TALISMAN

NAO ENGINEERING SPECIFICATIONS - PIPING FOR FACILITIES

EMERGENCY SHUTDOWN AND SLOWDOWN VALVES

NAO-SPC-D-PF-002

EMERGENCY SHUTDOWN AND SLOWDOWN VALVES


Issue: 2011/01/01

Next Review Date:


June 2011

HSE/OI Staff Responsible:


Mechanical Technical Authority

Published by: Talisman Energy Inc.

APPROVALS:
Tech Auth:
Eng. Auth:
VP-HSEOI:

Operational Integrity Department Calgary


Copyright is owned by Talisman Energy Inc. All rights are hereby reserved. This document (in whole or in part) may not be reproduced, stored in a retrieval system, or transmitted, in any form or means, without the prior written permission of Talisman, or as expressly permitted by law.

Note: This is an existing specification currently being used by Talisman and has not been
technically reviewed or signed off by the Technical Authority at this time. Over time, these specifications will be rebuilt and validated through a specification review process. Please ensure that you use the most current copy of the specs listed on the NAO Portal under Engineering Specifications. The Technical Authority identified on the cover sheet is the point of contact for this specification.

Attention: Paper copies are uncontrolled. This copy is valid only at time of printing, 12/15/2010. The controlled document is available on the Talisman NAO Portal.

Attention: Paper copies are uncontrolled. This copy is valid only at time of printing, 12/15/2010. The controlled document is available on the Talisman NAO Portal.

WorleyParsons
resources & energy

TALISMAN
ENE R G Y

GUIDELINE EMERGENCY SHUTDOWN AND BLOWDOWN VALVES

TABLE OF CONTENTS
TABLE OF CONTENTS ...............................................................................................................................111
LIST OF FIGURES .......................................................................................................................................111
1.

INTRODUCTION............................................................................................................................1
ESD VALVES.................................................................................................................................2
2.1

2.

Location of ESD valves.................................................................................................................. 2


Hydraulic vs. Pneumatic ESD Valve Actuators..............................................................................

2.2

2.3 2.4
3.

ESD Valve Hydraulic Circuitry .......................................................................................................4


ESD Valve Sizing ...........................................................................................................................6

BLOWDOWN VALVES.................................................................................................................. 7
3.1

Locating Blowdown Valves............................................................................................................ 7 Sizing Blowdown Valves................................................................................................................ 8

3.2

LIST OF FIGURES
Figure 1: SCHEMATIC FOR BETTIS PRESSUREGUARD HYDRAULIC ESD SYSTEM ...........................5

Incorprating Colt Engineering

EcoNomics
Page iii

SharePoinllPrime Operating ManuaIIGuidelineIProcessIIBU-TLM-GL-EM-PE-035 Emergency Shutdown and Blowdown Valves

GUIDELINE EMERGENCY SHUTDOWN AND BLOWDOWN VALVES

1.

INTRODUCTION

This document describes the recommended design standards for emergency shutdown (ESD) valves and blowdown valves for the design of Talisman wellsites and facilities. The section on ESD valves is limited to hydraulic and pneumatic types, as these comprise the vast majority of those used in the Talisman

system.

SharePointlPrime Operaling ManuaIIGuidelineIProcessIIBU-TLM-GL-EM-PE-035 Emergency Shutdown and Blowdown Valves

Page 1

GUIDELINE EMERGENCY SHUTDOWN AND BLOWDOWN VALVES

2. ESD VALVES
An ESD (emergency shutdown) valve is a valve equipped with a spring return actuator, such that when the actuator pressure signal is released the valve is forced closed by the actuator spring. Generally speaking, ESD valves are quarter turn actuated ball valves, but they can also be sliding stem gate valves or other types, although these are less common. The actuator types considered in this document are hydraulic or pneumatic. The actuator pressure signal can be tripped by a mechanical pilot assembly, a solenoid valve, or a combination of the two.

ESD valves are used to isolate the facilities in emergency situations. For single well tie-ins, a wellhead

ESD valve is usually suffcient. If the well is sour and fed with fuel gas for a line heater, then there should
also be a fuel gas ESD valve to shut off the fuel supply in the event of a line heater building fire. On single well tie-ins, there is generally no need for an outlet ESD valve, as these installations usually are not equipped with auto blowdown valves. Whenever an auto blowdown valve is added to a system, the outlet check valve should be accompanied by an outlet ESD valve.

2.1 Location of ESD valves


Wellhead ESD valves should be placed close to the wellhead; generally a 5 m removable spool is placed between the ESD valve and the wellhead to facilitate dismantling the high line for downhole wireline service work. On larger facilities, the ESD valves should be placed near the pipeline riser, with 15 meters separation between the ESD valves and the closest process building. The idea is to create an ESD "boundary", whereby all the piping and vessels on the "facility side" of the ESD valves would be de-pressured in an emergency condition and the ESD valve is located far enough away from probable fire areas to ensure the valve is not enveloped in the fire. The risers would remain pressurized. Ideally, all of the risers would be clustered in a common area close to one side of the facility lease, and the surface area of piping that would remain pressurized in an emergency condition would be minimized. This idealized layout is not always practical to achieve. Depending on the piping layout, it may be advisable to clad the exposed pressurized piping with fireproof insulation to mitigate risk to this piping in an ESD condition if the idealized layout can not be achieved.

SharePointlPrime Operating ManuaIIGuidelineIProcessIIBU-TLM-GL-EM-PE-035 Emergency Shuldown and Blowdown Valves

Page

GUIDELINE EMERGENCY SHUTDOWN AND BLOWDOWN VALVES

2.2 Hydraulic vs. Pneumatic ESD Valve Actuators


If a reliable pneumatic medium is available, pneumatic actuators should be used in preference to hydraulic actuators because they are less expensive, more reliable, cleaner, and simpler. "Reliable pneumatic medium" must be instrument air from a system equipped with a proper air dryer, or pipeline spec sweet fuel gas (dehydrated to 4 Ib water per MMSCF or dryer). Note that any system that uses process gas as the pneumatic instrument medium, such as sweet single well tie-ins, will not qualify for this definition of "reliable pneumatic medium". In these cases the ESD actuators must be hydraulic, UNLESS the ESD valve in question is located inside the heated facility building.

The one advantage of hydraulic actuators is that they do not require an instrument operating medium, and can therefore be used at sites that do not have instrument air or fuel gas. Also, the hydraulic fluid is totally impervious to cold temperature. The disadvantage of hydraulic systems is that they are reliant on a perfect seal in the actuator, leak free check valves on the hydraulic pump, and leak-free tubing from the hydraulic pump to the actuator. If a leak develops in a hydraulic system, the actuator spring will push the hydraulic fluid out of the leak, and this leaking hydraulic fluid will cause the valve to "creep" closed. This leak may also be a clean-up issue. Small hydraulic leaks can be managed by having the operators regularly pump the actuator back up to keep the valve open, and mopping up as needed with rags. In a pneumatic system, small leaks are replenished by the pneumatic supply on a continual basis, and the leak does not spill material on the ground. From this standpoint the pneumatic system is superior.

Another advantage of hydraulic systems is that each stroke of the pump handle will move the valve a predictable few degrees, and on smaller systems the hydraulic ESD valve would not require a car sealed closed bypass. The same can not be said of pneumatic ESD valves. Generally speaking, pneumatic ESD valve's should have a bypass to equalize the pressure across the valve prior to opening, unless the system is small and there is a means of throttling flow elsewhere on the piping system.

SharePointlPrime Operaling ManuaIIGuidelineIProcessIIBU-TLM-GL-EM-PE-035 Emergency Shutdown and Blowdown Valves

Page 3

GUIDELINE EMERGENCY SHUTDOWN AND BLOWDOWN VALVES

2.3 ESD Valve Hydraulic Circuitry


Detailed design of hydraulic ESD circuitry is generally beyond the scope of this document. However, one aspect of hydraulic ESD circuitry bears mention because there is chance of making the ESD circuit completely unresponsive with the prescribed design. Refer to Figure 1, Schematic for the Bettis ''PressureGuard'' hydraulic ESD System. The system shows a solenoid valve (20) between a highllow hydraulic pressure switch (14) and the reset valve (23). The reset valve is a latching relay that can be reset to enable the ESD valve to be pumped open before the conditions on the system are satisfied for the highllow pressure switch. A reset valve of this type is quite normal, as you would otherwise run into a "catch 22" where you can't open the ESD valve because pressure is too low, but you need to establish minimum pressure by opening the ESD valve. However, the problem with the design as drawn is that unless the solenoid valve is energized, the high/low pilot would be shut out of the system. A better design would be to install the solenoid valve (20) on the hydraulic feed to the highllow pilot, between the accumulator (27) and the reset valve (23). See Figure 1 below. The reason for modifying the vendor's recommended design is that their design would disable the ESD system if the operations people did not energize the solenoid valve before jacking the ESD valve open. The recommended procedure requires the reset valve to be latched to enable the actuator to be opened. If the solenoid valve is not energized, then this latching relay will never "arm" itself even when pressure comes up to normal to arm the pressure pilot. If the pressure then goes above the high trip on the pilot, the system is not going to respond and the ESD safety feature is disabled.
If on the other hand the solenoid valve is placed upstream of the reset valve, the procedure would be to first energize the solenoid valve, then latch the reset valve, and then pump the valve open. Energizing the solenoid valve with pressure below the low pressure shut down should be a feature that would be programmed into the site control system. Low pressure shut down should be configured as a class C shut down, which means that the control system ignores low pressure until system pressure rises above the trip point, after which the shut down is enabled. In this case, both the site control system (PLC or RTU or electric relay panel) and the hydraulic pressure pilot would be activated as soon as system pressure rises above the low trip points, and it would never be possible to inadvertently shut out the pressure switch and disable the ESD functionality.

SharePointlPrime Operaling ManuaIIGuidelineIProcessIIBU-TLM-GL-EM-PE-Q35 Emergency Shutdown and Blowdown Valves

Page

GUIDELINE EMERGENCY SHUTDOWN AND BLOWDOWN VALVES

"",J (11i1i?'r.I.:j) Ifr.hiiil\- ,H1!i'iirl'

r-....-....-....----...-..._.._..._..._ .---r~,~"i Ji"A:~ 1JII Ct"fri:..~t,f l-~J i~ :,:":y.:t'tci

.._--- ._- -._--------_. --..1


(~
.

,
I . I . , I

!.~~_-?n i : ~ L ! . in :
L....._ .... _....__ ._~.. _...__ ..._.. ..__._,
list of C:otnpo,cnl-s;
i 0pN.;tri'-

i. ~___l' i 'e -I: i....!l_ ~,~==== i : - I@ . '._..-..-..-.._.._..-..~.._.._~


-11q!1 'r~IL:Il!
-# Pri,=l!~!
- L"'''l ri~~~Ut'

: i
@~l 1'-

~~i','i.1 :-iitLlI'

-Si.(tKm
9 e..i,i-.HP i 0 l.i;ief '.'4'lt., i~

::::::: Lk'~!1 i.JI

20 ~i:,'naii:V:i~ic-. '-J.e. (l1pfor,l,l

2 lire 'o::l.'(.

4 Filtl.l

l H;indrA.lmp

I? Prl"l'lI't'R'1ll.1tr.
J J Rtli"f "'N'll!. LP
1.1 fit ~'\Y.J":' Pilri: i: iipliO'I)

23 Ri.'-l "'::II~
24 ~""...t"Jiir 27 J,((I.Il""~l';1l
J.S Im'.1liiin Ti1r,1 ..;l....I(lI~ir..1.11~

: C~n't( "'.,1."

i5 "ul'.lP

on ~"I","lllr '.''''~'''' ,/lpt.~IIi.)I)

FIGURE 1: SCHEMATIC FOR BETTIS PRESSUREGUARD HYDRAULIC ESD SYSTEM

SharePoinllPrime Operaling ManuaIIGuidelineIProcessIIBU-TLM-GL-EM-PE-Q35 Emergency Shutdown and Blowdown Valves

Page5

GUIDELINE EMERGENCY SHUTDOWN AND BLOWDOWN VALVES

2.4 ESD Valve Sizing


The ESD valve generally matches line size. Wellhead ESD valves should always be full port valves, as

these types would be less prone to erosion damage from sand that may come up hole. Port sizes on
other ESD valves would match what one would use on manual isolation valves on the same line. For example, if it is acceptable to use a reduced port ball valve for a manual isolation valve on a line, then the ESD valve would also be a regular port valve. In some cases, such as larger piping systems, it may be acceptable to reduce down to the next line size for the valve, but in this case the process engineer should check flowing fluid velocities and ensure that a reduced size will be acceptable.
The pressure rating of the valve matches the highest line classification that the valve is connected to. The actuator sizing is done by Instrumentation, but the process engineer should check to ensure that the maximum differential pressure used for sizing the actuator matches the full cold flange rating of the highest pipe classification. This ensures that the ESD valve can be re-used for any application that matches the pipe classification when the facility is abandoned or modified.

SharePoinllPrime Operating ManuaIIGuidelineIProcessIIBU-TLM-GL-EM-PE-Q35 Emergency Shuldown and Blowdown Valves

Page

GUIDELINE EMERGENCY SHUTDOWN AND BLOWDOWN VALVES

3.

BLOWDOWN VALVES

Blowdown valves are fail-open valves that allow the piping system to be de-pressured in an emergency condition. The actuator on the valve is usually a pneumatic actuator, tripped by either a pneumatic pilot or a solenoid valve. The trip device (pneumatic pilot or solenoid valve) is configured such that loss of signal to the device will vent the blowdown valve actuator, causing the valve to go to its fail position.

The valve is usually a control valve, although an actuated ball valve can be used. The advantage of using a control valve is that the blowdown rate can be accurately predicted based on the wide open flow coefficients as published by the valve manufacturer. If a ball valve is used as a blowdown valve, a

restriction orifice should be installed between the downstream valve flange and the pipe flange to
create a predictable flow through the valve.

3.1 Locating Blowdown Valves


Blowdown valves should be located so that all segments of piping and vessels between the inlet and outlet ESD valve's are de-pressured, with no pockets of pressurized piping remaining. This requires a thorough review of the system P&ID to determine where blowdown valves need to be added, along with consideration of all possible scenarios that might arise during the emergency condition.

For example, consider a simple compressor installation consisting of an inlet ESD valve, an inlet control valve, a separator, a compressor package, and an outlet ESD valve. Let's say that the compressor package is equipped with an auto blowdown valve. However, it is located upstream of the unit check valve, and would therefore not serve to de-pressure the piping from the unit check valve to the outlet ESD valve. This would mean it would be necessary to add an auto blowdown valve to the piping between the unit check valve and the outlet ESD valve. Under normal operation, when the compressor is running, these two blowdown valves would serve to depressure all piping between the inlet and outlet ESD valve's. However, let's say the compressor package can be double block and bleed isolated from the separator in order to perform maintenance. (The idea is to save the gas in the separator, so it is not blown down during maintenance.) Now if an ESD condition arose during the time when the compressor was isolated for maintenance, the two blowdown valves mentioned above (one in the compressor package, the other on the outlet line upstream of the outlet ESD valve) would not be able to blow down the site as needed, so another blowdown valve would be added to the separator package to blow it down.

SharePointlPrime Operaling ManuaIIGuidelineIProcessIIBU-TLM-GL-EM-PE-035 Emergency Shuldown and Blowdown Valves

Page 7

GUIDELINE EMERGENCY SHUTDOWN AND BLOWDOWN VALVES


One could assume that the segment of piping from the inlet ESD valve to the inlet control valve would be de-pressured by the separator blowdown valve. One could specify that this control valve remains on pressure control during the blowdown sequence, and as long as the signal and pneumatic supply to the inlet control valve were in tact, this assumption would be true. Usually, however, the inlet control valve is fail closed. One could not guarantee that the signal and pneumatic supply would remain in tact during the ESD condition. Therefore, it would be necessary to add either a blowdown valve on the inlet piping between the inlet ESD valve and inlet control valve, or a fail open bypass around the inlet control valve to enable this piping to blow down via the separator blowdown valve in an emergency condition. If there is a spec break at the inlet control valve, the fail open bypass should be sized such that the wide open capacity is not greater than the vessel PSV capacity at the highest possible pressure upstream of the control valve. In some cases, the inlet control valve is located close to the inlet ESD valve. In these cases, it is not necessary to add a blowdown valve or fail open auto bypass around the inlet control valve, but consideration should be given to having a manual bypass and pressure gauges to confirm if the

systems have been de-pressured.

3.2 Sizing Blowdown Valves


The blowdown valves are sized based on two constraints: flare system capacity and time to blowdown.

3.2.1

Flare System Capacity

During an ESD event, one assumes that all of the blowdown valves open at the same instant in time. The peak flow to flare can be modeled using Aspen Flare System Analizer (formerly Flarenet), and the flow specified for each blowdown valve would correspond to the wide open flow capacity of the blowdown valve at the maximum system operating pressure. This creates a large initial peak flow rate to flare, which must be within the allowable flow capacity of the flare system. In some cases, with existing flare systems, it may be necessary to stage the opening of blowdown valves or installing travels stops to limit the maximum opening of the blowdown valve in order to limit the instantaneous rate such that the peak capacity of the existing flare system capacity is not exceeded. Another consideration is that the blowdown valve on a separator or other vessel should not exceed the maximum gas capacity of the
separator or vesseL.

Most of Talisman's newer compressor packages are equipped with electronic control panels that automatically open the compressor recycle valve on unit shut down. This creates a condition where the pressure in the compressor system settles out to an average pressure that is higher than normal suction pressure, but substantially lower than the normal discharge pressure. This would in turn result in much lower pressure at the inlet of the compressor blowdown valve, and hence much less flow. However, for the purposes of calculating the initial peak flow rate to flare, this settle-out phenomenon should be ignored, as we can't guarantee that the recycle valve opens quicker than the blowdown valve.

SharePointlPrime Operaling ManuaIIGuidelineIProcessIIBU-TLM-GL-EM-PE-035 Emergency Shuldown and Blowdown Valves

Page 8

GUIDELINE EMERGENCY SHUTDOWN AND BLOWDOWN VALVES


The maximum possible system operating pressure is something that the individual process engineer should assess and make reasonable judgments on a case by case basis. By illustrative example, let's consider the separator/compressor scenario discussed in section 2.1 above. On a compressor, the maximum possible discharge pressure should be taken as the high discharge pressure shut down setting. The maximum suction pressure would correspond to the highest set point of the pressure controller on the inlet control valve, which should be determined by the compression engineer, as it is dependent on
cylinder loading.

3.2.2

Time to Blowdown

The other design parameter regarding blowdown valve sizing is time to blowdown. The standard for blowdown time is to follow API STD521, which indicates "de-pressured rate to achieve 100 psig or 50 percent of vessel design pressure, whichever is lower, in 15 minutes or less".
The time to blowdown from a given pressure can be estimated using the spreadsheet "IBU-TLM-CLCEM-PE-003 Depressuring Time.xls located at SharePoint\Prime Operating Manual\Standard Calculations\Engineering Management - Process. Note that this spreadsheet includes a feature whereby the valve percent open can be specified. In most cases this would be 100 percent. In some cases, the blowdown rate must be limited by the use of actuator travel stops, which limit the opening of the valve by the setting of the stop. If possible, the system should be designed without travel stops. Travel stops introduce a possibility of operator intervention such that the capacity of the system would be exceeded, and also add cost. A valve with a certain orifice size is much more difficult to tamper with and from this standpoint is more desirable in order to ensure that we don't exceed flare capacity.
For purposes of estimating the blowdown time (NOT FOR DETERMINING THE PEAK RATE OF THE VALVE), the settle out pressure should be used as valve inlet pressure in a compressor situation

(provided it is certain that the recycle valve opens on compressor shut down). This is because the time required to open both the blowdown valve and the recycle valve is small in relation to the time needed to

de-pressure.
The other pertinent parameter to specify for using this spread sheet is the system volume. For purposes of estimating blowdown times, assume that any separators or scrubbers are empty. This would give a conservative blowdown time, as any liquid would reduce the volume of gas present. Piping volumes can be estimated by estimating total length from the piping GA's or plot plan. If the project is being done in Autoplant, the piping designer can provide an accurate estimate of piping lengths by line number. Useful spreadsheets for determining the vessel volumes are:

"IBU-TLM-CLC-EM-PE-006 Horizontal Vessel Volume" located at SharePoint\Prime Operating


Manual\Standard Calculations\Engineering Management - Process

"IBU-TLM-CLC-EM-PE-007 Vertical Vessel Volume" located at SharePoint\Prime Operating


Manual\Standard Calculations\Engineering Management - Process

SharePointlPrime Operaling ManuaIIGuidelineIProcessIIBU-TLM-GL-EM-PE-035 Emergency Shuldown and Blowdown Valves

Page

You might also like