DESIGN MANUAL

R410A
Indoor Unit
<4-way Air Discharge Cassette Type>

Outdoor Unit
Cooling Only Model
<Inverter Unit>

MMU-AP0091H, AP0121H, AP0151H, MMU-AP0181H, AP0241H, AP0271H, MMU-AP0301H, AP0361H, AP0481H MMU-AP0561H
<2-way Air Discharge Cassette Type>

MMU-AP0071WH, AP0091WH, AP0121WH, MMU-AP0151WH, AP0181WH, AP0241WH, MMU-AP0271WH, AP0301WH MMU-AP0481WH (CHINA market only)
<1-way Air Discharge Cassette Type>

MMY-MAP0501T8, MAP0601T8 MMY-MAP0801T8, MAP1001T8 MMY-MAP1201T8

Heat Pump Model


<Inverter Unit>

MMU-AP0071YH, AP0091YH, AP0121YH, MMU-AP0151SH, AP0181SH, AP0241SH


<Concealed Duct Standard Type>

MMD-AP0071BH, AP0091BH, AP0121BH, MMD-AP0151BH, AP0181BH, AP0241BH, MMD-AP0271BH, AP0301BH, AP0361BH, MMD-AP0481BH, AP0561BH
<Concealed Duct High Static Pressure Type>

MMY-MAP0501HT8, MAP0601HT8 MMY-MAP0801HT8, MAP1001HT8 MMY-MAP1201HT8

Heat Pump Model


<Inverter Unit>

MMD-AP0181H, AP0241H, AP0271H, MMD-AP0361H, AP0481H, AP0721H, MMD-AP0961H


<Under Ceiling Type>

MMY-MAP0501HT7, MAP0601HT7 MMY-MAP0801HT7, MAP1001HT7 MMY-MAP1201HT7

MMC-AP0151H, AP0181H, AP0241H, MMC-AP0271H, AP0361H, AP0481H


<High Wall Type>

MMK-AP0071H, AP0091H, AP0121H, MMK-AP0151H, AP0181H, AP0241H


<Floor Standing Cabinet Type>

MML-AP0071H, AP0091H, AP0121H, MML-AP0151H, AP0181H, AP0241H


<Floor Standing Concealed Type>

MML-AP0071BH, AP0091BH, AP0121BH, MML-AP0151BH, AP0181BH, AP0241BH


<Floor Standing Type>

MMF-AP0151H, AP0181H, AP0241H MMF-AP0271H, AP0361H, AP0481H MMF-AP0561H

PRINTED IN JAPAN, 2004

This Manual is used for both models, Cooling Only model and Heat Pump model. Positions shaded with screens in the description and tables are applied to the Heat Pump model only. Parts marked with XXX indicate the 60Hz, 380V model only.

CONTENTS
DESIGN MANUAL ..................................................................3
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. OUTLINE OF TOSHIBA SUPER MMS (SUPER MODULAR MULTI SYSTEM) ............................................... 3 SUMMARY OF SYSTEM EQUIPMENTS ............................................ 6 BASIC SYSTEM CONFIGURATION ................................................. 13 EQUIPMENT SELECTION PROCEDURE ........................................ 19 REFRIGERANT PIPING DESIGN ..................................................... 29 WIRING DESIGN ................................................................................ 34 CONTROLS ........................................................................................ 41 ACCESSORIES .................................................................................. 47 TECHNICAL SPECIFICATIONS ........................................................ 49 FAN CHARACTERISTICS ................................................................. 91 DIMENSIONAL DRAWINGS .............................................................. 95

DESIGN MANUAL
1. OUTLINE OF TOSHIBA SUPER MMS (Super Modular Multi System)
Shortest route design by free branching
Combination of line and header branching is highly flexible. This follows for the shortest design route possible, thereby saving on installation time and cost. Line/header branching after header branching is only available with TOSHIBA Super MMS.

Line branching
Outdoor unit Branching joint

8F

Indoor unit

Header branching
Outdoor unit Branching header

7F

Indoor unit

Line + Header branching


Outdoor unit

Header

2F

Branching joint

Indoor unit

Line branching after header branching


Outdoor unit Header Super MMS MMS Only Only Indoor unit Branching joint

1F

Header branching after header branching


Outdoor unit Header Super MMS Only Header Indoor unit

Non-polarized control wiring between outdoor and indoor units


Outdoor unit
U1 U2

Indoor unit

U1 U2

U1 U2

U1 U2

Wiring diagnosis system


Use the switches on the micro processor P.C. board of the outdoor unit. Detects wiring to the indoor unit a4 which should not be in system A. b4 is missing in system B.
Piping

8F

A system

Outdoor unit a1 a2 a3 a4

Wiring

Indoor unit

B system

Outdoor unit b1 b2 b3 b4

7F
Outdoor unit Allowable pipe length : 175m equivalent length

Height difference between indoor unit and outdoor unit : 50m

Height difference between indoor unit and indoor unit : 30m

1st branching section

2F

From 1st branching to the farthest indoor unit : 65m

1F

Compact design
The design of the modular TOSHIBA Super MMS outdoor unit allows for easy unit maneuvering into any standard lift. Its compactness also allows it to be easily installed in limited spaces.

Largest system capacity


TOSHIBA Super MMS can be combined up to 48 HP (135kW) as one refrigerant system.

Energy saving
No. 1 COP in VRF industry. Compared with the conventional chiller fan coil system, a large energy saving can be realized.

Advanced bus communication system


Wiring between indoor and outdoor unit is a simple 2 wire system. Communication address is also automatically configured. A default test mode operation is available.

Self diagnostics system


Comprehensive troubleshooting code allows for timely identification of problems arising.

High lift design


Equivalent pipe length of 175m and vertical lift of 50m is made possible with TOSHIBA Super MMS. Vertical lift between indoor units of 30m is the highest in the industry. This allows for greater flexibility in the location of the system.

Multiplied indoor units


Indoor units with different capacities and configurations can be combined up to 135% of the outdoor unit capacity. A maximum of 48 indoor units can be combined with the 30 48 HP outdoor units.

Intelligent control
TOSHIBA Super MMS intelligent controls and modulating valves deliver the required capacity, according to the load variation from 50% to 100%. The intelligent controls and modulating valves limit or increase the cooling capacity dynamically so humidity and temperature are kept in the comfort zone.

Conforms to building control law


IAQ (Indoor Air Quality) is also achieved by combining various accessories required by the Building Control Law.

Wide control applications


Artificial Intelligence Network system
Central control and monitoring system available Weekly schedule operation through weekly timer

Integration with Building Management System (BMS) is available.

2. SUMMARY OF SYSTEM EQUIPMENTS


Equipments
1. Outdoor units
Corresponding HP Inverter unit 5 HP 6 HP 8 HP 10 HP 12 HP Appearance Heat pump MMY- MAP0501HT8 MAP0601HT8 MAP0801HT8 MAP1001H8 MAP1201HT8 Model Heat pump MMY- MAP0501HT7 MAP0601HT7 MAP0801HT7 MAP1001HT7 MAP1201HT7 name Cooling only MMY- MAP0501T8 MAP0601T8 MAP0801T8 MAP1001T8 MAP1201T8 Cooling capacity (kW) Heating capacity (kW) 14.0 16.0 16.0 18.0 22.4 25.0 28.0 31.5 33.5 37.5

2. Outdoor units (Combination of outdoor units)


Corresponding HP 5 HP 6 HP 8 HP 10 HP 12 HP MMY- MAP0501HT8 MAP0601HT8 MAP0801HT8 MAP1001HT8 MAP1201HT8 MMY- MAP0501HT7 MAP0601HT7 MAP0801HT7 MAP1001HT7 MAP1201HT7 MMY- MAP0501T8 MAP0601T8 MAP0801T8 MAP1001T8 MAP1201T8 Cooling capacity (kW) 14.0 16.0 22.4 28.0 33.5 Heating capacity (kW) 16.0 18.0 25.0 31.5 37.5 5 HP 6 HP 8 HP 10 HP 12 HP Combined outdoor units No. of connectable 8 10 13 16 20 indoor units Combined Model Corresponding HP MMYMMYMMYCooling capacity (kW) Heating capacity (kW) Combined Model Combined outdoor units No. of connectable indoor units Corresponding HP MMYMMYMMYCooling capacity (kW) Heating capacity (kW) Combined Model Combined outdoor units No. of connectable indoor units 22 HP AP2211HT8 AP2211HT7 AP2211T8 61.5 69.0 12 HP 10 HP 37 36 HP AP3601HT8 AP3601HT7 AP3601T8 101.0 113.0 10 HP 10 HP 8 HP 8 HP 48 24 HP AP2401HT8 AP2401HT7 AP2401T8 68.0 76.5 8 HP 8 HP 8 HP 40 36 HP AP3611HT8 AP3611HT7 AP3611T8 101.0 113.0 12 HP 12 HP 12 HP 48 24 HP AP2411HT8 AP2411HT7 AP2411T8 68.0 76.5 12 HP 12 HP 40 38 HP AP3801HT8 AP3801HT7 AP3801T8 106.5 119.5 10 HP 10 HP 10 HP 8 HP 48 26 HP AP2601HT8 AP2601HT7 AP2601T8 73.0 81.5 10 HP 8 HP 8 HP 43 40 HP AP4001HT8 AP4001HT7 AP4001T8 112.0 126.5 10 HP 10 HP 10 HP 10 HP 48 28 HP AP2801HT8 AP2801HT7 AP2801T8 78.5 88.0 10 HP 10 HP 8 HP 47 42 HP AP4201HT8 AP4201HT7 AP4201T8 118.0 132.0 12 HP 10 HP 10 HP 10 HP 48 14 HP AP1401HT8 AP1401HT7 AP1401T8 38.4 43.0 8 HP 6 HP 23 30 HP AP3001HT8 AP3001HT7 AP3001T8 84.0 95.0 10 HP 10 HP 10 HP 48 44 HP AP4401HT8 AP4401HT7 AP4401T8 123.5 138.0 12 HP 12 HP 10 HP 10 HP 48 16 HP AP1601HT8 AP1601HT7 AP1601T8 45.0 50.0 8 HP 8 HP 27 32 HP AP3201HT8 AP3201HT7 AP3201T8 90.0 100.0 8 HP 8 HP 8 HP 8 HP 48 46 HP AP4601HT8 AP4601HT7 AP4601T8 130.0 145.0 12 HP 12 HP 12 HP 10 HP 48 18 HP AP1801HT8 AP1801HT7 AP1801T8 50.4 56.5 10 HP 8 HP 30 32 HP AP3211HT8 AP3211HT7 AP3211T8 90.0 100.0 12 HP 10 HP 10 HP 48 48 HP AP4801HT8 AP4801HT7 AP4801T8 135.0 150.0 12 HP 12 HP 12 HP 12 HP 48 20 HP AP2001HT8 AP2001HT7 AP2001T8 56.0 63.0 10 HP 10 HP 33 34 HP AP3401HT8 AP3401HT7 AP3401T8 96.0 108.0 10 HP 8 HP 8 HP 8 HP 48 22 HP AP2201HT8 AP2201HT7 AP2201T8 61.5 69.0 8 HP 8 HP 6 HP 37 34 HP AP3411HT8 AP3411HT7 AP3411T8 96.0 108.0 12 HP 12 HP 10 HP 48

3. Branching joints and headers


Y-shape branching joint (*3) 4-branching header (*4) 8-branching header (*4) (*5) Model name RBM-BY53E RBM-BY103E RBM-BY203E RBM-BY303E RBM-HY1043E RBM-HY2043E RBM-HY1083E RBM-HY2083E Usage Indoor unit capacity code (*1) : Total below 6.4 Indoor unit capacity code (*1) : Total 6.4 or more and below 14.2 (*2) Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2 (*2) Indoor unit capacity code (*1) : Total 25.2 or more (*2) Indoor unit capacity code (*1) : Total below 14.2 Max.4 Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2 branches Indoor unit capacity code (*1) : Total below 14.2 Max.8 Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2 branches 1 set of 3 types of T-shape joint pipes as described below: The required quantity is arranged and they are combined at the site. Connection piping Corresponded dia. (mm) Balance pipe 9.5 Piping at liquid side 9.5 to 22.2 Piping at gas side 15.9 to 41.3 Appearance

T-shape branching joint (For connection of outdoor units)

RBM-BT13E

Q'ty 1 1 1

*1 *2 *3 *4 *5 *6

Capacity code can be obtained from page 10. (Capacity code is not actual capacity) If total capacity code value of indoor unit exceeds that of outdoor unit, apply capacity code of outdoor unit. When using Y-shape branching joint for 1st branching, select according to capacity code of outdoor unit. Max. 6.0 capacity code in total can be connected. If capacity code of outdoor unit is 26 and more, it is not used for 1st branching. Model names for outdoor and indoor units described in this guide are shortened because of the space constraint.

Cooling Only model

50Hz

Super Modular Multi System Outdoor Unit : List of Product and Combined Model Name
HP No. of Model name (Capacity combined MMYcode) units 5HP ( 5) 6HP ( 6) 8HP ( 8) MAP0501T8 MAP0601T8 MAP0801T8 1 1 1 1 1 2 2 2 2 3 2 3 2 3 3 3 4 3 4 3 4 3 4 4 4 4 4 4 MAP0801T8 1 MAP1001T8 MAP1001T8 MAP1001T8 MAP1001T8 MAP1001T8 3 4 3 2 1 MAP1201T8 MAP1201T8 MAP1201T8 MAP1201T8 1 2 3 4 MAP0801T8 2 MAP0801T8 3 MAP0801T8 4 MAP1001T8 MAP1001T8 MAP1001T8 MAP1001T8 2 1 1 2 MAP1201T8 3 MAP1201T8 2 MAP1201T8 1 MAP0801T8 MAP0801T8 2 1 MAP1001T8 MAP1001T8 MAP1001T8 1 2 3 MAP0801T8 3 MAP1201T8 2 MAP0601T8 1 MAP0801T8 2 MAP1001T8 1 MAP1201T8 1 MAP0601T8 1 MAP0801T8 MAP0801T8 MAP0801T8 1 2 1 MAP1001T8 MAP1001T8 1 2 Inverter 5HP MMYMAP0501T8 Used Q'ty 1 MAP0601T8 1 MAP0801T8 1 MAP1001T8 1 MAP1201T8 1 Inverter 6HP MMYUsed Q'ty Inverter 8HP MMYUsed Q'ty Inverter 10HP MMYUsed Q'ty Inverter 12HP MMYUsed Q'ty

10HP (10) MAP1001T8 12HP (12) MAP1201T8 14HP (14) 16HP (16) 18HP (18) 20HP (20) 22HP (22) 22HP (22) 24HP (24) 24HP (24) 26HP (26) 28HP (28) 30HP (30) 32HP (32) 32HP (32) 34HP (34) 34HP (34) 36HP (36) 36HP (36) 38HP (38) 40HP (40) 42HP (42) 44HP (44) 46HP (46) 48HP (46) AP1401T8 AP1601T8 AP1801T8 AP2001T8 AP2201T8 AP2211T8 AP2401T8 AP2411T8 AP2601T8 AP2801T8 AP3001T8 AP3201T8 AP3211T8 AP3401T8 AP3411T8 AP3601T8 AP3611T8 AP3801T8 AP4001T8 AP4201T8 AP4401T8 AP4601T8 AP4801T8

1. Allocation standard of model name


MMY M AP T 8
Power supply specifications, 3 380415 V, 50Hz ....... 8 T : Capacity variable unit Development series No. Capacity rank HP x 10 New refrigerant R410A M : Single module unit, No mark : Combined Model name Modular Multi

2. Range of combined capacity


No. of combined units : 1 to 4 units Capacity of combined units : 14 HP (140 type) to 48 HP (480 type)

3. Rated conditions (Rated mode : Condition)


Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB

Heat Pump model

50Hz

Super Modular Multi System Outdoor Unit : List of Product and Combined Model Name
HP No. of Model name (Capacity combined MMYcode) units 5HP ( 5) MAP0501HT8 6HP ( 6) MAP0601HT8 8HP ( 8) MAP0801HT8 10HP (10) MAP1001HT8 12HP (12) MAP1201HT8 14HP (14) AP1401HT8 16HP (16) AP1601HT8 18HP (18) AP1801HT8 20HP (20) AP2001HT8 22HP (22) AP2201HT8 22HP (22) AP2211HT8 24HP (24) AP2401HT8 24HP (24) AP2411HT8 26HP (26) AP2601HT8 28HP (28) AP2801HT8 30HP (30) AP3001HT8 32HP (32) AP3201HT8 32HP (32) AP3211HT8 34HP (34) AP3401HT8 34HP (34) AP3411HT8 36HP (36) AP3601HT8 36HP (36) AP3611HT8 38HP (38) AP3801HT8 40HP (40) AP4001HT8 42HP (42) AP4201HT8 44HP (44) AP4401HT8 46HP (46) AP4601HT8 48HP (46) AP4801HT8 1 1 1 1 1 2 2 2 2 3 2 3 2 3 3 3 4 3 4 3 4 3 4 4 4 4 4 4 MAP0801HT8 1 MAP1001HT8 MAP1001HT8 MAP1001HT8 MAP1001HT8 MAP1001HT8 3 4 3 2 1 MAP1201HT8 MAP1201HT8 MAP1201HT8 MAP1201HT8 1 2 3 4 MAP0801HT8 2 MAP0801HT8 3 MAP0801HT8 4 MAP1001HT8 MAP1001HT8 MAP1001HT8 MAP1001HT8 2 1 1 2 MAP1201HT8 3 MAP1201HT8 2 MAP1201HT8 1 MAP0801HT8 MAP0801HT8 2 1 MAP1001HT8 MAP1001HT8 MAP1001HT8 1 2 3 MAP0801HT8 3 MAP1201HT8 2 MAP0601HT8 1 MAP0801HT8 2 MAP1001HT8 1 MAP1201HT8 1 MAP0601HT8 1 MAP0801HT8 MAP0801HT8 MAP0801HT8 1 2 1 MAP1001HT8 MAP1001HT8 1 2 Inverter 5 HP MMYMAP0501HT8 Used Q'ty 1 MAP0601HT8 1 MAP0801HT8 1 MAP1001HT8 1 MAP1201HT8 1 Inverter 6 HP MMYUsed Q'ty Inverter 8 HP MMYUsed Q'ty Inverter 10 HP MMYUsed Q'ty Inverter 12 HP MMYUsed Q'ty

1. Allocation standard of model name


MMY M AP H T 8
Power supply specifications, 3 380415 V, 50Hz ....... 8 T : Capacity variable unit H : Heat pump Development series No. Capacity rank HP x 10 New refrigerant R410A M : Single module unit, No mark : Combined Model name Modular Multi

2. Range of combined capacity


No. of combined units : 1 to 4 units Capacity of combined units : 14 HP (140 type) to 48 HP (480 type)

3. Rated conditions (Rated mode : Condition)


Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

Heat Pump model

60Hz

Super Modular Multi System Outdoor Unit : List of Product and Combined Model Name
HP No. of Model name (Capacity combined MMYcode) units 5HP ( 5) MAP0501HT7 6HP ( 6) MAP0601HT7 8HP ( 8) MAP0801HT7 10HP (10) MAP1001HT7 12HP (12) MAP1201HT7 14HP (14) AP1401HT7 16HP (16) AP1601HT7 18HP (18) AP1801HT7 20HP (20) AP2001HT7 22HP (22) AP2201HT7 22HP (22) AP2211HT7 24HP (24) AP2401HT7 24HP (24) AP2411HT7 26HP (26) AP2601HT7 28HP (28) AP2801HT7 30HP (30) AP3001HT7 32HP (32) AP3201HT7 32HP (32) AP3211HT7 34HP (34) AP3401HT7 34HP (34) AP3411HT7 36HP (36) AP3601HT7 36HP (36) AP3611HT7 38HP (38) AP3801HT7 40HP (40) AP4001HT7 42HP (42) AP4201HT7 44HP (44) AP4401HT7 46HP (46) AP4601HT7 48HP (46) AP4801HT7 1 1 1 1 1 2 2 2 2 3 2 3 2 3 3 3 4 3 4 3 4 3 4 4 4 4 4 4 MAP0801HT7 1 MAP1001HT7 MAP1001HT7 MAP1001HT7 MAP1001HT7 MAP1001HT7 3 4 3 2 1 MAP1201HT7 MAP1201HT7 MAP1201HT7 MAP1201HT7 1 2 3 4 MAP0801HT7 2 MAP0801HT7 3 MAP0801HT7 4 MAP1001HT7 MAP1001HT7 MAP1001HT7 MAP1001HT7 2 1 1 2 MAP1201HT7 3 MAP1201HT7 2 MAP1201HT7 1 MAP0801HT7 MAP0801HT7 2 1 MAP1001HT7 MAP1001HT7 MAP1001HT7 1 2 3 MAP0801HT7 3 MAP1201HT7 2 MAP0601HT7 1 MAP0801HT7 2 MAP1001HT7 1 MAP1201HT7 1 MAP0601HT7 1 MAP0801HT7 MAP0801HT7 MAP0801HT7 1 2 1 MAP1001HT7 MAP1001HT7 1 2 Inverter 5 HP MMYMAP0501HT7 Used Q'ty 1 MAP0601HT7 1 MAP0801HT7 1 MAP1001HT7 1 MAP1201HT7 1 Inverter 6 HP MMYUsed Q'ty Inverter 8 HP MMYUsed Q'ty Inverter 10 HP MMYUsed Q'ty Inverter 12 HP MMYUsed Q'ty

1. Allocation standard of model name


MMY M AP H T 7
Power supply specifications, 3 380 V, 60Hz ....... 7 T : Capacity variable unit H : Heat pump Development series No. Capacity rank HP x 10 New refrigerant R410A M : Single module unit, No mark : Combined Model name Modular Multi

2. Range of combined capacity


No. of combined units : 1 to 4 units Capacity of combined units : 14 HP (140 type) to 48 HP (480 type)

3. Rated conditions (Rated mode : Condition)


Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

4. Indoor unit
Type Appearance Model name MMU-AP0091H MMU-AP0121H MMU-AP0151H MMU-AP0181H MMU-AP0241H MMU-AP0271H MMU-AP0301H MMU-AP0361H MMU-AP0481H MMU-AP0561H MMU-AP0071WH MMU-AP0091WH MMU-AP0121WH MMU-AP0151WH MMU-AP0181WH MMU-AP0241WH MMU-AP0271WH MMU-AP0301WH MMU-AP0481WH (China only) MMU-AP0071YH MMU-AP0091YH MMU-AP0121YH MMU-AP0151SH MMU-AP0181SH MMU-AP0241SH MMD-AP0071BH MMD-AP0091BH MMD-AP0121BH MMD-AP0151BH MMD-AP0181BH MMD-AP0241BH MMD-AP0271BH MMD-AP0301BH MMD-AP0361BH MMD-AP0481BH MMD-AP0561BH MMD-AP0181H MMD-AP0241H MMD-AP0271H MMD-AP0361H MMD-AP0481H MMD-AP0721H MMD-AP0961H MMC-AP0151H MMC-AP0181H MMC-AP0241H MMC-AP0271H MMC-AP0361H MMC-AP0481H MMK-AP0071H MMK-AP0091H MMK-AP0121H MMK-AP0151H MMK-AP0181H MMK-AP0241H MML-AP0071H MML-AP0091H MML-AP0121H MML-AP0151H MML-AP0181H MML-AP0241H MML-AP0071BH MML-AP0091BH MML-AP0121BH MML-AP0151BH MML-AP0181BH MML-AP0241BH MMF-AP0151H MMF-AP0181H MMF-AP0241H MMF-AP0271H MMF-AP0361H MMF-AP0481H MMF-AP0561H Capacity rank Capacity code 009 type 012 type 015 type 018 type 024 type 027 type 030 type 036 type 048 type 056 type 007 type 009 type 012 type 015 type 018 type 024 type 027 type 030 type 048 type 007 type 009 type 012 type 015 type 018 type 024 type 007 type 009 type 012 type 015 type 018 type 024 type 027 type 030 type 036 type 048 type 056 type 018 type 024 type 027 type 036 type 048 type 072 type 096 type 015 type 018 type 024 type 027 type 036 type 048 type 007 type 009 type 012 type 015 type 018 type 024 type 007 type 009 type 012 type 015 type 018 type 024 type 007 type 009 type 012 type 015 type 018 type 024 type 015 type 018 type 024 type 027 type 036 type 048 type 056 type 1 1.25 1.7 2 2.5 3 3.2 4 5 6 0.8 1 1.25 1.7 2 2.5 3 3.2 5 0.8 1 1.25 1.7 2 2.5 0.8 1 1.25 1.7 2 2.5 3 3.2 4 5 6 2 2.5 3 4 5 8 10 1.7 2 2.5 3 4 5 0.8 1 1.25 1.7 2 2.5 0.8 1 1.25 1.7 2 2.5 0.8 1 1.25 1.7 2 2.5 1.7 2 2.5 3 4 5 6 Cooling capacity (kW) 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 14.0 2.2 2.8 3.6 4.5 5.6 7.1 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 5.6 7.1 8.0 11.2 14.0 22.4 28.0 4.5 5.6 7.1 8.0 11.2 14.0 2.2 2.8 3.6 4.5 5.6 7.1 2.2 2.8 3.6 4.5 5.6 7.1 2.2 2.8 3.6 4.5 5.6 7.1 4.5 5.6 7.1 8.0 11.2 14.0 16.0 Heating capacity (kW) 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 16.0 2.5 3.2 4.0 5.0 6.3 8.0 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 6.3 8.0 9.0 12.5 16.0 25.0 31.5 5.0 6.3 8.0 9.0 12.5 16.0 2.5 3.2 4.0 5.0 6.3 8.0 2.5 3.2 4.0 5.0 6.3 8.0 2.5 3.2 4.0 5.0 6.3 8.0 5.0 6.3 8.0 9.0 12.5 16.0 18.0

4-way Air Discharge Cassette Type

2-way Air Discharge Cassette Type

1-way Air Discharge Cassette Type

Concealed Duct Standard Type

Concealed Duct High Static Pressure Type

Under Ceiling Type

High Wall Type

Floor Standing Cabinet Type

Floor Standing Concealed Type

Floor Standing Type

10

5. Remote controller
Name Model name Appearance Application Function

CODE No.
SET DATA

UNIT No.
SETTING TEST
R.C. No.

UNIT
SET
CL

Start / Stop Changing mode Temperature setting Air flow changing Timer function c Either ON time or OFF time or CYCLIC can be set how many 30 min. later ON or OFF is operated. d Combined with the weekly timer, weekly schedule operation can be operated. Filter sign Displays automatically maintenance time of indoor filter. Filter sign flashes. Wired remote Wired remote controller Self-diagnosis function controller (In case of control by 2 remote controllers) Pressing CHECK button displays cause of trouble on the check code. Control by 2 remote controllers is available. Two remote controllers can be connected to one indoor unit. The indoor unit can be separately operated from the isolated places. Connected to indoor unit Start / Stop Temperature setting Air flow changing Check code display

Wired remote controller

RBC-AMT21E

Connected to indoor unit

Simple remote controller

RBC-AS21E

TEST
SETTING

C F

Simple remote controller

Wireless remote controller kit

TCB-AX21U (W)-E

Connected to indoor unit

RBC-AX22CE

Start / Stop Changing mode Temperature setting Air flow changing Timer function Either ON time or OFF time or CYCLIC can be set how many 30 min. later ON or OFF is operated. Control by 2 remote controllers is available. Two wireless remote controllers can operate one indoor unit. The indoor unit can be separately operated from the isolated places. Check code display TCB-AX21U (W)-E (For 4-way Air Discharge Cassette) RBC-AX22CE (For Under Ceiling)

TCB-AX21E

TCB-AX21E (For others except concealed duct high static pressure)

11

Name

Model name

Appearance

Application

Performance Weekly schedule operation

Connected to central remote controller, wired remote controller

c Setting different start / stop time for


each day of the week a day.

d ON / OFF can be easily set 3 times


ON OFF ON OFF ON OFF

8:00

12:00 13:00 18:00 19:00 21:00

RBC-EXW21E

Weekly timer

SuMoTuWeTh Fr Sa
PROGRAM1 PROGRAM2 PROGRAM3
ERROR

Wired remote controller

Weekly timer

e CHECK

PROGRAM DAY button make setting copy easy. week can be specified. (Summer schedule and winter schedule, etc.) holiday setting easy.

f Two patterns of schedule for a


Outdoor unit

WEEKLY TIMER

g CANCEL DAY button make h If power supply fails, the setting


contents are stored in memory, for 100 hours.

Central remote controller

Weekly timer

Individual control up to 64 indoor units. Connected to outdoor unit, indoor unit


Header Follower

Individual control for max. 64 indoor units divided 1 to 4 zone. Up to 16 indoor units for each zone Up to 16 outdoor header units are connectable.

Central remote controller

TCB-SC642TLE

ZONE ALL ZONE GROUP

4 type central control setting to inhibit individual operation by remote controller can be selected.
CODE No.

Outdoor unit

1234
SET DATA SETTING

UNIT No. No.

TEST

Setting for one of 1 to 4 zone is available. Usable with other central control devices (Up to 10 central control devices in one control circuit) Two control mode selectivity Central controller mode Remote controller mode Setting of simultaneous ON/OFF 3 times for each day of the week combined with weekly timer.

R.C.

GROUP SELECT ZONE

Central remote controller

CL

SET

Central remote controller

Indoor remote controller

12

3. BASIC SYSTEM CONFIGURATION


System legend (ex.)
Max. indoor unit : 13 units Capacity code of indoor unit : Min. : 4 Max. : 10.8 Capacity code Total 10.4 No. of total units 13

Outdoor unit 8HP Capacity code over the branch (0.8 + 0.8 = 1.6) Indoor unit designation 10.4 4.8
007 (0.8)

4.0
007 (0.8)

3.2
007 (0.8)

2.4
007 (0.8)

1.6
007 (0.8) 007

Capacity code
(0.8)

5.6 Indoor unit 007


(0.8) Remote controller

4.8
007 (0.8)

4.0
007 (0.8)

3.2
007 (0.8)

2.4
007 (0.8)

1.6
007 (0.8)

0.8
007 (0.8)

13

10 HP system
Max. indoor unit : 16 units Capacity code of indoor unit : Min. : 5 Max. : 13.5

Capacity code Total 12.8 No. of total units 16

Outdoor unit 10HP

12.8

6.4
007 (0.8)

5.6
007 (0.8)

4.8
007 (0.8)

4.0
007 (0.8)

3.2
007 (0.8)

2.4
007 (0.8)

1.6
007 (0.8) 007 (0.8)

6.4 Indoor unit 007 Remote controller


(0.8)

5.6
007 (0.8)

4.8
007 (0.8)

4.0
007 (0.8)

3.2
007 (0.8)

2.4
007 (0.8)

1.6
007 (0.8) 007 (0.8)

14

20 HP system
Max. indoor unit : 33 units Capacity code of indoor unit : Min. : 10 Max. : 27

Capacity code Total 26.75 No. of total units 19

Outdoor unit 10HP 10HP

10 26.75 10.25
018 (2.0)

8.25
018 (2.0)

6.25
012 (1.25)

5.0
012

3.75
012 (1.25)

2.5
012 (1.25) 012 (1.25)

(1.25)

16.5

8.25
018 (2.0)

6.25
012 (1.25)

5.0
012

3.75
012 (1.25)

2.5
012 (1.25) 012 (1.25)

(1.25)

8.25 Indoor unit 018 Remote controller


(2.0)

6.25
012 (1.25)

5.0
012

3.75
012 (1.25)

2.5
012 (1.25) 012 (1.25)

(1.25)

15

30 HP system
Max. indoor unit : 48 units Capacity code of indoor unit : Min. : 15 Max. : 40.5

Capacity code Total 40 No. of total units 28

Outdoor unit 10HP 10HP 10HP

20 40 10
007 (0.8)

10 9.2
007 (0.8)

8.4
007 (0.8)

7.6
007 (0.8)

6.8
007 (0.8)

6
018 (2) 036 (4)

30

10
007 (0.8)

9.2
007 (0.8)

8.4
007 (0.8)

7.6
007 (0.8)

6.8
007 (0.8)

6
018 (2) 036 (4)

20

10
007 (0.8)

9.2
007 (0.8)

8.4
007 (0.8)

7.6
007 (0.8)

6.8
007 (0.8)

6
018 (2) 036 (4)

10 Indoor unit 007 Remote controller


(0.8)

9.2
007 (0.8)

8.4
007 (0.8)

7.6
007 (0.8)

6.8
007 (0.8)

6
018 (2) 036 (4)

16

40 HP system
Max. indoor unit : 48 units Capacity code of indoor unit : Min. : 20 Max. : 54

Capacity code Total 53.75 No. of total units 32

Outdoor unit 10HP 10HP 10HP 10HP

30 53.75 14.0
009 (1)

20

10 12.0
009 (1)

13.0
009 (1)

11.0
012

9.75
012 (1.25)

8.5
018 (2.0)

6.5
024 (2.5) 036 (4)

(1.25)

39.75

13.25
009

12.25
009

11.25
009

10.25
012 (1.25)

9.0
012

7.75
012 (1.25)

6.5
024 (2.5) 036 (4)

(1)

(1)

(1)

(1.25)

26.5

13.25
009

12.25
009

11.25
009

10.25
012 (1.25)

9.0
012

7.75
012 (1.25)

6.5
024 (2.5) 036 (4)

(1)

(1)

(1)

(1.25)

13.25 Indoor unit 009 Remote controller

12.25
009

11.25
009

10.25
012 (1.25)

9.0
012

7.75
012 (1.25)

6.5
024 (2.5) 036 (4)

(1)

(1)

(1)

(1.25)

17

System legend (ex.)


Max. indoor unit : 48 units Capacity code of indoor unit : Min. : 24 Max. : 64.8

Capacity code Total 61.9 No. of total units 40

Outdoor unit 12HP 12HP 12HP 12HP

36 61.9 16.55 15.75


007 (0.8)

24

12 9.25
018 (2)

14.5 13.25 12.25 11.25


012 (1.25) 009 (1.0) 009 (1.0) 018

7.25
018 (2)

5.25
012 (1.25) 036 (4)

012 (1.25)

(2)

45.35

16.3
007

15.5 14.25 13.25 12.25 11.25


012 (1.25) 009 (1.0) 009 (1.0) 009 (1.0) 018

9.25
018

7.25
018

5.25
012 (1.25) 036 (4)

(0.8)

(2.0)

(2.0)

(2.0)

29.05

14.3
007

13.5 12.25 11.25 10.25


012 (1.25) 009 (1.0) 009 (1.0) 009

9.25
018

7.25
018

5.25
018

3.25
012 (1.25) 018 (2.0)

(0.8)

(1.0)

(2.0)

(2.0)

(2.0)

14.75 Indoor unit 012 Remote controller

13.5 12.25 11.25 10.25


012 (1.25) 009 (1.0) 009 (1.0) 009

9.25
018

7.25
018

5.25
018

3.25
012 (1.25) 018 (2.0)

(1.25)

(1.0)

(2.0)

(2.0)

(2.0)

18

4. EQUIPMENT SELECTION PROCEDURE


1. Selection flow chart
1. Determination of indoor air conditioning load 2. Preliminary selection of indoor units 3. Preliminary selection of outdoor unit with indoor units 4. Capacity correction for piping length/height between indoor and outdoor units 5. Capacity correction based on indoor and outdoor temperature 6. Validate preliminary selection of indoor units 7. Confirmation of selection for indoor unit and outdoor units NO

End

2. Combination conditions for indoor unit and outdoor unit


1. For indoor unit, the capacity code is decided for each capacity rank.
Capacity rank type Capacity code 007 0.8 009 1 012 1.25 015 1.7 018 2 024 2.5 027 3 030 3.2 036 4 048 5 056 6 072 8 096 10

NOTE :
Capacity rank : Correspondence to Btu/h. Capacity code : Correspondence to Horsepower.

2. For outdoor unit, maximum No. of connectable indoor units and total capacity code of indoor units are decided.
Outdoor unit (Cooling only) MMY-MAP0501T8 MMY-MAP0601T8 MMY-MAP0801T8 MMY-MAP1001T8 MMY-MAP1201T8 MMY-AP1401T8 MMY-AP1601T8 MMY-AP1801T8 MMY-AP2001T8 MMY-AP2201T8 MMY-AP2211T8 MMY-AP2401T8 MMY-AP2411T8 MMY-AP2601T8 MMY-AP2801T8 MMY-AP3001T8 MMY-AP3201T8 MMY-AP3211T8 MMY-AP3401T8 MMY-AP3411T8 MMY-AP3601T8 MMY-AP3611T8 MMY-AP3801T8 MMY-AP4001T8 MMY-AP4201T8 MMY-AP4401T8 MMY-AP4601T8 MMY-AP4801T8 Outdoor unit (Heat pump) MMY-MAP0501HT8 MMY-MAP0601HT8 MMY-MAP0801HT8 MMY-MAP1001HT8 MMY-MAP1201HT8 MMY-AP1401HT8 MMY-AP1601HT8 MMY-AP1801HT8 MMY-AP2001HT8 MMY-AP2201HT8 MMY-AP2211HT8 MMY-AP2401HT8 MMY-AP2411HT8 MMY-AP2601HT8 MMY-AP2801HT8 MMY-AP3001HT8 MMY-AP3201HT8 MMY-AP3211HT8 MMY-AP3401HT8 MMY-AP3411HT8 MMY-AP3601HT8 MMY-AP3611HT8 MMY-AP3801HT8 MMY-AP4001HT8 MMY-AP4201HT8 MMY-AP4401HT8 MMY-AP4601HT8 MMY-AP4801HT8 Outdoor unit (Heat pump) MMY-MAP0501HT7 MMY-MAP0601HT7 MMY-MAP0801HT7 MMY-MAP1001HT7 MMY-MAP1201HT7 MMY-AP1401HT7 MMY-AP1601HT7 MMY-AP1801HT7 MMY-AP2001HT7 MMY-AP2201HT7 MMY-AP2211HT7 MMY-AP2401HT7 MMY-AP2411HT7 MMY-AP2601HT7 MMY-AP2801HT7 MMY-AP3001HT7 MMY-AP3201HT7 MMY-AP3211HT7 MMY-AP3401HT7 MMY-AP3411HT7 MMY-AP3601HT7 MMY-AP3611HT7 MMY-AP3801HT7 MMY-AP4001HT7 MMY-AP4201HT7 MMY-AP4401HT7 MMY-AP4601HT7 MMY-AP4801HT7 Capacity code of outdoor unit 5 6 8 10 12 14 16 18 20 22 22 24 24 26 28 30 32 32 34 34 36 36 38 40 42 44 46 48 Max. No. of indoor units 8 10 13 16 20 23 27 30 33 37 37 40 40 43 47 48 48 48 48 48 48 48 48 48 48 48 48 48 Total capacity code of indoor units 2.5 to 6.75 3 to 8.1 4 to 10.8 5 to 13.5 6 to 16.2 7 to 18.9 8 to 21.6 9 to 24.3 10 to 27.0 11 to 29.7 11 to 29.7 12 to 32.4 12 to 32.4 13 to 35.1 14 to 37.8 15 to 40.5 16 to 43.2 16 to 43.2 17 to 45.9 17 to 45.9 18 to 48.6 18 to 48.6 19 to 51.3 20 to 54.0 21 to 56.7 22 to 59.4 23 to 62.1 24 to 64.8

50 to 135 % of outdoor unit capacity

19

3. Cooling/heating capacity characteristics


1. Cooling capacity calculation method : Required cooling capacity = Cooling capacity x Factor (c, d, e, f, g*1) kW

Indoor air wet bulb temperature vs. capacity correction value

Capacity correction value

1.2 1.1 1.0 0.9 0.8 15 20 24

Indoor air wet bulb temp. (C)

Outdoor air dry bulb temperature vs.capacity correction value

Capacity correction value

1.2 1.1 1.0 0.9 5 0 5 10 15 20 25 30 35 40 43

Outdoor air dry bulb temp. (C)

Air flow variation ratio of indoor unit vs. capacity correction (For concealed duct type only)

Capacity correction value

1.1

1.0

0.9 80 90 100 110 120

Air flow variation ratio (%)

*1 : Coefficient to use for correction of outdoor unit capacity when total capacity of the indoor units are not equal to the outdoor unit capacity.
20

Connecting pipe length and lift difference between indoor and outdoor units vs. capacity correction value

Height of outdoor unit H (m)

50 40 30 20 10 0 10 20 30 40

Outdoor unit (5 to 44HP)

%100 98 96

94

92

90

88

86

84

82

80

78

76

0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170

Pipe length (Equivalent length) L (m)


Outdoor unit

Height of outdoor unit H (m)

50 40 30 20 10 0 10 20 30 40

Outdoor unit (46 to 48HP)


ho
100% 98 96 94 92

lo

L is the longest one of (lo + la, lo + lb, lo + lc) H = ho + (Largest one of ha, hb, and hc)

90

88

86

84

82

80

78

76

74

72

hc

hb

ha

75

la lb lc

A B Indoor unit C

0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160

Pipe length (Equivalent length) L (m)

Correction of outdoor unit diversity


120

Correction (%)

100 80 60 40 20 0 20 40 60 80 100 120 135

Standard capacity ratio Indoor units total capacity ratio (%)

21

2. Heating capacity calculation method : Required heating capacity = Heating capacity x Factor (c, d, e, f, g*1, h*2) kW

Indoor air dry bulb temperature vs. capacity correction value

Capacity correction value

1.2 1.1 1.0 0.9 0.8 15

20

24

Indoor air dry bulb temp. (C)

Outdoor air wet bulb temperature vs. capacity correction value

Capacity correction value

1.2 1.1 1.0 0.9 0.8 0.7 0.6 0.5 15 10 5 0 5 10 15

Outdoor air wet bulb temp. (C)

Air flow variation ratio of indoor unit vs. capacity correction (For concealed duct type only)

Capacity correction value

1.1

1.0

0.9 80

90

100

110

120

Air flow variation ratio (%)

*1 : Coefficient to use for correction of outdoor unit capacity when total capacity of the indoor units are not equal to the outdoor unit capacity. *2 : Refer to item 3 in page 24.
22

Connecting pipe length and lift difference between indoor and outdoor units vs. capacity correction value

Height of outdoor unit H (m)

50 40 30 20 10 0 10 20 30 40

Outdoor unit (5 to 48HP)

100% 99

98

97

96

95

94

93

92

91

90

0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170

Pipe length (Equivalent length) L (m)


Outdoor unit L is the longest one of (lo + la, lo + lb, lo + lc) H = ho + (Largest one of ha, hb, and hc) ha

ho

lo

hc

hb

la lb lc

A B Indoor unit C

Correction of outdoor unit diversity

120

Correction (%)

100 80 60 40 20 0 20 40 60 80 100 120 135

Standard capacity ratio Indoor units total capacity ratio (%)

23

89

3. Capacity correction in case of frost on the outdoor heat exchanger in heating


Correct the heating capacity when frost was found on the outdoor heat exchanger. Heating capacity = Capacity after correction of outdoor unit Correction value of capacity resulted from frost (Capacity after correction of outdoor unit : Heating capacity calculated in the above item 2.)
6 Capacity correction in case of frost on the outdoor heat exchanger
Capacity correction value
1.0

0.9

0.8 15

10

10

Outdoor air wet bulb temp. (C)

4. Capacity calculation for each indoor unit


Capacity for each indoor unit = Capacity after correction of outdoor unit Required standard capacity of indoor unit Total value of standard indoor unit capacity

5. Operating temperature range


In cooling time
45 40 35 30
Usable range (in pull down)

In heating time
20 15 10 5 0 5 10 15 20

25 20 15 10 5 0 5 10 10 15

Usable range (in warming-up)

Continuously operable range

Outdoor air wet bulb temp. (C)

Outdoor air dry bulb temp. (C)

Continuously operable range

20

25

28

30

10

15

20

25

30

Indoor air wet bulb temp. (C)

Indoor air dry bulb temp. (C)

6. Rated conditions
Cooling : Indoor air temperature 27C DB/19.0C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

* The unit can be operated even if outdoor temperature


gets down to 20C, however note that the warranty covers only up to 15C because operation beyond that temperature is out of specification. When outdoor air temperature falls to under 15C, it may cause shortening the product lifetime.

24

4. Example of equipment selection


The following shows an example of equipment selection based upon a building model Fig. 1 Overview of building model
<Outside view> <Stories configuration>

41 42 43 44 45

Small meeting room Executive rooms

4F 3F 2F
7. 2m

14m

Office rooms (Entire floor)

1F
14.4m

21

22

23

Office rooms

11

14

Stores Steel frame, reinforced concrete building, four stories 13 12 above ground. Total floor area : 415m Outdoor unit is installed on the roof. Non-air conditioning zone Design indoor conditions Cooling : 27.0/19.0C DB/WB, Heating : 20C DB Design outdoor conditions Cooling : 35C DB (Standard condition), Heating : 3C WB (Standard condition : 6C WB)

+ Selection Criteria for Each Floor


1F : Outdoor capacity exactly matches the total indoor capacity.
Total indoor HP = Outdoor unit HP Indoor : 2.5 HP x 2 units + 3.2 HP + 2 HP = 10.2 HP Outdoor : 10 HP Same capacity

2F : Outdoor capacity matches the potential total indoor capacity in consideration of future extension.
The office rooms 2 and 3 are to be used as warehouses at first, so air conditioner is not necessary now. However, there is a plan to convert them into offices, so an outdoor module with bigger capacity is required. Piping/wiring are carried out. Indoor unit is not yet installed. When the room is used as an office room, the indoor unit is installed.

3F : One indoor unit is connected to one outdoor unit.


The outdoor module should have sufficient capacity to cover the peak demand of the indoor unit connected.

4F : Consider the diversity factor and have the outdoor module match 135% of indoor unit capacity.
This is a typical matching of indoor/outdoor units for Super MMS system. Total indoor units HP > Outdoor unit HP Select each indoor unit based on individual peak room load. Indoor : 2.5 HP + 2.5 HP + 2 HP +2 HP (Capacity difference in each room) + 1.3 HP = 10.3 HP (Different capacity) Outdoor : 8 HP (Different capacity) Consideration for cooling load profile is required.

25

Procedure and result of equipment selection


1. Procedure of equipment selection
a. Calculate cooling for every rooms. b. Select an indoor unit to match the cooling load for every room from the table in page 10. c. Select the outdoor module to match the indoor units selected in item b. Select the outdoor modules based on the critials and the combination rule. Choose a tentative outdoor module that will match with the indoor units, and check whether the selection agrees with the combination rule. Peform capacity correction based on the pipe length, system lift, indoor set temperature, outdoor temperature. Then, make sure the corrected system cooling capacity satisfies the cooling load.

2. Equipment selection and capacity check


Air conditioning load Indoor air conditioning load (kW) Cooling 4-1 4-2 4F 4-3 4-4 4-5 3F 3-1 2-1 2F 2-2 2-3 1-1 1F 1-2 1-3 1-4 6.0 (16 oclock) 5.2 (14 oclock) 5.0 (14 oclock) 3.2 (12 oclock) 6.4 (10 oclock) 12.7 4.8 4.6 6.5 6.5 7.2 5.1 Heating 5.4 4.2 4.2 2.7 5.4 12.0 4.5 4.8 6.0 6.3 7.0 4.5 Indoor unit Model MMUAP0241H AP0181H AP0181H AP0121H AP0241H AP0481H AP0181H AP0181H AP0241H AP0241H AP0301H AP0181H Capacity (kW) Cooling 7.1 5.6 5.6 3.6 7.1 14.0 5.6 5.6 7.1 7.1 9.0 5.6 Heating 8.0 6.3 6.3 4.0 8.0 16.0 6.3 6.3 8.0 8.0 10.0 6.3 AP2801HT7 78.5 88.0 AP2801HT8 Model MMYEquipment selection Outdoor unit Capacity (kW) Cooling Heating

Floor

Room No.

Note 1) ( ) : Peak occurrence time


Piping distance Equivalent length (m) Height difference (m) Capacity correction Pipe correction x temp. correction Cooling 4-1 4-2 4F 4-3 4-4 4-5 3F 3-1 2-1 2F 2-2 2-3 1-1 1F 1-2 1-3 1-4 43 12 0.920 1.0 1.0 = 0.920 0.957 1.0 0.95 0.95 = 0.864 Heating Capacity check after correction Capacity Capacity (kW) Cooling 6.5 5.2 5.2 3.3 6.5 12.9 5.2 5.2 6.5 6.5 8.3 5.2 Heating 6.9 5.4 5.4 3.5 6.9 13.8 5.4 5.4 6.9 6.9 8.6 5.4 Good Judgment

Floor

Room No.

26

Example: Equipment selection based on system load profile


Since the five rooms on the 4th floor face different directions, their hourly cooling load profile will be also different. We select each indoor unit based on the individual room peak load. However, we need to use the total load profile on the 4th floor as a base to choose the outdoor module.

Load in each room


8

Total load in all rooms of 4th floor


22 20 18 16 14 12 10 8 6

41
Load (kW)
6 4 2 0 0 8 12 16 20 Hour

42
Load (kW)
6 4 2 0 0 8 12 16 20 Hour

Total Load (kW)

4 2

43
Load (kW)
6 4 2 0 0 8 12 16 20 Hour

0 0 8 12 16 20 Hour

44
Load (kW)
6 4 2 0 0 8 12 16 20 Hour

1. The total load on the 4th floor is calculated by adding the hourly cooling loads of the five rooms. 2. The maximum value of total load is used to select outdoor module.

45
Load (kW)
6 4 2 0 0 8 12 16 20 Hour

27

Schematic diagram
MMY-AP2801T8 MMY-AP2801HT8 MMY-AP2801HT7
10 10 8

Outdoor unit

1st branching joint

3rd branching joint

4th branching joint

5th branching joint

2nd branching joint


Indoor unit MMU-AP0241H Indoor unit MMU-AP0181H Indoor unit MMU-AP0181H Indoor unit MMU-AP0121H Indoor unit MMU-AP0241H

R 2nd branching joint 41

42

43

44

45

35 R
Indoor unit MMD-AP0481H

3rd branching joint 4th branching joint

Indoor unit MMU-AP0181H

Indoor unit MMU-AP0181H

No Air Conditioner

21

22 Branching header

23

Indoor unit MMU-AP0241H

Indoor unit MMU-AP0241H

Indoor unit MMU-AP0301H

Indoor unit MMU-AP0181H

11

12

13

14

28

5. REFRIGERANT PIPING DESIGN


1. Warnings on refrigerant leakage
Check of Concentration Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit. The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost non-existent. With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur). In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The concentration is as given below. Total amount of refrigerant (kg) Min. volume of the indoor unit installed room (m) Concentration limit (kg/m) The concentration limit of R410A which is used in multi air conditioners is 0.3kg/m.
Outdoor unit Very small room Small room Medium room Large room

Important
NOTE : 2
The standards for minimum room volume are as follows. (1) No partition (shaded portion)

(2) When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).
Outdoor unit Refrigerant piping Indoor unit

(3) If an indoor unit is installed in each partitioned room and the refrigerant tubing is interconnected, the smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object.
Refrigerant piping

Indoor unit

NOTE 1 :
If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as charged in each independent device.
Outdoor unit e.g., charged amount (15kg)

Mechanical ventilation device - Gas leak detector

NOTE 3 :
The minimum indoor floor area compared with the amount of refrigerant is roughly as follows: (When the ceiling is 2.7m high)
40 m 35 30 Min. indoor floor area 25 20 15 10 5 0 10 20 30 Total amount of refrigerant Range above the density limit of 0.3 kg/m (countermeasures needed) Range below the density limit of 0.3 kg/m (countermeasures not needed)

e.g., charged amount (10kg)

Room A Room B Room C Room D Room E Room F Indoor unit

For the amount of charge in this example: The possible amount of leaked refrigerant gas in rooms A, B and C is 10kg. The possible amount of leaked refrigerant gas in rooms D, E and F is 15kg.

kg

29

2. Free branching system


c Line branching system d Header branching system e Header branching system after line branching f Line branching system after header branching g Header branching system after header branching
The above five branching systems are available to dramatically increase the flexibility of refrigerant piping design.

Outdoor unit Branching joint

Line branching system


Indoor unit Remote controller

Outdoor unit

Header branching system


Indoor unit Remote controller

Branching header

Outdoor unit Branching joint

Header branching system after line branching

Branching header

Indoor unit Remote controller

Line branching system after header branching

Outdoor unit

Branching header

Header branching system after header branching

Branching joint Indoor unit Remote controller

30

3. Allowable length/height difference of refrigerant piping


D Follower unit 3 A Header unit Outdoor unit B Follower unit 1 C Follower unit 2 Connecting piping of outdoor unit Header unit

<Ex. 1>
Follower unit 1 Follower unit 2 Header unit

<Ex. 2>
Follower unit 1 Follower unit 2

Height difference between outdoor units H3 5 m

T-shape branching La joint LA

Lb LB

Lc

Ld

Main piping

Main connecting piping between outdoor units Length corresponded to farthest piping between outdoor units LO 25 m

NOTE : In case of connecting method <Ex. 2>, a large amount of refrigerant and refrigerant oil may return to the head unit. Therefore, set the T-shape joint so that oil does not enter directly.
Branching header

L1

Branching piping L2 Connecting piping of indoor unit a b

Height difference between outdoor units H1 50 m

1st branching section

L7 c d e

L3

Indoor unit Equivalent length corresponded to farthest piping L 175 m Equivalent length corresponded to farthest piping after 1st branching Li 65 m L4 f g L5 h Indoor unit L6 Height difference between indoor units H2 30 m j

Y-joint

System restrictions
Max. No. of combined outdoor units 4 units Note 1) Combination of outdoor units : Header unit (1 unit) + Follower units (0 to 3 units). Header unit is the outdoor unit nearest to the connected indoor units. Note 2) Install the outdoor units in order of capacity. (Header unit > Follower unit 1 > Follower unit 2 > Follower unit 3) Note 3) Refer to outdoor unit combination table in page 6. Note 4) Piping to indoor units shall be perpendicular to piping to the head outdoor unit as <Ex.1>. Do not connect piping to indoor units in the same direction of Head outdoor unit as <Ex.2>. Max. capacity of combined outdoor units 48 HP Max. No. of connected indoor units Max. capacity of combined H2 <15 indoor units H2 >15 48 units 135% 105%

Allowable length and height difference of refrigerant piping


Allowable value Total extension of pipe (Liquid pipe, real length) Farthest piping length L (*) Piping length Real length Equivalent length 300 m 150 m 175 m Piping section LA + LB + La + Lb + Lc + Ld + L1 + L2 + L3 + L4+ L5 + L6 + L7 + a + b + c + d + e + f + g + h + i + j LA + LB + Ld + L1 + L3 + L4 + L5 + L6 + j L3 + L4 + L5 + L6 + j LA + LB + Ld, Ld, (LA + Lb, LA + LB + Lc) L1 (La, Lb, Lc) a, b, c, d, e, f, g, h, i, j

Equivalent length of farthest piping from 1st branching Li ( ) Equivalent length of farthest piping between outdoor units LO ( ) Max. equivalent length of main piping (

65 m

25 m 85 m 10 m 30 m 50 m 40 m (**) 30 m 5m

***

Max. equivalent length of outdoor unit connecting piping Max. real length of indoor unit connecting piping Height between indoor and outdoor units H1 Upper outdoor unit Lower outdoor unit

Height difference Height between indoor units H2 Height between outdoor units H3

* (D) is outdoor unit farthest from 1st branching, and ( j ) is indoor unit farthest from 1st branching. ** If the height difference (H2) between indoor units exceeds 3m, set below 30m. *** If the maximum capacity of combination of the outdoor units is 46 HP or more, the maximum equivalent
length is restricted up to 70m.

31

4. Selection of refrigerant piping


Branching piping Follower unit 3 Follower unit 2 Follower unit 1 Header unit Outdoor unit

6 Header branching pipe

Indoor unit connecting piping

4 5 5 5

2 Balance pipe 6 T-shape 1 Outdoor unit


connecting piping Indoor unit

1 2

1 2

branching joint

6 Y-shape

3 Main piping 4
Main connecting piping between outdoor units

branching joint 4

1st branching Indoor unit section connecting piping

Indoor unit

c Pipe size of outdoor unit (Table 1)


Model name MAP0501T8 MAP0601T8 MAP0801T8 MAP1001T8 MAP1201T8 MMYMAP0501HT7 MAP0601HT7 MAP0801HT7 MAP1001HT7 MAP1201HT7 Gas side 15.9 19.1 22.2 22.2 28.6 Liquid side 9.5 9.5 12.7 12.7 12.7 MAP0501HT8 MAP0601HT8 MAP0801HT8 MAP1001HT8 MAP1201HT8

g Piping of indoor unit (Table 5)


Capacity rank 007 type to 012 type Real length 15m or less Real length exceeds 15m 015 type to 018 type 024 type to 056 type 072 type to 096 type Gas side 9.5 12.7 12.7 15.9 22.2 Liquid side 6.4 6.4 6.4 9.5 12.7

d Connecting pipe size between outdoor units (Table 2)


Total capacity code of outdoor units at downstream side 14 to below 22 22 to below 26 26 to below 36 36 or more Gas side 28.6 34.9 34.9 41.3 Liquid side 15.9 15.9 19.1 22.2 9.5 Balance pipe

h Selection of branching section (Table 6)


Total capacity code of indoor unit Below 6.4 Y-shape branching joint 2 6.4 to below 14.2 14.2 to below 25.2 25.2 or more Branching header For 4 branching For 8 branching Below 14.2 14.2 to below 25.2 Below 14.2 14.2 to below 25.2

*1

Model name RBM-BY53E RBM-BY103E RBM-BY203E RBM-BY303E RBM-HY1043E RBM-HY2043E RBM-HY1083E RBM-HY2083E

*
Liquid side 9.5 9.5 12.7 12.7 15.9 15.9 19.1 22.2

e Size of main pipe (Table 3)


Total capacity code of all outdoor units Below 6 6 to below 8 8 to below 12 12 to below 14 14 to below 22 22 to below 26 26 to below 36 36 to below 46 46 or more

Gas side 15.9 19.1 22.2 28.6 28.6 34.9 34.9 41.3 41.3

* 3

1 set of 3 types of T-shape joint pipes as described below: The required quantity is arranged and combined T-shape at the site. branching joint Balance pipe (For (Corresponded difference 9.52) 1 connecting Piping at liquid side outdoor unit) (Corresponded difference 9.5 to 22.1) 1 Piping at gas side (Corresponded difference 15.9 to 41.3) 1

RBM-BT13E

22.2

Determine thickness of the main pipe according to capacity of the outdoor units.

f Pipe size between branching sections (Table 4)


Total capacity code of indoor units at downstream side 1 2.8 or less 2.8 to below 6.4 6.4 to below 12.2 12.2 to below 20.2 20.2 to below 25.2 25.2 to below 35.2 35.2 or more

i Minimum wall thickness for R410A application


(Table 7)
OK OK OK OK OK OK Soft Half hard or hard OD (Inch) OD (mm) OK OK OK OK NG NG NG NG NG 1/4 3/8 1/2 5/8 3/4 7/8 1.1/8 1.3/8 1.5/8 6.35 9.52 12.70 15.88 19.05 22.20 28.58 34.92 41.28 Minimum wall thickness (mm) 0.80 0.80 0.80 1.00 1.00 1.00 1.00 1.10 1.25

Gas side 12.7 15.9 22.2 28.6 34.9 34.9 41.3

Liquid side 9.5 9.5 12.7 15.9 15.9 19.1 22.2

If the total capacity code value of indoor units exceeds that of outdoor units, apply the capacity code of outdoor units.

OK OK OK

*1 Code is determined according to the capacity rank. For details, refer to page 6 to page 9. *2 When using Y-shape branching joint for 1st branching, select according to capacity code of outdoor unit. *3 For 1 line after header branching, indoor units with a maximum of 6.0 capacity code in total can be connected. 4 If the pipe size is 19.0 or more, use a hard type or half hard type for material of the pipe. * 5 The maximum equivalent length of the main pipe should be 70m or shorter. *

32

5. Charging requirement with additional refrigerant


After the system has been vacuumed, replace the vacuum pump with a refrigerant cylinder and charge the system with additional refrigerant.

Calculating the amount of additional refrigerant required


Refrigerant in the system when shipped from the factory
5HP Refrigerant amount charged in factory Heat pump model Cooling only model 8.5kg 8.0kg 6HP 8.5kg 8.0kg 8HP 12.5kg 11.0kg 10HP 12.5kg 11.0kg

R410A
12HP 12.5kg 11.0kg

When the system is charged with refrigerant at the factory, the amount of refrigerant needed for the pipes at the site is not included. Calculate the additional amount needed, and add that amount to the system.

(Calculation) Additional refrigerant charge amount is calculated from size of liquid pipe at site and its real length.
Additional refrigerant charge amount at site = Real length of liquid pipe Additional refrigerant charge amount + Compensation by system HP (Table 2) per liquid pipe 1m (Table 1) Example : Additional charge amount R (kg) = (L1 x 0.025kg/m) + (L2 x 0.055kg/m) + (L3 x 0.105kg/m) + (3.0kg) L1 : Real total length of liquid pipe 6.4 (m) L2 : Real total length of liquid pipe 9.5 (m) L3 : Real total length of liquid pipe 12.7 (m)

Table 7-1
Pipe dia. at liquid side Additional refrigerant amount/1m 6.4 0.025kg 9.5 0.055kg 12.7 0.105kg 15.9 0.160kg 19.0 0.250kg 22.2 0.350kg

Table 7-2
Combined horse power (HP) 5 6 8 10 12 14 16 18 20 22 Outdoor combination (HP) 5 6 8 10 12 8 8 10 10 12 8 12 8 10 6 8 8 10 10 8 12 8 8 8 8 6 Compensation by system HP (kg) 0.0 0.0 1.5 2.5 3.5 0.0 0.0 0.0 3.0 5.0 0.0 7.0 4.0 4.0 Combined horse power (HP) 28 30 32 Outdoor combination (HP) 10 10 12 8 12 10 12 10 10 10 12 12 12 12 10 10 10 8 12 8 12 10 10 10 10 12 12 12 8 10 10 8 10 8 12 8 10 10 10 10 12 12 8 8 10 10 10 10 12 8 8 Compensation by system HP (kg) 2.0 0.0 1.0 6.0 3.0 6.0 4.0 6.0 6.0 5.0 4.0 2.0 0.0 2.0

34

36 38 40 42 44 46 48

24 26

33

6. WIRING DESIGN
1. General
(1) Perform wiring of the power supply in conformance with the regulations of the local electric company. (2) For the control wires connecting indoor units, outdoor units, and between indoor and outdoor units, use of double-core shield wires is recommended to prevent noise trouble. (3) Be sure to set the earth leakage breaker and the switches to the power supply section of the indoor unit. (4) Supply power to each outdoor unit and provide an earth leakage breaker or hand switch for each outdoor unit. (5) Never connect the 220240V power to the terminal block (U1, U2, U3, U4, U5, U6) for control cables. (Trouble is caused.) (6) Store wiring system for control and refrigerant piping system in the same line. (7) Arrange the cables so that the electric wires do not come to contact with high-temperature part of the pipe ; otherwise coating melts and an accident may be caused. (8) Do not turn on power of the indoor unit until vacuuming of the refrigerant pipe will finish.

2. For outdoor unit power supply


Select the power supply cabling and fuse of each outdoor unit from the following specifications: Cable 5-core, in conformance with Design 60245 IEC 66 Do not connect the outdoor units by crossing outside of them, but connect them via the incorporated terminal block (L1, L2, L3, N).
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N

Outdoor power supply 3-phase 380V415, 50Hz 380V, 41560Hz

3. Electrical wiring design


3-phase 50Hz 380-415V Earth or 60Hz 380V Earth leakage breaker hand switch Outdoor power source Indoor power source Single phase 50Hz 220-240V or 60Hz 220V Earth leakage breaker power switch
Model MMY-AP T8, HT8 MMY-AP HT7 Outdoor power supply 3phase, 380415 V, 50Hz 3phase, 380 V, 60Hz

Pull box

Unit capacities and power supply wire sizes (Reference)

Model MMYMAP0501T8 MAP0601T8 MAP0801T8 MAP1001T8 MAP1201T8 MAP0501HT8 MAP0601HT8 MAP0801HT8 MAP1001HT8 MAP1201HT8 MAP0501HT7 MAP0601HT7 MAP0801HT7 MAP1001HT7 MAP1201HT7

Power supply wiring Wire size 3.5 mm (AWG #12) Max. 26 m 3.5 mm (AWG #12) Max. 26 m 3.5 mm (AWG #10) Max. 20 m 5.5 mm (AWG #10) Max. 28 m 5.5 mm (AWG #10) Max. 27 m

Field fuse 20 A 20 A 30 A 30 A 30 A

Determine the wire size for indoor unit according to the number of connected indoor units downstream. Observe local regulation regarding wire size selection and installation.

34

4. For Indoor unit power supply (Must be independent from outdoor unit power.)
Item Model All models of indoor units 2.0mm (AWG#14) Max. 20m Power supply wiring Wire size 3.5mm (AWG#12) Max. 50m Field fuse 15A

NOTE :
The connecting length indicated in the table represents the length from the pull box to the outdoor unit when the indoor units are connected in parallel for power, as shown in the above illustration. A voltage drop of no more than 2% is also assumed. If the connecting length will exceed the length indicated in the table, select the wire thickness in accordance with local wiring standards.

CAUTIONS
(1) Keep the refrigerant piping system and the indoor-indoor/indoor-outdoor control wiring systems together. (2) When running power wires and control wires parallel to each other, either run them through separate conduits, or maintain a suitable distance between them. (Current capacity of power wires: 10A or less for 300m, 50A or less for 500m)

5. Design of control wiring


Power supply Single phase 220-240V 50Hz 220V~60Hz

(Open) Earth

[Central remote controller] (Option) TCB-SC642TLE (For Line 64)

Transmission wire for control Connection of shield wire must be connected between outdoor units (Connected to all connecting sections in each outdoor unit) Transmission wire for control Connection of shield wire must be connected between outdoor unit and (Connected to all connecting sections in each indoor unit) indoor unit

Standard remote controller

Wire specification, quantity, size of crossover wiring and remote controller wiring
Name Crossover wiring (indoor-indoor / indoor-outdoor / outdoor-outdoor control wiring, central control wiring) Remote controller wiring Qty 2 cores 2 cores Up to 500m Size Up to 1000m 1000 to 2000m 2.0mm2 Specification Shield wire

1.25mm2 0.5 to 2.0mm2

(1) The crossover wiring and central control wiring use 2-core non-polarity transmission wires. Use 2-core shield wires to prevent noise trouble. In this case, close (connect) the end of shield wires, and perform the functional grounding for the end of the shield wires which are connected to both indoor and outdoor units. For the shield wires which are connected between the central remote controller and the outdoor unit, perform the functional grounding at only one end of central control wiring. (2) Use 2-core and non-polarity wire for remote controller. (A, B terminals) Use 2-core and non-polarity wire for wiring of group control. (A, B terminals)

35

6. Control wiring Diagram


1. All control wiring is 2-core and non-polarity wire. 2. Be sure to use shield wire for the following wiring to prevent noise trouble. Outdoor-outdoor / indoor-indoor / outdoor-indoor control wiring, Central control wiring.

Central control device U1 U2 U3 U4

Super modular multi system L4 Follower unit


U3 U4 U1 U2 U5 U6

Table-1 Follower unit


U3 U4 U1 U2 U5 U6

Header unit
U3 U4

Header unit
U3 U4 U1 U2 U5 U6

Follower unit
U3 U4 U1 U2 U5 U6

Header unit
U3 U4 U1 U2 U5 U6

Follower unit
U3 U4

Outdoor unit
U1 U2 U5 U6 U1 U2 U5 U6

L1

L5

Table-1

Table-2

L2
U1 U2 U1 U2 A B U1 U2 A B U1 U2 A B U1 U2 A B U1 U2 A B

L3
U1 U2 A B U1 U2 A B

Indoor unit

A B

Table-3 Remote controller

L7 Remote controller

L6

Remote controller

Table-1 Control wiring between indoor and outdoor units (L1, L2, L3), Central control wiring (L4)
Wiring Type Size Length 2-core, non-polarity Shield wire 1.25 mm : Up to 1000 m 2.0 mm : Up to 2000 m (*1)

Note (*1) : Total of control wiring length for all refrigerant circuits ( L1 + L2 + L3 + L4 )

Table-2 Control wiring between outdoor units (L5)


Wiring Type Size Length 2-core, non-polarity Shield wire 1.25 mm to 2.0 mm Up to 100 m (L5)

Table-3 Remote controller wiring (L6, L7)


Wire Size Length 2-core 0.5 mm to 2.0 mm Up to 500 m ( L6 + L7 ) Up 400m in case of wireless remote controller in group control. Up to 200m total length of control wiring between indoor units ( L6 )

36

7. Design
Type Model MMU-AP0091H MMU-AP0121H MMU-AP0151H MMU-AP0181H MMU-AP0241H MMU-AP0271H MMU-AP0301H MMU-AP0361H MMU-AP0481H MMU-AP0561H MMU-AP0071WH MMU-AP0091WH MMU-AP0121WH MMU-AP0151WH MMU-AP0181WH MMU-AP0241WH MMU-AP0271WH MMU-AP0301WH MMU-AP0481WH MMU-AP0071YH MMU-AP0091YH MMU-AP0121YH MMU-AP0151SH MMU-AP0181SH MMU-AP0241SH MMD-AP0071BH MMD-AP0091BH MMD-AP0121BH MMD-AP0151BH MMD-AP0181BH MMD-AP0241BH MMD-AP0271BH MMD-AP0301BH MMD-AP0361BH MMD-AP0481BH MMD-AP0561BH MMD-AP0181H MMD-AP0241H MMD-AP0271H MMD-AP0361H MMD-AP0481H MMD-AP0721H MMD-AP0961H MMC-AP0151H MMC-AP0181H MMC-AP0241H MMC-AP0271H MMC-AP0361H MMC-AP0481H MMK-AP0071H MMK-AP0091H MMK-AP0121H MMK-AP0151H MMK-AP0181H MMK-AP0241H MML-AP0071H MML-AP0091H MML-AP0121H MML-AP0151H MML-AP0181H MML-AP0241H MML-AP0071BH MML-AP0091BH MML-AP0121BH MML-AP0151BH MML-AP0181BH MML-AP0241BH MMF-AP0151H MMF-AP0181H MMF-AP0241H MMF-AP0271H MMF-AP0361H MMF-AP0481H MMF-AP0561H Nominal Voltage (V-Ph-Hz) 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 Voltage Range Min Max 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 198 264 Fan Motor kW FLA 0.060 0.20 0.060 0.20 0.060 0.22 0.060 0.24 0.060 0.28 0.060 0.28 0.060 0.40 0.090 0.68 0.090 0.93 0.090 0.95 0.053 0.36 0.053 0.36 0.053 0.36 0.039 0.37 0.039 0.37 0.053 0.53 0.053 0.53 0.053 0.54 0.092 1.33 0.022 0.28 0.022 0.28 0.022 0.28 0.034 0.55 0.034 0.55 0.034 0.63 0.120 0.33 0.120 0.33 0.120 0.39 0.120 0.39 0.120 0.50 0.120 0.60 0.120 0.60 0.120 0.70 0.120 0.96 0.120 1.13 0.120 1.13 0.160 0.93 0.160 1.55 0.160 1.55 0.260 1.87 0.260 2.12 0.370 3 6.04 0.370 3 6.35 0.030 0.33 0.030 0.37 0.040 0.48 0.040 0.48 0.080 0.90 0.080 0.96 0.030 0.35 0.030 0.35 0.030 0.35 0.030 0.37 0.030 0.37 0.030 0.40 0.045 0.30 0.045 0.30 0.045 0.49 0.045 0.49 0.070 0.54 0.070 0.54 0.019 0.29 0.019 0.29 0.019 0.29 0.070 0.52 0.070 0.52 0.070 0.53 0.037 0.77 0.037 0.77 0.063 1.01 0.063 1.01 0.110 1.48 0.160 1.84 0.160 1.84

50Hz
Power Supply MCA MOCP 0.25 15 0.25 15 0.28 15 0.30 15 0.35 15 0.35 15 0.50 15 0.85 15 1.16 15 1.19 15 0.45 15 0.45 15 0.45 15 0.46 15 0.46 15 0.66 15 0.66 15 0.68 15 1.67 15 0.35 15 0.35 15 0.35 15 0.69 15 0.69 15 0.79 15 0.41 15 0.41 15 0.49 15 0.49 15 0.62 15 0.75 15 0.75 15 0.88 15 1.20 15 1.41 15 1.41 15 1.16 15 1.94 15 1.94 15 2.34 15 2.65 15 7.55 15 7.94 15 0.41 15 0.46 15 0.60 15 0.60 15 1.13 15 1.20 15 0.44 15 0.44 15 0.44 15 0.46 15 0.46 15 0.50 15 0.37 15 0.37 15 0.62 15 0.62 15 0.68 15 0.68 15 0.36 15 0.36 15 0.36 15 0.65 15 0.65 15 0.66 15 0.96 15 0.96 15 1.27 15 1.27 15 1.85 15 2.30 15 2.30 15

4-way Air Discharge Cassette Type

2-way Air Discharge Cassette Type

1-way Air Discharge Cassette Type

Concealed Duct Type

Concealed Duct High Static Pressure Type

Under Ceiling Type

High Wall Type

Floor Standing Cabinet Type

Floor Standing Concealed Type

Floor Standing Type

Legend

MCA : Minimum Circuit Amps MOCP : Maximum Overcurrent Protection (Amps)

FLA kW

: Full Load Amps : Fan Motor Rated Output (kW)

37

60Hz
Type Model MMU-AP0091H MMU-AP0121H MMU-AP0151H MMU-AP0181H MMU-AP0241H MMU-AP0271H MMU-AP0301H MMU-AP0361H MMU-AP0481H MMU-AP0561H MMU-AP0071WH MMU-AP0091WH MMU-AP0121WH MMU-AP0151WH MMU-AP0181WH MMU-AP0241WH MMU-AP0271WH MMU-AP0301WH MMU-AP0071SH MMU-AP0091SH MMU-AP0121SH MMU-AP0151SH MMU-AP0181SH MMU-AP0241SH MMD-AP0071BH MMD-AP0091BH MMD-AP0121BH MMD-AP0151BH MMD-AP0181BH MMD-AP0241BH MMD-AP0271BH MMD-AP0301BH MMD-AP0361BH MMD-AP0481BH MMD-AP0561BH MMD-AP0181H MMD-AP0241H MMD-AP0271H MMD-AP0361H MMD-AP0481H MMD-AP0721H MMD-AP0961H MMC-AP0151H MMC-AP0181H MMC-AP0241H MMC-AP0271H MMC-AP0361H MMC-AP0481H MMK-AP0071H MMK-AP0091H MMK-AP0121H MMK-AP0151H MMK-AP0181H MMK-AP0241H MML-AP0071H MML-AP0091H MML-AP0121H MML-AP0151H MML-AP0181H MML-AP0241H MML-AP0071BH MML-AP0091BH MML-AP0121BH MML-AP0151BH MML-AP0181BH MML-AP0241BH MMF-AP0151H MMF-AP0181H MMF-AP0241H MMF-AP0271H MMF-AP0361H MMF-AP0481H MMF-AP0561H Nominal Voltage (V-Ph-Hz) 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 Voltage Range Min Max 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 198 242 Fan Motor kW FLA 0.060 0.21 0.060 0.21 0.060 0.23 0.060 0.25 0.060 0.29 0.060 0.29 0.060 0.42 0.090 0.70 0.090 0.98 0.090 1.00 0.053 0.38 0.053 0.38 0.053 0.38 0.039 0.44 0.039 0.44 0.053 0.61 0.053 0.61 0.053 0.67 0.022 0.30 0.022 0.30 0.022 0.30 0.034 0.62 0.034 0.62 0.034 0.70 0.120 0.35 0.120 0.35 0.120 0.41 0.120 0.41 0.120 0.52 0.120 0.63 0.120 0.63 0.120 0.73 0.120 1.00 0.120 1.18 0.120 1.18 0.160 1.06 0.160 2.07 0.160 2.07 0.260 2.38 0.260 2.60 0.370 3 8.17 0.370 3 8.53 0.030 0.35 0.030 0.39 0.040 0.50 0.040 0.50 0.080 0.94 0.080 1.00 0.030 0.37 0.030 0.37 0.030 0.37 0.030 0.39 0.030 0.39 0.030 0.40 0.045 0.29 0.045 0.29 0.045 0.51 0.045 0.51 0.070 0.61 0.070 0.61 0.019 0.31 0.019 0.31 0.019 0.31 0.070 0.53 0.070 0.53 0.070 0.59 0.037 0.77 0.037 0.77 0.063 1.04 0.063 1.04 0.110 1.58 0.160 2.01 0.160 2.01 Power Supply MCA MOCP 0.26 15 0.26 15 0.29 15 0.31 15 0.37 15 0.37 15 0.52 15 0.88 15 1.22 15 1.25 15 0.47 15 0.47 15 0.47 15 0.55 15 0.55 15 0.76 15 0.76 15 0.84 15 0.37 15 0.37 15 0.37 15 0.78 15 0.78 15 0.88 15 0.43 15 0.43 15 0.51 15 0.51 15 0.65 15 0.78 15 0.78 15 0.91 15 1.25 15 1.48 15 1.48 15 1.32 15 2.59 15 2.59 15 2.98 15 3.25 15 10.2 15 10.7 15 0.43 15 0.48 15 0.63 15 0.63 15 1.18 15 1.25 15 0.46 15 0.46 15 0.46 15 0.48 15 0.48 15 0.50 15 0.36 15 0.36 15 0.63 15 0.63 15 0.76 15 0.76 15 0.39 15 0.39 15 0.39 15 0.66 15 0.66 15 0.73 15 0.96 15 0.96 15 1.29 15 1.29 15 1.97 15 2.52 15 2.52 15

4-way Air Discharge Cassette Type

2-way Air Discharge Cassette Type

1-way Air Discharge Cassette Type

Concealed Duct Type

Concealed Duct High Static Pressure Type

Under Ceiling Type

High Wall Type

Floor Standing Cabinet Type

Floor Standing Concealed Type

Floor Standing Type

Legend

MCA : Minimum Circuit Amps MOCP : Maximum Overcurrent Protection (Amps)

FLA kW

: Full Load Amps : Fan Motor Rated Output (kW)

38

Single outdoor unit


Heat Pump Model MMYMAP0501HT8 MAP0601HT8 MAP0801HT8 MAP1001HT8 MAP1201HT8 Nominal Cooling Only model Voltage MMY(V-Ph-Hz) MAP0501T8 MAP0601T8 MAP0801T8 MAP1001T8 MAP1201T8 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 Voltage Range Min Max 342 457 342 457 342 457 342 457 342 457 Compressor RLA 4.0 + 4.0 4.6 + 4.6 5.2 + 5.2 6.5 + 6.5 9.5 + 9.5 LRA kW 0.60 0.60 0.60 0.60 0.60 Fan Motor FLA 0.8 0.8 1.0 1.1 1.1

50Hz
Power Supply MCA MOCP 16.5 20 16.5 20 20.0 30 22.5 30 24.5 30 ICF

Combination of outdoor unit


Heat Pump Model MMYAP1401HT8 AP1601HT8 AP1801HT8 AP2001HT8 AP2201HT8 AP2211HT8 AP2401HT8 AP2411HT8 AP2601HT8 AP2801HT8 AP3001HT8 AP3201HT8 AP3211HT8 AP3401HT8 AP3411HT8 AP3601HT8 AP3611HT8 AP3801HT8 AP4001HT8 AP4201HT8 AP4401HT8 AP4601HT8 AP4801HT8 Legend Nominal Cooling Only model Voltage MMY(V-Ph-Hz) AP1401T8 AP1601T8 AP1801T8 AP2001T8 AP2201T8 AP2211T8 AP2401T8 AP2411T8 AP2601T8 AP2801T8 AP3001T8 AP3201T8 AP3211T8 AP3401T8 AP3411T8 AP3601T8 AP3611T8 AP3801T8 AP4001T8 AP4201T8 AP4401T8 AP4601T8 AP4801T8 MCA MOCP ICF RLA 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 Voltage Range Min 342 342 342 342 342 342 342 342 342 342 342 342 342 342 342 342 342 342 342 342 342 342 342 Max 457 457 457 457 457 457 457 457 457 457 457 457 457 457 457 457 457 457 457 457 457 457 457 Unit No.1 RLA LRA 5.2 + 5.2 5.2 + 5.2 6.5 + 6.5 6.5 + 6.5 5.2 + 5.2 9.5 + 9.5 5.2 + 5.2 9.5 + 9.5 6.5 + 6.5 6.5 + 6.5 6.5 + 6.5 5.2 + 5.2 9.5 + 9.5 6.5 + 6.5 9.5 + 9.5 6.5 + 6.5 9.5 + 9.5 6.5 + 6.5 6.5 + 6.5 9.5 + 9.5 9.5 + 9.5 9.5 + 9.5 9.5 + 9.5 Compressor Unit No.2 Unit No.3 RLA LRA RLA LRA 4.6 + 4.6 5.2 + 5.2 5.2 + 5.2 6.5 + 6.5 5.2 + 5.2 4.6 + 4.6 6.5 + 6.5 5.2 + 5.2 5.2 + 5.2 9.5 + 9.5 5.2 + 5.2 5.2 + 5.2 6.5 + 6.5 5.2 + 5.2 6.5 + 6.5 6.5 + 6.5 5.2 + 5.2 5.2 + 5.2 6.5 + 6.5 6.5 + 6.5 5.2 + 5.2 5.2 + 5.2 9.5 + 9.5 6.5 + 6.5 6.5 + 6.5 5.2 + 5.2 9.5 + 9.5 9.5 + 9.5 6.5 + 9.5 6.5 + 6.5 6.5 + 6.5 6.5 + 6.5 6.5 + 6.5 6.5 + 6.5 9.5 + 9.5 6.5 + 6.5 9.5 + 9.5 9.5 + 9.5 9.5 + 9.5 9.5 + 9.5 LRA FLA kW Unit No.4 RLA LRA 5.2 + 5.2 5.2 + 5.2 5.2 + 5.2 5.2 + 5.2 6.5 + 6.5 6.5 + 6.5 6.5 + 6.5 6.5 + 6.5 9.5 + 9.5 Fan Motor kW 0.6 2 0.6 2 0.6 2 0.6 2 0.6 3 0.6 2 0.6 3 0.6 2 0.6 3 0.6 3 0.6 3 0.6 4 0.6 3 0.6 4 0.6 3 0.6 4 0.6 3 0.6 4 0.6 4 0.6 4 0.6 4 0.6 4 0.6 4 FLA 1.0 + 0.8 1.0 + 1.0 1.0 + 1.1 1.1 + 1.1 1.0 + 1.0 + 0.8 1.1 + 1.1 1.0 + 1.0 + 1.0 1.1 + 1.1 1.1 + 1.1 + 1.0 1.1 + 1.1 + 1.0 1.1 + 1.1 + 1.1 1.0 + 1.0 + 1.0 + 1.0 1.1 + 1.1 + 1.1 1.1 + 1.0 + 1.0 + 1.0 1.1 + 1.1 + 1.1 1.1 + 1.1 + 1.0 + 1.0 1.1 + 1.1 + 1.1 1.1 + 1.1 + 1.1 + 1.0 1.1 + 1.1 + 1.1 + 1.1 1.1 + 1.1 + 1.1 + 1.1 1.1 + 1.1 + 1.1 + 1.1 1.1 + 1.1 + 1.1 + 1.1 1.1 + 1.1 + 1.1 + 1.1 Power Supply MCA MOCP 36.5 40 40.0 50 42.5 50 45.0 60 56.5 70 47.0 60 60.0 70 49.0 60 62.5 70 65.0 80 67.5 80 80.0 90 69.5 80 82.5 100 71.5 80 85.0 100 73.5 90 87.5 100 90.0 100 92.0 110 94.0 110 96.0 110 98.0 110 ICF

39

: Minimum Circuit Amps : Maximum Overcurrent Protection (Amps) : Maximum Instantaneous Current Flow Start : Rated Load Amps

: Locked Rotor Amps : Full Load Amps : Fan Motor Rated Output (kW)

NOTE : RLA is based on the following conditions. Indoor temperature : 27C DB/19C WB Outdoor temperature : 35C DB

Single outdoor unit


Heat Pump Model MMYMAP0501HT7 MAP0601HT7 MAP0801HT7 MAP1001HT7 MAP1201HT7 Nominal Voltage (V-Ph-Hz) 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 Voltage Range Min Max RLA 342 418 4.2 + 4.2 342 418 4.8 + 4.8 342 418 5.4 + 5.4 342 418 6.9 + 6.9 342 418 10.0 + 10.0 Compressor LRA kW 0.60 0.60 0.60 0.60 0.60 Fan Motor FLA 0.8 0.8 1.0 1.1 1.1

60Hz
Power Supply MCA MOCP 16.5 20 16.5 20 20.0 30 22.5 30 24.5 30 ICF

Combination of outdoor unit


Heat Pump Model MMYAP1401HT7 AP1601HT7 AP1801HT7 AP2001HT7 AP2201HT7 AP2211HT7 AP2401HT7 AP2411HT7 AP2601HT7 AP2801HT7 AP3001HT7 AP3201HT7 AP3211HT7 AP3401HT7 AP3411HT7 AP3601HT7 AP3611HT7 AP3801HT7 AP4001HT7 AP4201HT7 AP4401HT7 AP4601HT7 AP4801HT7 Legend Nominal Voltage (V-Ph-Hz) 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 380-3-60 MCA MOCP ICF RLA Voltage Range Min 342 342 342 342 342 342 342 342 342 342 342 342 342 342 342 342 342 342 342 342 342 342 342 Unit No.1 Max RLA LRA 418 5.4 + 5.4 418 5.4 + 5.2 418 6.9 + 6.9 418 6.9 + 6.9 418 5.4 + 5.4 418 10.0 + 10.0 418 5.4 + 5.4 418 10.0 + 10.0 418 6.9 + 6.9 418 6.9 + 6.9 418 6.9 + 6.9 418 5.4 + 5.4 418 10.0 + 10.0 418 6.9 + 6.9 418 10.0 + 10.0 418 6.9 + 6.9 418 10.0 + 10.0 418 6.9 + 6.9 418 6.9 + 6.9 418 10.0 + 10.0 418 10.0 + 10.0 418 10.0 + 10.0 418 10.0 + 10.0 Compressor Unit No.2 Unit No.3 RLA LRA RLA LRA 4.8 + 4.8 5.4 + 5.4 5.4 + 5.4 6.9 + 6.9 5.4 + 5.4 4.8 + 4.8 6.9 + 6.9 5.4 + 5.4 5.4 + 5.4 10.0 + 10.0 5.4 + 5.4 5.4 + 5.4 6.9 + 6.9 5.4 + 5.4 6.9 + 6.9 6.9 + 6.9 5.4 + 5.4 5.4 + 5.4 6.9 + 6.9 6.9 + 6.9 5.4 + 5.4 5.4 + 5.4 10.0 + 10.0 6.9 + 6.9 6.9 + 6.9 5.4 + 5.4 10.0 + 10.0 10.0 + 10.0 6.9 + 9.9 6.9 + 6.9 6.9 + 6.9 6.9 + 6.9 6.9 + 6.9 6.9 + 6.9 10.0 + 10.0 6.9 + 6.9 10.0 + 10.0 10.0 + 10.0 10.0 + 10.0 10.0 + 10.0 LRA FLA kW Unit No.4 RLA LRA 5.4 + 5.4 5.4 + 5.4 5.4 + 5.4 5.4 + 5.4 6.9 + 6.9 6.9 + 6.9 6.9 + 6.9 6.9 + 6.9 10.0 + 10.0 Fan Motor kW 0.6 2 0.6 2 0.6 2 0.6 2 0.6 3 0.6 2 0.6 3 0.6 2 0.6 3 0.6 3 0.6 3 0.6 4 0.6 3 0.6 4 0.6 3 0.6 4 0.6 3 0.6 4 0.6 4 0.6 4 0.6 4 0.6 4 0.6 4 FLA 1.0 + 0.8 1.0 + 1.0 1.0 + 1.1 1.1 + 1.1 1.0 + 1.0 + 0.8 1.1 + 1.1 1.0 + 1.0 + 1.0 1.1 + 1.1 1.1 + 1.1 + 1.0 1.1 + 1.1 + 1.0 1.1 + 1.1 + 1.1 1.0 + 1.0 + 1.0 + 1.0 1.1 + 1.1 + 1.1 1.1 + 1.0 + 1.0 + 1.0 1.1 + 1.1 + 1.1 1.1 + 1.1 + 1.0 + 1.0 1.1 + 1.1 + 1.1 1.1 + 1.1 + 1.1 + 1.0 1.1 + 1.1 + 1.1 + 1.1 1.1 + 1.1 + 1.1 + 1.1 1.1 + 1.1 + 1.1 + 1.1 1.1 + 1.1 + 1.1 + 1.1 1.1 + 1.1 + 1.1 + 1.1 Power Supply MCA MOCP 36.5 40 40.0 50 42.5 50 45.0 60 56.5 70 47.0 60 60.0 70 49.0 60 62.5 70 65.0 80 67.5 80 80.0 90 69.5 80 82.5 100 71.5 80 85.0 100 73.5 90 87.5 100 90.0 100 92.0 110 94.0 110 96.0 110 98.0 110 ICF

40

: Minimum Circuit Amps : Maximum Overcurrent Protection (Amps) : Maximum Instantaneous Current Flow Start : Rated Load Amps

: Locked Rotor Amps : Full Load Amps : Fan Motor Rated Output (kW)

NOTE : RLA is based on the following conditions. Indoor temperature : 27C DB/19C WB Outdoor temperature : 35C DB

7. CONTROLS
Enabling a range of controls to meet various system needs
As the size of the building increases so does the number of air-conditioning units required. The multiple air-conditioning system Super MMS ensures energy-saving and comfort by allowing a control of multiple units requiring different loads. The Super MMS provides a range of functions to enable an integrated, centralized control of multiple units. Design an optimal system that best suits the application and scale of your project.

1. Control via indoor remote controller


1-1. Remote contoller
Individual air-conditioning units can be controlled remotely

3. Network control
The Super MMS control system can realize flexible centralized network control facility according to customers various requirements, for both open network building control in combination with other building apparatus like elevator, fire alarm, lighting, etc., and also for stand-alone air conditioning central control. These central control scheme is mainly established by advanced local server platform.

1-2. Group control


One remote controller can control a maximum of 8 indoor units in group

1-3. Two remote controller


The units can be controlled from two locations using two remote controllers.

3-1. Open network control


Super MMS open network facility is applicable for major building management global standards.

1-4. Weekly timer


The units can be run on a weekly schedule using a remote controller with weekly timer.

2. Control via the central remote controller


2-1. Central control + individual control
Up to 64 units can be controlled using the central remote controller and/or indoor remote controllers.

3-1-1. LONWORKS The LONWORKS interface manages the Super MMS air conditioning system as a LON device to command a building computer message and to monitor the operation status. 3-1-2. BACnet The local server serves air conditioning sub-system in a building control BACnet system.

2-2. Weekly timer controller


The central remote controller can be connected to a weekly timer to set a weekly running schedule.

3-2. Stand-alone central control


Simple stand-alone type exclusive air conditioning central control with less system integration work.

2-3. Control without indoor remote controller


The units can be operated from the central remote controller only, without the use of indoor remote controllers.

2-4. Control control with 1 by 1 model


Additionally, 1 by 1 model as Digital Inverter or Super Digital Inverter can be joined into the Super MMS central control scheme.

3-2-1. Touch screen controller Combination of touch screen and local server enables easy operation and comfortable display. 3-2-2. Windows based Plug-in central controller The local server serves central control function only by Plug-in into a customers computer.

41

1. Applications for indoor remote controller


Basic function System diagram Model

Main remote controller

Wireless remote controller


Wired remote controller RBC-AMT21E Simple remote controller RBC-AS21E Wireless remote controller kit TCB-AX21U(W)-E RBC-AX22CE TCB-AX21E

Individual control
1-1 Air conditioner is individually oper ated at a distance.

Indoor unit Possible up to Max. total length 500m Remote controller

Indoor unit Receiver unit Wireless remote controller

Max.8 indoor units

GROUP control
1-2 One remote controller can control group of Max. 8 indoor units. Operating on the same setting
Indoor unit Indoor unit Indoor unit Indoor unit

Wired remote controller RBC-AMT21E Simple remote controller RBC-AS21E

Remote controller

Possible up to Max.total length 500m

Wired system

Wireless system

Indoor unit

Indoor unit
Wired remote controller RBC-AMT21E Simple remote controller RBC-AS21E Wireless remote controller kit TCB-AX21U(W)-E RBC-AX22CE TCB-AX21E

Two remote control


1-3 Air conditioner is controlled by two remote controllers at two places.

Remote controller Master

Remote controller Side

Wireless remote controller 1 Master

Wireless remote controller 2 Side

Possible up to Max. total length 500m Indoor unit


Wired & Wireless combination control (Either controller should be set as side controller)

Remote controller

Wireless remote controller

Weekly timer function

1-4

Weekly schedule operation

Control by weekly timer

Indoor unit

Setting of ON-OFF 3 times par day Timer time is displayed. Designation of holiday

Wired remote controller RBC-AMT21E + Weekly timer RBC-EXW21E

Remote controller

Weekly timer

42

2. Application controls for central remote controller


Basic function
Header unit

System diagram

Model

U3, U4

Outdoor unit Line-3 Indoor unit U5, U6 U1, U2

Zone 4

Header unit

Indoor remote controller Outdoor unit U5, U6 Line-2 Indoor unit

U3, U4

Zone 3

U1, U2

Zone 2
Header unit

Indoor remote controller Outdoor unit Line-1 Indoor unit

U3, U4

Central remote controller TCB-SC642TLE <Indoor remote controller> Wired remote controller RBC-AMT21E Simple remote controller RBC-AS21E

2-1

Central management controller for 64 units

Zone 1

U1, U2

Indoor remote controller Power Central supply remote controller Single phase 220/230/240V

Function of central remote controller Individual control up to 64 indoor units. Individual control for max. 64 indoor units divided 1 to 4 zone. (Up to 16 indoor units for each zone.) Up to 16 outdoor header units are connectable. 4 type central control setting to inhibit individual operation by remote controller can be selected. Setting for one of 1 to 4 zone is available. Usable with other central comtrol devices (Up to 10 central control devices in one control circuit) Two control mode selectivity Central controller mode/Remote controller mode Setting of simultaneous ON/OFF 3 times for each day of the week combined with weekly timer.

U3, U4

Outdoor unit Indoor unit U1, U2

2-2

Central remote controller + Weekly timer Weekly operation schedule can be set by connecting a weekly timer to the central remote controller

Central remote controller TCB-SC642TLE + Weekly timer RBC-EXW21E <Indoor remote controller> Wired remote controller RBC-AMT21E or Simple remote controller RBC-AS21E

Indoor remote controller Single phase 220/230/240V Power supply Weekly timer

Central remote controller

43

Basic function
U3, U4

System diagram

Model

Outdoor unit U1, U2

Power supply Single phase 220/230/240V

Indoor unit Central remote controller

Even when grouping operation is performed by connecting multiple indoor units to 1 line, the indoor remote controller is required. Example of grouping operation U3, U4

Central remote controller TCB-SC642TLE <Indoor remote controller> Wired remote controller RBC-AMT21E

2-3

Remote central control without indoor remote controller


Power supply Single phase 220/230/240V

Outdoor unit U1, U2

(Group) Indoor remote controller is required Central remote controller

Available

U3, U4 Outdoor unit U1, U2

Power supply Single phase 220/230/240V

(Group)

Available
Central remote controller

Power supply U3, U4

Central remote controller

2-4

Central management control with 1 : 1 model

Header unit U1, U2

Super MMS

*1

Indoor unit

"1:1 model" connection interface

Central remote controller TCB-SC642TLE 1 : 1 model connection interface TCB-PCNT30TLE RAV-SM560KRT-E, SM800KRT-E are not available <Indoor remote controller> Wired remote controller RBC-AMT21E Simple remote controller RBC-AS21E

Indoor remote controller

* TOSHIBA Digital Inverter System and Super Digital Inverter System

44

3. Application control for network


Basic function 3-1-1 LONWORKS
LON Center LON Talk LON Interfaces

System diagram

Model

TCB-

TCBIFLN060

TCB-

LON Gateway TCB-IFLN**** 1 : 1 model connection interface TCB-PCNT30TLE RAV-SM560KRT-E, SM800KRT-E are not available

Super MMS

*1
<Indoor remote controller> Wired remote controller RBC-AMT21E or Simple remote controller RBC-AS21E

Remote controller

"1:1 model" connection interface

*1 TOSHIBA Digital Inverter System and Super Digital Inverter System

The LONWORKS interface shall be connected between a building management computer and the Super MMS air conditioning system.

3-1-2

BACnet
BAC net center

BACnet local server BMS-LSV****** TCS-Net Relay Interface BMS-IFLSV1E 1 : 1 model connection interface TCB-PCNT30TLE RAV-SM560KRT-E, SM800KRT-E are not available <Indoor remote controller> Wired remote controller RBC-AMT21E Simple remote controller RBC-AS21E

TCBLocal server TCS-Net Relay Interface Super MMS

*1

Remote controller

"1:1 model" connection interface

*1 TOSHIBA Digital Inverter System and Super Digital Inverter System

The local server shall be connected under the BACnet network, and shall be connected the Super MMS air conditioning system through the interface.

45

Basic function 3-2-1 Touch screen controller

System diagram

Model Touch screen controller BMS-TP5120ACE Intelligent server BMS-LSV2E BMS-STC01E TCS-Net Relay Interface BMS-IFLSV1E Energy Monitoring Relay Interface BMS-IFWH3E Digital I/O Relay Interface BMS-IFDD01E 1 : 1 model connection interface TCB-PCNT30TLE RAV-SM560KRT-E, SM800KRT-E are not available <Indoor remote controller> Wired remote controller RBC-AMT21E Simple remote controller RBC-AS21E

Touch screen controller

Local server

Relay Interface Super MMS

*1

Remote controller

"1:1 model" connection interface

Energy monitoring relay interface Digital I/O relay interface

*1 TOSHIBA Digital Inverter System and Super Digital Inverter System

Conbination of touch screen and local server.

3-2-2

Windows based central controller


Personal computer on site

Local server Relay Interface Super MMS

*1

Remote controller

"1:1 model" connection interface

Energy monitoring relay interface Digital I/O relay interface

WINDOWS based central controller BMS-LSV** TCS-Net Relay Interface BMS-IFLSV1E Intelligent server BMS-LSV2E BMS-STC01E Energy Monitoring Relay Interface BMS-IFWH3E Digital I/O Relay Interface BMS-IFDD01E 1 : 1 model connection interface TCB-PCNT30TLE RAV-SM560KRT-E, SM800KRT-E are not available <Indoor remote controller> Wired remote controller RBC-AMT21E Simple remote controller RBC-AS21E

*1 TOSHIBA Digital Inverter System and Super Digital Inverter System

The local server shall be Plug-in into a cutomers personal computer.

46

8. ACCESSORIES
Accessories parts for Indoor unit
Remote controller
Indoor unit type 4-way Air Discharge Cassette Type 2-way Air Discharge Cassette Type 1-way Air Discharge Cassette Type Concealed Duct Type Concealed Duct, High Static Pressure Type Under Ceiling Type High Wall Type Floor Standing Cabinet Type Floor Standing Concealed Type TCB-AX21E Floor Standing Type Accessory parts name Wired remote controller Central remote controller Weekly timer Simple remote controller Model RBC-AMT21E TCB-SC642TLE RBC-EXW21E RBC-AS21E Applicable model

Common parts for all type model

TCB-AX21U (W)-E

4-way Air Discharge Cassette Type

Wire-less remote controller kit *1

RBC-AX22CE

Under Ceiling Type

Universal Type (except concealed duct high static pressure)

47

Panels
Indoor unit type Accessory parts name Required accessory Ceiling panel Super Long Life Filter High Efficiency Filter 65 High Efficiency Filter 90 Filter Frame Fresh air and Filter Chamber Optional Fresh air inlet Box Auxiliary fresh air Flange Model Application model Remarks RBC-U21PG(W)-E TCB-UF1601UE TCB-UFM1601UE TCB-UFH1601UE TCB-DF21UKE TCB-GFC1601UE TCB-GB1601UE TCB-FF101URE TCB-SP1601UE Spacer for height adjustment TCB-SP1601U-KW50E Air discharge direction kit TCB-BC1601UE RBC-UW136PG Required accessory Ceiling panel RBC-UW266PG RBC-UW466PG RBC-US165PG RBC-US265PG Required accessory Ceiling panel RBC-UY135PG TCB-UFM11BFCE TCB-UFM21BFCE High Efficiency Filter 65 TCB-UFM11BE TCB-UFM21BE TCB-UFM31BE TCB-UFM41BE TCB-UFH51BFCE TCB-UFH61BFCE TCB-UFH51BE TCB-UFH61BE TCB-UFH71BE TCB-UFH81BE RBC-UD281PE(W) RBC-UD501PE(W) RBC-UD801PE(W) RBC-UD1401PE(W) TCB-CA281BE TCB-CA501BE TCB-CA801BE TCB-CA1401BE TCB-FC281BPE TCB-FC501BPE TCB-FC801BPE TCB-FC1401BPE TCB-FK281BE TCB-FK501BE TCB-FK801BE TCB-FK1401BE TCB-UFM1D-1E TCB-UFM2D-1E TCB-UFM3DE TCB-UFH5D-1E TCB-UFH6D-1E TCB-UFH7DE TCB-PF1D-1E TCB-PF2D-1E TCB-PF3DE TCB-FCY21DE TCB-FCY31DE TCB-FCY51DE TCB-FCY100DE TCB-DP21DE TCB-DP22DE TCB-DP22CE Under Ceiling Type Optional Drain pump kit TCB-KP12CE TCB-KP22CE

Be necessary for first using Be used with TCB-GFC1601UE

4-way Air Discharge Cassette Type

Three-piece group AP0071-0121 AP0151-0301 AP0361-0561 AP0151-0181 AP0241 AP0071-0121 AP0071-0121/AP0241-0301 AP0241-AP0301 use two piece AP0151-0181/AP0361-0561 AP0361-AP0581 use two piece AP0071-0121 AP0151-0181 AP0241-0301 AP0361-0561 AP0071-0121/AP0241-0301 AP0241-AP0301 use two piece AP0151-0181/AP0361-0561 AP0361-AP0581 use two piece AP0071-0121 AP0151-0181 AP0241-0301 AP0361-0561 AP0071-0121 AP0151-0181 AP0241-0301 AP0361-0561 AP0071-0121 AP0151-0181 AP0241-0301 AP0361-0561 AP0071-0121 AP0151-0181 AP0241-0301 AP0361-0561 AP0071-0121 AP0151-0181 AP0241-0301 AP0361-0561 AP0181-0481 AP0241-0361 AP0721-0961 AP0181-0481 AP0241-0361 AP0721-0961 AP0181-0481 AP0241-0361 AP0721-0961 AP0181 AP0241-0361 AP0481 AP0721-0961 AP0181-0481 AP0721-0961 AP0151-0481 AP0151-0181 AP0241-0481 * Required accessory when using Drain Pump Kit AP0481 use two piece Use two piece AP0481 use two piece Use two piece AP0481 use two piece Use two piece

2-way Air Discharge Cassette Type

1-way Air Discharge Cassette Type

High Efficiency Filter 90

Concealed Duct Type

Optional

Ceiling panel

Suction Canvas

Filter Chamber

Filter kit for underside

High Efficiency Filter 65

High Efficiency Filter 90

Concealed Duct High Static Pressure Type

Optional

Long Life Pre Filter

Filter Chamber

Drain pump kit

Note 1 : Concerning the Wire-less Remote Controller Kit and other optional equipments out of the table, consult your dealer about availabilities.

*1 : For handling the Wireless Remote Controller Kit, consult your dealer about availability.
48

9. TECHNICAL SPECIFICATIONS
Indoor unit (50Hz specifications)
4-way Air Discharge Cassette Type
Model name Cooling/Heating capacity (Note 1) Power supply Running current (A) 0.17 0.020 0.30 MMU- AP0091H (kW) 2.8/3.2 AP0121H 3.6/4.0 AP0151H 4.5/5.0 AP0181H 5.6/6.3 AP0241H 7.1/8.0 AP0271H 8.0/9.0 AP0301H 9.0/10.0 AP0361H AP0481H

50Hz

AP0561H 16.0/18.0

11.2/12.5 14.0/16.0

1 phase 50Hz 230V (220 240V) (Power exclusive for indoor is required.) 0.19 0.022 0.33 0.21 0.026 0.36 0.24 0.032 0.42 0.35 0.048 0.59 0.59 0.070 0.87 0.81 0.110 1.23 0.83 0.112 1.26

Electrical characteristics

Power consumption (kW) Starting current Main unit (A)

Heat-insulating material attached Model Panel color Height (mm) (mm) (mm) (mm) (mm) (mm) (kg) (kg) 20 22 4.5

Zinc hot dipping steel plate

Appearance

Ceiling Panel

RBC-U21PG (W)-E Moon white (Munsell/2.5GY 9.0/0.5) 256 840 840 35 950 950 23 28 319

Main unit Width Depth Height Ceiling panel Width Depth Main unit Total weight Ceiling panel Heat exchanger Soundproof/Heat-insulating material Fan Fan unit

Outer dimension

Finned tube Non-flammable insulation

Turbo fan 800 (730/680) 930 (830/790) 1,050 (920/800) 60 Standard filter attached (Long life filter) Remote controller 1,200 (920/820) 1,320 1,680 2,040 2,090 (1,110/850) (1300/1,070) (1,430/1,130) (1,520/1,230) 90

Standard air flow High (m/h) (Mid./Low) Motor (W)

Air filter Controller Gas side Connecting Liquid side pipe Drain port Sound level(Note 2) High (Mid./Low) (mm) (mm) (Nominal dia.) (dB(A)) 30/29/27 31/29/27 9.5 6.4 12.7

15.9 9.5 25 (Polyvinyl chloride tube)

32/29/28

34/31/28

37/33/30

40/36/33

44/38/34

45/40/34

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

49

50Hz

2-way Air Discharge Cassette Type


Model name Cooling/Heating capacity Power supply Running current Electrical Power characteristics consumption Power factor Starting current Main unit Appearance Model Ceiling panel Panel color Height (mm) Main unit Outer dimension Ceiling panel Width Depth (mm) (mm) 830 550 8 1,000 650 33 8 Finned tube Non-flammable insulation Centrifugal fan (m/h) 570/510/450 53 780/700/600 39 Standard filter attached (Long life filter) Remote controller Gas side Connecting Liquid side pipe (mm) (mm) 9.5 6.4 25 (Polyvinyl chloride tube) 34/32/30 35/33/30 38/35/33 40/37/34 45/42/39 12.7 15.9 9.5 1140/960/720 53
1260/1140/960 1920/1500/1050

MMU(kW)

AP0071WH 2.2/2.5

AP0091WH 2.8/3.2

AP0121WH 3.6/4.0

AP0151WH 4.5/5.0

AP0181WH 5.6/6.3

AP0241WH 7.1/8.0

AP0271WH 8.0/9.0

AP0301WH 9.0/10.0

AP0481WH China only 14.0/16.0 1 phase 50Hz 220V

1 phase 50Hz 230V (220 240V) (Power exclusive for indoor is required.) (A) (kW) (%) (A) 0.47 0.31 0.070 97 0.60 0.32 0.072 0.46 0.105 99 0.89 0.47 0.106 98 0.98

1.16 0.250 98 1.33

Heat-insulating material attached Zinc hot dipping steel plate RBC-UW136PG RBC-UW266PG Light ivory (Munsell 10Y 9/0.5) 398 1,350 406 1,650 620 RBC-UW46 6PG

Height (mm) Width Depth Main unit (mm) (mm) (kg) (kg)

1,520

1,898 680 48 52 18

44 11

Total weight Ceiling panel Heat exchanger Soundproof/Heat-insulating material Fan Fan unit Standard air flow (High/Mid./Low) Motor Air filter Controller

(W)

92

Drain port (Nominal dia.) Sound level (Note 2) (High/Mid./Low) (dB(A))

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

50

50Hz

1-way Air Discharge Cassette Type


Model name Cooling/Heating capacity (Note 1) Power supply Running current Electrical characteristics Power consumption (Note 2) Power factor Starting current Main unit Appearance Ceiling panel Model Panel color Height Main unit Width Outer dimension Ceiling panel Depth Height Width Depth Main unit Total weight Ceiling panel Heat exchanger Soundproof/Heat-insulating material Fan Fan Standard air flow (High/Mid./Low) (m/h) unit Motor Controller Room thermostat Air filter Gas side Connecting pipe Liquid side Drain port (mm) (mm) (Nominal dia.) (dB(A)) 42/39/34 9.5 6.4 25 (Polyvinyl chloride tube) 42/39/35 43/41/37 (W) 540/480/420 22 Remote controller Attached Standard filter attached (Long life filter) 12.7 15.9 9.5 (kg) 3.5 Finned tube Non-flammable insulation Centrifugal fan 780/720/660 34 1,200/1,140/1,020 8 9 (mm) (mm) (mm) (mm) (mm) (mm) (kg) 235 850 400 18 1,050 470 22 27 1,220 755 31 1,000 655 10 1,420 (A) (kW) (%) (A) MMU(kW) AP0071YH 2.2/2.5 AP0091YH 2.8/3.2 AP0121YH 3.6/4.0 AP0151SH 4.5/5.0 AP0181SH 5.6/6.3 AP0241SH 7.1/8.0

1 phase 50Hz 230V (220 240V) (Power exclusive for indoor is required.) 0.24 0.053 95 0.6 0.48 0.103 93 0.8 0.55 0.115 91 1.1

Heat-insulating material attached Zinc hot dipping steel plate RBC-UY135PG RBC-US165PG W : Silky shade (1Y8.5/0.5) 198 1,200 RBC-US265PG

Sound level (Note 2) (High/Mid./Low)

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

51

50Hz

Concealed Duct Type


Model name Cooling/Heating capacity (Note 1) Power supply Electrical characteristics Running current (A) 0.29 0.033 0.5 MMD- AP0071BH AP0091BH AP0121BH AP0151BH AP0181BH AP0241BH AP0271BH AP0301BH AP0361BH AP0481BH AP0561BH (kW) 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0 8.0/9.0 9.0/10.0 11.2/12.5 14.0/16.0 16.0/18.0

1 phase 50Hz 230V (220 240V) (Power exclusive for indoor is required.) 0.34 0.039 0.59 0.43 0.050 0.75 0.52 0.060 0.90 0.61 0.071 1.05 0.83 0.107 1.44 0.98 0.128 1.70

Power consumption (kW) Starting current (A)

Appearance

Main unit Height Main unit Width (mm) (mm) (mm) (mm) (mm) (mm) (kg) (kg) 28 3.5 32 4 630 550

Zinc hot dipping steel plate 320 700 800 9 780 500 43 6 Finned tube Non-flammable insulation Centrifugal fan (m/h) (W) (Pa) (Pa) 480 (420/340) 570 650 780 (490/400) (540/480) (660/540) 1,140 (990/870) 120 50 (4 mmAq) 110 (10 mmAq) Standard filter attached (Long life filter) Remote controller 1,260 1,620 (1080/870) (1410/1200) 1,980 (1710/1490) 55 7 1,080 1,430 1,000 1,350

Outer dimension Suction ceiling panel

Depth Height Width Depth Main unit

Total weight Ceiling panel Heat exchanger Soundproof/Heat-insulating material Fan Standard air flow High (Mid./Low) Fan unit Motor External static pressure (factory setting) External static pressure Air filter Controller Gas side Connecting pipe Liquid side Drain port Sound level (Note 2) (High/Mid./Low) (mm) (mm) (Nominal dia.) (dB(A)) 30/28/26 31/29/27 9.5 6.4 25 (Polyvinyl chloride tube) 32/30/28 33/31/29 34/32/29 36/34/32 38/36/32

12.7

15.9 9.5

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

52

50Hz

Concealed Duct High Static Pressure Type


Model name Cooling/Heating capacity (Note 1) Power supply Running current (A) 0.81 0.184 99 1.3 MMD(kW) AP0181H 5.6/6.3 AP0241H 7.1/8.0 AP0271H 8.0/9.0 AP0361H 11.2/12.5 AP0481H 14.0/16.0 AP0721H 22.4/25.0 AP0961H 28.0/31.5

1 phase 50Hz 230V (220 240V) (Power exclusive for indoor is required.) 1.35 0.299 96 3.5 1.63 0.368 98 4.1 Zinc hot dipping steel plate 380 x 850 x 660 50 52 56 Finned tube Non-flammable insulation Centrifugal fan (m/h) (W) (Pa) (Pa) (m/h) 720/1,080 1,060/1,580 900 160 137 68.6-137-196 1,280/1,920 1,680/2,520 2,880/4,320 3,360/5,040 1,320 1,600 260 2,100 3,600 370 x 3 4,200
380 x 1,200 x 660

1.84 0.414 98 4.8

5.25 1.200 99 13.6

5.52 1.260 99 14.8

Electrical Power consumption (kW) characteristics Power factor Starting current Appearance Outer Height x Width x Depth (mm) dimension Total weight Heat exchanger Soundproof/Heat-insulating material Fan Standard air flow Motor Fan unit External static pressure (Factory setting) External static pressure Air flow limit Lower limit/Upper limit Air filter Controller Gas side Connecting Liquid side pipe Drain port Sound level (Note 2) (High/Mid./Low) (mm) (mm) (Nominal dia.) (dB(A)) (kg) (%) (A)

470 x 1,380 x 1,250 150

67

Option or field supply Remote controller 12.7 6.4 15.9 9.5 25 (One side of male screw) 37 40 49 50 22.2 12.7

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

53

50Hz

Under Ceiling Type


Model name Cooling/Heating capacity (Note 1) Power supply Running current Electrical characteristics Power consumption (kW) Starting current Appearance Outer Height x Width x Depth (mm) dimension Total weight Heat exchanger Soundproof/Heat-insulating material Fan Standard air flow (High/Mid./Low) Motor Controller Room thermostat Air filter Gas side Connecting Liquid side pipe Drain port Sound level (Note 2) (High/Mid./Low) (mm) (mm) (Nominal dia.) 12.7 6.4 20 (Polyvinyl chloride tube) (kg) (A) 0.033 0.43 0.038 0.48 0.050 0.62 White (Munsell 10Y 9.3/0.4) 0.091 1.17 0.110 1.25 (A) 0.29 MMC(kW) AP0151H 4.5/5.0 AP0181H 5.6/6.3 AP0241H 7.1/8.0 AP0271H 8.0/9.0 AP0361H 11.2/12.5 AP0481H 14.0/16.0

1 phase 50Hz 230V (220 240V) (Power exclusive for indoor is required.) 0.32 0.42 0.78 0.84

210 x 910 x 680

210 x 1,180 x 680

210 x 1,595 x 680

22

26 Finned tube Non-flammable insulation Centrifugal fan

34

Fan unit

(m/h)

720/600/540

780/660/540

1,110/900/840

1,650/1,380/1,200 1,800/1,560/1,320

(W)

30

40 Remote controller Attached Standard filter attached (Long life filter) 15.9 9.5

80

(dB(A))

35/32/30

36/33/30

38/36/33

41/38/35

43/40/37

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

54

50Hz

High Wall Type


Model name Cooling/Heating capacity (Note 1) Power supply Running current Power consumption Starting current (A) (kW) (A) MMK(kW) AP0071H 2.2/2.5 AP0091H 2.8/3.2 AP0121H 3.6/4.0 AP0151H 4.5/5.0 AP0181H 5.6/6.3 AP0241H 7.1/8.0

1 phase 50Hz 230V (220 240V) (Power exclusive for indoor is required.) 0.30 0.035 0.36 0.32 0.037 0.42 Silky mist (Munsell 1Y 8.9/0.5) City gray (Munsell N6.5) Silky mist (Munsell 1Y 8.9/0.5) 368 x 895 x 210 18 Finned tube Non-flammable insulation Cross-flow fan 600/540/480 30 Standard filter attached (Simple filter) Remote controller 780/660/600 1,200/1,020/900 368 x 1,055 x 210 19 368 x 1,430 x 210 25 0.35 0.040 0.47

Electrical characteristics

Suction grille and side panel Appearance Discharge grille Bottom surface Outer dimension Total weight Heat exchanger Soundproof/Heat-insulating material Fan Fan Standard air flow (High/Mid./Low) (m/h) unit Motor outlet Air filter Controller Gas side Connecting pipe Liquid side Drain port Sound level (Note 2) (High/Mid./Low) (mm) (mm) (Nominal dia.) (dB(A)) 39/34/31 9.5 (W) Height x Width x Depth (mm) (kg)

12.7 6.4 20 (Polyvinyl chloride tube) 42/38/35

15.9 9.5

42/38/35

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

55

50Hz

Floor Standing Cabinet Type


Model name Cooling/Heating capacity (Note 1) Power supply Running current Electrical Power consumption characteristics Power factor Starting current Appearance Outer dimension Total weight Heat exchanger Soundproof/Heat-insulating material Fan Fan unit Standard air flow (High/Mid./Low) Motor outlet Air filter Controller Gas side Connecting pipe Liquid side Drain port Sound level (Note 2) (High/Mid./Low) (mm) (mm) (Nominal dia.) (dB(A)) 39/37/35 9.5 6.4 20 (Polyvinyl chloride tube) 45/41/38 49/44/39 (m/h) (W) 480/420/360 45 Standard filter attached (Simple filter) Remote controller 12.7 15.9 9.5 Height x Width x Depth (mm) (kg) 37 Finned tube Non-flammable insulation Centrifugal fan 900/780/650 1,080/930/780 70 (A) (kW) (%) (A) MML(kW) AP0071H 2.2/2.5 AP0091H 2.8/3.2 AP0121H 3.6/4.0 AP0151H 4.5/5.0 AP0181H 5.6/6.3 AP0241H 7.1/8.0

1 phase 50Hz 230V (220 240V) (Power exclusive for indoor is required.) 0.26 0.056 94 0.60 0.43 0.092 93 0.80 Silky shade (1Y8.5/0.5) 630 x 950 x 230 40 40 0.47 0.102 94 1.10

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

56

50Hz

Floor Standing Concealed Type


Model name Cooling/Heating capacity (Note 1) Power supply Running current Electrical Power consumption characteristics Power factor Starting current Appearance Outer dimension Total weight Heat exchanger Soundproof/Heat-insulating material Fan Standard air flow (High/Mid./Low) Motor Static pressure range Air filter Controller Gas side Connecting pipe Liquid side Drain port (mm) (mm) (Nominal dia.) 9.5 6.4 20 (One side of male screw) 36/34/32 42/37/33 (m/h) (W) (kPa) 460/400/300 19 0 Standard filter attached (Simple filter) Remote controller 12.7 15.9 9.5 Height x Width x Depth (mm) (kg) 600 x 745 x 220 21 Finned tube Non-flammable insulation Centrifugal fan 740/600/490 70 950/790/640 (A) (kW) (%) (A) MML(kW) AP0071BH 2.2/2.5 AP0091BH 2.8/3.2 AP0121BH 3.6/4.0 AP0151BH 4.5/5.0 AP0181BH 5.6/6.3 AP0241BH 7.1/8.0

1 phase 50Hz 230V (220 240V) (Power exclusive for indoor is required.) 0.25 0.056 97 0.60 Zinc hot dipping steel plate 600 x 1,045 x 220 29 0.45 0.090 87 0.80 0.46 0.095 90 1.00

Fan unit

Sound level (Note 2) (High/Mid./Low) (dB(A))

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

57

50Hz

Floor Standing Type


Model name Cooling/Heating capacity (Note 1) Power supply Running current Electrical Power consumption characteristics Power factor Starting current Appearance Outer dimension Total weight Heat exchanger Soundproof/Heat-insulating material Fan unit Fan Standard air flow (High/Mid./Low) Motor Air filter Controller Gas side Connecting pipe Liquid side Drain port (mm) (mm) (Nominal dia.) 46/43/38 12.7 6.4 (m/h) (W) 900/780/660 37 Height x Width x Depth (mm) (kg) 48 (A) (kW) (%) (A) MMF(kW) AP0151H 4.5/5.0 AP0181H 5.6/6.3 AP0241H 7.1/8.0 AP0271H 8.0/9.0 AP0361H 11.2/12.5 AP0481H 14.0/16.0 AP0561H 16.0/18.0

1 phase 50Hz 230V (220 240V) (Power exclusive for indoor is required.) 0.67 0.150 97 0.90 1.10 0.88 0.190 94 1.70 1.29 0.280 1.60 0.350 95 2.10

W : Silky shade (1Y 8.5/0.5) 1750 600 210 49 Finned tube Non-flammable insulation Centrifugal fan 1,200/1,020/840 63
1,920/1,680/1,380

1750 600 390 65

2,160/1,860/1,560 160

110

Standard filter attached (Simple filter) Remote controller 15.9 9.5 20 (One side of male screw) 49/45/40 51/48/44 54/50/46

Sound level (Note 2) (High/Mid./Low) (dB(A))

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

58

60Hz

Indoor unit (60Hz specifications)


4-way Air Discharge Cassette Type
Model name Cooling/Heating capacity (Note 1) Power supply Running current (A) 0.18 0.020 0.30 MMU- AP0091H (kW) 2.8/3.2 AP0121H 3.6/4.0 AP0151H 4.5/5.0 AP0181H 5.6/6.3 AP0241H 7.1/8.0 AP0271H 8.0/9.0 AP0301H 9.0/10.0 AP0361H AP0481H AP0561H 16.0/18.0

11.2/12.5 14.0/16.0

1 phase 60Hz 220V (Power exclusive for indoor is required.) 0.20 0.022 0.33 0.22 0.026 0.36 0.26 0.032 0.42 0.37 0.048 0.59 0.61 0.070 0.87 0.85 0.110 1.23 0.87 0.112 1.26

Electrical characteristics

Power consumption (kW) Starting current Main unit (A)

Heat-insulating material attached Model Panel color Height (mm) (mm) (mm) (mm) (mm) (mm) (kg) (kg) 20 22 4.5

Zinc hot dipping steel plate

Appearance

Ceiling Panel

RBC-U21PG (W) E Moon white (Munsell/2.5GY 9.0/0.5) 256 840 840 35 950 950 23 28 319

Main unit Width Depth Height Ceiling panel Width Depth Main unit Total weight Ceiling panel Heat exchanger Soundproof/Heat-insulating material Fan Fan unit

Outer dimension

Finned tube Non-flammable insulation

Turbo fan 800 (730/680) 930 (830/790) 1,050 (920/800) 60 Standard filter attached (Long life filter) Remote controller 1,200 (920/820) 1,320 1,680 2,040 2,090 (1110/850) (1,300/1,070) (1,430/1,130) (1,520/1,230) 90

Standard air flow High (m/h) (Mid./Low) Motor (W)

Air filter Controller Gas side Connecting Liquid side pipe Drain port Sound level(Note 2) High (Mid./Low) (mm) (mm) (Nominal dia.) (dB(A)) 30/29/27 31/29/27 9.5 6.4 12.7

15.9 9.5 25 (Polyvinyl chloride tube)

32/29/28

34/31/28

37/33/30

40/36/33

44/38/34

45/40/34

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

59

60Hz

2-way Air Discharge Cassette Type


Model name Cooling/Heating capacity Power supply Running current Electrical Power characteristics consumption Power factor Starting current Main unit Appearance Model Panel color Height (mm) Main unit Outer dimension Ceiling panel Width Depth (mm) (mm) 830 550 8 1,000 650 33 8 Finned tube Non-flammable insulation Centrifugal fan flow (m/h) 570/510/450 53 780/700/600 39 Standard filter attached (Long life filter) Remote controller Gas side Connecting Liquid side pipe (mm) (mm) 9.5 6.4 25 (Polyvinyl chloride tube) 34/32/30 35/33/30 38/35/33 40/37/34 12.7 15.9 9.5 1140/960/720 53
1260/1140/960

MMU(kW)

AP0071WH 2.2/2.5

AP0091WH 2.8/3.2

AP0121WH 3.6/4.0

AP0151WH 4.5/5.0

AP0181WH 5.6/6.3

AP0241WH 7.1/8.0

AP0271WH 8.0/9.0

AP0301WH 9.0/10.0

1 phase 60Hz 220V (Power exclusive for indoor is required.) (A) (kW) (%) (A) 0.33 0.070 97 0.46 0.38 0.076 90 0.59 Heat-insulating material attached RBC-UW136PG 0.53 0.115 99 0.87 Zinc hot dipping steel plate RBC-UW266PG Light ivory (Munsell 10Y 9/0.5) 398 1,350 0.58 0.123 96 0.96

Ceiling panel

Height (mm) Width Depth Main unit (mm) (mm) (kg) (kg)

1,520

44 11

48

Total weight Ceiling panel Heat exchanger Soundproof/Heat-insulating material Fan Fan unit Standard air (High/Mid./Low) Motor Air filter Controller

(W)

Drain port (Nominal dia.) Sound level (Note (High/Mid./Low) 2) (dB(A))

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

60

60Hz

1-way Air Discharge Cassette Type


Model name Cooling/Heating capacity (Note 1) Power supply Running current Electrical characteristics Power consumption (Note 2) Power factor Starting current Main unit Appearance Ceiling panel Model Panel color Height Main unit Width Outer dimension Ceiling panel Depth Height Width Depth Main unit Total weight Ceiling panel Heat exchanger Soundproof/Heat-insulating material Fan Fan Standard air flow (High/Mid./Low) (m/h) unit Motor Controller Room thermostat Air filter Gas side Connecting pipe Liquid side Drain port (mm) (mm) (Nominal dia.) (dB(A)) 42/39/34 9.5 6.4 25 (Polyvinyl chloride tube) 42/39/35 43/41/37 (W) 540/480/420 22 Remote controller Attached Standard filter attached (Long life filter) 12.7 15.9 9.5 (kg) 3.5 Finned tube Non-flammable insulation Centrifugal fan 780/720/660 34 1,200/1,140/1,020 8 9 (mm) (mm) (mm) (mm) (mm) (mm) (kg) 235 850 400 18 1,050 470 22 27 1,220 755 31 1,000 655 10 1,420 (A) (kW) (%) (A) MMU(kW) AP0071YH 2.2/2.5 AP0091YH 2.8/3.2 AP0121YH 3.6/4.0 AP0151SH 4.5/5.0 AP0181SH 5.6/6.3 AP0241SH 7.1/8.0

1 phase 60Hz 220V (Power exclusive for indoor is required.) 0.26 0.056 98 0.60 0.54 0.115 97 0.80 0.61 0.130 97 1.10

Heat-insulating material attached Zinc hot dipping steel plate RBC-UY135PG RBC-US165PG W : Silky shade (1Y8.5/0.5) 198 1,200 RBC-US265PG

Sound level (Note 2) (High/Mid./Low)

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

61

60Hz

Concealed Duct Type


Model name Cooling/Heating capacity (Note 1) Power supply Electrical characteristics Running current (A) 0.30 0.033 0.5 MMD- AP0071BH AP0091BH AP0121BH AP0151BH AP0181BH AP0241BH AP0271BH AP0301BH AP0361BH AP0481BH AP0561BH (kW) 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0 8.0/9.0 9.0/10.0 11.2/12.5 14.0/16.0 16.0/18.0

1 phase 60Hz 220V (Power exclusive for indoor is required.) 0.35 0.039 0.59 0.45 0.050 0.75 0.55 0.060 0.90 0.64 0.071 1.05 0.87 0.107 1.44 1.03 0.128 1.70

Power consumption (kW) Starting current (A)

Appearance

Main unit Height Main unit Width (mm) (mm) (mm) (mm) (mm) (mm) (kg) (kg) 28 3.5 32 4 630 550

Zinc hot dipping steel plate 320 700 800 9 780 500 43 6 Finned tube Non-flammable insulation Centrifugal fan (m/h) (W) (Pa) (Pa) 480 (420/340) 570 650 780 (490/400) (540/480) (660/540) 1,140 (990/870) 120 50 (4 mmAq) 110 (10 mmAq) Standard filter attached (Long life filter) Remote controller 1,260 1,620 (1080/870) (1410/1200) 1,980 (1710/1490) 55 7 1,080 1,430 1,000 1,350

Outer dimension Suction ceiling panel

Depth Height Width Depth Main unit

Total weight Ceiling panel Heat exchanger Soundproof/Heat-insulating material Fan Standard air flow High (Mid./Low) Fan unit Motor External static pressure (factory setting) External static pressure Air filter Controller Gas side Connecting pipe Liquid side Drain port Sound level (Note 2) (High/Mid./Low) (mm) (mm) (Nominal dia.) (dB(A)) 30/28/26 31/29/27 9.5 6.4 25 (Polyvinyl chloride tube) 32/30/28 33/31/29 34/32/29 36/34/32 38/36/32 12.7

15.9 9.5

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

62

60Hz

Concealed Duct High Static Pressure Type


Model name Cooling/Heating capacity (Note 1) Power supply Running current (A) 0.92 0.198 98 1.30 MMD(kW) AP0181H 5.6/6.3 AP0241H 7.1/8.0 AP0271H 8.0/9.0 AP0361H 11.2/12.5 AP0481H 14.0/16.0 AP0721H 22.4/25.0 AP0961H 28.0/31.5

1 phase 60Hz 220V (Power exclusive for indoor is required.) 1.80 0.385 97 3.40 3.90 4.35 2.07 0.450 2.26 0.490 99 13.00 13.60 7.10 1.540 7.42 1.610

Electrical Power consumption (kW) characteristics Power factor Starting current Appearance Outer Height x Width x Depth (mm) dimension Total weight Heat exchanger Soundproof/Heat-insulating material Fan Standard air flow Motor Fan unit External static pressure (Factory setting) External static pressure Air flow limit Lower limit/Upper limit Air filter Controller Gas side Connecting Liquid side pipe Drain port Sound level (Note 2) (High/Mid./Low) (mm) (mm) (Nominal dia.) (dB(A)) (m/h) (W) (Pa) (Pa) (m/h) (kg) (%) (A)

Zinc hot dipping steel plate 380 x 850 x 660 50 52 56 Finned tube Non-flammable insulation Centrifugal fan 900 160 137 68.6-137-196 720/1,080 1,060/1,580 1,280/1,920 1,680/2,520 2,880/4,320 3,360/5,040 1,320 1,600 260 2,100 3,600 370 x 3 4,200
380 x 1,200 x 660

470 x 1,380 x 1,250 150

67

Option or field supply Remote controller 12.7 6.4 15.9 9.5 25 (One side of male screw) 37 40 49 50 22.2 12.7

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

63

60Hz

Under Ceiling Type


Model name Cooling/Heating capacity (Note 1) Power supply Running current Electrical characteristics Power consumption (kW) Starting current Appearance Outer Height x Width x Depth (mm) dimension Total weight Heat exchanger Soundproof/Heat-insulating material Fan Standard air flow (High/Mid./Low) Motor Controller Room thermostat Air filter Gas side Connecting Liquid side pipe Drain port Sound level (Note 2) (High/Mid./Low) (mm) (mm) (Nominal dia.) 12.7 6.4 20 (Polyvinyl chloride tube) (kg) (A) 0.033 0.43 0.038 0.48 0.050 0.62 White (Munsell 10Y 9.3/0.4) 0.091 1.17 0.110 1.25 (A) 0.30 MMC(kW) AP0151H 4.5/5.0 AP0181H 5.6/6.3 AP0241H 7.1/8.0 AP0271H 8.0/9.0 AP0361H 11.2/12.5 AP0481H 14.0/16.0

1 phase 60Hz 220V (Power exclusive for indoor is required.) 0.34 0.44 0.82 0.87

210 x 910 x 680

210 x 1,180 x 680

210 x 1,595 x 680

22

26 Finned tube Non-flammable insulation Centrifugal fan

34

Fan unit

(m/h)

720/600/540

780/660/540

1,110/900/840

1,650/1,380/1,200 1,800/1,560/1,320

(W)

30

40 Remote controller Attached Standard filter attached (Long life filter) 15.9 9.5

80

(dB(A))

35/32/30

36/33/30

38/36/33

41/38/35

43/40/37

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

64

60Hz

High Wall Type


Model name Cooling/Heating capacity (Note 1) Power supply Running current Power consumption Starting current (A) (kW) (A) MMK(kW) AP0071H 2.2/2.5 AP0091H 2.8/3.2 AP0121H 3.6/4.0 AP0151H 4.5/5.0 AP0181H 5.6/6.3 AP0241H 7.1/8.0

1 phase 60Hz 220V (Power exclusive for indoor is required.) 0.32 0.035 0.46 0.34 0.037 0.48 Silky mist (Munsell 1Y 8.9/0.5) City gray (Munsell N6.5) Silky mist (Munsell 1Y 8.9/0.5) 368 x 895 x 210 18 Finned tube Non-flammable insulation Cross-flow fan 600/540/480 30 Standard filter attached (Simple filter) Remote controller 780/660/600 1,200/1,020/900 368 x 1,055 x 210 19 368 x 1,430 x 210 25 0.35 0.040 0.60

Electrical characteristics

Suction grille and side panel Appearance Discharge grille Bottom surface Outer dimension Total weight Heat exchanger Soundproof/Heat-insulating material Fan Fan Standard air flow (High/Mid./Low) (m/h) unit Motor outlet Air filter Controller Gas side Connecting pipe Liquid side Drain port Sound level (Note 2) (High/Mid./Low) (mm) (mm) (Nominal dia.) (dB(A)) 39/34/31 9.5 (W) Height x Width x Depth (mm) (kg)

12.7 6.4 20 (Polyvinyl chloride tube) 42/38/35

15.9 9.5

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

65

60Hz

Floor Standing Cabinet Type


Model name Cooling/Heating capacity (Note 1) Power supply Running current Electrical Power consumption characteristics Power factor Starting current Appearance Outer dimension Total weight Heat exchanger Soundproof/Heat-insulating material Fan Fan unit Standard air flow (High/Mid./Low) Motor outlet Air filter Controller Gas side Connecting pipe Liquid side Drain port Sound level (Note 2) (High/Mid./Low) (mm) (mm) (Nominal dia.) (dB(A)) 39/37/35 9.5 6.4 20 (Polyvinyl chloride tube) 45/41/38 49/44/39 (m/h) (W) 480/420/360 45 Standard filter attached (Simple filter) Remote controller 12.7 15.9 9.5 Height x Width x Depth (mm) (kg) 37 Finned tube Non-flammable insulation Centrifugal fan 900/780/650 1,080/930/780 70 (A) (kW) (%) (A) 0.25 0.053 96 0.60 MML(kW) AP0071H 2.2/2.5 AP0091H 2.8/3.2 AP0121H 3.6/4.0 AP0151H 4.5/5.0 AP0181H 5.6/6.3 AP0241H 7.1/8.0

1 phase 60Hz 220V (Power exclusive for indoor is required.) 0.44 0.092 95 0.80 Silky shade (1Y8.5/0.5) 630 x 950 x 230 40 0.53 0.113 97 1.10

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

66

60Hz

Floor Standing Concealed Type


Model name Cooling/Heating capacity (Note 1) Power supply Running current Electrical Power consumption characteristics Power factor Starting current Appearance Outer dimension Total weight Heat exchanger Soundproof/Heat-insulating material Fan Standard air flow (High/Mid./Low) Motor Static pressure range Air filter Controller Gas side Connecting pipe Liquid side Drain port (mm) (mm) (Nominal dia.) 9.5 6.4 20 (One side of male screw) 36/34/32 42/37/33 (m/h) (W) (kPa) 460/400/300 19 0 Standard filter attached (Simple filter) Remote controller 12.7 15.9 9.5 Height x Width x Depth (mm) (kg) 600 x 745 x 220 21 Finned tube Non-flammable insulation Centrifugal fan 740/600/490 70 950/790/640 (A) (kW) (%) (A) MML(kW) AP0071BH 2.2/2.5 AP0091BH 2.8/3.2 AP0121BH 3.6/4.0 AP0151BH 4.5/5.0 AP0181BH 5.6/6.3 AP0241BH 7.1/8.0

1 phase 60Hz 220V (Power exclusive for indoor is required.) 0.27 0.058 98 0.60 Zinc hot dipping steel plate 600 x 1,045 x 220 29 0.46 0.096 95 0.80 0.51 0.110 98 1.00

Fan unit

Sound level (Note 2) (High/Mid./Low) (dB(A))

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

67

60Hz

Floor Standing Type


Model name Cooling/Heating capacity (Note 1) Power supply Running current (A) 0.67 0.146 99 0.90 1.10 W : Silky Shade (1Y 8.5/0.5) Height x Width x Depth (mm) (kg) 48 1750 600 210 49 Finned tube Non-flammable insulation Centrifugal fan (m/h) (W) 900/780/660 37 1,200/1,020/840 63 2,160/1,860/1,560 160 1750 600 390 65 MMF(kW) AP0151H 4.5/5.0 AP0181H 5.6/6.3 AP0241H 7.1/8.0 AP0271H 8.0/9.0 AP0361H 11.2/12.5 AP0481H 14.0/16.0 AP0561H 16.0/18.0

1 phase 60Hz 220V (Power exclusive for indoor is required.) 0.90 0.195 98 1.80 1.37 0.295 1.75 0.380 99 2.30

Electrical Power consumption (kW) characteristics Power factor Starting current Appearance Outer dimension Total weight Heat exchanger Soundproof/Heat-insulating material Fan Fan unit Standard air flow (High/Mid./Low) Motor Air filter Controller Gas side Connecting pipe Liquid side Drain port Sound level (Note 2) (High/Mid./Low) (mm) (mm) (Nominal dia.) (dB(A)) (%) (A)

1,920/1,680/1,380

110

Standard filter attached (Simple filter) Remote controller 12.7 6.4 20 (One side of male screw) 46/43/38 49/45/40 51/48/44 54/50/46 15.9 9.5

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

68

50Hz

Outdoor unit (50Hz)


Equivalent HP Model name Outdoor unit type Cooling capacity ( Power supply ( Standard heating capacity ( Cooling Only Heat Pump MMYMMY(kW) Equivalent to 5HP MAP0501T8 MAP0501HT8 14.0 16.0 5.85 3.65 90 3.84 1.0 6.09 3.84 91 4.17 1.0 227 228 Silky shade (Munsell 1Y8.5/0.5) Type Motor output Fan Fan unit Motor output Air volume Heat exchanger Refrigerant R410A (Charged refrigerant amount) ( High-pressure switch Protective devices Gas side Connecting port dia Liquid side Balance pipe Gas side Connecting Refrigerant Liquid side method piping Balance pipe specifications Max. equivalent length ( 4) Max. real length (mm) (mm) (mm) Flare Flare Flare (m) (m) (m) (m) 175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( Shield wire 1.25mm x 2 cores. up to 2000m 15.9 9.5 9.5 Brazing 19.1 Cooling Only 3) Heat Pump (kW) (m/h) (kg) (kg) (MPa) 9,000 8.0 8.5 OFF : 2.90 ( ON : 3.73 (kW) 1.1 2 1.4 2 Hermetic type 2.3 2 Propeller fan 0.60 9,900 Finned tube 11 12.5 10,500 3.1 2 4.2 2 Equivalent to 6HP MAP0601T8 MAP0601HT8 16.0 18.0 7.28 4.64 92 3.45 1.0 7.08 4.56 93 3.95 1.0 Equivalent to 8HP MAP0801T8 MAP0801HT8 Inverter unit 22.4 25.0 8.62 5.67 95 3.95 1.0 8.93 5.88 95 4.25 1.0 Equivalent to 10HP MAP1001T8 MAP1001HT8 28.0 31.5 11.55 7.68 96 3.65 1.0 11.98 7.97 96 3.95 1.0 256 258 Equivalent to 12HP MAP1201T8 MAP1201HT8 33.5 37.5 18.30 11.92 94 2.81 1.0 15.65 10.19 94 3.68 1.0

1)

* 2)

* 1)

(kW) (A) (kW) (%) (kW/kW) (A) (A) (kW) (%) (kW/kW) (A) (mm) Cooling Only Heat Pump (kg) (kg)

3 phase 50Hz 400V (380 415V)

Running current Power consumption

Cooling Power factor EER (Energy Efficiency Ratio) Electrical characteristics ( 1) Starting current Running current Power consumption Heating Power factor EER (Energy Efficiency Ratio) Starting current External dimension Total weight Color Compressor

Height 1,800 x Width 990 x Depth 750

5) 22.2 12.7 28.6

Max. total pipe length (Real length) Max. height difference Control wiring Central remote controller Max. No. of connected indoor units Sound level

* 6)
20 59

When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m and (Shield wire) 2.0mm x 2 cores up to 2000m 8 (dB(A)) 55 10 56 13 57 16 58

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

69

50Hz

Outdoor unit (Combination) (50Hz)


Equivalent HP Set Model name Outdoor unit type Outdoor unit model Cooling Only Heat Pump Cooling Only Heat Pump MMYMMYEquivalent to 14HP AP1401T8 AP1401HT8 Equivalent to 16HP AP1601T8 AP1601HT8 Inverter MMY- MAP0801T8 MAP0601T8 MAP0801T8 MAP0801T8 MAP1001T8 MAP0801T8 MAP1001T8 MAP1001T8 MMY- MAP0801HT8 MAP0601HT8 MAP0801HT8 MAP0801HT8 MAP1001HT8 MAP0801HT8 MAP1001HT8 MAP1001HT8 (kW) (kW) (A) (kW) (%) 38.4 43.0 17.08 11.12 94 3.45 1.0 16.83 10.96 94 3.92 1.0 256 258 227 228 Hermetic type (kW) (kW) (m/h) Cooling Only Heat Pump (kg) (kg) (MPa) (mm) (mm) (mm) 22.2 12.7 19.1 9.5 9.5 Brazing Flare Flare (m) (m) (m) (m) 175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( Shield wire 1.25mm x 2 cores. up to 2000m 9,900 11.0 12.5 9,000 8.0 8.5 OFF : 2.90 ( 9,900 2.3 2 1.4 2 2.3 2 0.6 10,500 Finned tube 11.0 12.5 ON : 3.73 9,900 10,500 3.1 2 Propeller fan 2.3 2 3.1 2 45 50.0 18.54 12.20 95 3.69 1.0 18.65 12.28 95 4.07 1.0 50.4 56.5 21.29 14.16 96 3.56 1.0 21.61 14.37 96 3.93 1.0 256 258 Silky shade (Munsell 1Y8.5/0.5) Type Motor output Fan Fan unit Motor output Air volume Heat exchanger Refrigerant R410A Charged amount ( 3) 56.0 63.0 24.31 16.17 96 3.46 1.0 24.75 16.46 96 3.83 1.0 Equivalent to 18HP AP1801T8 AP1801HT8 Equivalent to 20HP AP2001T8 AP2001HT8

Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2)

3 phase 50Hz 400V (380 415V)

Running current Power consumption Power factor

Cooling Electrical characteristics ( 1)

EER (kW/kW) (Energy Efficiency Ratio) Starting current Running current Power consumption Heating Power factor (A) (A) (kW) (%)

EER (kW/kW) (Energy Efficiency Ratio) Starting current External dimension Total weight Color Compressor Cooling Only Heat Pump (A) (mm) (kg) (kg)

Height 1,800 x Width 990 x Depth 750

High-pressure switch Protective devices Gas side Connecting Liquid side port dia. Balance side Gas side Refrigerant pipe spec. ( 4) Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference Control wiring Central remote controller Max. No. of connected indoor units Sound level

5) 22.2 12.7

* 6)
33 61

When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m and (Shield wire) 2.0mm x 2 cores up to 2000m 23 (dB(A)) 59.5 27 60 30 60.5

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

70

50Hz

Equivalent HP Set Model name Outdoor unit type Outdoor unit model Cooling Only Heat Pump MMYMMY(kW) (kW) 26.42 17.39 MAP0801T8 MAP0801HT8 MAP0801T8 MAP0801HT8 Cooling Only Heat Pump MMYMMYAP2201T8 AP2201HT8

Equivalent to 22HP AP2211T8 AP2211HT8 Inverter MAP0601T8 MAP0601HT8 61.5 69.0 3 phase 50Hz 400V (380 415V) 31.01 20.41 95 3.54 1.0 26.36 17.35 95 3.98 1.0 Height 1,800 x Width 990 x Depth 750 256 258 227 228 Silky shade (Munsell 1Y8.5/0.5) Type Motor output Fan Motor output Air volume (kW) (kW) (m/h) Cooling Only Heat Pump (kg) (kg) (MPa) (mm) (mm) (mm) 22.2 12.7 9,900 11.0 12.5 OFF : 2.90 ( 5) 19.1 9.5 9.5 Brazing Flare Flare (m) (m) (m) (m) 175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( 6) Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m, and (Shield wire) 2.0mm x 2 cores up to 2000m 37 (dB(A)) 61.5 28.6 12.7 22.2 2.3 2 Hermetic type 1.4 2 Propeller fan 0.6 9,000 Finned tube 8.0 8.5 ON : 3.73 11.0 12.5 10,500 4.2 2 3.1 2 256 258 3.69 1.0 3.01 1.0 28.38 18.68 MAP1201T8 MAP1201HT8 MAP1001T8 MAP1001HT8

Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2)

Running current (A) Power consumption (kW) Power factor (%) EER (kW/kW) (Energy Efficiency Ratio)

Cooling Electrical characteristics ( 1)

Starting current Running current Power factor

(A) (A) (%)

Power consumption (kW) Heating EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) (mm) Cooling Only Heat Pump (kg) (kg)

External dimension Total weight Color Compressor

Fan unit

Heat exchanger Refrigerant R410A Charged amount ( 3)

High-pressure switch Protective devices Gas side Connecting Liquid side port dia. Balance side Gas side Refrigerant pipe spec. ( 4) Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference Control wiring Central remote controller Max. No. of connected indoor units Sound level

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

71

50Hz

Equivalent HP Set Model name Outdoor unit type Outdoor unit model Cooling Only Heat Pump MMYMMY(kW) (kW) (A) (%) 27.73 18.44 96 3.69 1.0 27.96 18.79 97 4.07 1.0 MAP0801T8 MAP0801HT8 MAP0801T8 MAP0801HT8 Cooling Only Heat Pump MMYMMYAP2401T8 AP2401HT8

Equivalent to 24HP AP2411T8 AP2411HT8 Inverter MAP0801T8 MAP0801HT8 68.0 76.5 3 phase 50Hz 400V (380 415V) 38.02 25.02 95 2.72 1.0 32.06 21.32 96 3.59 1.0 Height 1,800 x Width 990 x Depth 750 256 258 Silky shade (Munsell 1Y8.5/0.5) Hermetic type (kW) (kW) (m/h) Cooling Only Heat Pump (kg) (kg) (MPa) (mm) (mm) (mm) 22.2 9,900 Finned tube 11.0 12.5 OFF : 2.90 ON : 3.73 ( 5) 2.3 2 Propeller fan 0.6 10.500 4.2 2 MAP1201T8 MAP1201HT8 MAP1201T8 MAP1201HT8

Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2)

Running current Power factor

Power consumption (kW) Cooling Electrical characteristics ( 1) EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) Running current Power factor (A) (%) Power consumption (kW) Heating EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) External dimension Total weight Color Compressor Type Motor output Fan Motor output Air volume Heat exchanger Refrigerant R410A Charged amount ( 3) Cooling Only Heat Pump (mm) (kg) (kg)

Fan unit

High-pressure switch Protective devices Gas side Connecting Liquid side port dia. Balance side Gas side Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference Control wiring Central remote controller Max. No. of connected indoor units Sound level

28.6

12.7 9.5 Brazing Flare Flare

Refrigerant pipe spec. ( 4)

(m) (m) (m) (m)

175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( 6) Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m, and (Shield wire) 2.0mm x 2 cores up to 2000m 40

(dB(A))

62

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

72

50Hz

Equivalent HP Set Model name Outdoor unit type Outdoor unit model Cooling Only Heat Pump Cooling Only Heat Pump MMYMMY-

Equivalent to 26HP AP2601T8 AP2601HT8

Equivalent to 28HP AP2801T8 AP2801HT8 Inverter

Equivalent to 30HP AP3001T8 AP3001HT8

MMY- MAP1001T8 MAP0801T8 MAP0801T8 MAP1001T8 MAP1001T8 MAP0801T8 MAP1001T8 MAP1001T8 MAP1001T8 MMY- MAP1001HT8 MAP0801HT8 MAP0801HT8 MAP1001HT8 MAP1001HT8 MAP0801HT8 MAP1001HT8 MAP1001HT8 MAP1001HT8 (kW) (kW) (A) (%) 3.60 1.0 31.16 20.51 95 3.97 1.0 73 81.5 30.51 20.29 78.5 88.0 3 phase 50Hz 400V (380 415V) 33.48 22.27 96 3.52 1.0 33.98 22.60 96 3.89 1.0 Height 1,800 x Width 990 x Depth 750 256 258 Silky shade (Munsell 1Y8.5/0.5) Hermetic type (kW) (kW) (m/h) 10,500 9,900 2.3 2 3.1 2 Propeller fan 0.6 10,500 Finned tube 11.0 12.5 OFF : 2.90 ON : 3.73 ( 5) 22.2 12.7 9.5 Brazing Flare Flare (m) (m) (m) (m) 175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( 6) Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m, and (Shield wire) 2.0mm x 2 cores up to 2000m 43 (dB(A)) 62 47 62.5 48 63 9,900 10,500 2.3 2 3.1 2 3.46 1.0 36.93 24.82 97 3.83 1.0 36.48 24.26 84.0 95.0

Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2)

Running current Power factor

Power consumption (kW) Cooling Electrical characteristics ( 1) EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) Running current Power factor (A) (%) Power consumption (kW) Heating EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) External dimension Total weight Color Compressor Type Motor output Fan Motor output Cooling Only Heat Pump (mm) (kg) (kg)

Fan unit

Air volume Heat exchanger Refrigerant R410A Charged amount ( 3)

Cooling Only Heat Pump

(kg) (kg) (MPa) (mm) (mm) (mm)

High-pressure switch Protective devices Gas side Connecting Liquid side port dia. Balance side Gas side Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference Control wiring Central remote controller Max. No. of connected indoor units Sound level

Refrigerant pipe spec. ( 4)

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

73

50Hz

Equivalent HP Set Model name Outdoor unit type Outdoor unit model Cooling Only Heat Pump MMY(kW) (kW) (A) (%) 37.09 24.41 95 3.69 1.0 37.32 24.56 95 4.07 1.0 MAP0801T8 MAP0801T8 MAP0801T8 Cooling Only Heat Pump MMYMMYAP3201T8 AP3201HT8

Equivalent to 32HP AP3211T8 AP3211HT8 Inverter MAP0801T8 90.0 100.0 3 phase 50Hz 400V (380 415V) 43.08 28.65 96 3.14 1.0 40.69 26.78 95 3.73 1.0 Height 1,800 x Width 990 x Depth 750 256 258 Silky shade (Munsell 1Y8.5/0.5) Hermetic type (kW) (kW) (m/h) Cooling Only Heat Pump (kg) (kg) (MPa) (mm) (mm) (mm) 22.2 9,900 Finned tube 11.0 12.5 OFF : 2.90 ON : 3.73 ( 5) 2.3 2 Propeller fan 0.6 10,500 4.2 2 3.1 2 MAP1201T8 MAP1001T8 MAP1001T8 MMY- MAP0801HT8 MAP0801HT8 MAP0801HT8 MAP0801HT8 MAP1201HT8 MAP1001HT8 MAP1001HT8

Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2)

Running current Power factor

Power consumption (kW) Cooling Electrical characteristics ( 1) EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) Running current Power factor (A) (%) Power consumption (kW) Heating EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) External dimension Total weight Color Compressor Type Motor output Fan Motor output Air volume Heat exchanger Refrigerant R410A Charged amount ( 3) Cooling Only Heat Pump (mm) (kg) (kg)

Fan unit

High-pressure switch Protective devices Gas side Connecting Liquid side port dia. Balance side Gas side Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference Control wiring Central remote controller Max. No. of connected indoor units Sound level

28.6

22.2

12.7 9.5 Brazing Flare Flare

Refrigerant pipe spec. ( 4)

(m) (m) (m) (m)

175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( 6) Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m, and (Shield wire) 2.0mm x 2 cores up to 2000m 48

(dB(A))

63

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

74

50Hz

Equivalent HP Set Model name Outdoor unit type Outdoor unit model Cooling Only Heat Pump MMY(kW) (kW) (A) (%) 39.89 26.53 96 3.62 1.0 40.22 27.03 97 4.00 1.0 MAP1001T8 MAP0801T8 MAP0801T8 Cooling Only Heat Pump MMYMMYAP3401T8 AP3401HT8

Equivalent to 34HP AP3411T8 AP3411HT8 Inverter MAP0801T8 96.0 108.0 3 phase 50Hz 400V (380 415V) 50.26 33.08 95 2.90 1.0 44.42 29.54 96 3.66 1.0 Height 1,800 x Width 990 x Depth 750 256 258 Silky shade (Munsell 1Y8.5/0.5) Hermetic type (kW) (kW) (m/h) Cooling Only Heat Pump (kg) (kg) (MPa) Gas side Liquid side Balance side Gas side (mm) (mm) (mm) 22.2 10,500 9,900 Finned tube 11.0 12.5 OFF : 2.90 ON : 3.73 ( 5) 3.1 2 2.3 2 Propeller fan 0.6 10,500 4.2 2 3.1 2 MAP1201T8 MAP1201T8 MAP1001T8 MMY- MAP1001HT8 MAP0801HT8 MAP0801HT8 MAP0801HT8 MAP1201HT8 MAP1201HT8 MAP1001HT8

Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2)

Running current Power factor

Power consumption (kW) Cooling Electrical characteristics ( 1) EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) Running current Power factor (A) (%) Power consumption (kW) Heating EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) External dimension Total weight Color Compressor Type Motor output Fan Motor output Air volume Heat exchanger Refrigerant R410A Charged amount ( 3) Cooling Only Heat Pump (mm) (kg) (kg)

Fan unit

High-pressure switch Protective devices Connecting port dia.

28.6

22.2

12.7 9.5 Brazing Flare Flare

Refrigerant pipe spec. ( 4)

Connecting method

Liquid side Balance side (m) (m) (m) (m)

Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference

175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( 6) Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m, and (Shield wire) 2.0mm x 2 cores up to 2000m 48

Control wiring Central remote controller Max. No. of connected indoor units Sound level (dB(A))

63.5

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

75

50Hz

Equivalent HP Set Model name Outdoor unit type Outdoor unit model Cooling Only Heat Pump MMY(kW) (kW) (A) (%) 42.67 28.38 96 3.56 1.0 43.21 28.74 96 3.93 1.0 MAP1001T8 MAP1001T8 MAP0801T8 Cooling Only Heat Pump MMYMMYAP3601T8 AP3601HT8

Equivalent to 36HP AP3611T8 AP3611HT8 Inverter MAP0801T8 101.0 113.0 3 phase 50Hz 400V (380 415V) 57.06 37.16 94 2.72 1.0 48.36 31.49 94 3.59 1.0 Height 1,800 x Width 990 x Depth 750 256 258 Silky shade (Munsell 1Y8.5/0.5) Hermetic type (kW) (kW) (m/h) Cooling Only Heat Pump (kg) (kg) (MPa) (mm) (mm) (mm) 22.2 10,500 3.1 2 2.3 2 Propeller fan 0.6 9,900 Finned tube 11.0 12.5 OFF : 2.90 ON : 3.73 ( 5) 10,500 4.2 2 MAP1201T8 MAP1201T8 MAP1201T8 MMY- MAP1001HT8 MAP1001HT8 MAP0801HT8 MAP0801HT8 MAP1201HT8 MAP1201HT8 MAP1201HT8

Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2)

Running current Power factor

Power consumption (kW) Cooling Electrical characteristics ( 1) EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) Running current Power factor (A) (%) Power consumption (kW) Heating EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) External dimension Total weight Color Compressor Type Motor output Fan Motor output Air volume Heat exchanger Refrigerant R410A Charged amount ( 3) Cooling Only Heat Pump (mm) (kg) (kg)

Fan unit

High-pressure switch Protective devices Gas side Connecting Liquid side port dia. Balance side Gas side Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference Control wiring Central remote controller Max. No. of connected indoor units Sound level

28.6

12.7 9.5 Brazing Flare Flare

Refrigerant pipe spec. ( 4)

(m) (m) (m) (m)

175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( 6) Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m, and (Shield wire) 2.0mm x 2 cores up to 2000m 48

(dB(A))

63.5

64

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.
76

50Hz

Equivalent HP Set Model name Outdoor unit type Outdoor unit model Cooling Only Heat Pump Cooling Only Heat Pump MMYMMY-

Equivalent to 38HP AP3801T8 AP3801HT8 Inverter

Equivalent to 40HP AP4001T8 AP4001HT8

MMY- MAP1001T8 MAP1001T8 MAP1001T8 MAP0801T8 MAP1001T8 MAP1001T8 MAP1001T8 MAP1001T8 MMY- MAP1001HT8 MAP1001HT8 MAP1001HT8 MAP0801HT8 MAP1001HT8 MAP1001HT8 MAP1001HT8 MAP1001HT8 (kW) (kW) (A) (%) 3.51 1.0 46.36 30.83 96 3.88 1.0 Height 1,800 x Width 990 x Depth 750 256 258 Silky shade (Munsell 1Y8.5/0.5) Hermetic type (kW) (kW) (m/h) 10,500 9,900 Finned tube 11.0 12.5 OFF : 2.90 ( 5) (mm) (mm) (mm) 22.2 12.7 9.5 Brazing Flare Flare (m) (m) (m) (m) 175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( 6) Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m, and (Shield wire) 2.0mm x 2 cores up to 2000m 48 (dB(A)) 64 ON : 3.73 3.1 2 2.3 2 Propeller fan 0.6 10,500 3.1 2 3.83 1.0 106.5 119.5 3 phase 50Hz 400V (380 415V) 45.65 30.36 96 3.46 1.0 49.69 33.05 48.63 32.34 112.0 126.5

Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2)

Running current Power factor

Power consumption (kW) Cooling Electrical characteristics ( 1) EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) Running current Power factor (A) (%) Power consumption (kW) Heating EER (kW/kW) (Energy Efficiency Ratio) Starting current External dimension Total weight Color Compressor Type Motor output Fan Fan unit Heat exchanger Refrigerant R410A Charged amount ( 3) Cooling Only Heat Pump (kg) (kg) (MPa) Motor output Air volume Cooling Only Heat Pump (A) (mm) (kg) (kg)

High-pressure switch Protective devices Gas side Connecting Liquid side port dia. Balance side Gas side Refrigerant pipe spec. ( 4) Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference Control wiring Central remote controller Max. No. of connected indoor units Sound level

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

77

50Hz

Equivalent HP Set Model name Outdoor unit type Outdoor unit model Cooling Only Heat Pump Cooling Only Heat Pump MMYMMY-

Equivalent to 42HP AP4201T8 AP4201HT8 Inverter

Equivalent to 44HP AP4401T8 AP4401HT8

MMY- MAP1201T8 MAP1001T8 MAP1001T8 MAP1001T8 MAP1201T8 MAP1201T8 MAP1001T8 MAP1001T8 MMY- MAP1201HT8 MAP1001HT8 MAP1001HT8 MAP1001HT8 MAP1201HT8 MAP1201HT8 MAP1001HT8 MAP1001HT8 (kW) (kW) (A) (%) 118.0 132.0 3 phase 50Hz 400V (380 415V) 55.24 36.74 96 3.21 1.0 53.39 35.14 95 3.76 1.0 Height 1,800 x Width 990 x Depth 750 256 258 Silky shade (Munsell 1Y8.5/0.5) Hermetic type (kW) (kW) (m/h) 4.2 2 3.1 2 Propeller fan 0.6 10,500 Finned tube 11.0 12.5 OFF : 2.90 ( 5) (mm) (mm) (mm) 28.6 22.2 28.6 22.2 12.7 9.5 Brazing Flare Flare (m) (m) (m) (m) 175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( 6) Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m, and (Shield wire) 2.0mm x 2 cores up to 2000m 48 (dB(A)) 64.5 ON : 3.73 4.2 2 3.1 2 3.69 1.0 62.28 40.99 95 3.01 1.0 56.76 37.36 123.5 138.5

Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2)

Running current Power factor

Power consumption (kW) Cooling Electrical characteristics ( 1) EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) Running current Power factor (A) (%) Power consumption (kW) Heating EER (kW/kW) (Energy Efficiency Ratio) Starting current External dimension Total weight Color Compressor Type Motor output Fan Fan unit Heat exchanger Refrigerant R410A Charged amount ( 3) Cooling Only Heat Pump (kg) (kg) (MPa) Motor output Air volume Cooling Only Heat Pump (A) (mm) (kg) (kg)

High-pressure switch Protective devices Gas side Connecting Liquid side port dia. Balance side Gas side Refrigerant pipe spec. ( 4) Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference Control wiring Central remote controller Max. No. of connected indoor units Sound level

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

78

50Hz

Equivalent HP Set Model name Outdoor unit type Outdoor unit model Cooling Only Heat Pump Cooling Only Heat Pump MMYMMY-

Equivalent to 46HP AP4601T8 AP4601HT8 Inverter

Equivalent to 48HP AP4801T8 AP4801HT8

MMY- MAP1201T8 MAP1201T8 MAP1201T8 MAP1001T8 MAP1201T8 MAP1201T8 MAP1201T8 MAP1201T8 MMY- MAP1201HT8 MAP1201HT8 MAP1201HT8 MAP1001HT8 MAP1201HT8 MAP1201HT8 MAP1201HT8 MAP1201HT8 (kW) (kW) (A) (%) 2.85 1.0 60.55 39.85 95 3.64 1.0 Height 1,800 x Width 990 x Depth 750 256 258 Silky shade (Munsell 1Y8.5/0.5) Hermetic type (kW) (kW) (m/h) 4.2 2 3.1 2 Propeller fan 0.6 10,500 Finned tube 11.0 12.5 OFF : 2.90 ( 5) (mm) (mm) (mm) 28.6 22.2 28.6 12.7 9.5 Brazing Flare Flare (m) (m) (m) (m) 160 135 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( 6) Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m, and (Shield wire) 2.0mm x 2 cores up to 2000m 48 (dB(A)) 65 ON : 3.73 4.2 2 130.0 145.0 3 phase 50Hz 400V (380 415V) 69.27 45.59 95 2.72 1.0 64.19 41.80 94 3.59 1.0 75.47 49.67 135.0 150.0

Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2)

Running current Power factor

Power consumption (kW) Cooling Electrical characteristics ( 1) EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) Running current Power factor (A) (%) Power consumption (kW) Heating EER (kW/kW) (Energy Efficiency Ratio) Starting current External dimension Total weight Color Compressor Type Motor output Fan Fan unit Heat exchanger Refrigerant R410A Charged amount ( 3) Cooling Only Heat Pump (kg) (kg) (MPa) Motor output Air volume Cooling Only Heat Pump (A) (mm) (kg) (kg)

High-pressure switch Protective devices Gas side Connecting Liquid side port dia. Balance side Gas side Refrigerant pipe spec. ( 4) Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference Control wiring Central remote controller Max. No. of connected indoor units Sound level

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

79

60Hz

Outdoor unit (60Hz)


Equivalent HP Model name Outdoor unit type Cooling capacity ( Heat Pump MMYEquivalent to 5HP MAP0501HT7 Equivalent to 6HP MAP0601HT7 Equivalent to 8HP MAP0801HT7 Inverter unit Equivalent to 10HP MAP1001HT7 Equivalent to 12HP MAP1201HT7

* 1)

(kW)

14.0 16.0

16.0 18.0

22.4 25.0 3 phase 60Hz 380V

28.0 31.5

33.5 37.5

Standard heating capacity ( Power supply (

* 2)

1)

(kW)

Running current Power consumption Cooling Power factor EER (Energy Efficiency Ratio) Electrical characteristics ( 1) Starting current Running current Power consumption Heating Power factor EER (Energy Efficiency Ratio) Starting current External dimension Total weight Color Compressor Type Motor output Fan Fan unit Motor output Air volume Heat exchanger Refrigerant R410A (Charged refrigerant amount) ( High-pressure switch Protective devices Gas side Connecting port dia Liquid side Balance pipe Gas side Connecting Refrigerant Liquid side method piping Balance pipe specifications Max. equivalent length ( 4)

(A) (kW) (%) (kW/kW) (A) (A) (kW) (%) (kW/kW) (A) (mm) (kg)

6.16 3.65 90 3.84 1.0 6.41 3.84 91 4.17 1.0

7.66 4.64 92 3.45 1.0 7.45 4.56 93 3.95 1.0

9.07 5.67 95 3.95 1.0 9.40 5.88 95 4.25 1.0

12.16 7.68 96 3.65 1.0 12.61 7.97 96 3.95 1.0

19.27 11.92 94 2.81 1.0 16.47 10.19 94 3.68 1.0

Height 1,800 x Width 990 x Depth 750 228 Silky shade (Munsell 1Y8.5/0.5) Hermetic type 258

(kW)

1.1 2

1.4 2

2.3 2 Propeller fan

3.1 2

4.2 2

(kW) (m/h) 9,000

0.60 9,900 Finned tube 10,500

* 3)

(kg) (MPa)

R410A (8.5) OFF : 2.95 (

R410A (12.5) ON : 3.73

* 5)
22.2 12.7 28.6

(mm) (mm) (mm)

15.9 9.5

19.1

9.5 Flare Flare Flare Brazing

(m) (m) (m) (m)

175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 (

Max. real length Max. total pipe length (Real length) Max. height difference

* 6)
20 59

Control wiring Central remote controller Max. No. of connected indoor units Sound level (dB(A))

Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 pcs. up to 1000m and (Shield wire) 2.0mm x 2 pcs. up to 2000m 8 55 10 56 13 57 16 58

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

80

60Hz

Outdoor unit (Combination) (60Hz)


Equivalent HP Set Model name Outdoor unit type Outdoor unit model Heat Pump Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2) Heat Pump MMYEquivalent to 14HP AP1401HT7 Equivalent to 16HP AP1601HT7 Inverter MMY- MAP0801HT7 MAP0601HT7 MAP0801HT7 MAP0801HT7 MAP1001HT7 MAP0801HT7 MAP1001HT7 MAP1001HT7 (kW) (kW) (A) (kW) (%) 38.4 43.0 17.97 11.12 94 3.45 1.0 17.72 10.96 94 3.92 1.0 258 228 Hermetic type (kW) (kW) (m/h) 9,900 12.5 9,000 8.5 OFF : 2.90 ( Gas side Connecting Liquid side port dia. Balance side Gas side Refrigerant pipe spec. ( 4) Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference Control wiring Central remote controller Max. No. of connected indoor units Sound level (dB(A)) (m) (m) (m) (m) (mm) (mm) (mm) 22.2 12.7 19.1 9.5 9.5 Brazing Flare Flare 175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m and (Shield wire) 2.0mm x 2 cores up to 2000m 23 59.5 27 60 30 60.5 33 61 9,900 2.3 2 1.4 2 2.3 2 0.6 10,500 Finned tube 12.5 ON : 3.73 9,900 10,500 3.1 2 Propeller fan 2.3 2 3.1 2 45 50.5 3 phase 60Hz 380V 19.51 12.20 95 3.69 1.0 19.64 12.28 95 4.07 1.0 22.41 14.16 96 3.56 1.0 22.74 14.37 96 3.93 1.0 258 Silky shade (Munsell 1Y8.5/0.5) Type Motor output Fan Fan unit Motor output Air volume Heat exchanger Refrigerant R410A Charged amount ( 3) High-pressure switch Protective devices 25.59 16.17 96 3.46 1.0 26.05 16.46 96 3.83 1.0 50.4 56.5 56.0 63.0 Equivalent to 18HP AP1801HT7 Equivalent to 20HP AP2001HT7

Running current Power consumption Power factor

Cooling

EER (kW/kW) (Energy Efficiency Ratio) Electrical characteristics ( 1) Starting current Running current Power consumption Heating Power factor (A) (A) (kW) (%)

EER (kW/kW) (Energy Efficiency Ratio) Starting current External dimension Total weight Color Compressor (A) (mm) (kg)

Height 1,800 x Width 990 x Depth 750

(kg) (MPa)

* 5)

22.2 12.7

* 6)

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

81

60Hz

Equivalent HP Set Model name Outdoor unit type Outdoor unit model Heat Pump MMY(kW) (kW) (A) 27.81 17.39 MAP0801HT7 MAP0801HT7 Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2) Heat Pump MMYAP2201HT7

Equivalent to 22HP AP2211HT7 Inverter MAP0601HT7 61.5 69.0 3 phase 60Hz 380V 32.64 20.41 95 3.54 1.0 27.75 17.35 95 3.98 1.0 Height 1,800 x Width 990 x Depth 750 258 228 Silky shade (Munsell 1Y8.5/0.5) Type Motor output Fan Motor output Air volume (kW) (kW) (m/h) 9,900 12.5 OFF : 2.90 ( 5) Gas side Connecting Liquid side port dia. Balance side Gas side Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference (m) (m) (m) (m) (mm) (mm) (mm) 22.2 12.7 19.1 9.5 9.5 Brazing Flare Flare 175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( 6) Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m, and (Shield wire) 2.0mm x 2 cores up to 2000m 37 (dB(A)) 61.5 28.6 12.7 22.2 2.3 2 Hermetic type 1.4 2 Propeller fan 0.6 9,000 Finned tube 8.5 ON : 3.73 10,500 12.5 4.2 2 3.1 2 258 3.69 1.0 3.01 1.0 29.88 18.68 MAP1201HT7 MAP1001HT7

Running current

Power consumption (kW) (%) Cooling Power factor EER (kW/kW) (Energy Efficiency Ratio) Electrical characteristics ( 1) Starting current Running current (A) (A)

Power consumption (kW) (%) Heating Power factor EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) (mm) (kg)

External dimension Total weight Color Compressor

Fan unit

Heat exchanger Refrigerant R410A Charged amount ( 3) High-pressure switch Protective devices

(kg) (MPa)

Refrigerant pipe spec. ( 4)

Control wiring Central remote controller Max. No. of connected indoor units Sound level

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

82

60Hz

Equivalent HP Set Model name Outdoor unit type Outdoor unit model Heat Pump MMY(kW) (kW) (A) (%) 29.19 18.44 96 3.69 1.0 29.43 18.79 97 4.07 1.0 MAP0801HT7 MAP0801HT7 Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2) Heat Pump MMYAP2401HT7

Equivalent to 24HP AP2411HT7 Inverter MAP0801HT7 68.0 76.5 3 phase 60Hz 380V 40.02 25.02 95 2.72 1.0 33.74 21.32 96 3.59 1.0 Height 1,800 x Width 990 x Depth 750 258 Silky shade (Munsell 1Y8.5/0.5) Type Motor output Fan Motor output Air volume (kW) (kW) (m/h) 9,900 Finned tube 12.5 OFF : 2.90 ( 5) (mm) (mm) (mm) 22.2 28.6 12.7 9.5 Brazing Flare Flare (m) (m) (m) (m) 175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( 6) Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m, and (Shield wire) 2.0mm x 2 cores up to 2000m 40 (dB(A)) 62 ON : 3.73 2.3 2 Propeller fan 0.6 10.500 Hermetic type 4.2 2 MAP1201HT7 MAP1201HT7

Running current Power factor

Power consumption (kW) Cooling EER (kW/kW) (Energy Efficiency Ratio) Electrical characteristics ( 1) Starting current Running current Power factor (A) (A) (%)

Power consumption (kW) Heating EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) (mm) (kg)

External dimension Total weight Color Compressor

Fan unit

Heat exchanger Refrigerant R410A Charged amount ( 3) High-pressure switch Protective devices Gas side Connecting Liquid side port dia. Balance side Gas side Refrigerant pipe spec. ( 4) Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference Control wiring Central remote controller Max. No. of connected indoor units Sound level

(kg) (MPa)

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

83

60Hz

Equivalent HP Set Model name Outdoor unit type Outdoor unit model Heat Pump Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2) Heat Pump MMY-

Equivalent to 26HP AP2601HT7

Equivalent to 28HP AP2801HT7 Inverter

Equivalent to 30HP AP3001HT7

MMY- MAP1001HT7 MAP0801HT7 MAP0801HT7 MAP1001HT7 MAP1001HT7 MAP0801HT7 MAP1001HT7 MAP1001HT7 MAP1001HT7 (kW) (kW) (A) (%) 3.60 1.0 32.80 20.51 95 3.97 1.0 73 81.5 32.11 20.29 78.5 88.0 3 phase 60Hz 380V 35.25 22.27 96 3.52 1.0 35.77 22.60 96 3.89 1.0 Height 1,800 x Width 990 x Depth 750 258 Silky shade (Munsell 1Y8.5/0.5) Hermetic type (kW) (kW) (m/h) 10,500 9,900 10,500 Finned tube 12.5 OFF : 2.90 ( 5) 22.2 12.7 9.5 Brazing Flare Flare (m) (m) (m) (m) 175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( 6) Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m, and (Shield wire) 2.0mm x 2 cores up to 2000m 43 (dB(A)) 62 47 62.5 48 63 ON : 3.73 2.3 2 3.1 2 Propeller fan 0.6 9,900 10,500 2.3 2 3.1 2 3.46 1.0 38.88 24.82 97 3.83 1.0 38.40 24.26 84.0 95.0

Running current Power factor

Power consumption (kW) Cooling EER (kW/kW) (Energy Efficiency Ratio) Electrical characteristics ( 1) Starting current Running current Power factor (A) (A) (%)

Power consumption (kW) Heating EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) (mm) (kg) Type Motor output Fan Motor output Air volume

External dimension Total weight Color Compressor

Fan unit

Heat exchanger Refrigerant R410A Charged amount ( 3) High-pressure switch Protective devices Gas side Connecting Liquid side port dia. Balance side Gas side Refrigerant pipe spec. ( 4) Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference Control wiring Central remote controller Max. No. of connected indoor units Sound level (mm) (mm) (mm)

(kg) (MPa)

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

84

60Hz

Equivalent HP Set Model name Outdoor unit type Outdoor unit model Heat Pump Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2) Heat Pump MMYAP3201HT7

Equivalent to 32HP AP3211HT7 Inverter MMY- MAP0801HT7 MAP0801HT7 MAP0801HT7 MAP0801HT7 MAP1201HT7 MAP1001HT7 MAP1001HT7 (kW) (kW) (A) (%) 39.04 24.41 95 3.69 1.0 39.28 24.56 95 4.07 1.0 Height 1,800 x Width 990 x Depth 750 258 Silky shade (Munsell 1Y8.5/0.5) Type Motor output Fan Motor output Air volume (kW) (kW) (m/h) 9,900 Finned tube 12.5 OFF : 2.90 ( 5) Gas side Connecting Liquid side port dia. Balance side Gas side Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference (m) (m) (m) (m) (mm) (mm) (mm) 22.2 28.6 22.2 12.7 9.5 Brazing Flare Flare 175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( 6) Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m, and (Shield wire) 2.0mm x 2 cores up to 2000m 48 (dB(A)) 63 ON : 3.73 2.3 2 Propeller fan 0.6 10,500 Hermetic type 4.2 2 3.1 2 90.0 100.0 3 phase 60Hz 380V 45.34 28.65 96 3.14 1.0 42.83 26.78 95 3.73 1.0

Running current Power factor

Power consumption (kW) Cooling EER (kW/kW) (Energy Efficiency Ratio) Electrical characteristics ( 1) Starting current Running current Power factor (A) (A) (%)

Power consumption (kW) Heating EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) (mm) (kg)

External dimension Total weight Color Compressor

Fan unit Heat exchanger

Refrigerant R410A Charged amount ( 3) High-pressure switch Protective devices

(kg) (MPa)

Refrigerant pipe spec. ( 4)

Control wiring Central remote controller Max. No. of connected indoor units Sound level

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

85

60Hz

Equivalent HP Set Model name Outdoor unit type Outdoor unit model Heat Pump Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2) Heat Pump MMYAP3401HT7

Equivalent to 34HP AP3411HT7 Inverter MMY- MAP1001HT7 MAP0801HT7 MAP0801HT7 MAP0801HT7 MAP1201HT7 MAP1201HT7 MAP1001HT7 (kW) (kW) (A) (%) 41.99 26.53 96 3.62 1.0 42.34 27.03 97 4.00 1.0 Height 1,800 x Width 990 x Depth 750 258 Silky shade (Munsell 1Y8.5/0.5) Type Motor output Fan Motor output Air volume (kW) (kW) (m/h) 10,500 9,900 Finned tube 12.5 OFF : 2.90 ( 5) Gas side Connecting Liquid side port dia. Balance side Gas side Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference (m) (m) (m) (m) (mm) (mm) (mm) 22.2 28.6 22.2 12.7 9.5 Brazing Flare Flare 175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( 6) Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m, and (Shield wire) 2.0mm x 2 cores up to 2000m 48 (dB(A)) 63.5 ON : 3.73 3.1 2 2.3 2 Propeller fan 0.6 10,500 Hermetic type 4.2 2 3.1 2 96.0 108.0 3 phase 60Hz 380V 52.91 33.08 95 2.90 1.0 46.75 29.54 96 3.66 1.0

Running current Power factor

Power consumption (kW) Cooling EER (kW/kW) (Energy Efficiency Ratio) Electrical characteristics ( 1) Starting current Running current Power factor (A) (A) (%)

Power consumption (kW) Heating EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) (mm) (kg)

External dimension Total weight Color Compressor

Fan unit Heat exchanger

Refrigerant R410A Charged amount ( 3) High-pressure switch Protective devices

(kg) (MPa)

Refrigerant pipe spec. ( 4)

Control wiring Central remote controller Max. No. of connected indoor units Sound level

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

86

60Hz

Equivalent HP Set Model name Outdoor unit type Outdoor unit model Heat Pump Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2) Heat Pump MMYAP3601HT7

Equivalent to 36HP AP3611HT7 Inverter MMY- MAP1001HT7 MAP1001HT7 MAP0801HT7 MAP0801HT7 MAP1201HT7 MAP1201HT7 MAP1201HT7 (kW) (kW) (A) (%) 44.92 28.38 96 3.56 1.0 45.49 28.74 96 3.93 1.0 Height 1,800 x Width 990 x Depth 750 258 Silky shade (Munsell 1Y8.5/0.5) Type Motor output Fan Motor output Air volume (kW) (kW) (m/h) 10,500 9,900 Finned tube 12.5 OFF : 2.90 ( 5) Gas side Connecting Liquid side port dia. Balance side Gas side Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference (m) (m) (m) (m) (mm) (mm) (mm) 22.2 28.6 12.7 9.5 Brazing Flare Flare 175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( 6) Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m, and (Shield wire) 2.0mm x 2 cores up to 2000m 48 (dB(A)) 63.5 64 ON : 3.73 3.1 2 Hermetic type 2.3 2 Propeller fan 0.6 10,500 4.2 2 101.0 113.0 3 phase 60Hz 380V 60.06 37.16 94 2.72 1.0 50.90 31.49 94 3.59 1.0

Running current Power factor

Power consumption (kW) Cooling EER (kW/kW) (Energy Efficiency Ratio) Electrical characteristics ( 1) Starting current Running current Power factor (A) (A) (%)

Power consumption (kW) Heating EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) (mm) (kg)

External dimension Total weight Color Compressor

Fan unit Heat exchanger

Refrigerant R410A Charged amount ( 3) High-pressure switch Protective devices

(kg) (MPa)

Refrigerant pipe spec. ( 4)

Control wiring Central remote controller Max. No. of connected indoor units Sound level

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

87

60Hz

Equivalent HP Set Model name Outdoor unit type Outdoor unit model Heat Pump Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2) Heat Pump MMY-

Equivalent to 38HP AP3801HT7 Inverter

Equivalent to 40HP AP4001HT7

MMY- MAP1001HT7 MAP1001HT7 MAP1001HT7 MAP0801HT7 MAP1001HT7 MAP1001HT7 MAP1001HT7 MAP1001HT7 (kW) (kW) (A) (%) 3.51 1.0 48.79 30.83 96 3.88 1.0 Height 1,800 x Width 990 x Depth 750 258 Silky shade (Munsell 1Y8.5/0.5) Hermetic type (kW) (kW) (m/h) 10,500 9,900 Finned tube 12.5 OFF : 2.90 ( 5) (mm) (mm) (mm) 22.2 12.7 9.5 Brazing Flare Flare (m) (m) (m) (m) 175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( 6) Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m, and (Shield wire) 2.0mm x 2 cores up to 2000m 48 (dB(A)) 64 ON : 3.73 3.1 2 2.3 2 Propeller fan 0.6 10,500 3.1 2 3.83 1.0 106.5 119.5 3 phase 60Hz 380V 48.05 30.36 96 3.46 +.0 52.31 33.05 51.18 32.34 112.0 126.5

Running current Power factor

Power consumption (kW) Cooling EER (kW/kW) (Energy Efficiency Ratio) Electrical characteristics ( 1) Starting current Running current Power factor (A) (A) (%)

Power consumption (kW) Heating EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) (mm) (kg) Type Motor output Fan Motor output Air volume

External dimension Total weight Color Compressor

Fan unit Heat exchanger

Refrigerant R410A Charged amount ( 3) High-pressure switch Protective devices Gas side Connecting Liquid side port dia. Balance side Gas side Refrigerant pipe spec. ( 4) Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference Control wiring Central remote controller Max. No. of connected indoor units Sound level

(kg) (MPa)

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

88

60Hz

Equivalent HP Set Model name Outdoor unit type Outdoor unit model Heat Pump Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2) Heat Pump MMY-

Equivalent to 42HP AP4201HT7 Inverter

Equivalent to 44HP AP4401HT7

MMY- MAP1201HT7 MAP1001HT7 MAP1001HT7 MAP1001HT7 MAP1201HT7 MAP1201HT7 MAP1001HT7 MAP1001HT7 (kW) (kW) (A) (%) 118.0 132.0 3 phase 60Hz 380V 58.15 36.74 96 3.21 1.0 56.20 35.14 95 3.76 1.0 Height 1,800 x Width 990 x Depth 750 258 Silky shade (Munsell 1Y8.5/0.5) Hermetic type (kW) (kW) (m/h) 4.2 2 3.1 2 Propeller fan 0.6 10,500 Finned tube 12.5 OFF : 2.90 ( 5) (mm) (mm) (mm) 28.6 22.2 28.6 22.2 12.7 9.5 Brazing Flare Flare (m) (m) (m) (m) 175 150 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( 6) Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m, and (Shield wire) 2.0mm x 2 cores up to 2000m 48 (dB(A)) 64.5 ON : 3.73 4.2 2 3.1 2 3.69 1.0 60.56 40.99 95 3.01 1.0 59.75 37.36 123.5 138.0

Running current Power factor

Power consumption (kW) Cooling EER (kW/kW) (Energy Efficiency Ratio) Electrical characteristics ( 1) Starting current Running current Power factor (A) (A) (%)

Power consumption (kW) Heating EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) (mm) (kg) Type Motor output Fan Motor output Air volume

External dimension Total weight Color Compressor

Fan unit Heat exchanger

Refrigerant R410A Charged amount ( 3) High-pressure switch Protective devices Gas side Connecting Liquid side port dia. Balance side Gas side Refrigerant pipe spec. ( 4) Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference Control wiring Central remote controller Max. No. of connected indoor units Sound level

(kg) (MPa)

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

89

60Hz

Equivalent HP Set Model name Outdoor unit type Outdoor unit model Heat Pump Rated cooling capacity ( 1) Standard heating capacity ( 1) Power supply ( 2) Heat Pump MMY-

Equivalent to 46HP AP4601HT7 Inverter

Equivalent to 48HP AP4801HT7

MMY- MAP1201HT7 MAP1201HT7 MAP1201HT7 MAP1001HT7 MAP1201HT7 MAP1201HT7 MAP1201HT7 MAP1201HT7 (kW) (kW) (A) (%) 2.85 1.0 63.73 39.85 95 3.64 1.0 Height 1,800 x Width 990 x Depth 750 258 Silky shade (Munsell 1Y8.5/0.5) Hermetic type (kW) (kW) (m/h) 4.2 2 3.1 2 Propeller fan 0.6 10,500 Finned tube 12.5 OFF : 2.90 ( 5) (mm) (mm) (mm) 28.6 22.2 28.6 12.7 9.5 Brazing Flare Flare (m) (m) (m) (m) 160 135 (However, if equivalent bend length is longer, equivalent length is the standard.) 300 Outdoor unit is higher than indoor unit : 50 Outdoor unit is lower than indoor unit : 40 ( 6) Shield wire 1.25mm x 2 cores. up to 2000m When connecting to outdoor unit : (Shield wire) 1.25mm x 2 cores up to 1000m, and (Shield wire) 2.0mm x 2 cores up to 2000m 48 (dB(A)) 65 ON : 3.73 4.2 2 130.0 145.0 3 phase 60Hz 380V 72.92 45.59 95 2.72 1.0 67.56 41.80 94 3.59 1.0 79.44 49.67 135.0 150.0

Running current Power factor

Power consumption (kW) Cooling EER (kW/kW) (Energy Efficiency Ratio) Electrical characteristics ( 1) Starting current Running current Power factor (A) (A) (%)

Power consumption (kW) Heating EER (kW/kW) (Energy Efficiency Ratio) Starting current (A) (mm) (kg) Type Motor output Fan Motor output Air volume

External dimension Total weight Color Compressor

Fan unit Heat exchanger

Refrigerant R410A Charged amount ( 3) High-pressure switch Protective devices Gas side Connecting Liquid side port dia. Balance side Gas side Refrigerant pipe spec. ( 4) Connecting Liquid side method Balance side Max. equivalent length Max. real length Max. total pipe length (Real length) Max. height difference Control wiring Central remote controller Max. No. of connected indoor units Sound level

(kg) (MPa)

*1 : Rated conditions * * *

Cooling : Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB Heating : Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB The standard piping measns that main pipe length is 5m, branching pipe length 2.5m of branch piping connected with a 0 meter height. 2 : The source voltage must not fluctuate more than 10%. 3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length. 4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.

System safety protection


temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure switch, Over-current sensor, *5 : Discharge High-pressure sensor, Low pressure sensor, Over-current relay. *6 : 30m when the height difference between indoor units exceeds 3m.

90

10. FAN CHARACTERISTICS


In case of square duct flange of discharge section
MMD-AP0071BH, AP0091BH
140

MMD-AP0121BH
140

Standard air volume: 480m/h

Standard air volume: 570m/h

Hi
120

gh

Hi -st a ti cp re s
120

gh

-st

a ti

cp

su

re

lim it

2H

Ap pl ica tio n

ta p
A
100

l pp

ic a

n tio

lim

it

re s

su

re

2H

ta p

100

Hig h

External static pressure (Pa)

pre ss ure

1H

External static pressure (Pa)

sta t

ic

Hi gh sta tic

pr es su re 1H

tap
Air volume limit (Max)

tap

80

80

Air volume limit (Min)

ard

Air volume limit (Min)

nd

Ht

ap

tap

60

60

Lo w

40

Lo ws tat ic p res su re H

sta tic pre ss ure H

tap

tap

40

Sta

nd

S ta

ard

nd

Lt

ard

ap
20

Lt

ap

20

Long life filter


0 200 400 480 600 0 300

Long life filter


500 570 700

Air volume (m/h)

Air volume (m/h)

MMD-AP0151BH
140

MMD-AP0181BH
Standard air volume: 650m/h
140

Standard air volume: 780m/h

120

Hig
lim it

Hig
h -s tatic p re
120

h -s

tatic

p re

ssu

ssu

Ap
100

c p li

at

io n

re 2

H ta

p
100

n tio ca pli p A

it lim

re 2

H ta

Air volume limit (Max)

Sta

St an da rd H

Hig h st

External static pressure (Pa)

High stat ic p ress ure 1H


80

tap
Air volume limit (Max)

External static pressure (Pa)

atic pre ssu re 1 H ta p

80

Air volume limit (Min)

60

Sta nda rd H

Sta nda rd H

tap

tap

60

Low

sta

tic

40

pre

Low sta tic pre ssu re

ssu

re H

40

Ht ap

tap
Sta nda rd L ta

Sta nda rd L
20

tap
20

Long life filter


0 1200 600 350 2000 0 500

Long life filter


700 780 900

Air volume (m/h)

Air volume (m/h)

91

Air volume limit (Max)

Air volume limit (Min)

MMD-AP0241BH, AP0271BH
Standard air volume: 1140m/h

MMD-AP0301BH
Standard air volume: 1260m/h

140

140

120

Ap
100

plic

o a ti

nl

im

it

High-s tatic p ressu re 2H

120

tap

it lim tion a c i pl Ap
100

High -stati c pre ssure 2H

tap

External static pressure (Pa)

tap

External static pressure (Pa)

High s tatic p ressure 1H

High static press ure 1 H

tap

80

80

Air volume limit (Min)

Air volume limit (Max)

Air volume limit (Min)

Stand

Stand

ard H

ard H

60

tap

tap

60

Low s

tatic p

Low

ressu

static

re H

press

tap

ure H

tap

40

40

Stand ard L tap

Stand
20

ard L

tap

20

0 800

Long life filter


1000 1140 1200 600

0 300

Long life filter


1100 1260 1300

Air volume (m/h)

Air volume (m/h)

MMD-AP0361BH
140

MMD-AP0481BH, AP0561BH
Standard air volume: 1620m/h
140

Standard air volume: 1980m/h

120

tio ca pli Ap
100

it lim

High -stati c pre ssure 2H

tap

120

Ap
High
100

ca pli

tio

nl

im

it

Hig h-st atic pre ssu re 2 H ta p

External static pressure (Pa)

s u re

External static pressure (Pa)

static

pre s

High

1H ta

stat ic p

ress

ure

1H

tap

80

80

Air volume limit (Max)

Air volume limit (Min)

Air volume limit (Min)

Stan

d a rd

St a

nda

H tap

rd H

tap

60

60

40

Low static press ure H

Low

stati

c pre

ssur

eH

tap

tap

40

Stan dard L tap


20 20

Stan dard L

tap

0 1200

Long life filter


1620 2000

Long life filter


0 1400 1800 1980 2200 900

Air volume (m/h)

Air volume (m/h)

92

Air volume limit (Max)

Air volume limit (Max)

Concealed Duct High Static Pressure type


MMD-AP0181H
Fan motor current (A)
1.5 Standard air volume: 900 m/h

MMD-AP0241H, AP0271H
Fan motor current (A)
2.0 Standard air volume: 1,320 m/h

High static pressure tap

High static pressure tap


Medium static pressure tap

Medium static pressure tap


1.0

1.5

0.5

Low static pressure tap

1.0

Low static pressure tap

300 250
Hi

50Hz 60Hz
gh pre

Air volume lower limit

250

50Hz 60Hz
st at ic

Outside static pressure (Pa)

Air volume lower limit

ss

ed

ure

Outside static pressure (Pa)

200

s ta

tic

Air volume upper limit

iu

ta p

200

150

st

ed

at

iu

ic

pr es su re

pr

Lo w

es

st

ta p

su

150

at

ic

100

st

re

pr

at

ta

es

ic

su

re

pr

ta

es

su

100

re

ta

50

50

700

800

900

1,000

1,100

0 1,000

1,100

1,200

1,320 1,300 1,400 Air volume (m/h)

1,500

1,600

Air volume (m/h)

MMD-AP0361H
Standard air volume: 1,600 m/h 2.5

MMD-AP0481H
3.0 Standard air volume: 2,100 m/h

Fan motor current (A)

Fan motor current (A)

High static pressure tap


2.0

High static pressure tap


2.5

Medium static pressure tap


1.5

2.0

Medium static pressure tap

Low static pressure tap


1.0

1.5

Low static pressure tap


0.5 50Hz 60Hz

Air volume upper limit

250

Hig

250 50Hz Hig hs 60Hz tat ic pre ss ure M tap ed ium sta tic pr es su re Lo ta p w st at ic pr es su re ta p

Air volume lower limit

Outside static pressure (Pa)

Air volume lower limit

ap

Outside static pressure (Pa)

200
Me d iu

pre

ssu

re t

200

150

s ta

t ic

p re

ssu

re

ta p

150

100

Lo ws

ta t

100

ic p

re s

su

re

50

ta p

50

1,400

1,500

1,600

1,700

1,800

2,100 1,500 2,000 Air volume (m/h) 2,500

Air volume (m/h)

93

Air volume upper limit

h st

atic

Air volume upper limit

Hi gh

w Lo st at ic pr es su re

ta p

MMD-AP0721H
8 7.5

Standard air volume : 3600m/h


High static pressure tap (60Hz)

Current of fan motor (A)

7 6.5 6 5.5 5 4.5

Medium static pressure tap (60Hz) Low static pressure tap (60Hz)

High static pressure tap (50Hz) Medium static pressure tap (50Hz)

Low static pressure tap


4

External static pressure (Pa)

300

High static pressure tap (50Hz)


250 200 150 100 50 5 3000 2880 3200 3400 3600 3800 4000 4200 4320

High static pressure tap (60Hz) Medium static pressure tap (50Hz) Medium static pressure tap (60Hz) Low static pressure tap (60Hz)

Low static pressure tap (50Hz)

Lower limit of air volume

Air volume (m/h)

Upper limit of air volume

MMD-AP0961H
Standard air volume : 4200m/h
8.5 8

High static pressure tap (60Hz) Medium static pressure tap (60Hz) Low static pressure tap (60Hz) High static pressure tap (50Hz) Medium static pressure tap (50Hz)

Current of fan motor (A)

7.5 7 6.5 6 5.5 5 4.5 4

Low static pressure tap

External static pressure (Pa)

350

High static pressure tap (60Hz)


300

High static pressure tap (50Hz)


250 200 150 100 50

Medium static pressure tap (50Hz) Low static pressure tap (50Hz) Low static pressure tap (60Hz)
4200 4000 4400 4600 4800 5000 5040

5 3400 3800 3360 3600

Medium static pressure tap (60Hz)

Lower limit of air volume

Air volume (m/h)

Upper limit of air volume

REQUIREMENT
Add a air volume damper to the air supply duct, and adjust the air volume in the range from 80% to 120% of the standard air volume.

94

11.

DIMENSIONAL DRAWINGS

Indoor unit
4-way Air Discharge Cassette Type
MMU-AP0091H to P0561H
415 Suction grille (Air suction port) Electric parts box Air discharge port (4-way)
346.5 790 hanging bolt pitch 950 panel external dimension 860 to 910 ceiling open dimension

254.5

35

381.6 723 hanging bolt pitch

860 to 910 ceiling open dimension For branch duct knockout square hole 150 (2 positions at right side) Refrigerant pipe connecting port 840 (Gas) 250 70 Refrigerant pipe Drain discharge port 270 connecting port 105 (Liquid)
210
105

950 panel external dimension

Hanging bolt M10 or W3/8 local arrange 840 480 227


97 B 35

130

88

30

45 113 174

Bottom face of ceiling

Bottom face of ceiling


360
Stand-up 640 or less Stand-up 850 or less 15 or more

Model AP0091H to AP0301H AP0361H to AP0561H


15 or more

A 250 319

mm B 120 183

.5 57 5 2

18

Bottom face of ceiling Knockout for simple OA For 100

64

(NOTE) As ABS is used for the drain discharge port of the main unit, the vinyl chloride paste cannot be used. Use the flexible hose (Band fix) included in the package.

Z view

Drain-up standing-up size

Space required for installation and servicing

Wired remote controller (RBC-AMT21E)


4
2.7

200

120

Check port ( 450) 16 Check port ( 450)


200

120

95

1000 or more

57

1000 or more

1000 or more

Indoor unit

Bottom face of ceiling

2-way Air Discharge Cassette Type


MMU-AP0071WH, AP0091WH, AP0121WH

Z view
Center of main unit 35 Center of panel Electric parts box 95
Hanging bolt pitch 480 Unit external dimension 550 Ceiling open dimension 620 Panel external dimension 650

Air discharge port (2-way) 1000

Air discharge port (2-way)

30 Unit external dimension 830 Hanging bolt pitch 880 Ceiling open dimension 960 Panel external dimension 1000

5mm or more Ceiling 1000 or more Obstruction 1000 or more 1000 or more
20 0

265

Hanging bolt 4-M10 procured locally

398

222

Ceiling panel (Procured by locally)

156

Bottom face of ceiling

Branch duct knockout hole (Provided also at the reverse side)

Space required for installation and servicing

160mm or less

Refrigerant pipe connecting port (Gas side 9.5) 100 Refrigerant pipe connecting port (Liquid side 6.4)

Drain pipe connecting port Inner 32, Nominal 25 for vinyl chloride pipe 56 75 55 Pour water port

508mm or less

100mm or less Indoor unit

35 210 Power supply connecting port


78

35

Knockout hole for taking-in air (Only at reverse side)

Bottom face of ceiling

96

178 242 282 348

150

53

60

650

MMU-AP0151WH, AP0181WH, AP0241WH, AP0271WH. AP0301WH

Z view
Center of main unit 35 Center of panel Electric parts box 95
Unit external dimension 550 Ceiling open imension 620 Panel external dimension 650 Hanging bolt pitch 480

Air discharge port (2-way)

Air suction port (2-way)

30 Unit external dimension 1350 Hanging bolt pitch 1400 Ceiling open dimension 1480 Panel external dimension 1520

5mm or more

295
0 20

Hanging bolt 4-M10 procured locally

398

Ceiling

Obstruction

1000 or more

1000 or more

Space required for installation and servicing

Ceiling panel (Procured by locally)

156

1000 or more

222

Bottom face of ceiling

Branch duct knockout hole (Provided also at the reverse side)

160mm or less

Refrigerant pipe connecting port (Gas side B) 56 Refrigerant pipe connecting port 100 (Liquid side A)
508mm or less

Drain pipe connecting port Inner 32, Nominal 25 for vinyl chloride pipe 75 55 Pour water port

35
78

35

100mm or less

210 Power supply connecting port

Knockout hole for taking-in air (Only at reverse side) A 6.4 9.5 B 12.7 15.9

Bottom face of ceiling Model MMU-AP0151WH to AP0181WH MMU-AP0241WH to AP0301WH

97

178 242 282 348

150

53

60

650

MMU-AP0481WH
Z view
Center of main unit 95 5 Center of panel Electric parts box 105
Unit external dimension 620 Ceiling open dimension 650 Panel external dimension 680

Air discharge port (2-way) 1898


Hanging bolt pitch 510

Air suction port (2-way)

Unit external dimension 1650 Hanging bolt pitch 1700 Ceiling open dimension 1850 Panel external dimension 1898 Hanging bolt 4-M10 procured locally

5mm or more

455
2 00

150
2 00

406

1000 or more Ceiling 1000 Obstruction or more 1000 or more

230 166

60

Space required for installation and servicing

Ceiling panel (Procured by locally)

Bottom face of ceiling

Branch duct knockout hole (Provided also at the reverse side)

160mm or less

516mm or less

100mm or less

Refrigerant pipe connecting port (Gas side 15.9) Refrigerant pipe 56 connecting port 100 (Liquid side 9.5)

Drain pipe connecting port (VP25) 75 55 Pour water port


50 1

210 Power supply Knockout hole for taking-in air connecting port (Only at reverse side)

Wired remote controller (RBC-AMT21E)


4
2.7

120

120

16

98

86

Bottom face of ceiling

15

15

186 250 290 356

68

680

1-way Air Discharge Cassette Type


MMU-AP0071YH, AP0091YH, AP0121YH
Panel external dimension 1050 Ceiling open dimension 1010

Ceiling open dimension 430

20

Power supply connecting port Drain pipe connecting port (VP25) Center of panel

Hanging bolt 4-M10 procured locally

Refrigerant pipe connecting port (Gas side) 9.5 Discharge louver Refrigerant pipe connecting port (Liquid side) 6.4

Ceiling panel Procured by locally Air discharge port Bottom face of ceiling

Panel mounting hole 5 positions

Air suction port

Dimensions Wired remote controller (RBC-AMT21E)


4
2.7

Model MMUAP0071YH, AP0091YH, AP0121YH

20

Support metal

Panel external dimension 470

A 235

B 245

C 200

120

100 or more 120 16

100 or more

200 or more

Space required for installation and servicing

99

B or more

MMU-AP0151SH, AP0181SH, AP0241SH


150 knockout hole (For air taking-in)

96

20

30 65

Panel external dimension A Ceiling open dimension B Center of panel

30

Ceiling open dimension 695 Panel external dimension 755

530 655

20

30

50 10

E Pitch 200 N

F 10

110

80

100

130

100

100

Knockout hole for discharge forward

10

198

Refrigerant pipe connecting port (Liquid side) I Refrigerant pipe connecting port (Gas side) J Drain pipe connecting port (VP25)

Dimensions
Model MMUAP0151SH,AP0181SH AP0241SH A 1220 1420 B 1160 1360 C 545 645 D 485 585 E 530 630 F 470 570 G 254 460 H 800 1000 I 6.4 9.5 J 12.7 15.9 N 4 5

Wired remote controller (RBC-AMT21E)


2.7
4

200 or more

160 120 100

80 60

440 335 255

Z view

Air discharge port

Power supply connecting port

1000 or more 1000 or more Obstacle 1000 or more

Ceiling

Space required for installation and servicing


120

120

16

100

755

1 80
C

30 125 A

Suction port

Concealed Duct Standard Type


MMD-AP0071BH, AP0091BH, AP0121BH, AP0151BH, AP0181BH, AP0241BH, AP0271BH, AP0301BH, AP0361BH, AP0481BH, AP0561BH
Drain pipe connecting port (Inner 32 vinyl chloride pipe VP25 connection) Hanging bolt 4-M10 (Procured locally) 41 Hanging bolt pitch A 7.5 B 50 25 Unit external dimension 40 800 Hanging bolt pitch 700 59 638 498 393
41

(When attaching directly)

150

125 knockout hole (For air taking-in air)

142 Refrigerant pipe connecting port (Gas side F) 44

91

131 50

50 243

215

49

Air discharge

196

Air suction

70 to 270

10-4 tapping screw 160

Refrigerant pipe connecting port (Liquid side G)

26 power supply, remote controller wires drawing-out port

Panel C, L

Ceiling open dimension D

Ceiling opening 470

Air suction
Model MMD-

A 616 766 1066 1416

B 550 700 1000 1350

240
C 350 500 800 1150

D 600 750 1050 1400

D 600 750 1050 1400

E 470 620 920 1270

F 9.5 12.7 15.9 15.9

G 6.4 9.4 9.5 9.5

AP0071BH, AP0091BH, AP0121BH AP0151BH, AP0181BH AP0241BH, AP0271BH, AP0301BH AP0361BH, AP0481BH, AP0561BH

(Note) Two of high efficiency filter and deodorant filter cannot applied. (Note) Be sure to place a check port A at the position indicated in the following figure for maintenance of the equipment. Air outlet Ceiling opening part

(150mm) Check port A 450mm

550mm or less

300mm

100mm or less

Check port B 450mm Air filter 700mm for maintenance of air filter

Drain-up piping

700mm for maintenance of air filter

101

271mm or less

Concealed Duct High Static Pressure Type


MMD-AP0181H, AP0241H, AP0271H, AP0361H, AP0481H, AP0721H, AP0961H
MMD-AP0181H to AP0361H
710 (Hanging bolt mounting pitch 800)

MMD-AP0481H

Long hole for hanging bolt (4-12 72)

Power supply/ communication piping port (26) (Under electric parts box)

Long hole for hanging bolt (4-12 72) Power supply/ communication piping port (26) (Under electric parts box)

Electric parts box Refrigerant pipe connecting port (Gas side B)

Refrigerant pipe connecting port (Liquid side A)

Electric parts box Refrigerant pipe connecting port (Liquid side 9.5) Refrigerant pipe connecting port (Gas side 15.9)

Screw hole for duct mounting (6-M6) Air suction port Drain pipe connecting port (VP25)

Screw hole for duct mounting (8-M6) Air suction port Drain pipe connectingport (VP25) Z view

Z view

Z view

Screw hole for duct mounting (4-M6)

Air discharge port

Air discharge port Screw hole for duct mounting (6-M6)

Screw hole for duct mounting (8-M6)

Air discharge port

AP0181H to AP0271H type


Model MMDAP0181H AP0241H, AP0271H, AP0361H, AP0481H

AP0361H type
A 6.4 9.5 B 12.7 15.9

Space required for installation and servicing *1


500 mm or more 600 mm or more

Service space

MMD-AP0721H, AP0961H
1260 (Hanging bolt mounting pitch)

Check port 600

Service space

1380

*1

Long hole for hanging bolt (4-12 92) 1288 (Hanging bolt mounting pitch) 1328 Refrigerant pipe connecting port (Gas side 22.2) 1250
200 150

Service spaces for MMD-AP0721H and AP0961H are different from those in the above figure. For inquiries please contact us separately.

Electric parts box

100

Wired remote controller (RBC-AMT21E)


4
406

Refrigerant pipe connecting port (Liquid side 12.7) 190 250 250 250 250
470

45

624 698

Drain pipe connecting port (VP25)


370

65

Discharge port Screw hole for duct mounting (10-M6)

120

120

Screw hole for duct Suction port mounting (10-M6) 250 250 250 250 190

35

31

2.7

16

102

Under Ceiling Type


MMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H
Upper piping drawing-out port (Knockout hole) Power supply cable taking-in port (Knockout) Remote controller piping taking-in port (Knockout hole)

Piping drawing-out port (Knockout port)

320 170

(Hanging position)

70

Left drain size

Drain port VP20 (Inner diam. 26, hose attached)

B (Hanging position) Refrigerant pipe (Liquid side D) Refrigerant pipe (Gas side C)

Drain pipe connecting port

Model MMCAP0151H, AP0181H

A 910

B 855

C 12.7 15.9 15.9

D 6.4 9.5 9.5

AP0241H to AP0271H AP0361H, AP0481H

1180 1125 1595 1540

Wireless sensor mounting section (Option)

Hanging bolt

Within 50

Ceiling surface Unit

250 or more

250 or more (Front side is placed to a level.)

Space required for installation and servicing Wired remote controller (RBC-AMT21E)
4

Remote controller cable taking-in port Power supply taking-in port (Knockout hole) Remote controller cable taking-in port (Knockout hole)

2.7

120

Air taking-in port (Duct sold separately) (Knockout hole 92)


16

120

Piping hole on the wall (100 hole)

Drain left piping drawing-out port (Knockout hole)

103

500 or more

High Wall Type


MMK-AP0071H, AP0091H, AP0121H
Position of installation board hole

Long hole for wooden screw 15-6 30 690 (Installation board) Long hole for anchor bolt 10-10 20 long hole (Including installation board) 210 Including installation board (Accessory) Earth screw (M4) (Inner of electric parts box) Refrigerant pipe connecting port Gas side 9.5 9.5 Refrigerant pipe connecting port Liquid side 6.4

Upper end of installation board

Air suction port Discharge port (Air direction upward/downward/leftward/rightward is adjustable.) Piping port from left/right sides (Knockout hole) Gas pipe 440 Liquid pipe 540 Drain pipe 560 At shipment (When drawing pipe from left)

Drain pipe connecting port

300 or more

300 or more

Space required for service

Wired remote controller (RBC-AMT21E)


4
2.7

120

120

30 or more
16

104

MMK-AP0151H, AP0181H

Position of installation board hole

182.5

690 (Installation board)

Long hole for wooden screw 15-6 30 182.5 Long hole for anchor bolt 10-10 20 long hole

Upper end of installation board

(Including installation board) 210 Including installation board (Accessory) Earth screw (M4) (Inner of electric parts box) Refrigerant pipe Refrigerant pipe connecting port connecting port Liquid side 6.4 Gas side 12.7

Air suction port Air discharge port (Air direction upward/downward/leftward/rightward is adjustable.) Piping port from left/right sides (Knockout hole) Gas pipe 440 Liquid pipe 540 Drain pipe 560 At shipment (When drawing pipe from left)

Drain pipe connecting port

300 or more

300 or more

Space required for service

105

30 or more

MMK-AP0241H

Position of installation board hole

Long hole for wooden screw 21-6 30 170 1090 (Installation board) 170

Long hole for anchor bolt 16-10 20 long hole

Upper end of installation board

(Including installation board) 210 Including installation board (Accessory) Earth screw (M4) (Inner of electric parts box) Refrigerant pipe connecting port Gas side 15.9 Refrigerant pipe connecting port Liquid side 9.5

Air discharge port (Air direction upward/ Air suction port downward/leftward/rightward is adjustable.) Piping port from left/right sides (Knockout hole) Gas pipe 440 Liquid pipe 540 Drain pipe 560 At shipment (When drawing pipe from left)

Drain pipe connecting port

300 or more

300 or more

Space required for service

106

30 or more

Floor Standing Cabinet Type


MML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241H

Hole fixing floor (2-10)

Lower refrigerant piping port (50 100 knockout hole)

Air discharge port

130

Operation switch section (Sold separately) Hole fixing wall (10-20 knockout pulsometor hole 2)

Hole fixing wall (2-10 24 long hole)

Air suction port Refrigerant pipe port (50 100 knockout hole) (Both sides) 100 ( left side ) Earth screw (M6) Refrigerant pipe port (130 knockout hole)

Power supply cord hole (26 knockout) (Both sides)

Dimensions
Model MMLAP0071H, AP0091H, AP0121H AP0151H, AP0181H AP0241H A 9.5 12.7 15.9 B 6.4 6.4 9.5

Refrigerant pipe connecting port (Liquid side B) Refrigerant pipe connecting port (Gas side A) Drain pipe connecting port (20) Space required for service Piping positional Figure shows piping at the left side drawing Wall

1000 or more

(Front side) or more

500

300 or more

Wall (Front side)

107

Floor Standing Concealed Type


MML-AP0071BH, AP0091BH, AP0121BH, AP0151BH, AP0181BH, AP0241BH

Hole fixing floor

(Discharge port size in flange) Ceiling board section

150 or more (Service space) (Air discharge port size in flange)

150 or more (Service space)

2-4.7 hole (Left/right side each)

Expansion valve box G-4.7 hole (Front side and rear side each)

4-15 hole (For mounting rear side)

2-12 18 long hole (Hole fixing floor)

No.

Name Pipe connecting port at liquid side (E) Pipe connecting port at gas side (F) Drain pipe connecting port (20A) Electric parts box (Earth terminal is provided in inner side.) Air filter

Dimensions
Model MMLAP0071BH, AP0091BH, AP0121BH AP0151BH, AP0181BH AP0241BH A B C D 4 7 E 6.4 9.5 F 9.5 12.7 15.9 G 5 8 610 580 550 910 880 850

Wired remote controller (RBC-AMT21E)


4

2.7

120

120

16

108

Floor Standing Type


MMF-AP0151H, AP0181H, AP0241H, AP0271H
Wall of installing distance ( Incase ) 50mm from wall Lower refrigerant piping port (50 120 Knockout hole) Installation plate Discharge port 600 30 3 30 3 80 Wall

Wall

a
Control part Control cover

Wall

Space required for service (In case of right side piping )


Wall

More than 1000

Front

More Front than 500

More than 200

Wall

Floor Refrigerant piping port (Both side) (80 Knockout hole)

Installation plate

Dtain hose

Earth screw (M4)

Suction port Refrigerant piping hole (Back side) (130 Knockout hole)

Refrigerant piping hole (Bottom side) (50 120 Knockout hole) Refrigerant piping joint (Gas side A)

Refrigerant piping position

Dimensions
Model MMF-AP0151H, AP0181H MMF-AP0241H, AP0271H A 12.7 15.7 B 6.4 9.5
Refrigerant piping joint (Liquid side B)

Details of hole for back side piping


In case a 1770 In case b 1773

Details of hole for lower side piping

2- lower hole For M8 Screw bolt or M8 Anchor bolt

4- lower hole M8 Screw bolt ( For or M8 Anchor bolt ) 50 120 (Square hole ) (For under surface piping)

130 Knockout hole (For backside piping)

109

MMF-AP0361H, AP0481H, AP0561H


Wall of installing distance ( Incase ) 50mm from wall

Lower refrigerant piping port (50 120 Knockout hole) Installation plate Discharge port 600 30 3 30 3 80 Wall

Wall

a
Control part Control cover

Wall

Space required for service (In case of right side piping )


Wall
More than 1000 More than 200

Front

More Front than 500

Wall

Floor Refrigerant piping port (Both side) (80 Knockout hole) Dtain hose

Installation plate

Earth screw (M4) Dtain hose Refrigerant piping hole (Bottom side) (50 120 Knockout hole)

Suction port Refrigerant piping hole (Back side) (130 Knockout hole)

Refrigerant piping position


Refrigerant piping joint (Gas side 19) Gas side Liquid side

Refrigerant piping joint (Liquid side 9.5)

Details of hole for back side piping


In case a 1770

Details of hole for lower side piping

2- lower hole M8 Screw bolt ( For or M8 Anchor bolt )

In case b 1773

130 Knockout hole (For backside piping)

4- lower hole For M8 Screw bolt or M8 Anchor bolt

50 120 (Square hole ) (For under surface piping)

110

Remote controller
Wired remote controller
RBC-AMT21E
2.7

120

16 120

Simple remote controller


RBC-AS21E

120

80

60 70

13 16

111

Wireless remote controller


TCB-AX21U (W)-E

186 58 19.5

186

Wireless remote controller kit


RBC-AX22CE

32

61

130 58 19.5

177

61

177

112

65

Wireless remote controller kit


TCB-AX21E

58

19.5

4.4 x 9.4 long hole 13

83.5

177

70

4.4 x 5.4 long hole

61

Weekly timer
RBC-EXW21E
2.7

120

16 120

113

83.5

Central remote controller


TCB-SC642TLE
116 47
15

160 148

13

21 (6)

69

160

148

121

115

(6)

121 128 80

128

LON Gateway
TCB-IFLN

80

36

47

114

13

TCS-Net relay interface


BMS-IFLSV1E
200

(2.4)

63.6

5.5 mounting hole


7

146.9

144.9

156

12.55

(2.4)

63.6

22

78

78

22

Touch screen controller


BMS-TP5120ACE

54 49

316 249 75

242

95.75

75

99.3

82.5 48 16

302 55.5 19 30

70

115

91.75

256

12.55

170

Intelligent server
BMS-LSV2E

Energy mountoring relay interface


BMS-IFWH3E
200

(2.4)

63.6

5.5 mounting hole

146.9

144.9 12.55

156

12.55 170

(2.4)

63.6

22

78

78

22

116

Digital I/O relay interface


BMS-IFDD01E
200

(2.4)

63.6

5.5 mounting hole


7

146.9

144.9 12.55

156

12.55 170

(2.4)

63.6

22

78

78

22

WINDOWS based central controller


BMS-LSV**

117

Outdoor module
MMY-MAP0501T8, MAP0601T8, MAP0801T8, MAP1001T8, MAP1201T8 MMY-MAP0501HT8, MAP0601HT8, MAP0801HT8, MAP1001HT8, MAP1201HT8 MMY-MAP0501HT7, MAP0601HT7, MAP0801HT7, MAP1001HT7, MAP1201HT7
(NOTES) 1. If there is an obstacle at the upper side of the outdoor unit, set the top end of the outdoor unit 2000mm apart from the obstacle. 2. Limit the height of the obstacle surrounding the outdoor unit to 800mm or less from the bottom end of the outdoor unit. 3. Draw out the pipe procured locally to the front of the outdoor unit horizontally, and keep 500mm or more between the outdoor unit and traversing pipe if placing pipe transversely.
790 (including steady leg) 755 anchor bolt pitch

4-15 20 (Long hole)

700 anchor bolt pitch 990

750

Applied model
165

C 280 280

MMY-MAP0501T8, MAP0501HT8, MAP0501HT7 15.9 9.5 MMY-MAP0601T8, MAP0601HT8, MAP0601HT7 19.1 9.5

MMY-MAP0801T8, MAP0801HT8, MAP0801HT7 22.2 12.7 (205) MMY-MAP1001T8, MAP1001HT8, MAP1001HT7 22.2 12.7 (205) MMY-MAP1201T8, MAP1201HT8, MAP1201HT7 28.6 12.7 (205)
1800 1640

700

Refrigerant pipe connecting port (Gas side) A

position of L-shape pipe when pipe *1 Cutting at gas side is connected (Recommended pipe connecting position)
1010 or more

241 C

500 or more

88

Balance pipe connecting port 9.5

500 or more

2-60 150 square hole (Hole for handling goods)

500

Refrigerant pipe connecting port (Liquid side) B

1750 or more

Front side (For work and service)


10 or more

10 or more

Earth-attaching section of bottom plate

Space required for service


(Note 3) 600 (1000 or more) 500 600 or more or more or more (Note 3) 500 (1000 or more) 500 or more 600 or more or more

100

80

Foundation

755 anchor bolt pitch

610

100

700 anchor bolt pitch

500 or more

MMY-MAP0501T8 MMY-MAP0501T8 MMY-MAP0501HT8 MMY-MAP0601HT8 MMY-MAP0601HT7 MMY-MAP0601HT7

80

630

Front side Front side

Front side Front side

Foundation

Front side

Knockout for Knockout hole for control piping (27) power piping (48) Balance pipe connecting port 67 55

Refrigerant pipe connecting port (Liquid side)

215

135

115 225 230

88

140

88

Square hole

20 52 173 Refrigerant pipe connecting port (Gas side)

Details of front pipe/cabling holes

Details of hole for piping at lower side (Plane view)

118

136 64 125

155

800 or less

<Two units connected>


MMY-AP1401T8, AP1601T8, AP1801T8, AP2001T8, AP2211T8, AP2411T8 MMY-AP1401HT8, AP1601HT8, AP1801HT8, AP2001HT8, AP2211HT8, AP2411HT8 MMY-AP1401HT7, AP1601HT7, AP1801HT7, AP2001HT7, AP2211HT7, AP2411HT7
990 20 or more 990

(NOTES) 1. If there is an obstacle at the upper side of the outdoor unit, set the top end of the outdoor unit 2000mm apart from the obstacle. 2. Limit the height of the obstacle surrounding the outdoor unit to 800mm or less from the bottom end of the outdoor unit. 3. Draw out the pipe procured locally to the front of the outdoor unit horizontally, and keep 500mm or more between the outdoor unit and traversing pipe if placing pipe transversely. 4. Arrange each outdoor unit in order of its capacity. (Head unit > Follower)

700 anchor bolt pitch

(310)

700 anchor bolt pitch

8-15 20 (Long hole)

1800 1640

88

700

165

2000

Combination outdoor unit Combination unit Header MMY-AP1401T8, AP1401HT8, AP1401HT7 MMY-AP1601T8, AP1601HT8, AP1601HT7 MMY-AP1801T8, AP1801HT8, AP1801HT7 MMY-AP2001T8, AP2001HT8, AP2001HT7 MMY-AP2211T8, AP2211HT8, AP2211HT7 MMY-AP2411T8, AP2411HT8, AP2411HT7 MMY-MAP0801T8, MAP0801HT8, MAP0801HT7 MMY-MAP0801T8, MAP0801HT8, MAP0801HT7 MMY-MAP1001T8, MAP1001HT8, MAP1001HT7 MMY-MAP1001T8, MAP1001HT8, MAP1001HT7 MMY-MAP1201T8, MAP1201HT8, MAP1201HT7 MMY-MAP1201T8, MAP1201HT8, MAP1201HT7 Follower MMY-MAP0601T8, MAP0601HT8, MAP0601HT7 MMY-MAP0801T8, MAP0801HT8, MAP0801HT7 MMY-MAP0801T8, MAP0801HT8, MAP0801HT7 MMY-MAP1001T8, MAP1001HT8, MAP1001HT7 MMY-MAP1001T8, MAP1001HT8, MAP1001HT7 MMY-MAP1201T8, MAP1201HT8, MAP1201HT7

(Note 4) (Note 3) (1000 or more) 500 600 or more or more

(Note 3) (Note 4) (Note 4) 500 (1000 or more) 500 or more 600 or more or more

Front side Front side Front side Front side

(Note 4) 500mm or more

750 755 anchor bolt pitch 790 (including steady leg)

Front side Front side Front side Front side

1750mm or more
10mm or more 20mm or more

600 or more

500 or more

Front side Front side

500mm or more

10mm or more

Front side (For work and service)


2020mm or more

800 or less

800 or less

Space required for service

119

<Three units connected>


MMY-AP2201T8, AP2401T8, AP2601T8, AP2801T8, AP3001T8, AP3211T8, AP3411T8, AP3611T8 MMY-AP2201HT8, AP2401HT8, AP2601HT8, AP2801HT8, AP3001HT8, AP3211HT8, AP3411HT8, AP3611HT8 MMY-AP2201HT7, AP2401HT7, AP2601HT7, AP2801HT7, AP3001HT7, AP3211HT7, AP3411HT7, AP3611HT7
(NOTES) 1. If there is an obstacle at the upper side of the outdoor unit, set the top end of the outdoor unit 2000mm apart from the obstacle. 2. Limit the height of the obstacle surrounding the outdoor unit to 800mm or less from the bottom end of the outdoor unit. 3. Draw out the pipe procured locally to the front of the outdoor unit horizontally, and keep 500mm or more between the outdoor unit and traversing pipe if placing pipe transversely. 4. Arrange each outdoor unit in order of its capacity. (Head unit > Follower 2 > Follower 3 )
990 20 or more 990 20 or more 990

700 anchor bolt pitch

(310)

700 anchor bolt pitch

(310)

700 anchor bolt pitch

12-15 20 (Long hole)

1800 1640

88

700

165

3010

Combination outdoor unit Combination unit MMY-AP2201T8, HT8, HT7 MMY-AP2401T8, HT8, HT7 MMY-AP2601T8, HT8, HT7 MMY-AP2801T8, HT8, HT7 MMY-AP3001T8, HT8, HT7 MMY-AP3221T8, HT8, HT7 MMY-AP3411T8, HT8, HT7 MMY-AP3611T8, HT8, HT7 Header MMY-MAP0801T8, HT8, HT7 MMY-MAP0801T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1201T8, HT8, HT7 MMY-MAP1201T8, HT8, HT7 MMY-MAP1201T8, HT8, HT7
(Note 3) 600 (1000 or more) (Note 4) or more 600 or more 500 or more

Follower MMY-MAP0801T8, HT8, HT7 MMY-MAP0801T8, HT8, HT7 MMY-MAP0801T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1201T8, HT8, HT7 MMY-MAP1201T8, HT8, HT7
(Rear side)

Follower MMY-MAP0601T8, HT8, HT7 MMY-MAP0801T8, HT8, HT7 MMY-MAP0801T8, HT8, HT7 MMY-MAP0801T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1201T8, HT8, HT7

(Note 3) (Note 4) (1000 or more) (Note 4) 500 or more 600 or more 500 or more

(Note 4) 500mm or more

Front side Front side Front side Front side Front side Front side

1750mm or more

500mm or more

Front side Front side Front side Front side Front side Front side

10mm or more 20mm or more 20mm or more

Front side (For work and service)


(Front side)

500 or more

Front side Front side Front side

3030mm or more

Space required for service

800 or less

800 or less

120

750 755 anchor bolt pitch 790 (including steady leg)

10mm or more

<Four units connected>


MMY-AP3201T8, AP3401T8, AP3601T8, AP3801T8, AP4001T8, AP4201T8, AP4401T8, AP4601T8, AP4801T8 MMY-AP3201HT8, AP3401HT8, AP3601HT8, AP3801HT8, AP4001HT8, AP4201HT8, AP4401HT8, AP4601HT8, AP4801HT8 MMY-AP3201HT7, AP3401HT7, AP3601HT7, AP3801HT7, AP4001HT7, AP4201HT7, AP4401HT7, AP4601HT7, AP4801HT7
990 20 or more 990 20 or more 990 20 or more 990

700 anchor bolt pitch

(310)

700 anchor bolt pitch

(310)

700 (310) anchor bolt pitch

700 anchor bolt pitch

16-15 20 (Long hole)


4

1
165

1800 1640

88

700

4020
Combination unit MMY-AP3201T8, HT8, HT7 MMY-AP3401T8, HT8, HT7 MMY-AP3601T8, HT8, HT7 MMY-AP3801T8, HT8, HT7 MMY-AP4001T8, HT8, HT7 MMY-AP4201T8, HT8, HT7 MMY-AP4401T8, HT8, HT7 MMY-AP4601T8, HT8, HT7 MMY-AP4801T8, HT8, HT7 Combination outdoor unit Follower Follower MMY-MAP0801T8, HT8, HT7 MMY-MAP0801T8, HT8, HT7 MMY-MAP0801T8, HT8, HT7 MMY-MAP0801T8, HT8, HT7 MMY-MAP0801T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1201T8, HT8, HT7 MMY-MAP1201T8, HT8, HT7 MMY-MAP1201T8, HT8, HT7 MMY-MAP1201T8, HT8, HT7 MMY-MAP1201T8, HT8, HT7

Header MMY-MAP0801T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1201T8, HT8, HT7 MMY-MAP1201T8, HT8, HT7 MMY-MAP1201T8, HT8, HT7 MMY-MAP1201T8, HT8, HT7

Follower MMY-MAP0801T8, HT8, HT7 MMY-MAP0801T8, HT8, HT7 MMY-MAP0801T8, HT8, HT7 MMY-MAP0801T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1001T8, HT8, HT7 MMY-MAP1201T8, HT8, HT7

800 or less

(Note 4) 500mm or more

800 or less

(NOTES) 1. If there is an obstacle at the upper side of the outdoor unit, set the top end of the outdoor unit 2000mm apart from the obstacle. 2. Limit the height of the obstacle surrounding the outdoor unit to 800mm or less from the bottom end of the outdoor unit. 3. Draw out the pipe procured locally to the front of the outdoor unit horizontally, and keep 500mm or more between the outdoor unit and traversing pipe if placing pipe transversely. 4. Arrange each outdoor unit in order of its capacity. Head unit > Follower 2 > ) ( Follower 3 > Follower 4

(Note 3) (Note 4) (1000 or more) (Note 4) 500 or more 600 or more 500 or more

(Note 4) (Note 3) (1000 or more) 500 600 600 or more or more or more

Front side Front side Front side Front side Front side Front side Front side Front side

Front side Front side Front side Front side Front side Front side Front side Front side

500 or more

Front side Front side Front side Front side

500mm or more

10mm or more

20mm or more

20mm or more

20mm or more

10mm or more

Front side (For work and service)


4040mm or more

Space required for service

121

1750mm or more

750 755 anchor bolt pitch 790 (including steady leg)

Branch header/Branch joint


Branch header
RBM-HY1043E, HY1083E, HY2043E, HY2083E Gas side
B 80 n A 50 E

Insulator

Liquid side
B 80 n

C
A B E

Insulator

74.5

Model RBM-HY1043E Gas side Liquid side Gas side Liquid side Gas side Liquid side Gas side Liquid side

A 380 360 700 680 385.5 360 705.5 680

B 90 60 90 60 95.5 60 95.5 60

C 83.6 83.6 89.3 89.3

D 22.2 15.9 22.2 15.9 31.8 15.9 31.8 15.9

E 15.9 9.5 15.9 9.5 15.9 9.5 15.9 9.5

n 3 3 7 7 3 3 7 7

Accessory soket Qty 6 4, 9 4, 14 1, 18 1, 70 1 1 4, 6 1, 9 1 6 8, 9 8, 14 1, 18 1, 70 1 1 8, 6 1, 9 1 6 2, 9 2, 27 1, 59 1 1 2 6 7, 9 7, 27 1, 59 1 1 7

RBM-HY1083E

RBM-HY2043E

RBM-HY2083E

T-shape branch joint


RBM-BT13E Gas side
38.1 22.2 9.5

Liquid side

Balance pipe

14

10 26

39

61 38.1 38.1 22.2 22.2 9.5


10 14 78
Accessory soket Qty Gas side Liquid side 61 1, 62 1, 71 2, 73 2, 74 1 14 2, 18 1, 85 2, 86 1

10 52

7 32

14

122

9.5

7 13

Y-shape branch joint


RBM-BY53E, BY103E Gas side Liquid side

D
Insulator A

Insulator A

RBM-BY203E, BY303E Gas side Liquid side

D
Insulator

D D
Insulator A
Accessory soket Qty

Model RBM-BY53E Gas side

A 250

C D

80 15.9 12.7 70 12.7 9.5

5 2, 54 2, 9 1, 51 1 1 2, 5 1 7 1, 10 1, 13 2, 18 1, 52 2, 70 1, 89 1 2 1, 5 2, 6 1, 9 1, 54 1 16 1, 20 1, 27 1, 43 2, 48 1, 49 1, 58 1, 59 1 3 1, 6 1, 9 2 61 3, 62 2, 71 2, 73 1, 74 1, 75 1, 76 1, 77 1 4 1, 7 1, 10 1, 13 2, 14 1, 18 1, 52 1

Liquid side 200 Gas side 350

RBM-BY103E

80 22.2 19.1 80 15.9 12.7 80 31.8 28.6 80 15.9 15.9

Liquid side 250 Gas side 350

RBM-BY203E

Liquid side 250 Gas side

RBM-BY303E

400 110 38.1 38.1 80 22.2 19.1

Liquid side 350

123

Accessory socket
1 2 5 54

6.4
24

A
2

B 6.4 9.5

29 26

9.5 Outer dia

12.7 Outer dia

54

31 15.9

51

10 13 52 89

B
A
4

B 6.4 9.5

39 39

3 6 9

35 32

6.4 9.5

10 13 52

36 12.7 33 15.9 43 22.2 53 28.6

28 12.7 38 19.1

15.9 Outer dia

51

19.1 Outer dia

89

14 18 70 85 86

16 20 43 48 49 58 A
14 18 70 85

B
A
16 20

40 15.9 40 19.1 41 12.7 44 9.5

50 15.9 52 19.1 50 22.2 54 9.5 52 12.7 62 34.9

54 28.6

43 48 49

22.2 Outer dia

86

28.6 Outer dia

58

27 59

61 62 73 74 75 76 77

A
61 62 71 73

55 34.9 66 41.3 66 28.6 66 22.2 66 19.1 64 15.9 62 12.7 62 9.5

74 75 76

A
27

49 28.6 59 34.9

31.8 Outer dia

59

38.1 Outer dia

77

124