INVERTER INSTALLATION GUIDELINE

FR-F720-00046 to 04750-NA FR-F740-00023 to 12120-NA

Thank you for choosing this Mitsubishi Inverter. Please read through this Installation Guideline and a CD-ROM enclosed to operate this inverter correctly. Do not use this product until you have a full knowledge of the equipment, safety information and instructions. Please forward this Installation Guideline and the CD-ROM to the end user.

1 2 3 4 5 6 7

CONTENTS INSTALLATION OF THE INVERTER AND INSTRUCTIONS................. 1 OUTLINE DRAWING............................................................................... 2 WIRING.................................................................................................... 4 PRECAUTIONS FOR USE OF THE INVERTER................................... 11 FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER ............ 12 PARAMETER LIST................................................................................ 13 TROUBLESHOOTING........................................................................... 19

700

This section is specifically about safety matters


Do not attempt to install, operate, maintain or inspect the inverter until you have read through this Installation Guideline and appended documents carefully and can use the equipment correctly. Do not use the inverter until you have a full knowledge of the equipment, safety information and instructions. In this Installation Guideline, the safety instruction levels are classified into "WARNING" and "CAUTION". Assumes that incorrect handling may cause hazardous conditions, resulting in death or severe injury. Assumes that incorrect handling may cause hazardous conditions, resulting in medium or slight injury, or may cause physical damage only.

(2) Wiring

Do not install a power factor correction capacitor or surge suppressor on the inverter output side. These devices on the inverter output side may be overheated or burn out. The connection orientation of the output cables U, V, W to the motor will affect the direction of rotation of the motor.

CAUTION

WARNING CAUTION

(3) Test operation and adjustment

Before starting operation, confirm and adjust the parameters. A failure to do so may cause some machines to make unexpected motions.

CAUTION

CAUTION level may lead to a serious consequence Note that even the according to conditions. Please follow strictly the instructions of both levels because they are important to personnel safety.

(4) Operation

When you have chosen the retry function, stay away from the equipment as it will restart suddenly after an alarm stop. Since pressing key may not stop output depending on the function setting status, provide a circuit and switch separately to make an emergency stop (power off, mechanical brake operation for emergency stop, etc). Make sure that the start signal is off before resetting the inverter alarm. A failure to do so may restart the motor suddenly. The load used should be a three-phase induction motor only. Connection of any other electrical equipment to the inverter output may damage the inverter as well as equipment. Do not modify the equipment. Do not perform parts removal which is not instructed in this manual. Doing so may lead to fault or damage of the inverter.

WARNING

1. Electric Shock Prevention

While power is on or when the inverter is running, do not open the front cover. Otherwise you may get an electric shock. Do not run the inverter with the front cover removed. Otherwise, you may access the exposed high-voltage terminals or the charging part of the circuitry and get an electric shock. Even if power is off, do not remove the front cover except for wiring or periodic inspection.You may access the charged inverter circuits and get an electric shock. Before starting wiring or inspection, check to make sure that the operation panel indicator is off, wait for at least 10 minutes after the power supply has been switched off, and check that there are no residual voltage using a tester or the like. The capacitor is charged with high voltage for some time after power off and it is dangerous. This inverter must be grounded. Grounding must conform to the requirements of national and local safety regulations and electrical codes. (NEC section 250, IEC 536 class 1 and other applicable standards) Use an neutral-point earthed (grounded) power supply for 400V class inverter in compliance with EN standard. Any person who is involved in the wiring or inspection of this equipment should be fully competent to do the work. Always install the inverter before wiring. Otherwise, you may get an electric shock or be injured. Perform setting dial and key operations with dry hands to prevent an electric shock. Otherwise you may get an electric shock. Do not subject the cables to scratches, excessive stress, heavy loads or pinching. Otherwise you may get an electric shock. Do not replace the cooling fan while power is on. It is dangerous to replace the cooling fan while power is on. Do not touch the printed circuit board with wet hands. You may get an electric shock. When measuring the main circuit capacitor capacity, the DC voltage is applied to the motor for 1s at powering off. Never touch the motor terminal, etc. right after powering off to prevent an electric shock.

WARNING

2. Fire Prevention

Install the inverter on a nonflammable wall without holes (so that nobody can touch the inverter heatsink on the rear side, etc.). Mounting it to or near flammable material can cause a fire. If the inverter has become faulty, switch off the inverter power. A continuous flow of large current could cause a fire. Do not connect the resistor directly to the DC terminals P/+ and N/-. This could cause a fire.

CAUTION

The electronic thermal relay function does not guarantee protection of the motor from overheating. It is recommended to install both an external thermal and PTC thermistor for overheat protection. Do not use a magnetic contactor on the inverter input for frequent starting/ stopping of the inverter. Use a noise filter to reduce the effect of electromagnetic interference. Otherwise nearby electronic equipment may be affected. Take measures to suppress harmonics. Otherwise power supply harmonics from the inverter may heat/damage the power factor correction capacitor and generator. When a 400V class motor is inverter-driven, please use an insulationenhanced motor or measures taken to suppress surge voltages. Surge voltages attributable to the wiring constants may occur at the motor terminals, deteriorating the insulation of the motor. When parameter clear or all clear is performed, reset the required parameters before starting operations. Each parameter returns to the initial value. The inverter can be easily set for high-speed operation. Before changing its setting, fully examine the performances of the motor and machine. In addition to the inverter's holding function, install a holding device to ensure safety. Before running an inverter which had been stored for a long period, always perform inspection and test operation. For prevention of damage due to static electricity, touch nearby metal before touching this product to eliminate static electricity from your body.

CAUTION

(5) Emergency stop

3. Injury Prevention

Apply only the voltage specified in the instruction manual to each terminal. Otherwise, burst, damage, etc. may occur. Ensure that the cables are connected to the correct terminals. Otherwise, burst, damage, etc. may occur. Always make sure that polarity is correct to prevent damage, etc. Otherwise, burst, damage, etc. may occur. While power is on or for some time after power-off, do not touch the inverter as it is hot and you may get burnt.

CAUTION

Provide a safety backup such as an emergency brake which will prevent the machine and equipment from hazardous conditions if the inverter fails. When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the inverter, etc. Identify the cause of the trip, then remove the cause and power on the breaker. When the protective function is activated, take the corresponding corrective action, then reset the inverter, and resume operation.

CAUTION

(6) Maintenance, inspection and parts replacement


Do not carry out a megger (insulation resistance) test on the control circuit of the inverter. It will cause a failure.

4. Additional Instructions

CAUTION

Also note the following points to prevent an accidental failure, injury, electric shock, etc.

(1) Transportation and installation

When carrying products, use correct lifting gear to prevent injury. Do not stack the inverter boxes higher than the number recommended. Ensure that installation position and material can withstand the weight of the inverter. Install according to the information in the instruction manual. Do not install or operate the inverter if it is damaged or has parts missing. This can result in breakdowns. When carrying the inverter, do not hold it by the front cover or setting dial; it may fall off or fail. Do not stand or rest heavy objects on the product. Check the inverter mounting orientation is correct. Prevent other conductive bodies such as screws and metal fragments or other flammable substance such as oil from entering the inverter. As the inverter is a precision instrument, do not drop or subject it to impact. Use the inverter under the following environmental conditions. Otherwise, the inverter may be damaged.
Surrounding LD air SLD temperature (initial setting) Ambient humidity Storage temperature Atmosphere Altitude, vibration
-10C to +50C(14F to 122F)(non-freezing) -10C to +40C (14F to 104F)(non-freezing) 90% RH or less (non-condensing) -20C to +65C *1 (-4F to 149F) Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt) Maximum 1000m (3280.80feet) above sea level for standard operation. After that derate by 3% for every extra 500m (1640.40feet) up to 2500m (8202feet) (91%) 5.9m/s2 or less *2

CAUTION

(7) Disposing of the inverter


Treat as industrial waste.

CAUTION

General instructions
Many of the diagrams and drawings in instruction manuals show the inverter without a cover, or partially open. Never run the inverter in this status. Always replace the cover and follow instruction manuals when operating the inverter.

Environment

*1 Temperature applicable for a short time, e.g. in transit. *2 2.9m/s2 or less for the FR-F740-04320 or more.

A-1

INSTALLATION OF THE INVERTER AND INSTRUCTIONS

1 INSTALLATION OF THE INVERTER AND INSTRUCTIONS


Inverter Type

FR - F740 - 00126 - NA
Symbol F720 F740 Voltage Class Three-phase 200V class Three-phase 400V class Symbol 200V class 00046 to 04750 400V class 00023 to 12120 Type number Displays the rated current.
Rating plate

Rating plate
Inverter type Input rating
Output rating
LD (50 C) XXA SLD (40 C) XXA

FR-F740-00126-NA

Serial number
Capacity plate

Capacity plate

FR-F740-00126-NA
Overload Current Rating Ambient Temperature

Inverter type
Installation of the inverter

Serial number

LD SLD

120% 60s, 150% 3s 110% 60s, 120% 3s

50 C(122 F) 40 C(104 F)

Note - Some inverter models may be installed outside an enclosure. See Appendix 2 for details.

CAUTION
When encasing multiple inverters, install them in parallel as a cooling measure.

Installation on the enclosure


FR-F720-01250 or less FR-F740-00620 or less FR-F720-01540 or more FR-F740-00770 or more

10cm(3.94inches) or more *2

10cm(3.94inches) or more *2

5cm(1.97inch

es) or more *1

*1 1cm or more for FR-F720-00167 (FR-F740-00083) or less 10cm or more for FR-F720-03160 (FR-F740-01800) or more *2 20cm or more for FR-F720-03160 (FR-F740-01800) or more

Fix six positions for the FR-F74004320 to 08660 and fix eight positions for the FR-F740-09620 to 12120. General Precaution

The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more than 10 minutes, and check for residual voltage between terminal P/+ and N/- with a meter etc., to avoid a hazard of electrical shock. Environment Before installation, check that the environment meets following specifications.
LD: -10C to + 50C (14F to 122F) Maximum (nonfreezing) SLD (initial setting): -10C to + 40C (14F to 104F) Maximum (non-freezing)
Measurement position 5cm (1.97inches) Measurement position Inverter 5cm (1.97inches) 5cm (1.97inches)

Surrounding Air Temperature

Ambient humidity Storage temperature Ambience Altitude, vibration

90%RH or less (non-condensing) -20C to + 65C (-4F to 149F) Indoors (No corrosive and flammable gases, oil mist, dust and dirt.) Below 1000m, 5.9m/s2 or less (2.9m/s2 or less for the FR-F740-04320 or more)

CAUTION
Install the inverter on a non-combustible wall surface such as metal or concrete. Mount the inverter on a strong surface securely and vertically with bolts. Provide sufficient clearance distances away from other devices. WARNING: HEAT SINK SURFACE MAY BE HOT. TO REDUCE RISK OF BURN - DO NOT TOUCH.

OUTLINE DRAWING

2 OUTLINE DRAWING
FR-F720-00046 to 04750-NA FR-F740-00023 to 03610-NA FR-F740-04320 to 08660-NA FR-F740-09620 to 12120-NA

H1 H

H1 H

W1 W

W1 W

W1

W1

W1 W

W1

H1 H

(Unit:mm(inches)) 200V class


Inverter Type
FR-F720-00046-NA FR-F720-00077-NA FR-F720-00105-NA FR-F720-00167-NA FR-F720-00250-NA FR-F720-00340-NA FR-F720-00490-NA FR-F720-00630-NA FR-F720-00770-NA FR-F720-00930-NA FR-F720-01250-NA FR-F720-01540-NA FR-F720-01870-NA FR-F720-02330-NA FR-F720-03160-NA FR-F720-03800-NA FR-F720-04750-NA

W
110 (4.33)

W1
95 (3.74)

H1

D
110 (4.33) 125 (4.92)

150 (5.91)

125 (4.92)

260 (10.24)

245 (9.65)

140 (5.51)

220 (8.66)

195 (7.68) 300 (11.81) 285 (11.22) 380 (14.96) 530 (20.87) 550 (21.65) 525 (20.67)

170 (6.69)

250 (9.84) 325 (12.8) 435 (17.13)

230 (9.06) 270 (10.63) 380 (14.96)

400 (15.75)

190 (7.48)

195 (7.68) 250 (9.84)

465 (18.31)

400 (15.75)

740 (29.13)

715 (28.15)

360 (14.17)

OUTLINE DRAWING
400V class
Inverter Type
FR-F740-00023-NA FR-F740-00038-NA FR-F740-00052-NA FR-F740-00083-NA FR-F740-00126-NA FR-F740-00170-NA FR-F740-00250-NA FR-F740-00310-NA FR-F740-00380-NA FR-F740-00470-NA FR-F740-00620-NA FR-F740-00770-NA FR-F740-00930-NA FR-F740-01160-NA FR-F740-01800-NA FR-F740-02160-NA FR-F740-02600-NA FR-F740-03250-NA FR-F740-03610-NA FR-F740-04320-NA FR-F740-04810-NA FR-F740-05470-NA FR-F740-06100-NA FR-F740-06830-NA FR-F740-07700-NA FR-F740-08660-NA FR-F740-09620-NA FR-F740-10940-NA FR-F740-12120-NA

W1

H1

150 (5.91)

125 (4.92) 260 (10.24) 245 (9.65)

140 (5.51)

170 (6.69) 220 (8.66) 195 (7.68) 300 (11.81) 250 (9.84) 325 (12.8) 435 (17.13) 230 (9.06) 270 (10.63) 380 (14.96) 400 (15.75) 550 (21.65) 550 (21.65) 285 (11.22) 380 (14.96) 530 (20.87) 525 (20.67) 190 (7.48) 190 (7.48) 195 (7.68) 250 (9.84)

620 (24.41) 465 (18.31) 400 (15.75) 740 (29.13) 498 (19.6) 200 (7.87) 1010 (39.76) 680 (26.77) 300 (11.81)

595 (23.43) 715 (28.15)

300 (11.81) 360 (14.17)

984 (38.77)

380 (14.96)

790 (31.1)

315 (12.4)

1330 (52.36)

1300 (51.18) 440 (17.32)

995 (39.17)

300 (11.81)

1580 (62.2)

1550 (61.02)

3 WIRING
Sink logic Main circuit terminal Control circuit terminal *1. DC reactor (FR-HEL)
Be sure to connect the DC reactor supplied with the FR-F720-03160 (FR-F740-01800) or more. When a DC reactor is connected to the 02330 (FR-F740-01160) or less, remove the jumper across P1-P/+.

*1

Resistor unit *6. A CN8 (for MT-BU5) connector is (Option) provided for the FR-F720-03160 Brake unit (FR-F740-01800) or more. (Option) Jumper

Ground

Jumper P/+

MCCB Three-phase AC power supply

MC

P1 R/L1 S/L2 T/L3

Jumper *2. To supply power to the control circuit separately, remove the jumper across R1/L11 and S1/L21.

*2

R1/L11 S1/L21

PR*7 PX*7 N/- CN8*6 U V W ON EMC filter ON/OFF OFF connector *8

*7. Do not use PR and PX terminals. Please do not remove the jumper connected to terminal PR and PX.
Motor IM Ground

Ground

Main circuit Control circuit


STF STR
STOP

*8. The 200V class 00046 and 00077 are not provided with the ON/OFF connector EMC filter.

Control input signals (No voltage input allowed) Forward Terminal functions vary rotation with the input terminal start assignment Reverse (Pr. 178 to Pr. 189) rotation (Refer to the Instruction start Manual chapter4.) Start self-holding selection High speed Multi-speed selection Middle speed Low speed Jog mode Second function selection *3. AU terminal can be used as PTC input terminal. Output stop Reset

C1 B1 A1 C2 B2 Relay output 2 A2

Relay output Terminal functions vary with the output Relay output 1 terminal assignment (Fault output) (Pr. 195, Pr. 196)
Refer to the Instruction Manual chapter4.

RH RM RL JOG RT MRS RES *3 AU AU


SINK

RUN SU IPF OL FU
SOURCE

Open collector output Running Terminal functions vary with the output Up to frequency terminal assignment (Pr. 190 to Pr. 194) Instantaneous Refer to the power failure Instruction Manual
chapter4.

Overload Frequency detection

Terminal 4 input selection (Current input selection) Selection of automatic restart after instantaneous power failure Contact input common 24VDC power supply (Common for external power supply transistor) Frequency setting signal (Analog) Frequency setting potentiometer 1/2W1k *5
*4. Terminal input specifications can be changed by analog input specifications switchover (Pr. 73, Pr. 267). Set the voltage/current input switch in the OFF position to select voltage input (0 to 5V/0 to 10V) and ON to select current input (0 to 20mA).

CS PTC SD PC

SE

Open collector output common Sink/source common

*4 Voltage/current

PU connector

3 2 1

input switch 4 2 10E(+10V) ON 10(+5V) OFF 0 to 5VDC Initial value 2 0 to 10VDC selected *4 0 to 20mADC 5 (Analog common) Initial 0 to 10VDC value 1 0 to 5VDC selected *4 Initial 4 to 20mADC value 4 0 to 5VDC selected *4 0 to 10VDC

CA

(+) (-)

Analog current output (0 to 20mADC)

AM 5

(+) (-)

Analog signal output (0 to 10VDC) RS-485 terminals

Auxiliary (+) input (-) Terminal 4 input (+) (-) (Current input) Connector for plug-in option connection

TXD+ TXDRXD+ RXDSG

Data transmission Data reception


GND 5V (Permissible load current 100mA)

(Refer to the Instruction Manual chapter4.)

*5. It is recommended to use 2W1k when the frequency setting signal is changed frequently.

Option connector 1

Terminating resistor VCC

To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables. Also separate the main circuit wire of the input side and the output side. After wiring, wire offcuts must not be left in the inverter. Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes in a control box etc., take care not to allow chips and other foreign matter to enter the inverter. Set the voltage/current input switch correctly. Different setting may cause a fault, failure or malfunction.

CAUTION

WIRING

3.1 Main circuit terminal


(1) Terminal layout and wiring 200V class
FR-F720-00046, 0007-NA
Jumper Jumper Screw size (M4) R/L1 S/L2 T/L3
Screw size (M4)

FR-F720-00105 to 00250-NA
Jumper N/P/+ PR

PR
Jumper

R/L1 S/L2 T/L3

R1/L11 S1/L21 N/-

P/+

PX

R1/L11 S1/L21

PX

IM
Power supply Motor

Charge lamp As this is an inside cover fixing screw, do not remove it.

Screw size (M4)

IM
Power supply Motor

Screw size (M4)

Charge lamp

FR-F720-00340, 00490NA

FR-F720-00630-NA

R1/L11 S1/L21

Charge lamp

Screw size (M4) Jumper

Charge lamp

Jumper Screw size (M5)

N/-

P/+ PR

R1/L11 S1/L21

Jumper
Screw size (M5)

Jumper P/+

PX R/L1 S/L2 T/L3

R/L1 S/L2 T/L3

N/-

PR

IM
Power supply Screw size of terminal R1/L11, S1/L21, PR and PX is M4. Motor Screw size (M5)

IM
Motor Power supply Screw size (M5)

FR-F720-00770 to 01250-NA

FR-F720-01540 to 02330-NA
R1/L11 S1/L21 R1/L11 S1/L21

Screw size (M4) Charge lamp Screw size (00770:M6, 00930/01250:M8) Jumper

Screw size (M4) Charge lamp PR Jumper

R/L1 S/L2 T/L3

N/-

P/+ Jumper Screw size (01540:M8, 01870/02330:M10)

IM
Power supply Motor

Screw size (M6) R/L1 S/L2 T/L3 N/P/+ Jumper

Power supply

Screw size (01540:M6, 01870/02330:M8)

IM
Motor

WIRING
FR-F720-03160 to 04750-NA
R1/L11 S1/L21 Screw size (M4) Charge lamp Jumper

Screw size (M12) R/L1 S/L2 T/L3 P/+ Screw size (M10) P/+ Power supply Screw size (M12) (for option) N/P/+

IM
Motor

DC reactor

400V class
FR-F740-00023, 00038, 00052, 00083, 00126-NA
Jumper Screw size (M4) Jumper R/L1 S/L2 T/L3 N/P/+ PR

FR-F740-00170, 00250-NA

Charge lamp

R1/L11 S1/L21

PX

IM
Power supply Motor

Screw size (M4)

Jumper
Charge lamp

N/R1/L11 S1/L21

P/+ PR

Jumper

Screw size (M4) PX R/L1 S/L2 T/L3

IM
Motor Power supply Screw size (M4)

FR-F740-00310, 00380-NA
R1/L11 S1/L21 Screw size (M4)

FR-F740-00470, 00620-NA

Jumper Charge lamp Jumper


P/+

R1/L11 S1/L21 Screw size (M4) Charge lamp Screw size (M6) Jumper PR

Screw size (M5)

R/L1 S/L2 T/L3

N/-

P/+

R/L1 S/L2 T/L3

N/-

PR

IM
Power supply Motor

Jumper

IM
Motor Power supply Screw size (M5)

Screw size (M6)

WIRING
FR-F740-00770 to 01160-NA
R1/L11 S1/L21 Screw size(M4) Charge lamp Jumper
R1/L11 S1/L21 Screw size (M4) Charge lamp Jumper

FR-F740-01800 to 02600-NA

Screw size (00770: M6 00930/01160: M8)

Screw size Screw size (01800: M8, 02160/02600: M10) Screw size (M10) (01800: M8, 02160/02600: M10)

R/L1 S/L2 T/L3

N/-

P/+ P/+

R/L1 S/L2 T/L3

N/-

P/+ Jumper

IM
Motor Screw size (01800: M8, 02160/02600: M10)

Power supply

Screw size (00770: M6 00930/01160: M8)

IM
Motor

Power supply

DC reactor

FR-F740-03250 to 04810-NA
R1/L11 S1/L21 Screw size (M4) Charge lamp Jumper

FR-F740-05470 to 12120-NA
R1/L11 S1/L21 Screw size (M4) Charge lamp Jumper

Screw size (03250/03610: M10 04320/04810: M12) R/L1 S/L2 T/L3 P/+ R/L1 S/L2 T/L3 N/Screw size (M10)

N/-

P/+ Screw size (M12) P/+

P/+ Power supply Screw size (M12) (for option)

IM
Motor P/+ Power supply DC reactor Screw size (M10)

DC reactor

IM
Motor

CAUTION
The power supply cables must be connected to R/L1, S/L2, T/L3. (Phase sequence needs not to be matched.) Never connect the power cable to the U, V, W of the inverter. Doing so will damage the inverter. Connect the motor to U, V, W. At this time, turning on the forward rotation switch (signal) rotates the motor in the counterclockwise direction when viewed from the motor shaft. When wiring the inverter main circuit conductor of the FR-F740-05470 or more, tighten a nut from the right side of the conductor. When wiring two wires, place wires on both sides of the conductor. (Refer to the drawing below.) For wiring, use bolts (nuts) provided with the inverter.

WIRING
(2) Cable size
Select the recommended cable size to ensure that a voltage drop will be 2% max. If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to decrease especially at the output of a low frequency. The following table indicates a selection example for the wiring length of 20m (65.62feet).

200V class (when input power supply is 220V)


Applicable Inverter Type Crimping Terminal Tightening Terminal Screw Torque R/L1, Size *4 Nm S/L2, U, V, W
T/L3

Cable Sizes
HIV, etc. (mm2) *1
R/L1, S/L2, T/L3

AWG/MCM *2 U, V, W 14 12 10 8 6 6 (*5) 2 2 1/0 3/0 4/0 4/0 250 24/0 24/0

PVC, etc. (mm2) *3


R/L1, S/L2, T/L3

Ground R/L1, S/L2, U, V, W T/L3 cable 2 2 3.5 5.5 14 14 14 22 22 38 38 60 60 38 38 38 14 12 10 6 6 4 2 2 1/0 3/0 4/0 4/0 250 24/0 24/0

U, V, W 2.5 4 6 10 16 25 50 50 50 70 95 95

Ground cable 2.5 4 6 16 16 16 25 25 25 35 50 50

FR-F720-00046 to M4 00105-NA FR-F720-00167-NA M4 FR-F720-00250-NA M4 FR-F720-00340-NA M5 FR-F720-00490-NA M5 FR-F720-00630-NA M5 FR-F720-00770-NA M6 FR-F720-00930-NA M8(M6) FR-F720-01250-NA M8(M6) FR-F720-01540-NA M8(M6) FR-F720-01870-NA M10(M8) FR-F720-02330-NA M10(M8) FR-F720-03160-NA M12(M10) FR-F720-03800-NA M12(M10) FR-F720-04750-NA M12(M10)
*1

1.5 1.5 1.5 2.5 2.5 2.5 4.4 7.8 7.8 7.8 14.7 14.7 24.5 24.5 24.5

2-4 5.5-4 5.5-4 14-5 14-5 22-5 38-6 38-8 60-8 80-8 100-10 100-10 150-12 150-12 100-12

2-4

2.5 4 6 16 16 25 50 50 50 70 95 95

5.5-4 3.5 3.5 5.5-4 5.5 5.5 8-5 14 8 14-5 14 14 22-5 22 22 38-6 38 38 38-8 38 38 60-8 60 60 80-8 80 80 100-10 100 100 100-10 100 100 150-12 125 125 150-12 150 150 100-12 2100 2100

*2

*3

*4 *5

The recommended cable size is that of the cable (e.g. HIV cable (600V class 2 vinyl-insulated cable)) with continuous maximum permissible temperature of 75C (167F). Assumes that the surrounding air temperature is 50C (122F) or less and the wiring distance is 20m (65.62feet) or less. The recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75C (167F). Assumes that the surrounding air temperature is 40C (104F) or less and the wiring distance is 20m (65.62feet) or less. (Selection example for use mainly in the United States.) For the FR-F720-00930 or less, the recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70C (158F). Assumes that the surrounding air temperature is 40C (104F) or less and the wiring distance is 20m(65.62feet) or less. For the FR-F720-01250 or more, the recommended cable size is that of the cable (XLPE cable) with continuous maximum permissible temperature of 90C (194F). Assumes that the surrounding air temperature is 40C (104F) or less and wiring is performed in an enclosure. (Selection example for use mainly in Europe.) The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, and a screw for grounding. A screw for earthing (grounding) of the FR-F720-00930 or more is indicated in ( ). When connecting the option unit to P/+, P1, N/-, use THHN cables for the option and terminals R/L1, S/L2, T/L3, U, V, W.

WIRING
400V class (when input power supply is 440V based on the rated current for 110% overload for 1 minute)
Applicable Inverter Type Terminal Tightening Screw Size Torque Nm *4 Crimping (Compression) Terminal R/L1, U, V, S/L2, W T/L3
2-4 2-4 5.5-4 5.5-4 8-5 14-5 14-6 22-6 22-6 38-8 60-8 60-8 100-10 100-10 150-10 150-10 100-12 100-12 150-12 150-12 200-12 C2-200 C2-250 C2-250 C2-200 C2-200 2-4 2-4 5.5-4 5.5-4 8-5 8-5 14-6 22-6 22-6 38-8 60-8 60-8 100-10 150-10 150-10 150-10 100-12 100-12 150-12 150-12 200-12 C2-200 C2-250 C2-250 C2-200 C2-200

Cable Sizes HIV, etc. (mm2) *1 R/L1, S/L2, T/L3


2 2 3.5 5.5 8 14 14 22 22 38 60 60 80 100 125 150 2100 2100 2125 2150 2200 2200 2250 2250 3200 3200

AWG/MCM *2 R/L1, S/L2, T/L3


14 12 12 10 8 6 6 4 4 1 1/0 1/0 3/0 4/0 250 300 24/0 24/0 2250 2300 2350 2400 2500 2500 3350 3400

PVC, etc. (mm2) *3 R/L1, S/L2, T/L3


2.5 2.5 4 6 10 16 16 25 25 50 50 50 70 95 120 150 295 295 2120 2150 2185 2185 2240 2240 3185 3185

U, V, W
2 2 3.5 5.5 8 8 14 22 22 38 60 60 80 100 125 150 2100 2100 2125 2150 2200 2200 2250 2250 3200 3200

Ground

cable
2 3.5 3.5 8 8 14 14 14 14 22 22 38 38 38 38 38 38 38 38 38 60 60 60 100 100 100

U, V, W
14 14 12 10 8 8 6 4 4 2 1/0 1/0 3/0 4/0 250 300 24/0 24/0 2250 2300 2350 2400 2500 2500 3350 3400

U, V, W
2.5 2.5 4 6 10 10 16 25 25 50 50 50 70 95 120 150 295 295 2120 2150 2185 2185 2240 2240 3185 3185

Ground

cable
2.5 4 4 10 10 16 16 16 16 25 25 25 35 50 70 95 95 95 120 150 295 295 2120 2120 2150 2150

FR-F740-00023 to 00083-NA FR-F740-00126-NA FR-F740-00170-NA FR-F740-00250-NA FR-F740-00310-NA FR-F740-00380-NA FR-F740-00470-NA FR-F740-00620-NA FR-F740-00770-NA FR-F740-00930-NA FR-F740-01160-NA FR-F740-01800-NA FR-F740-02160-NA FR-F740-02600-NA FR-F740-03250-NA FR-F740-03610-NA FR-F740-04320-NA FR-F740-04810-NA FR-F740-05470-NA FR-F740-06100-NA FR-F740-06830-NA FR-F740-07700-NA FR-F740-08660-NA FR-F740-09620-NA FR-F740-10940-NA FR-F740-12120-NA
*1

M4 M4 M4 M4 M5 M5 M6 M6 M6 M8 M8 M8 M10 M10 M10 M10 M12(M10) M12(M10) M12(M10) M12(M10) M12(M10) M12(M10) M12(M10) M12(M10) M12(M10) M12(M10)

1.5 1.5 1.5 1.5 2.5 2.5 4.4 4.4 4.4 7.8 7.8 7.8 14.7 14.7 14.7 14.7 24.5 24.5 24.5 24.5 24.5 24.5 24.5 24.5 24.5 24.5

*2

*3

*4

For the FR-F740-01160 or less, the recommended cable size is that of the cable (e.g. HIV cable (600V class 2 vinyl-insulated cable)) with continuous maximum permissible temperature of 75C (167F). Assumes that the ambient temperature is 50C (122F) or less and the wiring distance is 20m (65.62feet) or less. For the FR-F740-01800 or more, the recommended cable size is that of the cable (e.g. LMFC (heat resistant flexible cross-linked polyethylene insulated cable)) with continuous maximum permissible temperature of 90C (194F). Assumes that the surrounding air temperature is 50C (122F) or less and wiring is performed in an enclosure. For the FR-F740-00930 or less, the recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75C (167F). Assumes that the surrounding air temperature is 40C (104F) or less and the wiring distance is 20m (65.62feet) or less. For the FR-F740-01160 or more, the recommended cable size is that of the cable (THHN cable) with continuous maximum permissible temperature of 90C (194F). Assumes that the surrounding air temperature is 40C (104F) or less and wiring is performed in an enclosure. (Selection example for use mainly in the United States.) For the FR-F740-00930 or less, the recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70C (158F). Assumes that the surrounding air temperature is 40C (104F) or less and the wiring distance is 20m (65.62feet) or less. For the FR-F740-01160 or more, the recommended cable size is that of the cable (XLPE cable) with continuous maximum permissible temperature of 90C (194F). Assumes that the surrounding air temperature is 40C (104F) or less and wiring is performed in an enclosure. (Selection example for use mainly in the Europe.) The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, and a screw for grounding. A screw for earthing (grounding) of the FR-F740-04320 or more is indicated in ( ).

The line voltage drop can be calculated by the following formula: line voltage drop [V]=

3 wire resistance[m/m] wiring distance[m] current[A] 1000

Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque reduction) in the low speed range. CAUTION
Tighten the terminal screw to the specified torque. A screw that has been tighten too loosely can cause a short circuit or malfunction. A screw that has been tighten too tightly can cause a short circuit or malfunction due to the unit breakage. Use crimping terminals with insulation sleeve to wire the power supply and motor.

WIRING
(3) Total wiring length The overall wiring length for connection of a single motor or multiple motors should be within the value in the table below.
Pr. 72 PWM frequency selection setting (carrier frequency)
2 (2kHz) or less 3 to 15 (3kHz to 14.5kHz)

FR-F720-00046 FR-F740-00023
300m (984.25feet) 200m (656.19feet)

FR-F720-00077 FR-F740-00038
500m (1640.42feet) 300m (984.25feet)

FR-F720-00105 or more FR-F740-00052 or more


500m (1640.42feet) 500m (1640.42feet)

When driving a 400V class motor by the inverter, surge voltages attributable to the wiring constants may occur at the motor terminals, deteriorating the insulation of the motor. Take the following measures in this case. Take the following measures (1) or (2) in this case. (1) Use a "400V class inverter-driven insulation-enhanced motor" and set frequency in Pr. 72 PWM frequency selection according to wiring length.
Wiring Length
50m (164.04feet) or less Pr. 72 PWM frequency selection setting (carrier frequency) 50m (164.04feet) to 100m(328.08feet) exceeding 100m (328.08feet)

14.5kHz or less

9kHz or less

4kHz or less

(2) Connect the surge voltage suppression filter (FR-ASF-H) to the FR-F720-02330 (FR-F740-01160) or less and the sine wave filter (MT-BSL/BSC) to the FR-F720-03160 (FR-F740-01800) or more on the inverter output side. CAUTION
Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray capacitances of the wiring, leading to a malfunction of the overcurrent protective function or fast response current limit function or a malfunction or fault of the equipment connected on the inverter output side. If fast-response current limit function malfunctions, disable this function. (For Pr.156 Stall prevention operation selection, refer to the Instruction Manual.) For details of Pr. 72 PWM frequency selection ,refer to the Instruction Manual. When using an optional sine wave filter (MT-BSL/BSC) for

the FR-F720-03160 (FR-F740-01800) or more, set 25 in Pr.72 (2.5kHz).


For explanation of surge voltage suppression filter (FR-ASF-H) and sine wave filter (MT-BSL/BSC), refer to the manual of each option.

(4) Cable size of the control circuit power supply (terminal R1/L11, S1/L21)
Terminal screw size: M4 Cable size: 0.75mm2 to 2mm2 Tightening torque: 1.5Nm

3.2 Control circuit terminals


(1) Terminal layout
Terminal Screw Size: M3.5 Tightening torque: 1.2Nm
A1 B1 C1 A2 B2 C2 10E 10 2 5 CA AM 4 1 PC

RL RM RH

RT

AU STOP MRS RES SD FU SD

SE RUN SU IPF OL

SD STF STR JOG CS

(2) Instructions for wiring of the control circuit terminal


1) 2) 3) Terminals 5, PC and SE are common to the I/O signals and isolated from each other. Do not ground. Use shielded or twisted cables for connection to the control circuit terminals and run them away from the main and power circuits (including the 200V relay sequence circuit). Use two or more parallel micro-signal contacts or twin contacts to prevent a contact faults when using contact inputs since the control circuit input signals are micro-currents.

Micro signal contacts

Twin contacts

4) 5) 6)

7)

Do not apply a voltage to the contact input terminals (e.g. STF) of the control circuit. Always apply a voltage to the fault output terminals (A, B, C) via a relay coil, lamp, etc. It is recommended to use the cables of 0.75mm2 gauge for connection to the control circuit terminals. If the cable gauge used is 1.25mm2 or more, the front cover may be lifted when there are many cables running or the cables are run improperly, resulting in an operation panel contact fault. The wiring length should be 30m (98.43feet) maximum.

10

PRECAUTIONS FOR USE OF THE INVERTER

4 PRECAUTIONS FOR USE OF THE INVERTER


The FR-F700 series is a highly reliable product, but incorrect peripheral circuit making or operation/handling method may shorten the product life or damage the product. Before starting operation, always recheck the following items.
(1) (2) (3) (4) (5) Use crimping terminals with insulation sleeve to wire the power supply and motor. Application of power to the output terminals (U, V, W) of the inverter will damage the inverter. Never perform such wiring. After wiring, wire offcuts must not be left in the inverter. Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter. Use cables of the size to make a voltage drop 2% maximum. If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to decrease especially at the output of a low frequency. Refer to page 8 for the recommended cable sizes. The overall wiring length should be 500m (1640.4 feet) maximum. Especially for long distance wiring, the fast response current limit function may decrease or the equipment connected to the secondary side may malfunction or become faulty under the influence of a charging current due to the stray capacity of the wiring. Therefore, note the overall wiring length. (Refer to page 10.) Electromagnetic wave interference The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the communication devices (such as AM radios) used near the inverter. In this case, set the EMC filter valid to minimize interference. Do not install a power factor correction capacitor, surge suppressor or radio noise filter on the inverter output side. This will cause the inverter to trip or the capacitor, varistor, or arrester to be damaged. If any of the above devices is installed, immediately remove it. Before starting wiring or other work after the inverter is operated, wait for at least 10 minutes after the power supply has been switched off, and check that there are no residual voltage using a tester or the like. The capacitor is charged with high voltage for some time after power off and it is dangerous. A short circuit or ground fault on the inverter output side may damage the inverter modules. Fully check the insulation resistance of the circuit prior to inverter operation since repeated short circuits caused by peripheral circuit inadequacy or a ground fault caused by wiring inadequacy or reduced motor insulation resistance may damage the inverter modules. Fully check the to-ground insulation and phase to phase insulation of the inverter output side before power-on. Especially for an old motor or use in hostile atmosphere, securely check the motor insulation resistance etc. Do not use the inverter input side magnetic contactor to start/stop the inverter. Always use the start signal (ON/OFF of STF and STR signals) to start/stop the inverter. Do not apply a voltage higher than the permissible voltage to the inverter I/O signal circuits. Application of permissible voltage to the inverter I/O signal circuit and incorrect polarity may damage the I/O terminal. Especially check the wiring to prevent the speed setting potentiometer from being connected incorrectly to short terminals 10E-5. Provide electrical and mechanical interlocks for MC1 and MC2 MC1 which are used for bypass operation. Interlock When the wiring is incorrect and if there is a bypass operation Power R/L1 U IM circuit as shown right, the inverter will be damaged when the supply S/L2 V MC2 power supply is connected to the inverter U, V, W terminals, due T/L3 W Undesirable current to arcs generated at the time of switch-over or chattering caused Inverter by a sequence error. If the machine must not be restarted when power is restored after a power failure, provide a magnetic contactor in the inverter's input side and also make up a sequence which will not switch on the start signal. If the start signal (start switch) remains on after a power failure, the inverter will automatically restart as soon as the power is restored. Instructions for overload operation When performing operation of frequent start/stop of the inverter, increase/decrease in the temperature of the transistor element of the inverter may repeat due to a continuous flow of large current, shortening the life from thermal fatigue. Since thermal fatigue is related to the amount of current, the life can be increased by reducing bound current, starting current, etc. Decreasing current may increase the life. However, decreasing current will result in insufficient torque and the inverter may not start. Therefore, increase the inverter capacity to have enough allowance for current. Make sure that the specifications and rating match the system requirements. When the motor speed is unstable, due to change in the frequency setting signal caused by electromagnetic noises from the inverter, take the following measures when applying the motor speed by the analog signal. Do not run the signal cables and power cables (inverter I/O cables) in parallel with each other and do not bundle them. Run signal cables as far away as possible from power cables (inverter I/O cables). Use shield cables as signal cables. Install a ferrite core on the signal cable (Example: ZCAT3035-1330 TDK).

(6)

(7) (8) (9)

(10) (11)

(12)

(13)

(14)

(15) (16)

11

FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER

5 FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER


When a fault occurs, the inverter trips to output a fault signal. However, a fault output signal may not be output at an inverter fault occurrence when the detection circuit or output circuit fails, etc. Although we assure best quality products, provide an interlock which uses inverter status output signals to prevent accidents such as damage to machine when the inverter fails for some reason and at the same time consider the system configuration where failsafe from outside the inverter, without using the inverter, is enabled even if the inverter fails. (1) Interlock method which uses the inverter status output signals By combining the inverter status output signals to provide an interlock as shown below, an inverter alarm can be detected.
No
1)

Interlock Method
Inverter protective function operation Inverter running status

Check Method
Operation check of an alarm contact Circuit error detection by negative logic Operation ready signal check Logic check of the start signal and running signal Logic check of the start signal and output current

Used Signals
Fault output signal (ALM signal) Operation ready signal (RY signal) Start signal (STF signal, STR signal) Running signal (RUN signal) Start signal (STF signal, STR signal) Output current detection signal (Y12 signal)

Refer to Page
Refer to the chapter 4 of the Instruction Manual. Refer to the chapter 4 of the Instruction Manual. Refer to the chapter 4 of the Instruction Manual. Refer to the chapter 4 of the Instruction Manual.

2)

3)

Inverter running status

4)

Inverter running status

(2) Backup method outside the inverter Even if the interlock is provided by the inverter status signal, enough failsafe is not ensured depending on the failure status of the inverter itself. For example, when the inverter CPU fails, even if the interlock is provided using the inverter fault signal, start signal and RUN signal, there is a case where a fault signal is not output and RUN signal is kept output even if an inverter fault occurs. Provide a speed detector to detect the motor speed and current detector to detect the motor current and consider the backup system such as checking up as below according to the level of importance of the system.
1) Start signal and actual operation check Check the motor running and motor current while the start signal is input to the inverter by comparing the start signal to the inverter and detected speed of the speed detector or detected current of the current detector. Note that the motor current runs as the motor is running for the period until the motor stops since the inverter starts decelerating even if the start signal turns off. For the logic check, configure a sequence considering the inverter deceleration time. In addition, it is recommended to check the three-phase current when using the current detector. 2) Command speed and actual operation check Check if there is no gap between the actual speed and commanded speed by comparing the inverter speed command and detected speed of the speed detector.
Controller System failure

Inverter

Sensor (speed, temperature, air volume, etc.) To the alarm detection sensor

12

PARAMETER LIST

6 PARAMETER LIST
6.1 Parameter list
In the initial setting, only the simple mode parameters are displayed. Set Pr. 160 User group read selection as required.
Parameter Name Initial Value Setting Range
9999 160 User group read selection 0 0 1

Remarks
Only the simple mode parameters can be displayed. Simple mode and extended mode parameters can be displayed. Only the parameters registered in the user group can be displayed.

REMARKS
The parameters marked  are the simple mode parameters. The parameters marked with is set in Pr. 77 Parameter write selection. in the table allow its setting to be changed during operation even if "0" (initial value)

Parameters

Name
Torque boost Maximum frequency Minimum frequency Base frequency Multi-speed setting (high speed) Multi-speed setting (middle speed) Multi-speed setting (low speed) Acceleration time Deceleration time Electronic thermal O/L relay DC injection brake operation frequency DC injection brake operation time DC injection brake operation voltage Starting frequency Load pattern selection Jog frequency Jog acceleration/ deceleration time

Setting Range
0 to 30% 0 to 120Hz 0 to 120Hz 0 to 400Hz 0 to 400Hz 0 to 400Hz 0 to 400Hz 0 to 3600/360s 0 to 3600/360s 0 to 500/ 0 to 3600A *1 0 to 120Hz, 9999 0 to 10s, 8888 0 to 30% 0 to 60Hz 0, 1 0 to 400Hz 0 to 3600/360s

Initial Value
6/4/3/2/ 1.5/1% *2 120/60Hz
*1

Parameters

Name
MRS input selection

Setting Range
0, 2

Initial Value
0 120/60Hz
*1

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

17 18 19 20 21 22 23

High speed 120 to 400Hz maximum frequency Base frequency voltage Acceleration/ deceleration reference frequency Acceleration/ deceleration time increments Stall prevention operation level Stall prevention operation level compensation factor at double speed Multi-speed setting Multi-speed input compensation selection Acceleration/ deceleration pattern selection Regenerative function selection Frequency jump 1A Frequency jump 1B 0 to 1000V, 8888, 9999 1 to 400Hz

0Hz 60Hz 60Hz 30Hz 10Hz 5s/15s *3 10s/30s *3 Rated inverter current 3Hz

9999 60Hz

0, 1 0 to 120%, 9999

0 110%

0 to 150%, 9999 0 to 400Hz, 9999 0, 1

9999

24 to 27 4 speed to 7 speed 28

9999 0

0.5s 4/2/1% *4 0.5Hz 1 5Hz 0.5s

29 30 31 32

0, 1, 2, 3 0, 2/0, 1, 2 *1 0 to 400Hz, 9999 0 to 400Hz, 9999

0 0 9999 9999

*1 *2 *3 *4

The setting depends on capacities. (FR-F720-02330 (FR-F740-01160) or less/FR-F720-03160 (FR-F740-01800) or more) The setting depends on capacities. (FR-F720-00046/00077 to 00167/00250, 00340/00490 to 01540/01870, FR-F740-00023/00038 to 00083/00126, 00170/00250 to 00770/00930, 01160/01800 or more) The setting depends on capacities. (FR-F720-00340 ( FR-F740-00170) or less/FR-F720-00490 (FR-F740-00250) or more) The setting depends on capacities. (FR-F720-00340 (FR-F740-00170) or less/FR-F720-00490 to 02330 (FR-F740-00250 to 01160)/FR-F720-03160 (FR-F740-01800) or more)

13

PARAMETER LIST
Parameters

Name
Frequency jump 2A Frequency jump 2B Frequency jump 3A Frequency jump 3B Speed display Up-to-frequency sensitivity Output frequency detection Output frequency detection for reverse rotation Second acceleration/ deceleration time Second deceleration time Second torque boost Second V/F (base frequency) Second stall prevention operation current Second stall prevention operation frequency Second output frequency detection Second electronic thermal O/L relay DU/PU main display data selection CA terminal function selection Frequency monitoring reference Current monitoring reference

Setting Range
0 to 400Hz, 9999 0 to 400Hz, 9999 0 to 400Hz, 9999 0 to 400Hz, 9999 0, 1 to 9998 0 to 100% 0 to 400Hz 0 to 400Hz, 9999 0 to 3600/360s 0 to 3600/ 360s, 9999 0 to 30%, 9999 0 to 400Hz, 9999 0 to 120% 0 to 400Hz, 9999 0 to 400Hz 0 to 500A, 9999/ 0 to 3600A, 9999 *1 0, 5, 6, 8 to 14, 17, 20, 23 to 25, 50 to 57, 100 *2 1 to 3, 5, 6, 8 to 14, 17, 21, 24, 50, 52, 53
*2

Initial Value
9999 9999 9999 9999 0 10% 6Hz 9999 5s 9999 9999 9999 110%

Parameters

Name
Stall prevention operation reduction starting frequency Number of retries at fault occurrence Retry waiting time Retry count display erase Special regenerative brake duty *3 Applied motor PWM frequency selection Analog input selection Input filter time constant Reset selection/ disconnected PU detection/PU stop selection Fault code output selection Parameter write selection Reverse rotation prevention selection Operation mode selection Motor capacity(Simple magnetic flux vector control)

Setting Range
0 to 400Hz 0, 1 to 10, 101 to 110 0 to 10s 0 0 to 10% 0, 1, 2, 20 0 to 15/ 0 to 6, 25 *1 0 to 7, 10 to 17 0 to 8 0 to 3, 14 to 17, 100 to 103, 114 to 117 *4 0, 1, 2 0, 1, 2 0, 1, 2 0, 1, 2, 3, 4, 6, 7

Initial Value
60Hz 0 1s 0 0% 0 2 1 1

33 34 35 36 37 41 42 43 44 45 46 47 48 49 50 51

66 67 68 69 70 71 72 73 74 75 76 77 78  79 80

14

0 0 0 0

0Hz 30Hz

9999

90 100 101

52

0.4 to 55kW, 9999/ 0 to 3600kW, 9999 *1 0 to 50, 9999/ Motor constant (R1) 0 to 400m, 9999 *1 0 to 400Hz, V/F1 (first frequency) 9999 V/F1 (first frequency 0 to 1000V voltage) V/F2 (second frequency) V/F2 (second frequency voltage) V/F3 (third frequency) V/F3 (third frequency voltage) V/F4 (fourth frequency) V/F4 (fourth frequency voltage) 0 to 400Hz, 9999 0 to 1000V 0 to 400Hz, 9999 0 to 1000V 0 to 400Hz, 9999 0 to 1000V

9999

9999 9999 0V 9999 0V 9999 0V 9999 0V 9999 0V 0

54 55 56

102 103 104 105 106 107

0 to 400Hz 0 to 500A/ 0 to 3600A *1

60Hz Rated inverter current 9999 1s 0 0 0

57 58 59  60 65
*1 *2 *3 *4

0, 0.1 to 5s, 9999/ Restart coasting time 0, 0.1 to 30s, 9999 *1 Restart cushion time Remote function selection Energy saving control selection Retry selection 0 to 60s 0, 1, 2, 3 0, 4, 9 0 to 5

108 109 117

0 to 400Hz, V/F5 (fifth frequency) 9999 V/F5 (fifth frequency 0 to 1000V voltage) PU communication 0 to 31 station

The setting depends on capacities. (FR-F720-02330 (FR-F740-01160) or less/FR-F720-03160 (FR-F740-01800) or more) Setting of "9" can be made for the FR-F720-03160 (FR-F740-01800) or more. Setting can be made for the FR-F720-03160 (FR-F740-01800) or more. Setting of "100 to 103", "114 to 117" can be made for the FR-F720-03160 (FR-F740-01800) or more.

14

PARAMETER LIST
Parameters

Name
PU communication speed PU communication stop bit length. PU communication parity check Number of PU communication retries PU communication check time interval PU communication waiting time setting PU communication CR/LF selection Terminal 2 frequency setting gain frequency Terminal 4 frequency setting gain frequency PID control automatic switchover freqeuncy PID action selection PID proportional band PID integral time PID upper limit PID lower limit PID action set point PID differential time Electronic bypass sequence selection MC switchover interlock time Waiting time at a start Bypass selection at a fault Automatic switchover frequency from inverter to bypass operation Backlash acceleration stopping frequency Backlash acceleration stopping time Backlash deceleration stopping frequency Backlash deceleration stopping time

Setting Range
48, 96, 192, 384 0, 1, 10, 11 0, 1, 2 0 to 10, 9999 0, 0.1 to 999.8s, 9999 0 to 150ms, 9999 0, 1, 2 0 to 400Hz

Initial Value
192 1

Parameters

Name
Speed setting switchover PU display language selection Stall prevention level at 0V input. Stall prevention level at 10V input. Output current detection level Output current detection signal delay time Zero current detection level Zero current detection time Voltage reduction selection during stall prevention operation RT signal reflection time selection Stall prevention operation selection OL signal output timer AM terminal function selection Automatic switchover frequency range from bypass to inverter operation User group read selection Frequency setting/ key lock operation selection Automatic restart after instantaneous power failure selection First cushion time for restart First cushion voltage for restart Stall prevention operation level for restart Output current detection signal retention time Output current detection operation selection

Setting Range
0, 2, 4, 6, 8, 10, 102, 104, 106, 108, 110 0 to 7 0 to 120% 0 to 120% 0 to 120% 0 to 10s 0 to 150% 0 to 1s

Initial Value
4 1 110% 120% 110% 0s 5% 0.5s

118 119 120 121 122 123 124  125  126 127 128 129 130 131 132 133 134 135 136 137 138

144 145

148
1 9999 9999 1 60Hz

149 150 151 152 153 154 155 156 157 158

0 to 400Hz 0 to 400Hz, 9999 10, 11, 20, 21, 50, 51, 60, 61 0.1 to 1000%, 9999 0.1 to 3600s, 9999 0 to 100%, 9999 0 to 100%, 9999 0 to 100%, 9999 0.01 to 10.00s, 9999 0, 1 0 to 100s 0 to 100s 0, 1

60Hz 9999 10 100% 1s 9999 9999 9999 9999 0 1s 0.5s 0

0, 1

0, 10 0 to 31, 100, 101 0 to 25s, 9999 1 to 3, 5, 6, 8 to 14, 17, 21, 24, 50, 52, 53 *1 0 to 10Hz, 9999

0 0 0s 1

159

9999

160 161 162 163 164

0, 1, 9999 0, 1, 10, 11

0 0

0, 1, 10, 11 0 to 20s 0 to 100% 0 to 120%

0 0s 0% 110%

139

0 to 60Hz, 9999

9999

165 166 167

140 141 142 143


*1

0 to 400Hz

1Hz

0 to 10s, 9999

0.1s

0 to 360s

0.5s

0, 1

0 to 400Hz

1Hz

0 to 360s

0.5s

Setting of "9" can be made for the FR-F720-03160 (FR-F740-01800) or more.

15

PARAMETER LIST
Parameters

Name

Setting Range

Initial Value

Parameters

Name

Setting Range
0 to 5, 7, 8, 10 to 19, 25, 26, 45 to 47, 64, 70 to 78, 90, 91, 94 to 96, 98, 99,100 to 105, 107, 108, 110 to 116, 125, 126, 145 to 147, 164, 170, 190, 191, 194 to 196,198, 199, 9999 *1 0 to 400Hz, 9999 0, 1 0, 1

Initial Value

168 169 170 171 172 173 174 178

Parameter for manufacturer setting. Do not set. Cumulative power meter clear Operation hour meter clear User group registered display/ batch clear User group registration User group clear STF terminal function selection 0, 10, 9999 0, 9999 9999, (0 to 16) 0 to 999, 9999 0 to 999, 9999 0 to 8, 10 to 12, 14, 16, 24, 25, 60, 62, 64 to 67, 9999 0 to 8, 10 to 12, 14, 16, 24, 25, 61, 62, 64 to 67, 9999 9999 9999 0 9999 9999 60

195

ABC1 terminal function selection

99

196

ABC2 terminal function selection

9999

232 to 239 240

Multi-speed setting (speeds 8 to 15) Soft-PWM operation selection Analog input display unit switchover Terminal 1 added compensation amount (terminal 2) Terminal 1 added compensation amount (terminal 4) Cooling fan operation selection Rated slip Slip compensation time constant Constant-power range slip compensation selection Stop selection Output phase loss protection selection Override bias Override gain Life alarm status display Inrush current limit circuit life display Control circuit capacitor life display Main circuit capacitor life display

9999 1 0

179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194
*1

STR terminal function selection RL terminal function selection RM terminal function selection RH terminal function selection RT terminal function selection AU terminal function selection JOG terminal function selection CS terminal function selection MRS terminal function selection STOP terminal function selection RES terminal function selection RUN terminal function selection SU terminal function selection IPF terminal function selection OL terminal function selection FU terminal function selection

61

241 242 243 244 245 246

0 0 to 8, 10 to 14, 16, 24, 25, 62, 64 to 67, 9999 1 2 3 0 to 8, 10 to 14, 16, 24, 25, 62 to 67, 9999 4 5 6 0 to 8, 10 to 14, 16, 24, 25, 62, 64 to 67, 9999 24 25 62 0 to 5, 7, 8, 10 to 19, 25, 26, 45 to 47, 64, 70 to 78, 90 to 96, 98, 99, 100 to 105, 107, 108, 110 to 116, 125, 126, 145 to 147, 164, 170, 190 to 196, 198, 199, 9999
*1

0 to 100%

100%

0 to 100% 0, 1 0 to 50%, 9999 0.01 to 10s

75% 1 9999 0.5s

247

0, 9999 0 to 100s, 1000 to 1100s, 8888, 9999 0, 1 0 to 200% 0 to 200% (0 to 15) (0 to 100%) (0 to 100%)

9999

250 251 252 253 255 256

9999 1 50% 150% 0 100% 100%

0 1 2

257
3

258
4

(0 to 100%)

100%

Setting of "7, 107" can be made for the FR-F720-03160 (FR-F740-01800) or more.

16

PARAMETER LIST
Parameters

Name
Main circuit capacitor life measuring PWM frequency automatic switchover Power failure stop selection Subtracted frequency at deceleration start Subtraction starting frequency Power-failure deceleration time 1 Power-failure deceleration time 2

Setting Range
0, 1

Initial Value
0

Parameters

Name
Communication error count Remote output selection

Setting Range

Initial Value
0 0 0 0 0 9999 9999 1 9999 2 1s 0s Rated inverter current 0 0 0 9999 9999 1s 0Hz 1000% 0 0 1s 1s 1s 1s 60Hz 60Hz 60Hz 0Hz

259 260 261 262 263 264 265 266 267 268 269 299 331 332 333 334 335 336 337 338 339 340 341 342
*1

343 495

0, 1, 10, 11

0, 1 0, 1, 2 0 to 20Hz 0 to 120Hz, 9999 0 to 3600/ 360s 0 to 3600/ 360s, 9999

1 0 3Hz 60Hz 5s 9999

496 497 503 504 539 549 550 551

Remote output data 1 0 to 4095 Remote output data 2 0 to 4095 Maintenance timer Maintenance timer alarm output set time Modbus-RTU communication check time interval Protocol selection NET mode operation command source selection PU mode operation command source selection Current average time Data output mask time Current average value monitor signal output reference current Energization time carrying-over times Operating time carrying-over times Multiple rating setting Holding time at a start 4mA input check selection Output interruption detection time Output interruption detection level Output interruption cancel level Auxiliary motor operation selection Motor swichover selection MC switching interlock time Start waiting time Auxiliary motor connection-time deceleration time Auxiliary motor disconnection-time acceleration time Auxiliary motor 1 starting frequency Auxiliary motor 2 starting frequency Auxiliary motor 3 starting frequency Auxiliary motor 1 stopping frequency 0 (1 to 9998) 0 to 9998, 9999 0 to 999.8s, 9999 0, 1 0, 1, 9999 1, 2 0.1 to 1.0s 0.0 to 20.0s 0 to 500A/ 0 to 3600A *1 (0 to 65535) (0 to 65535) 0, 1 0.0 to 10.0s, 9999 1,9999 0 to 3600s, 9999 0 to 400Hz 900 to 1100% 0 to 3 0 to 3 0 to 100s 0 to 100s 0 to 3600s, 9999 0 to 3600s, 9999 0 to 400Hz 0 to 400Hz 0 to 400Hz 0 to 400Hz

Power failure deceleration time 0 to 400Hz switchover frequency Terminal 4 input 0, 1, 2 selection Monitor decimal 0, 1, 9999 digits selection Parameter for manufacturer setting. Do not set. Rotation direction detection selection 0, 1, 9999 at restarting RS-485 0 to 31 communication (0 to 247) station 3, 6, 12, 24, RS-485 communication speed 48, 96, 192, 384 RS-485 communication stop 0, 1, 10, 11 bit length RS-485 communication parity 0, 1, 2 check selection RS-485 communication 0 to 10, 9999 number of retries RS-485 0 to 999.8s, communication 9999 check time interval RS-485 0 to 150ms, communication waiting time setting 9999 Communication operation command 0, 1 source Communication speed command 0, 1, 2 source Communication startup mode 0, 1, 2, 10, 12 selection RS-485 communication 0, 1, 2 CR/LF selection Communication EEPROM write 0, 1 selection

60Hz

555
0 9999

556 557 563 564

9999

0 96 1

570 571 573 575

576 577 578

0s

579
9999

580 581

582 583 584 585 586

587

The setting depends on capacities. (FR-F720-02330 (FR-F740-01160) or less/FR-F720-03160 (FR-F740-01800) or more)

17

PARAMETER LIST
Parameters

Name
Auxiliary motor 2 stopping frequency Auxiliary motor 3 stopping frequency Auxiliary motor start detection time Auxiliary motor stop detection time Acceleration time at a restart AM output filter Current output filter Input phase loss protection selection Regeneration avoidance operation selection Regeneration avoidance operation level Regeneration avoidance at deceleration detection sensitivity Regeneration avoidance compensation frequency limit value Regeneration avoidance voltage gain Free parameter 1 Free parameter 2 Cumulative power monitor digit shifted times Load factor Energy saving monitor reference (motor capacity) Control selection during commercial power-supply operation Power saving rate reference value Power unit cost

Setting Range
0 to 400Hz 0 to 400Hz 0 to 3600s 0 to 3600s 0 to 3600s, 9999 0 to 5s 0 to 5s 0, 1 0, 1, 2

Initial Value
0Hz 0Hz 5s 5s 5/15s *1 0.01s 0.02s 0 0 380VDC/ 760VDC

Parameters

Name
Terminal 2 frequency setting bias frequency Terminal 2 frequency setting bias Terminal 2 frequency setting gain frequency Terminal 2 frequency setting gain Terminal 4 frequency setting bias frequency Terminal 4 frequency setting bias Terminal 4 frequency setting gain frequency Terminal 4 frequency setting gain Current output bias signal Current output bias current Current output gain signal Current output gain current Parameter copy alarm release PU buzzer control

Setting Range
0 to 400Hz

Initial Value
0Hz

588 589 590 591 611 867 869 872 882 883

C2 (902) C3 (902) 125 (903) C4 (903) C5 (904) C6 (904) 126 (905) C7 (905) C8 (930) C9 (930) C10 (931) C11 (931) 989 990

0 to 300%

0%

0 to 400Hz

60Hz

0 to 300%

100%

0 to 400Hz

0Hz

0 to 300%

20%

300 to 800V

0 to 400Hz

60Hz

884

0 to 5

0 to 300% 0 to 100% 0 to 100% 0 to 100% 0 to 100% 10/100 *1 0, 1 0 to 63 0, 1 0, 1 0, 1 0, 1, 2, 3

100% 0% 0% 100% 100% 10/100 *1 1 58 0 0 0 0

885

0 to 10Hz, 9999

6Hz

886 888 889 891 892 893

0 to 200% 0 to 9999 0 to 9999 0 to 4, 9999 30 to 150% 0.1 to 55kW/ 0 to 3600kW *1

100% 9999 9999 9999 100% LD/SLD value of applied motor capacity 0

PU contrast  991 adjustment Pr.CL Parameter clear ALLC All parameter clear Er.CL Faults history clear PCPY Parameter copy

894 895 896 897 898 899 C0 (900) C1 (901)


*1

0, 1, 2, 3

0, 1, 9999 0 to 500, 9999

9999 9999 9999 9999 9999

0, 1 to 1000h, Power saving monitor average time 9999 Power saving cumulative monitor 0, 1, 10, 9999 clear 0 to 100%, Operation time rate (estimated value) 9999 CA terminal calibration AM terminal calibration

The setting depends on capacities. (FR-F720-02330 (FR-F740-01160) or less/FR-F720-03160 (FR-F740-01800) or more)

18

TROUBLESHOOTING

7 TROUBLESHOOTING
When a fault occurs in the inverter, the inverter trips and the PU display automatically changes to any of the following fault or alarm indications. If the fault does not correspond to any of the following faults or if you have any other problem, please contact your sales representative. z Retention of fault output signal........... When the magnetic contactor (MC) provided on the input side of the inverter is opened when a fault occurs, the inverter's control power will be lost and the fault output will not be held. z Fault or alarm indication ..................... When a fault or alarm occurs, the operation panel display automatically switches to the fault or alarm indication. z Resetting method ............................... When a fault occurs, the inverter output is kept stopped. Unless reset, therefore, the inverter cannot restart. (Refer to page 19.) z When any fault occurs, take the appropriate corrective action, then reset the inverter, and resume operation. Not doing so may lead to the inverter fault and damage. Inverter fault or alarm indications are roughly divided as below. (1) Error message A message regarding operational fault and setting fault by the operation panel (FR-DU07) and parameter unit (FR-PU07/FR-PU04) is displayed. The inverter does not trip. (2) Warnings The inverter does not trip even when a warning is displayed. However, failure to take appropriate measures will lead to a fault. (3) Alarm The inverter does not trip. You can also output an alarm signal by making parameter setting. (4) Fault When a fault occurs, the inverter trips and a fault signal is output.

7.1 Reset method of protective function


(1) Resetting the inverter The inverter can be reset by performing any of the following operations. Note that the internal thermal integrated value of the electronic thermal relay function and the number of retries are cleared (erased) by resetting the inverter. Recover about 1s after reset is cancelled. Operation 1: ..... Using the operation panel, press to reset the inverter.

(This may only be performed when a fault occurs (Refer to the Instruction Manual for fault.))

Operation 2:...... Switch power off once, then switch it on again.


ON

OFF

Operation 3: ..... Turn on the reset signal (RES) for more than 0.1s. (If the RES signal is kept on, "Err." appears (flickers) to indicate that the inverter is in a reset status.)

Inverter RES SD

19

TROUBLESHOOTING

7.2 List of fault or alarm display


Operation Panel Indication
E--Error message HOLD Faults history Operation panel lock

Name

Operation Panel Indication


E.ILF* E.OLT E.GF E.LF

Name
Input phase loss Stall prevention Output side ground fault overcurrent Output phase loss External thermal relay operation*2 PTC thermistor operation Option fault Communication option fault (e.g.communication error) Option fault (e.g.connection or contact fault) Parameter storage device fault PU disconnection Retry count excess Parameter storage device fault

to

Er1 to 4 Parameter write error rE1 to 4 Copy operation error Err. OL oL Error Stall prevention (overcurrent) Stall prevention (overvoltage) Regenerative brake prealarm Electronic thermal relay function prealarm PU stop Fault Maintenance signal output Parameter copy Fan fault Overcurrent trip during acceleration Overcurrent trip during constant speed Overcurrent trip during deceleration or stop Regenerative overvoltage trip during acceleration Regenerative overvoltage trip during constant speed Regenerative overvoltage trip during deceleration or stop Inverter overload trip
(electronic thermal relay function)

to

E.OHT E.PTC* E.OPT E.OP1 E. 1 E.PE E.PUE E.RET E.PE2*

Warnings

RB TH PS MT CP

Alarm

FN E.OC1 E.OC2 E.OC3 E.OV1 E.OV2

/ /

E. 6 / E. 7 / E.CPU

CPU fault

E.CTE E.P24 E.CDO* E.IOH* E.SER* E.AIE* E.BE E.13

Operation panel power supply short circuit, RS-485 terminal power supply short circuit 24VDC power output short circuit Output current detection value exceeded Inrush current limit circuit fault Communication fault (inverter) Analog input fault Brake transistor alarm detection/ internal circuit error Internal circuit fault

Fault

E.OV3 E.THT E.THM E.FIN E.IPF E.UVT

Motor overload trip


(electronic thermal relay function)

Fin overheat Instantaneous power failure Undervoltage

* If an error occurs when using the FR-PU04, "Fault 14" is displayed on the FR-PU04.

20

Appendix 1 Instructions for Compliance with the European Directives


(1) EMC Directive
We have self-confirmed our inverters as products compliant to the EMC Directive (second environment of conforming standard EN618003) and place the CE mark on the inverters. Note: First environment Environment including residential buildings. Includes buildings directly connected without a transformer to the low voltage power supply network which supplies power to residential buildings. Second environment Environment including all buildings except buildings directly connected without a transformer to the low voltage power supply network which supplies power to residential buildings. Set the EMC filter valid and install the inverter and perform wiring according to the following instructions. * The inverter is equipped with a built-in EMC filter. Set the EMC filter valid. (The EMC filter is invalid when shipped from the factory. (The FR-F720-00046 and 00077 are always valid.)) * Connect the inverter to an earthed power supply. * Install a motor and a control cable written in the EMC Installation Manual (BCN-A21041-204) according to the instruction. * The cable length between the inverter and the motor is 5 m (16.4 feet) maximum. * Confirm that the inverter complies with the EMC Directive as the industrial drives application for final installation.

1) Notes

(2) Low Voltage Directive


1)Outline of instructions

We have self-confirmed our inverters as products compliant to the Low Voltage Directive (Conforming standard EN 50178) and place the CE mark on the inverters.

* Do not use an earth leakage current breaker as an electric shock protector without connecting the equipment to the earth. Connect the equipment to the earth securely. * Wire the earth terminal independently. (Do not connect two or more cables to one terminal.) * Use the cable sizes on page 8 under the following conditions. Ambient temperature: 40C (104F) maximum If conditions are different from above, select appropriate wire according to EN60204 Appendix C TABLE 5. * Use a tinned (plating should not include zinc) crimping terminal to connect the ground cable. When tightening the screw, be careful not to damage the threads. For use as a product compliant with the Low Voltage Directive, use PVC cable whose size is indicated on page 8. * Use the moulded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard. * When using an earth leakage current breaker, use a residual current operated protective device (RCD) of type B (breaker which can detect both AC and DC). If not, provide double or reinforced insulation between the inverter and other equipment, or put a transformer between the main power supply and inverter. * Use the inverter under the conditions of overvoltage category II (usable regardless of the ground condition of the power supply), overvoltage category III (usable with the earthed-neutral system power supply, 400V class only) and pollution degree 2 or lower specified in IEC664. To use the inverter of 00770 or more (IP00) under the conditions of pollution degree 2, install it in the enclosure of IP 2X or higher. To use the inverter under the conditions of pollution degree 3, install it in the enclosure of IP54 or higher. To use the inverter of 00620 or less (IP20) outside of an enclosure in the environment of pollution degree 2, fix a fan cover with fan cover fixing screws enclosed.
Fan cover fixing screw

Fan cover fixing screw Fan cover

Fan cover fixing screws Fan cover Fan

Fan cover

Fan

Fan

FR-F720-00105 to 00250 FR-F740-00083, 00126

FR-F720-00340 to 00630 FR-F740-00170 to 00380

FR-F720-00770 to 01250 FR-F740-00470, 00620

* On the input and output of the inverter, use cables of the type and size set forth in EN60204 Appendix C. * The operating capacity of the relay outputs (terminal symbols A1, B1, C1, A2, B2, C2) should be 30VDC, 0.3A. (Relay outputs are basically isolated from the inverter internal circuit.) * Control circuit terminals on page 4 are safely isolated from the main circuit. * Environment

During Operation
Surrounding air temperature Ambient humidity Maximum altitude
LD: -10C to +50C (14F to 122F) SLD (initial setting): -10C to +40C (14F to 104F) 90% RH or less 1000m (3280.80feet)

In Storage
-20C to +65C (-4F to +149F) 90% RH or less 1000m (3280.80feet)

During Transportation
-20C to +65C (-4F to +149F) 90% RH or less 10000m (32808feet)

Details are given in the technical information "Low Voltage Directive Conformance Guide" (BCN-A21041-203). Please contact your sales representative.

21

Appendix 2 Instructions for UL and cUL Compliance


(Conforming standard UL 508C, CSA C22.2 No.14)

(1) Installation
This inverter is a UL / cUL Listed open type device for use inside an enclosure, or enclosed Type 1 device with a suitably rated enclosure. For open type, design an enclosure so that the inverter ambient temperature, humidity and atmosphere satisfy the specifications. (Refer to page 1.) The following UL / cUL Listed FR-F700 Series Inverters employ a UL Type 1 Enclosure - Suitable for Installation in a Compartment Handling Conditioned Air (Plenum): Models FR-F720-00046, -00077, -00105, -00167, -00250, -00340, -00490, 00630, -00770, -00930, followed by -NA suffix. Models FR-F740-00023, -00038, -00052, -00083, -00126, -00170, -00250, -00310, -00380, -00470, -00620, followed by -NA suffix.

Wiring protection
For installation in the United States, branch circuit protection must be provided in accordance with the National Electrical Code and any applicable provincial codes. For installation in Canada, branch circuit protection must be provided in accordance with the Canadian Electrical Code and any applicable provincial codes. Provide the appropriate UL and cUL listed Class RK5, Class T or Class L type fuse or UL489 molded case circuit breaker (MCCB) that is suitable for branch circuit protection in accordance with the table below. Note, the Class L fuses can be used if the applicable current rating is larger than 600A.
FR-F720--NA
Rated fuse voltage(V) Without power Fuse factor improving Maximum reactor allowable With power factor rating (A)* improving reactor Molded case circuit breaker (MCCB) Maximum allowable rating (A)*

00046 00077 00105 00167 00250 00340 00490 00630 00770 00930 01250 01540 01870 02330
240V or more 15 15 15 20 20 15 30 20 25 40 30 40 60 50 60 80 70 80 150 125 110 175 150 150 200 200 175 225 200 225 300 250 300 350 300 350 400 350 450 500 400 500

FR-F720--NA
Rated fuse voltage(V) Without power Fuse factor improving Maximum reactor allowable With power factor rting (A)* improving reactor Molded case circuit breaker (MCCB) Maximum allowable rating (A)*

03160 03800 04750


240V or more 500 700 600 900 700 1000

FR-F740--NA
Rated fuse voltage(V) Without power Fuse factor improving Maximum reactor allowable With power factor rating (A)* improving reactor Molded case circuit breaker (MCCB) Maximum allowable rating (A)*

00023 00038 00052 00083 00126 00170 00250 00310 00380 00470 00620 00770 00930 01160
480V or more 6 6 15 10 10 15 15 10 15 20 15 20 30 25 30 40 35 40 70 60 60 80 70 70 90 90 90 110 100 100 150 125 150 175 150 175 200 175 225 250 200 250

FR-F740--NA
Rated fuse voltage(V) Without power Fuse factor improving Maximum reactor allowable With power factor rating (A)* improving reactor Molded case circuit breaker (MCCB) Maximum allowable rating (A)*

01800 02160 02600 03250 03610 04320 04810 05470 06100 06830 07700 08660 09620 10940 12120
500V or more 300 450 350 500 400 600 500 800 600 900 700 800 900

1000 1100 1200 1350 1500 1800 2000

1000 1200 1200 1200 1600 1600 2000 2000 2500 3000

* Maximum allowable rating by US National Electrical Code at SLD rating. Exact size must be chosen for each installation.

22

(2) Wiring of the power supply and motor


For wiring the input (R/L1, S/L2, T/L3) and output (U, V, W) terminals of the inverter, use the UL Listed copper, stranded wires (rated at 75C(167F)) and round ring crimping terminals. Crimp the crimping terminals with the crimping tool recommended by the terminal maker.

(3) Short circuit ratings


200V class Suitable For Use in A Circuit Capable Of Delivering Not More Than 100kA rms Symmetrical Amperes, 264V Maximum. 400V class Model 01160 or less Suitable For Use in A Circuit Capable Of Delivering Not More Than 100kA rms Symmetrical Amperes, 528V Maximum. Model 01800 or more Suitable For Use in A Circuit Capable Of Delivering Not More Than 100kA rms Symmetrical Amperes, 550V Maximum.

(4) Motor overload protection


This inverter is certified as a motor overload protection device by UL. When using the electronic thermal relay function as motor overload protection, set the rated motor current to Pr. 9 Electronic thermal O/L relay. Electronic thermal relay function operation characteristic This function detects the overload (overheat) of the motor, stops the operation of the inverter's output Pr. 9 = 50% setting of Pr. 9 = 100% setting inverter rating*1.2 of inverter rating*1.2 transistor, and stops the output. (The operation characteristic is shown on the left) 70 30Hz or more* 30Hz When using the Mitsubishi constant-torque motor 20Hz or more* Operation range Range on the right of 10Hz 20Hz 1) Set "1" in Pr. 71. (This provides a 100% continuous torque 60 characteristic curve 10Hz 6Hz Non-operation range characteristic in the low-speed range.) 6Hz Range on the left of 0.5Hz characteristic curve 50 0.5Hz 2) Set the rated current of the motor in Pr. 9.
Operation time (min) (min) unit display in this range
3 3

(s) unit display in this range

240

Operation time (s)

180

Characteristic when electronic thermal relay function for motor protection is turned off (When Pr. 9 setting is 0(A))

120 Electronic thermal relay function for transistor protection 52.5% 105% 100 120 50 150 Inverter output current (%) (% to the rated output current)

*1 *2 *3

60

When a value 50% of the inverter rated output current (current value) is set in Pr. 9 The % value denotes the percentage to the inverter rated output current. It is not the percentage to the motor rated current. When you set the electronic thermal relay function dedicated to the Mitsubishi constant-torque motor, this characteristic curve applies to operation at 6Hz or higher.

CAUTION
Protective function by electronic thermal relay function is reset by inverter power reset and reset signal input. Avoid unnecessary reset and power-off. When multiple motors are operated by a single inverter, protection cannot be provided by the electronic thermal relay function. Install an external thermal relay to each motor. When the difference between the inverter and motor capacities is large and the setting is small, the protective characteristics of the electronic thermal relay function will be deteriorated. In this case, use an external thermal relay. A special motor cannot be protected by the electronic thermal relay function. Use the external thermal relay. Electronic thermal relay does not function when 5% or less of inverter rated current is set to electronic thermal relay setting.

23

MEMO

24

MEMO

25

REVISIONS *The manual number is given on the bottom left of the back cover.

Print Date
Sep., 2004 Dec., 2004

*Manual

Number
First edition Additions
FR-F720 - 03160 to 04750 - NA FR-F740 - 04320 to 12120 - NA

Revision

IB(NA)-0600218ENG-A IB(NA)-0600218ENG-B

May, 2006

IB(NA)-0600218ENG-C

Additions
Electronic thermal relay function operation characteristic. Pr. 539 Modbus-RTU communication check time interval Voltage/current input switch

Aug., 2008

IB(NA)-0600218ENG-D

Additions
Breaker selection when using the inverter as UL or cUL listed product Setting values "10, 11" of Pr.495 Remote output selection

For Maximum Safety Mitsubishi inverters are not designed or manufactured to be used in equipment or systems in situations that can affect or endanger human life. When considering this product for operation in special applications such as machinery or systems used in passenger transportation, medical, aerospace, atomic power, electric power, or submarine repeating applications, please contact your nearest Mitsubishi sales representative. Although this product was manufactured under conditions of strict quality control, you are strongly advised to install safety devices to prevent serious accidents when it is used in facilities where breakdowns of the product are likely to cause a serious accident. Please do not use this product for loads other than three-phase induction motors.

26