The capacity of the Proposed Solar Power Plant has been fixed at 1 MWp.x 5Nos. The principle factors considered for designing and selection of proposed plant are local solar radiations, ambient conditions and electrical load characteristics of major system namely the array and power conditioning unit. Moreover, the proposed plant is situated at remote village location, so maximum use of local materials available on site for construction and to retain or preserve the original appearance of the sire and the environment are considered SR.NO. ITEM PV arrays 1.0 Modules in a string 2.0 3.0 4.0 5.0 String in a array Inverters Transformer
ITEM Output Power-Pmax (Watt) Voltage at maximum power-Vmp (Volts) Current at maximum power-Imp (Amps) Open circuit voltage Voc (Volts) Short circuit current-Ise (Amps) Type of solar PV cell Dimensions weight 200 Wp 28.60 V 7.02 36 7.55 Poly Crystalline 1619MM x 1002MM 23.50Kg
17 | P a g e
SOLAR INVERTER ITEM Nominal Voltage 230/400 volts three phase, 4 Wire, grid tracking Nominal
2.0
Output Frequency
50Hz 0.5% inverter to follow grid frequency up to 3Hz of the nominal output frequency during normal operation
3.0
Continuous rating
4.0
800 volts DC
5.0
MPPT Range
6.0
Control Type
7.0
Waveform
8.0
THD
Less than 3 %
9.0
Efficiency
Up to 94%
10.0
Internal
continuous
overload
protection inverter peak current (short circuit) protection Heatsink over temperature grid protection voltage AC
over/under
18 | P a g e
11.0
Alarm Signals
12.0
LCD
panel
with
membrane
inverter (grid ) on line status PV panel voltage Solar charge current and ambient temperature
individual power stage heat sink and cabinet temperature solar radiation (optional ) Inverter Import & export kWh summation solar kWh summation system stepoints and event logs
13.0
Auto connect
mode
selectionTest off
Inverter System
selection
14.0
15.0
Circuit Breakers
ACB / MCCB
16.0
RFI
to and
minimize radiated
both RFI
19 | P a g e
17.0
Earthing Provisions
18.0
19.0
Humidity
20.0
Enclosure
21.0
Computer port
Isolated RS232 port. Provision for Mod bus protocol. WiFi, LAN protocol
22.0
Computer Access
telecommunication dialup facility incorporating either a standard PTSN modem or GSM modem for remote access. SCADA package will be windows based OPSComs.
23.0
System feature
Adjustable logging repetition from 1 sec to 900 seconds Storage capacity of up to 3 year with 10 min logs Time and date stamped log entries Time and Date
annotated fault log, holding the fault description and operating statistics View and change system stapoint configurations remotely Bulk log download for data
20 | P a g e
24.0
Logging Attributes
system for instantaneous viewing and periodic logging are listed below:
System
summations
inverter
import and export kWh Solar (C) 415V PCC x 125 Nos Parameters Inverter volts, amps, kW, kVA, frequency Grid volts and frequency SR. NO. 1.0 1.1 1.1.1 1.1.2 1.1.3 ITEM TECHNICAL PARAMETERS System particulars Rated voltage and phases Frequency System earthing Solar panel temp.
Ambient temperature PV panel voltage Solar charge current Heat sink & cabinet temperatures solar 415 V, 3 Phase, 4 wire radiation (with external 50 Hz pyranometer optional). Effectively earthed
21 | P a g e
1.1.4 1.1.5
Maximum system voltage One minute power frequency withstand voltage (a) Power circuit (b) Control circuit
457 V
2.5 kV 1.5 kV
1.1.6
1.1.7
Short circuit withstand (a) PCC 50 kA/1 sec. 500C max. 900C
Reference ambient Max temp of busbars at rated current CONSTRUCTIONAL REQUIREMENTS Sheet steel thickness Frames Doors Covers Degree of protection Colour finish shade as per IS: 5
2.5 mm cold rolled 2.5 mm cold rolled 2.0 mm cold rolled IP 52 Seven tank process painting with epoxy based
2.3.1 2.3.2
Interior Exterior
2.4
Busbar material
All alloy of E 91 E grade. For main bus bars - copper for Auxiliary bus bars fully insulated
2.4.1 2.5
Fully insulated
22 | P a g e
2.5.1 2.5.2
GS
By bidder 5-50 degrees Celsuis 25.4 mm 19.4 mm All panels Rate for IP30 Draw out type Fixed / plug in type Through cables Minimum 250 mm Bottom
2.6 2.6.1 2.6.2 2.7 2.8 2.8.1 2.8.2 2.9 2.10 2.11 3.0 3.1
Clearances in air of live parts Phase to Phase Phase to earth Single front design Draw out / Fixed type design PCC-ACB MCCB Incoming supply to PCCs Vertical cable alley Cable entry INCOMER CIRCUIT BREAKER FOR PCC Circuit breaker type
No. of Phases Rated breaking capacity Short circuit withstand current Rated current Type of operating mechanism
4 pole 50 kA 50 kA for 1 Second Refer enclosed SLD Motorized spring charged Motor voltage, 220 V Ac, 1Ph.
3.7 3.8
Yes Overload / Earth fault / short circuit / static with settable settings (Microprocessor based)
3.9
Remote communication
Through serial link, Port Rs. 485 with formation of bus wires and communication modem
3.10
Required
Local- Remote selector switch Minimum no. of auxiliary contacts OUTGOING CIRCUIT BREAKER FOR PCC Circuit breaker type
MCCB
23 | P a g e
No. of phases Rated breaking capacity Type of operating mechanism Shunt trip required Relays / series releases
(D) SR. NO. 1.0 1.1 1.2 1.3 1.4 1.5 1.6 2.0 2.1 2.2 2.3 2.4
TRANSFORMER ITEM
GENERAL Application Quantity Installation (Indoor / Outdoor ) Type (Auto / 2 Winding / 3 Winding) Rating Cooling TEMRATURE RISE Ambient temp. maximum Temp. Rise of oil by thermometer Temp. Rise of winding by resistance method Impedance at rated current frequency at 75 C 45 C 50 C 55 C 6.25% Power Transformer 1 No. Outdoor 2 Winding 1.6 MVA ONAN
24 | P a g e
TAPPING: Off Load Tap Changer Tapping on winding (HV) Total tapping range Step RATING No load voltages (a) HV Winding (b) LV Winding 11 kV 433 V 433 V +5 to -5% +10 2.5% ( 5 taps)
50 Hz
5.2 5.3
5.4
Separate Neutral bushing for earth connection (suitable for 1.1kV grade) (a) Material -- G.I. strip (b) Size -- 60 x 12 mm (a) HV Nominal / Highest 11/12 kV (b) LV Nominal / Highest 0.433/0.457 kV (a) HV (6.6kV) system 40 kA (b) LV (415V) system 50 kA (a) HV (11kV) Earth through Resistor (b) LV (415V) Solidly Earth System
6.2
Fault levels
6.3
WINDING Material of Winding Winding connection & vector group Transformer neutral Type of Earthing (a) HV Not applicable (b) LV Solidly Earthed (a) Plain / Flanged : Flanged (b) Unidirectional / Bidirectional : Bidirectional Copper HV (11kV) Delta LV (433V) Star Dyn 11
8.0 8.1
MISCELLANEOUS Wheels
25 | P a g e
Winding temp. indicator required Any special final paint required (Epoxy etc.) Additional connection features for terminal
9.1
HV cable box:
With disconnecting chamber, phase segregated type, provided with space heater thermostat Required for earth connection to earth pit 2000/1 A, class PS for 64R, 2000/1 A, CL 5P10, 15 VA for 51NS shall be provided
(E) SR. NO. 1.0 2.0 3.0 4.0 5.0 6.0 7.0
HT CABLES ITEM Voltage Grade Conductor Conductor Screen Insulation Inner sheath Outer sheath Armoring 11 kV (UE) grade cables, heavy duty Stranded Aluminium Semi conducting compound XLPE Extruded PVC (Type ST-2) Extruded PVC (Type ST-2) Galvanized steel strips for multi-core cables and non-magnetic Aluminium wires for single core cables 90 C current 40kA for 1 sec. 250 C
8.0 9.0
10.0
LT CABLES ITEM POWER CABLE Voltage Grade V/V 1100V for 415V system UNIT
26 | P a g e
Frequency Earthing system Conductor Material Max withstand Temp (a) Normal condition (b) Short circuit condition
Hz C C -
Annealed Cu
90 250 Stranded H4
1.4.3 1.4.4 1.5 1.5.1 1.5.2 1.6 1.6.1 1.6.2 1.7 1.7.1 1.7.2
Conductor type Grade Insulation Material Reference standard Inner Sheath Material Type Outer Sheath Material Type
(G)
EARTHING & LIGHITNG PROTECTION CODES & STANDARDS The earthing of all outdoor equipment and provision of associated earthing systems, electrodes and connections shall be in accordance with the recommendations in the latest IEEE 80/IS 3043. DESIGN CRITERIA GROUNDING SYSTEM The grounding design calculation shall conform to ANSI / IEEE Standard 802000. Earth electrodes shall be provided throughout the plant areas along with the main earth grid. The number of earth electrodes shall be according to achieve the total earth grid resistance less than one (1) ohm. Earth electrodes shall be provided in earth pits. The earth pits shall be of two types namely treated with
27 | P a g e
test links and untreated. Earth electrodes shall be of heavy duty GI pipes, 40 mm dia and 3 meter long. The main buried grid conductors shall be connected to all the earth electrodes to form a total earth grid.
28 | P a g e
GROUNDING MATERIAL Galvanised steel flats of required size shall be used as per approved design. In any case the minimum size shall be 75 x 10 mm. GS strip for earthing conductor. Treated earth pits shall conform to relevant INDIAN Standards. The earth grid shall be installed specified / approved depth of minimum 600mm. EQUIPMENT EARTHING The frames of all electrical equipment and structural steel work shall be earthed by connection to earth grid by branches of same cross sectional area of the earth grid. LIGHTINING PROTECTION SYSTEM Power plant needs protection against Lighting. The system will be designed as per IS: 2309 and Indian Electricity Rules. Vertical air termination of 40mm diameter, 3 M long shall be provided above highest point of array to provide radius of protection full array. (H) SR. NO. 1.0 2.0 3.0 4.0 STRUCTURAL MOUNTING EQUIPMENT ITEM
Ground Mounting MS Galvanized As per design Hot dip (Galvanized) Minimum of 130 Micron size 150 km / hr 30 PCC SS 304 Fastners
29 | P a g e