PT
2008 11 12
CONTENTS 1. SPECIFICATION OF CALCULATION ....................................................................1 2. PRINCIPLE ON PT SELECTION ..............................................................................1 3 CALCULATION FORMULA.......................................................................................1 3.1 SELECTION FOR RATIO OF PT........................................................................1 3.2 SELECTION OF ACCURACY CLASS OF PT ...................................................2 4. SECONDARY LOAD VERIFICATION .....................................................................3 4.1 SECONDARY LOAD OF PT ...............................................................................3 4.2 PARAMETERS OF PT .........................................................................................4
1. SPECIFICATION OF CALCULATION
This calculation shall be done according to the specifications as follows: The Guide for selection and calculation of current transformers and voltage transformers Manual for designing electrical part of electric power engineering (2)
2. PRINCIPLE ON PT SELECTION
2.1 It should meet the requirement of rated primary voltage. 2.2 It should meet the requirement of accuracy class and capacity for measuring meters, protection equipments and automation equipments
Tab. 1-1 Selection of Secondary Voltage of PT Winding Main winding Wiring winding mode of Phase phase voltage Secondary (V) voltage 110 110/3 to phase voltage secondary Aux. secondary winding for zero
sequence voltage In network where In network where neutral point is neutral point is not directly grounded 110/3
1/5
Tab. 1-2 Accuracy Class of Secondary Winding of PT Accuracy Error limits Phase displacement Accuracy class voltage error ( %) min crad Apply to function condition Range of voltage % 0.15 0.3 0.6 1.2 80~120 99~101 25~100 and 120 240 3.5 7.0 5~150 or(5~190 6P 6.0 240 7.0 ) 96~102 0.8(lag) Range of frequenc y % Burden and power factor%
0.1 measure ment 0.2 0.5 1.0 3.0 protectio n Residual voltage winding 3P 6P
5 10 20 40
Tab. 1-1 Accuracy Class of PT and Electrical Measuring Devices Accuracy class Accuracy class of PT of meters 0.5 1.0 1.5 2.5 0.5 0.5 1.0 1.0
2/5
Tab. 1-2 Accuracy Class of PT and Energy Metering Accuracy class of watthour Accuracy class of varhour Accuracy class of CT meters 0.2S 0.5S 1.0 2.0 meters 2.0 2.0 2.0 3.0 0.2 0.2 0.5 0.5
Secondary load of PT for each phase shall be derived from the formula as follows:
W= P 2 + Q 2
(1-2)
Where:
W--- Secondary load of PT(VA); P--- Active power load (W); Q--- Reactive power load (var).
Active power load (P) for each phase shall be derived from the formula as follows: P= Wmcos
(1-3)
Where:
Wm--- Actual secondary load of PT for each phase (VA); --- Phase angle error.
Reactive power load for each phase (Q) shall be derived from the formula as follows: Q= Wmsin
(1-4)
Where:
Wm--- Actual secondary load of PT for each phase (VA); --- Phase angle error.
3/5
When the maximum actual secondary load is smaller than permissible load of PT for each phase, then PT meets the requirement of accuracy class for measuring meters and relays.
4.2 PARAMETERS OF PT
According to the parameter supplied by manufacturer, burden of different devices shall be as below: Each set of protection or automation devices: <5VA/phase Each transducer : <0.5VA ; Each set of tariff metering devices: <6VA/phase;
Ratio:
Accuracy class0.2/3P/6P
For accuracy class 0.2, Wm (for tariff metering or measuring) 12VA, select W=30VA
For accuracy class 3P, Wm: 10(for measuring)+15(for protection) +5(for automation equipment s) 30VA, select W=75VA
For accuracy class 6P(Residual voltage winding), Wm: 2(for measuring)+10(for protection) 12VA, select W=30VA
According to the version supplied by PT manufacturer, rated secondary load of PT shall be capacity: 30/75/30VA(corresponding to 0.2/3P/6P) Therefore, -It meets the requirement of secondary load of PT.
4.2.2 PARAMETERS OF THE OTHERS PT PT at HV side of main transformer, station transformer and startup transformer Ratio: 400 0.11 0.11 0.11 / / / /0.11kV 3 3 3 3
Accuracy class0.2/3P/3P/6P
4/5
Capacity: 30/75/75/30VA
5/5