TECHNICAL

BULLETIN

SMARTPACK
DIRECT EXPANSION HIGH EFFICIENCY PACKAGED
AIR CONDITIONER ROOF TOP
CKN-XHE SERIES
AIR-AIR HEAT PUMP
Air flow rate from 2200 to 9600 m 3/h

SMARTPACK is the high efficiency packaged roof top "air conditioning unit designed to provide makeup air and the energy recovery in the served zone.
Easy to position thanks to its compact dimensions, SMARTPACK simplifies system installation and
increases its reliability. It contains In fact all the functions that, in traditional systems, are entrusted to
separate products and components that must be first carefully selected and then assembled on site.
The automatic on-board control makes it possible to be used by non-specialised personnel,
guaranteeing considerable savings in operating costs thanks, also to its high efficiency.
SMARTPACK is therefore the ideal decentralised solution for the air-conditioning of shops, showrooms,
outlet villages, bar and restaurants, service stations, small and medium service rooms and productive
areas.

BT09N004GB-00

SMARTPACK CKN-XHE

FOR MANY BUSINESSES,


SUCCESS DEPENDS ON THE RIGHT COMFORT OF THE USERS
A correct air-conditioning is an essential component in the management of various sales areas.
Optimum temperature and humidity, air purification and correct ventilation are primary factors that guarantee to users and
operators to remain in these spaces independently of outdoor conditions.
This is what happens in single shops as well as in outlet villages, automobile showrooms and in modern service stations.
Make-up air becomes even more a determining factor in restaurants, to control odours and vapours.
Ventilation and air conditioning are also fundamental in service rooms for the proper operation of the equipment they contain.

ROOFTOP UNITS ARE OFTEN THE BEST SOLUTION


FOR AIR CONDITIONING THE ENVIRONMENTS
LOCATED IN A SINGLE AREA
Despite their apparently low costs, split and multisplit direct expansion systems
have a lot of limits in these applications. For example, they require a separate
system for the treatment of the primary air. The pipes that contain the refrigerant
cross the served rooms and therefore they are subject to restrictions and use
limitations. From a technical point of view they cannot operate in freecooling
mode, which is very efficient and convenient thanks to the generated energy
savings.
On the other hand, the hydronic systems are certainly more complete and
versatile. They make it possible to adopt various types of terminals in the served
environment, from fan coil units exposed or integrated in the furnishings, up to
radiant or induction systems. The cost for medium and small installations is often
higher as they are more complex and require more labour for installation, startup and adjustment.
In this context, many rooftop solutions available on the market help to simplify
the installation as they reduce the quantity and quality of operations performed at
the worksite. On the other hand, these units are often not very versatile and
rather noisy, with limited functions, mediocre energy performance and a not very
long lifetime.

CLIVET ROOFTOP UNITS ARE EVEN MORE ADAPTABLE, SIMPLE TO USE


AND CONSUMPTION REDUCING
With more than twenty years of technological evolution, Clivet rooftop units
represent the state of the art in climate control for large commercial and industrial
environments.
The specialised ranges for applications with medium to high occupancy are
widely used in buildings such as hypermarkets, shopping centres, multiplex
cinemas and restaurants.
Their success is based on their high energy efficiency, their compact size and
operation and maintenance simplicity as well as the great flexibility in selecting
best suited the model for the specific installation.
BT09N004GB-00

SMARTPACK CKN-XHE

SMARTPACK IMPLEMENTS CLIVET'S TECHNOLOGICAL EVOLUTION IN


SMALL AND MEDIUM SIZED COMMERCIAL APPLICATIONS
High efficiency Scroll compressors, electronically controlled fans, automatic renewal air management and air quality control
through an integrated CO2 probe, Freecooling, heat pump with extended functional limits, thermodynamical energy recovery,
variable capacity versions: these are just some of the technologies available with SMARTPACK, a range of models that are
ideal for air conditioning small and medium sized commercial and industrial rooms.
Their compact size and strength to weathering agents makes it possible to install them outside of the served rooms: this
results in maximum integration with internal furnishings and simplifies periodic maintenance, which can be completely
performed without accessing the environment.

COMPETITIVE ADVANTAGES
SMARTPACK simplifies the system and reduces the cost
Thanks to its packaged design, the system components are already enclosed and installed
inside the unit. The heating or cooling energy generated by the unit is transferred directly to the
served environment . This eliminates all internal units, pipes, cables and technical spaces for
their connection, and therefore also their related purchase and installation costs.

SMARTPACK frees up precious space


Its very compact design, even in comparison to rooftop units of the same size available on the
market, makes it quick and easy to position it on a flat roof, in an attic or on the ground. All of
the features are provided by Clivet already assembled and tested onboard, differently then
other manufacturers who make numerous additional components available to be installed on
site.

SMARTPACK reduces consumption and operating costs


The high efficiency of the adopted technological solutions considerably reduces the energy
required for their proper operation. This results in lower operating costs and CO2 emissions,
to the benefit of the environment. The constructive rationality also simplifies the maintenance
operations, resulting in a farther reduction in annual expenses for the user.

BT09N004GB-00

SMARTPACK CKN-XHE

THE SYSTEM IS INCLUDED INTO A SINGLE UNIT


SMARTPACK contains all the components that are necessary for its proper operation.
In the standard configuration (Clivet reference key CAK), the return air is filtered and treated by the direct expansion cooling
circuit and then introduced again into the area to be air conditioned.
The configuration with the fresh air damper (Clivet reference key CBK) allows to introduce a predetermined quantity of
renewal air.
The automatic control with a microprocessor is based on the conditions detected by the sensor installed in the served area and
on those of the outdoor air. If the application is not suited for the installation of sensors in the served area, the optional
on-board temperature and humidity probes are available.

R. Intake air
S. Treated air supply
FA. Fresh air
EX. Exhaust
A. Supply fan and air filter
Electronically controlled, it introduces air in
the served area after its recovery, filtration
with G4 efficiency and treatment.

B. Internal exchanger
It transfers energy (heating or cooling) to
the intake air

C. External exchanger
It exchanges energy (heating or cooling)
with the outdoor air

D. External fan
Axial flow fan used for efficient energy
exchange with the outdoor air

E. Direct expansion circuit


It produces cooling energy (or heating
energy on reversible models) to be
introduced in the served area

F. User interface
Easy to use, with
sensors on-board.

automatic

control

MAIN OPTIONS

VERSION WITH EXTRACTION AND EXHAUST

1. High efficiency filtration


Electronic, second stage (equivalent efficiency H10)

6a. Extraction and exhaust fan

2. Electric / hot water heating


It integrates and/or replaces the direct expansion circuit operation.

Electronically controlled, it extracts the unhealthy air from the served area
and it exhausts it outside after the thermodynamic energy recovery. It allows
automatic Freecooling operating.

3. Hot gas post-heating

6b. Overpressure damper

It recovers condensing energy in the summer humidity control.

4. Humidification

It prevents the introduction of air into the served area from the extraction/
exhaust section with the stopped fan.

Steam immersed electrode humidification

6c. Ambient pressure controller

5. Fresh air damper (CBK/CCK configuration)

It calibrates the fresh air damper opening and to balance the ambient
pressure.

It allows to introduce renewed air in the served area. The fresh air
damper is manual in the CB construction configuration (optional on off
motorized ) and modulating motorised version in the CC construction
configuration. It is not present in the CA constructive configuration
(100% recirculation).

SMARTPACK is also available in the optional configuration equipped with air extraction and exhaust system (Clivet
reference key CCK). This functionality is implemented with an extraction fan, which draws a part of the return air and ejects it
on the outdoor finned coil exchanger, performing the thermodynamic energy recovery. This increases the seasonal efficiency of
the direct expansion circuit, avoiding the large pressure drops typical of traditional static or rotary recovery units.
This version also includes the automatic control of the modulating fresh air dumper and the freecooling function, which allows
the cooling of the served area without activating the compressors.

BT09N004GB-00

SMARTPACK CKN-XHE

VERSATILE, EFFICIENT,
ENCREASES THE VALUE OF YOUR REAL ESTATE INVESTMENT
GREAT SIMPLIFICATION OF THE INSTALLATION AND INCREASE OF RELIABILITY
SMARTPACK significantly reduces the initial system costs in comparison to
traditional solutions based on hydronic systems with separate production, for
example with chillers and boilers, or on direct expansion systems with renewal
of air.
Most usual system activities are already carried out by Clivet inside the unit:
- Component selection and sizing
- Mechanical and hydraulic connections
- Electrical and control wirines
- Functional test.
The user simply has to connect the air distribution ducts and power the unit.

MADE FOR COMFORT AND BUSINESS


The numerous options and accessories that are available make it possible
to always select the best solution, based on the following factors:
- Outdoor climate, thanks to configurations for hot, temperate, severe or
extremely severe climates;
- Building type and layout of the technical spaces, with possible positioning
on the roof, in the attic or on the ground;
- Typical application and operating profile thanks to the version with 100%
recirculation, with fresh air intake and also with integrated exhaust system;
- Required comfort level, with high efficiency filtration, air quality control,
devices for humidity control;
- Importance of the energy savings for the user, thanks to functions such as
freecooling, energy recovery, modulation of the renewal air, external
electronically controlled ECOBREEZE ventilating section.

HIGH/EXTREMELY HIGH ENERGY EFFICIENCY


SMARTPACK is available in two versions that differ in the technology used
for the direct expansion circuit:
CONSTANT POWER UNIT
equipped with a high efficiency Scroll compressor, electronic controlled
expansion valve and high thermodynamic efficiency exchangers.
VARIABLE POWER UNIT
also equipped with automatic regulation of the output power for maximum
energy efficiency all year long.

INCREASING THE VALUE OF THE BUILDING AND REDUCING OPERATING COSTS


The numerous technical solutions used in SMARTPACK's cooling circuit and ventilating sections
makes it possible to obtain very high overall efficiency levels.
This also reduces seasonal consumption up to 50% in comparison to traditional solutions.
As a result, this also reduces operating costs and the environmental impact of the system, thanks
to the lower amount of primary energy needed for its function.
The reduction in the overall requirement for primary energy, in comparison to traditional
solutions, improves the building's energy performance and therefore its market value.

AA
B
C
D
D
E
E
F
F
G
G

BT09N004GB-00

SMARTPACK CKN-XHE

REFRIGERANT CIRCUIT OPTIMIZED FOR ENERGY SAVING AND RELIABILITY


CONSTANT POWER UNIT
Using a simple and robust geometry composed by of a single constant power compressor in combination with a high
efficiency cooling circuit, the unit delivers the adequate heating and cooling capacity to the system. This is made possible
thanks to the regulating logic which sequentially activates the compressors in order to reach the required comfort and keep
the ambient temperature constant.

HIGH RELIABILITY SCROLL TECHNOLOGY


The entire range uses high efficiency orbiting spiral Scroll
compressors.
The advantages are:
- Compressors manufactured in large numbers on an industrial
scale, with strict quality checks and highest reliability thanks to
the high scale mass production volumes.
- High energy efficiency

STABLE AND RELIABLE OPERATION


The electronic expansion valve (EEV) adapts rapidly
and precisely to the actual load required for usage,
allowing stable and reliable adjustment in comparison
with mechanical thermostatic valves (TEV). This
results also in a further increase in efficiency and
longer compressor life.

VARIABLE POWER UNIT


Besides taking advantage of the technical features adopted for the constant power units, the variable power unit favours the
production energy efficiency. This is made possible thanks to the partialisation of the compressor capacity and the
regulating system which provides the system only with the capacity that is actually required.
In this case, the conditions of the introduced air vary constantly for maximum user comfort.
The adopted solution uses Digital ScrollTM technology or different sized compressors on the same cooling circuit depending on
the unit size.

DIGITAL SCROLL THECNOLOGYTM

BT09N004GB-00

SCROLL COMPRESSORS CONNECTED IN TANDEM

SMARTPACK CKN-XHE

THE TECHNOLOGIES ADOPTED FOR THE CONTINUOUS MODULATION


OF THE YIELD POWER
The need to adapt the delivered power to the required load becomes a compulsory condition in order to control energy
consumption. The variable capacity unit satisfies this request.

DIGITAL SCROLLTM THECNOLOGY

Unit size from 41 to 71

The operation of the Digital ScrollTM compressor,


which is very simple and reliable, consists in
alternating compression phases and refrigerant
discharge phases by moving the spirals in the
compression chamber nearer or further away.

OPERATION: CONTINUOUS MODULATION OF THE SUPPLIED POWER


EXAMPLE
CAPACITY 50%

EXAMPLE
CAPACITY 30%

A Orbiting spiral

USEFUL EFFECT: MAINTAINING THE REQUIRED TEMPERATURE

B Fixed spiral
C Refrigerant drain
D Modulation chamber
E Piston
F Solenoid valve
G Spring
H Refrigerant return
I

Elecric motor

SCROLL COMPRESSORS CONNECTED IN TANDEM


Unit size from 91 to 151

As maximum power is only required for short periods


of time, it is very important to achieve maximum
efficiency in partial load conditions.
By using only one of the two compressors, efficiency
is increased by more than 40%, thanks to the larger
heat exchange surfaces.
In addition, the selection of different sized
compressors makes it possible to obtain more
adjustment steps, providing only the effectively
necessary energy for use.
By continuously adapting itself to the inlet air
conditions in the environment, this solution also
improves comfortable conditions for the users
and operators.

THE USE OF DIFFERENT SIZED COMPRESSORS OPTIMALLY COMPENSATES


FOR THE AMBIENT LOAD

C1+C2

C2

C1

THE SEQUENTIAL DEACTIVATION OF THE COMPRESSORS


INCREASES EFFICIENCY

Example referred to CKN-XHE 151. EER e COP referred to nominal temperature

BT09N004GB-00

SMARTPACK CKN-XHE

CONFIGURED FOR INTELLIGENT RESOURCE MANAGEMENT


AND FOR USER COMFORT
ADVANCED STANDARD ELECTRONIC CONTROL
SMARTPACK is also equipped with everything that is required for the
automatic control of ambient temperature and humidity and, through their
comparison with the outdoor air conditions:
selects the operating mode (heating or cooling);
decides which and how many resources to activate basing on the distance
from the determined set-point;
manages the renewal air and the free-cooling activation to maintain the
comfort conditions.
SIMPLE AND INTUITIVE USER INTERFACE
An innovative graphic interface prepared for wall-installation (with 230V
power supply and wiring at the customers care) is supplied as standard, with
the option to be removed from the support and connected on-board for
maintenance operations.
Its main functions include:
temperature and humidity survey through its internal probes;
daily/weekly programming for switching the unit on and off;
manual changing of the operating mode (heating or cooling) and/or the setpoint;
alarm and unit status display;
management of the operating parameters.

PROMPT FEEDBACK IN CASE OF FIRE


The unit logic is able to manage the signals coming from a fire detection unit, performing one of the actions specified below,
depending on the parameter settings. In the case of an alarm signal and according the defined logic, the compressors are
always switched off.
The roof-top units cannot be used as smoke extractors.
COMPLETE UNIT SHUTDOWN

Standard in all configurations.

BT09N004GB-00

AMBIENT IN HIGH PRESSURE

AMBIENT IN NEGATIVE PRESSURE

Only with units in CBK or CCK constructive


configuration , thus provided with outdoor air
dampers.

Only with units in CCK constructive


configuration thus provided with extraction
fans.

SMARTPACK CKN-XHE

ADVANCED HEAT PUMP


COILS PROTECTED AGAINST THE FORMATION OF ICE
The particular heat pump technology developed for CLIVET PACK guarantees
its continuous and reliable operation.
The ICE PROTECTION SYSTEM prevent the formation of ice at the base of
the external exchanger during winter operation, thanks to a special sub-cooling
circuit.
This prevents the exchanger damages caused by freezing.

INTELLIGENT DEFROSTING MANAGEMENT


The automatic defrosting cycles on surfaces of the external exchanger are managed by SMARTPACK in a predictive manner,
which reduces both the frequency and the duration. The on-board electronic regulation analyses not only the external
conditions but also the changes of the evaporating pressure in the exchanger.
The standard defrosting cycle management involves the stop of the ventilation.
This reduces the time required for defrosting and prevents the introduction of
too cold air in the served area, maintaining comfortable conditions for the
users.

EFFICIENT AND RELIABLE AIR CONDITIONER


ALSO IN SEVERE CLIMATES
HIGHLY EFFICIENCY HEATING SOLUTIONS
The reversible heat pump version of SMARTPACK is also able to operate
with particularly severe outdoor temperatures.
In many areas these conditions only occur for short periods effective use of
the system.
The use of electric heaters (I) makes it possible to maintain the
advantages of the packaged solution, both in terms of design simplicity and
installation rationality.
The electric heaters can turn on automatically as auxiliary elements to
preheat the external air before being treated by the heat pump.
Alternatively, the optional hot water coil (II) extends the operating range of
the units in even colder climates.
It also integrates the heating capacity by preheating the external air before
being treated by the heat pump.
It can also take automatically the function of main heating source below an
outdoor temperature selected by the user.
This can be done, for example, after evaluating the costs associated with
the energy sources in the specific cases.
The hot water coil is activated automatically in emergency mode in the case
of a heat pump failure.
The Electric panel antifreeze protection' option is necessary in very cold
climates.

BT09N004GB-00

SMARTPACK CKN-XHE

SANDWICH PANELS WITH IMPROVED THERMAL INSULATION AND ACCESSIBILITY


The use of sandwich panels reduces the thermal dispersions and then the
energy consumptions.
The panels have dual walls in steel sheet metal with polyurethane insulation
and feature seal gaskets along the diameter.
The door used to access to the air handling area, manufactured with this
technology, is moreover characterized with seal gaskets, handles, for a safe
use, and adjustable locks, simplifying the access to the unit for the
maintenance.

ADDITIONAL BENEFITS OF UNITS


WITH EXTRACTION AND EXHAUST SYSTEM
Units equipped with an extraction and exhaust section (Clivet reference CCK) have unique advantages that make
SMARTPACK the ideal tool for maximizing energy savings.
FREE COOLING
As soon as the external conditions allow it, the unit is capable of automatically activating the free-cooling mode,
which, keeping the compressors off and drawing in suitably filtered fresh air allows to cool the served room. . This
operating mode is especially useful in spring and autumn or in case of high ambient loads. It allows substantial
reduction of the unit energy consumption and compressors.
ACTIVE ENERGY RECOVERY OF THE EXHAUST AIR
The energy contained in the exhaust air is recovered by forcing the air flow to pass
through the external finned coil exchanger. This reduces the electric energy
absorbed by the compressors, increases overall unit efficiency and extends its
operating limits.
Such thermodynamic recovery system does not involve additional electric
consumption by the fans, unlike the rotary or crossed flow recovery system. The
greater electric consumption caused by strong pressure drops on the air side of the
rotary or crossed flow recovery systems often equals the amount of energy recovered
and in some situations even exceeds it.
When operating in heat pump mode, the exhaustion of pre-treated air on the external
exchanger reduces the possibility of ice formation and consequently the number
of defrosting cycles thanks to the external and hot exhaust air mix.
The result is a smoother continuous operation and overall unit efficiency improvement.

AMBIENT PRESSURE CONTROL DEVICE


The ambient pressure control device, which
compares the intake air pressure with the
external air pressure, detects if the pressure
is too high, too low or if it is balanced
whether the served room is in over-pression
or under-pression conditions.
Using the external air damper, the unit is
able to compensate the difference of
pressure and to keep the served room at
the required pressure.
The pressure is regulated basing on the unit
settings defined at the start-up.

BT09N004GB-00

10

SMARTPACK CKN-XHE

HIGH EFFICIENCY VENTILATION


WITH ELECTRONIC CONTROLLED FANS
HOW TO IMPROVE VENTILATION WHILE REDUCING IS CONSUMPTION
A significant portion of the running costs of the fresh air systems is due to the consumption for ventilation. To this there should
be added the charge for the study of the correct operating conditions, and for the required long and precise calibrations at the
worksite. The SMARTPAK ventilation technique allows both of these operational costs to be greatly minimised.
VERSATILITY OF REVERSED BLADES IMPELLERS
This particular type of impeller offers a wider field of operation compared
with a traditional straight-bladed fan. When necessary, it can produce high
static pressures simply by varying the number of revolutions.
The accurate balancing and the self-lubricating bearings ensure its rotating
stability over time.
EFFICIENCY OF THE ELECTRONIC CONTROLLED MOTOR
The external rotor electric motor is driven by the continuous magnetic
switching of the stator. The advantages are:
- The absence of brushes and the particular power supply system increase
efficiency by 70%;
- Even the life cycle increases, thanks to the elimination of the natural
wearing effects of the brushes;
- The electronic control also includes a "soft start" solution, which drastically
reduces the starting current of the fan and limits even more the electrical
requirements of the system.

EC
TECHNO-

ADVANTAGES OF DIRECT COUPLING (PLUG FAN)


The rotation of the motor is transmitted directly to the impeller, without the
use of transmissions (belts and pulleys):
- The inefficiencies of the transmission are eliminated;
- The belt consumption and maintenance are eliminated.
THE EFFICIENCY OF THE
VENTILATION SYSTEM INCREASES
BY 30%
The whole ventilation system, composed
by the impeller and the motor, is
therefore very versatile and efficient.
The consumption is 30% lower
compared to a ventilation system of
the same capacity used on traditional
units available on the market.
Electrical power absorbed by the electric motor, manufactured data - Example, referred to 7.800 m3/h, air flow at 500 Pa external static pressure.

THE RIGHT AIR FLOW RATE FOR EVERY TYPE OF SYSTEM


By controlling the fan speed, the air flow rate can be varied and the static pressure capacity can be adapted to the system
pressure drop, making the unit start-up particularly simple.
The adjustment or modification of the transmission is no longer required as the ventilation system will adapt itself to the
system.
The possibility to modify the fan start-up ramp makes this unit suitable for most applications with textile air distribution
ducting.
HIGH EFFICIENCY OUTDOOR FANS WITH LOW NOISE EMISSION
The external axial fans have an innovative
Winglet profile with an integrated flap which
increases the aerodynamic efficiency.
This solution reduces the consumption by
10% and it has an average sound emission
level which is 6 dB lower in comparison to
traditional fans.

11

BT09N004GB-00

SMARTPACK CKN-XHE

HIGH AIR FILTRATION EFFICIENCY


AIR QUALITY ALWAYS UNDER CONTROL
Air filtration is a compulsory function in order to correctly maintain conditions
of wellness and hygiene in the served environments.
For this reason, it is subjected to precise regulations based on the specific
applications.
The units are provided standard with large surface area and low pressure
drop filters with a G4 efficiency level.
HOW TO INCREASE THE FILTRATION EFFICIENCY WHILST MINIMISING ITS OPERATIONAL COSTS
High efficiency filters (F7 category) of a traditional system increase the energy spent on ventilation, because of greater loss of
pressure. These also require more frequent maintenance, with a significant cost at the end of each year to replace the filters. The
electronic filters available for SMARTPAK make outdoor air filtering even more efficient and at the same time they reduce costs
for ventilation and maintenance compared with traditional systems.
VERY HIGH FILTRATION EFFICIENCY
The efficiency of electronic filters on SMARTPAK is equivalent to classification H10 used in traditional filters, that is the
category indicated as "absolute filter". These are effective even against smoke, fine dust, particulates PM10, PM2,5, PM1,
bacteria, germs and viruses.

THE VENTILATION ENERGY IS REDUCED


The very high efficiency of filtration is achieved
with very low pressure drops.
These are dependant on the metal pre-filter
located upstream of the plates to trap the
largest particles, to homogeneously distribute
the air flow and to contain the magnetic field
generated during operation.

GAINS ALREADY FROM THE SECOND YEAR


OF OPERATION
The reduction of ventilation consumption is the
first item of saving for electronic filters.
Savings on maintenance are even more
evident, because electronic filters are washable
and do not need to be replaced at regularly as
traditional filters.
Taking as reference the price of a standard unit,
the total yearly running cost is reduced from
over 20% for the version with traditional-bag
filters to less than 8% thanks to the electronic
filters.
The deriving payback is usually less than
one and a half years.

BT09N004GB-00

12

SMARTPACK CKN-XHE

STANDARD UNIT SPECIFICATIONS - CONSTANT AND VARIABLE POWER VERSION


COMPRESSOR
Hermetic orbiting scroll compressor complete with motor over-temperature and
over-current devices and protection against excessive gas discharge
temperature. Fitted on rubber antivibration mounts and complete with oil
charge.
A oil heater is automatically switched on at the compressor shut-down to
prevent oil dilution by the refrigerant.
STRUCTURE
The basement is assembled with a painted galvanized steel frame. The
internal structure is made of ALUZINK bent galvanized steel . The alloy that
protects the Aluzink allow an excellent corrosion proofing thanks to the
galvanic protection typical of the combination aluminium-zinc.
PANELLING
Panels of the compressor panel in steel sheet metal, painted using polyester
powders, colour RAL 9001 and covered on the inside with as hared soundabsorbent material.
Sandwich panels in the air treatment section with dual walls in steel sheet
metal with polyurethane insulation (40 kg/m3), thickness of outer sheet metal
6/10 mm galvanized and painted using polyester powders colour RAL 9001,
polyurethane thickness 40 mm with thermal conductivity coefficient 0.022W/
mK, thickness of internal sheet metal 5/10 mm hot galvanized. The panel is
also provided with a PVC profile for thermal insulation and a EPDM rubber
gasket that ensures the hermetic seal.
All panelling can easily be removed to allow complete accessibility to internal
components.
INTERNAL EXCHANGER
Direct expansion finned exchanger, made from copper pipes in staggered rows
and mechanically expanded to the fin collars. The fins are made from
aluminium with a corrugated surface and adequately distanced to ensure the
maximum heat exchange efficiency.
EXTERNAL EXCHANGER
Direct expansion finned exchanger, made from copper pipes in staggered rows
and mechanically expanded to the fin collars. The fins are made from
aluminium with a corrugated surface and adequately distanced to ensure the
maximum heat exchange efficiency. The coils are complete with integral subcooling circuit which assures the correct refrigerant feeding of the expansion
valve. This circuit prevents the formation of frost on the exchanger during
winter operation.
FAN
Internal section
Plug fans without scroll with reverse blades driven by electronically-controlled
"brushless" dc motors with direct coupling. No transmission sizing is needed.
External section
helical fans with die-cast aluminium blades, directly coupled to a three-phase
electric motor with external rotor, with built-in thermal overload protection, IP
54 index of protection. Housed inside an aerodynamically shaped nozzles to
increase efficiency and minimise noise levels; fitted with safety grills.
REFRIGERANT CIRCUIT
The circuit is complete with:
- refrigerant charge
- sight glass with moisture indicator
- high pressure switch
- low pressure switch
- filter dryer
- electronic expansion valve
- non-return valve
- 4-way reverse cycle valve
- liquid receiver
- liquid separator
- high pressure safety valve
- low-pressure safety valve
FILTRATION
Pleated filter for greater filtering surface, made up of galvanized plate frame
with galvanized and electric-welded protective mesh, and regenerable filtering
media made from polyester fibre sized with synthetic resins. G4 efficiency
according to CEN-EN 779 standard (Eurovent class EU4/5 - average efficiency
90.1% ASHRAE 52-76 Atm). Self-extinguishing (resistance to fire class 1 - DIN
53438).
TRAY
Internal section
condensate collecting tray in aluminium alloy 1050 H24 with anti-condensate
insulation, welded and equipped with discharge coupling
External section
Thermoformed ABS condensate collection tray fitted with drain.

ELECTRICAL PANEL
The electrical panel is situated inside the units and is accessed through a
hinged door that is opened by a special key
The Power Section includes:
- main door lock isolator switch
- compressor circuit breaker
- compressor power supply remote control switch
- fan motor thermal protections of internal section and external section
- circuit breaker to protect auxiliary circuit
Microprocessor control section:
- treated air temperature control
- daily, weekly programmer of temperature set point and unit on/off
- compressor overload protection and timer
- self-diagnosis system with immediate display of the error code
- demand limit
- clean contacts for remote ON-OFF, cumulative alarm, fan status, compressor
status, summer/winter mode
Wall room electronic control including:
- intuitive graphical interface retro lighted
- temperature and humidity measurement through its internal probes;
- Unit On/Off and overload reset
- manual changing of the operating mode (hot or cold) and/or the set-point;
- setting of ventilation only operation
- display of operating status
- display of alarms and failure code;
- management of the operating parameters.
VARIABLE CAPACITY VERSION
This has the same technical specifications as with the constant capacity
version, plus:
For sizes between 41 and 71 -> Hermetic orbiting spiral DigitalScroll
compressor complete with motor protection against over temperatures, over
currents and against excessive outlet gas temperatures. It is installed on
antivibration rubbers and comes complete with an oil charge.
The automatic oil heater prevents the oil from being diluted by the refrigerant
when the compressor stops.
For sizes between 91 and 151 -> Hermetic Scroll compressors parallel
connected (TANDEM) on a single cooling circuit have two-phased oil
balancing and are provided with shut-off valves. Complete with motor
protection against over temperatures, over currents and against excessive
outlet gas temperatures. They are installed on antivibration rubbers and come
complete with an oil charge.
The automatic oil heater prevents the oil from being diluted by the refrigerant
when the compressor stops.
CONFIGURATION WITH EXTRACTION AND EXHAUST (CCK)
Standard unit specifications like standard version, and then:
- exhaust fan
Plug fans without scroll with reverse blades driven by electronically-controlled
"brushless" dc motors with direct coupling. No transmission sizing is needed.

ACCESSORIES
- Variable power unit
- 2row hot water coil
- Modulating three-way valve
- hot gas re-heating coil
- Electrode boiler steam humidifier
- Electric heaters.
- Air quality sensor for CO2 p.p.m. control
- Air quality sensor for CO2 and VOC p.p.m. control
- Electronic filters
- differential pressure switch for dirty air filters
- serial port RS485 with MODBUS protocol
- Serial communication module LON WORKS
- Temperature and humidity ambient control by on-board probes
- Supply constant air flow rate
- phase monitor
- power factor correction capacitors (cosfi > 0.9)
- Enthalpy Free-cooling (only with configuration CCK)
- Device for reducing consumption of the outdoor section variable speed fans
(phase-cut)
- high and low pressure gauges
- finned coil protection grill.
- Antifreeze device electrical panel
- Rubber antivibration mounts (separately supplied accessories)
The following are also available for these units:
- copper / copper evaporator coils with brass shoulders
- copper / copper condenser coil with brass shoulders
- copper / copper hot gas re-heating coil with brass shoulders
TEST
Unit manufactured according to the ISO 9001 quality standards and subject to
functional testing at the end of the production line

13

BT09N004GB-00

SMARTPACK CKN-XHE

VERSION: CONSTANT POWER UNIT (Clivet abbreviation SHC)


STANDARD AIR FLOW

GENERAL TECHNICAL SPECIFICATIONS SMARTPACK (PRODUCT CKN-XHE)


COOLING
SIZE
Cooling capacity
Sensible capacity
Compressor power input
EER

1
1
1
1

HEATING
Heating capacity
2
Compressor power input
2
COP
2
COMPRESSOR
Type of compressors
3
No. of Compressors
Std Capacity steps
Refrigerant circuits
AIR HANDLING SECTION FANS (OUTLET)
Type of fans
4
Number of fans
Fan diameter
Type of motor
5
Air flow
Air flow
Installed unit power
Max outside static pressure
6
FANS (EXHAUST) (ONLY WITH CONFIGURATION CCK)
Type of fans
7
Number of fans
7
Fan diameter
7
Type of motor
7
Installed unit power
7
EXTERNAL AREA FANS
Type of fans
8
Number of fans
Fan diameter
Fan RPM
Standard air flow
Installed unit power
POWER SUPPLY
Standard power supply

41

51

61

71

91

101

131

151

kW
kW
kW

12.7
10.4
2.8
4.57

15.5
12.0
4.0
3.9

21.4
16.7
4.7
4.58

24.0
18.2
5.6
4.31

30.3
23.8
6.8
4.42

34.2
26.5
8.3
4.13

45.6
35.6
10.0
4.56

52.3
41.4
11.9
4.38

kW
kW

12.2
2
6.12

15.3
2.8
5.53

20.9
3.6
5.8

23.5
4.1
5.71

29.9
5.2
5.8

34.3
6
5.69

44.1
7.5
5.9

51.2
8.9
5.73

Scroll
1
1
1

Scroll
1
1
1

Scroll
1
1
1

Scroll
1
1
1

Scroll
1
1
1

Scroll
1
1
1

Scroll
1
1
1

Scroll
1
1
1

RAD
1
355
EC
611
2200
0.7
600

RAD
1
355
EC
750
2700
0.7
500

RAD
1
450
EC
944
3400
1.1
460

RAD
1
450
EC
1139
4100
1.1
380

RAD
1
500
EC
1444
5200
2.7
750

RAD
1
500
EC
1778
6400
2.7
660

RAD
1
500
EC
2222
8000
2.7
520

RAD
1
560
EC
2667
9600
3.1
480

kW

RAD
1
280
EC
0.2

RAD
1
280
EC
0.2

RAD
1
355
EC
0.7

RAD
1
355
EC
0.7

RAD
1
355
EC
0.7

RAD
1
355
EC
0.7

RAD
1
450
EC
1.1

RAD
1
450
EC
1.1

Nr
mm
rpm
l/s
kW

AX
1
500
890
1389
0.2

AX
1
500
890
1389
0.2

AX
1
630
1040
2778
0.8

AX
1
630
1040
2778
0.8

AX
1
630
1330
3472
1.3

AX
1
630
1330
3472
1.3

AX
1
800
685
5000
1.2

AX
1
800
895
6111
2

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

Nr
Nr
Nr

Nr
mm
l/s
m3/h
kW
Pa

Nr
mm

Performance refers to operation with 30% of exhaust air (configuration CCK)


(1) Indoor air 27C D.B./19C W.B. External exchanger air intake temperature 35C
EER referred to only the compressors
(2) Indoor air 20 C D.B. Outdoor air 7 C D.B./6C W.B.
COP referred only to compressors
(3) SCROLL = scroll compressor

(4) RAD = radial ventilation


(5) EC Electronic switching motor
(6) Net outside static pressure to win the outlet and intake onboard pressure drops
(7) CCK - Configuration with exhaust air fan and mixing box
(8) AX = axial fans

CONFIGURATION: FULL RE-CIRCULATION (CAK) / RECIRCULATION AND RENEWAL AIR (CBK)

ELECTRICAL DATA
SIZE

41

51

61

71

91

101

131

151

9,8
0,9
1,5
12,7

12,1
1,4
2,2
16,2

14,3
1,4
2,2
18,4

17,4
2,5
4,3
24,7

20,4
2,5
4,3
27,7

25,4
2,3
4,3
32,5

30,6
4,2
4,9
40,2

64,0
-

75,0
-

101,0
-

111,0
-

118,0
-

140,0
-

173,0
-

5,9
0,2
1,0
7,4

7,3
0,8
1,0
9,4

8,3
0,8
1,0
10,4

9,9
1,3
2,7
14,2

11,7
1,3
2,7
16,0

14,6
1,2
2,7
18,8

17,0
2,0
3,1
22,4

66,9

79,1

105,1

118,3

125,3

147,1

182,6

F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS


F.L.A. - Compressor 1
A
7,5
F.L.A. - Compressor 2
A
F.L.A. - Single external fan
A
0,9
F.L.A. - Single supply air fan
A
1,5
F.L.A. - Total
A
10,4
1
.R.A. LOCKED ROTOR AMPERES
L.R.A. - Compressor 1
A
48,0
L.R.A. - Compressor 2
A
F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION
F.L.I. - Compressor 1
kW
4,3
F.L.I. - Compressor 2
kW
F.L.A. - Single external fan
kW
0,2
F.L.A. - Single supply air fan
kW
1,0
F.L.I. - Total
5,8
2 kW
M.I.C. MAXIMUM INRUSH CURRENT
M.I.C. - Value

50,9

Data referred to standard units.


Power supply: 400/3/50 Hz +/-6%. Voltage unbalance: max 2%
(1) Values not including accessories to obtain the value of F.L.A. including accessories, add
to the total F.L.A. value that of any accessories (see electrical data of accessories)

BT09N004GB-00

(2) Values not including accessories to obtain the value of F.L.I. including accessories, add to
the total F.L.I. value that of any accessories (see electrical data of accessories)

14

SMARTPACK CKN-XHE

VERSION: CONSTANT POWER UNIT (Clivet abbreviation SHC)


CONFIGURATION: RECIRCULATION, RENEWAL AND EXAUST AIR (CCK)

ELECTRICAL DATA
SIZE

41

F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS


F.L.A. - Compressor 1
A
7,5
F.L.A. - Compressor 2
A
F.L.A. - Single external fan
A
0,9
F.L.A. - Single supply air fan
A
1,5
F.L.A. - Single exhaust air fan
A
1,3
F.L.A. - Total
A
11,7
1
L.R.A. LOCKED ROTOR AMPERES
L.R.A. - Compressor 1
A
48,0
L.R.A. - Compressor 2
A
F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION
F.L.A. - Compressor 1
kW
4,3
F.L.A. - Compressor 2
kW
F.L.A. - Single external fan
kW
0,2
F.L.A. - Single supply air fan
kW
1,0
F.L.A. - Single exhaust air fan
kW
0,2
F.L.A. - Total
6,0
2 kW
M.I.C. MAXIMUM INRUSH CURRENT
M.I.C. - Value

52,2

Data referred to standard units.


Power supply: 400/3/50 Hz +/-6%. Voltage unbalance: max 2%
(1) Values not including accessories to obtain the value of F.L.A. including accessories, add
to the total F.L.A. value that of any accessories (see electrical data of accessories)

51

61

71

91

101

131

151

9,8
0,9
1,5
1,3
14,0

12,1
1,4
2,2
1,5
17,7

14,3
1,4
2,2
1,5
19,9

17,4
2,5
4,3
1,5
26,2

20,4
2,5
4,3
1,5
29,2

25,4
2,3
4,3
2,2
34,7

30,6
4,2
4,9
2,2
42,4

64,0
-

75,0
-

101,0
-

111,0
-

118,0
-

140,0
-

173,0
-

5,9
0,2
1,0
0,2
7,6

7,3
0,8
1,0
1,0
10,4

8,3
0,8
1,0
1,0
11,4

9,9
1,3
2,7
1,0
15,2

11,7
1,3
2,7
1,0
17,0

14,6
1,2
2,7
1,0
19,8

17,0
2,0
3,1
1,0
23,4

68,2

80,6

106,6

119,8

126,8

149,3

184,8

(2) Values not including accessories to obtain the value of F.L.I. including accessories, add to
the total F.L.I. value that of any accessories (see electrical data of accessories)

ELECTRICAL INPUT OF OPTIONAL COMPONENTS


To obtain the electrical input of the unit including accessories, add the standard data in Electrical Data table to those for the selected
accessories.
SIZE

41

51

61

71

91

101

131

151

A
A
A
A
A
A
A
A
A
A
A

6.5
8.7
13.0
3.2
0.1
1

6.5
8.7
13.0
3.2
0.1
1

8.7
13.0
17.3
3.2
0.16
1

8.7
13.0
17.3
3.2
0.16
1

13.0
17.3
26.0
3.2
8.7
8.7
0.2
1

13.0
17.3
26.0
3.2
8.7
8.7
0.2
1

17.3
26.0
34.6
3.2
8.7
8.7
0.32
1

17.3
26.0
34.6
3.2
8.7
8.7
0.32
1

kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW

4.5
6.0
9.0
2.3
0.02
0.2

4.5
6.0
9.0
2.3
0.02
0.2

6.0
9.0
12.0
2.3
0.03
0.2

6.0
9.0
12.0
2.3
0.03
0.2

9.0
12.0
18.0
2.3
6.0
6.0
0.04
0.2

9.0
12.0
18.0
2.3
6.0
6.0
0.04
0.2

12.0
18.0
24.0
2.3
6.0
6.0
0.61
0.2

12.0
18.0
24.0
2.3
6.0
6.0
0.61
0.2

F.L.A. FULL LOAD CURRENT


F.L.A. EH09 Electric heaters from 4.5 kW
F.L.A. EH10 Electric heaters from 6 kW
F.L.A. EH12 Electric heaters from 9 kW
F.L.A. EH14 Electric heaters from 12 kW
F.L.A. EH17 Electric heaters from 18 kW
F.L.A. EH20 Electric heaters from 24 kW
F.L.A. HSE3 - Electrode boiler steam humidifier from 3 kg/h
F.L.A. HSE5 - Electrode boiler steam humidifier from 5 kg/h
F.L.A. HSE8 - Electrode boiler steam humidifier from 8 kg/h
F.L.A FES - Electronic filters
F.L.A AGQ - Antifreeze device electrical panel
F.L.I. FULL LOAD POWER INPUT
F.L.I. EH09 Electric heaters from 4.5 kW
F.L.I. EH10 Electric heaters from 6 kW
F.L.I. EH12 Electric heaters from 9 kW
F.L.I. EH14 Electric heaters from 12 kW
F.L.I. EH17 Electric heaters from 18 kW
F.L.I. EH20 Electric heaters from 24 kW
F.L.I. HSE3 - Electrode boiler steam humidifier from 3 kg/h
F.L.I. HSE5 - Electrode boiler steam humidifier from 5 kg/h
F.L.I. HSE8 - Electrode boiler steam humidifier from 8 kg/h
F.L.I FES - Electronic filters
F.L.I AGQ - Antifreeze device electrical panel

SOUND LEVELS
Sound Power Level (dB)
SIZE

Octave band (Hz)

Sound
pressure
level

Sound
power
level

63

125

250

500 1000 2000 4000 8000

dB(A)

dB(A)

41

79

72

78

71

74

70

61

52

57

74

51

81

74

78

73

75

70

62

52

58

75

61

82

78

81

75

75

71

63

56

59

77

71

85

84

83

78

76

72

65

57

60

78

91

87

86

86

80

79

74

70

64

62

81

101

87

88

86

81

78

72

71

65

63

81

131

88

89

87

82

81

75

72

66

64

83

151

89

86

89

85

84

81

73

67

67

86

15

The sound levels are referred to units working at full load in nominal
conditions.
The sound pressure level is referred at a distance of 1 m. from the
ducted unit surface working in free field conditions. External static
pressure 50 Pa.
(STANDARD UNI EN ISO 3744)
Please note that when the unit is installed in conditions other than
nominal test conditions (e.g. near walls or obstacles in general), the
sound levels may undergo substantial variations.

BT09N004GB-00

SMARTPACK CKN-XHE

PRESSURE DROPS OF OPTIONAL COMPONENTS


The value of static pressure available on the supply and return duct is obtained by subtracting from the available net maximum pressure (see
general table of technical data) the pressure drops of any accessories.
SIZE
CHW2 - 2 - row hot water coil
CPHG - hot gas re-heating coil
FES - electronic filters

Pa
Pa
Pa

41

51

61

71

91

101

131

151

17
10
39

24
15
60

20
10
43

27
15
63

23
10
55

33
15
80

22
10
60

31
15
83

The values shown are to be considered approximate for units operating power in normal use with standard air flow rate.

PERFORMANCES OF THE HANDLING ELECTRIC FANS - STANDAR AIR FLOW


PRESSIONE
UTILE (Pa) (Pa)
EXTERNALSTATICA
STATIC PRESSURE
Portata
aria
Standard
airstandard
flow
41

51

61

71

91

101

131

151

Portata
aria
Standard
airstandard
flow
N
di RPM
giri ventilatori
Fan

m3/h

90

100

120

150

180

210

240

270

300

330

360

390

420

450

510

2200

2200

2200

2200

2200

2200

2200

2200

2200

2200

2200

2200

2200

2200

2200

l/s

611

611

611

611

611

611

611

611

611

611

611

611

611

611

611

rpm

1386

1405

1443

1500

1554

1608

1660

1711

1761

1811

1859

1906

1952

1997

2084

Potenza
elettrica assorbita
Total input

kW

0,23

0,24

0,26

0,29

0,32

0,36

0,39

0,43

0,47

0,50

0,54

0,58

0,62

0,66

0,74

Standard
airstandard
flow
Portata
aria

m3/h

2700

2700

2700

2700

2700

2700

2700

2700

2700

2700

2700

2700

2700

2700

Standard
airstandard
flow
Portata
aria

l/s

750

750

750

750

750

750

750

750

750

750

750

750

750

750

Fan
N
di RPM
giri ventilatori

rpm

1619

1634

1666

1712

1759

1805

1850

1895

1939

1982

2025

2066

2108

2149

Potenza
elettrica assorbita
Total input

kW

0,36

0,37

0,39

0,43

0,47

0,51

0,55

0,59

0,63

0,67

0,71

0,76

0,80

0,85

Standard
airstandard
flow
Portata
aria

m3/h

3400

3400

3400

3400

3400

3400

3400

3400

3400

3400

3400

3400

3400

3400

Standard
airstandard
flow
Portata
aria

l/s

944

944

944

944

944

944

944

944

944

944

944

944

944

944

Fan
N
di RPM
giri ventilatori

rpm

1059

1074

1103

1145

1186

1227

1268

1308

1348

1387

1426

1463

1499

1535

Potenza
elettrica assorbita
Total input

kW

0,31

0,32

0,35

0,40

0,45

0,49

0,55

0,60

0,65

0,71

0,76

0,82

0,87

0,93

Portata
aria
Standard
airstandard
flow

m3/h

4100

4100

4100

4100

4100

4100

4100

4100

4100

4100

4100

Portata
aria
Standard
airstandard
flow

l/s

1139

1139

1139

1139

1139

1139

1139

1139

1139

1139

1139

N
di RPM
giri ventilatori
Fan

rpm

1214

1230

1257

1295

1331

1366

1400

1435

1469

1502

1536

Potenza
elettrica assorbita
Total input

kW

0,46

0,48

0,51

0,57

0,62

0,67

0,73

0,79

0,85

0,91

0,97

Portata
aria
Standard
airstandard
flow

m3/h

5200

5200

5200

5200

5200

5200

5200

5200

5200

5200

5200

5200

5200

5200

5200

Portata
aria
Standard
airstandard
flow

l/s

1444

1444

1444

1444

1444

1444

1444

1444

1444

1444

1444

1444

1444

1444

1444

N
di RPM
giri ventilatori
Fan

rpm

1029

1039

1059

1090

1123

1156

1189

1222

1254

1286

1317

1348

1378

1409

1470

Potenza
elettrica assorbita
Total input

kW

0,55

0,57

0,61

0,67

0,74

0,81

0,89

0,96

1,03

1,11

1,18

1,26

1,34

1,43

1,60

Standard
airstandard
flow
Portata
aria

m3/h

6400

6400

6400

6400

6400

6400

6400

6400

6400

6400

6400

6400

6400

6400

6400

Standard
airstandard
flow
Portata
aria

l/s

1778

1778

1778

1778

1778

1778

1778

1778

1778

1778

1778

1778

1778

1778

1778

Fan
N
di RPM
giri ventilatori

rpm

1218

1225

1242

1266

1291

1316

1341

1369

1395

1422

1450

1477

1503

1529

1580

Potenza
elettrica assorbita
Total input

kW

0,87

0,90

0,96

1,03

1,10

1,17

1,25

1,33

1,42

1,51

1,61

1,70

1,79

1,88

2,06

Portata
aria
Standard
airstandard
flow

m3/h

8000

8000

8000

8000

8000

8000

8000

8000

8000

8000

8000

8000

8000

8000

8000

Portata
aria
Standard
airstandard
flow

l/s

2222

2222

2222

2222

2222

2222

2222

2222

2222

2222

2222

2222

2222

2222

2222

N
di RPM
giri ventilatori
Fan

rpm

1428

1436

1451

1467

1482

1499

1546

1535

1555

1574

1594

1613

1633

1653

1695

Potenza
elettrica assorbita
Total input

kW

1,27

1,29

1,34

1,42

1,50

1,58

1,67

1,77

1,88

1,98

2,06

2,15

2,24

2,33

2,53

Standard
airstandard
flow
Portata
aria

m3/h

9600

9600

9600

9600

9600

9600

9600

9600

9600

9600

9600

9600

9600

9600

Standard
airstandard
flow
Portata
aria

l/s

2667

2667

2667

2667

2667

2667

2667

2667

2667

2667

2667

2667

2667

2667

Fan
N
di RPM
giri ventilatori

rpm

1265

1278

1289

1307

1325

1344

1362

1380

1398

1416

1433

1451

1470

1490

Potenza
elettrica assorbita
Total input

kW

1,49

1,55

1,61

1,71

1,81

1,93

2,04

2,16

2,27

2,38

2,48

2,59

2,71

2,84

The performance takes into account the pressure drops in the unit (pressure drops in treatment, standard filters, etc.)
To determine the performance required of the fans, you must add to the usable static pressure desired the pressure drops of any accessories.

PERFORMANCES OF THE HANDLING ELECTRIC FANS - REDUCED AIR FLOW


PRESSIONE
UTILE (Pa) (Pa)
EXTERNAL STATICA
STATIC PRESSURE
Portata
aria
Standard
airstandard
flow
41

51

61

71

91

101

131

151

Portata
aria
Standard
airstandard
flow
N
di RPM
giri ventilatori
Fan

m3/h

90

100

120

150

180

210

240

270

300

330

360

390

420

450

510

1760

1760

1760

1760

1760

1760

1760

1760

1760

1760

1760

1760

1760

1760

1760

l/s

489

489

489

489

489

489

489

489

489

489

489

489

489

489

489

rpm

1191

1214

1260

1326

1389

1451

1511

1569

1624

1678

1730

1780

1829

1878

1972

Potenza
elettrica assorbita
Total input

kW

0,15

0,15

0,17

0,20

0,23

0,26

0,29

0,33

0,35

0,39

0,42

0,45

0,49

0,53

0,60

Portata
aria
Standard
airstandard
flow

m3/h

2160

2160

2160

2160

2160

2160

2160

2160

2160

2160

2160

2160

2160

2160

2160

600

600

600

600

600

0,1864 1912

1957

2002

2088

Portata
aria
Standard
airstandard
flow
N
di RPM
giri ventilatori
Fan

l/s

600

600

600

600

600

600

600

600

600

600

rpm

1389

1408

1447

1503

1558

1612

1664

1715

1766

1816

Potenza
elettrica assorbita
Total input

kW

0,23

0,24

0,26

0,29

0,33

0,36

0,40

0,43

0,47

0,51

0,54

0,58

0,62

0,66

0,74

Portata
aria
Standard
airstandard
flow

m3/h

2720

2720

2720

2720

2720

2720

2720

2720

2720

2720

2720

2720

2720

2720

2720

l/s

756

756

756

756

756

756

756

756

756

756

756

756

756

756

756

rpm

912

929

964

1015

1065

1114

1161

1207

1251

1294

1335

1375

1414

1452

1526

Portata
aria
Standard
airstandard
flow
N
di RPM
giri ventilatori
Fan
Potenza
elettrica assorbita
Total input

kW

0,20

0,21

0,24

0,28

0,32

0,36

0,41

0,45

0,50

0,55

0,60

0,65

0,70

0,75

0,86

Portata
aria
Standard
airstandard
flow

m3/h

3280

3280

3280

3280

3280

3280

3280

3280

3280

3280

3280

3280

3280

3280

Portata
aria
Standard
airstandard
flow

l/s

911

911

911

911

911

911

911

911

911

911

911

911

911

911

N
di RPM
giri ventilatori
Fan

rpm

1053

1068

1097

1140

1183

1225

1266

1308

1348

1388

1426

1463

1500

1536

Potenza
elettrica assorbita
Total input

kW

0,31

0,32

0,35

0,40

0,44

0,49

0,54

0,60

0,65

0,70

0,75

0,81

0,87

0,92

Portata
aria
Standard
airstandard
flow

m3/h

4160

4160

4160

4160

4160

4160

4160

4160

4160

4160

4160

4160

4160

4160

4160

Portata
aria
Standard
airstandard
flow

l/s

1156

1156

1156

1156

1156

1156

1156

1156

1156

1156

1156

1156

1156

1156

1156

N
di RPM
giri ventilatori
Fan

rpm

871

885

912

956

994

1034

1073

1111

1149

1187

1224

1260

1296

1330

1395

Potenza
elettrica assorbita
Total input

kW

0,34

0,36

0,40

0,46

0,52

0,58

0,64

0,70

0,77

0,84

0,91

0,98

1,06

1,13

1,29

Portata
aria
Standard
airstandard
flow

m3/h

5120

5120

5120

5120

5120

5120

5120

5120

5120

5120

5120

5120

5120

5120

5120

Portata
aria
Standard
airstandard
flow

l/s

1422

1422

1422

1422

1422

1422

1422

1422

1422

1422

1422

1422

1422

1422

1422

N
di RPM
giri ventilatori
Fan

rpm

1027

1037

1058

1091

1124

1158

1191

1224

1256

1288

1320

1351

1382

1413

1474

Potenza
elettrica assorbita
Total input

kW

0,55

0,57

0,61

0,67

0,74

0,82

0,89

0,96

1,03

1,11

1,19

1,27

1,35

1,43

1,60

Portata
aria
Standard
airstandard
flow

m3/h

6400

6400

6400

6400

6400

6400

6400

6400

6400

6400

6400

6400

6400

6400

6400

Portata
aria
Standard
airstandard
flow

l/s

1778

1778

1778

1778

1778

1778

1778

1778

1778

1778

1778

1778

1778

1778

1778

N
di RPM
giri ventilatori
Fan

rpm

1174

1180

1193

1215

1239

1264

1288

1315

1338

1365

1392

1419

1446

1473

1525

Potenza
elettrica assorbita
Total input

kW

0,73

0,75

0,79

0,86

0,95

1,03

1,09

1,17

1,24

1,32

1,41

1,50

1,59

1,69

1,86

Portata
aria
Standard
airstandard
flow

m3/h

7680

7680

7680

7680

7680

7680

7680

7680

7680

7680

7680

7680

7680

7680

7680

Portata
aria
Standard
airstandard
flow

l/s

2133

2133

2133

2133

2133

2133

2133

2133

2133

2133

2133

2133

2133

2133

2133

N
di RPM
giri ventilatori
Fan

rpm

1057

1064

1080

1102

1125

1147

1170

1194

1219

1244

1238

1295

1321

1346

1396

Potenza
elettrica assorbita
Total input

kW

0,91

0,94

1,00

1,10

1,19

1,27

1,36

1,46

1,56

1,67

1,64

1,90

2,02

2,13

2,35

The performance takes into account the pressure drops in the unit (pressure drops in treatment, standard filters, etc.)
To determine the performance required of the fans, you must add to the usable static pressure desired the pressure drops of any accessories.

BT09N004GB-00

16

SMARTPACK CKN-XHE

PERFORMANCES OF THE HANDLING ELECTRIC FANS - HIGH AIR FLOW


PRESSIONE
STATICA
UTILE (Pa)
EXTERNAL STATIC
PRESSURE
(Pa)
m3/h

Standardaria
air flow
Portata
standard
Standardaria
air flow
Portata
standard

41

FandiRPM
N
giri ventilatori

71

131

151

180

210

240

270

300

330

360

390

2640

2640

2640

2640

2640

2640

2640

2640

l/s

733

733

733

733

733

733

733

733

733

733

733

733

rpm

1585

1601

1633

1680

1728

1775

1821

1867

1912

1956

1999

2041

kW

0,34

0,35

0,37

0,41

0,44

0,48

0,52

0,56

0,60

0,64

0,69

0,73

3100

3100

3100

3100

3100

3100

3100

3100

3100

3100

3100

3100

l/s

861

861

861

861

861

861

861

861

861

861

861

861

rpm

1803

1817

1845

1887

1927

1967

2008

2048

2088

2128

2167

2205

Potenza
Total inputelettrica assorbita

kW

0,49

0,50

0,53

0,57

0,61

0,65

0,69

0,74

0,78

0,83

0,87

0,92

Standardaria
air flow
Portata
standard

m3/h

4080

4080

4080

4080

4080

4080

4080

4080

4080

4080

4080

Standardaria
air flow
Portata
standard

l/s

1133

1133

1133

1133

1133

1133

1133

1133

1133

1133

1133

FandiRPM
N
giri ventilatori

rpm

1203

1217

1243

1282

1318

1354

1388

1423

1457

1491

1525

Total inputelettrica assorbita


Potenza

kW

0,45

0,46

0,50

0,55

0,60

0,66

0,71

0,77

0,83

0,89

0,95

Portata
standard
Standardaria
air flow

m3/h

4600

4600

4600

4600

4600

4600

4600

4600

Standardaria
air flow
Portata
standard

l/s

1278

1278

1278

1278

1278

1278

1278

1278

FandiRPM
N
giri ventilatori

rpm

1332

1344

1368

1404

1438

1471

1503

1534

Potenza
Total inputelettrica assorbita

kW

0,60

0,62

0,66

0,72

0,78

0,83

0,89

0,95

Standardaria
air flow
Portata
standard

m3/h

6240

6240

6240

6240

6240

6240

6240

6240

6240

6240

6240

6240

l/s

1733

1733

1733

1733

1733

1733

1733

1733

1733

1733

1733

1733

FandiRPM
N
giri ventilatori

rpm

1191

1199

1215

1240

1266

1291

1318

1346

1373

1401

1429

1456

Total inputelettrica assorbita


Potenza

kW

0,82

0,85

0,90

0,97

1,04

1,11

1,19

1,27

1,36

1,45

1,54

1,63

Standardaria
air flow
Portata
standard

m3/h

7000

7000

7000

7000

7000

7000

7000

7000

7000

7000

7000

7000

Standardaria
air flow
Portata
standard

101

150
2640

m3/h

Standardaria
air flow
Portata
standard

91

120
2640

Portata
standard
Standardaria
air flow
FandiRPM
N
giri ventilatori

61

100
2640

Potenza
Total inputelettrica assorbita
Standardaria
air flow
Portata
standard

51

90
2640

l/s

1944

1944

1944

1944

1944

1944

1944

1944

1944

1944

1944

1944

FandiRPM
N
giri ventilatori

rpm

1323

1330

1344

1366

1389

1411

1434

1457

1481

1505

1530

1555

Total inputelettrica assorbita


Potenza

kW

1,10

1,13

1,19

1,29

1,36

1,44

1,51

1,60

1,68

1,78

1,87

1,97

Standardaria
air flow
Portata
standard

m3/h

9600

9600

9600

9600

9600

9600

9600

9600

9600

Standardaria
air flow
Portata
standard

l/s

2667

2667

2667

2667

2667

2667

2667

2667

2667

FandiRPM
N
giri ventilatori

rpm

1591

1598

1613

1632

1647

1661

1674

1689

1705

Total inputelettrica assorbita


Potenza

kW

1,75

1,78

1,83

1,91

2,00

2,09

2,18

2,27

2,38

Standardaria
air flow
Portata
standard

m3/h

10500 10500 10500 10500 10500 10500 10500 10500 10500 10500

Standardaria
air flow
Portata
standard

l/s

2917

2917

2917

2917

2917

2917

2917

2917

2917

2917

FandiRPM
N
giri ventilatori

rpm

1381

1387

1398

1415

1431

1448

1465

1482

1498

1515

Total inputelettrica assorbita


Potenza

kW

1,94

1,97

2,04

2,14

2,25

2,36

2,48

2,61

2,74

2,87

The performance takes into account the pressure drops in the unit (pressure drops in treatment, standard filters, etc.)
To determine the performance required of the fans, you must add to the usable static pressure desired the pressure drops of any accessories.

OPERATING LIMITS (COOLING)


30

THE LIMITS ARE INDICATIVE AND CONSIDERED:


- GENERAL AND NON-SPECIFIC SIZES
- STANDARD AIR FLOW-RATE
- CORRECTLY INSTALLED AND MAINTAINED UNIT
- OPERATION AT FULL LOAD

TM (W.B.)

25

TO VERIFY THE UNIT OPERATING LIMITS WITH PERCENTAGES OF OUTDOOR AIR, ALWAYS
CALCULATE THE TEMPERATURE TM OF THE MIXTURE GENERATED AT THE INLET OF THE INTERNAL
EXCHANGER.

(1)

(2)
20

TM = INLET AIR TEMPERATURE IN THE INTERNAL EXCHANGER


ATTENTION! TEMPERATURE MEASURED WITH A WET BULB
(W.B. = WET BULB)

15

TEXT = INLET AIR TEMPERATURE IN THE EXTERNAL EXCHANGER


ATTENTION! TEMPERATURE MEASURED WITH A DRY BULB
(D.B. = DRY BULB)

10

1 = STANDARD OPERATING RANGE


2 = OPERATION FIELD OF THE UNIT FITTED WITH THE LOW TEMPERATURE DEVICE

5
0

10

15

20

25

30

35

40

45

50

DRY BULB TEMPERATURE - EXAMPLE

TEXT (D.B.)

OPERATING LIMITS (HEATING)


THE LIMITS ARE INDICATIVE AND CONSIDERED:
- GENERAL AND NON-SPECIFIC SIZES
- STANDARD AIR FLOW-RATE
- OPERATION AT FULL LOAD
- CORRECTLY INSTALLED AND MAINTAINED UNIT

30
25

TO VERIFY THE UNIT OPERATING LIMITS WITH PERCENTAGES OF OUTDOOR AIR, ALWAYS
CALCULATE THE TEMPERATURE TM OF THE MIXTURE GENERATED AT THE INLET OF THE INTERNAL
EXCHANGER.

TM (D.B.)

20

TM = INLET AIR TEMPERATURE IN THE INTERNAL EXCHANGER


ATTENTION! TEMPERATURE MEASURED WITH A WET BULB
(W.B. = WET BULB)

(1)

15

(2)

10

TEXT = INLET AIR TEMPERATURE IN THE EXTERNAL EXCHANGER


ATTENTION! TEMPERATURE MEASURED WITH A DRY BULB
(D.B. = DRY BULB)

1 = OPERATION AT FULL LOAD


2 = OPERATION FIELD OF THE UNIT ONLY FOR A LIMITED PERIOD OF TIME (MAX 1 HOUR

0
-5
-15

-10

-5

10

15

20

TEXT (W.B.)

17

IN PROLONGED HEAT PUMP OPERATING MODE WITH OUTDOOR AIR TEMPERATURES BELOW 6 C THE
UNIT WILL PERFORM DEFROSTING CYCLES WITH CYCLE INVERSION TO ELIMINATE THE ICE FORMED
ON THE SURFACES OF THE OUTDOOR EXCHANGER. IN THE CASE OF NEGATIVE TEMPERATURES, IT IS
IMPORTANT TO DISCHARGE THE WATER PRODUCED FROM THE DEFROSTING CYCLE TO PREVENT ICE
FROM ACCUMULATING NEAR THE UNIT'S BASE. PAY ATTENTION SO THIS DOES NOT REPRESENT A
HAZARD TO PEOPLE OR PROPERTY.
WITH AN OUTDOOR AIR TEMPERATURE BETWEEN 10C AND 20C INSTALL THE FOLLOWING
OPTIONS: 2-ROW HOT WATER COIL AND ELECTRIC PANEL ANTIFREEZE PROTECTION.

BT09N004GB-00

SMARTPACK CKN-XHE

VERSION: CONSTANT POWER UNIT (Clivet abbreviation SHC)


STANDARD AIR FLOW
SIZE
Air flow
Air flow
Max outside static pressure

l/s
m3/h
Pa

41

51

61

71

91

101

131

151

611
2200
600

750
2700
500

944
3400
460

1139
4100
390

1444
5200
750

1778
6400
660

2222
8000
520

2667
9600
490

COOLING PERFORMANCE
GRANDEZZE
SIZE

41

51

61

71

91

101

131

151

TEMPERATURA
ARIA ESTERNA
C
EXTERNAL
AIR TEMPERATURE
C D.B.

Ta
(C)
DB/WB

kWf

kWe

kWs

kWf

kWe

kWs

kWf

kWe

kWs

kWf

kWe

kWs

kWf

kWe

kWs

kWf

kWe

kWs

22 / 16

12.1

1.9

9.7

12.1

2.2

9.4

12.0

2.4

9.2

12.1

2.7

8.9

12.1

3.0

8.6

12.2

3.2

8.4

24 / 17
26 / 18

12.2
12.4

2.0
2.0

10.4
11.2

12.3
12.5

2.2
2.2

10.2
10.9

12.3
12.5

2.4
2.5

10.0
10.7

12.2
12.4

2.7
2.7

9.7
10.5

12.2
12.4

3.0
3.1

9.5
10.2

12.2
12.3

3.3
3.3

9.3
10.0

27 / 19

12.7

2.0

11.1

12.7

2.2

10.9

12.7

2.5

10.6

12.7

2.8

10.4

12.6

3.1

10.2

28 / 20

13.0

2.0

11.1

13.0

2.2

10.8

13.0

2.5

10.6

12.9

2.8

10.3

30 / 22

13.8

2.0

10.9

13.7

2.2

10.6

13.5

2.5

10.3

13.4

2.8

10.0

22 / 16

14.6

2.8

11.7

14.7

3.1

11.4

14.8

3.5

11.1

14.9

3.9

10.7

14.9

4.2

10.4

14.9

4.6

10.1

24 / 17
26 / 18

14.9
15.2

2.8
2.9

12.5
13.2

15.0
15.3

3.2
3.2

12.1
12.8

15.1
15.3

3.5
3.6

11.8
12.5

15.1
15.3

3.9
3.9

11.5
12.1

15.1
15.2

4.3
4.3

11.1
11.8

15.0
15.2

4.6
4.6

10.8
11.5

27 / 19

15.5

2.9

13.0

15.5

3.3

12.7

15.5

3.6

12.4

15.5

4.0

12.0

15.4

4.3

11.7

15.4

4.6

11.4

28 / 20

15.8

3.0

12.9

15.7

3.3

12.6

15.7

3.6

12.3

15.7

4.0

12.0

15.7

4.4

11.7

30 / 22

16.4

3.1

12.9

16.1

3.4

12.6

16.0

3.7

12.4

16.1

4.0

12.1

16.3

4.4

11.9

22 / 16

20.1

3.3

15.7

20.2

3.7

15.3

20.3

4.1

14.9

20.4

4.5

14.5

20.5

5.0

14.1

20.6

5.4

13.8

24 / 17
26 / 18

20.5
20.9

3.3
3.4

16.8
17.9

20.5
20.9

3.7
3.8

16.4
17.5

20.6
20.9

4.2
4.2

16.0
17.1

20.7
21.0

4.6
4.6

15.6
16.8

20.8
21.1

5.0
5.1

15.3
16.4

21.0
21.3

5.4
5.5

15.0
16.1

27 / 19

21.3

3.4

17.8

21.3

3.8

17.4

21.3

4.2

17.1

21.4

4.7

16.7

21.5

5.1

16.3

21.6

5.5

16.1

28 / 20

21.8

3.4

17.7

21.8

3.8

17.3

21.7

4.3

16.9

21.7

4.7

16.5

21.7

5.2

16.2

21.8

5.6

15.9

30 / 22

22.7

3.5

17.1

22.8

3.9

16.7

22.7

4.3

16.2

22.6

4.7

15.8

22.3

5.2

15.3

22 / 16

22.3

4.0

17.8

22.3

4.4

17.4

22.4

4.9

16.9

22.8

5.4

16.4

23.3

5.9

15.9

23.8

6.4

15.6

24 / 17
26 / 18

22.9
23.4

4.0
4.0

18.8
19.7

22.9
23.5

4.4
4.5

18.4
19.3

23.0
23.5

4.9
5.0

17.9
18.8

23.2
23.6

5.5
5.5

17.4
18.3

23.4
23.6

6.0
6.1

17.0
17.9

23.6
23.6

6.5
6.6

16.6
17.5

27 / 19

24.0

4.0

19.5

24.0

4.5

19.1

24.0

5.0

18.6

24.0

5.6

18.2

23.9

6.2

17.7

23.7

6.7

17.4

28 / 20

24.4

4.1

19.5

24.5

4.6

19.0

24.5

5.1

18.6

24.4

5.6

18.1

24.2

6.2

17.7

30 / 22

25.4

4.2

19.9

25.3

4.7

19.5

25.3

5.2

19.1

25.2

5.7

18.7

25.1

6.3

18.3

22 / 16

28.5

4.9

22.6

28.5

5.4

22.0

28.6

6.0

21.4

28.8

6.7

20.8

29.1

7.3

20.2

29.4

7.9

19.7

24 / 17
26 / 18

29.0
29.6

5.0
5.0

24.1
25.6

29.0
29.5

5.5
5.5

23.5
25.0

29.1
29.6

6.1
6.1

23.0
24.5

29.3
29.8

6.7
6.8

22.4
23.9

29.6
30.1

7.4
7.5

21.8
23.4

29.9
30.5

8.0
8.2

21.4
22.9

27 / 19

30.2

5.1

25.4

30.1

5.6

24.9

30.1

6.2

24.3

30.3

6.8

23.8

30.6

7.6

23.2

31.0

8.3

22.8

28 / 20

30.9

5.1

25.2

30.7

5.6

24.7

30.7

6.2

24.1

30.8

6.9

23.6

31.1

7.7

23.1

31.5

8.4

22.6

30 / 22

32.1

5.2

24.7

31.9

5.8

24.2

31.8

6.4

23.7

31.9

7.1

23.1

32.2

7.8

22.6

32.5

8.5

22.2

22 / 16

32.6

6.0

25.8

32.7

6.7

25.1

32.7

7.4

24.4

32.8

8.1

23.7

32.8

9.0

23.0

32.8

9.8

22.4

24 / 17
26 / 18

33.1
33.7

6.1
6.1

27.4
28.8

33.2
33.7

6.7
6.7

26.7
28.1

33.2
33.8

7.4
7.4

25.9
27.4

33.2
33.7

8.2
8.2

25.2
26.7

33.2
33.6

9.0
9.1

24.5
25.9

33.1
33.4

9.8
9.8

23.9
25.4

27 / 19

34.3

6.1

28.7

34.3

6.8

27.9

34.3

7.5

27.2

34.2

8.3

26.5

34.0

9.1

25.8

33.8

9.8

25.2

28 / 20

34.9

6.2

28.6

34.9

6.8

27.9

34.9

7.6

27.2

34.7

8.3

26.5

34.5

9.2

25.8

34.2

9.9

25.2

30 / 22

36.3

6.3

29.4

36.3

7.0

28.7

36.1

7.7

28.0

35.9

8.5

27.4

35.6

9.3

26.7

35.3

10.0

26.2

22 / 16

42.1

7.3

33.8

42.5

8.0

33.1

42.9

8.8

32.3

43.2

9.7

31.5

43.6

10.7

30.7

43.9

11.6

30.1

24 / 17
26 / 18

43.0
43.9

7.3
7.4

36.0
37.9

43.4
44.2

8.0
8.1

35.2
37.2

43.7
44.5

8.9
9.0

34.5
36.5

44.0
44.8

9.8
9.9

33.8
35.8

44.3
45.0

10.8
10.9

33.0
35.1

44.5
45.2

11.7
11.8

32.5
34.6

27 / 19

44.8

7.5

37.6

45.1

8.2

37.0

45.3

9.0

36.3

45.6

10.0

35.6

45.8

11.0

34.9

45.9

11.9

34.4

28 / 20

45.7

7.6

37.6

45.9

8.3

36.9

46.1

9.1

36.2

46.3

10.1

35.5

46.6

11.1

34.8

46.8

12.0

34.2

30 / 22

47.4

7.9

38.4

47.5

8.5

37.6

47.7

9.3

36.8

47.9

10.2

36.1

48.3

11.2

35.3

22 / 16

48.6

8.6

38.7

49.0

9.5

37.8

49.3

10.5

36.9

49.6

11.6

36.0

49.8

12.8

35.1

50.0

13.8

34.4

24 / 17
26 / 18

49.6
50.6

8.7
8.8

41.3
44.0

50.0
51.0

9.7
9.7

40.4
43.2

50.3
51.3

10.6
10.7

39.6
42.3

50.5
51.4

11.7
11.8

38.8
41.5

50.6
51.3

12.9
13.0

37.9
40.7

50.5
51.1

13.9
14.0

37.2
40.1

27 / 19

51.6

8.9

43.8

52.1

9.8

43.0

52.3

10.8

42.2

52.3

11.9

41.4

52.1

13.1

40.6

51.7

14.1

39.9

28 / 20

52.7

9.0

43.5

53.1

9.9

42.7

53.3

10.9

41.9

53.2

12.0

41.1

52.9

13.2

40.3

52.4

14.2

39.6

30 / 22

54.8

9.2

42.4

55.1

10.1

41.5

55.2

11.1

40.6

55.0

12.2

39.8

54.6

13.3

38.9

54.1

14.2

38.2

20

25

Performance refers to operation with 30% of exhaust air (configuration CCK)


Ta = Indoor air temperature D.B/W.B
D.B. = dry bulb
W.B. = wet bulb
kWf = Cooling capacity in kW

BT09N004GB-00

30

35

40

44

kWe = Compressor power input in kW


kWs = sensible cooling capacity (kW)
All cooling capacities do not take into account the heat generated by fan motors

18

SMARTPACK CKN-XHE

VERSION: CONSTANT POWER UNIT (Clivet abbreviation SHC)


INTEGRATED HEATING CAPACITIES
External exchanger inlet temperature C (D.B./W.B.)
Heating capacity multiplication coefficient

-5 / -5.4
0,89

0 / -0.6
0,88

5 / 3.9
0,94

ALTRI
1

The integrated heating capacity represents the real heating capacity considering the defrost cycles too.
To obtain the integrated heating capacity multiply the heating performance value in kWt ( shown in the heating performance tables) by the coefficients indicated in the table.
D.B. = DRY BULB
W.B. = WET BULB
ATTENTION! In prolonged heat pump operating mode with negative outdoor temperatures, it is important to remove the water produced from t he defrosting cycle to prevent ice from
accumulating near the unit's base. Pay attention so this does not represent a hazard to people or property.

AIR FLOW: STANDARD


SIZE
Air flow
Air flow
Max outside static pressure

l/s
m3/h
Pa

41

51

61

71

91

101

131

151

611
2200
600

750
2700
500

944
3400
460

1139
4100
390

1444
5200
750

1778
6400
660

2222
8000
520

2667
9600
490

HEATING PERFORMANCE
Ta
GRANDEZZE
(C)
-7 / -8
SIZE
DB
kWt
kWe

kWt

kWe

kWt

kWe

kWt

kWe

kWt

kWe

kWt

kWe

10

9.3

1.5

10.4

1.5

10.8

1.6

12.2

1.7

13.7

1.8

15

9.1

1.5

9.5

1.6

10.5

1.7

10.9

1.7

12.2

1.8

13.6

2.0

18

9.2

1.6

9.5

1.6

10.5

1.7

11.0

1.8

12.2

1.9

13.6

2.1

20

9.2

1.6

9.5

1.7

10.6

1.8

11.0

1.9

12.2

2.0

13.6

2.2

22

9.2

1.7

9.5

1.7

10.6

1.8

11.0

1.9

12.2

2.0

13.6

2.2

25

9.1

1.8

9.5

1.8

10.6

2.0

11.1

2.0

12.3

2.2

13.6

2.4

10

11.2

2.0

11.6

2.0

12.9

2.1

13.5

2.1

15.0

2.3

16.9

2.5

15

11.5

2.1

11.9

2.1

13.1

2.3

13.6

2.3

15.2

2.5

16.9

2.8

18

11.6

2.2

12.0

2.2

13.2

2.4

13.8

2.5

15.2

2.7

16.9

2.9

20

11.8

2.3

12.2

2.3

13.3

2.5

13.8

2.5

15.3

2.8

16.9

3.0

22

11.8

2.3

12.2

2.3

13.4

2.5

13.9

2.6

15.3

2.8

16.9

3.1

25

12.1

2.5

12.5

2.5

13.5

2.7

14.0

2.8

15.4

3.0

17.0

3.3

10

17.7

2.7

18.5

2.8

20.8

3.1

23.4

3.4

15

15.9

2.7

17.8

2.9

18.6

3.0

20.8

3.3

23.3

3.6

18

15.3

2.8

16.0

2.9

17.9

3.1

18.7

3.2

20.9

3.5

23.3

3.8

20

15.3

2.8

16.0

2.9

17.9

3.2

18.7

3.3

20.9

3.6

23.3

3.9

22

15.3

2.9

16.0

3.0

17.9

3.2

18.7

3.4

20.9

3.7

23.3

4.0

25

15.2

3.1

15.9

3.2

17.9

3.4

18.8

3.6

21.0

3.9

23.3

4.3

10

20.1

3.1

20.9

3.2

23.4

3.5

26.1

3.8

15

18.0

3.0

20.1

3.3

21.0

3.4

23.4

3.8

26.1

4.2

18

17.4

3.1

18.1

3.2

20.2

3.5

21.1

3.6

23.5

4.0

26.1

4.4

20

17.5

3.2

18.2

3.3

20.3

3.6

21.1

3.7

23.5

4.1

26.1

4.5

22

17.5

3.3

18.3

3.4

20.3

3.7

21.2

3.8

23.5

4.2

26.1

4.6

25

18.0

3.5

18.7

3.6

20.6

4.0

21.4

4.1

23.7

4.5

26.2

4.9

10

25.4

4.0

26.5

4.1

29.7

4.4

33.2

4.8

15

22.6

4.0

25.4

4.3

26.6

4.4

29.8

4.7

33.1

5.2

18

21.6

4.0

22.7

4.1

25.6

4.4

26.8

4.6

29.8

5.0

33.1

5.5

20

21.7

4.1

22.8

4.3

25.7

4.6

26.8

4.7

29.9

5.2

33.1

5.6

22

21.8

4.2

22.9

4.3

25.7

4.7

26.9

4.8

29.9

5.2

33.1

5.7

25

22.4

4.5

23.4

4.6

26.0

5.0

27.1

5.1

30.1

5.6

33.1

6.1

10

28.7

4.5

30.1

4.7

33.8

5.1

37.6

5.5

15

25.4

4.5

26.5

4.6

29.4

4.9

30.6

5.1

34.0

5.5

37.7

6.0

18

25.9

4.7

26.9

4.8

29.7

5.2

30.9

5.4

34.1

5.8

37.8

6.4

20

26.1

4.9

27.1

5.0

29.8

5.4

31.0

5.5

34.3

6.0

37.8

6.6

22

26.1

4.9

27.2

5.1

29.9

5.5

31.1

5.6

34.3

6.1

37.8

6.7

25

26.1

5.2

27.2

5.4

30.1

5.8

31.4

6.0

34.5

6.6

37.9

7.1

10

37.1

5.7

39.0

5.9

43.5

6.4

47.8

6.9

15

33.8

5.8

37.7

6.2

39.3

6.4

43.7

6.9

48.5

7.5

18

33.0

5.9

34.3

6.0

37.9

6.5

39.6

6.7

43.9

7.2

48.8

7.9

20

33.2

6.1

34.5

6.2

38.1

6.7

39.7

6.9

44.1

7.5

49.0

8.1

22

33.3

6.1

34.6

6.3

38.2

6.8

39.8

7.0

44.1

7.6

49.0

8.3

25

33.1

6.5

34.5

6.7

38.4

7.2

40.1

7.4

44.4

8.1

49.1

8.8

10

43.3

6.9

45.3

7.1

50.8

7.7

57.1

8.4

15

38.8

6.9

43.5

7.4

45.6

7.6

50.9

8.3

56.7

9.0

18

37.3

7.0

39.1

7.2

43.8

7.7

45.8

8.0

51.0

8.7

56.7

9.4

20

37.7

7.3

39.4

7.4

44.0

8.0

45.9

8.2

51.2

8.9

56.9

9.7

22

38.0

7.4

39.6

7.6

44.1

8.1

46.0

8.3

51.2

9.1

57.0

9.9

25

39.3

7.9

40.6

8.1

44.5

8.6

46.3

8.9

51.6

9.7

57.8

10.6

41

51

61

71

91

101

131

151

TEMPERATURA
ESTERNA (C)
D.B./W.B.
EXTERNAL AIR ARIA
TEMPERATURE
C D.B.
-5 / -6

0 / -1

Performance refers to operation with 30% of exhaust air (configuration CCK)


Ta = Indoor air temperature D.B
D.B. = dry bulb
W.B. = wet bulb

2/1

7/6

12 / 11

kWt = Supplied heating capacity in kW with unfrozen coils


kWe = Compressor power input in kW
All cooling capacities do not take into account the heat generated by fan motors

19

BT09N004GB-00

SMARTPACK CKN-XHE

VERSION: CONSTANT POWER UNIT (Clivet abbreviation SHC)


REDUCED AIR FLOW
SIZE
Air flow
Air flow
Max outside static pressure

l/s
m3/h
Pa

41

51

61

71

91

101

131

151

489
1760
670

600
2160
610

756
2720
550

911
3280
480

1156
4160
800

1422
5120
760

1778
6400
730

2133
7680
660

COOLING PERFORMANCE
SIZE
GRANDEZZE

41

51

61

71

91

101

131

151

TEMPERATURA
ESTERNA
C
EXTERNAL
AIR TEMPERATURE
C
D.B.
TEMPERATURA
ARIAARIA
ESTERNAC
D.B.

Ta
(C)
DB/WB

kWf

kWe

kWs

kWf

kWe

kWs

kWf

kWe

kWs

kWf

kWe

kWs

kWf

kWe

kWs

kWf

kWe

kWs

24 / 17

11.9

2.0

9.6

11.9

2.2

9.3

11.9

2.4

9.1

11.9

2.7

8.8

11.9

3.1

8.6

11.9

3.4

8.4

26 / 18

12.1

2.0

10.2

12.1

2.2

9.9

12.1

2.5

9.7

12.1

2.7

9.4

12.2

3.0

9.2

12.2

3.3

9.0

27 / 19

12.4

2.0

10.1

12.3

2.2

9.8

12.3

2.5

9.6

12.4

2.7

9.4

12.4

3.0

9.1

12.5

3.3

8.9

28 / 20

12.6

2.0

10.0

12.6

2.2

9.8

12.6

2.5

9.5

12.6

2.8

9.3

12.7

3.0

9.1

30 / 22

13.2

2.0

9.8

13.1

2.3

9.5

13.1

2.5

9.3

13.1

2.8

9.1

13.1

3.1

8.8

32 / 24

13.7

2.1

9.4

13.7

2.3

9.1

13.6

2.6

8.9

13.6

2.8

8.7

24 / 17

14.6

2.8

11.4

14.6

3.2

11.1

14.6

3.5

10.9

14.6

3.9

10.6

14.7

4.3

10.3

14.8

4.6

10.0

26 / 18

14.9

2.8

12.1

14.8

3.2

11.8

14.8

3.6

11.5

14.8

3.9

11.2

14.9

4.3

10.9

14.9

4.6

10.7

27 / 19

15.1

2.9

12.0

15.1

3.2

11.7

15.1

3.6

11.4

15.1

4.0

11.2

15.1

4.4

10.9

15.1

4.7

10.6

28 / 20

15.4

2.9

11.9

15.4

3.3

11.7

15.4

3.7

11.4

15.3

4.0

11.1

15.3

4.4

10.8

15.3

4.7

10.6

30 / 22

16.0

3.0

11.8

16.0

3.4

11.5

15.9

3.7

11.2

15.9

4.1

10.9

15.8

4.4

10.6

32 / 24

16.7

3.0

11.5

16.6

3.4

11.1

16.5

3.8

10.8

16.4

4.1

10.5

24 / 17

19.9

3.3

15.5

19.8

3.7

15.1

19.9

4.1

14.7

20.0

4.6

14.2

20.2

5.1

13.8

20.4

5.5

13.5

26 / 18

20.3

3.3

16.3

20.3

3.7

15.9

20.3

4.1

15.5

20.4

4.6

15.0

20.5

5.1

14.6

20.7

5.5

14.3

27 / 19

20.7

3.4

16.3

20.7

3.7

15.9

20.7

4.2

15.4

20.8

4.6

15.0

20.9

5.1

14.6

21.0

5.6

14.2

28 / 20

21.2

3.4

16.2

21.2

3.8

15.8

21.2

4.2

15.4

21.2

4.7

15.0

21.2

5.2

14.6

21.2

5.6

14.3

30 / 22

22.1

3.5

16.2

22.1

3.8

15.8

22.1

4.3

15.4

22.0

4.7

15.1

21.9

5.2

14.7

32 / 24

23.0

3.5

16.3

23.0

3.9

16.0

23.0

4.3

15.7

22.8

4.8

15.4

22.6

5.3

15.1

24 / 17

22.2

3.9

17.5

22.4

4.4

17.0

22.5

4.9

16.6

22.5

5.5

16.2

22.5

6.1

15.7

22.5

6.6

15.4

26 / 18

22.8

4.0

18.4

22.8

4.4

18.0

22.8

5.0

17.5

22.9

5.5

17.1

22.9

6.1

16.7

23.0

6.6

16.4

27 / 19

23.3

4.0

18.3

23.2

4.5

17.9

23.2

5.0

17.5

23.2

5.6

17.1

23.3

6.1

16.6

23.4

6.6

16.3

28 / 20

23.8

4.1

18.3

23.7

4.5

17.9

23.6

5.1

17.4

23.6

5.6

17.0

23.7

6.2

16.6

23.9

6.7

16.3

30 / 22

24.8

4.1

18.3

24.6

4.6

17.8

24.5

5.1

17.4

24.5

5.7

17.0

24.5

6.3

16.5

32 / 24

25.7

4.2

18.4

25.6

4.7

18.0

25.5

5.2

17.5

25.4

5.8

17.1

25.4

6.3

16.6

24 / 17

28.2

4.9

22.2

28.1

5.4

21.6

28.3

6.0

21.1

28.5

6.7

20.6

28.8

7.4

20.1

29.2

8.0

19.7

26 / 18

28.8

4.9

23.4

28.7

5.5

22.9

28.7

6.1

22.4

28.9

6.8

21.9

29.2

7.5

21.4

29.6

8.1

21.0

27 / 19

29.5

5.0

23.3

29.2

5.5

22.9

29.2

6.1

22.4

29.3

6.8

21.9

29.6

7.6

21.4

30.1

8.2

21.0

28 / 20

30.1

5.0

23.3

29.8

5.6

22.8

29.7

6.2

22.3

29.8

6.9

21.8

30.1

7.6

21.3

30.5

8.3

20.9

30 / 22

31.3

5.1

23.0

30.9

5.7

22.4

30.8

6.3

21.9

30.9

7.0

21.4

31.2

7.8

20.9

31.6

8.5

20.4

32 / 24

32.5

5.2

22.5

32.2

5.8

21.8

32.1

6.4

21.2

32.1

7.1

20.6

32.4

7.9

20.0

32.7

8.7

19.6

24 / 17

31.9

5.9

25.6

32.0

6.6

24.9

32.0

7.3

24.1

32.1

8.1

23.3

32.1

9.0

22.5

32.1

9.7

21.9

26 / 18

32.5

6.0

27.0

32.6

6.6

26.2

32.6

7.4

25.5

32.6

8.2

24.7

32.6

9.0

23.9

32.6

9.7

23.2

27 / 19

33.2

6.0

26.9

33.2

6.7

26.1

33.2

7.5

25.4

33.2

8.3

24.6

33.2

9.1

23.8

33.1

9.8

23.2

28 / 20

33.8

6.1

26.7

33.9

6.8

26.0

33.8

7.5

25.3

33.8

8.3

24.5

33.7

9.2

23.8

33.6

9.9

23.2

30 / 22

35.3

6.2

26.4

35.2

6.9

25.8

35.1

7.7

25.2

35.0

8.5

24.6

34.8

9.3

24.0

34.6

10.0

23.6

32 / 24

36.8

6.3

26.1

36.6

7.0

25.7

36.4

7.8

25.4

36.2

8.6

25.0

35.9

9.5

24.7

35.7

10.2

24.4

24 / 17

41.7

7.3

33.3

42.0

8.0

32.6

42.3

8.9

31.9

42.7

9.8

31.1

43.1

10.8

30.4

43.5

11.6

29.8

26 / 18

42.5

7.3

35.3

42.8

8.1

34.6

43.1

9.0

33.9

43.4

9.9

33.1

43.8

10.9

32.4

44.1

11.7

31.8

27 / 19

43.4

7.4

35.2

43.7

8.2

34.5

44.0

9.0

33.7

44.2

10.0

33.0

44.5

11.0

32.3

44.7

11.9

31.7

28 / 20

44.3

7.5

35.0

44.6

8.2

34.3

44.9

9.1

33.5

45.1

10.0

32.8

45.2

11.1

32.0

45.3

12.0

31.4

30 / 22

46.3

7.6

34.2

46.7

8.3

33.5

46.9

9.1

32.7

47.0

10.2

31.9

46.9

11.4

31.1

32 / 24

48.3

7.6

32.6

48.9

8.3

31.7

49.1

9.2

30.9

24 / 17

48.4

8.8

38.0

48.8

9.6

37.2

49.1

10.5

36.3

49.1

11.7

35.5

49.0

13.0

34.6

48.8

14.3

33.9

26 / 18

49.3

8.8

39.9

49.6

9.7

39.1

49.7

10.6

38.2

49.9

11.8

37.4

49.9

13.1

36.5

49.9

14.2

35.8

27 / 19

50.2

8.9

39.7

50.3

9.7

38.9

50.5

10.7

38.0

50.7

11.9

37.2

50.8

13.1

36.3

51.0

14.2

35.6

28 / 20

51.1

8.9

39.5

51.2

9.8

38.7

51.3

10.9

37.8

51.5

12.0

37.0

51.7

13.2

36.2

51.9

14.2

35.5

30 / 22

52.8

9.0

39.3

53.1

10.0

38.5

53.3

11.0

37.6

53.4

12.1

36.8

53.4

13.3

36.0

53.4

14.2

35.3

32 / 24

54.6

9.1

39.3

55.2

10.2

38.5

55.5

11.2

37.6

55.4

12.3

36.8

55.0

13.4

36.0

54.4

14.2

35.4

20

25

Performance refers to operation with 30% of exhaust air (configuration CCK)


Ta = Indoor air temperature D.B/W.B
D.B. = dry bulb
W.B. = wet bulb
kWf = Cooling capacity in kW

BT09N004GB-00

30

35

40

44

kWe = Compressor power input in kW


kWs = sensible cooling capacity (kW)
All cooling capacities do not take into account the heat generated by fan motors

20

SMARTPACK CKN-XHE

VERSION: CONSTANT POWER UNIT (Clivet abbreviation SHC)


INTEGRATED HEATING CAPACITIES
External exchanger inlet temperature C (D.B./W.B.)
Heating capacity multiplication coefficient

-5 / -5.4
0,89

0 / -0.6
0,88

5 / 3.9
0,94

ALTRI
1

The integrated heating capacity represents the real heating capacity, including the effect of possible defrosting cycles.
To obtain the integrated heating capacity multiply the heating performance value in kWt ( shown in the heating performance tables) by the coefficients indicated in the table = at page 19
D.B. = DRY BULB
W.B. = WET BULB
ATTENTION! In prolonged heat pump operating mode with negative outdoor temperatures, it is important to remove the water produced from t he defrosting cycle to prevent ice from
accumulating near the unit's base. Pay attention so this does not represent a hazard to people or property.

AIR FLOW: REDUCED

41

51

61

71

91

101

131

151

489
1760
670

600
2160
610

756
2720
550

911
3280
480

1156
4160
800

1422
5120
760

1778
6400
730

2133
7680
660

GRANDEZZE
Air flow
Air flow
Max outside static pressure

l/s
m3/h
Pa

HEATING PERFORMANCE
Ta
SIZE
GRANDEZZE
-7 / -8
(C)
DB
kWt
kWe

kWt

kWe

kWt

kWe

kWt

kWe

kWt

kWe

kWt

kWe

10

8.8

1.5

9.3

1.5

10.4

1.6

10.8

1.7

12.0

1.8

13.2

2.0

15

8.8

1.6

9.2

1.6

10.2

1.8

10.7

1.8

12.0

2.0

13.4

2.2

18

8.8

1.7

9.1

1.7

10.2

1.9

10.7

1.9

12.0

2.1

13.4

2.3

20

8.8

1.7

9.2

1.8

10.2

1.9

10.7

2.0

12.0

2.2

13.5

2.4

22

8.8

1.8

9.2

1.8

10.2

1.9

10.7

2.0

12.0

2.2

13.5

2.4

25

8.9

1.9

9.3

1.9

10.4

2.1

10.8

2.2

12.1

2.4

13.6

2.6

10

11.1

2.0

11.7

2.1

13.1

2.2

13.7

2.3

15.1

2.5

16.5

2.7

15

11.3

2.2

11.8

2.2

13.2

2.4

13.8

2.5

15.2

2.7

16.6

3.0

18

11.4

2.3

11.9

2.3

13.3

2.5

13.9

2.6

15.3

2.9

16.7

3.1

20

11.4

2.3

12.0

2.4

13.4

2.6

13.9

2.7

15.3

3.0

16.7

3.3

22

11.5

2.4

12.0

2.5

13.4

2.7

13.9

2.8

15.3

3.0

16.7

3.3

25

11.6

2.6

12.2

2.6

13.5

2.9

14.1

3.0

15.4

3.3

16.8

3.6

10

17.7

2.9

18.5

3.0

20.9

3.3

23.6

3.6

15

15.1

2.7

15.8

2.8

17.7

3.1

18.6

3.2

20.7

3.5

23.1

3.9

18

15.1

2.9

15.8

3.0

17.7

3.3

18.6

3.4

20.7

3.7

23.0

4.1

20

15.1

3.0

15.8

3.1

17.8

3.4

18.6

3.5

20.7

3.8

23.0

4.2

22

15.1

3.0

15.8

3.1

17.8

3.4

18.6

3.5

20.7

3.9

23.0

4.3

25

15.1

3.2

15.8

3.3

17.7

3.6

18.6

3.8

20.8

4.2

23.2

4.6

10

19.9

3.2

20.7

3.3

23.4

3.7

26.7

4.2

15

17.4

3.1

18.1

3.2

20.0

3.5

20.9

3.6

23.2

4.0

25.8

4.5

18

17.3

3.2

18.0

3.4

20.1

3.7

20.9

3.8

23.2

4.2

25.6

4.7

20

17.2

3.3

18.0

3.5

20.1

3.8

21.0

4.0

23.2

4.4

25.6

4.8

22

17.2

3.4

18.0

3.5

20.1

3.9

21.0

4.0

23.2

4.4

25.6

4.9

25

17.3

3.6

18.1

3.8

20.2

4.1

21.0

4.3

23.4

4.8

25.9

5.3

10

25.1

4.1

26.4

4.2

29.6

4.6

33.0

5.1

15

21.3

4.0

22.4

4.1

25.3

4.4

26.5

4.6

29.6

5.0

32.8

5.5

18

21.4

4.2

22.5

4.3

25.3

4.7

26.5

4.8

29.6

5.3

32.8

5.8

20

21.6

4.3

22.6

4.4

25.4

4.8

26.6

5.0

29.6

5.5

32.7

6.0

22

21.6

4.3

22.7

4.5

25.4

4.9

26.6

5.1

29.6

5.5

32.7

6.1

25

21.8

4.6

22.8

4.8

25.6

5.2

26.7

5.4

29.6

5.9

32.6

6.5

10

29.0

4.9

30.2

5.0

33.6

5.5

37.5

6.0

15

25.0

4.7

26.1

4.9

29.1

5.3

30.4

5.5

33.8

6.0

37.5

6.6

18

25.1

5.0

26.2

5.1

29.2

5.5

30.5

5.7

33.8

6.3

37.4

6.9

20

25.2

5.1

26.3

5.3

29.3

5.7

30.6

5.9

33.9

6.5

37.4

7.1

22

25.3

5.2

26.4

5.4

29.4

5.8

30.6

6.0

33.9

6.6

37.4

7.3

25

25.7

5.6

26.7

5.7

29.6

6.3

30.8

6.5

34.0

7.1

37.4

7.8

10

37.2

6.0

39.2

6.2

44.0

6.8

48.5

7.4

15

31.6

5.8

33.3

6.0

37.7

6.5

39.5

6.7

44.0

7.3

48.5

8.0

18

32.2

6.1

33.8

6.3

37.9

6.8

39.6

7.0

44.0

7.7

48.5

8.4

20

32.4

6.2

34.0

6.4

38.0

7.0

39.7

7.2

44.0

7.9

48.5

8.6

22

32.4

6.3

34.0

6.5

38.1

7.1

39.8

7.4

44.0

8.0

48.5

8.7

25

32.2

6.7

33.9

6.9

38.1

7.5

39.8

7.8

44.1

8.5

48.5

9.3

10

43.1

7.2

45.3

7.4

50.5

8.1

55.8

8.7

15

36.9

7.0

38.5

7.1

43.0

7.7

45.0

8.0

50.4

8.7

56.5

9.5

18

37.4

7.3

38.9

7.5

43.1

8.1

45.1

8.3

50.4

9.1

56.6

10.0

20

37.7

7.5

39.1

7.7

43.3

8.3

45.2

8.6

50.5

9.4

56.6

10.3

22

37.8

7.6

39.2

7.8

43.4

8.4

45.3

8.7

50.5

9.5

56.5

10.5

25

38.0

8.1

39.6

8.3

44.0

9.0

45.9

9.3

50.8

10.2

56.1

11.2

41

51

61

71

91

101

131

151

TEMPERATURA
ARIA ESTERNA
(D.B./W.B.) C
EXTERNAL AIR TEMPERATURE
C D.B.
-5 / -6

0 / -1

Performance refers to operation with 30% of exhaust air (configuration CCK)


Ta = Indoor air temperature D.B/
D.B. = dry bulb
W.B. = wet bulb

2/1

7/6

12 / 11

kWt = Supplied heating capacity in kW with unfrozen coils


kWe = Compressor power input in kW
All cooling capacities do not take into account the heat generated by fan motors

21

BT09N004GB-00

SMARTPACK CKN-XHE

VERSION: CONSTANT POWER UNIT (Clivet abbreviation SHC)


AIR FLOW: HIGH
SIZE
Air flow
Air flow
Max outside static pressure

l/s
m3/h
Pa

41

51

61

71

91

101

131

151

733
2640
520

861
3100
410

1133
4080
400

1278
4600
310

1733
6240
680

1944
7000
580

2667
9600
310

2917
10500
340

COOLING PERFORMANCE
GRANDEZZE
SIZE

41

51

61

71

91

101

131

151

TEMPERATURA
ESTERNAD.B.
C
TEMPERATURA
ARIAARIA
ESTERNAC
EXTERNAL
AIR
TEMPERATURE
C D.B.

Ta
(C)
DB/WB

kWf

kWe

kWs

kWf

kWe

kWs

kWf

kWe

kWs

kWf

kWe

kWs

kWf

kWe

kWs

kWf

kWe

kWs

18 / 13

11.6

1.9

9.6

11.7

2.1

9.3

11.7

2.4

9.1

11.8

2.6

8.8

11.9

2.9

8.5

11.9

3.1

8.3

20 / 14

11.8

1.9

10.4

11.9

2.1

10.1

11.9

2.4

9.9

12.0

2.6

9.6

12.0

2.9

9.3

12.1

3.2

9.1

24 / 17

12.6

2.0

11.1

12.5

2.2

10.9

12.5

2.4

10.6

12.6

2.7

10.4

12.6

3.0

10.1

12.6

3.2

9.9

26 / 18

12.8

2.0

11.9

12.8

2.2

11.7

12.8

2.5

11.4

12.8

2.7

11.2

12.8

3.0

10.9

27 / 19

13.0

2.0

11.8

13.0

2.3

11.6

13.0

2.5

11.4

13.0

2.8

11.1

28 / 20

13.3

2.0

11.7

13.2

2.3

11.5

13.2

2.5

11.3

13.2

2.8

11.1

18 / 13

14.1

2.7

11.2

14.2

3.0

10.8

14.3

3.4

10.5

14.4

3.7

10.1

14.5

4.1

9.7

14.5

4.4

9.4

25

20

30

35

40

44

20 / 14

14.4

2.7

12.2

14.5

3.1

11.9

14.5

3.4

11.5

14.6

3.8

11.1

14.7

4.1

10.8

14.7

4.4

10.5

24 / 17

15.2

2.8

13.1

15.2

3.2

12.8

15.2

3.5

12.5

15.3

3.9

12.1

15.3

4.3

11.8

15.4

4.6

11.6

26 / 18

15.5

2.9

14.0

15.5

3.2

13.7

15.5

3.6

13.3

15.5

3.9

13.0

15.6

4.3

12.7

15.7

4.6

12.5

27 / 19

15.8

3.0

13.9

15.7

3.3

13.6

15.7

3.6

13.2

15.8

4.0

12.9

15.9

4.4

12.6

16.0

4.7

12.4

28 / 20

16.1

3.0

13.7

16.0

3.3

13.4

16.0

3.7

13.1

16.1

4.0

12.8

18 / 13

19.4

3.2

16.1

19.6

3.6

15.6

19.8

4.0

15.0

19.9

4.4

14.5

20.0

4.9

14.0

20.1

5.3

13.6

20 / 14

19.8

3.3

17.3

20.0

3.6

16.8

20.1

4.0

16.4

20.2

4.4

15.9

20.3

4.9

15.5

20.4

5.3

15.1

24 / 17

21.1

3.4

18.1

21.1

3.7

17.8

21.1

4.1

17.5

21.1

4.6

17.2

21.2

5.0

16.8

21.2

5.4

16.6

26 / 18

21.4

3.4

19.2

21.4

3.8

18.9

21.5

4.2

18.6

21.5

4.6

18.3

21.5

5.1

17.9

21.5

5.5

17.7

27 / 19

21.8

3.5

18.8

21.8

3.8

18.5

21.8

4.2

18.2

21.8

4.7

17.9

21.8

5.1

17.5

21.8

5.5

17.3

28 / 20

22.1

3.5

18.3

22.2

3.9

18.0

22.2

4.3

17.6

22.2

4.7

17.3

18 / 13

21.5

3.8

17.3

21.6

4.3

16.7

21.7

4.7

16.2

21.9

5.3

15.6

22.2

5.8

15.1

22.5

6.3

14.7

20 / 14

21.9

3.8

18.6

22.1

4.3

18.1

22.2

4.8

17.5

22.4

5.3

17.0

22.6

5.9

16.4

22.8

6.3

16.0

24 / 17

23.2

4.0

19.1

23.4

4.4

18.6

23.6

4.9

18.1

23.7

5.5

17.6

23.7

6.0

17.1

23.7

6.5

16.7

26 / 18

23.7

4.0

20.2

23.8

4.5

19.7

23.9

5.0

19.2

24.0

5.5

18.8

24.0

6.1

18.3

24.0

6.6

18.0

27 / 19

24.2

4.1

20.4

24.2

4.6

20.0

24.3

5.1

19.6

24.3

5.6

19.2

24.3

6.1

18.7

24.3

6.6

18.4

28 / 20

24.7

4.2

21.0

24.6

4.6

20.7

24.6

5.1

20.3

24.6

5.6

19.9

24.6

6.2

19.6

24.6

6.7

19.3

18 / 13

27.4

4.8

22.5

27.6

5.3

21.9

27.9

5.8

21.4

28.2

6.4

20.9

28.6

7.1

20.4

29.0

7.6

20.0

20 / 14

28.0

4.8

24.2

28.1

5.3

23.7

28.3

5.9

23.2

28.6

6.5

22.7

28.9

7.2

22.2

29.3

7.7

21.8

24 / 17

29.7

5.0

25.7

29.6

5.5

25.2

29.6

6.1

24.7

29.8

6.7

24.1

30.2

7.4

23.6

30.6

8.0

23.2

26 / 18

30.3

5.1

27.3

30.2

5.6

26.8

30.2

6.2

26.2

30.3

6.8

25.6

30.7

7.5

25.0

31.0

8.1

24.6

27 / 19

30.8

5.1

27.0

30.7

5.6

26.3

30.8

6.2

25.7

30.9

6.9

25.1

31.2

7.6

24.4

31.5

8.2

23.9

28 / 20

31.4

5.2

26.4

31.3

5.7

25.7

31.4

6.3

25.0

31.5

6.9

24.3

31.8

7.6

23.6

32.0

8.3

23.0

18 / 13

31.1

5.7

25.2

31.3

6.3

24.3

31.5

7.0

23.5

31.6

7.8

22.6

31.7

8.6

21.7

31.7

9.2

21.0

20 / 14

31.7

5.8

26.9

31.8

6.4

26.2

31.9

7.1

25.4

32.1

7.8

24.7

32.2

8.6

23.9

32.2

9.3

23.4

24 / 17

33.4

6.0

27.9

33.4

6.7

27.3

33.5

7.4

26.7

33.5

8.1

26.1

33.5

8.9

25.5

33.6

9.5

25.0

26 / 18

34.0

6.1

29.6

34.0

6.7

29.0

34.0

7.4

28.4

34.0

8.2

27.7

34.0

9.0

27.1

34.0

9.6

26.6

27 / 19

34.7

6.2

29.7

34.6

6.8

29.0

34.6

7.5

28.3

34.5

8.3

27.6

34.4

9.1

26.8

34.3

9.8

26.3

28 / 20

35.3

6.2

30.0

35.3

6.9

29.1

35.2

7.6

28.3

35.0

8.3

27.5

34.8

9.2

26.6

34.6

9.9

26.0

18 / 13

40.7

7.1

33.4

41.0

7.8

32.3

41.4

8.6

31.3

42.0

9.4

30.3

42.7

10.3

29.3

43.3

11.1

28.4

20 / 14

41.6

7.1

35.6

41.8

7.9

34.7

42.2

8.7

33.8

42.7

9.5

32.8

43.3

10.4

31.9

44.0

11.2

31.2

24 / 17

44.1

7.4

38.6

44.2

8.1

37.9

44.4

8.9

37.1

44.8

9.8

36.4

45.3

10.8

35.7

45.7

11.6

35.1

26 / 18

44.8

7.5

41.0

45.0

8.2

40.3

45.3

9.0

39.6

45.5

9.9

38.9

45.9

10.9

38.2

46.2

11.7

37.6

27 / 19

45.5

7.6

40.2

45.8

8.3

39.5

46.1

9.1

38.8

46.3

10.0

38.1

46.5

11.0

37.4

46.6

11.9

36.8

28 / 20

46.2

7.7

38.8

46.7

8.4

38.0

46.9

9.2

37.3

47.1

10.1

36.6

47.1

11.1

35.8

18 / 13

46.0

8.4

36.6

46.5

9.3

36.0

47.1

10.2

35.4

47.7

11.3

34.8

48.3

12.4

34.1

48.9

13.4

33.6

20 / 14

46.7

8.5

39.7

47.4

9.4

38.8

48.0

10.3

37.9

48.6

11.4

37.0

49.1

12.5

36.1

49.5

13.5

35.4

24 / 17

49.5

8.8

42.9

50.3

9.7

41.7

50.8

10.6

40.5

51.2

11.7

39.3

51.4

12.8

38.2

51.4

13.8

37.2

26 / 18

50.7

8.9

45.0

51.3

9.8

43.9

51.7

10.7

42.8

52.0

11.8

41.7

52.1

12.9

40.6

52.1

13.9

39.7

27 / 19

51.9

9.0

43.8

52.3

9.9

42.9

52.6

10.8

41.9

52.8

11.9

41.0

52.8

13.0

40.0

52.7

14.0

39.3

28 / 20

53.3

9.1

41.9

53.4

9.9

41.2

53.4

10.9

40.5

53.5

12.0

39.8

53.5

13.1

39.1

53.5

14.1

38.6

Performance refers to operation with 30% of exhaust air (configuration CCK)


Ta = Indoor air temperature D.B/W.B
D.B. = dry bulb
W.B. = wet bulb
kWf = Cooling capacity in kW

BT09N004GB-00

kWe = Compressor power input in kW


kWs = sensible cooling capacity (kW)
All cooling capacities do not take into account the heat generated by fan motors

22

SMARTPACK CKN-XHE

VERSION: CONSTANT POWER UNIT (Clivet abbreviation SHC)


INTEGRATED HEATING CAPACITIES
External exchanger inlet temperature C (D.B./W.B.)
Heating capacity multiplication coefficient

-5 / -5.4
0,89

0 / -0.6
0,88

5 / 3.9
0,94

ALTRI
1

The integrated heating capacity represents the real heating capacity, including the effect of possible defrosting cycles.
To obtain the integrated heating capacity multiply the heating performance value in kWt ( shown in the heating performance tables) by the coefficients indicated in the table = at page 19
D.B. = DRY BULB
W.B. = WET BULB
ATTENTION! In prolonged heat pump operating mode with negative outdoor temperatures, it is important to remove the water produced from t he defrosting cycle to prevent ice from
accumulating near the unit's base. Pay attention so this does not represent a hazard to people or property.

AIR FLOW: HIGH


SIZE
Air flow
Air flow
Max outside static pressure

l/s
m3/h
Pa

HEATING PERFORMANCE
Ta
GRANDEZZE
SIZE
(C)
DB
kWt

41

51

61

71

91

101

131

151

41

51

61

71

91

101

131

151

733
2640
520

861
3100
410

1133
4080
400

1278
4600
310

1733
6240
680

1944
7000
580

2667
9600
310

2917
10500
340

TEMPERATURA
ARIA ESTERNA
C D.B./W.B.
EXTERNAL AIR TEMPERATURE
C D.B.
-7 / -8

-5 / -6

0 / -1

2/1

7/6

12 / 11

kWe

kWt

kWe

kWt

kWe

kWt

kWe

kWt

kWe

kWt

kWe

10

10.6

1.5

11.1

1.5

12.3

1.6

13.5

1.7

15

9.1

1.5

9.5

1.5

10.7

1.6

11.2

1.7

12.3

1.8

13.5

1.9

18

9.2

1.6

9.7

1.6

10.7

1.7

11.2

1.7

12.4

1.9

13.6

2.0

20

9.3

1.6

9.7

1.6

10.8

1.7

11.2

1.8

12.4

1.9

13.6

2.1

22

9.4

1.6

9.8

1.7

10.8

1.8

11.3

1.8

12.4

2.0

13.6

2.1

25

9.5

1.7

9.9

1.8

10.9

1.9

11.4

2.0

12.5

2.1

13.7

2.3

10

11.6

2.0

13.2

2.1

13.9

2.1

15.4

2.2

16.9

2.4

15

11.6

2.1

12.0

2.1

13.3

2.2

13.9

2.3

15.4

2.4

17.0

2.7

18

11.8

2.2

12.3

2.2

13.5

2.3

14.0

2.4

15.5

2.6

17.1

2.8

20

12.0

2.2

12.4

2.3

13.6

2.4

14.1

2.5

15.5

2.7

17.1

2.9

22

12.0

2.2

12.4

2.3

13.6

2.5

14.2

2.5

15.6

2.7

17.2

3.0

25

12.2

2.4

12.7

2.5

13.9

2.6

14.5

2.7

15.9

3.0

17.3

3.2

10

15.4

2.7

17.0

2.9

17.7

3.0

19.8

3.3

22.2

3.7

15

15.0

2.9

15.5

3.0

17.2

3.2

17.9

3.3

19.9

3.6

22.1

4.0

18

15.0

3.0

15.6

3.1

17.3

3.4

18.0

3.5

20.0

3.8

22.1

4.2

20

15.1

3.1

15.7

3.2

17.4

3.5

18.1

3.6

20.0

4.0

22.1

4.4

22

15.1

3.1

15.7

3.3

17.4

3.5

18.1

3.7

20.0

4.0

22.1

4.4

25

15.3

3.4

15.9

3.5

17.5

3.8

18.2

3.9

20.1

4.3

22.1

4.7

10

20.8

3.1

23.4

3.4

25.8

3.7

15

18.0

3.0

20.1

3.2

21.0

3.3

23.5

3.7

26.1

4.0

18

17.7

3.1

18.4

3.1

20.3

3.4

21.2

3.5

23.5

3.9

26.2

4.3

20

17.9

3.2

18.5

3.3

20.4

3.5

21.3

3.7

23.6

4.0

26.3

4.4

22

17.9

3.2

18.6

3.3

20.5

3.6

21.3

3.7

23.7

4.1

26.3

4.5

25

17.9

3.4

18.6

3.5

20.7

3.9

21.5

4.0

23.8

4.4

26.4

4.8

10

27.3

3.9

30.4

4.2

33.3

4.6

15

25.6

4.1

26.7

4.2

29.8

4.5

33.4

5.0

18

22.6

4.0

23.3

4.1

25.6

4.3

26.7

4.4

29.8

4.8

33.4

5.2

20

22.7

4.1

23.5

4.2

25.8

4.4

26.9

4.5

29.9

4.9

33.4

5.4

22

22.7

4.1

23.5

4.2

25.9

4.5

27.0

4.6

30.0

5.0

33.5

5.5

25

22.6

4.3

23.7

4.5

26.6

4.8

27.8

5.0

30.7

5.4

33.5

5.8

10

29.7

4.5

30.9

4.6

34.2

5.0

37.8

5.4

15

26.0

4.5

26.8

4.6

29.3

4.8

30.5

5.0

33.8

5.4

37.8

5.9

18

26.1

4.7

26.9

4.8

29.4

5.1

30.6

5.2

33.9

5.7

37.9

6.2

20

26.3

4.8

27.1

4.9

29.7

5.3

30.8

5.4

34.1

5.9

38.0

6.4

22

26.5

4.9

27.4

5.1

30.0

5.5

31.2

5.6

34.4

6.1

38.0

6.7

25

26.8

5.2

27.9

5.4

30.8

5.8

32.0

6.0

35.1

6.5

38.2

7.0

10

43.6

6.2

48.8

6.7

15

37.6

6.0

39.3

6.2

43.8

6.7

49.0

7.2

18

33.4

5.8

34.6

5.9

38.0

6.3

39.6

6.5

44.0

7.0

49.1

7.6

20

33.8

5.9

34.9

6.1

38.3

6.5

39.8

6.7

44.1

7.2

49.1

7.8

22

33.9

6.0

35.1

6.2

38.4

6.6

40.0

6.8

44.2

7.3

49.2

7.9

25

34.3

6.4

35.5

6.5

38.9

7.0

40.4

7.2

44.6

7.8

49.3

8.4

10

43.5

6.8

45.8

7.0

51.4

7.6

56.8

8.2

15

39.3

6.8

44.0

7.3

46.0

7.5

51.2

8.1

56.8

8.8

18

38.4

7.0

39.9

7.2

44.3

7.6

46.1

7.9

51.2

8.5

56.9

9.2

20

38.7

7.2

40.2

7.4

44.5

7.9

46.3

8.1

51.3

8.8

57.0

9.5

22

38.8

7.3

40.4

7.5

44.6

8.0

46.4

8.2

51.4

8.9

57.0

9.7

25

38.8

7.7

40.5

7.9

44.9

8.5

46.8

8.8

51.9

9.5

57.3

10.3

Performance refers to operation with 30% of exhaust air (configuration CCK)


Ta = Indoor air temperature D.B/W.B
D.B. = dry bulb
W.B. = wet bulb
kWf = Cooling capacity in kW

kWe = Compressor power input in kW


kWs = sensible cooling capacity (kW)
All cooling capacities do not take into account the heat generated by fan motors

23

BT09N004GB-00

SMARTPACK CKN-XHE

VERSION: VARIABLE POWER UNIT (Clivet abbreviation CHC)


STANDARD AIR FLOW

GENERAL TECHNICAL SPECIFICATIONS SMARTPACK (PRODUCT CKN-XHE)


COOLING
SIZE
Cooling capacity
Sensible capacity
Compressor power input
EER
HEATING
Heating capacity
Compressor power input
COP
COMPRESSOR
Type of compressors
No. of Compressors
Std Capacity steps
Refrigerant circuits
AIR HANDLING SECTION FANS (OUTLET)
Type of fans
Number of fans
Fan diameter
Type of motor
Air flow
Air flow
Installed unit power
Max outside static pressure

41

51

61

71

91

101

131

151

1
1
1
1

kW
kW
kW

12.7
10.4
2.8
4.57

15.5
12
4
3.9

21.4
16.7
4.7
4.58

24
18.2
5.6
4.31

32.3
24.4
8.5
3.81

36.7
27.4
10.1
3.62

47.6
36.4
11.3
4.2

54.3
41.4
13.3
4.08

2
2
2

kW
kW

12.2
2
6.12

15.3
2.8
5.53

20.9
3.6
5.8

23.5
4.1
5.71

33.2
6.4
5.18

38
7.6
5.01

47.2
8.4
5.64

54.7
10
5.46

D-Scroll
1
1
1

D-Scroll
1
1
1

D-Scroll
1
1
1

D-Scroll
1
1
1

Scroll
2
3
1

Scroll
2
3
1

Scroll
2
2
1

Scroll
2
3
1

RAD
1
355
EC
611
2200
0.7
600

RAD
1
355
EC
750
2700
0.7
500

RAD
1
450
EC
944
3400
1.1
460

RAD
1
450
EC
1139
4100
1.1
390

RAD
1
500
EC
1444
5200
2.7
750

RAD
1
500
EC
1778
6400
2.7
660

RAD
1
500
EC
2222
8000
2.7
520

RAD
1
560
EC
2667
9600
3.1
490

kW

RAD
1
280
EC
0.2

RAD
1
280
EC
0.2

RAD
1
355
EC
0.7

RAD
1
355
EC
0.7

RAD
1
355
EC
0.7

RAD
1
450
EC
1.1

RAD
1
450
EC
1.1

RAD
1
450
EC
1.1

Nr
mm
l/s
kW

AX
1
500
1389
0.2

AX
1
500
1389
0.2

AX
1
630
2778
0.8

AX
1
630
2778
0.8

AX
1
630
3472
1.3

AX
1
630
3472
1.3

AX
1
800
5000
2

AX
1
800
6111
2

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

3
Nr
Nr
Nr

4
Nr
mm

FANS (EXHAUST) (ONLY WITH CONFIGURATION CCK)


Type of fans
7
Number of fans
7
Fan diameter
7
Type of motor
7
Installed unit power
7
EXTERNAL AREA FANS
Type of fans
8
Number of fans
Fan diameter
Standard flow rate
Installed unit power
POWER SUPPLY
Standard power supply

l/s
m3/h
kW
Pa

Nr
mm

Performance refers to operation with 30% of exhaust air (configuration CCk)


(1) Indoor air 27C D.B./19C W.B. External exchanger air intake temperature 35C
EER referred only to compressors
(2) Indoor air 20 C D.B. Outdoor air 7 C D.B./6C W.B.
COP referred only to compressors
(3) D-SCROLL = compressor at variable speed; SCROLL = scroll compressor

(4) RAD = radial ventilation


(5) EC Electronic switching motor
(6) Net outside static pressure to win the outlet and intake onboard pressure drops
(7) CCK - Configuration with exhaust air fan and mixing box
(8) AX = axial fans

CONFIGURATION: FULL RE-CIRCULATION (CAK) / RECIRCULATION AND RENEWAL AIR (CBK)

ELECTRICAL DATA
size

41

51

61

71

91

101

131

151

9,8
0,9
1,5
12,7

12,1
1,4
2,2
16,2

14,3
1,4
2,2
18,4

9,8
10,2
2,5
4,3
27,3

9,8
14,3
2,5
4,3
31,4

14,3
14,3
2,3
4,3
35,7

15,2
17,4
4,2
4,9
42,2

64,0
-

75,0
-

101,0
-

64,0
64,0

64,0
101,0

101,0
101,0

95,0
111,0

5,9
0,2
1,0
7,4

7,3
0,8
1,0
9,4

8,3
0,8
1,0
10,4

5,9
6,0
1,3
2,7
16,2

5,9
8,3
1,3
2,7
18,5

8,3
8,3
1,2
2,7
20,8

8,9
9,9
2,0
3,1
24,2

66,9

79,1

105,1

81,1

118,1

122,4

135,8

F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS


F.L.A. - Compressor 1
A
7,5
F.L.A. - Compressor 2
A
F.L.A. - External Single fan
A
0,9
F.L.A. - Single supply air fan
A
1,5
F.L.A. - Total
A
10,4
1
R.A. LOCKED ROTOR AMPERES
L.R.A. - Compressor 1
A
48,0
L.R.A. - Compressor 2
A
F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION
F.L.I. - Compressor 1
kW
4,3
F.L.I. - Compressor 2
kW
F.L.I. - Single External fan
kW
0,2
F.L.I. - Single Supply fan
kW
1,0
F.L.I. - Totale
5,8
2 kW
M.I.C. MAXIMUM INRUSH CURRENT
M.I.C. - Value

50,9

Data referred to standard units.


Power supply: 400/3/50 Hz +/-6%. Voltage unbalance: max 2%
(1) Values not including accessories to obtain the value of F.L.A. including accessories, add
to the total F.L.A. value that of any accessories (see electrical data of accessories)

BT09N004GB-00

(2) Values not including accessories to obtain the value of F.L.I. including accessories, add to
the total F.L.I. value that of any accessories (see electrical data of accessories)

24

SMARTPACK CKN-XHE

VERSION: VARIABLE POWER UNIT (Clivet abbreviation CHC)


CONFIGURATION: RECIRCULATION, RENEWAL AND EXAUST AIR (CCK)

ELECTRICAL DATA
SIZE

41

51

61

71

91

101

131

151

9,8
0,9
1,5
1,3
14,0

12,1
1,4
2,2
1,5
17,7

14,3
1,4
2,2
1,5
19,9

9,8
10,2
2,5
4,3
1,5
28,8

9,8
14,3
2,5
4,3
1,5
32,9

14,3
14,3
2,3
4,3
2,2
37,9

15,2
17,4
4,2
4,9
2,2
44,4

64,0
-

75,0
-

101,0
-

64,0
64,0

64,0
101,0

101,0
101,0

95,0
111,0

5,9
0,2
1,0
0,2
7,6

7,3
0,8
1,0
1,0
10,4

8,3
0,8
1,0
1,0
11,4

5,9
6,0
1,3
2,7
1,0
17,2

5,9
8,3
1,3
2,7
1,0
19,5

8,3
8,3
1,2
2,7
1,0
21,8

8,9
9,9
2,0
3,1
1,0
25,2

68,2

80,6

106,6

82,6

119,6

124,6

138,0

F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS


F.L.A. - Compressor 1
A
7,5
F.L.A. - Compressor 2
A
F.L.A. - Single external fan
A
0,9
F.L.A. - Single supply fan
A
1,5
F.L.A. - Single exhaust fan
A
1,3
F.L.A. - Total
A
11,7
1
L.R.A. LOCKED ROTOR AMPERES
L.R.A. - Compressor 1
A
48,0
L.R.A. - Compressor 2
A
F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION
F.L.I. - Compressor 1
F.L.I. - Compressor 2
F.L.I. - Single esxternal fan
F.L.I. - Single supply fan
F.L.I. - Single exhaust fan
F.L.I. - Total
M.I.C. MAXIMUM INRUSH CURRENT

M.I.C. - Value

kW
kW
kW
kW
kW
kW

4,3
0,2
1,0
0,2
6,0

52,2

Data referred to standard units.


Power supply: 400/3/50 Hz +/-6%. Voltage unbalance: max 2%
(1) Values not including accessories to obtain the value of F.L.A. including accessories, add
to the total F.L.A. value that of any accessories (see electrical data of accessories)

(2) Values not including accessories to obtain the value of F.L.I. including accessories, add to
the total F.L.I. value that of any accessories (see electrical data of accessories)

ELECTRICAL INPUT OF OPTIONAL COMPONENTS


To obtain the electrical input of the unit including accessories, add the standard data in Electrical Data table to those for the selected
accessories.
SIZE

41

51

61

71

91

101

131

151

A
A
A
A
A
A
A
A
A
A
A

6.5
8.7
13.0
3.2
0.1
1

6.5
8.7
13.0
3.2
0.1
1

8.7
13.0
17.3
3.2
0.16
1

8.7
13.0
17.3
3.2
0.16
1

13.0
17.3
26.0
3.2
8.7
8.7
0.2
1

13.0
17.3
26.0
3.2
8.7
8.7
0.2
1

17.3
26.0
34.6
3.2
8.7
8.7
0.32
1

17.3
26.0
34.6
3.2
8.7
8.7
0.32
1

kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW

4.5
6.0
9.0
2.3
0.02
0.2

4.5
6.0
9.0
2.3
0.02
0.2

6.0
9.0
12.0
2.3
0.03
0.2

6.0
9.0
12.0
2.3
0.03
0.2

9.0
12.0
18.0
2.3
6.0
6.0
0.04
0.2

9.0
12.0
18.0
2.3
6.0
6.0
0.04
0.2

12.0
18.0
24.0
2.3
6.0
6.0
0.61
0.2

12.0
18.0
24.0
2.3
6.0
6.0
0.61
0.2

F.L.A. - FULL LOAD CURRENT


F.L.A. EH09 Electric heaters from 4.5 kW
F.L.A. EH10 Electric heaters from 6 kW
F.L.A. EH12 Electric heaters from 9 kW
F.L.A. EH14 Electric heaters from 12 kW
F.L.A. EH17 Electric heaters from 18 kW
F.L.A. EH20 Electric heaters from 24 kW
F.L.A. HSE3 - Electrode boiler steam humidifier from 3 kg/h
F.L.A. HSE5 - Electrode boiler steam humidifier from 5 kg/h
F.L.A. HSE8 - Electrode boiler steam humidifier from 8 kg/h
F.L.A FES - Electronic filters
F.L.A AGQ - Antifreeze device electrical panel
F.L.I. FULL LOAD POWER INPUT
F.L.I. EH09 Electric heaters from 4.5 kW
F.L.I. EH10 Electric heaters from 6 kW
F.L.I. EH12 Electric heaters from 9 kW
F.L.I. EH14 Electric heaters from 12 kW
F.L.I. EH17 Electric heaters from 18 kW
F.L.I. EH20 Electric heaters from 24 kW
F.L.I. HSE3 - Electrode boiler steam humidifier from 3 kg/h
F.L.I. HSE5 - Electrode boiler steam humidifier from 5 kg/h
F.L.I. HSE8 - Electrode boiler steam humidifier from 8 kg/h
F.L.I FES - Electronicfilter
F.L.I AGQ - Antifreeze device electrical panel

SOUND LEVELS
Sound Power Level (dB)
SIZE

Octave band (Hz)

Sound
pressure
level

Sound
power
level

63

125

250

500 1000 2000 4000 8000

dB(A)

dB(A)

41

79

72

78

71

74

70

61

52

57

74

51

81

74

78

73

75

70

62

52

58

75

61

82

78

81

75

75

71

63

56

59

77

71

85

84

83

78

76

72

65

57

60

78

91

87

86

86

80

79

74

70

64

62

81

101

87

88

86

81

78

72

71

65

63

81

131

88

89

87

82

81

75

72

66

64

83

151

89

86

89

85

84

81

73

67

67

86

25

The sound levels are referred to units working at full load in nominal
conditions.
The sound pressure level is referred at a distance of 1 m. from the
ducted unit surface working in free field conditions. External static
pressure 50 Pa.
(STANDARD UNI EN ISO 3744)
Please note that when the unit is installed in conditions other than
nominal test conditions (e.g. near walls or obstacles in general), the
sound levels may undergo substantial variations.

BT09N004GB-00

SMARTPACK CKN-XHE

OPERATING LIMITS (COOLING)


30

THE LIMITS ARE INDICATIVE AND CONSIDERED:


- GENERAL AND NON-SPECIFIC SIZES
- STANDARD AIR FLOW-RATE
- CORRECTLY INSTALLED AND MAINTAINED UNIT
- OPERATION AT FULL LOAD

TM (W.B.)

25

20

TO VERIFY THE UNIT OPERATING LIMITS WITH PERCENTAGES OF OUTDOOR AIR, ALWAYS
CALCULATE THE TEMPERATURE TM OF THE MIXTURE GENERATED AT THE INLET OF THE INTERNAL
EXCHANGER.

15

TM = INLET AIR TEMPERATURE IN THE INTERNAL EXCHANGER


ATTENTION! TEMPERATURE MEASURED WITH A WET BULB
(W.B. = WET BULB)

(1)

(2)

TEXT = INLET AIR TEMPERATURE IN THE EXTERNAL EXCHANGER


ATTENTION! TEMPERATURE MEASURED WITH A DRY BULB
(D.B. = DRY BULB)
1 = STANDARD OPERATING RANGE
2 = OPERATION FIELD OF THE UNIT FITTED WITH THE LOW TEMPERATURE DEVICE

10

5
0

10

15

20

25

30

35

40

45

50

TEXT (D.B.)

WET BULB TEMPERATURE - EXAMPLE

OPERATING LIMITS (HEATING)


30

THE LIMITS ARE INDICATIVE AND CONSIDERED:


- GENERAL AND NON-SPECIFIC SIZES
- STANDARD AIR FLOW-RATE
- CORRECTLY INSTALLED AND MAINTAINED UNIT
- OPERATION AT FULL LOAD

25

TM (D.B.)

20

TO VERIFY THE UNIT OPERATING LIMITS WITH PERCENTAGES OF OUTDOOR AIR, ALWAYS
CALCULATE THE TEMPERATURE TM OF THE MIXTURE GENERATED AT THE INLET OF THE INTERNAL
EXCHANGER.

(1)

15

TO VERIFY THE UNIT OPERATING LIMITS WITH PERCENTAGES OF OUTDOOR AIR, ALWAYS
CALCULATE THE TEMPERATURE TM OF THE MIXTURE GENERATED AT THE INLET OF THE INTERNAL
EXCHANGER.

(2)

10

TM = INLET AIR TEMPERATURE IN THE INTERNAL EXCHANGER


ATTENTION! TEMPERATURE MEASURED WITH A WET BULB
(W.B. = WET BULB)

5
0

TEXT = INLET AIR TEMPERATURE IN THE EXTERNAL EXCHANGER


ATTENTION! TEMPERATURE MEASURED WITH A DRY BULB
(D.B. = DRY BULB)

-5
-15

-10

-5

10

15

20

TEXT (W.B.)

1 = OPERATION AT FULL LOAD


2 = OPERATION FIELD OF THE UNIT ONLY FOR A LIMITED PERIOD OF TIME (MAX 1 HOUR
IN PROLONGED HEAT PUMP OPERATING MODE WITH OUTDOOR AIR TEMPERATURES BELOW 6 C THE
UNIT WILL PERFORM DEFROSTING CYCLES WITH CYCLE INVERSION TO ELIMINATE THE ICE FORMED
ON THE SURFACES OF THE OUTDOOR EXCHANGER. IN THE CASE OF NEGATIVE TEMPERATURES, IT IS
IMPORTANT TO DISCHARGE THE WATER PRODUCED FROM THE DEFROSTING CYCLE TO PREVENT ICE
FROM ACCUMULATING NEAR THE UNIT'S BASE. PAY ATTENTION SO THIS DOES NOT REPRESENT A
HAZARD TO PEOPLE OR PROPERTY.
WITH AN OUTDOOR AIR TEMPERATURE BETWEEN 10C AND 20C INSTALL THE FOLLOWING
OPTIONS: 2-ROW HOT WATER COIL AND ELECTRIC PANEL ANTIFREEZE PROTECTION.

BT09N004GB-00

26

SMARTPACK CKN-XHE

VERSION: VARIABLE POWER UNIT (Clivet abbreviation CHC)


STANDARD AIR FLOW
SIZE
Air flow
Air flow

l/s
m3/h

41

51

61

71

611
2200

750
2700

944
3400

1139
4100

PERFORMANCES IN COOLING
SIZE
GRANDEZZE

TA (C)
DB/WB

22 / 16

24 / 17

41

26 / 18
27 / 19
28 / 20
30 / 22

22 / 16

24 / 17

51

26 / 18
27 / 19
28 /20
30 / 22

22 / 16

24 / 17

61

26 / 18
27 / 19
28 /20
30 / 22

22 / 16

24 / 17

71

26 / 18
27 / 19
28 /20
30 / 22

PERCENTUALE
% OF DI
PARTIAL
CARICO
LOAD
PARZIALE

25
50
75
100
50
75
100
50
75
100
50
75
100
50
75
100
50
75
100
25
50
75
100
25
50
75
100
50
75
100
50
75
100
50
75
100
50
75
100
25
50
75
100
25
50
75
100
50
75
100
50
75
100
50
75
100
50
75
100
25
50
75
100
25
50
75
100
50
75
100
50
75
100
50
75
100
50
75
100

TEMPERATURA
ARIA
ESTERNAC
TEMPERATURA
ARIA ESTERNA
C D.B.
EXTERNAL
AIR TEMPERATURE
C D.B
kWf
4.3
7.3
9.9
12.1
7.5
10.1
12.2
7.6
10.3
12.4
7.8
10.5
12.7
7.9
10.7
13.0
8.2
11.2
13.8
5.4
9.1
12.2
14.6
5.5
9.2
12.4
14.9
9.4
12.6
15.2
9.6
12.9
15.5
9.8
13.2
15.8
10.2
13.6
16.4
7.2
12.2
16.5
20.1
7.4
12.5
16.9
20.5
12.8
17.2
20.9
13.0
17.6
21.3
13.3
18.0
21.8
13.9
18.7
22.7
8.1
13.8
18.5
22.3
8.3
14.1
19.0
22.9
14.4
19.4
23.4
14.7
19.8
24.0
14.9
20.1
24.4
15.6
21.0
25.4

20
kWe kWs
0.5
4.1
1.0
6.6
1.4
7.8
1.9
9.7
1.0
7.0
1.4
8.2
2.0
10.4
1.0
7.2
1.4
8.5
2.0
11.2
1.0
7.3
1.4
8.5
2.0
11.1
1.0
7.3
1.4
8.4
2.0
11.1
1.0
7.2
1.4
8.3
2.0
10.9
0.7
5.2
1.3
7.9
2.0
9.3
2.8
11.7
0.7
5.3
1.4
8.5
2.0
9.8
2.8
12.5
1.4
8.8
2.0
10.2
2.9
13.2
1.4
8.8
2.0
10.1
2.9
13.0
1.4
8.7
2.1
10.0
3.0
12.9
1.4
8.6
2.1
9.9
3.1
12.9
1.0
6.7
1.7
10.6
2.4
12.5
3.3
15.7
1.0
7.0
1.7
11.2
2.4
13.1
3.3
16.8
1.8
11.7
2.5
13.7
3.4
17.9
1.8
11.7
2.5
13.6
3.4
17.8
1.8
11.6
2.5
13.5
3.4
17.7
1.8
11.4
2.6
13.3
3.5
17.1
1.2
7.8
2.0
12.0
2.9
14.1
4.0
17.8
1.2
8.0
2.0
12.7
2.9
14.7
4.0
18.8
2.1
13.3
2.9
15.4
4.0
19.7
2.1
13.2
3.0
15.3
4.0
19.5
2.1
13.2
3.0
15.4
4.1
19.5
2.2
12.9
3.0
15.0
4.2
19.9

EER
8.1
7.6
7.1
6.3
7.8
7.2
6.2
7.9
7.3
6.3
8.0
7.4
6.3
8.1
7.5
6.5
8.4
7.7
6.9
7.3
6.8
6.2
5.2
7.5
6.8
6.2
5.3
6.9
6.3
5.3
7.0
6.3
5.3
7.0
6.4
5.4
7.2
6.4
5.4
6.9
7.1
6.8
6.1
7.1
7.2
6.9
6.1
7.3
7.0
6.2
7.4
7.1
6.3
7.5
7.2
6.3
7.7
7.3
6.5
6.6
6.8
6.5
5.6
6.7
6.9
6.6
5.7
6.9
6.6
5.8
7.0
6.7
5.9
7.1
6.7
6.0
7.2
6.9
6.0

kWf
4.3
7.3
9.9
12.1
7.5
10.1
12.3
7.6
10.3
12.5
7.7
10.5
12.7
7.9
10.7
13.0
8.2
11.1
13.7
5.4
9.1
12.2
14.7
5.6
9.3
12.4
15.0
9.5
12.7
15.3
9.6
12.8
15.5
9.8
13.1
15.7
10.2
13.6
16.1
7.2
12.3
16.6
20.2
7.5
12.5
16.9
20.5
12.8
17.3
20.9
13.0
17.6
21.3
13.3
18.0
21.8
13.8
18.7
22.8
8.1
13.8
18.7
22.3
8.4
14.1
19.1
22.9
14.4
19.4
23.5
14.7
19.8
24.0
15.0
20.2
24.5
15.6
20.9
25.3

25
kWe kWs
0.6
4.1
1.1
6.7
1.6
7.7
2.2
9.4
1.1
7.0
1.6
8.1
2.2
10.2
1.1
7.2
1.6
8.5
2.2
10.9
1.1
7.4
1.6
8.5
2.2
10.9
1.1
7.4
1.6
8.5
2.2
10.8
1.1
7.3
1.6
8.4
2.2
10.6
0.8
5.2
1.5
8.0
2.2
9.3
3.1
11.4
0.8
5.4
1.5
8.5
2.2
9.8
3.2
12.1
1.5
8.9
2.3
10.2
3.2
12.8
1.6
8.9
2.3
10.2
3.3
12.7
1.6
8.9
2.3
10.1
3.3
12.6
1.6
8.8
2.4
10.0
3.4
12.6
1.1
6.8
1.9
10.6
2.7
12.5
3.7
15.3
1.1
7.1
1.9
11.3
2.7
13.1
3.7
16.4
1.9
11.8
2.7
13.8
3.8
17.5
1.9
11.8
2.7
13.7
3.8
17.4
2.0
11.8
2.8
13.6
3.8
17.3
2.0
11.7
2.8
13.5
3.9
16.7
1.3
7.9
2.2
12.1
3.2
14.0
4.4
17.4
1.4
8.1
2.3
12.8
3.2
14.7
4.4
18.4
2.3
13.4
3.2
15.5
4.5
19.3
2.3
13.4
3.3
15.4
4.5
19.1
2.3
13.4
3.3
15.4
4.6
19.0
2.4
13.2
3.4
15.3
4.7
19.5

EER
7.2
6.8
6.3
5.6
6.9
6.4
5.6
7.0
6.5
5.6
7.1
6.5
5.7
7.2
6.7
5.8
7.4
6.9
6.1
6.4
6.1
5.5
4.7
6.6
6.1
5.5
4.7
6.1
5.6
4.7
6.2
5.6
4.8
6.2
5.7
4.8
6.3
5.8
4.8
6.4
6.4
6.2
5.5
6.5
6.5
6.3
5.5
6.6
6.3
5.5
6.7
6.4
5.6
6.8
6.5
5.7
7.0
6.7
5.9
6.1
6.2
5.9
5.0
6.2
6.2
6.0
5.2
6.3
6.0
5.3
6.4
6.1
5.3
6.4
6.1
5.4
6.6
6.2
5.4

kWf
7.3
9.9
12.0
7.5
10.1
12.3
7.6
10.3
12.5
7.7
10.5
12.7
7.9
10.7
13.0
11.0
13.5
5.4
9.1
12.2
14.8
9.3
12.4
15.1
9.5
12.7
15.3
9.6
12.9
15.5
9.8
13.0
15.7
10.1
13.5
16.0
7.2
12.3
16.6
20.3
12.5
16.9
20.6
12.8
17.3
20.9
13.0
17.6
21.3
13.3
17.9
21.7
13.8
18.6
22.7
8.2
13.9
18.8
22.4
14.2
19.1
23.0
14.5
19.4
23.5
14.7
19.8
24.0
15.0
20.2
24.5
15.5
21.0
25.3

kWe
1.2
1.7
2.4
1.2
1.8
2.4
1.2
1.8
2.5
1.2
1.8
2.5
1.2
1.8
2.5
1.8
2.5
0.9
1.7
2.5
3.5
1.7
2.5
3.5
1.7
2.5
3.6
1.7
2.6
3.6
1.8
2.6
3.6
1.8
2.6
3.7
1.2
2.1
3.0
4.1
2.1
3.0
4.2
2.1
3.0
4.2
2.1
3.0
4.2
2.2
3.1
4.3
2.2
3.1
4.3
1.5
2.5
3.5
4.9
2.5
3.6
4.9
2.5
3.6
5.0
2.6
3.6
5.0
2.6
3.7
5.1
2.6
3.7
5.2

30
kWs
6.6
7.6
9.2
7.0
8.0
10.0
7.2
8.5
10.7
7.3
8.5
10.6
7.4
8.4
10.6
8.4
10.3
5.1
7.9
9.2
11.1
8.4
9.7
11.8
8.9
10.1
12.5
8.9
10.1
12.4
8.9
10.1
12.3
8.8
10.0
12.4
6.8
10.5
12.3
14.9
11.2
13.0
16.0
11.8
13.6
17.1
11.8
13.6
17.1
11.8
13.6
16.9
11.8
13.5
16.2
7.8
11.9
13.9
16.9
12.7
14.6
17.9
13.4
15.3
18.8
13.4
15.4
18.6
13.4
15.3
18.6
13.4
15.2
19.1

EER
6.1
5.7
5.0
6.2
5.8
5.0
6.2
5.8
5.1
6.3
5.9
5.1
6.4
6.0
5.2
6.1
5.4
5.7
5.4
4.9
4.2
5.4
4.9
4.3
5.5
5.0
4.3
5.5
5.1
4.3
5.6
5.0
4.3
5.6
5.1
4.4
5.8
5.8
5.6
4.9
5.9
5.7
5.0
6.0
5.7
5.0
6.1
5.8
5.0
6.2
5.9
5.1
6.3
6.0
5.3
5.6
5.6
5.3
4.6
5.7
5.3
4.7
5.7
5.4
4.7
5.8
5.4
4.8
5.8
5.5
4.8
6.0
5.6
4.9

kWf
7.3
9.9
12.1
7.4
10.1
12.2
7.6
10.3
12.4
10.5
12.7
10.6
12.9
13.4
9.1
12.2
14.9
9.3
12.5
15.1
9.4
12.6
15.3
9.6
12.9
15.5
13.1
15.7
13.4
16.1
12.3
16.7
20.4
12.6
17.0
20.7
12.8
17.4
21.0
13.0
17.7
21.4
17.9
21.7
18.5
22.6
14.0
18.9
22.8
14.2
19.2
23.2
14.5
19.5
23.6
14.7
19.8
24.0
15.0
20.2
24.4
20.9
25.2

kWe
1.3
1.9
2.7
1.3
2.0
2.7
1.4
2.0
2.7
2.0
2.8
2.0
2.8
2.8
1.9
2.8
3.9
1.9
2.8
3.9
1.9
2.8
3.9
1.9
2.8
4.0
2.8
4.0
2.9
4.0
2.3
3.3
4.5
2.3
3.3
4.6
2.4
3.4
4.6
2.4
3.4
4.7
3.4
4.7
3.4
4.7
2.8
3.9
5.4
2.8
4.0
5.5
2.8
4.0
5.5
2.8
4.0
5.6
2.8
4.1
5.6
4.1
5.7

35
kWs
6.4
7.4
8.9
6.9
7.8
9.7
7.2
8.3
10.5
8.3
10.4
8.4
10.3
10.0
7.7
8.9
10.7
8.2
9.4
11.5
8.7
9.9
12.1
8.8
9.9
12.0
9.9
12.0
9.9
12.1
10.2
11.9
14.5
10.9
12.5
15.6
11.6
13.2
16.8
11.6
13.2
16.7
13.3
16.5
13.3
15.8
11.6
13.5
16.4
12.4
14.3
17.4
13.2
15.1
18.3
13.3
15.1
18.2
13.3
15.1
18.1
15.1
18.7

EER
5.5
5.1
4.5
5.5
5.2
4.5
5.6
5.3
4.5
5.3
4.6
5.3
4.6
4.8
4.9
4.4
3.8
4.9
4.5
3.9
4.9
4.5
3.9
4.9
4.6
3.9
4.6
3.9
4.6
4.0
5.3
5.1
4.5
5.4
5.1
4.5
5.4
5.2
4.5
5.5
5.2
4.6
5.3
4.6
5.4
4.8
5.1
4.8
4.2
5.1
4.8
4.2
5.2
4.9
4.3
5.2
4.9
4.3
5.3
5.0
4.3
5.1
4.4

kWf
10.0
12.1
10.1
12.2
10.3
12.3
9.2
12.3
14.9
12.5
15.1
12.6
15.2
12.8
15.4
13.0
15.7
16.3
12.4
16.8
20.5
12.5
17.0
20.8
17.3
21.1
17.5
21.5
17.8
21.7
22.3
14.1
18.9
23.3
14.3
19.3
23.4
19.6
23.6
19.9
23.9
20.2
24.2
25.1

kWe
2.1
3.0
2.2
3.0
2.2
3.3
2.1
3.0
4.2
3.0
4.3
3.1
4.3
3.1
4.3
3.1
4.4
4.4
2.6
3.6
5.0
2.6
3.7
5.0
3.7
5.1
3.7
5.1
3.7
5.2
5.2
3.0
4.3
5.9
3.1
4.4
6.0
4.4
6.1
4.4
6.2
4.5
6.2
6.3

40
kWs
7.0
8.6
7.5
9.5
8.0
10.0
7.3
8.4
10.4
9.0
11.1
9.5
11.8
9.6
11.7
9.6
11.7
11.9
9.7
11.2
14.1
10.5
12.1
15.3
12.7
16.4
12.9
16.3
12.9
16.2
15.3
11.1
12.9
15.9
12.0
13.7
17.0
14.5
17.9
14.6
17.7
14.6
17.7
18.3

EER
4.7
4.0
4.7
4.0
4.7
3.7
4.4
4.1
3.5
4.1
3.5
4.1
3.5
4.1
3.6
4.2
3.6
3.7
4.8
4.6
4.1
4.8
4.6
4.1
4.7
4.2
4.7
4.2
4.8
4.2
4.3
4.6
4.4
3.9
4.6
4.4
3.9
4.4
3.9
4.5
3.9
4.5
3.9
4.0

PARTIAL LOAD PERCENTAGE = SUPPLIED POWER / FULL LOAD CAPACITY, REFERRED TO THE SAME CONDITIONS
Performance refers to operation with 30% of exhaust air (configuration CCK)
Ta = Indoor air temperature D.B/W.B
D.B. = Dry bulb, W.B. = Wet bulb
EER referred to only compressors

kWf = Cooling capacity in kW


kWe = Compressor power input in kW
kWs = sensible cooling capacity (kW)
All cooling capacities do not take into account the heat generated by fan motors

27

BT09N004GB-00

SMARTPACK CKN-XHE

VERSION: VARIABLE POWER UNIT (Clivet abbreviation CHC)


STANDARD AIR FLOW
SIZE
Air flow
Air flow

l/s
m3/h

91

101

131

151

1444
5200

1778
6400

2222
8000

2667
9600

PERFORMANCES IN COOLING
SIZE
GRANDEZZE

TA (C)
DB/WB
22 / 16

24 / 17

26 / 18

91
27 / 19

28 / 20

30 / 22

22 / 16

24 / 17

26 / 18

101
27 / 19

28 / 20

30 / 22

22 / 16

24 / 17

26 / 18

131
27 / 19

28 / 20

30 / 22

22 / 16

24 / 17

26 / 18

151
27 / 19

28 / 20

30 / 22

GRADINI
POWER
STEPS
DI
POTENZA

C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2

TEMPERATURA
ARIA ESTERNA
C
EXTERNAL
AIR TEMPERATURE
C D.B
kWf
18.0
19.8
30.6
18.4
20.2
31.1
18.8
20.7
31.7
19.2
21.1
32.3
19.5
21.6
33.0
20.4
22.4
34.5
18.3
24.9
34.5
18.7
25.4
35.3
19.2
25.8
36.1
19.5
26.5
36.9
19.9
27.0
37.5
20.6
28.0
38.5
27.3
27.3
44.5
27.8
27.8
45.6
28.4
28.4
46.6
29.0
29.0
47.6
29.7
29.7
49.6
30.8
30.8
50.6
29.6
33.4
51.1
30.2
34.0
52.1
30.8
34.7
53.2
31.4
35.4
54.3
32.0
36.1
55.4
33.4
37.5
57.7

20
kWe kWs
2.2
15.5
2.8
16.3
5.9
23.7
2.3
16.4
2.8
17.1
6.0
25.1
2.3
17.3
2.8
18.0
6.0
26.5
2.3
17.2
2.9
17.9
6.1
26.4
2.3
17.0
2.9
17.8
6.2
26.3
2.3
16.8
2.9
17.5
6.3
25.9
2.3
16.9
3.7
19.7
7.1
27.0
2.3
17.7
3.8
20.6
7.2
28.5
2.3
18.3
3.8
21.9
7.3
30.0
2.3
18.5
3.9
21.5
7.4
29.8
2.3
18.4
3.9
21.3
7.4
29.6
2.4
18.3
4.0
21.1
7.6
29.9
3.5
23.7
3.5
23.7
8.0
35.2
3.6
25.1
3.6
25.1
8.1
37.3
3.6
26.3
3.6
26.3
8.2
39.4
3.6
26.2
3.6
26.2
8.3
39.1
3.7
25.8
3.7
25.8
8.5
36.4
3.7
25.6
3.7
25.6
8.6
38.9
3.8
26.2
4.4
27.8
9.5
40.0
3.9
27.7
4.5
29.4
9.6
42.4
3.9
29.0
4.5
30.9
9.7
44.8
3.9
28.9
4.6
30.7
9.8
44.5
4.0
28.8
4.6
30.5
9.9
44.4
4.1
28.2
4.7
30.0
10.1 44.3

EER
8.0
7.1
5.2
8.1
7.2
5.2
8.3
7.3
5.2
8.3
7.4
5.3
8.4
7.5
5.4
8.8
7.7
5.5
8.1
6.7
4.9
8.2
6.7
4.9
8.3
6.7
5.0
8.4
6.8
5.0
8.5
6.9
5.0
8.6
7.0
5.1
7.8
7.8
5.6
7.8
7.8
5.6
7.9
7.9
5.7
8.0
8.0
5.7
8.1
8.1
5.8
8.2
8.2
5.9
7.7
7.5
5.4
7.8
7.6
5.4
7.9
7.6
5.5
8.0
7.7
5.5
8.0
7.8
5.6
8.2
8.0
5.7

kWf
18.1
19.9
30.6
18.4
20.3
31.2
18.8
20.6
31.7
19.2
21.1
32.4
19.5
21.5
33.0
20.2
22.4
34.3
18.3
25.0
34.7
18.7
25.4
35.4
19.2
26.0
36.1
19.5
26.4
36.8
19.8
27.0
37.5
20.5
28.1
39.0
27.4
27.4
44.7
27.9
27.9
45.7
28.6
28.6
46.7
29.1
29.1
47.7
29.6
29.6
49.5
30.8
30.8
50.3
29.8
33.4
51.4
30.4
33.9
52.3
31.0
34.6
53.3
31.6
35.2
54.2
32.2
35.9
55.3
33.5
37.3
57.5

Performance refers to operation with 30% of exhaust air (configuration CCK)


Ta = Indoor air temperature D.B/W.B
D.B. = Dry bulb, W.B. = Wet bulb
kWf = Cooling capacity in kW
kWe = Compressor power input in kW

BT09N004GB-00

25
kWe kWs
2.5
15.6
3.1
16.3
6.7
23.0
2.6
16.5
3.1
17.3
6.7
24.4
2.6
17.4
3.1
18.3
6.8
25.9
2.6
17.3
3.2
18.1
6.9
25.8
2.6
17.3
3.2
18.0
6.9
25.6
2.7
17.1
3.2
17.8
7.1
25.3
2.5
16.9
4.1
19.7
8.0
26.2
2.6
17.8
4.2
20.8
8.1
27.8
2.6
18.3
4.3
21.8
8.2
29.2
2.6
18.6
4.3
21.7
8.3
29.0
2.6
18.7
4.3
21.5
8.4
28.9
2.7
18.6
4.4
21.3
8.6
29.1
3.9
23.9
3.9
23.9
8.9
34.2
3.9
25.2
3.9
25.2
9.0
36.4
4.0
26.5
4.0
26.5
9.1
38.5
4.0
26.5
4.0
26.5
9.2
38.2
4.1
26.4
4.1
26.4
9.5
35.6
4.1
26.2
4.1
26.2
9.6
38.1
4.2
26.3
4.9
27.9
10.5 38.9
4.3
28.0
5.0
29.6
10.7 41.4
4.3
29.3
5.0
31.0
10.8 43.8
4.4
29.3
5.1
30.9
10.9 43.5
4.4
29.0
5.1
30.8
11.0 43.3
4.5
28.9
5.2
30.5
11.2 43.0

EER
7.1
6.5
4.6
7.2
6.5
4.6
7.3
6.6
4.7
7.4
6.7
4.7
7.4
6.8
4.8
7.6
7.0
4.8
7.2
6.0
4.4
7.3
6.1
4.4
7.4
6.1
4.4
7.4
6.1
4.5
7.5
6.2
4.5
7.6
6.4
4.6
7.0
7.0
5.0
7.1
7.1
5.1
7.2
7.2
5.1
7.2
7.2
5.2
7.3
7.3
5.2
7.4
7.4
5.3
7.1
6.8
4.9
7.1
6.8
4.9
7.2
6.9
4.9
7.2
7.0
5.0
7.3
7.0
5.0
7.5
7.2
5.1

kWf
18.1
19.9
30.6
18.4
20.3
31.2
18.8
20.6
31.8
19.1
21.0
32.3
19.5
21.4
32.9
20.1
22.2
34.1
18.4
25.0
35.0
18.7
25.5
35.5
19.2
25.9
36.1
19.5
26.4
36.8
19.7
26.9
37.5
20.4
28.0
39.2
27.6
27.6
45.0
28.1
28.1
45.9
28.6
28.6
46.8
29.1
29.1
47.6
29.7
29.7
49.3
30.9
30.9
50.2
30.0
33.3
51.7
30.5
33.9
52.5
31.1
34.5
53.3
31.7
35.1
54.2
32.2
35.7
55.2
33.4
37.0
57.3

kWe
2.9
3.4
7.5
2.9
3.4
7.5
2.9
3.5
7.6
2.9
3.5
7.7
3.0
3.5
7.7
3.0
3.5
7.9
2.8
4.6
8.9
2.9
4.7
9.0
2.9
4.7
9.1
2.9
4.8
9.2
3.0
4.8
9.3
3.0
4.9
9.5
4.3
4.3
10.0
4.4
4.4
10.0
4.4
4.4
10.1
4.4
4.4
10.3
4.5
4.5
10.5
4.6
4.6
10.6
4.7
5.4
11.7
4.7
5.5
11.8
4.8
5.5
11.9
4.8
5.6
12.1
4.8
5.6
12.2
4.9
5.7
12.4

30
kWs
15.4
16.1
22.3
16.4
17.1
23.8
17.3
18.0
25.2
17.3
18.0
25.1
17.3
18.0
25.0
17.2
18.0
24.7
16.7
19.5
25.4
17.7
20.6
27.0
18.2
21.7
28.4
18.5
21.7
28.2
18.7
21.7
28.1
18.8
21.5
28.4
23.5
23.5
33.2
25.1
25.1
35.4
26.5
26.5
37.6
26.5
26.5
37.3
26.5
26.5
34.8
26.3
26.3
37.3
26.2
27.5
37.8
27.7
29.2
40.3
29.3
30.8
42.8
29.4
30.8
42.5
29.5
30.8
42.2
29.4
30.7
41.6

EER
6.3
5.8
4.1
6.4
5.9
4.1
6.5
5.9
4.2
6.5
6.0
4.2
6.6
6.1
4.3
6.7
6.3
4.3
6.4
5.4
3.9
6.5
5.5
4.0
6.6
5.5
4.0
6.6
5.6
4.0
6.7
5.6
4.0
6.8
5.7
4.1
6.4
6.4
4.5
6.4
6.4
4.6
6.5
6.5
4.6
6.6
6.6
4.6
6.6
6.6
4.7
6.8
6.8
4.7
6.4
6.1
4.4
6.5
6.2
4.4
6.5
6.2
4.5
6.6
6.3
4.5
6.6
6.3
4.5
6.8
6.5
4.6

kWf
18.1
20.0
30.7
18.4
20.3
31.2
18.8
20.7
31.7
19.0
21.0
32.3
19.3
21.3
32.8
21.3
33.9
18.4
25.1
35.2
18.7
25.6
35.6
19.1
26.1
36.1
19.4
26.4
36.7
26.9
37.4
27.8
39.1
27.7
27.7
45.3
28.2
28.2
46.0
28.7
28.7
46.8
29.2
29.2
47.6
29.7
29.7
49.2
50.0
30.1
33.4
52.0
30.7
34.0
52.7
31.2
34.5
53.5
31.7
35.1
54.3
32.2
35.6
55.2
33.4
36.9
57.1

kWe
3.2
3.8
8.3
3.2
3.8
8.3
3.3
3.8
8.4
3.3
3.8
8.5
3.3
3.8
8.5
3.8
8.7
3.2
5.1
9.8
3.2
5.1
9.9
3.3
5.2
10.0
3.3
5.3
10.1
5.3
10.2
5.4
10.5
4.8
4.8
11.0
4.8
4.8
11.1
4.9
4.9
11.2
4.9
4.9
11.3
4.9
4.9
11.6
11.7
5.2
6.0
12.9
5.2
6.0
13.1
5.3
6.1
13.2
5.3
6.2
13.3
5.3
6.2
13.4
5.4
6.3
13.7

35
kWs
14.9
15.6
21.7
16.1
16.7
23.1
17.0
17.7
24.5
17.1
17.7
24.4
17.1
17.8
24.3
17.8
24.1
16.2
19.0
24.6
17.4
20.1
26.2
18.2
21.2
27.7
18.5
21.4
27.4
21.4
27.3
21.3
27.6
22.9
22.9
32.2
24.6
24.6
34.5
26.0
26.0
36.7
26.2
26.2
36.4
26.3
26.3
34.0
36.6
25.5
26.7
36.7
27.3
28.5
39.3
28.8
30.3
41.8
29.1
30.4
41.4
29.1
30.4
41.1
29.2
30.3
40.3

EER
5.6
5.3
3.7
5.7
5.4
3.7
5.8
5.4
3.8
5.8
5.5
3.8
5.8
5.5
3.8
5.5
3.9
5.8
4.9
3.6
5.8
5.0
3.6
5.9
5.0
3.6
5.9
5.0
3.6
5.1
3.7
5.2
3.7
5.8
5.8
4.1
5.8
5.8
4.1
5.9
5.9
4.2
5.9
5.9
4.2
6.0
6.0
4.3
4.3
5.8
5.6
4.0
5.9
5.6
4.0
5.9
5.6
4.1
6.0
5.7
4.1
6.0
5.7
4.1
6.2
5.8
4.2

kWf
18.1
19.9
30.8
18.4
20.2
31.2
31.6
32.1
32.6
33.7
18.5
25.4
35.3
18.7
25.7
35.7
26.1
36.1
26.5
36.7
26.9
37.3
27.8
27.8
45.6
28.3
28.3
46.2
46.8
47.5
49.0
49.9
30.2
33.6
52.2
30.7
34.2
52.9
31.1
34.6
53.6
31.6
35.3
54.3
32.1
35.8
55.2
33.1
36.9
56.9

kWe
3.6
4.1
9.1
3.6
4.2
9.2
9.2
9.3
9.3
9.4
3.5
5.6
10.8
3.6
5.6
10.9
5.7
11.0
5.8
11.1
5.8
11.2
5.3
5.3
12.1
5.3
5.3
12.2
12.4
12.5
12.7
12.8
5.7
6.6
14.2
5.7
6.7
14.4
5.8
6.7
14.5
5.8
6.8
14.6
5.8
6.9
14.8
5.9
7.0
15.0

40
kWs
14.1
14.8
21.0
15.3
15.9
22.4
23.8
23.8
23.7
23.5
15.6
18.0
23.9
16.8
19.3
25.4
20.5
26.9
20.6
26.6
20.7
26.5
21.8
21.8
31.2
23.5
23.5
33.5
35.7
35.6
33.2
35.8
24.4
25.4
35.6
26.3
27.3
38.3
28.1
29.3
40.7
28.2
29.3
40.4
28.4
29.5
40.0
28.6
29.7
38.9

kWs = sensible cooling capacity (kW)


C1,C2 indicate the active compresors and then reliable capacity steps
All cooling capacities do not take into account the heat generated by fan motors

28

EER
5.1
4.8
3.4
5.1
4.9
3.4
3.4
3.5
3.5
3.6
5.2
4.5
3.3
5.3
4.6
3.3
4.6
3.3
4.6
3.3
4.6
3.3
5.3
5.3
3.8
5.3
5.3
3.8
3.8
3.8
3.9
3.9
5.3
5.1
3.7
5.4
5.1
3.7
5.4
5.1
3.7
5.4
5.2
3.7
5.5
5.2
3.7
5.6
5.3
3.8

SMARTPACK CKN-XHE

VERSION: VARIABLE POWER UNIT (Clivet abbreviation CHC)


STANDARD AIR FLOW

INTEGRATED HEATING CAPACITIES


External exchanger inlet temperature C (D.B./W.B.)
Heating capacity multiplication coefficient

-5 / -5.4
0,89

0 / -0.6
0,88

5 / 3.9
0,94

ALTRI
1

The integrated heating capacity represents the real heating capacity, including the effect of possible defrosting cycles.
To obtain the integrated heating capacity multiply the heating performance value in kWt ( shown in the heating performance tables) by the coefficients indicated in the table = at page 19
D.B. = DRY BULB W.B. = WET BULB

PERFORMANCES IN HEATING
GRANDEZZE
SIZE

TA (C)
DB
10

15

18

41
20

22

25

10

15

18

51
20

22

25

10

15

18

61
20

22

25

10

15

18

71
20

22

25

PERCENTUALE
% OF DI
CARICO
PARTIAL
LOAD
PARZIALE

50
75
100
50
75
100
25
50
75
100
25
50
75
100
25
50
75
100
25
50
75
100
50
75
100
25
50
75
100
25
50
75
100
25
50
75
100
25
50
75
100
25
50
75
100
75
100
50
75
100
50
75
100
50
75
100
50
75
100
50
75
100
75
100
50
75
100
50
75
100
50
75
100
50
75
100
50
75
100

kWt
7.1
9.1
7.1
9.2
5.1
7.2
9.2
5.1
7.2
9.1
5.2
7.2
9.1
11.2
9.1
11.5
6.7
9.2
11.6
6.7
9.3
11.8
6.8
9.4
11.9
6.9
9.6
12.1
15.3
15.3
15.3
12.2
15.2
17.4
13.9
17.5
14.0
17.7
10.1
14.0
18.0

-7 / -8
kWe
1.1
1.5
1.2
1.6
0.8
1.2
1.6
0.9
1.2
1.7
0.9
1.3
1.8
2.0
1.6
2.1
1.1
1.6
2.2
1.1
1.6
2.3
1.2
1.7
2.3
1.2
1.8
2.5
2.8
2.8
2.9
2.3
3.1
3.1
2.3
3.2
2.4
3.3
1.7
2.5
3.5

COP
6.3
5.9
6.1
5.7
6.1
5.9
5.6
6.0
5.8
5.4
5.7
5.6
5.2
5.7
5.9
5.5
5.9
5.8
5.3
5.9
5.7
5.2
5.8
5.6
5.1
5.7
5.4
4.9
5.5
5.4
5.2
5.4
5.0
5.6
5.9
5.5
5.8
5.3
5.8
5.5
5.1

kWt
9.3
7.4
9.5
7.5
9.5
5.4
7.5
9.5
5.4
7.5
9.5
5.4
7.5
9.5
11.6
9.6
11.9
7.0
9.7
12.0
7.0
9.7
12.2
7.1
9.8
12.3
7.2
9.9
12.5
15.9
16.0
12.7
16.0
12.8
16.0
9.1
12.8
15.9
18.0
14.5
18.1
14.5
18.2
14.6
18.4
10.5
14.7
18.7

-5 / -6
kWe
1.5
1.1
1.6
1.2
1.6
0.9
1.2
1.7
0.9
1.3
1.7
0.9
1.3
1.8
2.0
1.6
2.1
1.1
1.6
2.2
1.2
1.7
2.3
1.2
1.7
2.4
1.2
1.8
2.5
2.7
2.9
2.1
2.9
2.2
3.0
1.6
2.3
3.2
3.0
2.3
3.2
2.4
3.3
2.5
3.4
1.8
2.6
3.6

TEMPERATURA
ARIA ESTERNA (C)
D.B./W.B.
EXTERNAL
AIR TEMPERATURE
C D.B
0 / -1
2/1
COP
kWt
kWe COP
kWt
kWe COP
8.3
1.1
7.4
8.7
1.1
7.6
6.4
10.4
1.5
6.8
10.8
1.6
6.9
6.3
0.8
7.5
6.5
8.3
1.2
6.9
8.7
1.2
7.1
6.0
10.5
1.7
6.3
10.9
1.7
6.4
6.0
0.9
7.0
6.3
0.9
7.1
6.2
8.4
1.3
6.6
8.7
1.3
6.7
5.8
10.5
1.7
6.0
11.0
1.8
6.1
6.3
6.0
0.9
6.8
6.3
0.9
6.9
6.1
8.4
1.3
6.4
8.7
1.3
6.5
5.7
10.6
1.8
5.9
11.0
1.9
5.9
6.1
6.0
0.9
6.6
6.3
0.9
6.7
5.9
8.4
1.3
6.2
8.8
1.4
6.3
5.5
10.6
1.9
5.7
11.0
1.9
5.8
5.9
6.0
1.0
6.3
6.3
1.0
6.4
5.7
8.4
1.4
6.0
8.8
1.5
6.0
5.2
10.6
2.0
5.4
11.1
2.0
5.5
11.0
1.6
7.0
5.8
12.9
2.1
6.2
13.5
2.1
6.3
7.7
1.1
6.8
8.1
1.1
7.0
6.1
10.6
1.6
6.5
11.1
1.7
6.6
5.6
13.1
2.3
5.8
13.6
2.3
5.9
4.5
0.7
6.7
6.1
7.8
1.2
6.6
8.1
1.2
6.8
5.9
10.7
1.7
6.2
11.1
1.8
6.3
5.4
13.2
2.4
5.6
13.8
2.5
5.6
4.3
0.7
6.4
4.5
0.7
6.6
6.1
7.8
1.2
6.5
8.1
1.2
6.6
5.8
10.8
1.8
6.1
11.2
1.8
6.2
5.3
13.3
2.5
5.4
13.8
2.5
5.4
4.3
0.7
6.2
4.5
6.4
6.0
7.9
1.2
6.3
8.2
1.3
6.4
5.7
10.9
1.8
5.9
11.3
1.9
6.0
5.1
13.4
2.6
5.2
13.9
2.6
5.3
4.4
0.7
6.0
4.6
0.7
6.2
5.8
7.9
1.3
6.1
8.2
1.3
6.2
5.5
11.0
1.9
5.7
11.4
2.0
5.7
4.9
13.5
2.7
5.0
14.0
2.8
5.0
17.7
2.7
6.5
18.5
2.8
6.6
14.2
2.1
6.6
14.9
2.2
6.8
5.9
17.8
2.9
6.1
18.6
3.0
6.1
10.7
1.6
6.8
14.2
2.2
6.4
14.9
2.3
6.5
5.6
17.9
3.1
5.8
18.7
3.2
5.9
10.2
1.6
6.5
10.7
1.6
6.6
5.9
14.3
2.3
6.2
14.9
2.4
6.3
5.4
17.9
3.2
5.6
18.7
3.3
5.7
10.2
1.6
6.3
10.7
1.7
6.4
5.8
14.3
2.4
6.0
14.9
2.5
6.1
5.3
17.9
3.3
5.4
18.7
3.4
5.5
5.7
10.3
1.7
6.0
10.7
1.8
6.1
5.5
14.3
2.5
5.7
15.0
2.6
5.8
5.0
17.9
3.4
5.2
18.8
3.6
5.2
20.1
3.1
6.6
20.9
3.2
6.6
16.1
2.4
6.7
16.8
2.5
6.8
5.9
20.1
3.3
6.1
21.0
3.4
6.1
12.2
1.8
6.9
6.2
16.2
2.5
6.4
16.9
2.6
6.5
5.7
20.2
3.5
5.8
21.1
3.6
5.8
11.7
1.8
6.6
12.2
1.8
6.6
6.0
16.2
2.6
6.2
16.9
2.7
6.3
5.5
20.3
3.6
5.6
21.1
3.7
5.6
11.7
1.8
6.4
12.2
1.9
6.4
5.9
16.2
2.7
6.0
16.9
2.8
6.1
5.4
20.4
3.7
5.4
21.3
3.9
5.5
5.9
11.8
1.9
6.1
12.3
2.0
6.2
5.6
16.3
2.8
5.8
17.0
2.9
5.8
5.2
20.6
4.0
5.2
21.4
4.1
5.2

kWt
7.0
9.7
12.2
7.0
9.7
12.2
3.8
7.0
9.7
12.2
3.8
7.0
9.7
12.2
3.9
7.0
9.7
12.3
3.9
7.0
9.7
12.3
8.9
12.1
15.0
5.0
8.9
12.2
15.2
5.0
9.0
12.3
15.2
5.0
9.0
12.3
15.3
5.0
9.0
12.4
15.3
5.1
9.1
12.5
15.4
16.7
20.8
12.0
16.6
20.8
12.0
16.6
20.9
12.0
16.6
20.9
12.0
16.6
20.9
12.0
16.7
21.0
18.7
23.4
13.6
18.7
23.4
13.6
18.8
23.5
13.6
18.8
23.5
13.7
18.8
23.6
13.7
18.9
23.7

7/6
kWe
0.8
1.2
1.7
0.9
1.3
1.8
0.5
0.9
1.4
1.9
0.5
1.0
1.4
2.0
0.5
1.0
1.5
2.1
0.6
1.0
1.6
2.2
1.1
1.6
2.3
0.7
1.2
1.8
2.5
0.7
1.3
1.9
2.7
0.7
1.3
2.0
2.8
0.7
1.3
2.0
2.9
0.8
1.4
2.1
3.0
2.2
3.1
1.6
2.4
3.3
1.7
2.5
3.5
1.7
2.6
3.6
1.8
2.7
3.7
1.9
2.8
3.9
2.5
3.5
1.8
2.7
3.8
1.9
2.8
4.0
2.0
2.9
4.1
2.1
3.0
4.3
2.2
3.2
4.5

COP
8.7
8.1
7.2
8.0
7.4
6.6
7.6
7.6
7.1
6.3
7.4
7.3
6.8
6.1
7.1
7.1
6.6
5.9
6.8
6.7
6.3
5.6
8.0
7.4
6.5
7.7
7.5
6.8
6.0
7.3
7.2
6.6
5.7
7.1
6.9
6.3
5.5
6.9
6.7
6.1
5.3
6.6
6.4
5.8
5.1
7.6
6.8
7.4
7.0
6.3
7.1
6.7
6.0
6.9
6.5
5.8
6.7
6.3
5.6
6.4
6.0
5.4
7.5
6.7
7.4
6.9
6.2
7.1
6.6
5.9
6.9
6.4
5.7
6.6
6.2
5.5
6.3
5.9
5.3

kWt
7.8
10.8
13.7
7.8
10.8
13.6
4.3
7.8
10.8
13.6
4.3
7.8
10.8
13.6
4.3
7.8
10.8
13.6
4.3
7.8
10.8
13.6
9.9
13.5
16.9
5.5
9.9
13.5
16.9
5.5
9.9
13.6
16.9
5.6
10.0
13.6
16.9
5.6
10.0
13.7
17.0
5.6
10.0
13.8
17.0
18.7
23.4
13.5
18.6
23.3
13.4
18.6
23.3
13.4
18.6
23.3
13.4
18.6
23.3
13.4
18.5
23.3
20.8
26.1
15.2
20.9
26.1
15.2
21.0
26.1
15.2
21.0
26.1
15.2
21.0
26.1
15.2
21.0
26.2

12 / 11
kWe COP
0.8
9.3
1.3
8.5
1.8
7.5
0.9
8.5
1.4
7.7
2.0
6.9
0.5
8.3
1.0
8.0
1.5
7.3
2.1
6.5
0.5
8.0
1.0
7.7
1.5
7.1
2.2
6.3
0.6
7.7
1.0
7.4
1.6
6.8
2.2
6.1
0.6
7.3
1.1
7.0
1.7
6.5
2.4
5.8
1.1
8.6
1.8
7.7
2.5
6.7
0.7
8.3
1.3
7.9
1.9
7.0
2.8
6.1
0.7
7.9
1.3
7.4
2.0
6.6
2.9
5.8
0.7
7.6
1.4
7.2
2.1
6.4
3.0
5.6
0.8
7.3
1.4
6.9
2.2
6.2
3.1
5.4
0.8
6.9
1.5
6.6
2.3
5.9
3.3
5.1
2.4
7.9
3.4
7.0
1.7
7.8
2.6
7.3
3.6
6.4
1.8
7.4
2.7
6.9
3.8
6.1
1.9
7.2
2.8
6.7
3.9
5.9
1.9
6.9
2.9
6.5
4.1
5.7
2.0
6.6
3.0
6.2
4.3
5.4
2.7
7.6
3.8
6.8
2.0
7.6
3.0
7.1
4.2
6.3
2.1
7.3
3.1
6.8
4.4
5.9
2.2
7.1
3.2
6.6
4.5
5.7
2.2
6.8
3.3
6.3
4.7
5.6
2.3
6.5
3.5
6.1
4.9
5.3

PARTIAL LOAD PERCENTAGE = SUPPLIED POWER / FULL LOAD CAPACITY, REFERRED TO THE SAME CONDITIONS
Performance refers to operation with 30% of exhaust air (configuration CCK)
Ta = Indoor air temperature D.B/W.B
D.B. = dry bulbe W.B. = wet bulb

COP referred to only unfrozen coils


kWe = Compressor power input in kW
All cooling capacities do not take into account the heat generated by fan motors

29

BT09N004GB-00

SMARTPACK CKN-XHE

VERSION: VARIABLE POWER UNIT (Clivet abbreviation CHC)


STANDARD AIR FLOW

INTEGRATED HEATING CAPACITIES


External exchanger inlet temperature C (D.B./W.B.)
Heating capacity multiplication coefficient

-5 / -5.4
0,89

0 / -0.6
0,88

5 / 3.9
0,94

ALTRI
1

The integrated heating capacity represents the real heating capacity, including the effect of possible defrosting cycles.
To obtain the integrated heating capacity multiply the heating performance value in kWt ( shown in the heating performance tables) by the coefficients indicated in the table = at page 19
D.B. = DRY BULB W.B. = WET BULB

PERFORMANCES IN HEATING
GRANDEZZE
SIZE

TA (C)
D.B.

GRADINI
POWER
DI
STEPS
POTENZA

10

C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2
C1
C2
C1+C2

15

18

91

20

22

25
10
15

18

101
20

22

25
10
15

18

131

20

22

25
10
15

18

151

20

22

25

kWt
24.0
24.0
24.2
24.4
13.0
14.2
24.8
27.8
28.2
28.3
28.5
19.0
28.7
33.7
34.9
35.3
35.4
19.7
19.7
35.5
39.4
39.6
39.9
40.4
21.5
24.1
41.2

-7 / -8
kWe
4.3
4.5
4.7
4.9
2.1
2.3
5.2
5.4
5.7
5.9
6.1
3.2
6.4
5.9
6.3
6.5
6.7
3.0
3.0
7.1
7.4
7.7
7.9
8.2
3.5
4.1
8.6

COP
5.6
5.3
5.1
5.0
6.1
6.3
4.8
5.1
5.0
4.8
4.7
5.9
4.5
5.7
5.6
5.4
5.3
6.5
6.5
5.0
5.3
5.1
5.0
4.9
6.1
5.8
4.8

kWt
25.2
25.2
25.4
25.6
13.6
15.0
25.9
29.1
29.4
19.6
29.6
19.7
29.7
14.0
19.8
29.9
35.7
36.5
36.9
37.0
20.5
20.5
37.1
41.5
41.7
41.9
42.4
22.5
25.3
43.0

-5 / -6
kWe
4.5
4.7
4.9
5.1
2.2
2.4
5.5
5.6
5.9
3.1
6.1
3.2
6.3
2.1
3.3
6.6
6.1
6.5
6.7
7.0
3.1
3.1
7.3
7.6
7.9
8.2
8.5
3.6
4.2
8.9

Performance refers to operation with 30% of exhaust air (configuration CCK)


Ta = Indoor air temperature D.B
D.B. = dry bulb
W.B. = wet bulb
kWt = Supplied heating capacity in kW with unfrozen coils

BT09N004GB-00

TEMPERATURA
ARIA ESTERNA
(C) D.B./W.B.
EXTERNAL AIR TEMPERATURE
C D.B
0 / -1
2/1
COP kWt
kWe COP kWt
kWe COP kWt
28.1
4.6
6.1
29.3
4.8
6.1
32.7
17.5
19.6
5.6
28.2
5.0
5.6
29.5
5.2
5.6
32.9
15.7
2.1
7.5
17.6
16.6
2.4
7.1
17.4
2.5
7.1
19.6
5.3
28.4
5.3
5.3
29.7
5.5
5.4
33.1
15.1
2.1
7.1
15.8
2.2
7.3
17.6
16.7
2.4
6.8
17.5
2.5
6.9
19.6
5.1
28.5
5.5
5.2
29.8
5.8
5.2
33.2
15.1
2.2
6.9
15.8
2.2
7.1
17.6
16.7
2.5
6.6
17.5
2.6
6.7
19.6
5.0
28.7
5.7
5.0
29.9
6.0
5.0
33.2
6.3
15.2
2.3
6.7
15.9
2.3
6.8
17.6
6.3
16.8
2.7
6.3
17.6
2.8
6.4
19.6
4.8
28.9
6.1
4.8
30.2
6.3
4.8
33.3
24.7
32.0
5.5
5.8
33.4
5.7
5.8
37.3
17.7
24.9
5.2
32.5
6.1
5.4
33.9
6.3
5.4
37.7
17.7
21.5
3.2
6.7
22.5
3.3
6.8
24.9
5.0
32.8
6.4
5.1
34.2
6.6
5.1
37.9
15.4
2.1
7.4
16.0
2.1
7.6
17.8
6.4
21.6
3.3
6.5
22.6
3.4
6.7
25.0
4.9
32.9
6.6
5.0
34.3
6.9
5.0
38.0
15.4
2.1
7.2
16.1
2.2
7.4
17.8
6.2
21.7
3.4
6.4
22.7
3.5
6.4
25.1
4.7
33.1
6.9
4.8
34.5
7.2
4.8
38.1
6.6
15.5
2.2
7.0
16.2
2.3
7.1
17.9
6.0
21.9
3.6
6.1
22.7
3.7
6.1
25.2
4.5
33.3
7.3
4.6
34.7
7.6
4.6
38.3
40.1
6.2
6.5
42.5
6.4
6.6
47.7
26.4
26.4
5.8
40.6
6.7
6.0
42.5
7.0
6.1
47.3
23.8
3.1
7.7
26.5
23.8
3.1
7.7
26.5
5.6
40.8
7.1
5.7
42.6
7.4
5.8
47.2
22.8
3.1
7.4
23.8
3.2
7.5
26.5
22.8
3.1
7.4
23.8
3.2
7.5
26.5
5.5
40.9
7.4
5.6
42.7
7.6
5.6
47.2
22.9
3.2
7.2
23.8
3.3
7.3
26.6
22.9
3.2
7.2
23.8
3.3
7.3
26.6
5.3
41.1
7.6
5.4
42.8
7.9
5.4
47.3
6.6
23.0
3.3
6.9
23.9
3.4
6.9
26.6
6.6
23.0
3.3
6.9
23.9
3.4
6.9
26.6
5.1
41.3
8.0
5.1
43.0
8.3
5.2
47.5
46.4
7.6
6.1
48.5
7.8
6.2
54.1
28.8
32.6
5.5
46.7
8.2
5.7
48.9
8.4
5.8
54.4
26.0
3.5
7.4
28.9
27.9
4.0
6.9
29.2
4.1
7.1
32.6
5.3
46.9
8.6
5.5
49.1
8.9
5.5
54.6
25.0
3.5
7.1
26.0
3.6
7.2
29.0
28.0
4.1
6.8
29.3
4.2
6.9
32.7
5.1
47.1
8.9
5.3
49.3
9.2
5.4
54.7
25.0
3.6
6.9
26.1
3.7
7.0
29.0
28.1
4.3
6.6
29.4
4.4
6.7
32.7
5.0
47.4
9.2
5.2
49.4
9.5
5.2
54.8
6.2
25.1
3.8
6.6
26.2
3.9
6.7
29.1
6.0
28.3
4.5
6.4
29.5
4.6
6.4
32.8
4.8
47.7
9.7
4.9
49.7
10.0
5.0
54.9

7/6
kWe
5.3
2.1
2.6
5.8
2.2
2.7
6.2
2.3
2.8
6.4
2.4
2.9
6.6
2.5
3.0
7.0
3.1
6.3
2.0
3.4
6.9
2.1
3.6
7.3
2.2
3.7
7.6
2.3
3.8
7.9
2.4
4.0
8.3
7.1
3.2
3.2
7.7
3.3
3.3
8.1
3.4
3.4
8.4
3.6
3.6
8.7
3.7
3.7
9.1
8.4
3.6
4.2
9.2
3.8
4.5
9.7
3.9
4.6
10.0
4.0
4.7
10.4
4.2
5.0
10.9

COP
6.1
8.3
7.6
5.6
7.9
7.2
5.4
7.7
7.0
5.2
7.4
6.8
5.0
7.1
6.5
4.8
7.9
5.9
8.7
7.3
5.5
8.3
7.0
5.2
8.0
6.8
5.0
7.7
6.5
4.8
7.4
6.2
4.6
6.7
8.3
8.3
6.1
8.0
8.0
5.8
7.7
7.7
5.6
7.5
7.5
5.4
7.1
7.1
5.2
6.4
8.0
7.7
5.9
7.7
7.3
5.6
7.5
7.1
5.5
7.2
6.9
5.3
6.9
6.6
5.0

kWt
36.5
19.5
21.8
36.6
19.5
21.9
36.6
19.5
21.9
36.6
19.5
21.9
36.7
19.5
21.9
36.7
27.7
41.4
19.6
27.7
41.7
19.7
27.8
41.8
19.7
27.9
41.9
19.7
27.9
42.0
19.8
28.0
42.2
52.0
29.6
29.6
52.1
29.5
29.5
52.1
29.5
29.5
52.1
29.6
29.6
52.2
29.6
29.6
52.3
60.2
32.1
36.3
60.2
32.1
36.4
60.2
32.1
36.4
60.2
32.2
36.4
60.3
32.3
36.4
60.3

12 / 11
kWe COP
5.9
6.2
2.2
8.8
2.8
7.8
6.5
5.7
2.4
8.3
2.9
7.5
6.8
5.4
2.4
8.0
3.0
7.2
7.1
5.2
2.5
7.7
3.1
7.0
7.3
5.0
2.7
7.3
3.3
6.7
7.7
4.8
3.4
8.2
6.9
6.0
2.2
9.0
3.7
7.5
7.6
5.5
2.3
8.6
3.9
7.2
8.1
5.2
2.4
8.3
4.0
6.9
8.4
5.0
2.5
8.0
4.2
6.7
8.7
4.9
2.6
7.6
4.4
6.4
9.1
4.6
7.8
6.7
3.4
8.7
3.4
8.7
8.5
6.1
3.6
8.2
3.6
8.2
8.9
5.8
3.7
7.9
3.7
7.9
9.2
5.7
3.8
7.7
3.8
7.7
9.5
5.5
4.0
7.3
4.0
7.3
10.0
5.2
9.3
6.5
3.9
8.2
4.7
7.8
10.1
6.0
4.1
7.8
4.9
7.5
10.6
5.7
4.2
7.6
5.0
7.3
11.0
5.5
4.4
7.4
5.2
7.0
11.3
5.3
4.6
7.1
5.4
6.7
11.9
5.1

kWe = Compressor power input in kW


C1,C2 indicate the active compresors and then the reliable capacity steps
All cooling capacities do not take into account the heat generated by fan motors

30

SMARTPACK CKN-XHE

ACCESSORIES
EHP - PREHEATING ELECTRIC HEATERS
The option is indicated for cold climate and permit to preheat the inlet air to the water
treatment battery and to extend the work limit.
Ideal for places where the outside temperatures to active the heaters during for a short in all
year. In these cases the simplification of the system is widely offset than conduction cost.
The fins are made of aluminium, with a size suitable to ensure high efficiency and maintain
low power density on the surfaces to limit overheating. The low temperature of the heating
elements increases their lifespan and limits the effect of air ionization.
The electrical heating elements are managed by a thermal control device with two power
settings.
The electric heater activation depends on the outside air temperature. This electric heater
generate a preliminary treatment of the outside air before entering into the active
thermodynamic heat recovery exchanger. Just in case the outdoor air temperature might be
lower than the set parameter inside the electronic control, the unit stops both electric heater
and ventilation in order to introduction of too cold air in the served area.
COMBINATIONS PREHEATING ELECTRIC HEATERS
GRANDEZZE
SIZE

This operation involves variation of the main electrical data of the unit.
Hot water coil and electric heaters cannot be mounted at the same time

EXTENSION OF OPERATING FIELD WITH PRE-HEATING ELEMENTS


The minimum work temperature of the heat pump with electric heater change and depends on the series and the power of the
electric heater. The minimum temperature is easily to reckon subtrahend the DELTA T value (table following below) to the air
temperature inlet on exchanger.
SIZE
GRANDEZZE

POWER
ELECTRIC HEATERS
/ DELTA
T (C)
POTENZA
RESISTENZE
ELETTRICHE
/ DELTA
T [C]

3
AIR FLOW
(M[m/H)
PORTATA
ARIA
/h]

41
51
61
71
91
101
131
151

2200
2700
3400
4100
5200
6400
8000
9600

4,5 kW

6kW

9kW

12kW

18kW

24kW

6,1
4,9
-

8,1
6,6
5,2
4,3
-

12,1
9,9
7,8
6,5
5,1
4,2
-

10,5
8,7
6,8
5,6
4,4
3,7

10,3
8,3
6,7
5,6

8,9
7,4

30

THE LIMITS ARE INDICATIVE AND CONSIDERED:


- GENERAL AND NON-SPECIFIC SIZES
- STANDARD AIR FLOW-RATE
- CORRECTLY INSTALLED AND MAINTAINED UNIT
- OPERATION AT FULL LOAD

25

TM (D.B.)

20
15

TO VERIFY THE UNIT OPERATING LIMITS WITH PERCENTAGES OF


OUTDOOR AIR, ALWAYS CALCULATE THE TEMPERATURE TM OF THE
MIXTURE GENERATED AT THE INLET OF THE INTERNAL EXCHANGER.

(1)

10
5

TM = INLET AIR TEMPERATURE IN THE INTERNAL EXCHANGER


ATTENTION! TEMPERATURE MEASURED WITH A DRY BULB
(D.B. = DRY BULB)

(2)

Delta T

-5
-15

-10

-5

10

15

20

TEXT (W.B.)

TEXT = INLET AIR TEMPERATURE IN THE EXTERNAL EXCHANGER


ATTENTION! TEMPERATURE MEASURED WITH A WET BULB
(W.B. = WET BULB)
1 = OPERATION AT FULL LOAD
2 = UNIT OPERATING FIELD WITH HEATING ELECTRIC HEATER OPTION
WITH AN OUTDOOR AIR TEMPERATURE BETWEEN 10C AND 20C
INSTALL THE FOLLOWING OPTIONS: 2-ROW HOT WATER COIL AND
ELECTRIC PANEL ANTIFREEZE PROTECTION.

31

BT09N004GB-00

SMARTPACK CKN-XHE

CHW2 - TWO-ROW HOT WATER COIL


Option recommended for very cold climates since it allows heating of the served room. The battery is equipped with a
thermostat for the anti-freeze function. The anti-freeze function is always active, even when the unit is in standby. If necessary,
it forces opening of the valve to the maximum allowable value for allow passage of water in the coil and to prevent the
formation of ice.
The hot water coil allows the integration of the capacity provided by the heat pump and, being placed before the handling coil,
it operates as air pre-heating extending the unit operating limits.
As alternative, it may operate in complete substitution of the thermal capacity provided by the compressors.
This is possible by setting a turning point, i.e. a temperature limit of the fresh air below which use of the compressors is
blocked, and the water coil is used as the sole resource. If the water coil provides pre-heating of the air, the control logic
reduces its power to a preset value, which keeps the compressors from working with condensation temperatures that are too
high. If instead the water coil is used as the main resource (e.g. because the compressors are not available), the maximum
power will be provided.
WATER COIL PRESSURE DROPS : AIR SIDE
50
45
91-101

40
131-151

61-71

25

THE AIR SIDE PRESSURE DROPS


ARE RELATIVE TO THE MEDIUM AIR
TEMPERATURE OF 20C AND ARE TO
BE ADDED TO THE PRESSURE
DROPS DUE TO DUCTS, TERMINAL
DEVICES
AND
ANY
OTHER
COMPONENT THAT CAUSES A DROP
IN WORKING DISCHARGE HEAD.

20

QA = AIR FLOW
DP = PRESSURE DROP

DP [Pa]

35

41-51

30

15
10

1500

3000

4500

6000

7500

9000

10500

12000

QA [m /h]
WATER COIL PRESSURE DROPS : WATER SIDE

80
61-71

70

PRESSURE DROPS ON THE WATER


SIDE ARE CALCULATED
CONSIDERING AN AVERAGE WATER
TEMPERATURE OF 65C

91-101

DP [kPa]

60
131-151

41-51

50

QW = WATER FLOW-RATE (L/S)


DP = PRESSURE DROP
THE WATER FLOW RATE MUST BE
CALCULATED WITH THE
FOLLOWING FORMULA

40

QW [L/S] = P / (4,186 X DT)

30

P = HEATING CAPACITY / COOLING


IN kW
DT = TEMPERATURE DIFFERENCE
BETWEEN WATER INLET / OUTLET

20
10
0
0

0,25

0,5

0,75

1,25

1,5

QW [l/s]
This option reduces the available static pressure (air side).
The component requires connection to the plumbing system (to be provided for by the client).
Water coil and electric heaters cannot be mounted at the same time.

BT09N004GB-00

32

1,75

SMARTPACK CKN-XHE

TWO-ROW HOT WATER COIL PERFORMANCES


Ti/To (C)
GRANDEZZE
SIZE

T M (C)

151

TM (C)

131

T M (C)

101

T M (C)

91

39.6
36.3
33.7
32.4
31.1
29.8

TM (C)

71

34.9
32.0
29.7
28.5
27.4
26.3

52.8
48.3
44.8
43.1
41.4
39.7

TM (C)

61

26.9
24.6
22.8
21.9
21.1
20.2

60.7
55.6
51.5
49.5
47.6
45.6

T M (C)

51

23.4
21.4
19.8
19.1
18.3
17.6

81.4
74.6
69.2
66.4
63.8
61.2

T M (C)

41

Qo (l/s)
5
10
14
16
18
20
Qo (l/s)
5
10
14
16
18
20
Qo (l/s)
5
10
14
16
18
20
Qo (l/s)
5
10
14
16
18
20
Qo (l/s)
5
10
14
16
18
20
Qo (l/s)
5
10
14
16
18
20
Qo (l/s)
5
10
14
16
18
20
Qo (l/s)
5
10
14
16
18
20

80/65
kWt

92.0
84.3
78.2
75.2
72.2
69.2

70/55
kWt
1760
19.7
17.8
16.2
15.5
14.8
14.0
2160
22.6
20.4
18.7
17.8
16.9
16.1
2720
29.5
26.6
24.3
23.2
22.1
21.0
3280
33.4
30.1
27.6
26.3
25.0
23.8
4160
44.5
40.1
36.7
35.0
33.3
31.6
5120
51.1
46.1
42.1
40.2
38.2
36.3
6400
68.6
61.9
56.6
53.9
51.4
48.8
7680
77.5
69.9
63.9
61.0
58.0
55.1

60/40
kWt

80/65
kWt

14.8
12.9
11.4
10.7
9.9
9.2

27.2
24.9
23.1
22.2
21.3
20.5

17.0
14.8
13.1
12.2
11.4
10.5

31.2
28.6
26.5
25.5
24.5
23.4

22.2
19.4
17.1
16.0
14.9
13.8

40.6
37.2
34.5
33.2
31.9
30.5

25.1
21.9
19.4
18.1
16.9
15.6

45.9
42.1
39.0
37.5
36.0
34.6

33.4
29.1
25.7
24.1
22.4
20.7

61.3
56.1
52.1
50.1
48.1
46.1

38.3
33.3
29.4
27.5
25.6
23.7

70.2
64.3
59.6
57.3
55.0
52.8

51.6
45.0
39.8
37.2
34.6
32.0

94.6
86.6
80.3
77.2
74.2
71.1

58.2
50.7
44.8
41.9
38.9
36.0

106.5
97.6
90.5
87.0
83.6
80.1

70/55
kWt
2200
22.9
20.7
18.9
18.0
17.2
16.3
2700
26.3
23.7
21.6
20.6
19.7
18.6
3400
34.2
30.9
28.2
26.9
25.6
24.4
4100
38.7
34.9
31.9
30.4
28.9
27.5
5200
51.6
46.5
42.5
40.6
38.6
36.7
6400
59.1
53.3
48.7
46.4
44.2
42.0
8000
79.7
71.8
65.7
62.6
59.6
56.6
9600
89.7
80.9
74.0
70.5
67.1
63.7

60/40
kWt

80/65
kWt

17.2
15.0
13.2
12.4
11.5
10.7

30.7
28.1
26.1
25.1
24.1
23.1

19.6
17.1
15.1
14.1
13.1
12.1

34.1
31.2
29.0
27.9
26.8
25.7

25.7
22.4
19.8
18.5
17.3
16.0

45.8
41.9
38.9
37.4
35.9
34.4

29.0
25.3
22.4
20.9
19.4
18.0

49.4
45.3
42.0
40.4
38.8
37.2

38.6
33.7
29.7
27.8
25.8
23.9

69.0
63.2
58.7
56.4
54.1
51.9

44.0
38.4
33.9
31.7
29.4
27.2

74.3
68.1
63.1
60.7
58.3
55.9

59.7
52.0
46.0
43.0
40.0
37.0

106.5
97.6
90.5
87.0
83.6
80.1

67.0
58.4
51.6
48.2
44.8
41.4

112.8
103.3
95.9
92.2
88.5
84.9

70/55
kWt
2640
25.9
23.3
21.3
20.3
19.4
18.4
3100
28.7
25.9
23.7
22.6
21.5
20.4
4080
38.6
34.8
31.8
30.3
28.9
27.4
4600
41.6
37.6
34.4
32.8
31.2
29.6
6240
58.1
52.4
47.9
45.7
43.5
41.3
7000
62.5
56.4
51.6
49.2
46.7
44.4
9600
89.7
80.9
74.0
70.5
67.1
63.7
10500
95.0
85.7
78.3
74.7
71.0
67.5

60/40
kWt
19.4
16.9
14.9
13.9
12.9
12.0
21.4
18.7
16.5
15.4
14.3
13.2
28.9
25.2
22.3
20.8
19.4
17.9
31.1
27.1
24.0
22.4
20.8
19.3
43.4
37.8
33.4
31.2
29.0
26.8
46.6
40.6
35.8
33.4
31.1
28.7
67.0
58.4
51.6
48.2
44.8
41.4
70.9
61.8
54.6
50.9
47.4
43.8

TM = air inlet temperature of water coil (C)


Ti/To = water temperature inlet/outlet (C)
Qo = air flow (l/s)
kWf = Cooling capacity (Kw)
Thermal yields referred to the max. water coil capacity. The thermo regulator coke the 3-way modulating valve limiting the inlet air temperature at desired values.

33

BT09N004GB-00

SMARTPACK CKN-XHE

3WVM - MODULATING 3-WAY VALVE


To be used in conjunction with the hot water coil (option). It is controlled by the on-board microprocessor by means of a 0-10V
signal and allows fully automatic adjustment of the water exchanger. The valve with modulating actuator is provided already
installed and wired on the unit.
PRESSURE DROP MODULATING THREE-WAY VALVE
45
40

91-151

35

DP [kPa]

30

41-71

25
Q [l/s] = water flow rate
DP = water-side pressure drop (kPa)

20
15
10
5
0
0

0,25

0,5

0,75

Q [l/s]

1,25

1,5

1,75

CSOND - TEMPERATURE AND HUMIDITY CONTROL WITH ON-BOARD PROBE


This option makes it possible to measure the ambient temperature and humidity directly on the air flow
entering the unit. The automatic thermal regulation is done using the on-board probes, whereas the probes
on the remote control are inhibited. The post-heating coil is heated by the hot gas piped by the delivery
pipe.
CPHG - HOT GAS RE-HEATING COIL
This option is recommended during the summer when
dehumidification of the room is required. The flow of
air to enter the room may contain a higher level of
humidity than desired.
The dehumidification process is used to reduce it. The
air flow is first cooled in the treatment coil with
separation of condensation. It is then freely postheated to maintain the desired condition of comfort in
the room served.
The post-heating coil is located behind the treatment
coil and is activated by drawing a flow of hot gas down
the line from the compressors through the action of a
dedicated solenoid valve.
The process starts working based on the humidity setpoint established by the user. With respect to
traditional devices, such as electrical heating elements
or hot water coils, the use of the post-heating coil does
not consume any energy. It also lowers the
condensation temperature, which provides two
positive effects: the power absorbed by the
compressors is considerably reduced, and at the same
time the cooling power is increased with greater
efficiency (EER).

The measurement of the ambient humidity is done


using the electronic ambient control wall unit with a
humidity probe (supplied standard with the unit).

RH

5
1)
2)
3)
4)
5)

External air and humidity / temperature probe


Air cooled and dehumidified on inside exchanger (evaporator)
Hot gas bypass valve
Treated air by the re-heating exchanger
External exchanger (condenser)

Indicative scheme - not in scale

This option reduces the available static pressure (air side).

BT09N004GB-00

34

SMARTPACK CKN-XHE

HOT GAS RE-HEATING COIL PERFORMANCES


TEMPERATURA
ARIA RIPRESA
DALLAMBIENTE (C)
RETURN
AIR TEMPERATURE
(C)
SIZE

25

27

30

32

35

25

27

30

32

35

25

27

30

32

35

kWt

kWt

kWt
1760

kWt

kWt

kWt

kWt

kWt
2200

kWt

kWt

kWt

kWt

kWt
2640

kWt

kWt

10

5,5

5,9

6,5

7,0

7,6

6,0

6,4

7,1

7,6

8,3

6,4

6,9

7,6

8,1

8,9

12

5,1

5,5

6,1

6,5

7,2

5,5

6,0

6,7

7,1

7,8

5,9

6,4

7,1

7,6

8,4

14

4,6

5,1

5,7

6,1

6,8

5,0

5,5

6,2

6,7

7,4

5,4

5,9

6,6

7,1

7,9

16

4,2

4,6

5,3

5,7

6,3

4,6

5,0

5,7

6,2

6,9

4,9

5,4

6,1

6,6

7,4

18

3,8

4,2

4,9

5,3

5,9

4,1

4,6

5,3

5,7

6,4

4,4

4,9

5,6

6,1

6,9

20

3,4

3,8

4,4

4,9

5,5

3,7

4,1

4,8

5,3

6,0

3,9

4,4

5,1

5,6

6,4

41

Ta (C)

Qo (l / s)

51

Ta (C)

Qo (l / s)

2160
5,9

6,4

7,1

7,5

8,2

6,4

6,9

7,7

8,2

8,9

6,7

7,3

8,0

8,6

9,4

12

5,5

5,9

6,6

7,1

7,8

5,9

6,4

7,2

7,7

8,4

6,2

6,7

7,5

8,0

8,8

14

5,0

5,5

6,1

6,6

7,3

5,4

5,9

6,7

7,2

7,9

5,7

6,2

7,0

7,5

8,3

16

4,6

5,0

5,7

6,2

6,8

4,9

5,4

6,2

6,7

7,4

5,2

5,7

6,5

7,0

7,8

18

4,1

4,6

5,2

5,7

6,4

4,4

4,9

5,7

6,2

6,9

4,7

5,2

6,0

6,5

7,3

20

3,7

4,1

4,8

5,2

5,9

4,0

4,4

5,2

5,7

6,4

4,1

4,7

5,4

6,0

6,7

Ta (C)

2720
7,8

8,4

9,3

9,9

10,8

8,4

9,1

10,1

10,8

11,8

9,0

9,7

10,8

11,5

12,6

7,2

7,8

8,7

9,3

10,2

7,8

8,4

9,4

10,1

11,1

8,3

9,0

10,1

10,8

11,8

14

6,6

7,2

8,1

8,7

9,6

7,1

7,8

8,8

9,4

10,4

7,6

8,3

9,3

10,1

11,1

16

6,0

6,6

7,5

8,1

9,0

6,5

7,1

8,1

8,8

9,8

6,9

7,6

8,6

9,4

10,4

18

5,4

6,0

6,9

7,5

8,4

5,8

6,5

7,4

8,1

9,1

6,2

6,9

7,9

8,6

9,7

20

4,8

5,4

6,3

6,9

7,8

5,2

5,8

6,8

7,5

8,4

5,5

6,2

7,2

7,9

9,0

Ta (C)

3280
8,3

9,0

10,0

10,6

11,6

9,0

9,7

10,8

11,5

12,6

9,4

10,1

11,2

12,0

13,1

7,7

8,3

9,3

10,0

11,0

8,3

9,0

10,1

10,8

11,9

8,6

9,4

10,5

11,2

12,3

14

7,0

7,7

8,7

9,3

10,3

7,6

8,3

9,4

10,1

11,1

7,9

8,6

9,7

10,5

11,6

16

6,4

7,0

8,0

8,7

9,6

6,9

7,6

8,7

9,4

10,4

7,2

7,9

9,0

9,7

10,8

18

5,7

6,4

7,4

8,0

9,0

6,2

6,9

8,0

8,7

9,7

6,4

7,2

8,3

9,0

10,1

20

5,1

5,7

6,7

7,4

8,3

5,5

6,2

7,2

8,0

9,0

5,7

6,4

7,5

8,3

9,4

Ta (C)

4160

Ta (C)
Ta (C)
Ta (C)

5200

6240

10

13,7

14,7

16,2

17,3

18,9

14,9

16,0

17,7

18,8

20,5

15,8

17,1

18,9

20,1

21,9

12

12,7

13,7

15,2

16,3

17,8

13,8

14,9

16,6

17,7

19,4

14,7

15,9

17,7

18,9

20,7

14

11,6

12,7

14,2

15,3

16,8

12,7

13,8

15,4

16,6

18,3

13,5

14,7

16,5

17,7

19,5

16

10,6

11,7

13,2

14,2

15,8

11,6

12,7

14,3

15,5

17,2

12,3

13,5

15,3

16,5

18,4

18

9,6

10,7

12,2

13,2

14,8

10,5

11,6

13,2

14,4

16,1

11,2

12,4

14,1

15,4

17,2

20

8,6

9,7

11,2

12,2

13,8

9,4

10,5

12,1

13,3

15,0

10,0

11,2

13,0

14,2

16,0

5120

6400

7000

10

14,8

15,9

17,6

18,7

20,4

16,0

17,2

19,0

20,3

22,1

16,5

17,7

19,6

20,9

22,8

12

13,7

14,8

16,5

17,6

19,3

14,8

16,0

17,8

19,1

20,9

15,3

16,5

18,4

19,7

21,6

14

12,6

13,7

15,4

16,5

18,2

13,6

14,8

16,6

17,9

19,7

14,0

15,3

17,2

18,4

20,3

16

11,5

12,6

14,3

15,4

17,1

12,4

13,6

15,4

16,7

18,5

12,8

14,1

15,9

17,2

19,1

18

10,4

11,5

13,2

14,3

16,0

11,3

12,5

14,3

15,5

17,3

11,6

12,9

14,7

16,0

17,9

20

9,3

10,4

12,1

13,2

14,9

10,1

11,3

13,1

14,3

16,1

10,4

11,6

13,5

14,7

16,6

6400

8000

9600

10

19,2

20,6

22,8

24,3

26,5

20,8

22,4

24,8

26,4

28,8

22,2

23,9

26,4

28,1

30,7

12

17,8

19,2

21,4

22,8

25,1

19,3

20,8

23,2

24,8

27,2

20,5

22,2

24,7

26,4

29,0

14

16,3

17,8

19,9

21,4

23,6

17,7

19,3

21,6

23,2

25,6

18,9

20,6

23,1

24,8

27,3

16

14,9

16,3

18,5

20,0

22,2

16,2

17,7

20,1

21,7

24,1

17,2

18,9

21,4

23,1

25,7

18

13,5

14,9

17,1

18,5

20,7

14,6

16,2

18,5

20,1

22,5

15,6

17,2

19,8

21,4

24,0

20

12,1

13,5

15,6

17,1

19,3

13,1

14,6

17,0

18,5

20,9

13,9

15,6

18,1

19,8

22,3

Qo (l / s)

151

4600

12

Qo (l / s)

131

4100

10

Qo (l / s)

101

4080

12

Qo (l / s)

91

3400

10

Qo (l / s)

71

3100

10

Qo (l / s)

61

2700

7680

9600

10500

10

20,5

22,1

24,4

26,0

28,4

22,2

23,9

26,4

28,1

30,7

22,9

24,6

27,2

29,0

31,7

12

19,0

20,5

22,9

24,4

26,8

20,5

22,2

24,7

26,4

29,0

21,2

22,9

25,5

27,3

29,9

14

17,5

19,0

21,3

22,9

25,3

18,9

20,6

23,1

24,8

27,3

19,5

21,2

23,8

25,5

28,2

16

15,9

17,5

19,8

21,4

23,7

17,2

18,9

21,4

23,1

25,7

17,7

19,5

22,1

23,8

26,5

18

14,4

15,9

18,2

19,8

22,2

15,6

17,2

19,8

21,4

24,0

16,0

17,8

20,4

22,1

24,7

20

12,9

14,4

16,7

18,3

20,6

13,9

15,6

18,1

19,8

22,3

14,4

16,1

18,7

20,4

23,0

Ta = outlet air temperature from the treatment coil and entering the post-heating coil
Qo = air flow rate (l/s)
kWt = thermal power provided (kW)
The post-heating coil is supplied with hot gas released from the outlet pipe.
Since the temperature of the hot condensation gas is related to the ambient air intake temperature, the approximate powers of the post-heating coil are expressed based on the ambient air
intake temperature.

35

BT09N004GB-00

SMARTPACK CKN-XHE

HSE - ELECTRODE BOILER STEAM HUMIDIFIER


This device is perfect for the winter period when it is necessary to add humidity to
the room without cooling the air flow. The modulating automatic adjustment makes
it possible to adapt the production of steam and the related operating costs to meet
actual needs. Available in different powers, the device is suitable for use with
unsoftened water of medium conductivity. It is complete with water filling solenoid
valve, disposable cylinder, water drainage solenoid valve, distribution nozzle,
electronic control card with functions of verification of water level, verification of
conductivity, anti-foam, manual override of water drainage. To ensure the utmost
hygiene, the cylinder is automatically drained after a certain period of inactivity. The
device includes an automatically activated anti-freeze device. A supply probe is
used to monitor the humidity level. It is installed and wired on-board the unit.
The accessory is installed inside the unit and is connected to the electrical panel of
the unit.
The measurement of the ambient humidity is done using the electronic ambient
control wall unit with a humidity probe (supplied standard with the unit).
COMBINATIONS ELECTRODE BOILER STEAM HUMIDIFIER
GRANDEZZE
SIZE

This operation involves variation of the main electrical data of the unit
This accessory requires the presence of a water circuit and drain on board the unit. Provided by the customer

CREFP - DEVICE TO REDUCE CONSUMPTION OF FANS OF TOF THE EXTERNAL SECTION (PHASE CUTTING)
The device makes it possible to control the external axial fans, adjusting their speed of rotation based on the condensation
pressure. When fresh air temperature is low, a minimum air flow rate is required to hold down the condensation pressure.
Therefore, at low fresh air temperatures, fan rotation speed is reduced, resulting in reduced energy consumption (low
temperature device).
In certain applications where the outdoor temperature is low and outdoor air cannot be introduced to cool the served
environment (free cooling) the phase cutting device ensures correct unit operation.
In heat pump mode, this device reduces the fan rotation speed when the outdoor air temperatures are high (high temperature
device).
FCE - ENTHALPIC FREE COOLING
This option is used to reduce energy consumption and compressor wear by using the outdoor air as an energy source to lower
the thermal loads and ambient humidity.
The temperature control compares the temperature and the humidity between the outdoor environment and the served
environment and decides the amount of renewal air needed to guarantee the correct temperature and humidity set-points in
the environment, keeping the compressors shut off.
The measurement of the ambient temperature and humidity is done using the electronic ambient control wall unit with a
humidity probe (supplied standard with the unit).
PCOS - CONSTANT OUTFLOW AIR FLOW RATE
The original technology used eliminates the need for on-site calibration of traditional fans, as well as the time that would be
required and the associated costs. The required flow rate is set on the display by the user and maintained automatically by the
unit, which adjusts the speed of the ventilating sections. During the installation and start-up phase, the unit adjusts to the
effective pressure drop in the air distribution and diffusion system. Furthermore, during its entire operating life, the progressive
fouling of the air filters is automatically compensated for thanks to this system.

BT09N004GB-00

36

SMARTPACK CKN-XHE

PSSAF - DIFFERENTIAL PRESSURE SWITCH FOR DIRTY AIR FILTERS


It makes it possible to detect and signal (with a suitable alarm) when the dirtiness of
the air filter reaches its maximum level. This provides the unit operator with
information on when filter maintenance is required. The detection signal is installed
in the unit. It is already connected to the electrical panel and pre-calibrated in the
factory. Calibration can be modified by a specialized service centre during the
commissioning phase.

FES - HIGH EFFICIENCY ELECTRONIC AIR FILTER (EQUIVALENT TO CLASS H10)


Class H10 high-efficiency filters are additional filtering components with an active electrostatic
system. Solid or liquid particles contained in the air flow are trapped by and electrical field. The air
flow through the filter is affected in two main phases: release of an electrical charge to the
particles (ionization), and capture of the particles by electrostatic deposit (captivation). On a
periodic basis, the filters must be washed to remove the captured particles. The filters are capable
of trapping fine dusts, some types of viruses and micro-organisms (anti-bacterial action) with very
modest pressure drops. The range of use normally includes fine powders that measure less than
1 m. Typical pollutants are cigarette smoke (0.50.3 m), oily vapours (10.2 m), PM10
(particles < 10 m), PM2.5 (particles < 2.5m), PM1 (particles < 1m), etc.
The fouling of the electric filter is indicated by a sensor, after which periodical maintenance can be
scheduled, which is easy to perform by simply washing the filter with a non-aggressive detergent
for aluminium and water.
The greater initial cost in comparison to a traditional bag filter is amortised in a short period of
time, considering that the useful life of the electrostatic filters is the same as the unit whereas the
bag filters must be periodically replaced.

FLOW OF CONTAMINATED

IONIZATION

CAPTIVATION

This option reduces the available static pressure (air side).


This operation involves variation of the main electrical data of the unit.

PAQC - AIR QUALITY SENSOR FOR CO2 P.P.M. CONTROL


This option is recommended for areas with highly variable rates of traffic.
The probe measure the amount of CO2 in the environment and sends the unit a
0/10V proportional signal.
Based on the received signal, the unit manages the input of the correct amount
of refresh air, preventing wasted energy and money due to a treatment of fresh
air in excess of actual needs.
The probe is installed and wired on board the unit and is located in the unit
supply duct.

PAQCV - AIR QUALITY SENSOR FOR CO2 AND VOC P.P.M. CONTROL
The option is recommended in areas with tobacco smoke, formaldehyde (from
solvents, deodorants, glues, paints, detergents), food preparation, etc. The
probe measure the amount of CO2 and VOC (volatile organic compounds) in the
environment and sends the unit a 0/10V proportional signal.
Based on the received signal, the unit manages the input of the correct amount
of refresh air, preventing wasted energy and money due to a treatment of fresh
air in excess of actual needs. The probe is installed and wired on board the unit
and is located in the unit's supply duct.

37

BT09N004GB-00

SMARTPACK CKN-XHE

AGQ - ELECTRIC PANEL ANTIFREEZE PROTECTION


This option is necessary for very cold climates where the outdoor
temperature may be between 10C and 20C.
This option includes self-regulating thermostat controlled heaters that
protect the electric panel against freezing, guaranteeing that is will
operate correctly.

This operation involves variation of the main electrical data of the unit.
This accesory is always operating even at switched off unit on condition that the power supply is maintained active and the unit isnt
sectionized.
Its necessary to provide appropriate precautions to avoid stock pile snow and ice in front of the inlet and outlet air.

PFCP - POWER FACTOR CORRECTION CAPACITORS (COSFI > 0.9)


The component is necessary to lower the phase difference between current
and voltage in the electromagnetic components of the unit, such as
asynchronous motors. By re-phasing it is possible to reduce the intensity of the
line current by reducing a part of the power of the mains (reactive power). This
leads to an economic benefit which the energy provider grants to the final user.
The component makes it possible to bring the cosfi power factor to values
which on average are greater than 0.9.
The device is installed and wired on board

MOB - SERIAL PORT RS485 WITH MODBUS PROTOCOL


It allows serial connection of supervision systems, using ModBus as the
communication protocol. It allows access to the complete list of operating
variables, controls and alarms.
The device is installed and wired on board

LONW - SERIAL PORT RS485 WITH LONWORKS PROTOCOL


Consente il collegamento seriale a sistemi di supervisione, utilizzando
LonWorks come protocollo di comunicazione. Permette laccesso ad un
elenco di variabili di funzionamento, comandi ed allarmi conforme allo
standard Echelon.
The device is installed and wired on board

PM - PHASE MONITOR
The phase monitor makes it possible to check the correct connection of the phases and their imbalance in units powered with
a tri-phase system. If the connection of the phases is not correct, or the threshold of phase imbalance is exceeded, or the
voltage is too high or too low for a certain amount of time, the monitor acts on the control circuit and orders the unit to be shut
down. As soon as nominal line conditions are restored, the unit is automatically reset.

The device is installed and wired on board

CMS - CLIVET MASTER SYSTEM


CLIVET MASTER SYSTEM (CMS) is the ideal system for the control of
air conditioning systems. It is able to manage up to six Roof-top units .
Through a single controller, with a built-in touch screen 5,7, it is
possible to easily and intuitively access to all information about the airconditioning system status and units.
Among the main functions it allows: the automatic recognition of
connected units, the setting of all parameters of the system and of the
single unit, the visualization of the unit status, the alarm control and
management, the operating hourly scheduling and the rotation of the
units also for single zone.
The data exchange between the system control and the unit is via
RS-485 serial connection.
For further information refer to the technical documentation.
BT09N004GB-00

38

GND

GND

RS485

GND

GND

RS485

SMARTPACK CKN-XHE

P-MATIC - CLIVET MANAGEMENT SYSTEM


Clivet P-MATIC is a Clivet supervision system that allow to schedule
and manage all the installed Clivet conditioning units, optimizing their
functional working and the others systems in order to reduce the energy
consumption.
Thanks to the simple use of the software and to the tridimensional
graphic interface, it is possible to change complex activities of system
operating into simple activities made by the customer.
Clivet P-MATIC let to visualize the maintenance state of the
conditioning units, valuate and manage the alarms.
The user makes operation on the supervision workstation or on the PLC
(Programmable Logic Controller) interface display. The exchange data
between workstation, units, control electronic devices, remote
managing electronic devices is made on serial bus networks by
communication standard protocol RS485, or on local network LAN
(Local Area Network) Ethernet TCP/IP.
The control software let to verify the conditioning unit and to make the
on-line assistance.
For further information refer to the technical documentation.

MHP - HIGH AND LOW PRESSURE GAUGES


Although the standard unit permit already to show the digital parameters of
pressure of the refrigeration circuit, this option allow the analogic measures of
the Freon pressures on suction and compression, giving a most easy way to
check the work parameters from specialists in the field.
The two liquid pressure gauges and corresponding pressure sockets are
installed on the unit in an easily accessible location.

M12

67

6.5

Separately supplied accessories

67

The rubber anti-vibration devices are fastened in housings on the


longitudinal members. They reduce the vibrations caused by the unit,
reducing the noises transmitted by the support structures. These elastic
bodies soften axial and tangential stresses. Their mechanical and physical
characteristics remain nearly unchanged over time thanks to the highly
resistant material they are made of.
As an alternative to the rubber anti-vibration devices, it is possible to use
neoprene rubberized strips on the longitudinal support members.
As an alternative to the rubber anti-vibration devices, it is possible to use
neoprene rubberized strips on the longitudinal support members (not
supplied by Clivet).

52

AMRX - RUBBER ANTIVIBRATION MOUNTS

80

PGFC - FINNED COIL PROTECTION GRILL


This accessory is used to protect the external coil from the accidental contact with
external things or people.
Ideal for installation in places where is possible the passage of people such as
parkings, terraces, etc.
The accessory is fournished and installed on-board

39

BT09N004GB-00

SMARTPACK CKN-XHE

BT09N004GB-00

40

SMARTPACK CKN-XHE

DIMENSIONAL
Size 41 - 151

2
ES

AE

3
P

17

15

12 13

14

W1

16

(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)

9
11

H1

1000*
2
W2

W4

1000*

10

SIZE

41 / 51

1990

1005

1270

75

510

475

110

600

87

760

144

360

350

1190

350

61 / 71

2320

1305

1270

75

510

475

110

900

147

900

170

450

350

1520

350

91 /101

2320

1605

1270

75

510

475

110

1200

147

900

170

450

350

1520

350

131/151

2680

1605

1710

75

800

625

110

1200

147

1260

170

630

350

1880

350

CONFIGURATION: FULL RE-CIRCULATION (CAK) / RECIRCULATION AND RENEWAL AIR (CBK)

SIZE

41 / 51

61 / 71

91 /101

131/151

W1

Kg

58

95

121

173

W2

Kg

61

99

126

181

W3

Kg

63

103

132

188

W4

kg

66

107

137

196

Peso tot

kg

247

403

516

738

CONFIGURATION: RECIRCULATION, RENEWAL AND EXAUST AIR (CCK)

SIZE

COMPRESSOR WITH REMOVABLE PANEL


ELECTRICAL PANEL
POWER INPUT
HUMIDIFIER CONNECTIONS
CONDENSATE DISCHARGE
INLET WATER LINE OF THE TWO-ROW HOT WATER COIL
OUTLET WATER LINE OF THE TWO-ROW HOT WATER COIL
HOT GAS RE-HEATING COIL (OPTIONAL)
INTERNAL EXCHANGER
EXTERNAL EXCHANGER
TWO-ROW HOT WATER COIL (OPTIONAL)
ELECTRONIC FILTERS (OPTIONAL)
PLEATED AIR FILTERS G4
SUPPLY FAN
EXCHANGER FOR THE OUTDOOR AIR HANDLING (ONLY CCK
CONFIGURATION)
(16) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING
THE UNIT)
(17) OVERPRESSURE DAMPER ON THE EXHAUST AIR (ONLY CCK
CONFIGURATION)
(18) ACCESS FOR INSPECTION OF COILS, FILTERS, HEATING ELEMENTS
(19) ACCESS FOR INSPECTION OF THE TWO-ROW HOT WATER COIL BLEED
(OPTIONAL)
(R) AMBIENT AIR INTAKE
(M) AMBIENT AIR DISTRIBUTION
(AE) FRESH AIR INTAKE
(1) (ES) AIR EXHAUST (ONLY CCK CONFIGURATION)
(H1) WALL WITH SAME HEIGHT AS UNIT ON A MAXIMUM OF THREE SIDES
(*) SUGGESTED CLEARANCE

W3

F
C

1000*

18

AE

19

41 / 51

61 / 71

91 /101

131/151

W1

Kg

61

99

127

182

W2

Kg

63

103

132

189

W3

Kg

66

108

138

197

W4

kg

69

112

143

205

Peso tot

kg

259

422

540

773

The presence of optional accessories may result in a substantial variation of the weights shown in the table.

41

BT09N004GB-00

SMARTPACK CKN-XHE

BT09N004GB-00

42

SMARTPACK CKN-XHE

43

BT09N004GB-00

The data contained in this bulletin is not binding and may be changed by the manufacturer without prior notice.
All reproduction, even partial, is prohibited. Copyright - CLIVET S.p.A. - Feltre (BL) - Italy