You are on page 1of 2

Made Date ZA 11-Jul-13 Check Date ZA 12-Jul-13 PROJECT TITLE: ABC LOCATION: XYZ DESIGN OF ISOLATED FOOTING Geometrical

Properties Material Properties Weight of soil "soil" Depth of Soil overburden 1 met Weight of plain concrete "pc" Thickness of plain concrete 100 mm Weight of reinforced concrete "rc" Thickness of Slab on garde 200 mm Depth of Column "D" Width of Column "B" Required Area of footing Required Length of footing Required Width of footing Provided Length of footing "L" Provided Width of footing "W" Provided area of footing "Af" Provided Depth of Footing "H" Length of plain concrete Width of plain concrete Reinforcement Type of Reinforcement Bottom Reinforcement Long dir. Bottom Reinforcement Short dir. 700 300 5.4112 2.54 2.14 2.6 2.1 5.46 600 2.74 2.54 mm mm m2 m m m m m2 mm m m Safe bearing pressure "q" Eff. Net bearing pressure "qnet" Strength of concrete "fc" Strength of steel "fy"

Sheet 1 Rev. 0

18 24 24 350 318.6 30 420

kN/m3 kN/m3 kN/m3 kN/m2 kN/m2 N/mm2 N/mm2 mm mm

Clear cover to concrete 75 Dia of rebar 16 Flexure strength reduction factor 0.9 Shear strength reduction factor 0.75 s, constant depend on column location 40 Loading Floor Finish on SOG Live load on SOG Service Dead Load "Pdl" Service Live Load "Pll" Live load reduction factor Total Serivce Load "Ptot" Total Ultimate Load "Pu,tot" 2 3 1422 302 1 1724 2189.6

Inetrior kN/m2 kN/m2 kN kN kN kN

No. 12 16

Area 2412.7 3217

Calculations
1. Calculate revised size of foundation Self wt. of SOG 4.8 Soil overburden 18 Adjust for Concrete Total surcharge Ult. press under RC base "pu" 3.6 31.4 402.83 kN/m2 kN/m2 kN/m2 kN/m2 kN/m2

DESIGN SUMMARY
REQUIRED DIMENSIONS PROVIDED DIMENSIONS L, Met 2.54 2.6 W,Met 2.14 2.1 H,mm 600 600

` 2. Check one way shear (cl. 11.3 ACI 318) Allowable shear stress vc=0.75*0.17*sqrt(fc') Effective dept "d1" short dir Effective dept "d2" long dir Shear is checked at "d" from column face Shear short dir /m Shear stress short dir. Shear long dir /m Shear stress long dir. 0.699 517.00 501.00 162.34 0.31 168.78 0.34 N/mm2 mm mm kN/m N/mm2 O.K < kN/m N/mm2 O.K <

0.699 0.699

N/mm2 N/mm2

Made ZA Check ZA PROJECT TITLE: ABC LOCATION: XYZ DESIGN OF ISOLATED FOOTING 3. Check two way shear (cl. 11.12 ACI 318) Average effective depth "dav" Shear perimeter "bo" Allowable shear stress is least of: a) vc = *1+(2/c)f'c b) vc = c) vc = 6 *0.083*(s*dav/bo + 2)f'c * 0.33*f'c 509.00 4036.00 1.30 2.40 1.36 mm mm N/mm2 N/mm2 N/mm2

Date 11-Jul-13 Date 12-Jul-13

Sheet 2 Rev. 0

Therefore allowable shear stress vc = Effective shear force at perimeter Actual shear stress 4. Reinforcement Calculation Short direction: Mu short = pu*L*((W-B)/2)2/2 0.85f'c*L Ast = fy d -

1.30 N/mm2 1795.6 kN 0.87 N/mm2 O.K

<

1.30

N/mm2

424.18 d2 2Mu 0.85**f'c*L

kN-m

Ast = 2235.74 mm2 Ast,min = 0.0018*L*H Hence Provide Ast = 2808.00

2808 mm2

mm2

Provide16mm dia 14 No. of Bars For rectangular footings and inorder to keep uniform spacing of reinforcement increase area of steel by 2/(1+) Therefore = L / W 1.24 Therefore revised reinforcement 16 No of bars dia 16 mm Long direction: Mu long = pu*W*((L-D)/2)2/2 358 kN-m Ast = 0.85f'c*W fy Ast = 1888.15 mm2 2268 2268.00 mm2 mm2 d d2 2Mu 0.85**f'c*W

ACI 318 Cl. 15.4.4.2

Ast,min = 0.0018*W*H Hence Provide Ast = Provide16mm dia 12

No. of Bars

You might also like