You are on page 1of 1

Project: Date:

Computed By: Eng. H.S & E.S Checked By: Approved By: Eng. M. Gamal Dr. H. Soliman

Foam Fire Fighting System Calculations


Design parameters
Solution Density 0.16 gpm/ft2 10.0 min

Discharge Time

Foam Concentration

3%

Sprinklers Spacing

3.0 m 5.6 gpm/psi1/2 10%

Sprinklers K-Factor

Safety Factor

Protected space dimensions

Name of Protected Space

LFO

Length

20.0

Width

10.0

Height

5.0

m m2
3

Area

200.0

2152.8

ft2

Volume

1,000

Foam system characteristics


Discharge rate 344 gpm

Solution volume

3,444

gallon

Foam volume

114

gallon

No of Sprinklers per length

No of Sprinklers per width

Total No. of Sprinklers

28

Sizing is based on NFPA-16