Technical Site Selection Report

ABB, Faridabad AG2 Location

ABB AG2 site, 5 nearest possible Industrial/commercial plot/properties identified by Infotel team are recommended for further commercial/technical evaluation after field survey by site selection team. The details of these recommended sites are as given below.

Location Co-ordinates Site Name ABB FARIDABAD AG2 Location as per Design - 2827' 22.732" N 7718' 25.849" E
Sl. No. Location Site Address Latitude Plot No. 1523, A Block Market, Green Field, Faridabad. Plot No. 1529, A Block Market, Green Field, Faridabad. Plot No. 644, B Block Market, Green Field, Faridabad. 121003 SCO 63, Huda market Sec 31, Adjoining Pristine Mall, Faridabad-121001 Plot 181, double story Sec 31. Adjoining Pristine mall, Faridabad -121001 2827' 53.4" N Longitude 7718' 3.42" E Distance from Design Location

Remarks

1126 m

Site suitable for AG2

2827' 53.34" N

7718' 1.62" E

1152 m
7717' 43.02" E

Site suitable for AG2

2827' 42.96" N

1320 m
2826'41.3"N 7718'58.6"E

Site suitable for AG2

1558 m
2826'45.6"N 7718'57.4"E

Site suitable for AG2

1432 m

Site suitable for AG2

Plot No -1523 Green Field Market Faridabad

10.00 Ft Road

63.30 ft 30.00 Ft Road

28.50 Ft

30 Ft Road

Front View

Left View

Right View

Road View

Term sheet/Checklist for AG2 facilities


Sl. No.
1

Description / Requirement
Location of Facility
Complete Postal Address with Pin Code Location Coordinates Longitude 7718' 3.42" E Latitude 2827' 53.4" N S.N. Arora 9810183093 Plot No. 1523, A Block Market, Green Field, Faridabad.

Contact Person Phone/Mobile No. of Contact person 2

Does the Property belong to Reliance?


if Yes Is property Owned by Reliance? Is property taken on Lease by Reliance? if No Is property available on Sale? Is property available on Lease? No Lease Period

No No From.. To .. Yes No Lease Period (required for 20 years) From.. To ..

Space Available for Infotel Facilities


Does available property have Open space ? Yes

Minimum Requirement for Open Space a) If Covered/Built-up Area not available i. 1600 sq ft , minimum 25 ft wide b) If Covered/Built-up Area is also available i. 400 sq ft - for Manhole, earth pits, DGs and transformer if emergency power (DG) is not available. ii. 250 sq ft - for Manholes, earth pits plus if DG power is available.

if yes

1804.05 Sqft (28.5 x63.3)

The site is available on sale. Corner Plot having area 1800 Sqft Space for MH, EP, GBM and DG are available. Plot requires Approx 2 m filling. The site is 1.1 Km from designed coordinates.

Minimum Requirement for Covered/Built-up space 400 sq ft, minimum 10 ft width 4

Does available property have covered/built-up space? if yes

No

Is Covered space air conditioned?


Minimum Requirement 8 ton cooling capacity. Only Precision AC is acceptable Controlled Temperature (maximum) 25 deg C if yes NA

No

Power Requirement
Minimum Requirement a) If non AC covered/built-in space or only open space available Normal Power (grid) : 3Ph, 415 V Power No Availab le If yes

Normal Power(grid), kW Emergency Power (DG), KW NA

Connected Load : 64 kW Operating Load : 50 kW Redundant Emergency Power (DG): 3-Ph, 415V, 13 kW b) If covered/built up space available is also having precision air conditioning Normal Power (grid) : 3Ph, 415 V Connected Load : 38 kW Operating Load : 38 kW Redundant Emergency Power (DG): 3-Ph, 415 V, 1 kW

Other Requirements
Access for Personnel 24x7 accesses available? Independent Entry Possible? Access for Equipment Vehicular access available (min 3m road)? Independent Entry for Infotel Possible? Access to Fiber and Electrical cables Space for cable routing to Infotel facility available (required for 20 fiber cables each in 40 mm duct and three phase power supply)? Facility has 24x7 securities? Can it be extended to Infotel? Potable Water Will 250 let potable water be available for use by Yes Yes

Yes Yes

Yes

Security for facilities

No No No

Infotel personnel?

Toilet Facilities

Are toilet facilities available for use by Infotel personnel? Is it possible to share existing earthling system with Infotel (for Lightning, electrical/equipment, DC (for electronic equipment), DG neutral etc.) if available?

No

Earthling Facilities

No

Plot No. 1529, A Block Market, Green Field, Faridabad.

10.00 Ft Road

63.30

28.50 Ft

Main view

inside view

Term sheet/Checklist for AG2 facilities


Sl. No.
1

Description / Requirement
Location of Facility
Complete Postal Address with Pin Code Location Coordinates Plot No. 1529, A Block Market, Green Field, Faridabad.

Contact Person Phone/Mobile No. of Contact person 2

Longitude 7718' 1.62" E Latitude 2827' 53.34" N S.N. Arora 9810183093

Does the Property belong to Reliance?


if Yes Is property Owned by Reliance? Is property taken on Lease by Reliance? if No Is property available on Sale? Is property available on Lease? No

No No Lease Period Yes No Lease Period (required for 20 years) From.. To .. From.. To ..

Space Available for Infotel Facilities


Does available property have Open space? if yes Yes

Minimum Requirement for Open Space a) If Covered/Built-up Area not available i. 1600 sq ft , minimum 25 ft wide b) If Covered/Built-up Area is also available i. 400 sq ft - for Manhole, earth pits, DGs and

1804.05 Sqft (28.5 x63.3)

The site is available on sale. Plot area 1800 Sqft Space for MH, EP, GBM and DG is available. Plot requires Approx 2 m filling. The site is 1.1 Km from designed coordinates.

transformer if emergency power (DG) is not available. ii. 250 sq ft - for Manholes, earth pits plus if DG power is available.

Minimum Requirement for Covered/Built-up space 400 sq ft, minimum 10 ft width 4

Does available property have covered/built-up space? if yes

No

Is Covered space air conditioned?


Minimum Requirement 8 ton cooling capacity. Only Precision AC is acceptable Controlled Temperature (maximum) 25 deg C if yes NA

No

Power Requirement
Minimum Requirement a) If non AC covered/built-in space or only open space available Normal Power (grid) : 3-Ph, 415 V Connected Load : 64 kW Operating Load : 50 kW Redundant Emergency Power (DG): 3-Ph, 415V, 13 kW b) If covered/built up space available is also having precision air conditioning Normal Power (grid) : 3-Ph, 415 V Connected Load : 38 kW Power N0 Available If yes Normal Power(grid), kW Emergency Power (DG), kW NA

Operating Load : 38 kW Redundent Emergency Power (DG): 3-Ph, 415 V, 1 kW

Other Requirements
Access for Personnel 24x7 access available? Independent Entry Possible? Vehicular access available (min 3m road)? Independent Entry for Infotel Possible? Space for cable routing to Infotel facility available (required for 20 fiber cables each in 40 mm duct and three phase power supply)? Facility has 24x7 securities? Can it be extended to Infotel? Will 250 lt potable water be available for use by Infotel personnel? Are toilet facilities available for use by Infotel personnel? Is it possible to share existing earthing system with Infotel (for Lightning, electrical/equipment, DC (for electronic equipment), DG neutral etc.) if available? Yes Yes

Access for Equipment

Yes

Yes

Access to Fiber and Electrical cables

Yes

Security for facilities

No No

Potable Water

No

Toilet Facilities

No

Earthing Facilities

No

Plot N0-644 B Block Mkt Green Field Faridabad121003

60.00 ft

24.00 Ft

30 Ft Road

Front View

Left view

Right View

Term sheet/Checklist for AG2 facilities


Sl. No.
1

Description / Requirement
Location of Facility
Complete Postal Address with Pin Code Location Coordinates Plot No-644 B Block Mkt Green Field faridabad-121003

Contact Person Phone/Mobile No. of Contact person

Longitude Latitude Rajveer Yadav 9811424208

7717' 43.02" E 2827' 42.96" N

Does the Property belong to Reliance?


if Yes Is property Owned by Reliance? Is property taken on Lease by Reliance? if No Is property available on Sale? Is property available on Lease? No

No No Lease Period Yes No Lease Period (required for 20 years) From.. To .. From.. To ..

Space Available for Infotel Facilities


Does available property have Open space? if yes Yes

Minimum Requirement for Open Space a) If Covered/Built-up Area not available i. 1600 sq ft, minimum 25 ft wide b) If Covered/Built-up Area is also available i. 400 sq ft - for Manhole, earth pits, DGs and transformer if emergency power (DG) is not available. ii. 250 sq ft - for Manholes, earth pits plus if DG power is available.

1440 Sqft (24 x 60)

The site is available on sale. Plot area 1440 Sqft Space for MH, EP, GBM and DG is available. Plot requires Approx 1 m filling. The site is 1.3 Km from designed coordinates.

Minimum Requirement for Covered/Built-up space 400 sq ft, minimum 10 ft width 4

Does available property have covered/builtup space? if yes

No

Is Covered space air conditioned?

No

Minimum Requirement 8 ton cooling capacity. Only Precision AC is acceptable Controlled Temperature (maximum) 25 deg C 5

if yes

NA

Power Requirement
Minimum Requirement a) If non AC covered/built-in space or only open space available Normal Power (grid) : 3-Ph, 415 V Connected Load : 64 kW Operating Load : 50 kW Redundant Emergency Power (DG): 3-Ph, 415V, 13 kW b) If covered/built up space available is also having precision air conditioning Normal Power (grid) : 3-Ph, 415 V Connected Load : 38 kW Operating Load : 38 kW Redundant Emergency Power (DG): 3-Ph, 415 V, 1 kW Power Available If yes No Normal Power(grid), kW Emergency Power (DG), kW NA

Other Requirements
Access for Personnel 24x7access available? Independent Entry Possible? Vehicular access available (min 3m road)? Independent Entry for Infotel Possible? Access to Fiber and Electrical cables Space for cable routing to Infotel facility available (required for 20 fiber cables each in 40 mm duct and three phase power supply)? Facility have 24x7 security? Can it be extended to Infotel? Yes Yes Yes Yes

Access for Equipment

Yes

Security for facilities

No No

Potable Water

Will 250 lt potable water be available for use by Infotel personnel? Are toilet facilities available for use by Infotel personnel? Is it possible to share existing earthing system with Infotel (for Lightning, electrical/equipment, DC (for electronic equipment), DG neutral etc.) if available?

No

Toilet Facilities

No

Earthing Facilities

No

Sco-63 Huda Market Sec-31 Faridabad

38

17.5

Front View

Right View

Left View

Right View

Term sheet/Checklist for AG2 facilities


Sl. No.
1

Description / Requirement
Location of Facility
Complete Postal Address with Pin Code Location Coordinates SCO 63, Huda Market Sec 31, Adjoining Pristine Mall, Faridabad-121001 Longitude Latitude Contact Person Phone/Mobile No. of Contact person 7718'58.6"E 2826'41.3"N

Mr. Manchanda 9350646304

Does the Property belong to Reliance?


if Yes Is property Owned by Reliance? Is property taken on Lease by Reliance? if No Is property available on Sale? Is property available on Lease? Yes No

Yes RIL Recommended Vendor Lease Period No Lease Period (required for 20 years) From.. To .. (Available on lease) From.. To ..

Space Available for Infotel Facilities


Does available property have Open space? if yes Yes

Minimum Requirement for Open Space a) If Covered/Built-up Area not available i. 1600 sq ft , minimum 25 ft wide b) If Covered/Built-up Area is also available i. 400 sq ft - for Manhole, earth pits, DGs and transformer if emergency power (DG) is not available. ii. 250 sq ft - for Manholes, earth pits plus if DG power is available.

162 Sq Ft. (12.5x13)

Open space for DG 162 Sqft available on back side.

Does available property have covered/ built-up space?

Yes

Minimum Requirement for Covered/Built-up space 400 sq ft, minimum 10 ft width

if yes

665 Sqft 17.5x38

The site is available on Lease. Total Covered area725 Sqft suitable for AG2. Space for MH, EP available. Open space for DG 162 Sqft available on back side. The site is 1.56 Km from designed coordinates.

Is Covered space air conditio ned?


Minimum Requirement 8 ton cooling capacity. Only Precision AC is acceptable Controlled Temperature (maximum) 25 deg C if yes

No

Cooling Capacity available, tons

NA

Power Requirement
Minimum Requirement a) If non AC covered/built-in space or only open space available Normal Power (grid) : 3Ph, 415 V Connected Load : 64 kW Operating Load : 50 kW Redundent Emergency Power (DG): 3-Ph, 415V, 13 kW b) If covered/built up space available is also having precision air conditioning Normal Power (grid) : 3Ph, 415 V Connected Load : 38 Power Available Yes Commercial Power available

If yes

Normal Power(grid), kW 50 Kw Emergency Power (DG), KW NA

kW Operating Load : 38 kW Redundent Emergency Power (DG): 3-Ph, 415 V, 1 kW

Other Requirements
Access for Personnel 24x7 access available? Independent Entry Possible? Access for Equipment Vehicular access available (min 3m road)? Independent Entry for Infotel Possible? Space for cable routing to Infotel facility available (required for 20 fiber cables each in 40 mm duct and three phase power supply)? Facility have 24x7 security? Can it be extended to Infotel? Potable Water Will 250 lt potable water be available for use by Infotel personnel? Are toilet facilities available for use by Infotel personnel? Is it possible to share existing earthing system with Infotel (for Lightning, electrical/equipment, DC (for electronic equipment), DG neutral etc.) if available? Yes Yes Yes Yes

Access to Fiber and Electrical cables Security for facilities

Yes

No NA Yes

Toilet Facilities Earthing Facilities

Yes

No

Plot No -181 Double Story Sec -31 Faridabad

46'

19'

Front View

Right View

Inside View

Left View

Term sheet/Checklist for AG2 facilities


Sl. No .
1

Description / Requirement

Location of Facility
Complete Postal Address with Pin Code Location Coordinates Plot 181, double story sec 31. adjoining pristine mall, Faridabad -121001 Longitu 7718'57.4"E de Latitud 2826'45.6"N e Mr. Manchanda 9350646304

Contact Person Phone/Mobile No. of Contact person 2

Does the Property belong to Reliance?


if Yes Is property Owned by Reliance? Is property taken on Lease by Reliance? if No Is property available on Sale? Is property available on Lease? No Lease Period (required for 20 years) No

Yes RIL Recommended Vendor Lease Period Yes From.. To .. (Available on lease) From.. To ..

Space Available for Infotel Facilities


Does available property have Open space ? Yes

Minimum Requirement for Open Space a) If Covered/Builtup Area not available i. 1600 sq ft , minimum 25 ft wide b) If Covered/Builtup Area is also available i. 400 sq ft - for Manhole, earthpits, DGs and transformer if emergency power (DG) is not available. ii. 250 sq ft - for Manholes, earthpits plus if DG power is available. Does available property have covered/built-up space? Minimum Requirement for Covered/Built-up space 400 sq ft, minimum 10 ft width 4 if yes No Built-up Area Available, Sq ft

if yes

874 Sqft (46x 19)

The site is available on sale. Total plot area 900 Sqft . As per FAR (19'*35') can be constructed on G. floor. We can construct as per our requirement. Space for MH, EP, DG is available. The site is 1.56 Km from designed coordinates.

NA

Is Covered space air conditioned?


Minimum Requirement 8 ton cooling capacity. Only Precision AC is acceptable Controlled Temperature if yes

No

Cooling Capacity available, tons

NA

(maximum) 25 deg C

Power Requirement
Minimum Requirement a) If non AC covered/built-in space or only open space available Normal Power (grid) : 3-Ph, 415 V Connected Load : 64 kW Operating Load : 50 kW Redundent Emergency Power (DG): 3-Ph, 415V, 13 kW b) If covered/built up space available is also having precision air conditioning Normal Power (grid) : 3-Ph, 415 V Connected Load : 38 kW Operating Load : 38 kW Redundent Power Available No

If yes

Normal Power(grid), kW NA Emergency Power (DG), kW NA

Emergency Power (DG): 3-Ph, 415 V, 1 kW

Other Requirements
Access for Personnel 24x7 access available? Independent Entry Possible? Access for Equipment Vehicular access available (min 3m road)? Independent Entry for Infotel Possible? Space for cable routing to Infotel facility avialble (required for 20 fiber cables each in 40 mm duct and three phase power supply)? Facility has 24x7 security? Can it be extended to Infotel? Will 250 lt potable water be available for use by Infotel personnel? Are toilet facilities available for use by Infotel personnel? Is it possible to share existing earthing system with Infotel (for Lightning, electrical/equipment, DC (for electronic equipment), DG neutral etc.) if available? Yes Yes

Yes

Yes

Access to Fiber and Electrical cables

Yes

Security for facilities

No NA

Potable Water

No

Toilet Facilities

No

Earthing Facilities

No