You are on page 1of 1

PROJECT:

UNIT.NO. : EF-05

SITE : RIYADH
BUILDING : 1st, 2nd & 3rd FLR

Date : 5/5/2009
Revision : 0

GENERAL DATA
DUCT MATERIAL

G. I. Sheet

ROUGHNESS COEF.

0.93

ALTITUDE

611

Meters

ALTITUDE COEF.

:
:

0.935
1.09

Kg/m3

AIR DENSITY

DUCTS PRESSURE LOSSES BOARD


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY
PD per Meter
PD x LENGTH

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
WIRE MESH
TOTAL
DUCTS PD
PRESSURE DROP

1
CFM
980
M3/H 1666
M
1.00
mm 382.61
382.61
mm
350
mm
350
M2
0.11
M/S
4.03
Pa
0.53
Pa
0.53
Co
0.07
0.09
0.15
0.3
1
1.5
0.05
0.22
0.05
0.04

Co
Pa
Pa

0.15
1.32
1.86

2
980
1666
1.50
382.61
382.61
350
350
0.11
4.03
0.53
0.80

3
980.0
1666
4.15
382.61
382.61
350
350
0.11
4.03
0.53
2.22

4
490
833
4.15
299.07
299.07
250
300
0.07
3.29
0.50
2.08

5
490
833
7.10
299.07
299.07
250
300
0.07
3.29
0.50
3.56

6
390
663
3.40
244.06
244.06
250
200
0.05
3.94
0.89
3.02

7
200
340
4.10
218.63
218.63
200
200
0.04
2.52
0.45
1.84

0.30
1.77
5.33

0.15
1.27
4.29

0.15
0.52
2.36

0.05
0.44
1.24

0.05
0.44
2.66

0.05
0.30
2.38

10

11

12

13

14

TOTAL

25.4 ml

14.06 Pa
9

10

11

12

13

14

TOTAL

0.90
6.06 Pa
20.12 Pa

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
VOLUME DAMPER
SUPPLY GRILLE
RETURN GRILLE
FRESH AIR LOUVER
VAV BOX
ALUMINUM FILTER
BAG FILTER
PLENUM BOX
DUCT HEATER
DISC EXHAUST VALVE
FLEXIBLE DUCT CONNECTION
SOUND ATTENUATOR
TOTAL

PD (PA)

QTY

TOTAL

10
10
15
10
20
100
80
150
50
5
70
15
75

1
1

10
10

50

1
1

70
15
155 Pa

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

0.70 W.g
175 Pa
1666 m/h
20 Pa
155 Pa

You might also like