: (b) No The box is limited to 7 cu in., and the conductor equivalents total 8 cu in. [314.16(B)(1) Ex]. Step 1: Determine the number and size of conductors within the box. Fixture wires, including the fixture equipment grounding conductor arent counted when the fixture has a domed canopy. 14/2 NM Cable clamps Ground wire Total 2 14 AWG 1 14 AWG + 1 14 AWG 4 14 AWG conductors (b) No Figure542

c Conductors Added to an Existing Box


Question: How many 14 AWG conductors can be pulled through a 4 x 2 18 in. square box that has a plaster ring of 3.60 cu in.? The box already contains two receptacles, five 12 AWG conductors, and one 12 AWG equipment grounding conductor. Figure543 (a) 4 conductors (c) 6 conductors Answer: (b) 5 conductors Step 1: Determine the number and size of the existing conductors. Two Receptacles (2 yokes x 2 conductors) Five 12 AWG One equipment grounding conductor Total 4 12 AWG conductors 5 12 AWG conductors + 1 12 AWG conductors 10 12 AWG conductors (b) 5 conductors (d) 7 conductors

Step 2: Determine the volume of the conductors [Table 314.16(B)]. 14 AWG = 2 cu in. Four 14 AWG conductors = 4 wires x 2 cu in. = 8 cu in.

140

Mike Holts Illustrated Guide to Electrical Exam Preparation 2011 Edition

Raceway and Box Calculations

Unit 5

Step 2: Determine the volume of the existing conductors [Table 314.16(B)]. 12 AWG conductor = 2.25 cu in. 10 wires x 2.25 cu in. = 22.50 cu in. Step 3: Determine the space remaining for the additional 14 AWG conductors. Remaining space = Total space less the area required for existing conductors Total space = 30.30 cu in. (box) [Table 314.16(A)] + 3.60 cu in. (ring) = 33.90 cu in. Remaining space = 33.90 cu in. 22.50 cu in. (ten 12 AWG conductors) Remaining space = 11.40 cu in. Step 4: Determine the number of 14 AWG conductors permitted in the spare space. Conductors added = Remaining space/added conductors volume Conductors added = 11.40 cu in./2 cu in. = 5.70 [Table 314.16(B)] Conductors added = 5 (Rounding up doesnt apply to box fill.)

Tips for Outlet Box Sizing


Tip 1: Tip 2: If conductors are the same size, add them together and size the box using the AWG size columns of Table 314.16(A). If the box contains different sizes of conductors, use Table 314.16(B) to find the area of each conductor, add them up, and size the box from Table 314.16(A) using the cu in. column. Practice sizing boxes on the jobsite or in your own home, or by drawing out a picture problem to solve.

Tip 3:

PART CPULL BOXES, JUNCTION BOXES, AND CONDUIT BODIES


Introduction
Pull boxes, junction boxes, and conduit bodies must be sized to permit conductors to be installed so that the conductor insulation isnt damaged. For conductors 4 AWG and larger, pull boxes, junction boxes, and conduit bodies must be sized in accordance with 314.28 of the NEC. Figure544

Figure544

Figure543

Mike Holt Enterprises, Inc. www.MikeHolt.com 888.NEC.CODE (632.2633)

141

Unit 5

Raceway and Box Calculations

5.8 Pull/Junction Box Sizing Requirements


Boxes and Conduit Bodies for Conductors 4 AWG and Larger [314.28]
Boxes and conduit bodies containing conductors 4 AWG and larger that are required to be insulated must be sized so the conductor insulation wont be damaged. (A) Minimum Size. For raceways containing conductors 4 AWG or larger, the minimum dimensions of boxes and conduit bodies must comply with the following: (1) Straight Pulls. The minimum distance from where the conductors enter to the opposite wall must not be less than eight times the trade size of the largest raceway. Figure545

Figure546 U Pulls. When a conductor enters and leaves from the same wall, the distance from where the raceways enter to the opposite wall must not be less than six times the trade size of the largest raceway, plus the sum of the trade sizes of the remaining raceways on the same wall and row. Figure547

Figure545

(2) Angle Pulls, U Pulls, or Splices. Angle Pulls. This occurs when conductors enter a wall and leave through a wall that is located 90 degrees from the entry wall. The distance from the raceway entry to the opposite wall must not be less than six times the trade size of the largest raceway, plus the sum of the trade sizes of the remaining raceways on the same wall and row. Figure546

Figure547

142

Mike Holts Illustrated Guide to Electrical Exam Preparation 2011 Edition

Raceway and Box Calculations

Unit 5

Splices. When conductors are spliced, the distance from where the raceways enter to the opposite wall must not be less than six times the trade size of the largest raceway, plus the sum of the trade sizes of the remaining raceways on the same wall and row. Figure548

Distance Between Raceways. The distance between raceways enclosing the same conductor must not be less than six times the trade size of the largest raceway, measured from the raceways nearest edge-to-nearest edge. Figure550

Figure548

Figure550

Rows. Where there are multiple rows of raceway entries, each row is calculated individually and the row with the largest distance must be used. Figure549

Exception: When conductors enter an enclosure with a removable cover, such as a conduit body or wireway, the distance from where the conductors enter to the removable cover must not be less than the bending distance as listed in Table 312.6(A) for one conductor per terminal. Figure551

Figure549 Figure551

Mike Holt Enterprises, Inc. www.MikeHolt.com 888.NEC.CODE (632.2633)

143

Unit 5

Raceway and Box Calculations

5.9 Pull/Junction Box Sizing Tips


When sizing pull and junction boxes, follow these suggestions: Step 1: Always draw out the problem. Step 2: Calculate the HORIZONTAL distance(s): Left to right straight calculation Right to left straight calculation Left to right angle or U pull calculation Right to left angle or U pull calculation Step 3: Calculate the VERTICAL distance(s): Top to bottom straight calculation Bottom to top straight calculation Top to bottom angle or U pull calculation Bottom to top angle or U pull calculation Step 4: Calculate the distance between raceways enclosing the same conductors.

Figure552

c Vertical Dimension
Question: Whats the vertical dimension of this box? Figure553

5.10 Pull Box Examples


Pull Box Sizing
A junction box contains two trade size 3 raceways on the left side and one trade size 3 raceway on the right side. The conductors from one of the trade size 3 raceways on the left wall are pulled through the trade size 3 raceway on the right wall. The conductors from the other trade size 3 raceways on the left wall are pulled through a trade size 3 raceway at the bottom of the pull box.

(a) 18 in.

(b) 21 in.

(c) 24 in.

(d) 30 in.

Answer: (a) 18 in. [314.28] Top to bottom straight Bottom to top straight Top to bottom angle Bottom to top angle No calculation No calculation No calculation 6 x 3 in. = 18 in.

c Horizontal Dimension
Question: Whats the horizontal dimension of this box? Figure552 (a) 18 in. (b) 21 in. (c) 24 in. (d) 30 in.

Answer: (c) 24 in. [314.28] Left to right straight pull Right to left straight pull Left to right angle pull Right to left angle pull 8 x 3 in. = 24 in. 8 x 3 in. = 24 in. (6 x 3 in.) + 3 in. = 21 in. No calculation

Figure553

144

Mike Holts Illustrated Guide to Electrical Exam Preparation 2011 Edition

Raceway and Box Calculations

Unit 5

c Distance Between Raceways


Question: Whats the minimum distance between the two trade size 3 raceways that contain the same conductors? Figure554 (a) 18 in. (b) 21 in. (c) 24 in. (d) 30 in.

Answer: (a) 18 in. [314.28] 6 x 3 in. = 18 in.

Figure555

c Vertical Dimension
Question: Whats the vertical dimension of the box? Figure556 (a) 14 in. (b) 18 in. (c) 21 in. (d) 26 in.

Answer: (b) 18 in. [314.28(A)(2)] Top to bottom straight Bottom to top straight Top to bottom angle Bottom to top angle No calculation No calculation 6 x 3 in. = 18 in. No calculation

Figure554

Pull Box Sizing


A pull box contains a trade size 2 and trade size 3 raceway on the left side, a trade size 3 raceway on the top, and a trade size 2 raceway on the right side. The trade size 2 raceways are a straight pull and the trade size 3 raceways are an angle pull.

c Horizontal Dimension
Question: Whats the horizontal dimension of the box? Figure555 (a) 20 in. (b) 24 in. (c) 28 in. (d) 30 in.

Answer: (a) 20 in. [314.28(A)(2)] Left to right straight pull Right to left straight pull Left to right angle pull Right to left angle pull 8 x 2 in. = 16 in. 8 x 2 in. = 16 in. (6 x 3 in.) + 2 in. = 20 in. No calculation

Figure556

Mike Holt Enterprises, Inc. www.MikeHolt.com 888.NEC.CODE (632.2633)

145

Unit 5

Raceway and Box Calculations

c Distance Between Raceways


Question: If the two trade size 3 raceways contain the same conductors, whats the minimum distance between these raceways? Figure557 (a) 18 in. (b) 21 in. (c) 24 in. (d) 30 in.

CONCLUSION TO UNIT 5RACEWAY AND BOX CALCULATIONS


The importance of protecting conductor insulation during installation is understood by every electrician. The principles covered in this unit have gone far toward helping you achieve that goal. In this unit, you learned how to use the tables in Chapter 9 of the NEC when completing raceway fill calculions. First, the area of the conductor is found, using Chapter 9, Table 5 for insulated conductors or Chapter 9, Table 8 for bare conductors. Then after totaling the crosssectional areas of all the conductors, the raceway trade size from Chapter 9, Table 4 is selected using the available cross-sectional area of the raceway. Take your time when working out these calculations to select the correct insulation type and the correct raceway for your problem. Annex C provides a quicker method for sizing raceways than the Chapter 9 Tables when the conductors are all the same AWG size, and the same size in cross-sectional area (including the insulation). There are numerous tables in Annex C (based on the raceway type) that can be used to reduce the time spent in calculations, so once again be sure to take your time and be certain youre using the correct table. Metal wireways must be sized using the requirements of Article 376. The maximum fill for wireways isnt just how much you can squeeze into them. There are specific limits on conductor cross-sectional area, number of conductors, and wire-bending radius. Following the rules of Article 376 will provide a much safer installation and takes the mystery out of sizing wireways. Maintaining proper outlet box fill is important as you rough-in the installation. There are a number of details that were covered in determining the correct box size to be used that will be important on an exam. Be sure to remember what items are counted in box fill calculations, and review the information if necessary. Junction box and pull box calculations only come into play when the conductors are 4 AWG and larger. Straight pulls, angle pulls, and U pulls were all covered in this unit, as well as an often forgotten requirement that applies to two raceways that contain the same conductors. Always draw out a problem involving junction or pull boxes so that youll be able to visualize it and properly apply the calculations youve learned.

Answer: (a) 18 in. [314.28(A)(2)] 6 x 3 in. = 18 in.

Figure557

Summary
1. Slow down and take your time on these calculations. Its easy to make simple mistakes. 2. Pull box calculations can be trickyremember which wall youre working on. 3. Box calculations become more familiar with more practice. Use practical field examples to practice calculations. 4. Draw up some sample pull boxes and calculate them for practice.

146

Mike Holts Illustrated Guide to Electrical Exam Preparation 2011 Edition

5
PART ARACEWAY FILL

UNIT

Practice Questions
4. How many 16 TFFN conductors can be installed in trade size electrical metallic tubing? (a) 26 (b) 29 (c) 30 (d) 40

Please use the 2011 Code book to answer the following questions, which are based on the 2011 NEC.

PRACTICE QUESTIONS FOR UNIT 5RACEWAY AND BOX CALCULATIONS


5.

How many 6 RHH conductors (without outer cover) can be installed in trade size 1 electrical nonmetallic tubing? (a) 7 (b) 13 (c) 16 (d) 25

5.1 Understanding the NEC, Chapter 9 Tables


1. When all the conductors are the same size (total crosssectional area including insulation), the number of conductors permitted in a raceway can be determined by simply looking at the Tables in _____ of the NEC. (a) Chapter 9 (b) Annex B (c) Annex C (d) Annex D

6.

How many 1/0 XHHW conductors can be installed in trade size 2 flexible metal conduit? (a) 6 (b) 7 (c) 13 (d) 16

2. When equipment grounding conductors are installed in a raceway, the actual area of the conductor must be used when calculating raceway fill. (a) True (b) False

7.

How many 12 RHH conductors (with outer cover) can be installed in a trade size 1 IMC raceway? (a) 4 (b) 5 (c) 7 (d) 11

3.

When a raceway doesnt exceed 24 in. in length, the raceway is permitted to be filled to _____ percent of its cross-sectional area. (a) 31 (b) 40 (c) 53 (d) 60

8.

Three THHN compact conductors are needed in a trade size 2 rigid metal conduit. Whats the largest compact conductor that can be installed? (a) 4/0 AWG (b) 250 kcmil (c) 350 kcmil (d) 500 kcmil

Mike Holt Enterprises, Inc. www.MikeHolt.com 888.NEC.CODE (632.2633)

147

Unit 5

Raceway and Box Calculations Practice Questions

9.

The actual area of conductor fill is dependent on the raceway size and the number of conductors installed. If there are three or more conductors installed in a raceway, the total area of conductor fill is limited to _____ percent. (a) 31 (b) 40 (c) 53 (d) 60

14. Whats the cross-sectional area in square inches for an 8 AWG bare solid conductor? (a) 0.013 sq in. (b) 0.027 sq in. (c) 0.038 sq in. (d) 0.045 sq in.

5.2 Raceway Calculations


15. The number of conductors permitted in a raceway is dependent on the _____. (a) area of the raceway (b) percent area fill as listed in Chapter 9, Table 1 (c) area of the conductors as listed in Chapter 9, Tables 5 and 8 (d) all of these

10. Whats the cross-sectional area in square inches for a 10 THW conductor? (a) 0.0172 sq in. (b) 0.0243 sq in. (c) 0.0252 sq in. (d) 0.0278 sq in.

11. Whats the cross-sectional area in square inches for a 14 RHW conductor (without an outer cover)? (a) 0.0172 sq in. (b) 0.0209 sq in. (c) 0.0252 sq in. (d) 0.0278 sq in.

16. A 200A feeder installed in Schedule 80 PVC has three 3/0 THHN conductors, one 2 THHN conductor, and one 6 THHN conductor. What size raceway is required? (a) A trade size 2 raceway. (b) A trade size 2 raceway. (c) A trade size 3 raceway. (d) A trade size 3 raceway.

12. Whats the cross-sectional area in square inches for a 10 THHN conductor? (a) 0.0117 sq in. (b) 0.0172 sq in. (c) 0.0211 sq in. (d) 0.0252 sq in.

17. What size rigid metal conduit is required for three 4/0 THHN conductors, one 1/0 THHN conductor, and one 4 THHN conductor when the raceway is 24 in. or less in length? (a) A trade size 1 rigid metal conduit. (b) A trade size 2 rigid metal conduit. (c) A trade size 2 rigid metal conduit. (d) A trade size 3 rigid metal conduit.

13. Whats the cross-sectional area in square inches for a 12 RHH conductor (with an outer cover)? (a) 0.0117 sq in. (b) 0.0252 sq in. (c) 0.0327 sq in. (d) 0.0353 sq in. 18. An existing trade size rigid metal conduit that does not exceed 24 in. in length contains four 10 THHN conductors and one 10 AWG (bare stranded) ground wire. How many additional 10 THHN conductors can be installed? (a) 5 (b) 7 (c) 9 (d) 11

148

Mike Holts Illustrated Guide to Electrical Exam Preparation 2011 Edition

Raceway and Box Calculations Practice Questions

Unit 5

5.3 Wireways
19. Whats the cross-sectional area of a 4 in. x 4 in. wireway? (a) 6 sq in. (b) 16 sq in. (c) 36 sq in. (d) 66 sq in.

5.6 Conductor Equivalents


24. Table 314.16(A) doesnt take into consideration the volume of _____. (a) switches and receptacles (b) luminaire studs and hickeys (c) internal cable clamps (d) all of these

20.

Whats the maximum allowable sq in. of conductor fill for a 4 in. x 4 in. wireway? (a) 2.40 sq in. (b) 3.20 sq in. (c) 5.30 sq in. (d) 12 sq in.

25. When determining the number of conductors for box fill calculations, which of the following statements is(are) true? (a) A luminaire stud or hickey is considered as one conductor for each type, based on the largest conductor that enters the outlet box. (b) Internal factory cable clamps are considered as one conductor for one or more cable clamps, based on the largest conductor that enters the outlet box. (c) The single gang device yoke is considered as two conductors, based on the largest conductor that terminates on the strap (device mounting fitting). (d) all of these

21. Whats the maximum number of 400 kcmil THHN conductors that can be installed in a 6 in. x 6 in. wireway? (a) 4 (b) 6 (c) 10 (d) 12

PART BOUTLET BOX FILL CALCULATIONS [314.16]


5.5 Sizing BoxConductors All the Same Size [Table 314.16(A)]
22. What size box is the minimum required for six 14 THHN conductors and three 14 THW conductors? (a) A 4 x 1 square box. (b) A 4 x 1 round box. (c) A 4 x 1 round box. (d) A 4 x 218 square box.

26. When determining the number of conductors for box fill calculations, which of the following statements is(are) true? (a) Each conductor that runs through the box without a splice or leaving a loop long enough to splice is considered as one conductor. (b) Each conductor that originates outside the box and terminates in the box is considered as one conductor. (c) Wirenuts, cable connectors, raceway fittings, and conductors that originate and terminate within the outlet box (equipment bonding jumpers and pigtails) arent counted for box fill calculations. (d) all of these

23. How many 10 AWG conductors are permitted in a 4 x 1 square box? (a) 8 conductors (b) 9 conductors (c) 10 conductors (d) 11 conductors

27. Its permitted to omit one equipment grounding con ductor and not more than _____ that enter a box from a luminaire canopy. (a) five fixture wires (b) four 16 AWG fixture wires (c) four 18 AWG fixture wires (d) b and c

Mike Holt Enterprises, Inc. www.MikeHolt.com 888.NEC.CODE (632.2633)

149

Unit 5

Raceway and Box Calculations Practice Questions

28. Can a round 4 x in. box marked as 8 cu in. with manufactured cable clamps supplied with 14/2 W/G NM be used with a luminaire that has two 18 TFN conductors and a canopy cover? (a) Yes (b) No

(c) The distance between raceways enclosing the same conductor(s) must not be less than six times the trade size diameter of the largest raceway. (d) all of these

5.7 Outlet Box Sizing [314.16(B)]


29. What size outlet box is required for one 12/2 W/G NM cable that terminates on a switch, one 12/3 W/G NM cable that terminates on a receptacle, and the box has manufactured cable clamps? (a) A 4 x 1 square box. (b) A 4 x 1 square box. (c) A 4 x 218 square box. (d) A 3 x 2 x 3 device box

32. When conductors enter an enclosure opposite a removable cover, the distance from where the conductors enter to the removable cover must not be less than _____. (a) six times the largest raceway (b) eight times the largest raceway (c) a or b (d) none of these The following information applies to the next three questions. A junction box contains two trade size 2 raceways on the left side and one trade size 2 raceway on the right side. The conductors from one trade size 2 raceway (on the left wall) are pulled through the raceway on the right wall. The other trade size 2 raceway conductors (on the left wall) are pulled through a trade size 2 raceway at the bottom of the pull box. 33. Whats the minimum distance from the left wall to the right wall? (a) 18 in. (b) 20 in. (c) 21 in. (d) 24 in.

30. How many 14 AWG conductors can be pulled through a 4 x 1 square box with a plaster ring marked 3.60 cu in.? The box already contains two duplex receptacles, five 14 AWG conductors, and two grounding conductors. (a) one conductor (b) two conductors (c) three conductors (d) four conductors

PART CPULL BOXES, JUNCTION BOXES, AND CONDUIT BODIES


5.8 Pull/Junction Box Sizing Requirements
31. When conductors 4 AWG and larger are installed in boxes and conduit bodies, the enclosure must be sized according to which of the following requirements? (a) The minimum distance for straight pull calculations from where the conductors enter to the opposite wall must not be less than eight times the trade size of the largest raceway. (b) The distance for angle pull calculations from the raceway entry to the opposite wall must not be less than six times the trade size diameter of the largest raceway, plus the sum of the diameters of the remaining raceways on the same wall and row.

34. Whats the minimum distance from the bottom wall to the top wall? (a) 15 in. (b) 18 in. (c) 21 in. (d) 24 in.

35. Whats the minimum distance between the raceways that contain the same conductors? (a) 15 in. (b) 18 in. (c) 21 in. (d) 24 in.

150

Mike Holts Illustrated Guide to Electrical Exam Preparation 2011 Edition

Raceway and Box Calculations Practice Questions

Unit 5

The following information applies to the next three questions. A junction box contains two trade size 2 raceways on the left side, and two trade size 2 raceways on the top. 36. Whats the minimum distance from the left wall to the right wall? (a) 14 in. (b) 21 in. (c) 24 in. (d) 28 in.

38. Whats the minimum distance between the trade size 2 raceways that contain the same conductors? (a) 12 in. (b) 18 in. (c) 21 in. (d) 24 in.

37. Whats the minimum distance from the bottom wall to the top wall? (a) 14 in. (b) 18 in. (c) 21 in. (d) 24 in.

Mike Holt Enterprises, Inc. www.MikeHolt.com 888.NEC.CODE (632.2633)

151

You might also like