You are on page 1of 4

Mxx AC and DC Modular Platform

>N+1 redundancy >Hot plug-in modules >Scalable and flexible

Key features and application areas

N+1 redundancy
One (N+1) or more (N+X) redundant modules may be added to the system, ensuring a high level of availability while reducing the initial investment. In the event of a module failure, the load remains secure and operators can swap in a new module to reestablish redundancy during operation. Hot plug-in technology means that modules can be replaced quickly and easily, leading to a low Mean Time To Repair (MTTR).

Scalability and flexibility


The Mxx platform can be easily scaled to accommodate for future changes in load requirements. If more power is needed or additional consumers are added to the system, new modules can be simply plugged into empty slots to meet the new needs. This allows the performance of the system to grow in line with the requirements of the user, thereby reducing the initial investment. Different types of modules (i.e. rectifiers, inverters, DC/DC converters, switches) can also be combined and added to a system, making the Mxx platform highly flexible and able to meet changing requirements.

CAN-bus communication
The Mxx platform links all modules and devices to one CAN-bus. This bus handles all system communication, such as control tasks, measurements and alarms. In this way, all devices, including rectifiers, inverters, controllers and switches can share information and react to one another. The CAN-bus itself is highly robust and immune to any interference. All power supply modules can also operate fully in standalone mode, in the event of a CAN-bus malfunction.

Monitoring and diagnostics


All important data, such as alarms and measurements, can be easily configured with GUTORs multi-management tool, via USB link to a local computer. This tool allows the user to set parameters, route signals and define alarms using a simple user interface. Data can be monitored in the following ways: >Alphanumeric LC display >LED signals >Isolated relay outputs >SNMP web interface

Oil&Gas

Energy & Power Generation

Mining

Water Treatment & Desalination

Transport

Chemical Industry

Industrial Process Control

All Industrial Applications

Mxx System types

N+1 redundancy Hot plug-in Scalable and flexible

MDC Rectifier
Output voltages: 24, 48, 110, 125, 220 VDC Output power: 0.5 to 25 kW Features >PFC rectifier (Input PF > 0.99, THDi < 5%) >Input over voltage protection >High power density >Backfeed protection through integrated decoupling from the DC bus >Optimal, temperature controlled cooling concept >Compact 19 design

MXP UPS
Output power: 1 to 12 kVA 1 or 3 phase output Features >PFC rectifier (Input PF > 0.99, THDi < 5%) >Redundant synchronization bus for increased reliability >Input over voltage protection >High power density >E xcellent sinusoidal output >Optimal, temperature controlled cooling concept >Compact 19 design

MXW Inverter
Output power: 1 to 12 kVA 1 or 3 phase output Features >E xcellent overall efficiency >Redundant synchronization bus for increased reliability >Resistant to sustained short circuit >High power density >E xcellent sinusoidal output >Optimal, temperature controlled cooling concept >Compact 19 design

MDD DC/DC Converter


Output voltages: 24, 48, 110, 125, 220 VDC Output power: 0.5 to 25 kW Features >Wide input voltage range >Input over voltage protection >High power density >Optimal, temperature controlled cooling concept >Compact 19 design

Technical information
MDC Rectifier
24V Input Voltage Allowable tolerance Current (per module) Power factor Output Voltage Voltage range Current (per module) Efficiency 24V DC 2133V DC 50.0A DC 48V DC 4262V DC 56.0A DC 110V DC 87150V DC 25.0A DC >91% 125V DC 87150V DC 22.0A DC 220V DC 170295V DC 12.5A DC 5.8A AC 230VAC +/- 20% 12.9A AC >0.99 @ output power >50% 48V 110V 125V 220V

MXP UPS
48V Input Voltage Allowable tolerance Current (per module) Power factor Battery circuit Voltage Voltage range Current (per module) Output Voltage Tolerance Adjustable range Current (per module) 230VAC +/- 0.5% 200242V DC 9.8A AC @ cos 0.8 48V DC 4262V DC 56.0A DC 110V DC 87150V DC 25.0A DC 125V DC 87150V DC 22.0A DC 220V DC 170295V DC 12.5A DC 230VAC +/- 20% 12.9A AC >0.99 @ output power >50% 110V 125V 220V

MXW Inverter
48V Input Voltage Current (per module) Output Voltage Voltage range Adjustable range Current (per module) Efficiency 230VAC +/- 0.5% 200242V DC 9.8A AC @ cos 0.8 >90% 40.867.5V DC 41.6A DC @ 48V DC 91.8145V DC 18.4A DC @ 108V DC 91.8145V DC 15.9A DC @ 125V DC 183.6270V DC 9.2A DC @ 216V DC 110V 125V 220V

MDD DC/DC Converter


24V Input Voltage Current (per module) Output Voltage Voltage range Current (per module) Efficiency 24V DC 2133V DC 50.0A DC 48V DC 4262V DC 25.0A DC 110V DC 87150V DC 11.0A DC >89% 125V DC 87150V DC 9.5A DC 220V DC 170295V DC 5.5A DC 91.7300V DC 20.7A@110V DC / 10.3A@220V DC 48V 110V 125V 220V

Offices GUTOR Electronic LLC Brazil > Canada > China > Germany > India Hardstrasse 7274 Japan > Malaysia > Mexico > Russia > Saudi Arabia 5430 Wettingen United Arab Emirates > USA Switzerland P +41 (0)56 437 34 34 F +41 (0)56 437 34 44 gutor.info@schneider-electric.com www.gutor.com