FT 37 AUTOMATIC ALARM SYS

AUTOMATIC FIRE DETECTORS


(Detector Circuits)
OBJECTIVE 1. To explain the fundamentals of detection, types of detectors, types of detectors their circuits function and operation. REFERENCE 2. a. b. Manual of Fireman ship Book 9. Fire College Notes.

CONTENTS 3. The function of the detector circuit in an automatic detection system is to transmit the signal given by the activated detector head (or manual call point) to centrally situated control and indicating equipments from which the alarm is raised. In practice those processes occur simultaneously. Basically there are two types of detector circuit: a. b. Open circuit. Closed circuit.

4. Open Circuit the theory. In an open circuit system detectors or call points are wired in parallel and can be regarded as switches in the off position i.e. there is no current flow in the circuit when on standby. The operation of a detector effectively closes the contacts and activates the alarm system.

Diagram of an Open Circuit System 5. As there is no current flow in the circuit when on standby it is not self monitoring as a result however it does not consume as mush electricity as a closed circuit and is therefore relatively cheaper to run. A short circuit in the detector wiring will rise on alarm, as it effectively closes. A broken circuit, on the other hand will not end if unidentified could render some detector heads inoperative.

223

6. It is important to remember that in all except the simplest, system the detector and alarm circuits are separate meeting only in the alarm control unit. 7. Closed Circuit The Theory. In a closed circuit the detectors (or call point) can be regarded as a series or switches whose contacts are normally closed when the system is on standby thus allowing current to flow in the detector circuit. This current energizes the relay which holds contact (1) against contact (3) and keeps the alarm circuit inoperative. Once a detector (or call point) operates the detector circuit is broken interrupting current flow to the relay.

Diagram of Closed Circuit System 8. The relay therefore de-energized releasing contact (1) which spring back to contact, (2), completing the alarm circuit and sounding the bells. 9. The main advantage of this type of circuit is that the continuous current flow on standby makes it self monitoring. Any break in the circuit will cause the alarm to ring which, at though it may be false, does at least draw attention to the fault. The fact that the circuit is drawing current from the supply on standby however can be regarded as a disadvantage the size and const of the battery and charger will be increased. In a basic closed circuit system a short circuit could remain unnoticed as it simply completes a separate path for current flow. In doing this it could by-pass some detectors and call points rendering them inoperative. 10. Detector and Alarm Circuits The Practice. It is essential that detector and alarm circuit are above all reliable. The diagrams in are basic illustration of open and closed principles, is more sophisticated than this. Ring circuits and other refinements can be used to achieve, as far as possible, a fail-safe situation and to overcome the disadvantage mentioned earlier. Resistors and/or additional relays are incorporated to reduce false alarms by providing for separate signaling of fault conditions (e.g. a broken circuit or a short circuit). 11. Closed circuits have the advantage mentioned earlier that they are continuously under test i.e. current flows in the circuit on standby. If desired, however, the continuity of an open circuit can be tested by incorporating an end -of-line resistor in the circuit.

224

An Open Circuit System with End-Of-Line Resistor 12. This allows a continuous but reduced current to flow through the detector circuit. The continuity of the flow will be mentioned at the control unit. The resistor incorporated in the circuit reduces the current sufficiently to prevent it activating the/alarms. 13. The more components there are introduced into a circuit or course; the more there is to fail. With this in mind the British Standard Code of Practice 1019 states. In the interests of reliability it is desirable that the number of circuit elements in the system should be kept to a minimum ..Every additional component will inevitably Add some risk. Never the less with care taken to mini bike these a fully discriminating system can be well justified. In deed the Fire Officers Committee rules require some element of discrimination (e.g. fault signaling or end-of-line testing) in approved systems. Some detectors and manual call points can be used either open or closed circuit systems. 14. Wiring and Power Supplies: a. Wiring. It is essential for reliability that the wiring in automatic fire alarm systems should be of high standard and be suitably protected against the possibility of accidental damage. The degree of protection needed in an open circuit will generally be greater than that needed in a closed circuit in which any break in the wiring will automatically sound an alarm. b. The thermostatic cable described can be used for wiring detector circuits it is mainly used with heat detectors. c. Power Supplies. Obviously an adequate and reliable power supply must be available to automatic detection systems. d. This can be a mains supply or a battery supply. In either case it is advisable (Fire Officers Committee rules require) that a standby supply must be au tomatically available in the event of a failure in the primary supply. The standby will normally be a battery maintained in a fully charge state. This supply can be automatically brought into operation by incorporating a changeover relay in the circuit. e. The preferred operating voltage is 24 V d.c. A transformer will therefore be necessary to reduce the voltage to installations using a mains supply.

225