You are on page 1of 10

Component Protection

Introduction and Current-Limitation


This issue analyzes the protection of electrical system components from fault currents. It gives the specifier the necessary information regarding the shortcircuit current or withstand rating of electrical circuit components, such as wire, bus, motor starters, etc. Proper protection of circuits will improve reliability and reduce the possibility of injury. Electrical systems can be destroyed if the overcurrent devices do not limit the short-circuit current to within the withstand rating of the systems components. Merely matching the amp rating of a component with the amp rating of a protective device will not assure component protection under short circuit conditions. The National Electrical Code covers Component Protection in several sections. The first section to note is 110.10.

Current-Limitation Defined
Today, most electrical distribution systems are capable of delivering very high short-circuit currents, some in excess of 200,000A. Many circuit components have relatively low short circuit withstandability of a few thousand amps. If the components are not capable of handling these short-circuit currents, they could easily be damaged or destroyed. The current-limiting ability of todays modern fuses allows components with low short-circuit withstand ratings to be specified in spite of high available fault currents. NEC 240.2 offers the following definition of a current-limiting device: Current-Limiting Overcurrent Protective Device: A device that, when interrupting currents in its current-limiting range, reduces the current flowing in the faulted circuit to a magnitude substantially less than that obtainable in the same circuit if the device were replaced with a solid conductor having comparable impedance. The concept of current-limitation is pointed out in the following graph, where the prospective available fault current is shown in conjunction with the limited current resulting when a current-limiting fuse clears. The area under the current curve is representative of the amount of short circuit energy being dissipated in the circuit. Since both magnetic forces and thermal energy are directly proportional to the square of the current, it is important to limit the short-circuit current to as small a value as possible. The maximum magnetic forces vary as the square of the PEAK current and thermal energy varies as the square of the RMS current.

Component Protection and The National Electrical Code


110.10 Circuit Impedance and Other Characteristics: The overcurrent protective devices, the total impedance, the component short-circuit current ratings, and other characteristics of the circuit to be protected shall be selected and coordinated to permit the circuit-protective devices used to clear a fault to do so without extensive damage to the electrical components of the circuit. This fault shall be assumed to be either between two or more of the circuit conductors or between any circuit conductor and the grounding conductor or enclosing metal raceway. Listed products applied in accordance with their listing shall be considered to meet the requirements of this section. This requires that overcurrent protective devices, such as fuses and circuit breakers be selected in such a manner that the short-circuit current (withstand) ratings of the system components will not be exceeded should a short circuit occur. The short-circuit withstand rating is the maximum short- circuit current that a component can safely withstand. Failure to provide adequate protection may result in component destruction under short circuit conditions. After calculating the fault levels throughout the electrical system, the next step is to check the withstand rating of wire and cable, circuit breakers, transfer switches, starters, etc., under short circuit conditions. Note: The let-through energy of the protective device must be equal to or less than the short-circuit withstand rating of the component being protected. CAUTION: Choosing overcurrent protective devices strictly on the basis of voltage, current, and interrupting rating alone will not assure component protection from short-circuit currents. High interrupting capacity electromechanical overcurrent protective devices (circuit breakers), especially those that are not current-limiting, may not be capable of protecting wire, cable or other components within high short circuit ranges. The interrupting rating of a protective device pertains only to that device and has absolutely no bearing on its ability to protect connected downstream components. Quite often, an improperly protected component is completely destroyed under short circuit conditions while the protective device is opening the faulted circuit. Before proceeding with the study of component withstandability, the technology concerning current-limitation will be reviewed.

Current-Limiting Effect of Fuses


100,000

Prospective available short-circuit current that would flow when a fuse is not used.

Current

10,000 0

Peak Let-Through Current of Fuse

tc Total Clearing Time of Fuse

Time

Thus, the current-limiting fuse in this example (above waveform) would limit the let-through energy to a fraction of the value which is available from the system. In the first major loop of fault current, standard non-current-limiting, electro-mechanical protective devices would let-through approximately 100 times* as much destructive energy as the fuse would let-through.
2

= 100 (100,000 10,000 )

2005 Cooper Bussmann

67

Component Protection
How To Use Current-Limitation Charts
Analysis of Current-Limiting Fuse Let-Through Charts
The degree of current-limitation of a given size and type of fuse depends, in general, upon the available short-circuit current that can be delivered by the electrical system. Current-limitation of fuses is best described in the form of a let-through chart that, when applied from a practical point of view, is useful to determine the let-through currents when a fuse opens. Fuse let-through charts are plotted from actual test data. The test circuit that establishes line A-B corresponds to a short circuit power factor of 15%, that is associated with an X/R ratio of 6.6. The fuse curves represent the cutoff value of the prospective available short-circuit current under the given circuit conditions. Each type or class of fuse has its own family of let-through curves. The let-through data has been generated by actual short- circuit tests of current-limiting fuses. It is important to understand how the curves are generated, and what circuit parameters affect the let-through curve data. Typically, there are three circuit parameters that can affect fuse let-through performance for a given available short-circuit current. These are:
1. Short-circuit power factor 2. Short-circuit closing angle 3. Applied voltage

Prior to using the Fuse Let-Through Charts, it must be determined what letthrough data is pertinent to equipment withstand ratings. Equipment withstand ratings can be described as: How Much Fault Current can the equipment handle, and for How Long? Based on standards presently available, the most important data that can be obtained from the Fuse LetThrough Charts and their physical effects are the following:
A. Peak let-through current: mechanical forces B. Apparent prospective RMS symmetrical let-through current: heating effect C. Clearing time: less than 12 cycle when fuse is in its current-limiting range (beyond where fuse curve intersects A-B line).

This is a typical example showing the short-circuit current available to an 800A circuit, an 800A Low-Peak current-limiting time-delay fuse, and the let-through data of interest.

800 Amp Low-Peak Current-Limiting Time-Delay Fuse and Associated Let-Through Data

Current-limiting fuse let-through curves are generated under worst case conditions, based on these three variable parameters. The benefit to the user is a conservative resultant let-through current (both Ip and IRMS). Under actual field conditions, changing any one or a combination of these will result in lower let-through currents. This provides for an additional degree of reliability when applying fuses for equipment protection. Current-Limiting Let-Through Charts for Cooper Bussmann fuses are near the back of this book.

Analysis of a Current-Limiting Fuse


B I

INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS

400,000 300,000 200,000

Available Peak ShortCircuit Current = 198,000A Available RMS ShortCircuit Current = 86,000A

100,000 80,000 60,000

800A

Peak Let-Through Current of Fuse= 49,000A RMS Let-Through Current of Fuse = 21,000A tm ta tc tm = Fuse Melt Time ta = Fuse Arc Time tc = Fuse Clearing Time TIME

30,000 20,000 10,000 8000 6000

A
2000 1000 1000 2000 3000 4000 6000

8000 10,000

20,000

30,000 40,000

60,000 80,000

100,000

PROSPECTIVE SHORT-CIRCUIT CURRENT SYMMETRICAL RMS AMPS

68

200,000

AMP RATING

4000 3000

2005 Cooper Bussmann

Component Protection
How To Use Current-Limitation Charts
How to Use the Let-Through Charts
Using the example given, one can determine the pertinent let-through data for the KRP-C-800SP amp Low-Peak fuse. The Let-Through Chart pertaining to the 800A Low-Peak fuse is illustrated. A.
Step 1.

Determine the PEAK let-through CURRENT.


Enter the chart on the Prospective Short-Circuit current scale at 86,000 amps and proceed vertically until the 800A fuse curve is intersected. Follow horizontally until the Instantaneous Peak Let-Through Current scale is intersected. Read the PEAK let-through CURRENT as 49,000A. (If a fuse had not been used, the peak current would have been 198,000A.)

Step 2. Step 3.

Most electrical equipment has a withstand rating that is defined in terms of an RMS symmetrical-short-circuit current, and in some cases, peak let-through current. These values have been established through short circuit testing of that equipment according to an accepted industry standard. Or, as is the case with conductors, the withstand rating is based on a mathematical calculation and is also expressed in an RMS short-circuit current. If both the let-through currents (IRMS and Ip) of the current-limiting fuse and the time it takes to clear the fault are less than the withstand rating of the electrical component, then that component will be protected from short circuit damage. The following Table shows typical assumed short-circuit current ratings for various unmarked components.

B.
Step 1.

Determine the APPARENT PROSPECTIVE RMS SYMMETRICAL let-through CURRENT.


Enter the chart on the Prospective Short-Circuit current scale at 86,000A and proceed vertically until the 800A fuse curve is intersected. Follow horizontally until line A-B is intersected. Proceed vertically down to the Prospective Short-Circuit Current. Read the APPARENT PROSPECTIVE RMS SYMMETRICAL let-through CURRENT as 21,000A. (The RMS SYMMETRICAL let-through CURRENT would be 86,000A if there were no fuse in the circuit.)

Typical Short-Circuit Current Ratings For Unmarked Components*


Component Industrial Control Equipment:
a. Auxiliary Devices b. Switches (other than Mercury Tube Type) c. Mercury Tube Switches Rated over 60 amperes or over 250 volts Rated 250 volts or less, 60 amperes or less, and over 2kVA Rated 250 volts or less and 2kVA or less Meter Socket Base Photoelectric Switches Receptacle (GFCI Type) Receptacle (other than GFCI Type) Snap Switch Terminal Block Thermostat 5 5 5 3.5 1 10 5 10 2 5 10 5

Short- Circuit Rating, kA

Step 2. Step 3. Step 4.

Current-Limitation Curves Cooper Bussmann Low-Peak Time-Delay Fuse KRP-C-800SP

*Based upon information in UL 891 (Dead-Front Switchboards) The following components will be analyzed by establishing the short-circuit withstand data of each component and then selecting the proper currentlimiting fuses for protection: Wire and Cable Bus (Busway, Switchboards, Motor Control Centers and Panelboards) Transfer Switches HVAC Equipment Ballasts Circuit Breakers A detailed analysis of motor circuit component protection is provided later in the section on motor circuits.

C. Clearing time
If the RMS Symmetrical available is greater than the point where the fuse characteristic curve intersects with the diagonal A-B line, then the fuse clearing time is 12 cycle or less. In this example, the intersection is approximately 9500A; so for short-circuit currents above approximately 9500A, this KRP-C-800SP fuse is current-limiting. The current-limiting charts and tables for Cooper Bussmann fuses are in the rear of this book under Current-Limiting Let-Through Charts. Refer to these tables when analyzing component protection in the following sections.

2005 Cooper Bussmann

69

Ground Fault Protection


Current-Limitation
The Need for Current-Limitation
If ground fault protection is required, then the best protection is a switch equipped with a ground fault relay scheme, a shunt trip mechanism, and current-limiting fuses. The reason is that this system will offer protection for high magnitude ground faults as well as low magnitude ground faults. Ground fault relay schemes and shunt trip mechanisms on switches or circuit breakers can protect equipment against extensive damage from low magnitude ground faults - this is their intended purpose. However, burn downs still occur in switchboards, large motor control centers, and large distribution panels generally located in equipment rooms where high available ground fault currents are present.
1,000 800 600 400 300 200 100 80 60 30
TIME IN SECONDS

The National Electrical Code requires ground fault protection for intermediate and high ground faults as well as low grade ground faults. For high magnitude ground faults, ground fault relay schemes operate too slowly to prevent extensive equipment damage. The main or feeder overcurrent devices, such as fuses or circuit breakers must clear the circuit. Current-limiting fuses substantially limit the energy let-through for higher magnitude ground faults and thereby offer a higher degree of protection. Conventional circuit breakers are not current-limiting protective devices and during higher magnitude ground faults can let-through large amounts of damaging energy.
1,000 800 600 400 300 200

100 80 60 40 30
KRP-C1600SP

1600A CB

40 20 10 8 6 4 3 2 1

20

TIME IN SECONDS

10 8 6 4 3 2

1 .8 .6 .4 .3 .2

.8 .6 .4 .3 .2

.1 .08 .06 .04 .03 .02

.1 .08 .06 .04 .03 .02

800 1,000

2,000

3,000

4,000

6,000 8,000 10,000

.01

CURRENT IN AMPS

CURRENT IN AMPS

Clearing characteristic for a 1600A fuse. A 20,000 amp fault is cleared by the KRP-C1600SP fuse in 0.019 to 0.039 seconds (between one and two cycles). For currents greater than 25,000A the fuse enters its current-limiting range. Then the clearing time is less than one half cycle (less than 0.008 seconds).

Clearing characteristic for 1600A circuit breaker. A 20,000A fault is cleared by the 1600A circuit breaker in 0.05 seconds. The circuit breaker has a fixed operating time for high values of current. This time is approximately 0.05 seconds (three cycles). Therefore, high magnitude ground faults and short circuits are permitted to flow for at least three cycles.

114

2005 Cooper Bussmann

60,000 80,000 100,000

.01 100 200 300 400 600

20,000

30,000

40,000

000,1 008

000,2

000,3

000,4

000,01 000,8 000,6

000,001 000,08 000,06

000,02

000,03

000,04

001 08

002

003

004

006

Ground Fault Protection


Current-Limitation
The previous two figures illustrate the time-current characteristics for a 1600A current-limiting fuse and a 1600A circuit breaker. The higher the fault current the faster the fuse operates. Notice, the mechanical overcurrent protective device reaches an irreducible operating time. For large conventional service entrance circuit breakers this fixed operating time varies from 112 cycles to five cycles depending on the type and size. (If short-time-delay trip settings are used, the operating time can be as long as 30 cycles.) Of importance is the fact that modern, rejection type fuses are current-limiting protective devices. For faults above approximately 25,000A, the 1600A fuse operates in its current-limiting range; clearing the circuit in less than 12 cycle and limiting the peak current and energy let-through to the circuit components.

Current-Limitation
The effect of a fuse protecting the circuit is to limit the instantaneous peak current and thermal or heating effect current to a value less than that which would flow in the first half cycle had the fuse not been in the circuit. Currentlimitation for high level ground faults can substantially reduce the damaging effect. The large conventional mechanical overcurrent protective device reaches an irreducible minimum clearing time and therefore permits the full fault current flow for several cycles. The damaging peak current and thermal or heating effect current flow unrestricted without limitation for several cycles. At higher magnitude fault currents, large amounts of heating energy and magnetic forces are permitted to flow and the equipment must absorb the full available fault current energy.

Current-Limitation
Available current that would flow without a fuse.

No Current-Limitation
Available current flows for operating time of circuit breaker.

Fuse CurrentLimiting Effect

3 Cycle Clearing Time

Compare the Difference

Arc-flash when circuit protected by 601A Class L current-limiting fuses.

Arc-flash when circuit protected by a 1600A non-current limiting circuit breaker set at 640A with short time delay: circuit interrupted in six cycles.

2005 Cooper Bussmann

115

Cooper Bussmann Current-Limiting Fuse Let-Through Data

See pages 67 to 69 for current-limiting definition and how to analyze these charts.

Low-Peak Class L Time-Delay Fuses KRP-C_SP


1000000 900000 800000 700000 600000 500000 400000 300000

KRP-C_SP Fuse RMS Let-Through Currents (kA)


Prosp. Short C.C. Fuse Size 601 IRMS 800 IRMS 1200 1600 IRMS IRMS 2000 2500 3000 4000 IRMS IRMS IRMS IRMS 5000 IRMS 6000 IRMS

5,000
6000A 5000A 4000A 3000A 2500A 2000A 1600A 1200A 800A 601A

5 8 9

5 10 12 13 14 14 15 16 17 18 19 20 21 22 25 27 29 31

5 10 15 17 19 20 21 22 23 25 26 27 29 30 34 37 40 43

5 10 15 20 22 24 25 26 28 30 32 33 34 36 41 45 49 52

5 10 15 20 25 27 29 30 32 34 36 38 39 41 47 51 55 59

5 10 15 20 25 30 35 35 37 40 42 44 45 47 54 59 64 68

5 10 15 20 25 30 35 40 50 49 52 54 56 58 67 73 79 84

5 10 15 20 25 30 35 40 50 60 62 65 67 70 80 87 94 100

5 10 15 20 25 30 35 40 50 60 70 76 79 81 93 102 110 117

5 10 15 20 25 30 35 40 50 60 70 80 90 100 104 114 123 30

10,000 15,000

INSTANTANEOUS PEAK LET THRU CURRENT IN AMPERES

200000

20,000 10 25,000 11 30,000 11 35,000 12 40,000 13 50,000 14 60,000 15 70,000 15 80,000 16 90,000 17 100,000 17 150,000 20 200,000 22 250,000 24 300,000 25

100000 90000 80000 70000 60000 50000 40000 30000

20000

10000 9000 8000 7000 6000 5000 4000 3000

A
2000

1000 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 60000 70000 80000 90000 100000 20000 30000 40000 50000 200000 300000

AMPERE RATING

Note: For IRMS value at 300,000 amperes, consult Factory.

PROSPECTIVE SHORT CIRCUIT CURRENT - SYMMETRICAL RMS AMPERES

Low-Peak Class J, Dual-Element Time-Delay Fuses LPJ_SP


100000 90000 80000 70000 60000 50000 40000 30000

LPJ_SP Fuse RMS Let-Through Currents (kA)


Prosp. Short C.C.
600A 400A 200A

Fuse Size 15 IRMS 30 IRMS 60 IRMS 100 IRMS 200 IRMS 400 IRMS 600 IRMS

1,000 3,000 5,000 10,000 15,000 20,000 25,000 30,000 35,000 40,000 50,000 60,000 80,000 100,000

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2

1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 3 3 3

1 1 1 2 2 2 2 2 2 3 3 3 3 4 4 4 5 5

1 2 2 2 3 3 3 3 4 4 4 4 5 5 6 6 7 7

1 2 3 4 4 4 5 5 5 6 6 6 7 8 9 9 10 11

1 3 5 6 7 7 8 8 9 9 10 11 12 12 14 16 17 18

1 3 5 8 9 10 10 11 12 12 13 14 15 17 19 21 23 24

INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPERES

20000

100A 60A

10000 9000 8000 7000 6000 5000 4000 3000

30A 15A
AMPERE RATING
100 200 300 400 500 600 700 800 900 1000 3000 4000 6000 7000 8000 9000 10000 2000 5000 60000 70000 80000 90000 100000 20000 30000 40000 50000 200000 300000

2000

1000 900 800 700 600 500 400 300

200

100

150,000 200,000 250,000 300,000

PROSPECTIVE SHORT-CIRCUIT CURRENT - SYMMETRICAL RMS AMPERES

Note: For IRMS value at 300,000 amperes, consult Factory.

210

2005 Cooper Bussmann

Cooper Bussmann Current-Limiting Fuse Let-Through Data

See pages 67 to 69 for current-limiting definition and how to analyze these charts.

Low-Peak Class RK1 Dual-Element Time-Delay Fuses LPN-RK_SP


B
400,000 300,000 200,000

LPN-RK_SP RMS Let-Through Currents (kA)


Prosp. Short C.C. Fuse Size 30 IRMS 60 IRMS 100 IRMS 200 IRMS 400 IRMS 600 IRMS

1,000 2,000
INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPERES
100,000 90,000 80,000 70,000 60,000 50,000 40,000 30,000

1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3

1 1 1 2 2 2 3 3 3 3 3 3 3 3 4 4 4 4 5 5 6

1 2 2 2 3 3 3 3 4 4 4 4 4 4 5 5 5 6 6 7 7

1 2 3 3 4 5 5 5 6 6 6 7 7 7 8 7 8 9 11 11 12

1 2 3 5 7 8 8 9 9 10 10 11 11 12 12 13 13 15 16 17 18

1 2 3 5 9 11 11 12 12 13 13 14 16 16 16 17 17 19 20 21 22

AMPERE RATING

3,000 5,000 10,000 15,000 20,000 25,000 30,000 35,000 40,000 50,000 60,000 70,000 80,000 90,000 100,000 150,000 200,000 250,000 300,000

600A 400A 200A

20,000

100A 60A
10,000 9,000 8,000 7,000 6,000 5,000 4,000 3,000

30A

A
2,000

1,000 100,000 200,000 300,000 10,000 20,000 30,000 40,000 60,000 80,000 1,000 2,000 3,000 4,000 6,000 8,000

PROSPECTIVE SHORT-CIRCUIT CURRENT - SYMMETRICAL RMS AMPERES

Low-Peak Class RK1 Dual-Element Time-Delay Fuses LPS-RK_SP


B
400,000 300,000

LPS-RK_SP RMS Let-Through Currents (kA)


Prosp. Short C.C. Fuse Size 30 IRMS 60 IRMS 100 IRMS 200 IRMS 400 IRMS 600 IRMS

1,000
200,000

1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3

1 1 1 2 2 2 3 3 3 3 3 3 4 4 4 4 4 5 5 6 6

1 2 2 2 3 3 3 4 4 4 4 5 5 5 5 5 6 6 7 7 7

1 2 3 3 4 5 5 6 6 6 6 7 7 8 8 8 9 10 11 12 12

1 2 3 5 7 8 9 9 10 10 10 11 12 13 13 13 14 15 16 17 18

1 2 3 5 10 11 12 12 13 13 14 15 15 16 16 17 17 19 21 22 23

2,000
INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPERES
100,000 90,000 80,000 70,000 60,000 50,000 40,000 30,000

AMPERE RATING

3,000 5,000 10,000 15,000 20,000 25,000 30,000 35,000 40,000 50,000 60,000 70,000 80,000 90,000 100,000 150,000 200,000 250,000 300,000

600A 400A 200A 100A 60A

20,000

10,000 9,000 8,000 7,000 6,000 5,000 4,000 3,000

30A

A
2,000

1,000 100,000 200,000 300,000 10,000 20,000 30,000 40,000 60,000 80,000 1,000 2,000 3,000 4,000 6,000 8,000

PROSPECTIVE SHORT-CIRCUIT CURRENT - SYMMETRICAL RMS AMPERES

2005 Cooper Bussmann

211

Cooper Bussmann Current-Limiting Fuse Let-Through Data

See pages 67 to 69 for current-limiting definition and how to analyze these charts.

Fusetron Class RK5 Dual-Element Time-Delay Fuses FRN-R


400000 300000 200000 AMPERE RATING

FRN-R RMS Let-Through Currents (kA)


Prosp. Short C.C. Fuse Size 30 IRMS 60 IRMS 100 IRMS 200 IRMS 400 IRMS 600 IRMS

5,000 10,000 15,000 20,000 25,000 30,000 35,000 40,000 50,000 60,000 70,000 80,000 90,000 100,000 150,000 200,000

1 2 2 2 2 2 2 2 3 3 3 3 3 3 4 4

2 3 3 4 4 4 4 5 5 5 6 6 6 6 7 8

3 4 5 5 6 6 6 7 7 8 8 8 9 9 10 11

5 7 8 8 9 10 10 11 11 12 13 13 14 14 16 18

5 10 11 12 13 14 15 15 17 18 19 19 20 21 24 26

5 10 15 16 17 18 19 20 21 22 23 24 25 26 29 32

INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPERES

100000 90000 80000 70000 60000 50000 40000 30000 20000

600A 400A 200A

100A 60A

10000 9000 8000 7000 6000 5000 4000 3000

30A

A
2000

1000 3000 4000 5000 6000 7000 8000 9000 10000 1000 2000 30000 50000 60000 70000 80000 90000 100000 20000 40000 200000

PROSPECTIVE SHORT-CIRCUIT CURRENT - SYMMETRICAL RMS AMPERES

Fusetron Class RK5 Dual-Element Time-Delay Fuses FRS-R


400000 300000

FRS-R RMS Let-Through Currents (kA)


Prosp. Short C.C. Fuse Size 30 IRMS 60 IRMS 100 IRMS 200 IRMS 400 IRMS 600 IRMS

5,000 10,000
AMPERE RATING

1 1 1 2 2 2 2 2 2 2 3 3 3 3 3 4

1 2 2 2 2 3 3 3 3 3 4 4 4 4 5 6

3 4 4 5 5 5 5 6 6 6 7 7 7 8 9 9

4 5 6 7 7 8 8 9 9 10 11 12 12 13 14 16

5 9 10 11 12 13 13 14 14 15 17 17 17 18 21 23

5 10 14 15 17 18 18 19 20 22 23 23 24 25 27 32

200000

15,000 20,000 25,000 30,000 35,000 40,000 50,000

INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPERES

100000 90000 80000 70000 60000 50000 40000

600A 400A

200A 30000 100A

20000

60A 10000 9000 8000 7000 6000 5000 4000 3000 30A

60,000 70,000 80,000 90,000 100,000 150,000 200,000

A
2000

1000 3000 4000 6000 7000 8000 9000 10000 1000 2000 5000 60000 70000 80000 90000 100000 20000 30000 40000 50000 200000

PROSPECTIVE SHORT-CIRCUIT CURRENT - SYMMETRICAL RMS AMPERES

212

2005 Cooper Bussmann

Cooper Bussmann Current-Limiting Fuse Let-Through Data

See pages 67 to 69 for current-limiting definition and how to analyze these charts.

Tron Class T Fast-Acting Fuses JJN


INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS
400,000 300,000 200,000 100,000 80,000 60,000 40,000 30,000 20,000 10,000 8,000 6,000 4,000 3,000 2,000 1,000 800 600 400 300 200

JJN RMS Let-Through Current (kA)


B Prosp. Short C.C. AMPERE RATING Fuse Size 15 IRMS 30 IRMS 60 IRMS 100 IRMS 200 IRMS 400 IRMS 600 IRMS 800 IRMS 1200 IRMS

500 1,000 5,000 10,000 15,000 20,000 25,000 30,000 35,000 40,000 50,000 60,000 70,000 80,000 90,000

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2

1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3

1 1 1 2 2 2 2 2 3 3 3 3 3 3 3 4 4 4

1 1 2 2 3 3 3 3 4 4 4 4 5 5 6 6 6 7

1 1 3 4 4 5 5 5 6 6 7 7 7 8 8 8 9 9

1 1 5 6 6 7 7 8 8 9 9 10 10 11 11 12 13 15

1 1 5 7 9 10 10 11 11 11 12 13 14 15 15 16 17 19

1 1 5 9 10 11 12 13 13 13 15 16 17 17 18 19 22 23

1200 800 600 400 200 100 60 30 15

A
6,000 8,000 10,000 20,000 30,000 40,000 60,000 80,000 100,000 100 200 300 400 600 800 1,000 2,000 3,000 4,000 200,000

100,000 1 150,000 1 200,000 2

PROSPECTIVE SHORT-CIRCUIT CURRENTSYMMETRICAL RMS AMPS

Tron Class T Fast-Acting Fuses JJS


INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS
400,000 300,000 200,000 100,000 80,000 60,000 40,000 30,000 20,000 10,000 8,000 6,000 4,000 3,000 2,000 1,000 800 600 400 300 200

JJS RMS Let-Through Current (kA)


B AMPERE RATING Prosp. Short C.C. Fuse Size 15 IRMS 30 IRMS 60 IRMS 100 IRMS 200 IRMS 400 IRMS 600 IRMS 800 IRMS

500 1,000 5,000 10,000 15,000 20,000 25,000 30,000 35,000 40,000 50,000 60,000 70,000 80,000 90,000

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 3 3

1 1 1 1 2 2 2 2 2 2 2 3 3 3 3 3 4 4

1 1 2 2 3 3 3 3 3 4 4 4 4 4 4 5 6 6

1 1 3 3 4 4 5 5 5 5 6 6 7 7 7 7 8 9

1 1 4 6 7 7 7 8 9 9 10 10 11 11 12 12 14 16

1 1 5 8 10 10 11 12 13 13 14 16 17 17 18 19 22 24

1 1 5 9 11 12 13 14 15 15 17 18 19 20 21 22 25 28

800 600 400 200 100 60 30 15

A
6,000 8,000 10,000 20,000 30,000 40,000 60,000 80,000 100,000 100 200 300 400 600 800 1,000 2,000 3,000 4,000 200,000

100,000 2 150,000 2 200,000 2

PROSPECTIVE SHORT-CIRCUIT CURRENTSYMMETRICAL RMS AMPS

2005 Cooper Bussmann

213

Cooper Bussmann Current-Limiting Fuse Let-Through Data

See pages 67 to 69 for current-limiting definition and how to analyze these charts.

Low-Peak Class CC Time-Delay Fuses LP-CC

LP-CC RMS Let-Through Currents (A)


Prosp. Short C.C. Fuse Size 11/4 IRMS 2 8/10 IRMS 15 IRMS 20 IRMS 25 IRMS 30 IRMS

INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS

1,000 3,000 5,000 10,000 20,000 30,000 40,000 50,000 60,000 80,000 100,000 200,000

100 140 165 210 260 290 315 340 350 390 420 525

135 210 255 340 435 525 610 650 735 785 830 1100

240 350 420 540 680 800 870 915 1050 1130 1210 1600

305 440 570 700 870 1030 1150 1215 1300 1500 1600 2000

380 575 690 870 1090 1300 1390 1520 1650 1780 2000 2520

435 580 710 1000 1305 1520 1700 1820 1980 2180 2400 3050

PROSPECTIVE SHORT-CIRCUIT CURRENTSYMMETRICAL RMS AMPS

Limitron Class J Fast-Acting Fuses JKS


400,000

JKS RMS Let-Through Currents (kA)


B Prosp. Short C.C. Fuse Size 30 IRMS 60 IRMS 100 IRMS 200 IRMS 400 IRMS 600 IRMS

INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS

300,000 200,000

5,000
AMPERE RATING

1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 3

1 2 2 2 3 3 3 3 3 3 3 3 4 4 5 5

2 3 3 3 3 3 4 4 4 5 5 5 6 6 6 7

3 4 4 5 6 6 6 7 7 7 8 8 9 9 9 10

4 6 7 8 9 9 9 10 10 11 11 12 13 13 14 16

5 9 10 11 12 13 13 14 15 16 17 17 18 18 22 24

10,000 15,000 20,000 25,000 30,000 35,000 40,000 50,000 60,000 70,000 80,000 90,000 100,000 150,000 200,000

100,000 80,000 60,000 50,000 40,000 30,000 20,000

600 400 200 100 60 30

10,000 8,000 6,000 5,000 4,000 3,000 2,000

1,000

2,000

3,000

4,000 5,000 6,000

8,000 10,000

80,000 100,000

PROSPECTIVE SHORT-CIRCUIT CURRENTSYMMETRICAL RMS AMPS

214

200,000

20,000

30,000

40,000 50,000 60,000

1,000

2005 Cooper Bussmann

You might also like