Professional Documents
Culture Documents
Supply
900
800
POWER IN WATT
700
600
500
400
300
200
100
0
2-3(am)
3-4(am)
4-5(am)
5-6(am)
6-7(am)
7-8(am)
8-9(am)
1-2(pm)
2-3(pm)
3-4(pm)
5-6(pm)
7-8(pm)
8-9(pm)
9-10(am)
4-5(pm)
6-7(pm)
11-12(am)
12-1(pm)
9-10(pm)
10-11(pm)
10-11(am)
TIME
Fig ( 3) : Daily Load Profile of Energy Consumption (Peak Load 1000W, Optimized Peak Load 600W)
The sum of loads as computed during the period of
Daily average Energy consumption on monthly basis no solar insolation from 06:00 pm to 11:00 pm has
been used to determine the size of Battery in the
M above calculation. The deficit of PV power for load
=( ∑ E j ) X 1/30(WH) = 2750 WH matching or during low insolation period has been
1
supplemented by utility supply
(where M = Total Number Of Days in a month i.e 30
j = 1, 2, 3…..M A Battery of 12V/200AH is considered for the above
Power supply system
The daily average consumption of energy on monthly basis
= 2750 W-H (C ) Cost analysis of PV Power Supply System
The Energy Balance Technique is used for optimal The cost of Power Supply will include the cost of PV
design of PV sizing of cells array , Battery and Power converter unit.
The load consumption of 970 W is powered by The proposed load controller match the PV power
battery source under no insolation for the back up source with load profile and regulate loads under
period where load has been considered constant various mode of operations which include peak
during each one hour interval . clipping, valley filling or load shedding etc.
In its peak clipping mode of control, the appliances • When a person enter in a village Farm House
whose disconnection do not create inconvenience, are or a Community center and lights of rooms
switched OFF. In valley filling mode of control, are needed to be switched ON and OFF
demand of load during peak hour is shifted to off peak sequentially one after another along with the
hour in order to adjust the demand of loads movement of a person(s) .
During power shortage, load shedding is activated and • .The number of lights to be switched ON in a
low priority loads are switched OFF in order to match
poultry Farm is regulated in proportion to the
with the available PV power. The Dummy Load i.e
increase in their population .
pump is categorized at the lowest priority Load and is
activated automatically when higher priority loads are
not switched ON by end users
• The duration of pump operation for irrigation
is similarly regulated on the amount of
In the system working in grid assisted mode of
moisture content in the soil and so on
operation , the deficit of the power supply in load (
PL ) due to less generation of PV Power ( PPV)source
on varying insolation is supplemented by utility supply
during insolation period and by energy storage device 9. Experimental Investigations
i.e the 12V Battery power (PBAT) during no insolation
back up period under charged condition of battery A simulation work was performed using
voltage exiting in between 10.5V to 14.5V , Further Programmable Logic Controller (PLC) in the
fall in battery voltage due to discharge below 10.5 Laboratory to verify the logical operation of Load
volt the load is connected to Grid (utility supply) Management Intelligent Controller.
power (PGrid ) till the period when battery become
fully charged by PV source and attain a value of 14.5 A computer program was developed in ladder diagram
volt for SIMATIC S5-95U PLC of Seimens make [ 5 ]. Loads
were switched ON and OFF sequentially depending on
i.e Demand of loads, Priority of loads and Availability of
.PLOAD + PBAT = PPV (Solar Insolation) PV Power level. The program was run successfully and
or PGRID (Low Battery/No nsolation) performance of the Load Management of PV Power
supply system was found satisfactory
PV System 3
1 2
PV ∑ Agro Based
LOADs
10. Acknowledgment
Literature
1. www.jharkhad.nic.in