You are on page 1of 76

CEILAiR

Engineering Manual

Precision Air Conditioning


1 to 10 Tons
(60 Hz Data)

Ceiling Mounted
Full line of DX & CW Systems
Air Technology Systems, Inc.

Air Technology Systems, Inc.

Stulz Air Technology Systems, Inc.

SATS is dedicated to providing innovative solutions for critical temperature and humidity control
needs. SATS designs and manufactures specialized
environmental control equipment for commercial,
industrial and custom military applications. SATS
serves a diverse marketplace - including telecommunications, information technology, medical,
financial, educational, industrial process and government contracts - utilizing world-class island
manufacturing processes in a modern, 150,000 ft2
facility. The addition of SATS to the STULZ family
of companies solidifies STULZ as a global leader in
the precision air conditioning marketplace. SATS
combines a global network of sales and service
companies with an extensive factory engineering
staff and highly flexible manufacturing resources
dedicated to providing world-class quality, innovation and customer service.

CeilAiR

ceiling mounted air conditioning units


provide temperature and/or humidity control
for those hot spot areas in
the building which exceed
the central system capacity.
They are an economical solution to such demands which
may, in fact, be temporary
until the next offices are
carved out of an existing
plant area, another laboratory
added to a school or new medical
equipment installed at a hospital. No floor space is
required by the CeilAiR ceiling mounted units. The
units are designed with a wide range of options to
handle both comfort and precision cooling applications. Typical applications include:

Air Technology Systems, Inc


COMFORT

ISO-9001:2001Quality Registered
Stulz-ATS is committed to satisfying customer
expectations by meeting and exceeding requirements. Our Quality Policy ensures that every
Employee is committed to Customer Satisfaction,
Teamwork and utilizing Continuous Process Improvement methods in order to deliver an exceptional product. We will continually measure our
performance to improve the effectiveness of our
quality management system

Precision A/C Applications


Stulz-ATS is dedicated to the manufacturing of
supplemental and precision air conditioning products. With an extensive installation base, SATS has
earned a solid reputation as a quality supplier and
leader in its field.

1-1

Air Technology Systems, Inc.

Conference Rooms
General Office Spaces
Modular Offices

CRITICAL / PRECISION









Telecommunications Rooms
Telephone Switch-Gear Rooms
Computer / LAN Rooms
Copier / Fax Rooms
ATM Bank Centers
Elevator Equipment Rooms
CAT SCAN / MRI Facilities
Hospital Operating & Isolation Rooms
Clean Rooms
Laboratories

PERFECT FOR TENANT RENOVATIONS!

Table of Contents
Table of Contents
SECTION - 5

SECTION - 1
Introduction to Stulz-ATS...................................................... 1-1
Table of Contents................................................................. 1-2

SECTION - 2

ELECTRICAL DATA: (FLA / MCA / MFS)


Electrical Data Index............................................................. 5-1
DX - Compressorized Systems:

CeilAiR SYSTEMS:
Outstanding Advantages...................................................... 2-1
User Oriented Features & Options......................................... 2-2
Available Configurations................................................... 2-3/4

Air Cooled, Self-Contained Systems...................................... 5-2


Air Cooled, Split Systems................................................... 5-2/4
Water Cooled Systems...................................................... 5-2/4
Glycol Cooled Systems...................................................... 5-2/4

MODEL NOMENCLATURE:
Nomenclature Chart............................................................. 2-5
Model Nomenclature Specifications...................................... 2-6

SECTION - 3
GUIDE SPECIFICATIONS:
Standard Features Index....................................................... 3-1
Standard Guide Specifications........................................... 3-2/4

DX - Air Handling & Remote Condensing Units:


DX - Air Handling Units..................................................... 5-5/6

Free-Cooling & Alternate Water Source:
DX with Free-Cooling........................................................ 5-7/8
DX with Alternate Water Source........................................ 5-7/8
Chilled Water Air Handling Systems:

Optional Features Index........................................................ 3-5


Optional Features Guide Specifications............................ 3-6/14

Chilled Water Systems.......................................................... 5-9

SECTION - 4

SECTION - 6

PERFORMANCE / CAPACITY SPECIFICATIONS:

DIMENSIONAL / INSTALLATION DRAWINGS:

Performance Data Index....................................................... 4-1

Dimensional Drawing "Quick Find" Index............................. 6-1

DX - Air Cooled Systems.................................................... 4-2/6

Physical Data - Unit Weights (lbs).......................................... 6-2


Connection Sizes - DX Refrigerant........................................ 6-3

DX - Water Cooled Systems............................................... 4-7/8


DX - Glycol Cooled Systems............................................. 4-9/10

Air Cooled Systems........................................................... 6-4/9


Water / Glycol Cooled Systems...................................... 6-10/13
Chilled Water Systems................................................... 6-14/15

Chilled Water Systems................................................... 4-11/16


Free-Cooling & Alternate Water Source Systems............ 4-17/28

Air Technology Systems, Inc.

1-2

CeilAiR Systems
CeilAiR ceiling A/C's are designed as the
ultimate space saver. They easily mount in a
standard 2' x 4' grid of a dropped ceiling plenum and are available with high static blowers (up to 2.0" e.s.p. available) for connection
to ceiling plenum ducts. CeilAiR units are especially useful where there is no floor or wall
space available for cooling units or where
aesthetics demand out-of-sight installation.

CeilAiR Systems Offer Outstanding Advantages


Flexibility

Microprocessor Controls

A wide variety of types are available to meet your unique


requirements.

Precision temperature and/or humidity control with unrivaled, user-friendly controls, offer a wide range of functions and alarms.

DX - Air Cooled
DX - Water Cooled
DX - Glycol Cooled (w/ Remote Drycoolers &

Pump Packages
DX - Air Handling Units
Chilled Water Air Handling Units

Air Technology Systems, Inc


Versatility
Spot Cooling & Ducted systems
Self-Contained & Split systems

A-Tech-1.1/.2

Space Saving Design

Complete Temperature & Humidity


Control

Compact, in-the-ceiling design saves valuable floor space.

Wide Size Range


1 to 10 tons capacity in eleven incremental sizes meets any
supplemental cooling requirement.

C-Tech-10

A-Tech-20

Steam Canister Humidification (Optional)


Dehumidification Mode (Optional) with
- Electric Reheat/Heat
- Hot Gas Reheat (Energy $aver)
- Hot Water & Steam Reheat/Heat

Capacity Modulation Options

Non-Proprietary Parts
All CeilAiR systems incorporate non-proprietary components where possible. Most major HVAC, refrigeration and
electrical distributors stock an exact model cross reference
or an alternate to most factory provided components.

Single & Dual Compressor Systems


Hot Gas Bypass Systems
Multistage Reheat/Heat

Code Conformance
Complies With

L LISTED
NRT

UL 1995
C

Listing E112043

CSA C22.2 No. 236


Heating & Cooling Equipment

- NYC MEA Approved (MEA-163-88-E)


- Chicago Code Approved
- MET-C recognized by Standards Council of Canada

2-1

Air Technology Systems, Inc.

User Oriented Features & Options


Scroll Compressors

Variety of Air Patterns

CeilAiR DX air conditioners incorporate Scroll Compressor Technology


(unless specified otherwise). Scroll
Compressors provide higher efficiency, higher reliability and lower
sound power than other compressor
technologies.

Spot Cooler

EVAPORATOR
AIR IN

Year Round Operation

Option offerings available with CeilAiR air conditioners allow for year-round, 24/7 continuous
on-line system operation in any environment in the world:

EVAPORATOR
AIR OUT

Ducted

Low Ambient Control (DX - Air Cooled)


0F Fan Cycling / Fan Speed
-20F Variable Fan Speed
-30F Flooded Head Pressure

EVAPORATOR
AIR IN
EVAPORATOR
AIR IN

Quiet Operation

EVAPORATOR
AIR OUT

Low sound power Scroll compressors coupled with low


RPM blowers, acoustically lined cabinets and low velocity
grilles provide the optimum in quiet operation.

Fast Delivery
Stock units complete and ready for shipment
"Rapid-Fire", 5 day Ship Program

Warranty

- 2 Year Parts Standard


- Optional 5 Year Compressor

EVAPORATOR
AIR OUT

Straight-Thru

90 / Right-Angle

Other Available Options












- Condensate Pumps
- Electrical Service Switches
- Firestats
- Smoke Detectors
- Water Leak Detectors
- Special High Efficiency Filtration
(2" & 4" Filters up-to 60% Dust Spot)
- High Pressure DX - Water/Glycol Cooled
Condenser Regulating Valves
- Free-Cooling & Alternate Water Source Units
- Many more options available (see page 3-5)!

Light weight ALL ALUMINUM cabinet and


chassis prevents rust & corrosion

Selected Standard Features:

Acoustical / Thermal Insulation


Aluminum Fin / Copper Tube Coils
Thermal Expansion Valve
Refrigerant Sight Glass
Filter / Drier Strainer
Liquid Refrigerant Reclaim Valves
Insulated SS or Polymer Drain Pans
Condensate Overflow Safety Switch
High / Low Pressure Switches

CeilAiR Ceiling AC Systems


(Model OHS-( )-AS Shown)

Air Technology Systems, Inc.

2-2

Space Saving Configuration Choices


AIR COOLED SYSTEMS
SELF-CONTAINED AIR COOLED - with INTEGRAL Air Cooled Condenser

OHS-012/040-AS

OHS-012/040-AS

(Self-Contained, Ducted Evaporator)

(Self-Contained, "Ductless" Spot Cooler)

SPLIT AIR COOLED -


with REMOTE OUTDOOR or INDOOR Air Cooled Condenser


(compressor located with Evaporator Section)

Please refer to the


SATS Heat Rejection
Engineering Manual for
specification and performance data on SATS
Remote Condensers &
Condensing Units

SATS Remote Outdoor


Propeller Condenser

SATS Remote Outdoor


Propeller Condenser

SATS Remote Indoor


Centrifugal Condenser

{
SATS Remote Indoor
Centrifugal Condenser

OHS-012/040-HAR & OHS-048/060-AR


(Single Compressor - Split Evaporator)
(Ducted Only)

OHS-012/040-AR

SATS Remote Outdoor


Propeller Condenser

(Split Evaporator, "Ductless" Spot Cooler)

Air Technology Systems, Inc


SATS Remote Outdoor
Propeller Condenser

SATS Remote Indoor


Centrifugal Condenser

OHS-040/120-(D)AR

OHS-012/032-AR

(Dual Compressors - Split Evaporator)


(Ducted Only)

(Split Evaporator, Ducted Evaporator)

SPLIT AIR COOLED -


AIR HANDLING UNIT w/ INDOOR or OUTDOOR REMOTE CONDENSING UNIT


(compressor located with Condensing Section)

SATS Outdoor Propeller


Remote Condensing Unit

SATS Outdoor Propeller


Remote Condensing Unit

SATS Indoor Centrifugal


Remote Condensing Unit
SATS Indoor Centrifugal
Remote Condensing Unit

OHS-012/040-AHU

(Split , DX - Air Handling Unit)


("Ductless" Spot Cooler)

OHS-048/060-AHU

(Split , DX - Air Handling Unit)


(Ducted Only)

SATS Outdoor Propeller


Remote Condensing Unit

OHS-048/120-DAHU

{
SATS Indoor Centrifugal
Remote Condensing Unit

(Split , DX - Air Handling Unit)


(Ducted Evaporator)

2-3

SATS Outdoor Propeller Remote


Condensing Unit

(Dual Circuit, Split, DX - Air Handling Unit)


(Ducted Only)

{
OHS-012/040-AHU &
HAHU

SATS Remote Indoor


Centrifugal Condenser

Air Technology Systems, Inc.

SATS Indoor Centrifugal


Remote Condensing Unit

More Space Saving Configuration Choices


WATER COOLED SYSTEMS

SELF-CONTAINED WATER COOLED SYSTEMS

Remote Water Source


(supplied by others)

Remote Water Source


(supplied by others)

OHS-012/040-W

OHS-012/032-W

(Self-Contained, "Ductless" Spot Cooler)

(Self-Contained, Ducted Evaporator)


Remote Water Source
(supplied by others)

OHS-012/040-HW & OHS-048/060-W

Remote Water Source


(supplied by others)

OHS-048/120-DW

(Single Compressor, Self-Contained, Ducted Only)

(Dual Compressors, Self-Contained, Ducted Only)

GLYCOL COOLED SYSTEMS


SELF-CONTAINED GLYCOL COOLED SYSTEMS
Please refer to the SATS
Glycol Systems Engineering Manual
for specification and
performance data on
SATS Glycol Pump Packages and Drycoolers

OHS-012/040-HG
&
OHS-048/060-G with
SATS DRYCOOLER & PUMP PACKAGE

(Single Compressor, Self-Contained, Ducted Only with


Outdoor Propeller Drycooler & Pump Package)

OHS-012/040-G with
SATS DRYCOOLER & PUMP PACKAGE
(Self-Contained, "Ductless" Spot Cooler with
Outdoor Propeller Drycooler & Pump Package)

OHS-048/120-DG with
SATS DRYCOOLER & PUMP PACKAGE

OHS-012/040-G with
SATS DRYCOOLER & PUMP PACKAGE

(Dual Compressors, Self-Contained, Ducted Only with


Outdoor Propeller Drycooler & Pump Package)

(Self-Contained, Ducted Evaporator with


Outdoor Propeller Drycooler & Pump Package)

CHILLED WATER SYSTEMS


Remote Liquid Chiller
(supplied by others)

Remote Liquid Chiller


(supplied by others)

OHS-012/040-C

(Self-Contained Air Handler)


("Ductless" Spot Cooler Evaporator)

Remote Liquid Chiller


(supplied by others)

OHS-012/040-C

(Self-Contained Air Handler)


(Ducted Evaporator)

Air Technology Systems, Inc.

OHS-048/120-C

(Self-Contained Air Handler)


(Ducted Only)

2-4

Model Nomenclature - "OHS" Systems


Nomenclature

CeilAiR - Ceiling Mounted A/C's


OHS-040-G-FC
AWS
FC
LP
OA
SF
SP

OHS = OverHead System


COS = CyberONE System
MCS = Modular Cyber System
VFS = Vertical Floor System
FCS = Floor Console System
SCS = STULZ Condensing Section*
GPS = Glycol Pump System*

- CeilAiR Systems

AHU
AR
AS
C
CAA
D( )
G
H( )

( )AA
( )SA
( )AA
EC

RCU-I

RCU-O
W

Nominal Capacity in 1,000's of BTU/H

=
=
=
=
=
=
=
=

=
=
=
=

=

=
=

=
=
=
=
=
=

"Alternate Water Source"


"Free-Cooling"
"Low Profile Configuration"
"Outside Air"*
"Same-Face" Air Pattern
"Special Configuration"

Air Handling Unit


Remote (Split) Air Cooled
Self-Contained Air Cooled
Chilled Water System
Indoor Centrifugal Condenser*
Dual (Two) Circuit System
Glycol Cooled
Horizontal Discharge, "H- Series"
Configuration (e.g.: HAHU, HAR, HW, HG, & HC)
Outdoor Prop Fan Condenser for 0 F*
Outdoor Prop Fan Condenser for -20 F*
Outdoor Prop Fan Condenser for -30 F*
Outdoor Prop Fan Condenser for -20 F*
w/ EC Fans
Indoor Centrifugal Remote Condensing
Unit*
Outdoor Remote Condensing Unit*
Water Cooled

Air Technology Systems, Inc


* SATS Condensers & Condensing Units
can be found in our "Heat Rejection"
engineering manual.
* SATS OHS Oustide Air Units can be
found in our "CeilAiR Outide Air"
engineering manual.
* SATS Pump Packages and Drycoolers can
be found in our "Glycol Systems"
engineering manual.

2-5

Air Technology Systems, Inc.

Model Nomenclature Specifications

AIR COOLED SELF-CONTAINED

Integral Self-Contained
(Models OHS-012/040-AS)

The system shall be a self-contained, ceiling mounted supplemental air conditioner with
factory mounted integral air
cooled condenser with centrifugal
blower.

The system shall require only


single point supply power connection and the system shall ship
from the SATS factory with a full
operating refrigerant charge.
DX - EVAPORATOR SECTIONS

Air Cooled Remote Evaporator


(Models OHS-( )-()AR)

The system shall be a remote


(split) air cooled, ceiling mounted
supplemental air conditioner
evaporator. The evaporator section shall house, as a minimum,
the evaporator coil, expansion
valve, compressor, evaporator
blower/motor and associated
electrical and refrigeration components.
The OHS-( )-()AR evaporator
section shall be located at some
distance from its corresponding CeilAiR model HES-( )-()CAA
indoor or WCS-( ) outdoor air
cooled condenser.

(Note: SATS Condensers & Condensing


Units can be found in our "Heat Rejection" engineering manual.)

DX - WATER COOLED SYSTEMS

Integral Self-Contained
(Models OHS-( )-W / DW)

The system shall be a self-contained, ceiling mounted supplemental air conditioner to include
integral water cooled, coaxial
condenser with factory installed
head pressure water regulating control valve(s). Condenser
(source) water shall be provided
by a cooling tower or some other
remote water source.
The system shall require only
single point supply power connection and shall ship from the
SATS factory with a full operating
refrigerant charge.
Water Regulating Valves:

Head pressure shall be automatically controlled by a factory


installed 2-way water regulating
valve rated for 150 psig w.w.p.
(Note: 3-way and high pressure 300 to
400 psig rated valves are available as options, page 3-9.)

DX - GLYCOL COOLED SYSTEMS

Integral Self-Contained
(Models OHS-( )-G / DG)

mental air conditioner to include


integral glycol cooled, coaxial condenser with factory installed head
pressure glycol regulating control
valve(s). Condenser (source) glycol solution shall be provided via
a CeilAiR model GPS-( )-( ) / HES-(
)-LGA remote glycol pump package and drycooler system.
The system shall require only
single point supply power connection and shall ship from the
SATS factory with a full operating
refrigerant charge.
Glycol Regulating Valves:
Head pressure shall be automatically controlled by a factory
installed 2-way glycol regulating
valve rated for 150 psig w.w.p.
(Note: 3-way and high pressure 300 to
450 psig rated valves are available as options, page 3-9.)

CHILLED WATER AIR HANDLERS

CHILLED WATER SYSTEM


(Models OHS-( )-C)

- CeilAiR Systems

The condenser shall be sized to


provide the total heat of rejection
of the system at a 95F DB ambient temperature.

The evaporator system shall


require only single point main
power supply connection and the
ystem shall ship from the SATS
factory with a dry nitrogen holding charge ready for field refrigerant (R-22) charging.

Nomenclature

"CeilAiR"
Model Nomenclature
Guide Specifications

The system shall be a ceiling


mounted chilled water supplemental air conditioner to include chilled water cooling coil,
evaporator blower and motor
and chilled water control valve.
Chilled water shall be provided by
a remote liquid chiller system.
Chilled Water Control Valve:

Cooling capacity shall be controlled with a slowly opening and


slowly closing 2-way motorized
control valve rated for 300 psig
w.w.p.
(Note: 3-way 300 psig motorized valves
and 2 or 3-way modulating valves are
available as options .)

The system shall be a self-contained, ceiling mounted supple-

Air Technology Systems, Inc.

2-6

Selected Standard Features Guide Spec's

"OHS" Model

012/040-( )

"OHS" Series

012/040-H( )

048/060-( )

048/120-D( )

Std
Opt

Std
Opt

Std
Opt

Std
Opt

Opt
Opt

Opt
Opt

Opt
Opt

Opt
Opt

Std
Opt
Opt

Std
Opt
Opt

Std
Opt
Opt

N/A
Std
Opt

Std
Std
Std
Std

Std
Std
Std
Std

Std
Std
Std
Std

Std
Std
Std
Std

Std
Opt

N/A
Std

N/A
Std

N/A
Std

Std
Opt
Std
Std
Std
Std
Std

Std
Opt
Std
Std
Std
Std
Std

Std
Opt
Std
Std
Std
Std
Std

Std
Opt
Std
Std
Std
Std
Std

Std
N/A

N/A
Std

N/A
Std

N/A
Std

SELECTED STANDARD FEATURES:


TEMPERATURE CONTROL
Cooling Only
Heating / Reheating Control

HUMIDITY CONTROL
Electrode Canister Steam Humidifier
Dehumidification Mode with Reheat

CONTROLS
A-Tech-1.1 single stage controls
A-Tech-1.2 two stage controls
C-Tech-10, A-Tech-20, C6000 T/H Microprocessor Controls

CABINET



All Aluminum Construction


Insulated SS or Polymer Condensate Drain Pan
1/2", 2 lb Density Thermal & Sound Insulation
Rubber Hanging Vibration Isolators

- Standard Features "Quick-Reference" Table

FILTERS / GRILLES
Spot Coolers with bottom supply / return filter grille
Ducted Units with flanged ducted connections

DX-REFRIGERATION CIRCUIT






R22 Refrigerant
R407C Refrigerant
Scroll Type Compressor(s), (unless otherwise noted)
High Efficiency, Aluminum Fin / Copper Tube Coils
Thermal Expansion Valve
Refrigerant Sight Glass & Filter/Drier Strainer
Refrigerant Service Valves

Air Technology Systems, Inc


BLOWERS / MOTORS

Direct-Drive Evaporator Motors


Belt-Drive Evaporator Motors

ELECTRICAL
Power Supply
Multi-Voltage Control Transformer (24V Class II)
Individual Motor Starter(s) / Contactor(s)

------------------------- See Electrical Tables Section 5 ------------------------Std


Std
Std
Std
Std
Std
Std
Std

SAFETY FEATURES
Condensate Pan Overflow Safety Switch(es)
High / Low Refrigerant Pressure Switches (DX units)
Motor Overcurrent and Overload Protection Per UL 1995

Std
Std
Std

Std
Std
Std

Std
Std
Std

Std
Std
Std

SPECIFIC MODEL STANDARD FEATURES:


AIR COOLED
Low Ambient Head Pressure Control
Integral (model OHS-()-AS) or Remote Air Cooled Condenser

------------------- Three types available 0F, -20F or -30F ------------------Std


Std
Std
Std

WATER / GLYCOL COOLED


2-way, 150 psig Water/Glycol Regulating Valves
High Pressure & 3-way Valves
Coaxial, Tube-in-Tube Heat Exchanger

Std
Opt
Std

Std
Opt
Std

Std
Opt
Std

Std
Opt
Std

Std

Std

Std

Std

N/A
N/A
N/A

N/A
N/A
N/A

N/A
N/A
N/A

Std
Std
Std

Std
Opt

Std
Opt

Std
Opt

Std
Opt

Std
Std

Std
Std

Std
Std

Std
Std

ALL SPLIT DX SYSTEMS


Liquid Line Solenoid Valve to Prevent Liquid Slugging

DUAL CIRCUIT DX SYSTEMS


Two(2) Independent Refrigerant Circuits
Two(2) Equal Horsepower Scroll Compressors (1 per circuit)
A-Tech-1.2 two stage controls

CHILLED WATER SYSTEMS


2-way, 300 psig Motorized Valve
Modulating, High Pressure & 3-way Valves

CODE CONFORMANCE

NRTL Conformance Compliance to UL 1995 Standard


NYC MEA-163-88-E / Chicago Code Approval

3-1

Air Technology Systems, Inc.

Guide Specifications (ISO-9001:2001 Registered)

Electrical System

SATS operates in an ISO-9001:2001


registered quality control environment. Each SATS employee is
committed to satisfying his or her
customer expectations with the
highest level of consistent, measurable and continuous quality
improvement.

GENERAL GUIDE
SPECIFICATION
General Description

The system shall be manufactured by


ISO-9001 Quality Registered Stulz Air
Technology Systems, Inc. in Frederick,
Maryland, USA.

Component Access
The air conditioner shall be fully
accessible in-place through easily
removable side access panels.

Cabinet Construction
The cabinet and access panels shall
be fabricated from aluminum for corrosion protection and to minimize the
systems weight. The panels shall be
lined with 2 lb/ft2 high density sound
and thermal insulation and sealed
with self-extinguishing gasketing conforming to NFPA 90A and 90B.

The evaporator coil shall be mounted


in an insulated stainless steel condensate pan.

DX- Refrigeration System


Thermal Expansion
Valves

The system shall incorporate overcurrent and overload protection in accordance with UL 1995 requirements.
Each blower motor, compressor,
electric heater stage and humidifier
(if applicable) shall be provided with
a factory mounted and wired starter /
contactor.
The control circuit shall be a 24 VAC
Class 2 low voltage circuit including
a circuit breaker for protection. Low
voltage, high voltage and grounding
wires shall be color coded and shall
be individually numbered at each
end for ease of service tracing. All
wiring shall be in accordance with the
National Electric Code (NEC).

Overflow Safety Float Switch

A condensate pan water level switch


shall be incorporated to shut the system down if a condensate overflow
condition is sensed.

Filter Drier/
Strainers
Sight Glasses

All refrigeration piping shall be refrigerant grade tubing. Each refrigerant


circuit shall include, as a minimum,
refrigerant drier/strainer, sight glass
with moisture detector, thermal
expansion valve with rapid bleed port
feature and external equalizer, evaporator coil, compressor, high pressure
switch with manual reset and a low
pressure switch with automatic reset.
Split / Remote systems shall have
a liquid line solenoid for refrigerant isolation to prevent liquid slugging. All high pressure joints shall be
brazed, and the entire system shall
be pressure tested at the factory with
dry nitrogen, evacuated to at least
50 microns and fully charged with
refrigerant.

- Standard Equipment

The system shall be a ceiling mounted


supplemental air conditioner designed and built to the highest of
industry standards. The system shall
be complete and factory run-tested
before shipment. The system shall be
listed and labeled in compliance with
UL 1995 (# SATS-1995) by an approved Nationally Recognized Testing
Laboratory (NRTL). The system shall
be MEA NYC (MEA-163-88-E) and
Chicago Code approved.

pered aluminum fins with a raisedlanced fin design for maximum heat
transfer. Coil end plates shall be hot
dipped galvanized.

Guide Spec's

QUALITY ASSURANCE

Standard Equipment

Note: All split / remote DX systems


ship with a dry nitrogen holding charge.
All self-contained DX systems ship with a
full refrigerant (R-22) operating charge.

Remote Stop / Start

Included in the system's electrical


control circuit shall be a 2-pin terminal connection for remote stop / start
of the CeilAiR air conditioner by a
remote source.

Scroll Compressors

Coils
Evaporator systems shall be configured for a draw-thru air pattern
to provide uniform air distribution
over the evaporator coil face. The
coils shall be seamless drawn copper
tubes, mechanically bonded to tem-

Air Technology Systems, Inc.

Each compressor shall be a high efficiency, high reliability and low sound
Scroll Compressor, unless specifically
noted otherwise.

3-2

Guide Specifications Guide Spec's

The compressor shall be complete


with charging and service schraeder
ports, internal vibration isolation,
internal thermal overloads, internal
pressure relief valve, internal discharge gas vibration eliminator and
external vibration mounting isolation.

Chilled Water Systems


(Models OHS-()-C)

Standard Equipment

motor shall be factory wired for the


correct speed to produce the specified air quantity. The motor(s) shall
have internal overload protection.
(277V & 460V direct-drive motors shall be
2-speed.)

Belt Driven Systems

Cooling Coil:
The chilled water coil shall be constructed of seamless drawn copper
tubes, mechanically bonded to tempered aluminum fins for maximum
heat transfer. Coil end plates shall be
hot dipped galvanized.

- Standard Equipment

The cooling coil shall be mounted in


an insulated stainless steel condensate drain pan.
Control Valve:

Temp & Humid Control


The standard CeilAiR system is configured as a "cooling only" system.
Heating, reheating and/or humidity
control can be optionally added to
provide total space temperature and
humidity control. (Please see pages
3-5 thru 3-7 for more details.)

A-Tech-1.1
The blower(s) shall be belt driven with
double width, double inlet housing and forward curved blades and
permanently lubricated ball bearings
sized for an average 100,000 hours
of service life. The blowers shall be
dynamically and statically balanced to
minimize vibration and operate in the
Class I range.

Standard
single stage
DX and nonproportional
CW Heat/Cool
programmable
digital thermostat.

A-Tech-1.2

Standard dual
stage DX Heat/
Cool programmable digital
thermostat.

Air Technology Systems, Inc


Cooling capacity shall be controlled
by a factory installed slowly opening
and slowly closing 2-way motorized
control valve rated for a maximum
300 psig w.w.p.

The blower(s) shall have an adjustable base for belt tensioning and a
locking system to prevent the motors from moving. The motors drive
sheaves shall have an adjustable pitch
to change the speed of the blowers.
The motor(s) shall be 1725 RPM and
shall have overload protection and
a minimum NEMA service factor of
1.15.

(Note: Please refer to page 3-10 for additional chilled water valve options.)

Optional
single or dual
stage DX or
non-proportional CW
Temperature and Humidity Microprocessor Controller with alarms.

Blowers / Motors

A-Tech-20 & C6000

Optional all purpose Advanced


Temperature
and Humidity
Microprocessor
Controllers with
alarms and optional remote
BMS communications
connections.

Direct Drive Systems

The blower(s) shall be direct driven


with double width, double inlet housing and forward curved blades. The
blower(s) shall be dynamically and
statically balanced to minimize vibration and operate in the Class I range.
The blower(s) shall be corrosion
protected with a painted housing and
impeller wheel.

(NOTE: Please refer to pages 3-6


& 3-7 for additional specification
details on all CeilAiR ceiling AC
control options.)

The three speed (208V) evaporator

3-3

C-Tech-10

Air Technology Systems, Inc.

Guide Specifications -

Standard Equipment

DX - Heat Rejection

"Ductless" Spot Cooler

AIR COOLED

(Models OHS-012 thru 040-( ) only.)


The air conditioner shall be designed
for installation in a standard 2' x 4'
ceiling grid for ductless supply and
return evaporator air through a factory provided bottom supply & return
filter grille.

Please refer to the SATS Heat Rejection Engineering Manual for specification details of air cooled condensers
and condensing units.

WATER / GLYCOL COOLED

Guide Spec's

Evaporator Air
Patterns & Filtration

Water/Glycol Cooled
Condensers
Coaxial Tube-In-Tube:

(Available on all model sizes)


The air conditioner shall be provided
with evaporator supply and return air
duct connections.
EVAPORATOR
AIR IN
EVAPORATOR
AIR IN

EVAPORATOR
AIR OUT

EVAPORATOR
AIR OUT

The unit shall have slide out, 1"


deep Class 2 (per U.L. Standard 900)
filter(s) easily accessed through a side
access panel. The filter shall have
a rating of at least 80% average
arrestance as measured by ASHRAE
Standard 52-76 test method.


Each evaporator refrigerant circuit
shall be provided with a factory
installed single pass, counterflow
configured, tube-in-tube coaxial
condenser; designed and tested for a
450 psig. w.w.p.
2-Way, 150 psig Regulating Valve
(Standard on all OHS-( )-()W/G)
Each refrigerant circuit's head pressure shall be controlled by a factory
installed 2-way water / glycol regulating valve rated for 150 psig. w.w.p.
(Note: 3-way and high pressure water/
glycol regulating valves are optionally
available, page 3-9.)

Standard Equipment

Ducted Evaporator

(Models OHS-012/120-()W/G)

The air conditioning unit shall have a


drop out, 1" deep, class 2 (per U.L.
Standard 900) filter easily accessed
through the hinged return grille. The
filter shall have a rating of at least
80% average arrestance as measured
by ASHRAE Standard 52-76 test
method.

(Note: Please refer to Section 6 for


standard CeilAiR cabinet configurations.
Consult your local SATS sales representative for special applications.)

Air Technology Systems, Inc.

3-4

Optional Features -

Guide Specifications

Optional Features

Optional Features Index

OPTION . ............................................. page


Microprocessor Controls
A-Tech-1.1
A-Tech-1.2
C-Tech-10
A-Tech-20
A-Tech-20
C6000
C6000

(Digital Thermostat, 1-stage)................. 3-6


(Digital Thermostat, 2-stage)................. 3-6
(Micro Temp/Humid w/ Alarms)............. 3-6
Advanced Microprocessor..................... 3-7
Remote Communications...................... 3-7
Advanced Microprocessor..................... 3-8
Remote Communications...................... 3-9

Humidity Control Options

Free Cooling - Valve Combinations


150 psig Rated System: (standard)....................... 3-11
- 3-way, 150 psig, DX Condenser Valve(s)
- 3-way, 300/400 psig, FC Coil Valve
300 psig Rated System: (optional)........................ 3-11
- 3-way, 350 psig, DX Condenser Valve(s)
- 3-way, 300/400 psig, FC Coil Valve
400 psig Rated System: (optional)........................ 3-11
- 3-way, 450 psig, DX Condenser Valves
- 3-way, 400 psig, FC Coil Valve

Steam Humidifier.................................................... 3-10

Capacity Modulation Options

Dehumidification Cycle

Index

- Electric Reheat / Heat....................................... 3-10


- Hot Gas Reheat................................................ 3-10
- Hot Water Reheat / Heat.................................. 3-10
- Steam Reheat / Heat........................................ 3-10
- SCR Fired (0-10 Vdc) Electric Reheat................. 3-10

Snap-Acting, Hot Gas Bypass.................................. 3-11


Full-Floating, Hot Gas Bypass.................................. 3-12
Dual Compressor / 2-Stage Systems........................ 3-12
Modulating Chilled Water Control Valves................ 3-12

Air Technology Systems, Inc


ACCESSORIES

High Static Pressure Blowers

High Static Belt-Drive Blower Upgrade............... 3-10/11


(Up to 2.0" ext. static pressure)

3-Phase Power Supply............................................ 3-12


277/1/60 Power Supply.......................................... 3-12
Condensate Pump............................................. 3-12/13

High Efficiency Filtration (IAQ)

Smoke Detector...................................................... 3-13

IAQ High Efficiency Filters...................................... 3-11

. ......................................................... 3-13

Remote Water / Leak Detector................................ 3-13


Acoustical Compressor Sound Jackets..................... 3-13

Head Pressure Control Options


Air Cooled - Low Ambient Control
0F Ambient..................................................... 3-11
-20F Ambient................................................. 3-11
-30F Ambient................................................. 3-11

Water/Glycol Cooled - Regulating Valves
2-way, 150 psig (Standard)............................... 3-11
2-way, 350 psig................................................ 3-11
2-way, 450 psig................................................ 3-11
3-way, 150 psig................................................ 3-11
3-way, 350 psig................................................ 3-11
3-way, 450 psig................................................ 3-11

3-5

Firestat

Low Entering Condenser Water.............................. 3-14


Main Power - Non-Fused Service Switch.................. 3-14
Refrigerant Lines with
Quick Disconnect Couplings................................... 3-14

Energy $aving Cooling Options


Free-Cooling Cycle.................................................. 3-14
Alternate Water Source Cycle................................. 3-14

Air Technology Systems, Inc.

Optional Features -

A-Tech-1.1

5-Levels of microprocessor control offerings allow you the flexibility of selecting


the best control scheme for their unique
requirements:

A-Tech-1.1

Standard single
stage DX and
non-proportional
CW Heat/Cool
programmable
digital thermostat.

Standard dual
stage DX Heat/
Cool programmable digital
thermostat.

C-Tech-10
The CeilAiR ceiling air conditioner
shall be provided with SATS'
"slimline", ultra-thin profile, 1stage cool / 1-stage heat, remote
wall mounted programmable
digital microprocessor based controller.
Note: The A-Tech-1.1 thermostat is standard on all single stage DX and non-proportional chilled water systems.

A-Tech-1.2

C-Tech-10

Optional single
or dual stage
DX or non-proportional CW
Temperature
and Humidity Microprocessor
Controller with alarms.

A-Tech-20

Optional all purpose Advanced


Temperature
and Humidity
Microprocessor Controller
with alarms and
optional remote BMS communications connections.

C6000

Optional
all purpose
Advanced
Temperature
and Humidity
Microprocessor Controller with
alarms and optional remote BMS
communications connections.

Temperature & Humidity


Microprocessor Controller

The CeilAiR ceiling mounted air


conditioner shall be provided with
SATS' C-Tech-10 Microprocessor
based Temperature and Humidity controller with Alarms. The
controller shall incorporate a userfriendly operating environment
with backlit graphic LCD display.
Standard Features:

The CeilAiR ceiling air conditioner


shall be provided with SATS'
"slimline", ultra-thin profile,
2-stage cool / 2-stage heat, remote wall mounted programmable digital microprocessor based
controller.
Note: The A-Tech-1.2 thermostat is standard on all dual stage DX systems.

Common A-Tech-1.1/1.2 Features:


Auto changeover for Heat/Cool Modes
Selectable F or degrees C display
Fan selector for continuous fan
operation
Built-in short cycle protection
Internal switch to lock-out the keypad
to prevent unauthorized tampering
Electronic calibration
45 second fan purge after heating
and cooling call
Day/Night button for user selectable
alternate setpoint manual setback

Air Technology Systems, Inc.

Display / Keypad:
Backlit LCD graphic display with
characters to show the operating mode, time, set points and
actual readings
Internal Temperature and Humidity Sensor
3 Set Point Programmable
(Normal, Temporary, Night) per
day, 7 days per week
Summary Alarm Contact

- Microprocessor Control Options

A-Tech-1.2

12 hour or 24 hour clock


Daylight Savings Time button to
adjust the clock +/- 1 hour
Copy button to allow one program to
be copied to subsequent days
Override feature
Does not require a battery
Solid state electronic output

Optional Features

CeilAiR Control
Options

Microprocessor Control Options

Visual/Audible Alarm Indication:


High Temp (HI T)
Low Temp (LO T)
High Humid (HI H)
Low Humid (LO H)

Dirty Filter (E FL)


Sensor Failure
Comm. Failure
Summary (E ID)

Summary Alarm (E ID): condensate


overflow/water detection; smoke detec-
tion; firestat (if applicable)



Maintenace Alarms: based on user


defined component run-times schedules
(compressor 1 (HR 1) & 2 (HR 2); evap
blower (HR F).

3-6

Optional Features Optional Features

System Operation:
Fan Continuous or on Demand
Auto-Restart Upon Power Loss
Remote Stop/Start Connection
Short Cycle Protection
Cold Start Time Delay
Pump-Down Cycle
Optional Features:

Remote Temp/Humid Sensor:


Optional remote wall mounted
temperature and humidity sensor
Remote Sensor Cable Options:
75 ft. cable length (standard option)
150 ft. cable length

A-Tech-20

Microprocessor Control Options

Remote Stop / Start Connection


Selectable Automatic or Manual
Restart Upon Power Loss
Sequential Load Activation Upon
Power Loss Restart
Alarm Delay for Space T/H Recovery Upon Power Loss Restart
Multi-Level Password Security
Protection
Short Cycle Protection
Cold Start Time Delay
Pump-Down Cycle
Service Mode
Time-Clock with Override
Night-Setback with Override

three methods:
1)
2)
3)

Manual ChangeOver
Automatic Timed (1-30 days)
Automatic ChangeOver on Unit
Failure (if applicable):

Interconnect Cable Options:


75 ft. cable length (standard option)
150 ft. cable length

Capacity Assist-Mode:
(Additionally Optional)

- Microprocessor Control Options

30 ft. cable length (standard)


75 ft. cable length
150 ft. cable length

In addition to switchover via


manual, automatic timed or
failure, the CyberLAN Multi-Unit
Sequencing Capacity AssistMode can initiate switchover to
standby unit operation to assist in
the temperature and/or humidity
control of the space.

Remote Sensor Cable Options:

Capacity Assist Sensor Cable Opts:

75 ft. cable length (standard option)


150 ft. cable length

75 ft. cable length (standard option)


150 ft. cable length

Display/Sensor Options:
Remote Display Cable Options:

Air Technology Systems, Inc


ALARM CONDITIONS:

Advanced Microprocessor
Temperature & Humidity
Controller with Alarms

The CeilAiR ceiling mounted air


conditioner shall be provided with
SATS' A-Tech-20 Advanced Microprocessor based Temperature and
Humidity controller with Alarms.
The controller shall incorporate a
"user-friendly" operating environment, to allow easy system setup
and operation.
Standard Features:









3-7

4 x 20 character liquid-crystal
alpha-numerical display
Field Configurable
30 Ft. Remote Display Cable
Unit Mounted T/H Sensor
Current Unit Status
Component Run-Time History
Visual & Audible Alarm Indication
Summary Alarm Contacts
Alarm History

The A-Tech-20 alerts to the following


alarm conditions (if applicable):
High Temperature
Low Temperature
High Humidity
Low Humidity
High Head Press
Low Suction Press
Loss of Air Flow
Loss of Power

Dirty Filter
Smoke Detection
Firestat
Leak Detection
GC Pump Failure
Sensor Failure
Comm. Failure

CyberLAN w/ A-Tech 20
Remote Communications
(Optional)

REMOTE BMS CONNECTION


(ModBus Gateway)

The operator may select which alarms


are active or inactive.
CyberLAN Networking Options:
Multi-Unit Sequencing:

Multiple CyberAiR air conditioners


incorporating A-Tech-20 controls
can be configured in groups of up
to 6 (six) units to allow for "N+1"
redundancy/backup critical application operation.
The A-Tech-20 is programmed to
automatically change from current
primary unit operation to secondary standby unit operation via

Air Technology Systems, Inc.

A-Tech-20 Inputs & Outputs can


be remotely monitored (address
readable) and remotely controlled
(address writable) via any building management system (BMS) /
local area network (LAN) control
system that can communicate via
a ModBus protocol.
16 Units Per CyberLAN ModBus:
Each ModBus Gateway can accommodate up to 16 (sixteen) A/C
units in a group.

Optional Features The CeilAiR ceiling-mounted air


conditioner shall be provided with
SATS C6000 Microprocessor based
Temperature and Humidity controller with Alarms. The controller shall
incorporate a user-friendly operating environment, to allow easy
system setup and operation.
The C6000 is a complete microprocessor based control system
designed for operating, controlling
and monitoring the precision air
conditioning unit.

The controller shall be mounted in


an indoor rated steel box. The box
shall be powder coated to match
the environmental control unit.
The box shall contain the controller
board, the IO board, and all necessary transformers and internal wiring. The control box shall be wall
mounted and field wired to the
environmental control unit.
Display Key Pad

The Display Key Pad shall feature an


easy to read, liquid-crystal alpha-numerical display. The keypad/display
allows the operator to visually monitor and customize unit functions
and settings. The self-explanatory,
keypad nomenclature shall aid in
the ease of location of system programming features.

Sensor Location Options


As a standard, the C6000 temperature and humidity sensor shall be
factory unit mounted in the return
air stream of the Precision AC unit,
after the return air filter(s).
System Setup & Adjustments
The C6000 shall be completely
factory preprogrammed, and therefore, most applications will require
no field setup. However, the default set points and their ranges
are easily adjusted from C6000
keypad/display.
Unit Status Display
The C6000 keypad displays current
unit functions and room status:
Current Dry Bulb Temp Set Point
Current Relative Humidity Set
Point
Current Unit Status
System ON/OFF
Cooling
Heating
Humidifying
Dehumidifying
Standby Mode
Reheating
Manual Mode
Actual Room DB Temperature
Actual Room Relative Humidity
Run Times
The historical run-time in hours of
the following major components
shall be available directly from
the C6000 keypad/display: (if applicable)
Blower Motor(s)
Humidifier

Air Technology Systems, Inc.

Chilled Water Valve


Alarm Conditions
Alarm conditions activate an audible and visual indicator. An alarm
shall be acknowledged through a
Reset button located on the keypad
display.
The C6000 alerts to the following
alarm conditions (if applicable):
High Temperature
Low Temperature
High Humidity
Low Humidity
Smoke Detection
Firestat
Leak Detection
Sensor Failure
Dirty Filter
Loss of Air Flow
Summary Alarm Contact
A summary alarm dry-contact (n/o)
connection shall be available for
remote annunciation of an alarm
condition. An additional user-defined custom alarm dry-contact
shall also be available on most
system configurations.
Alarm History
The C6000 controller provides users
with a recorded history of the last
80 alarms, including the time and
date of the alarm occurance.
Control Inputs/Outputs
The C6000 is capable of both
digital (on/off) and analog input
and output device control. Prior to
shipment, each Precision AC units
C6000 is factory program configured to match the units system
operational requirements.

- Microprocessor Control Options

The C 6000 controller shall include


a full-featured LED display for visual
indication of the units operating
conditions.

Field Configurable
The C6000 controller is field program configurable and capable of
matching the unique needs of any
data center, telecommunication or
other critical area.

Optional Features

C6000

Microprocessor Control Options

Temperature Anticipation
The C6000 shall incorporate a
self-calibrating and self-adjusting
control logic that adjusts the re-

3-8

Optional Features Optional Features

sponse of the SATS air conditioner


to changes in temperature and
humidity. The system shall provide
premium setpoint accuracy while
controlling the room conditions
rate of change, minimizing the
equipment energy consumption and
maximizing the systems operating
life and reliability.

- Microprocessor Control Options

Power Loss Restart


In the event of a loss of power to
the system, the C6000 can be configured for Automatic or Manual
Restart. The C6000s non-volatile
memory enables the system to restart when power is restored, without the loss of the last stored set
points and other system configuration settings.
Sequential Load Activation
To minimize the total in rush current
loads during system startup/restart,
the C6000 controller shall be configured for time-delay sequence
startup. The user can designate
specific unit restart time-delays, as
well as, each units respective electric
heater and/or humidifier. Unit restart
delay can be adjusted from 0 to 10
minutes.

Microprocessor Control Options

Diagnostic & Service Mode


The C6000 shall incorporate a
unique self-diagnostics algorithm
that continually tests systems functions and hardware operation. In
the event of such a failure, the user
will be alerted to the condition via a
visual and audible alarm.
Control Board
The Control Board shall initiate a
self-test of the control system.
Input Diagnostics
All system inputs and output devices
shall be continuously monitored for
proper operation.
Night Set-back
The C6000 shall include Night SetBack occupied/non-occupied energy
saving modes. This feature enables
the user to customize each units
daily 5-day/weekly and 2-day/weekend operational schedule.

MIB GATEWAY (Optional)


C-6000 Inputs & Outputs shall be
remotely monitored (address readable)
and remotely controlled (address writable) via any building management
system (BMS)/local area network (LAN)
control system that can communicate
via a ModBus protocol. Each C-6000
configured for BMS communication
shall incorporate an RS-485 Serial Communication Port that is field
connected to a factory provided wall
mounted MIB Gateway.

MIB-FS GATEWAY (Optional)


C-6000 Inputs & Outputs shall be
remotely monitored (address readable) and remotely controlled (address
writable) via a building management
system (BMS)/local area network (LAN)
control system. Available Protocols,
Modbus RTU, Modbus TCP/IP, Bacnet
IP, Bacnet MSTP, Bacnet Ethernet,
Metasys N-2, and Lonworks.

Air Technology Systems, Inc


Each C-6000 configured for BMS communication shall incorporate an RS485 Serial Communication Port that is
field connected to a factory provided
wall mounted MIB Gateway. The
MIB-FS requires field configuration.
Number of units, type of protocol
employed, and individual data-points
monitored must be configured in the
MIB-FS prior to use.

Recovery Delay
After a power loss, the C6000s
Recovery Delay feature allows the
system to operate without initiating
any high or low temperature or humidity alarms for a delayed period.
This feature allows time (15 to 60
minutes adj.) to pull-down the
conditioned spaces load without
nuisance alarms during initial startup
or power loss restart.
Security
Multiple security levels prevent
unauthorized adjustment of critical
system control parameters.

3-9

Remote BMS Connection

Air Technology Systems, Inc.

Optional Features -

Hot Water Reheat/Heat

Electric Reheat/Heat

A factory installed copper tube,


aluminum fin heat/reheat coil and
2-way control valve shall be provided
to control the flow of hot water for
automatic sensible reheating mode
during the dehumidification cycle and
automatic heating mode as required.

Humidity Control

Dehumidification Cycle
The ceiling air conditioner shall be
provided with a refrigeration based
dehumidification mode. Moisture
shall be condensed on the cooling
coil and discharged through the
condensate drain.
Reheat (electric, hot gas, hot water
or steam) shall be provided to offset
sensible cooling during the dehumidification cycle.

Hot Gas Reheat:


(Models OHS-()-AS, AR, W & G only)

Scroll
Compressor

Hot Gas
Reheat Valve
Flooded
Head Pressure
Control Valve
Relief
Valve

Refrigerant
Reclaim Port
Liquid Refrigerant
Receiver

Equalizer
Line

Remote Air
Cooled Condenser

LP

HP

Sight
Glass

Hot Gas
Evaporator
Cooling Coil Reheat Coil

Feeler
Bulb

Air
Flow

Steam Reheat/Heat
A factory installed copper tube, aluminum fin heat/reheat coil and
2-way control valve shall be provided
to control the flow of steam for
automatic sensible reheating mode
during the dehumidification cycle and
automatic heating mode as required.
(Note: Steam trap and steam piping
specialities shall be provided by others not
SATS.)

SCR Fired Reheat/Heat


The electric heat/reheat shall be
controlled through a Zero Firing
Silicon Controlled Rectifier (SCR) with
an extruded aluminum heat sink and
solid state logic system to provide
close dry bulb temperature control of
the conditioned air.
A-Tech-20 proportional (0-10 Vdc)
microprocessor controls shall be
provided with the SCR Fired Electric
Reheat option.

High Static Pressure


Belt-Drive Blowers

- Guide Specifications

The humidifier shall be an electrode


steam canister type and shall have an
adjustable humidity output setting
from 25 to 100% of the full rated
humidifier capacity, an automatic
flush cycle that senses the current
consumption of the humidifier and
controls mineral concentration of the
water. A Change Cylinder light
shall notify service personnel when
the humidification output is below
rated requirements and when maintenance is due.

Heaters shall use fast reacting nichrome wire heater elements which
cool quickly when turned off eliminating residual heat problems.

Equalizer
Line

Canister Steam Humidification

A factory mounted and wired electric


resistance heater shall be included to
provide automatic sensible reheating
mode during the dehumidification
cycle and automatic heating mode
as required. Electric heaters shall be
provided with thermal / magnetic
circuit breakers which shall protect
each conductor. The heater elements
shall be housed within a stainless
steel frame with mounted supports.
Included shall be one automatic
resetting over-temperature safety
device (pilot duty), and a non-resettable over-temperature safety device
(located in main power line).

Optional Features

SELECTED OPTIONS

Guide Specifications

Solenoid
Valve
Refrigerant
Drier / Strainer
Thermal Expansion
Valve

A factory installed copper tube,


alumninum fin hot gas reheat coil
and valve shall be provided for
automatic sensible reheating mode
during dehumidification cycle. Hot
compressor discharge gas shall be
diverted from the condenser to the
hot gas reheat coil providing energy
free sensible reheating.
(Note: Hot Gas Reheat is not available
on systems incorporating Free-Cooling
or Alternate Water Source, because no
method of reheat would be available
during non-compressorized FC or AWS
operation.)

Air Technology Systems, Inc.

The CeilAiR ceiling air conditioner


shall be provided with a high static
pressure belt-driven evaporator
blower to provide standard unit CFM
@ ____ " e.s.p.
(Note: Due to the probable change in
standard unit blower motor horsepower
for the High Static Belt-Drive Blower

3-10

Optional Features Optional Features

option, please consult your local SATS


sales representative for the following unit
specification changes:



Blower Motor Horsepower


Net Cooling Capacity
Electrical Data
Discharge Blower Data

Unit AIr Flow Rate (CFM) will match the


standard data as shown in Section 4
of this manual for each respective unit
model.)

Filtration

Guide Specifications

fan speed head pressure control for


year-round air conditioning system
operation down to 0F DB minimum
ambient air temperature.
(Note: 0F fan cycling head pressure control is a standard feature for all CeilAiR air
cooled condensers and condensing units
incorporating direct drive condenser fans.)

FREE-COOLING SYSTEMS

-20F, Variable Speed Control


(Model WCS-( ) Condensers)
The air cooled system shall incorporate a low ambient variable speed fan
head pressure control for year-round
system operation down to -20F DB
minimum ambient air temperature.
-30F, Flooded Control
Remote Air
Cooled Condenser
(Optional)

Flooded
Head Pressure
Control Valve

Relief
Valve

Liquid Refrigerant
Receiver

HP

Evaporator
Cooling Coil

LP

Sight
Glass
Refrigerant
Reclaim Port

Low
Pressure
Switch

Liquid Line
Solenoid Valve
Refrigerant
Drier / Strainer

Feeler
Bulb

Equalizer
Line

- Guide Specifications

High
Pressure
Switch



DX Water/Glycol Cooled systems with
Free-Cooling are available with the
following standard and optional DX
head pressure and Free-Cooling valve
combinations:
150 psig Rated System: (standard)

Scroll
Compressor

CeilAiR ceiling A/C's are available


with the following standard (F1) and
optional (F2, F3 & F4) high efficiency
IAQ conscious filtration:

Each refrigerant circuit's head pressure shall be controlled by a factory


(or field) installed ____-way water /
glycol regulating valve rated for ____
psig. w.w.p.

Thermal Expansion
Valve

DX Valves = 3-way, 150 psig


FC Valve = 3-way, 300/400 psig
300 psig Rated System: (optional)
DX Valves = 3-way, 350 psig
FC Valve = 3-way, 300/400 psig

Air Technology Systems, Inc


F1:
F2:
F3:
F4:

1", 20% Eff. Filters (standard)


2", 30% Eff. Filters
4", 60% Eff. Filters
2", 30% Pre / 4", 60% Eff. Final Filters

Air Pattern Type

Filters Avail.

Direct Drive 012/040:


w/ Spot Cooler:
w/ Ducted Return:

F1
F1, F2 (n/a 024)

Belt-Drive Units:
w/ Ducted Return:

F1, F2, F3 & F4

The air cooled system shall incorporate a low ambient flooded head
pressure control for year-round
system operation down to -30F DB
minimum ambient air temperature.

This option shall include a factory


installed crankcase heater, cold-start
relay, liquid refrigerant receiver with
receiver liquid level sight glass and
head pressure regulating valve for
flooded condenser operation.

Filter ratings are based on dust spot efficiency ratings per ASHRAE Test Standard
52-76.
(Note: F2, F3 & F4 optional filters create
additional static pressure and may require
the High Static Pressure Belt-Drive Option.
Please consult your local Sales Representative for details.)

Head Pressure Control


AIR COOLED - Low Ambient
0F, Fan Cycling / Fan Speed
The air cooled system shall incorporate a low ambient fan cycling /

3-11

400 psig Rated System: (optional)


DX Valves = 3-way, 450 psig
FC Valve = 3-way, 400 psig

Each refrigerant circuit's head pressure shall be controlled by a field


installed 3-way water / glycol regulating valve rated for ____ psig w.w.p.
Free-Cooling mode cooling shall be
controlled by a factory installed 3-way
motorized (on/off) control valve rated
for ____ psig. w.w.p.
Note: Modulating (0-10 Vdc) Free-Cooling mode cooling control is optionally
available via A-Tech-20 controls and
modulating 3-way FC control valve.

DX Water Cooled and Glycol Cooled


systems are available with following
standard (V1) and optional (V2-V6)
head pressure regulating control
valves:
V1: 2-way, 150 psig (standard)
V2: 2-way, 350 psig
V3: 2-way, 450 psig
V4: 3-way, 150 psig
V5: 3-way, 350 psig
V6: 3-way, 450 psig

Air Technology Systems, Inc.

3-way valves
ship loose
for field
installation.

DX - Capacity Modulation /
Freeze-Protection
SNAP-ACTING, Hot Gas Bypass
(Models OHS-()-AS, AR, W & G only)
The CeilAiR ceiling A/C shall incorporate a snap acting hot gas bypass
system to provide modulation of the
units cooling capacity and evaporator
coil freeze protection under low load
conditions.

Optional Features -

Guide Specifications

Scroll
Compressor

HP
LP

Low
Pressure
Switch

Flooded
Head Pressure
Control Valve

Feeler
Bulb

Equalizer
Line

High
Pressure
Switch

Evaporator
Cooling Coil

Hot Gas
Regulator Valve
(Optional)
Relief
Valve

Liquid Line
Solenoid Valve

Sight
Glass

Refrigerant
Liquid Refrigerant Reclaim Port
Receiver

Refrigerant
Drier / Strainer

Thermal Expansion
Valve

FULL-FLOATING, Hot Gas Bypass


(Models OHS-( )-()AHU/SCO only)

DUAL COMPRESSOR SYSTEMS


(Models OHS-( )-D())

V6: 3-way, 400 psig


Standard (On/Off) Valve Control :
A ____-way motorized (On/Off) CW
or AWS cooling control valve rated
for a maximum ____ psig w.w.p. shall
be factory unit installed. Precision
cooling control shall be accomplished
via a spring return slow open and
close valve design.
Optional (0-10 Vdc) Valve Control:
A ____-way modulating CW or AWS
cooling control valve rated for a
maximum ____ psig w.w.p. shall be
factory installed. Precision cooling
control shall be accomplished via a
0-10 Vdc A-Tech-20 analog control
signal to the proportional actuating
control valve.

ACCESSORIES

The air conditioner shall be provided


with a 2-Stage temperature controller with microprocessor based control
logic for automatic staging.

Chilled Water & AWS


Control Valves

Chilled Water and Alternate Water


Source cooling shall be controlled by
the following standard and optional
control valves:

Remote Air
Cooled Condenser
(Optional)
Scroll
Compressor

High
Pressure
Switch
Flooded
Head Pressure
Control Valve

Relief
Valve

Liquid Refrigerant
Receiver

HP

Evaporator
Cooling Coil

LP

Sight
Glass
Refrigerant
Reclaim Port

Low
Pressure
Switch

Liquid Line
Solenoid Valve
Refrigerant
Drier / Strainer

Thermal Expansion
Valve

Three phase power supply is available, as an option, on OHS-024, 032


& 040-() units.
Compressor, (belt-drive blower
motor(s) and electric heat/reheat if
applicable) shall be three phase in lieu
of standard single phase. All other
components (5/10 lb humidifier and
direct drive motor(s)) shall be single
phase, with each leg of power supply
balanced as closely as possible.
(Note: Three phase power supply is a
standard feature on models OHS-048 and
larger units.)

Models OHS-012/060-C / AWS:


V1:
V2:
V3:
V4:

Feeler
Bulb

Equalizer
Line

The air conditioner shall be a dual


scroll compressor system with two
independent refrigeration circuits to
provide 50% capacity unloading, as
well as component redundancy.

Note-1: Fast delivery orders sometimes require that the OHS system be
shipped from stock as 208/1/60. In
those cases, 277/1/60 applications are
provided with a field installed 277 to
208 step-down transformer.

Condensate Pump

3 Phase Power Supply

A main power distribution block shall


be located in the air conditioner's
electric box for single point power
connection to a 277/1/60 power supply source. All system components
(motor, heater & humidifier, if applicable) shall be rated for operation
with a 277/1/60 power supply. 277V
to 208V main power step-down
transformers shall not be required.

2-way, 300 psig (standard)


2-way, 400 psig
3-way, 300 psig
3-way, 400 psig
Air Technology Systems, Inc.

A Low-Profile condensate pump


designed for limited height ceiling
plenum installation shall be factory
provided for automatic removal of
condensate and humidifier flush
water (if applicable). The condensate
pump shall be field installed as a
standard.

- Guide Specifications

The CeilAiR ceiling A/C shall incorporate a full floating hot gas bypass
system to provide modulation of the
units cooling capacity and evaporator
coil freeze protection under low load
conditions.

(Models OHS-012 thru-040)

V5: 2-way, 400 psig (standard)

Optional Features

277/1/60 Power Supply

Models OHS-072/120-C / AWS:

Remote Air
Cooled Condenser
(Optional)

A heavy duty All-Metal condensate


pump shall be provided for automatic
removal of condensate and humidifier flush water (if applicable). The
pump shall be constructed with a
cast aluminum reservoir and impeller;
aluminum reservoir cover and impeller chamber cover; stainless steel
fasteners and a stainless steel motor
shaft. The condensate pump meets
most local codes for certification as a
"plenum rated" pump. The condensate pump shall be field installed only.

3-12

Optional Features Optional Features

The condensate pump shall be


specifically designed to operate with
the higher condensate temperatures
caused by the flush and drain cycle of
the electrode canister humidifiers.
Dual Overflow Safety Switches:
In addition to the standard condensate pan overflow safety float(s), the
condensate pump shall include an
internal overflow safety float switch
which, when wired to the A/C's remote stop/start terminals, shall open
the A/C's control circuit, thereby
shutting the A/C down in the event
of a condensate overflow.

Guide Specifications

1 to 3 Ton Models:
OHS-012/040-HAS, HAR, HAHU, HW,
HG & HC
4 to 10 Ton Models:
OHS-048/120-()AR, AHU, W, G & C

Factory Installed In-Pan


Condensate Pump
(Not Available w/ Humidifier)

Smoke Detector

water/leak detector per CeilAiR A/C


unit shall be factory provided for
remote field installation. Upon sensing a water leak, the normally closed
water detector control circuit shall
open, thereby shutting down the air
conditioner's water producing operations.

- Guide Specifications

Dual (two) - Spot Type Detectors:


Quantity 2(two) remote spot type
water/leak detectors per CeilAiR
A/C unit shall be factory provided
for remote field installation. Upon
sensing a water leak, the normally
closed water detector control circuit
shall open, thereby shutting down
the air conditioner's water producing
operations.
20 Ft. - Strip/Cable Type Detector:

Air Technology Systems, Inc


Factory Installed - Optional

A photo-electric smoke detector shall


be factory installed in the CeilAiR
evaporator section on the suction
side of the evaporator blower.

Low-Profile Condensate Pump


The CeilAiR Low-Profile condensate
pump can be factory installed as an
option on the following models:

The smoke detector shall be rated


for high air velocity applications, and
shall shut down the air conditioner
upon sensing smoke in the return air
stream.

OHS-012/040-AS, AHU, AR, W, G & C

Firestat

Factory Installed Low-Profile


Condensate Pump
In-Pan Condensate Pump
The CeilAiR In-Pan condensate pump
can be factory installed as an option
in the following models:

The air conditioner shall be provided


with a factory wired and mounted
firestat. The firestat shall shut down
the air conditioner upon sensing a
high return air temperature.

Compressor Sound Jackets


(Air Cooled 0F OHS-()-AS, and
Water/Glycol Cooled Only!)

Remote Water Detectors


Single (one) - Spot Type Detector:

Quantity 1(one) remote spot type

3-13

A 20 Ft. in length remote strip/cable


type water/leak detector shall be
factory provided for remote field
installation. In addition to the 20
ft. cable, a 24V power water detector power module shall require field
mounting and wiring to factory
provided terminal connection. Upon
sensing a water leak, the normally
closed water detector control circuit
shall open, thereby shutting down
the air conditioner's water producing
operations.

Air Technology Systems, Inc.

Each compressor shall be provided


with a factory installed acoustical
sound jacket. Each sound jacket shall
have a snap closure system for ease
of removing and reinstallation during

Optional Features -

Main Power - Electric


Non-Fused Service Switch
The main power service switch shall
be the NEMA 3R or NEMA-12 nonfused type, depending on the OHS
model selected. The disconnect
switch shall have a lockable handle.
(Note: Field installed main power service
switches shall be the standard option,
however, switches can be optionally factory mounted on select CeilAiR systems.
Factory mounting of disconnect switches
is not available on models OHS-012, 018,
024 & 032-AS incorporating the "Ducted"
Evaporator Connection option.)

Refrigerant Lines w/ Quick


Disconnects
(AHU/RCU-O Systems Only!)

Each refrigerant circuit shall be


supplied with factory assembled,
soft-copper refrigerant line set 50 ft.
in length complete with quick disconnect couplings and schraeder service
ports. The quick disconnect couples
shall be industrial grade, self-sealing,
reusable type couplings.
Suction lines shall be insulated, liquid
lines shall be uninsulated.

2) A backup DX compressorized
refrigerant circuit.
Remote Liquid Chiller
(by others)

A Free-Cooling cycle shall be provided


to take advantage of low ambient air
temperature conditions to provide
compressor-less cooling.

Alternate Water
Source Cooling Coil

Pump
(by others)
Flow
Switch

AWS
Control
Valve

FS

Alternate Water
Source Aqua-Stat
T

Remote Air Cooled


Condenser
Scroll
Compressor

Flooded
Head Pressure
Control Valve
Relief
Valve

Refrigerant
Reclaim Port
Receiver

When outdoor temperatures are


sufficiently low (setpoint adjustable),
source coolant shall be diverted from
the DX - Water or Glycol Cooled
refrigerant condenser to a chilled
water/glycol coil (free-cooling coil &
control valve). The drycooler capacity shall be increased by reversing
the typical drycooler fan(s) cycling
sequence of operation to provide the
maximum cooling effect for the coolant solution. The free-cooling coil
shall be closely sized to match the refrigerant cooling capacity to increase
the number of hours that the system
can operate in the free-cooling mode,
thereby increasing the operating savings of the installation.

LP

HP

Sight
Glass

DX - Cooling
Coil
Feeler
Bulb

Solenoid
Valve
Refrigerant
Drier / Strainer

Expansion
Valve

When chilled water is available, the


system shall operate as a chilled
water unit, without the compressor
operating. When the water temperature is too high, or the water flow
rate is not sufficient, the air conditioner shall automatically switch to
the DX compressorized refrigerant
operation.

- Guide Specifications

For Water/Glycol systems that require


entering condenser water temperatures from 65F to 45F, the system
shall be provided with a factory
installed in-line liquid refrigerant
receiver to help reduce the negative
effect the low condenser source can
have on the evaporator. A compressor crankcase heater shall also be
provided standard with this option.
(Compressor Sound Jackets are not
available with this option due to the
crankcase heater).

Free-Cooling Option
(Water/Glycol Economizer Coil)

1) A chilled water / glycol circuit


(AWS coil & control valve);

Equalizer
Line

Low Entering Condenser


Water Kit

ENERGY $AVING
COOLING OPTIONS

Optional Features

maintenance. Each sound jacket shall


have a Noise Reduction Coefficient
NRC of 85 per ASTM C-423 and a
Sound Transmission Loss STC of 11
per ASTM E-90.

Guide Specifications

Alternate Water Source


(Chilled Water by "Day"
and DX-Backup by "Night")

An Alternate Water Source cooling cycle shall be provided to utilize


building chilled water supply when
available as the primary cooling cycle
with DX - Air Cooled refrigerant cooling as a backup.
The air conditioner shall have two
cooling systems:

Air Technology Systems, Inc.

3-14

Performance Data -

Equipment Schedule Data

Performance Data

Performance Data Index


MODEL TYPE ........................................... page

DX - Air Cooled

DX with Free-Cooling

Self-Contained Air Cooled:

Self-Contained Glycol Cooled w/ FC:

1-3 Ton, models OHS-012/040-AS.................................... 4-2/3

1-5 Ton, models OHS-012/060-G-FC............................ 4-17/19


4-10 Ton, models OHS-048/120-DG-FC........................ 4-20/21

Split Air Cooled Remote w/ Condenser:

1-5 Ton, models OHS-012/060-AR.................................... 4-2/3


4-10 Ton, models OHS-048/120-DAR.................................. 4-4

Self-Contained Water Cooled w/ FC:


1-5 Ton, models OHS-012/060-W-FC............................ 4-22/23
4-10 Ton, models OHS-048/120-DW-FC....................... 4-24/25

Index

Split Air Cooled Air Handling w/ Condensing Unit:


1-5 Ton, models OHS-012/060-AHU.................................... 4-5
4-10 Ton, models OHS-048/120-DAHU................................ 4-6

DX with Alternate Water Source

Air Technology Systems, Inc


DX - Water Cooled

Alternate Water Source:

Self-Contained Water Cooled:

1-5 Ton, models OHS-012/060-W........................................ 4-7


4-10 Ton, models OHS-048/120-DW................................... 4-8

1-5 Ton, models OHS-012/060-( )-AWS............................. 4-26


4-10 Ton, models OHS-048/120-D()-AWS.......................... 4-27
42F / 50F EWT Performance Data................................... 4-28

DX - Glycol Cooled
Self-Contained Glycol Cooled:
1-5 Ton, models OHS-012/060-G......................................... 4-9
4-10 Ton, models OHS-048/120-DG.................................. 4-10

Chilled Water
Chilled Water Air Handlers:
1-3 Ton, models OHS-012/040-C.................................. 4-11/12
4-10 Ton, models OHS-048/120-C................................ 4-13/14
42F EWT Performance Data............................................. 4-15
50F EWT Performance Data............................................. 4-16

4-1

Air Technology Systems, Inc.

Air Cooled -

012-AS/AR

018-AS/AR

024-AS/AR

032-AS/AR

040-AS/AR

048-AR

060-AR

NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
13,985

19,465

25,740

32,770

35,800

59,970

65,975

10,585

15,235

19,470

23,430

27,950

47,685

52,435

Total

12,710

18,000

23,600

30,000

32,650

55,010

60,470

Sensible

10,645

15,400

19,025

22,920

27,430

46,960

51,630

Total

12,000

17,160

22,465

28,500

31,050

52,400

57,580

Sensible

10,405

15,100

18,580

22,400

26,690

46,020

50,590

Total

13,425

18,860

24,600

31,320

34,700

57,680

63,350

Sensible

11,840

16,990

20,900

24,905

30,900

52,080

57,325

Total

12,270

17,490

23,030

28,895

32,080

53,415

58,620

Sensible

11,385

16,400

20,500

23,940

29,650

50,250

55,285

Total

11,585

16,665

22,000

27,400

30,530

50,875

55,790

Sensible

11,110

16,065

20,060

23,600

28,990

49,180

54,080

75FDB/62.5FWB, 50% RH

72FDB/60FWB, 50% RH

80FDB/65FWB, 45% RH

75FDB/61FWB, 45% RH

72FDB/58.5FWB, 45% RH

Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)


ELECTRIC REHEAT / HEAT - BTU/H (Kw)
@ 208V

17,135 (5.0)

17,135 (5.0)

17,135 (5.0)

17,425 (5.1)

17,955 (5.3)

37,350 (10.9)

38,900 (11.4)

@ 230V

18,840 (5.5)

18,840 (5.5)

18,840 (5.5)

19,130 (5.6)

19,660 (5.8)

43,140 (12.6)

44,690 (13.1)

@ 460V

17,355 (5.1)

17,355 (5.1)

17,355 (5.1)

17,645 (5.2)

18,175 (5.3)

37,350 (10.9)

38,900 (11.4)

@ 277/480V

18,065 (5.3)

18,065 (5.3)

18,065 (5.3)

18,355 (5.4)

18,885 (5.5)

38,835 (11.4)

40,385 (11.8)

11,390

17,030

21,190

25,650

30,920

49,310

54,210

HOT GAS REHEAT


BTU/H

HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB
BTU/H

20,690

32,420

34,880

50,360

55,320

97,140

111,220

GPM

Pressure Drop, ft. wg


Control

0.1

0.3

0.3

0.3

0.3

0.4

0.6

Motorized

Motorized

Motorized

Motorized

Motorized

Motorized

Motorized
60,000

STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72F DB
BTU/H (nominal)
Condensate (lb/hr)
Control

12,000

18,000

24,000

32,000

40,000

48,000

13

19

25

34

42

50

63

Motorized

Motorized

Motorized

Motorized

Motorized

Motorized

Motorized

Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)


Lbs/Hr, (Kw Input)
Std Control

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

4-10, (3.4)

4-10, (3.4)

Cycling

Cycling

Cycling

Cycling

Cycling

Cycling

Cycling

1/4 Hp

1/4 Hp

1/3 Hp

1/2 Hp

1 Hp

1-1/2 Hp

- Air Cooled (1 to 5 ton Systems)

Total
Sensible

Performance Data

OHS Model

1 to 5 Ton "OHS" (Single Compressor), Self-Contained & Split

Evaporator Blower / Motor - DWDI Centrifugal


Horsepower

1/4 Hp

CFM @ ext. st. press.

500 @ 0.3"

750 @ 0.3"

900 @ 0.3"

1,000 @ 0.3"

1,415 @ 0.3"

2,200 @ 0.5"

2,500 @ 0.5"

Std. Drive Method

Direct Driven

Direct Driven

Direct Driven

Direct Driven

Direct Driven

Belt Driven

Belt Driven

Continued on next page

Air Technology Systems, Inc.

4-2

Air Cooled Performance Data

OHS Model

1 to 5 Ton "OHS" (Single Compressor), Self-Contained & Split

012-AS/AR

018-AS/AR

024-AS/AR

032-AS/AR

040-AS/AR

048-AR

060-AR

NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
Evaporator Coil - Aluminum Fin, Copper Tube
Rows/Face Area (Ft2)

3/ 2.1

3/ 2.1

3/ 2.1

3/ 2.8

3/ 2.8

4/ 5.0

4/ 5.0
Scroll, (1)

Compressor - Heat pump duty rated, HCFC Ozone Safe R-22


Recip., (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Watts - Input

Type, (Qty.)

1,405

1,614

2,092

2,711

2,842

4,415

4,959

Tot. Heat of Rej. (BTU/H)

17,595

24,260

31,480

40,500

43,830

70,080

77,395

20x20, (1)

20x20, (1)

20x20, (1)

20x20, (1)

20x20, (1)

20x16, (2)

20x16, (2)

Filters - 1" deep throwaway


Nom. Size (in.), (Qty.)

Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.)
Refrigerant: (OHS-012/060-()AR only)

- Air Cooled (1 to 5 ton Systems)

Liquid Line, (Qty.)

3/8" OD, (1)

3/8" OD, (1)

3/8" OD, (1)

1/2" OD (1)

1/2" OD (1)

1/2" OD (1)

1/2" OD (1)

Hot Gas Line, (Qty.)

1/2" OD, (1)

1/2" OD, (1)

5/8" OD, (1)

5/8" OD (1)

7/8" OD (1)

7/8" OD (1)

7/8" OD (1)

Condensate Drain

7/8" OD

7/8" OD

7/8" OD

7/8" OD

7/8" OD

3/4" FPT

3/4" FPT

Humidifier Inlet

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

Physical Size - (Please refer to Section 6 for detailed dimensional data.)


Approx. Wt. (OHS-()-AS)

210 lbs

215 lbs

220 lbs

255 lbs

265 lbs

N/A

N/A

Approx. Wt. (OHS-()-AR)

160 lbs

165 lbs

170 lbs

205 lbs

215 lbs

370 lbs

380 lbs

Air Cooled Condenser Data - (Self Contained)

Air Technology Systems, Inc


OHS Model @ 95F Amb.

012-AS

018-AS

024-AS

032-AS

040-AS

048

060

Integral Centrifugal Blower, Air Cooled Condenser Data for Self-Contained Model OHS-( )-AS
Condenser Blower Data

750 @ 0.3"

1,400 @ 0.3"

1,400 @ 0.3"

2,000 @ 0.3"

2,000 @ 0.3"

N/A

N/A

Motor Horsepower

CFM @ e.s.p

1/3 Hp.

1/2 Hp.

1/2 Hp.

1/2 Hp.

1/2 Hp.

N/A

N/A

Drive Method

Direct

Direct

Direct

Direct

Direct

N/A

N/A

4 / 2.1

4 / 2.1

4 / 2.1

4 / 2.8

4 / 2.8

N/A

N/A

0F

0F

0F

0F

0F

N/A

N/A

MotorSpeed

MotorSpeed

MotorSpeed

MotorSpeed

MotorSpeed

N/A

N/A

Condenser Coil
Rows/Face Area (ft2)
Low Ambient Control
Std. Minimum Op. Amb.
Head Pressure Method

Note:
Compressor is integral to the OHS-( )-AS Self-Contained Unit.
Please refer to the SATS Heat Rejection Engineering Manual for specification and performance data
on Remote Outdoor and Indoor Air Cooled Condensers used with OHS-( )-()AR Split Systems.

4-3

Air Technology Systems, Inc.

Air Cooled -

4 to 10 Ton "OHS" (Dual Compressors)


( )-048-DAR

( )-072-DAR

( )-084-DAR

( )-120-DAR

NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
Total

53,740

73,870

92,065

130,435

Sensible

40,860

62,110

71,070

98,030

75FDB/62.5FWB, 50% RH
Total

49,250

67,550

83,980

119,590

Sensible

40,290

61,525

70,840

96,230

72FDB/60FWB, 50% RH
Total

46,950

64,275

79,760

113,380

Sensible

39,480

60,215

69,565

94,580

80FDB/65FWB, 45% RH
Total

51,610

70,730

87,660

124,890

Sensible

44,310

68,085

79,060

106,480

75FDB/61FWB, 45% RH
Total

47,860

65,590

80,770

115,540

Sensible

42,830

64,070

76,215

102,850

Total

45,620

62,750

76,660

109,955

Sensible

42,040

61,910

73,710

100,920

72FDB/58.5FWB, 45% RH

ELECTRIC REHEAT / HEAT - BTU/H (Kw)


@ 208V/460V

36,810 (10.9)

38,900 (11.4)

40,510 (11.9)

43,580 (12.8)

@ 230V

42,600 (12.5)

44,690 (13.1)

46,300 (13.6)

49,370 (14.5)

@ 480V

38,295 (11.2)

40,385 (11.8)

41,995 (12.3)

45,065 (13.2)

21,150

32,300

37,190

50,520
130,500

HOT GAS REHEAT


BTU/H

HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB
BTU/H

50,360

97,880

99,830

GPM

10

0.3

0.3

0.3

2.2

Motorized

Motorized

Motorized

Motorized

48,000

72,000

90,000

120,000

50

75

94

125

Motorized

Motorized

Motorized

Motorized

Pressure Drop, ft. wg


Control

STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72F DB
BTU/H (nominal)
Condensate (lbs/hr)
Control

Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)


Lbs/Hr, (Kw Input)
Std Control

4-10, (3.4)

4-15, (5.1)

4-15, (5.1)

4-15, (5.1)

Cycling

Cycling

Cycling

Cycling

Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Horsepower
CFM @ ext. st. press.
Drive Method

3/4 Hp

1-1/2 Hp

2 Hp

3 Hp

1,800 @ 0.5"

3,000 @ 0.5"

3,350 @ 0.5"

4,400 @ 0.5"

Belt Driven

Belt Driven

Belt Driven

Belt Driven

Evaporator Coil - Aluminum Fin, Copper Tube


Rows
Face Area (Ft2)

4.1

6.7

6.7

10
Scroll, (2)

Compressor - Heat pump duty rated, HCFC Ozone Safe R-22


Scroll, (2)

Scroll, (2)

Scroll, (2)

Watts Input (per compressor)

Type, (Qty.)

2,054

2,797

3,848

4,959

Total Heat of Rejection, (BTU/H)

63,270

86,645

110,250

153,440

16x20, (2)

20x20, (2)

20x20, (2)

24x24, (2)

1/2" OD, (2)

Filters - 1" deep throwaway


Nominal Size (in.), (Qty.)

Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.)
Refrigerant:
Liquid Line, (Qty.)

3/8" OD, (2)

1/2" OD, (2)

1/2" OD, (2)

Hot Gas Line, (Qty.)

5/8" OD, (2)

5/8" OD, (2)

7/8" OD, (2)

7/8" OD, (2)

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

1/4" OD

1/4" OD

1/4" OD

1/4" OD

450 lbs

510 lbs

580 lbs

Condensate Drain, (w/ In-Pan Pump)


Humidifier Inlet

- Air Cooled (4 to 10 Ton, DUAL Compressor)

Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)

Performance Data

OHS Model

Physical Size - (Please refer to Section 6 for detailed dimensional data.)


Approx. Weight

420 lbs

Air Technology Systems, Inc.

4-4

Air Cooled AHU/RCU Performance Data

OHS Model

012-AHU

018-AHU

1 to 5 Ton "OHS"

024-AHU

032-AHU

040-AHU

048-AHU

060-AHU

NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
Total

13,985

19,465

25,740

32,940

36,505

59,970

65,975

Sensible

10,585

15,235

19,470

24,595

30,065

47,685

52,435

Total

12,710

18,000

23,600

30,355

33,750

55,010

60,470

Sensible

10,645

15,400

19,025

24,235

29,300

46,960

51,630

Total

12,000

17,160

22,465

29,035

32,320

52,400

57,580

Sensible

10,405

15,100

18,580

23,680

28,500

46,020

50,590

Total

13,425

18,860

24,600

31,670

35,120

57,680

63,350

Sensible

11,840

16,990

20,900

27,560

33,385

52,080

57,325

Total

12,270

17,490

23,030

29,500

32,790

53,415

58,620

Sensible

11,385

16,400

20,500

26,251

31,530

50,250

55,285

Total

11,585

16,665

22,000

28,220

31,410

50,875

55,790

Sensible

11,110

16,065

20,060

25,570

30,525

49,180

54,080

75FDB/62.5FWB, 50% RH

72FDB/60FWB, 50% RH

80FDB/65FWB, 45% RH

75FDB/61FWB, 45% RH

72FDB/58.5FWB, 45% RH

Air Cooled AHU/RCU (1 to 5 ton Systems)

Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)


ELECTRIC REHEAT / HEAT - BTU/H (Kw)
@ 208V

17,135 (5.0)

17,135 (5.0)

17,135 (5.0)

17,425 (5.1)

17,955 (5.3)

37,350 (10.9)

38,900 (11.4)

@ 230V

18,840 (5.5)

18,840 (5.5)

18,840 (5.5)

19,130 (5.6)

19,660 (5.8)

43,140 (12.6)

44,690 (13.1)

Air Technology Systems, Inc


@ 460V

17,355 (5.1)

17,355 (5.1)

17,355 (5.1)

17,645 (5.2)

18,175 (5.3)

37,350 (10.9)

38,900 (11.4)

@ 277/480V

18,065 (5.3)

18,065 (5.3)

18,065 (5.3)

18,355 (5.4)

18,885 (5.5)

38,835 (11.4)

40,385 (11.8)
111,220

HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB
BTU/H

20,690

32,420

34,880

50,360

55,320

97,140

GPM

0.1

0.3

0.3

0.3

0.3

0.4

0.6

Motorized

Motorized

Motorized

Motorized

Motorized

Motorized

Motorized
60,000

Pressure Drop, ft. wg


Control

STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72F DB
BTU/H (nominal)
Condensate (lb/hr)
Control

12,000

18,000

24,000

32,000

40,000

48,000

13

19

25

34

42

50

63

Motorized

Motorized

Motorized

Motorized

Motorized

Motorized

Motorized

Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)


Lbs/Hr, (Kw Input)
Std Control

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

4-10, (3.4)

4-10, (3.4)

Cycling

Cycling

Cycling

Cycling

Cycling

Cycling

Cycling

Evaporator Blower / Motor - DWDI Centrifugal


1/4 Hp

1/4 Hp

1/4 Hp

1/3 Hp

1/2 Hp

1 Hp

1-1/2 Hp

CFM @ ext. st. press.

Horsepower

500 @ 0.3"

750 @ 0.3"

900 @ 0.3"

1,000 @ 0.3"

1,415 @ 0.3"

2,200 @ 0.5"

2,500 @ 0.5"

Std. Drive Method

Direct Driven

Direct Driven

Direct Driven

Direct Driven

Direct Driven

Belt Driven

Belt Driven

Opt. Drive Method

Belt-Driven

Belt-Driven

Belt-Driven

Belt-Driven

Belt-Driven

N/A

N/A

3/ 2.1

3/ 2.1

3/ 2.1

3/ 2.8

3/ 2.8

4/ 5.0

4/ 5.0

20x20, (1)

20x20, (1)

20x20, (1)

20x20, (1)

20x20, (1)

20x16, (2)

20x16, (2)

Evaporator Coil - Aluminum Fin, Copper Tube


Rows/Face Area (Ft2)
Filters - 1" deep throwaway
Nom. Size (in.), (Qty.)

Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.)
Refrigerant:
Suction, (Qty.)

5/8" OD, (1)

3/4" OD, (1)

3/4" OD, (1)

3/4" OD (1)

7/8" OD (1)

7/8" OD (1)

7/8" OD (1)

Liquid Line, (Qty.)

3/8" OD, (1)

3/8" OD, (1)

3/8" OD, (1)

1/2" OD (1)

1/2" OD (1)

1/2" OD (1)

1/2" OD (1)

Condensate Drain

7/8" OD

7/8" OD

7/8" OD

7/8" OD

7/8" OD

3/4" FPT

3/4" FPT

Humidifier Inlet

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

120 lbs

155 lbs

165 lbs

270 lbs

280 lbs

Physical Size - (Please refer to Section 6 for detailed dimensional data.)


Approx. Wt.

120 lbs

120 lbs

Please refer to the SATS Heat Rejection Engineering Manual for specification and performance data on Remote Outdoor and Indoor Air Cooled Condensers

4-5

Air Technology Systems, Inc.

Air Cooled DAHU/DRCU - 4 to 10 Ton "OHS" (Dual)


( )-048-DAHU

( )-072-DAHU

( )-084-DAHU

( )-120-DAHU

NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
Total

53,740

73,870

92,065

130,435

Sensible

40,860

62,110

71,070

98,030

75FDB/62.5FWB, 50% RH
Total

49,250

67,550

83,980

119,590

Sensible

40,290

61,525

70,840

96,230

Total

46,950

64,275

79,760

113,380

Sensible

39,480

60,215

69,565

94,580

72FDB/60FWB, 50% RH

80FDB/65FWB, 45% RH
51,610

70,730

87,660

124,890

44,310

68,085

79,060

106,480

Total

47,860

65,590

80,770

115,540

Sensible

42,830

64,070

76,215

102,850

Total

45,620

62,750

76,660

109,955

Sensible

42,040

61,910

73,710

100,920

75FDB/61FWB, 45% RH

72FDB/58.5FWB, 45% RH

Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)


ELECTRIC REHEAT / HEAT - BTU/H (Kw)
@ 208V/460V

36,810 (10.9)

38,900 (11.4)

40,510 (11.9)

43,580 (12.8)

@ 230V

42,600 (12.5)

44,690 (13.1)

46,300 (13.6)

49,370 (14.5)

@ 480V

38,295 (11.2)

40,385 (11.8)

41,995 (12.3)

45,065 (13.2)
130,500

HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB
BTU/H

50,360

97,880

99,830

GPM

10

0.3

0.3

0.3

2.2

Motorized

Motorized

Motorized

Motorized
120,000

Pressure Drop, ft. wg


Control

STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72F DB
BTU/H (nominal)

48,000

72,000

90,000

50

75

94

125

Motorized

Motorized

Motorized

Motorized

Condensate (lbs/hr)
Control

Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)


Lbs/Hr, (Kw Input)
Std Control

4-10, (3.4)

4-15, (5.1)

4-15, (5.1)

4-15, (5.1)

Cycling

Cycling

Cycling

Cycling

Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Horsepower
CFM @ ext. st. press.
Drive Method

3/4 Hp

1-1/2 Hp

2 Hp

3 Hp

1,800 @ 0.5"

3,000 @ 0.5"

3,350 @ 0.5"

4,400 @ 0.5"

Belt Driven

Belt Driven

Belt Driven

Belt Driven

3/ 4.1

4/ 6.7

4/ 6.7

4/ 10.0

16x20, (2)

20x20, (2)

20x20, (2)

24x24, (2)

Evaporator Coil - Aluminum Fin, Copper Tube


Rows/Face Area (Ft2)
Filters - 1" deep throwaway
Nominal Size (in.), (Qty.)

Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.)
Refrigerant:
Suction Line, (Qty.)

3/4" OD, (2)

7/8" OD, (2)

7/8" OD, (2)

7/8" OD, (2)

Liquid Line, (Qty.)

3/8" OD, (2)

1/2" OD, (2)

1/2" OD, (2)

1/2" OD, (2)

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

1/4" OD

1/4" OD

1/4" OD

1/4" OD

350 lbs

410 lbs

480 lbs

Condensate Drain, (w/ In-Pan Pump)


Humidifier Inlet

Physical Size - (Please refer to Section 6 for detailed dimensional data.)


Approx. Weight

320 lbs

- Air Cooled DAHU/DRCU (4-10 Ton, DUAL Compressor)

Total
Sensible

Performance Data

OHS Model

Please refer to the SATS Heat Rejection Engineering Manual for specification and performance data on Remote Outdoor and Indoor Air Cooled Condensing Units

Air Technology Systems, Inc.

4-6

Water Cooled Performance Data

OHS Model

( )-012-W

1 to 5 Ton "OHS"

( )-018-W

( )-024-W

( )-032-W

( )-040-W

( )-048-W

( )-060-W

NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
Total

16,394

21,125

27,990

35,550

39,115

64,250

70,665

Sensible

11,675

16,000

20,455

24,575

29,500

49,240

54,100

Total

14,850

19,345

25,750

32,700

35,830

58,820

64,690

Sensible

11,340

15,625

20,100

24,265

28,800

48,580

53,445

Total

14,000

18,380

24,560

31,150

34,109

56,070

61,650

Sensible

11,050

16,400

19,680

23,775

28,093

47,600

52,345

Total

15,570

20,430

26,840

34,170

37,355

61,635

67,730

Sensible

12,440

17,645

21,825

26,300

31,600

53,560

58,955

Total

14,380

18,950

24,920

31,600

35,120

57,130

62,760

Sensible

12,250

17,040

21,075

25,360

30,560

51,780

56,975

Total

13,620

18,065

23,685

30,060

33,460

54,460

59,795

Sensible

12,010

16,710

20,700

24,820

30,470

50,820

55,910

75FDB/62.5FWB, 50% RH

72FDB/60FWB, 50% RH

80FDB/65FWB, 45% RH

75FDB/61FWB, 45% RH

72FDB/58.5FWB, 45% RH

Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)


ELECTRIC REHEAT / HEAT - BTU/H (Kw)

- Water Cooled (1 to 5 Ton Systems)

@ 208V

17,135 (5.0)

17,135 (5.0)

17,135 (5.0)

17,425 (5.1)

17,955 (5.3)

37,350 (10.9)

38,900 (11.4)

@ 230V

18,840 (5.5)

18,840 (5.5)

18,840 (5.5)

19,130 (5.6)

19,660 (5.8)

43,140 (12.6)

44,690 (13.1)

@ 460V

17,355 (5.1)

17,355 (5.1)

17,355 (5.1)

17,645 (5.2)

18,175 (5.3)

37,350 (10.9)

38,900 (11.4)

@ 277/480V

18,065 (5.3)

18,065 (5.3)

18,065 (5.3)

18,355 (5.4)

18,885 (5.5)

38,835 (11.4)

40,385 (11.8)

12,440

17,690

22,150

27,045

32,425

51,010

56,120

HOT GAS REHEAT


BTU/H

HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB

Air Technology Systems, Inc


BTU/H

20,690

32,420

34,880

50,360

55,320

97,140

GPM

0.1

0.3

0.3

0.3

0.3

0.4

0.6

Motorized

Motorized

Motorized

Motorized

Motorized

Motorized

Motorized
60,000

Pressure Drop, ft. wg


Control

111,220

STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72F DB
BTU/H (nominal)

Condensate (lb/hr)
Control

12,000

18,000

24,000

32,000

40,000

48,000

13

19

25

34

42

50

63

Motorized

Motorized

Motorized

Motorized

Motorized

Motorized

Motorized

Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)


Lbs/Hr, (Kw Input)
Std Control

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

4-10, (3.4)

4-10, (3.4)

Cycling

Cycling

Cycling

Cycling

Cycling

Cycling

Cycling

Evaporator Blower / Motor - DWDI Centrifugal


1/4 Hp

1/4 Hp

1/4 Hp

1/3 Hp

1/2 Hp

1 Hp

1-1/2 Hp

CFM @ ext. st. press.

Horsepower

500 @ 0.3"

750 @ 0.3"

900 @ 0.3"

1,000 @ 0.3"

1,415 @ 0.3"

2,200 @ 0.5"

2,500 @ 0.5"

Std. Drive Method

Direct Driven

Direct Driven

Direct Driven

Direct Driven

Direct Driven

Belt Driven

Belt Driven

Opt. Drive Method

Belt-Driven

Belt-Driven

Belt-Driven

Belt-Driven

Belt-Driven

N/A

N/A

3/ 2.1

3/ 2.1

3/ 2.8

3/ 2.8

4/ 5.0

4/ 5.0

Evaporator Coil - Aluminum Fin, Copper Tube


Rows/Face Area (Ft2)

3/ 2.1

Compressor - Heat pump duty rated, HCFC Ozone Safe R-22


Type, (Qty.)

Recip., (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Watts Input

1,245

1,239

1,633

2,118

2,222

3,451

3,867

Water Cooled Condenser Data - Based on 0% glycol solution


Tot Heat of Reject.

18,900 Btu/h

24,350 Btu/h

32,145 Btu/h

41,325 Btu/h

44,865 Btu/h

70,600 Btu/h

77,890 Btu/h

GPM @ 85F EWT

3.8 GPM

4.9 GPM

6.4 GPM

8.3 GPM

9.0 GPM

14.1 GPM

15.6 GPM

Total Unit PD (Ft. of H2O)

10.0 Ft.

6.5 Ft.

11.0 Ft.

11.7 Ft.

13.9 Ft.

16.5 Ft.

22.7 Ft.

Type

Coaxial

Coaxial

Coaxial

Coaxial

Coaxial

Coaxial

Coaxial

3/4" FPT

Head Pressure Control


Standard Control - 2-way, 150 psig Water Regulating Valve, (factory installed)
Optional Control - Refer to the Optional Guide Specifications Section for High Pressure and 3-way Valve Options!
Connection Sizes - Copper
Condensate Drain

7/8" OD

7/8" OD

7/8" OD

7/8" OD

7/8" OD

3/4" FPT

Humidifier Inlet

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

Source Water In/Out

5/8" OD

7/8" OD

7/8" OD

7/8" OD

7/8" OD

1-1/8" OD

1-1/8" OD

20x20 (1)

20x20, (1)

20x20, (1)

20x20, (1)

20x20, (1)

20x16, (2)

20x16, (2)

210 lbs

245 lbs

260 lbs

395 lbs

405 lbs

Filters - 1" deep throwaway


Nom. Size (in.), (Qty.)

Physical Size - (Please refer to Section 6 for detailed dimensional data.)


Approx. Weight

180 lbs

200 lbs

Please refer to the SATS Heat Rejection Engineering Manual for specification and performance data on Remote Outdoor and Indoor Air Cooled Condensing Units

4-7

Air Technology Systems, Inc.

Water Cooled -

OHS-048-DW

OHS-072-DW

OHS-084-DW

OHS-120-DW

NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
Total

57,200

79,165

98,760

139,210

Sensible

42,320

63,770

73,735

101,715

Total

52,580

72,510

90,475

127,660

Sensible

41,620

63,225

72,760

100,040

75FDB/62.5FWB, 50% RH

72FDB/60FWB, 50% RH
Total

50,100

69,035

86,090

121,610

Sensible

40,820

62,045

71,400

98,010

80FDB/65FWB, 45% RH
Total

54,890

75,840

94,300

133,265

Sensible

45,740

70,425

81,160

110,080

Total

50,960

70,200

87,050

123,460

Sensible

44,180

67,685

78,670

106,285

75FDB/61FWB, 45% RH

72FDB/58.5FWB, 45% RH
Total

48,620

66,785

82,760

117,645

Sensible

43,390

65,220

77,320

104,340

Performance Data

OHS Model

4 to 10 Ton "OHS" (Dual)

Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)


@ 208V/460V

36,810 (10.9)

38,900 (11.4)

40,510 (11.9)

43,580 (12.8)

@ 230V

42,600 (12.5)

44,690 (13.1)

46,300 (13.6)

49,370 (14.5)

@ 480V

38,295 (11.2)

40,385 (11.8)

41,995 (12.3)

45,065 (13.2)

21,850

33,195

38,200

52,520
130,500

HOT GAS REHEAT


BTU/H

HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB
BTU/H

50,360

97,880

99,830

GPM

10

0.3

0.3

0.3

2.2

Motorized

Motorized

Motorized

Motorized

48,000

72,000

90,000

120,000

50

75

94

125

Motorized

Motorized

Motorized

Motorized

4-10, (3.4)

4-15, (5.1)

4-15, (5.1)

4-15, (5.1)

Cycling

Cycling

Cycling

Cycling

Pressure Drop, ft. wg


Control

STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72F DB
BTU/H (nominal)
Condensate (lbs/hr)
Control

Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)


Lbs/Hr, (Kw Input)
Std Control

Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Horsepower

3/4 Hp

1-1/2 Hp

2 Hp

3 Hp

1,800 @ 0.5"

3,000 @ 0.5"

3,350 @ 0.5"

4,400 @ 0.5"

Belt Driven

Belt Driven

Belt Driven

Belt Driven

3/ 4.1

4/ 6.7

4/ 6.7

4/ 10.0

Scroll, (2)

Scroll, (2)

Scroll, (2)

Scroll, (2)

1,603

2,182

2,973

3,867

63,525 Btu/h

87,405 Btu/h

110,770 Btu/h

154,060 Btu/h

12.7 GPM

17.5 GPM

22.2 GPM

30.8 GPM

Total Unit Pressure Drop (Ft. of H2O)

12.4 Ft.

17.9 Ft.

12.4 Ft.

25.7 Ft.

Type

Coaxial

Coaxial

Coaxial

Coaxial

3/4" FPT, (1/2"OD)

CFM @ ext. st. press.


Drive Method
Evaporator Coil - Aluminum Fin, Copper Tube
Rows/Face Area (Ft2)

Compressor - Heat pump duty rated, HCFC Ozone Safe R-22


Type, (Qty.)
Watt Input (per compressor)

Water Cooled Condenser Data - Based on 0% glycol solution


Total Heat of Reject.
GPM @ 85F EWT

- Water Cooled (4 to 10 Ton Systems)

ELECTRIC REHEAT / HEAT - BTU/H (Kw)

Head Pressure Control


Standard Control - 2-way, 150 psig Water Regulating Valve, (factory installed)
Optional Control - Refer to the Optional Guide Specifications Section for High Pressure and 3-way Valve Options!
Connection Sizes - Copper
Condensate Drain, (w/ In-Pan Pump)
Humidifier Inlet
Source Water Inlet/Outlet

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1-1/8" OD

1-1/8" OD

1-3/8" OD

1-3/8" OD

16x20, (2)

20x20, (2)

20x20, (2)

24x24, (2)

470 lbs

550 lbs

625 lbs

Filters - 1" deep throwaway


Nominal Size (in.), (Qty.)

Physical Size - (Please refer to Section 6 for detailed dimensional data.)


Approx. Weight

440 lbs

Air Technology Systems, Inc.

4-8

Glycol Cooled Performance Data

OHS Model

( )-012-G

1 to 5 Ton "OHS"

( )-018-G

( )-024-G

( )-032-G

( )-040-G

( )-048-G

( )-060-G

NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
Total

13,390

18,960

25,090

32,000

34,910

57,150

62,670

Sensible

10,435

15,060

19,160

23,085

27,500

46,565

51,120

Total

12,200

17,541

22,975

28,175

31,855

52,325

57,335

Sensible

10,450

15,194

18,710

23,700

26,975

45,920

50,410

Total

11,510

16,720

21,900

27,800

30,540

49,770

54,525

Sensible

10,210

14,880

18,275

22,045

26,455

44,970

49,370

Total

12,900

18,375

23,990

30,580

33,840

54,920

60,120

Sensible

11,650

16,800

20,535

24,540

30,475

51,075

56,140

Total

11,780

17,035

22,430

28,175

31,290

50,785

55,550

Sensible

11,171

16,200

20,195

23,700

29,270

49,080

53,900

Total

11,120

16,235

21,355

27,065

29,770

48,360

52,680

Sensible

10,875

15,855

19,760

23,375

28,610

47,710

51,930

75FDB/62.5FWB, 50% RH

72FDB/60FWB, 50% RH

80FDB/65FWB, 45% RH

75FDB/61FWB, 45% RH

72FDB/58.5FWB, 45% RH

Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)

- Glycol Cooled (1 to 5 Ton Systems)

ELECTRIC REHEAT / HEAT - BTU/H (Kw)


@ 208V

17,135 (5.0)

17,135 (5.0)

17,135 (5.0)

17,425 (5.1)

17,955 (5.3)

37,350 (10.9)

38,900 (11.4)

@ 230V

18,840 (5.5)

18,840 (5.5)

18,840 (5.5)

19,130 (5.6)

19,660 (5.8)

43,140 (12.6)

44,690 (13.1)

@ 460V

17,355 (5.1)

17,355 (5.1)

17,355 (5.1)

17,645 (5.2)

18,175 (5.3)

37,350 (10.9)

38,900 (11.4)

@ 277/480V

18,065 (5.3)

18,065 (5.3)

18,065 (5.3)

18,355 (5.4)

18,885 (5.5)

38,835 (11.4)

40,385 (11.8)

11,290

16,845

20,895

25,295

30,555

48,220

52,930

HOT GAS REHEAT


BTU/H

Air Technology Systems, Inc


HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB
BTU/H

20,690

32,420

34,880

50,360

55,320

97,140

GPM

0.1

0.3

0.3

0.3

0.3

0.4

0.6

Motorized

Motorized

Motorized

Motorized

Motorized

Motorized

Motorized
60,000

Pressure Drop, ft. wg

Control

111,220

STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72F DB
BTU/H (nominal)
Condensate (lb/hr)
Control

12,000

18,000

24,000

32,000

40,000

48,000

13

19

25

34

42

50

63

Motorized

Motorized

Motorized

Motorized

Motorized

Motorized

Motorized

Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)


Lbs/Hr, (Kw Input)
Std Control

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

4-10, (3.4)

4-10, (3.4)

Cycling

Cycling

Cycling

Cycling

Cycling

Cycling

Cycling

Evaporator Blower / Motor - DWDI Centrifugal


1/4 Hp

1/4 Hp

1/4 Hp

1/3 Hp

1/2 Hp

1 Hp

1-1/2 Hp

CFM @ ext. st. press.

Horsepower

500 @ 0.3"

750 @ 0.3"

900 @ 0.3"

1,000 @ 0.3"

1,415 @ 0.3"

2,200 @ 0.5"

2,500 @ 0.5"

Std. Drive Method

Direct Driven

Direct Driven

Direct Driven

Direct Driven

Direct Driven

Belt Driven

Belt Driven

Opt. Drive Method

Belt-Driven

Belt-Driven

Belt-Driven

Belt-Driven

Belt-Driven

N/A

N/A

3/ 2.1

3/ 2.1

3/ 2.8

3/ 2.8

4/ 5.0

4/ 5.0

Evaporator Coil - Aluminum Fin, Copper Tube


Rows/Face Area (Ft2)

3/ 2.1

Compressor - Heat pump duty rated, HCFC Ozone Safe R-22


Type, (Qty.)

Recip., (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Watts Input

1,442

1,729

2,227

2,882

3,027

4,699

5,290

Glycol Condenser Data - Based on 40% ethylene glycol solution


Tot. Heat of Reject.

17,270 Btu/h

23,990 Btu/h

31,305 Btu/h

40,340 Btu/h

43,625 Btu/h

68,360 Btu/h

75,390 Btu/h

GPM @ 110F EGT

3.8 GPM

5.3 GPM

6.9 GPM

8.9 GPM

9.7 GPM

15.1 GPM

16.7 GPM

Total Unit PD (Ft. of H2O)

10.1 Ft.

7.0 Ft.

11.8 Ft.

12.8 Ft.

15.2 Ft.

18.0 Ft.

24.5 Ft.

Type

Coaxial

Coaxial

Coaxial

Coaxial

Coaxial

Coaxial

Coaxial

3/4" FPT

Head Pressure Control


Standard Control - 2-way, 150 psig Glycol Regulating Valve, (factory installed)
Optional Control - Refer to the Optional Guide Specifications Section for High Pressure and 3-way Valve Options!
Connection Sizes - Copper
Condensate Drain

7/8" OD

7/8" OD

7/8" OD

7/8" OD

7/8" OD

3/4" FPT

Humidifier Inlet

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

Source Glycol In/Out

5/8" OD

7/8" OD

7/8" OD

7/8" OD

7/8" OD

1-1/8" OD

1-1/8" OD

20x20, (1)

20x20, (1)

20x20, (1)

20x20, (1)

20x20, (1)

20x16, (2)

20x16, (2)

210 lbs

245 lbs

260 lbs

395 lbs

405 lbs

Filters - 1" deep throwaway


Nom. Size (in.), (Qty.)

Physical Size - (Please refer to Section 6 for detailed dimensional data.)


Approx. Weight

4-9

180 lbs

200 lbs

Air Technology Systems, Inc.

Glycol Cooled OHS-048-DG

OHS-072-DG

OHS-084-DG

OHS-120-DG

NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
Total

51,260

70,230

87,445

123,970

Sensible

39,730

61,010

69,465

95,280

75FDB/62.5FWB, 50% RH
Total

46,840

64,090

79,565

113,045

Sensible

39,230

60,180

69,420

93,920

72FDB/60FWB, 50% RH
Total

44,600

60,990

75,580

107,490

Sensible

38,400

58,520

68,115

91,925

80FDB/65FWB, 45% RH
Total

49,150

67,340

83,055

118,680

Sensible

43,340

65,360

77,390

104,065

75FDB/61FWB, 45% RH
Total

45,500

62,635

76,640

109,590

Sensible

41,840

61,750

73,350

100,420

Total

43,320

59,880

73,150

104,185

Sensible

41,000

59,635

71,130

98,400

72FDB/58.5FWB, 45% RH

Performance Data

OHS Model

4 to 10 Ton "OHS" (Dual)

Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)


@ 208V/460V

36,810 (10.9)

38,900 (11.4)

40,510 (11.9)

43,580 (12.8)

@ 230V

42,600 (12.5)

44,690 (13.1)

46,300 (13.6)

49,370 (14.5)

@ 480V

38,295 (11.2)

40,385 (11.8)

41,995 (12.3)

45,065 (13.2)

20,595

31,595

36,445

49,310
130,500

HOT GAS REHEAT


BTU/H

HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB
BTU/H

50,360

97,880

99,830

GPM

10

0.3

0.3

0.3

2.2

Motorized

Motorized

Motorized

Motorized

48,000

72,000

90,000

120,000

50

75

94

125

Motorized

Motorized

Motorized

Motorized

Pressure Drop, ft. wg


Control

STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72F DB
BTU/H (nominal)
Condensate (lbs/hr)
Control

Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)


Lbs/Hr, (Kw Input)
Std Control

4-10, (3.4)

4-15, (5.1)

4-15, (5.1)

4-15, (5.1)

Cycling

Cycling

Cycling

Cycling

Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Horsepower

3/4 Hp

1-1/2 Hp

2 Hp

3 Hp

1,800 @ 0.5"

3,000 @ 0.5"

3,350 @ 0.5"

4,400 @ 0.5"

Belt Driven

Belt Driven

Belt Driven

Belt Driven

3/ 4.1

4/ 6.7

4/ 6.7

4/ 10.0

Scroll, (2)

Scroll, (2)

Scroll, (2)

Scroll, (2)

2,188

2,973

4,103

5,290

61,775 Btu/h

84,385 Btu/h

107,570 Btu/h

149,155 Btu/h

13.7 GPM

18.7 GPM

23.8 GPM

33.0 GPM

Total Unit Pressure Drop (Ft. of H2O)

13.6 Ft.

20.0 Ft.

13.9 Ft.

28.1 Ft.

Type

Coaxial

Coaxial

Coaxial

Coaxial

3/4" FPT, (1/2"OD)

CFM @ ext. st. press.


Drive Method
Evaporator Coil - Aluminum Fin, Copper Tube
Rows/Face Area (Ft2)

Compressor - Heat pump duty rated, HCFC Ozone Safe R-22


Type, (Qty.)
Watt Input (per compressor)

Glycol Condenser Data - Based on 40% ethylene glycol solution


Total Heat of Rejection
GPM @ 110F EGT

- Glycol Cooled (4 to 10 Ton Systems)

ELECTRIC REHEAT / HEAT - BTU/H (Kw)

Head Pressure Control


Standard Control - 2-way, 150 psig Glycol Regulating Valves, (factory installed)
Optional Control - Refer to the Optional Guide Specifications Section for High Pressure and 3-way Valve Options!
Connection Sizes - Copper
Condensate Drain, (w/ In-Pan Pump)
Humidifier Inlet
Source Glycol Inlet/Outlet

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1-1/8" OD

1-1/8" OD

1-3/8" OD

1-3/8" OD

16x20, (2)

20x20, (2)

20x20, (2)

24x24, (2)

470 lbs

550 lbs

625 lbs

Filters - 1" deep throwaway


Nominal Size (in.), (Qty.)

Physical Size - (Please refer to Section 6 for detailed dimensional data.)


Approx. Weight

440 lbs

Air Technology Systems, Inc.

4-10

Chilled Water
Performance Data

OHS Model

- 1 to 3 Tons "OHS"

OHS-012-C

OHS-018-C

OHS-024-C

OHS-032-C

OHS-040-C

51,990

COOLING CAPACITY - BTU/H @ 45F EWT, 0% Glycol Solution (@ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
High Flow

Total

22,970

31,090

35,410

40,800

(8F Tw)

Sens.

15,340

21,440

24,820

28,730

37,670

5.8 / (19.6)

7.8 / (34.0)

8.8 / (43.1)

10.2 / (23.3)

13.0 / (36.8)
48,680

GPM / (pd. Ft.)


Med. Flow

Total

21,200

29,050

33,090

38,030

(10F Tw)

Sens.

14,560

20,520

23,770

27,430

36,100

4.3 / (11.2)

5.8 / (19.8)

6.6 / (25.1)

7.6 / (13.6)

9.7 / (21.5)
45,440

GPM / (pd. Ft.)


Low Flow

Total

19,390

26,830

30,910

34,950

(12F Tw)

Sens.

13,760

19,530

22,770

25,990

34,520

3.3 / (6.8)

4.5 / (12.2)

5.2 / (15.8)

5.8 / (8.3)

7.6 / (13.4)
38,890

GPM / (pd. Ft.)


75FDB/62.5FWB, 50% RH
High Flow

Total

16,460

22,840

26,110

30,170

(8F Tw)

Sens.

13,000

18,510

21,500

24,720

32,720

4.2 / (10.7)

5.7 / (19.4)

6.5 / (24.6)

7.6 / (13.4)

9.7 / (21.5)
36,190

GPM / (pd. Ft.)


Med. Flow

Total

15,110

21,080

24,380

27,720

(10F Tw)

Sens.

12,340

17,610

20,590

23,420

31,210

3.1 / (6.0)

4.2 / (11.1)

4.9 / (14.5)

5.6 / (7.6)

7.3 / (12.5)
33,310

GPM / (pd. Ft.)

- Chilled Water (1-3 ton) Systems

Low Flow

Total

13,840

19,420

22,490

25,470

(12F Tw)

Sens.

11,690

16,700

19,510

22,170

29,510

2.3 / (3.7)

3.3 / (6.8)

3.8 / (8.9)

4.3 / (4.7)

5.6 / (7.6)
32,490

GPM / (pd. Ft.)


72FDB/60FWB, 50% RH
High Flow

Total

13,510

18,810

21,750

24,930

(8F Tw)

Sens.

11,700

16,680

19,500

22,240

29,600

3.4 / (7.5)

4.7 / (13.6)

5.5 / (17.8)

6.3 / (9.5)

8.1 / (15.4)
29,590

GPM / (pd. Ft.)


Med. Flow

Total

12,390

17,240

19,910

22,830

(10F Tw)

Sens.

11,080

15,740

18,360

20,970

27,750

2.5 / (4.2)

3.5 / (7.7)

4.0 / (10.0)

4.6 / (5.4)

6.0 / (8.6)
25,970

Air Technology Systems, Inc


GPM / (pd. Ft.)

Low Flow

Total

11,120

15,380

17,680

20,240

(12F Tw)

Sens.

10,300

14,520

16,850

19,280

25,270

1.9 / (2.2)

2.6 / (4.5)

3.0 / (5.7)

3.4 / (3.1)

4.4 / (4.9)

47,370

GPM / (pd. Ft.)

80FDB/65FWB, 45% RH
High Flow

Total

20,300

27,780

31,800

36,940

(8F Tw)

Sens.

15,640

22,090

25,710

29,660

39,180

5.1 / (15.7)

6.9 / (27.5)

8.0 / (35.4)

9.2 / (19.5)

11.8 / (30.8)
44,850

GPM / (pd. Ft.)


Med. Flow

Total

18,880

26,180

30,070

34,620

(10F Tw)

Sens.

14,970

21,310

24,830

28,480

37,830

3.8 / (9.1)

5.2 / (16.3)

6.0 / (21.1)

6.9 / (11.5)

9.0 / (18.5)
42,110

GPM / (pd. Ft.)


Low Flow

Total

17,570

24,520

28,250

32,270

(12F Tw)

Sens.

14,340

20,460

23,870

27,250

36,300

2.9 / (5.7)

4.1 / (10.4)

4.7 / (13.4)

5.4 / (7.2)

7.0 / (11.7)
36,630

GPM / (pd. Ft.)


75FDB/61FWB, 45% RH
High Flow

Total

15,230

21,220

24,400

28,210

(8F Tw)

Sens.

13,420

19,160

22,330

25,550

33,970

3.8 / (9.3)

5.4 / (17.0)

6.1 / (21.9)

7.0 / (11.8)

9.2 / (19.3)
33,910

GPM / (pd. Ft.)


Med. Flow

Total

14,210

19,750

22,720

26,220

(10F Tw)

Sens.

12,850

18,270

21,260

24,340

32,200

2.9 / (5.4)

4.0 / (9.9)

4.6 / (12.7)

5.3 / (6.9)

6.8 / (11.0)
27,460

GPM / (pd. Ft.)


Low Flow

Total

13,040

17,980

20,610

23,830

(12F Tw)

Sens.

12,130

17,110

19,850

22,790

27,460

2.2 / (3.2)

3.0 / (5.9)

3.5 / (7.6)

4.0 / (4.2)

4.6 / (5.4)
28,360

GPM / (pd. Ft.)


72FDB/58.5FWB, 45% RH
High Flow

Total

12,650

17,360

19,380

23,310

(8F Tw)

Sens.

12,140

17,120

19,380

22,900

28,360

3.2 / (6.6)

4.4 / (11.8)

4.9 / (14.4)

5.9 / (8.5)

7.1 / (12.1)
25,700

GPM / (pd. Ft.)


Med. Flow

Total

10,780

15,310

17,820

19,440

(10F Tw)

Sens.

10,780

15,310

17,820

19,440

25,700

2.2 / (3.1)

3.1 / (6.2)

3.6 / (8.1)

3.9 / (4.0)

5.2 / (6.7)
22,870

GPM / (pd. Ft.)


Low Flow

Total

9,740

13,810

16,080

17,240

(12F Tw)

Sens.

9,740

13,810

16,080

17,240

22,870

1.7 / (1.6)

2.3 / (3.7)

2.7 / (4.8)

2.9 / (2.1)

3.9 / (3.9)

GPM / (pd. Ft.)

4-11

Air Technology Systems, Inc.

Chilled Water

OHS-012-C

OHS-018-C

OHS-024-C

OHS-032-C

OHS-040-C

Chilled Water Control Valve - Sized for Medium Flow @ 75FDB/62.5FWB EAT Conditions
2-way (standard) - Spring Actuated (Open/Close)
Size / (Cv)
Valve Pressure Rating
Total Unit Pressure Drop

1/2" / (3.5 Cv)

3/4" / (3.5 Cv)

3/4" / (3.7 Cv)

3/4" / (3.7 Cv)

3/4" / (3.7 Cv)

300 psig

300 psig

300 psig

300 psig

300 psig

8.0 Ft.

14.6 Ft.

19.4 Ft.

14.2 Ft.

22.6 Ft.

1/2" / (5.0 Cv)

3/4" / (5.0 Cv)

3/4" / (5.0 Cv)

3/4" / (5.0 Cv)

3/4" / (5.0 Cv)

300 psig

300 psig

300 psig

300 psig

300 psig

7.1 Ft.

12.9 Ft.

17.0 Ft.

11.2 Ft.

17.5 Ft.

4 / 2.1

4 / 2.1

4 / 2.8

4 / 2.8

3-way (optional) - Spring Actuated (Open/Close)


Size / (Cv)
Valve Pressure Rating
Total Unit Pressure Drop

Chilled Water Coil - Aluminum Fin, Copper Tube


Rows/Face Area (Ft2)

4 / 2.1

Evaporator Blower / Motor - DWDI Centrifugal


Horsepower

1/4 Hp

1/4 Hp

1/3 Hp

1/2 Hp

500 @ 0.3"

750 @ 0.3"

900 @ 0.3"

1,000 @ 0.3"

1,415 @ 0.3"

Std. Drive Method

Direct Driven

Direct Driven

Direct Driven

Direct Driven

Direct Driven

Opt. Drive Method

Belt-Driven

Belt-Driven

Belt-Driven

Belt-Driven

Belt-Driven

Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)


ELECTRIC REHEAT / HEAT - BTU/H (Kw)
@ 208V

17,135 (5.0)

17,135 (5.0)

17,135 (5.0)

17,425 (5.1)

17,955 (5.3)

@ 230V

18,840 (5.5)

18,840 (5.5)

18,840 (5.5)

19,130 (5.6)

19,660 (5.8)

@ 460V

17,355 (5.1)

17,355 (5.1)

17,355 (5.1)

17,645 (5.2)

18,175 (5.3)

@ 277/480V

18,065 (5.3)

18,065 (5.3)

18,065 (5.3)

18,355 (5.4)

18,885 (5.5)

50,360

55,320

HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB
BTU/H
GPM
Pressure Drop, ft. wg
Control

20,690

32,420

34,880

0.1

0.3

0.3

0.3

0.3

Motorized

Motorized

Motorized

Motorized

Motorized

STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72F DB
BTU/H (nominal)
Condensate (lb/hr)
Control

12,000

18,000

24,000

32,000

40,000

13

19

25

34

42

Motorized

Motorized

Motorized

Motorized

Motorized

Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)


Lbs/Hr, (Kw Input)
Std Control

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

Cycling

Cycling

Cycling

Cycling

Cycling

20x20, (1)

20x20, (1)

20x20, (1)

20x20, (1)

20x20, (1)

7/8" OD

7/8" OD

7/8" OD

7/8" OD

7/8" OD

Filters - 1" deep throwaway


Nom. Size (in.), (Qty.)

- Chilled Water (1-3 ton) Systems

1/4 Hp

CFM @ ext. st. press.

Performance Data

OHS Model

- 1 to 3 Tons "OHS"

Connection Sizes - Copper


Condensate Drain
Humidifier Inlet

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

Chilled Water In/Out

5/8" OD

7/8" OD

7/8" OD

7/8" OD

7/8" OD

125 lbs

160 lbs

170 lbs

Physical Size - (Please refer to Section 6 for detailed dimensional data.)


Approx. Wt.

120 lbs

125 lbs

Air Technology Systems, Inc.

4-12

Chilled Water Performance Data

OHS Model

OHS-048-C

4 to 10 Ton "OHS"
OHS-060-C

OHS-072-C

OHS-084-C

OHS-120-C

166,850

COOLING CAPACITY - BTU/H @ 45F EWT, 0% Glycol Solution (@ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
High Flow

Total

83,770

91,130

134,100

144,440

(8F Tw)

Sensible

59,280

65,250

90,760

98,710

117,880

20.9 / (18.6)

22.8 / (21.9)

33.5 / (46.3)

36.1 / (53.2)

41.8 / (18.6)
154,030

GPM / (pd. Ft.)


Med. Flow

Total

77,350

84,830

125,560

135,080

(10F Tw)

Sensible

56,410

62,390

87,010

94,600

112,150

15.5 / (10.7)

17.1 / (12.7)

25.2 / (27.5)

27.1 / (31.5)

31.0 / (10.7)
139,290

GPM / (pd. Ft.)


Low Flow

Total

69,980

77,170

117,370

126,560

(12F Tw)

Sensible

53,070

58,870

83,420

90,820

105,460

11.7 / (6.4)

13.0 / (7.7)

19.6 / (17.4)

21.2 / (20.1)

23.4 / (6.4)
121,940

GPM / (pd. Ft.)


75FDB/62.5FWB, 50% RH
High Flow

Total

61,310

67,460

99,080

106,720

(8F Tw)

Sensible

51,210

56,760

78,510

85,490

101,740

15.4 / (10.6)

17.0 / (12.7)

24.8 / (26.9)

26.8 / (30.8)

30.8 / (10.6)
109,650

GPM / (pd. Ft.)


Med. Flow

Total

55,160

61,100

93,260

100,560

(10F Tw)

Sensible

47,960

53,340

75,670

82,420

95,250

11.1 / (5.8)

12.4 / (7.1)

18.8 / (16.1)

20.3 / (18.5)

22.2 / (5.8)
97,640

GPM / (pd. Ft.)

- Chilled Water (4-10 ton) Systems

Low Flow

Total

49,160

54,360

87,270

94,830

(12F Tw)

Sensible

44,430

49,290

72,610

79,360

88,190

8.3 / (3.4)

9.2 / (4.1)

14.6 / (10.2)

15.9 / (11.9)

16.6 / (3.4)
99,540

GPM / (pd. Ft.)


72FDB/60FWB, 50% RH
High Flow

Total

50,110

55,070

83,050

89,560

(8F Tw)

Sensible

45,920

50,810

71,570

77,990

91,150

12.6 / (7.4)

13.9 / (8.8)

20.9 / (19.6)

22.5 / (22.6)

25.2 / (7.4)
85,960

GPM / (pd. Ft.)


Med. Flow

Total

43,320

47,530

78,610

84,870

(10F Tw)

Sensible

41,670

46,000

69,090

75,240

82,660

8.7 / (3.7)

9.6 / (4.5)

15.8 / (11.9)

17.2 / (13.7)

17.4 / (3.7)
67,580

Air Technology Systems, Inc


GPM / (pd. Ft.)

Low Flow

Total

34,130

37,920

71,630

77,770

(12F Tw)

Sensible

34,130

37,920

64,930

70,840

67,580

5.8 / (1.6)

6.4 / (2.1)

12.0 / (7.2)

13.1 / (8.4)

11.6 / (1.6)

150,470

GPM / (pd. Ft.)

80FDB/65FWB, 45% RH
High Flow

Total

75,570

82,490

120,390

130,020

(8F Tw)

Sens.

61,670

68,110

93,640

102,180

122,660

18.9 / (15.5)

20.7 / (18.3)

30.2 / (38.4)

32.6 / (44.1)

37.8 / (15.5)
139,440

GPM / (pd. Ft.)


Med. Flow

Total

70,060

77,190

114,230

123,240

(10F Tw)

Sens.

58,910

65,370

90,740

98,940

117,150

14.1 / (8.9)

15.5 / (10.7)

23.0 / (23.3)

24.8 / (26.7)

28.2 / (8.9)
128,090

GPM / (pd. Ft.)


Low Flow

Total

64,380

76,080

108,620

117,210

(12F Tw)

Sens.

55,910

62,060

88,020

95,950

111,140

10.8 / (5.5)

11.9 / (6.6)

18.2 / (15.1)

19.6 / (17.4)

21.6 / (5.5)
113,800

GPM / (pd. Ft.)


75FDB/61FWB, 45% RH
High Flow

Total

57,240

62,820

93,130

100,510

(8F Tw)

Sens.

53,140

58,810

81,850

89,260

105,610

14.4 / (9.4)

15.9 / (11.2)

23.4 / (24.1)

25.3 / (27.8)

28.8 / (9.4)
101,000

GPM / (pd. Ft.)


Med. Flow

Total

50,840

55,860

89,310

96,130

(10F Tw)

Sens.

49,150

54,370

79,650

86,670

97,630

10.2 / (5.0)

11.3 / (6.0)

18.0 / (14.9)

19.4 / (17.2)

20.4 / (5.0)
83,850

GPM / (pd. Ft.)


Low Flow

Total

42,260

46,900

84,180

91,060

(12F Tw)

Sens.

42,260

46,900

76,530

83,390

83,850

7.1 / (2.6)

7.9 / (3.1)

14.1 / (9.6)

15.3 / (11.1)

14.2 / (2.6)
89,130

GPM / (pd. Ft.)


72FDB/58.5FWB, 45% RH
High Flow

Total

44,900

49,650

79,680

85,280

(8F Tw)

Sens.

44,900

49,650

75,350

81,670

89,130

11.3 / (6.0)

12.5 / (7.3)

20.0 / (18.2)

21.4 / (20.6)

22.6 / (6.0)
79,120

GPM / (pd. Ft.)


Med. Flow

Total

39,900

44,230

66,750

72,960

(10F Tw)

Sens.

39,900

44,230

66,750

72,960

79,120

8.1 / (3.2)

9.0 / (3.9)

13.4 / (8.8)

14.8 / (10.5)

16.2 / (3.2)
67,330

GPM / (pd. Ft.)


Low Flow

Total

34,000

37,780

60,390

65,910

(12F Tw)

Sens.

34,000

37,780

60,390

65,910

67,330

5.7 / (1.6)

6.4 / (2.0)

10.2 / (5.3)

11.1 / (6.3)

11.4 / (1.6)

GPM / (pd. Ft.)

4-13

Air Technology Systems, Inc.

Chilled Water OHS-048-C

OHS-060-C

OHS-072-C

OHS-084-C

OHS-120-C

Chilled Water Control Valve - Sized for Medium Flow @ 75FDB/62.5FWB EAT Conditions
2-way (standard) - Spring Actuated (Open/Close)
1" / (8.0 Cv)

1" / (8.0 Cv)

1" / (14.0 Cv)

1" / (14.0 Cv)

1" / (14.0 Cv)

Valve Pressure Rating

Size / (Cv)

300 psig

300 psig

400 psig

400 psig

400 psig

Total Unit Pressure Drop

10.4 Ft.

12.7 Ft.

20.7 Ft.

24.1 Ft.

12.5 Ft.

3-way (optional) - Spring Actuated (Open/Close)


1" / (7.0 Cv)

1" / (7.0 Cv)

1" / (14.0 Cv)

1" / (14.0 Cv)

1" / (14.0 Cv)

Valve Pressure Rating

Size / (Cv)

300 psig

300 psig

400 psig

400 psig

400 psig

Total Unit Pressure Drop

11.8 Ft.

14.4 Ft.

20.7 Ft.

24.1 Ft.

12.5 Ft.

4/ 5.0

4/ 6.7

4/ 6.7

4/ 10.0

Chilled Water Coil - Aluminum Fin, Copper Tube


Rows/Face Area (Ft2)

4/ 5.0

Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Horsepower
CFM @ ext. st. press.
Drive Method

1-1/2 Hp

1-1/2 Hp

2 Hp

3 Hp

2,500 @ 0.5"

3,000 @ 0.5"

3,350 @ 0.5"

4,400 @ 0.5"

Belt Driven

Belt Driven

Belt Driven

Belt Driven

Belt Driven

38,900 (11.4)

40,510 (11.9)

43,580 (12.8)

Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)


ELECTRIC REHEAT / HEAT - BTU/H (Kw)
@ 208V/460V

37,350 (10.9)

38,900 (11.4)

@ 230V

43,140 (12.6)

44,690 (13.1)

44,690 (13.1)

46,300 (13.6)

49,370 (14.5)

@ 480V

38,835 (11.4)

40,385 (11.8)

40,385 (11.8)

41,995 (12.3)

45,065 (13.2)

99,830

130,500

HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB
BTU/H

97,140

111,220

97,880

GPM / Press. Drop (ft.wg)

4.0 / (0.4)

5.0 / (0.6)

3.0 / (0.3)

3.0 / (0.3)

10.0 / (2.2)

Control

Motorized

Motorized

Motorized

Motorized

Motorized

90,000

120,000

STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72F DB
BTU/H (nominal)
Condensate (lb/hr)
Control

48,000

60,000

72,000

50

63

75

94

125

Motorized

Motorized

Motorized

Motorized

Motorized

Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)


Lbs/Hr, (Kw Input)
Std Control

4-10, (3.4)

4-10, (3.4)

4-15, (5.1)

4-15, (5.1)

4-15, (5.1)

Cycling

Cycling

Cycling

Cycling

Cycling

20x16, (2)

20x16, (2)

20x20, (2)

20x20, (2)

24x24, (2)

Filters - 1" deep throwaway


Nominal Size (in.), (Qty)

Connection Sizes - Copper, (Water In/Out connections are sized for flow rates at 75FDB/62.5FWB EAT conditions.)
Cond. Drain, (w/ In-Pan Pump)
Humidifier Inlet
Chilled Water In/Out

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1-1/8" OD

1-1/8" OD

1-1/8" OD

1-1/8" OD

1-3/8" OD

365 lbs

415 lbs

495 lbs

- Chilled Water (4-10 ton) Systems

1 Hp
2,200 @ 0.5"

Performance Data

OHS Model

4 to 10 Ton "OHS"

Physical Size - (Please refer to Section 6 for detailed dimensional data.)


Approx. Weight

280 lbs

290 lbs

Air Technology Systems, Inc.

4-14

Chilled Water -

42F Entering Water Temperature

Cooling Capacities (BTU/H) for 42F Chilled Water Entering the Cooling Coil
80FDB/67FWB

OHS-012C

OHS-018C

OHS-024C

OHS-032C

OHS-040C

OHS-048C

OHS-060C

OHS-072C

OHS-084C

OHS-120C

High Flow

Total

26,260

35,660

40,630

46,540

59,330

96,270

104,840

153,410

165,430

191,860

(8F Tw)

Sensible

16,820

23,440

27,080

31,360

40,970

64,660

71,110

99,310

107,930

128,640

GPM/(Ft.)

6.6/(25.0)

8.9/(43.9)

10.1/(55.8)

11.6/(29.8)

14.8/(47.2)

24.0/(24.2)

26.2/(28.4)

38.3/(59.6)

41.3/(68.6)

42.0/(24.2)

Med Flow

Total

24,550

33,500

38,180

43,710

55,750

89,650

97,830

144,620

155,710

178,610

(10F Tw)

Sensible

16,030

22,450

25,960

30,010

39,270

61,650

67,920

95,310

103,520

122,630

GPM/(Ft.)

4.9/(14.8)

6.7/(25.8)

7.6/(32.9)

8.7/(17.6)

11.1/(27.7)

17.9/(14.1)

19.6/(16.6)

28.9/(35.7)

31.2/(41.0)

35.8/(14.1)

Low Flow

Total

22,660

31,170

35,790

40,430

52,300

81,320

59,560

135,610

146,250

161,960

(12F Tw)

Sensible

15,180

21,390

24,860

28,450

37,600

57,910

64,180

91,260

99,260

115,150

GPM/(Ft.)

3.8/(9.1)

5.2/(16.1)

6.0/(20.8)

6.7/(10.9)

8.7/(17.6)

13.6/(8.4)

15.0/(10.1)

22.6/(22.7)

24.5/(26.3)

27.2/(8.4)

OHS-012C

OHS-018C

OHS-024C

OHS-032C

OHS-040C

OHS-048C

OHS-060C

OHS-072C

OHS-084C

OHS-120C

75FDB/62.5FWB
High Flow

Total

19,450

26,760

30,590

35,200

45,190

72,100

79,070

115,660

124,650

143,530

(8F Tw)

Sensible

14,380

20,310

23,570

27,140

35,750

56,180

62,130

86,120

93,710

111,680

Air Technology Systems, Inc


GPM/(Ft.)

4.9/(14.5)

6.7/(25.9)

7.6/(33.2)

8.8/(17.9)

11.3/(28.4)

18.1/(14.3)

19.9/(17.1)

28.9/(35.8)

31.2/(41.1)

36.2/(14.3)

Med Flow

Total

17,880

24,830

28,560

32,460

42,280

65,300

72,010

108,750

117,090

129,920

(10F Tw)

Sensible

13,620

19,360

22,540

25,730

34,220

52,790

58,560

82,780

90,030

104,910

GPM/(Ft.)

3.6/(8.2)

5.0/(15.1)

5.7/(19.3)

6.5/(10.2)

8.5/(16.7)

13.1/(7.9)

14.5/(9.6)

21.8/(21.4)

23.5/(24.5)

26.2/(7.9)

Low Flow

Total

16,370

22,860

26,690

29,890

39,060

58,870

65,240

101,470

110,240

117,060

(12F Tw)

Sensible

12,880

18,360

21,440

24,390

32,470

49,420

54,950

79,230

86,610

98,170

GPM/(Ft.)

2.8/(5.0)

3.8/(9.2)

4.4/(11.9)

5.0/(6.3)

6.5/(10.2)

9.9/(4.7)

11.0/(5.7)

17.0/(13.6)

18.5/(15.8)

19.8/(4.7)

OHS-012C

OHS-018C

OHS-024C

OHS-032C

OHS-040C

OHS-048C

OHS-060C

OHS-072C

OHS-084C

OHS-120C

72FDB/60FWB
High Flow

Total

16,130

22,430

25,760

29,550

38,380

59,940

65,890

97,760

105,340

119,190

(8F Tw)

Sensible

12,960

18,450

21,470

24,590

32,650

50,840

56,300

78,590

85,540

100,990

GPM/(Ft.)

4.1/(10.4)

5.7/(19.0)

6.4/(24.0)

7.4/(13.0)

9.6/(21.0)

15.1/(10.2)

16.6/(12.3)

24.5/(26.4)

26.4/(30.3)

30.2/(10.2)

Med Flow

Total

14,790

20,650

23,870

27,110

35,430

53,890

59,500

91,990

99,230

107,110

(10F Tw)

Sensible

12,270

17,500

20,430

23,230

30,950

47,500

52,690

75,630

82,350

94,310

GPM/(Ft.)

3.0/(5.9)

4.2/(10.8)

4.8/(14.0)

5.4/(7.4)

7.1/(12.1)

10.8/(5.6)

12.0/(6.8)

18.5/(15.8)

20.0/(18.2)

21.6/(5.6)

Low Flow

Total

13,530

18,980

21,970

24,850

32,490

47,370

52,240

84,910

92,170

94,070

(12F Tw)

Sensible

11,590

16,540

19,310

21,920

29,140

43,510

48,160

71,880

78,490

86,340

GPM/(Ft.)

2.3/(3.4)

3.2/(6.6)

3.7/(8.6)

4.2/(4.5)

5.4/(7.3)

8.0/(3.2)

8.8/(3.8)

14.2/(9.9)

15.5/(11.4)

16.0/(3.2)

(Note: The above Cooling capacities @ standard CFM/e.s.p. as shown on page 4-19 & 4-21, Evaporator Blower/Motor.)

4-19
4-15

Air Technology Systems, Inc.

Chilled Water -

50F Entering Water Temperature

Cooling Capacities (BTU/H) for 50F Chilled Water Entering the Cooling Coil
80FDB/67FWB

OHS-012C

OHS-018C

OHS-024C

OHS-032C

OHS-040C

OHS-048C

OHS-060C

OHS-072C

OHS-084C

OHS-120C

High Flow

Total

17,340

23,720

27,070

31,550

40,300

64,160

69,840

102,640

110,880

127,640

(8F Tw)

Sensible

12,970

18,360

21,350

24,670

32,580

51,150

56,420

77,640

84,770

101,610

GPM/(Ft.)

4.4/(11.6)

6.0/(20.6)

6.8/(26.0)

7.9/(14.5)

10.1/(22.7)

16.1/(11.4)

17.6/(13.4)

25.7/(28.3)

27.9/(32.7)

32.2/(11.4)

Med Flow

Total

15,870

22,110

25,390

29,130

36,840

58,670

64,760

96,430

103,990

116,670

(10F Tw)

Sensible

12,330

17,620

20,530

23,520

31,310

48,530

53,880

74,920

81,700

96,380

GPM/(Ft.)

3.2/(6.5)

4.5/(12.0)

5.1/(15.3)

5.8/(8.2)

7.6/(13.4)

11.8/(6.4)

13.1/(7.8)

19.4/(16.9)

21.0/(19.5)

23.6/(6.4)

Low Flow

Total

14,570

20,410

23,660

26,770

35,130

52,860

58,460

91,030

97,870

105,040

(12F Tw)

Sensible

11,730

16,780

19,640

22,320

29,840

45,480

50,480

72,410

78,760

90,280

GPM/(Ft.)

2.5/(4.0)

3.4/(7.4)

4.0/(9.7)

4.5/(5.1)

5.9/(8.3)

8.9/(3.8)

9.9/(4.6)

15.3/(10.9)

16.4/(12.5)

17.8/(3.8)

OHS-012C

OHS-018C

OHS-024C

OHS-032C

OHS-040C

OHS-048C

OHS-060C

OHS-072C

OHS-084C

OHS-120C

75FDB/62.5FWB
High Flow

Total

12,100

16,730

19,200

22,380

28,770

43,580

45,430

75,480

80,860

86,480

(8F Tw)

Sensible

10,990

15,610

18,170

20,880

27,580

42,410

45,430

67,760

73,570

84,150

GPM/(Ft.)

3.1/(6.1)

4.2/(10.9)

4.8/(14.0)

5.7/(7.8)

7.2/(12.3)

11.0/(5.6)

11.5/(6.1)

19.0/(16.3)

20.4/(18.6)

22.0/(5.6)

Med Flow

Total

10,900

14,880

16,960

19,860

23,400

36,050

39,970

71,720

76,250

71,430

(10F Tw)

Sensible

10,270

14,430

16,690

19,290

23,400

36,050

39,970

65,350

70,550

71,430

GPM/(Ft.)

2.2/(3.3)

3.0/(5.8)

3.4/(7.4)

4.0/(4.2)

4.8/(5.7)

7.3/(2.7)

8.2/(3.3)

14.4/(9.9)

15.4/(11.2)

14.6/(2.7)

Low Flow

Total

8,710

12,380

14,420

15,370

20,380

30,000

33,350

54,330

59,290

59,330

(12F Tw)

Sensible

8,710

12,380

14,420

15,370

20,380

30,000

33,350

54,330

59,290

59,330

GPM/(Ft.)

1.5/(1.3)

2.1/(2.9)

2.4/(3.9)

2.6/(1.7)

3.5/(3.1)

5.1/(1.2)

5.7/(1.6)

9.2/(4.4)

10.0/(5.1)

10.2/(1.2)

OHS-012C

OHS-018C

OHS-024C

OHS-032C

OHS-040C

OHS-048C

OHS-060C

OHS-072C

OHS-084C

OHS-120C

72FDB/60FWB
High Flow

Total

8,950

12,720

14,820

16,220

21,520

33,560

37,150

55,560

60,470

66,440

(8F Tw)

Sensible

8,950

12,720

14,820

16,220

21,520

33,560

37,150

55,560

60,470

66,440

GPM/(Ft.)

2.3/(3.5)

3.2/(6.6)

3.7/(8.7)

4.1/(4.3)

5.5/(7.3)

8.5/(3.5)

9.5/(4.3)

14.1/(9.5)

15.4/(11.1)

17.0/(3.5)

Med Flow

Total

7,930

11,260

13,120

14,070

18,640

27,890

30,910

49,330

53,790

55,100

(10F Tw)

Sensible

7,930

11,260

13,120

14,070

18,640

27,890

30,910

49,330

53,790

55,100

GPM/(Ft.)

1.6/(1.6)

2.3/(3.5)

2.7/(4.6)

2.9/(2.1)

3.8/(3.7)

5.7/(1.6)

6.4/(2.0)

10.0/(5.1)

11.0/(6.0)

11.4/(1.6)

Low Flow

Total

6,690

9,550

11,140

11,500

15,340

20,870

23,350

41,390

45,320

41,060

(12F Tw)

Sensible

6,690

9,550

11,140

11,500

15,340

20,870

23,350

41,390

45,320

41,060

GPM/(Ft.)

1.1/(0.7)

1.6/(1.6)

1.9/(2.3)

2.0/(0.8)

2.6/(1.7)

3.6/(0.5)

4.1/(0.7)

7.0/(2.7)

7.7/(3.2)

7.2/(0.5)

(Note: The above Cooling capacities @ standard CFM/e.s.p. as shown on page 4-19 & 4-21, Evaporator Blower/Motor.)

Air Technology Systems, Inc.

4-16

Free-Cooling & Alternate Water Source

Free-Cooling

MODEL TYPE ........................................... page

DX with Free-Cooling
Self-Contained Glycol Cooled w/ FC:
1-5 Ton, models OHS-012/060-G-FC............................ 4-17/19
4-10 Ton, models OHS-048/120-DG-FC........................ 4-20/21

Self-Contained Water Cooled w/ FC:

- Free-Cooling & Alternate Water Source Systems

1-5 Ton, models OHS-012/060-W-FC............................ 4-22/23


4-10 Ton, models OHS-048/120-DW-FC....................... 4-24/25

DX with Alternate Water Source

Air Technology Systems, Inc


Alternate Water Source:

1-5 Ton, models OHS-012/060-( )-AWS............................. 4-26


4-10 Ton, models OHS-048/120-D()-AWS.......................... 4-27
42F / 50F EWT Performance Data................................... 4-28

Alternate Water
Source

Remote Liquid Chiller


(by others)

Alternate Water
Source Cooling Coil

Pump
(by others)
Flow
Switch

Alternate Water
Source Aqua-Stat
T

Remote Air Cooled


Condenser
Scroll
Compressor

Flooded
Head Pressure
Control Valve
Relief
Valve

Receiver

Air Technology Systems, Inc.

DX - Cooling
Coil

LP

HP

Sight
Glass

Refrigerant
Reclaim Port

4-17

AWS
Control
Valve

FS

Equalizer
Line

Performance Data

Free-Cooling / Alternate Water Source

Feeler
Bulb

Solenoid
Valve
Refrigerant
Drier / Strainer

Expansion
Valve

DX Glycol Cooled w/ Free-Cooling - 1 to 5 Ton "OHS"


012-HG-FC

018-HG-FC

024-HG-FC

032-HG-FC

040-HG-FC

048-G-FC

060-G-FC

NET DX COOLING CAPACITY - BTU/H, (includes standard DX w/ FC evaporator motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
13,390

18,960

25,090

32,000

34,910

57,150

62,670

Sensible

10,435

15,060

19,160

23,085

27,500

46,565

51,120

Total

12,200

17,541

22,975

28,175

31,855

52,325

57,335

Sensible

10,450

15,194

18,710

23,700

26,975

45,920

50,410

Total

11,510

16,720

21,900

27,800

30,540

49,770

54,525

Sensible

10,210

14,880

18,275

22,045

26,455

44,970

49,370

Total

12,900

18,375

23,990

30,580

33,840

54,920

60,120

Sensible

11,650

16,800

20,535

24,540

30,475

51,075

56,140

Total

11,780

17,035

22,430

28,175

31,290

50,785

55,550

Sensible

11,171

16,200

20,195

23,700

29,270

49,080

53,900

Total

11,120

16,235

21,355

27,065

29,770

48,360

52,680

Sensible

10,875

15,855

19,760

23,375

28,610

47,710

51,930

75FDB/62.5FWB, 50% RH

72FDB/60FWB, 50% RH

80FDB/65FWB, 45% RH

75FDB/61FWB, 45% RH

72FDB/58.5FWB, 45% RH

FREE-COOLING CAPACITY - BTU/H @ 45F Entering Glycol Temperature, 40% Ethylene Glycol Solution
80FDB/67FWB, 50% RH
Total

16,040

22,685

27,755

32,355

39,420

57,050

63,700

Sensible

12,500

17,960

21,670

25,080

32,180

48,450

54,265

Total

12,880

18,190

22,170

25,910

31,670

45,395

50,560

Sensible

11,460

16,440

19,800

22,795

29,290

44,130

49,325

Total

11,160

15,670

19,125

22,455

27,265

39,955

44,570

Sensible

10,665

15,235

18,370

21,150

27,025

39,955

44,570

Total

15,110

21,330

25,990

30,380

37,140

53,235

59,270

Sensible

13,400

19,225

23,140

26,640

34,270

51,680

57,765

Total

12,200

16,815

20,840

24,630

29,405

44,500

49,635

Sensible

12,000

16,815

20,630

23,820

29,405

44,500

49,635

Total

10,740

15,260

18,465

21,010

26,380

39,890

44,490

Sensible

10,740

15,260

18,465

21,010

26,380

39,890

44,490

5.3 GPM

6.9 GPM

8.9 GPM

9.7 GPM

15.1 GPM

16.7 GPM

75FDB/62.5FWB, 50% RH

72FDB/60FWB, 50% RH

80FDB/65FWB, 45% RH

75FDB/61FWB, 45% RH

72FDB/58.5FWB, 45% RH

Flow Rates, Free-Cooling Coil


Flow Rate

3.8 GPM

Evaporator Blower / Motor, DX w/ Free-Cooling - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
1/4 Hp

1/3 Hp

1/2 Hp

1/2 Hp

3/4 Hp

1-1/2 Hp

2 Hp

CFM @ ext. st. press.

Horsepower

500 @ 0.5"

750 @ 0.5"

900 @ 0.5"

1,000 @ 0.5"

1,415 @ 0.5"

2,200 @ 0.5"

2,500 @ 0.5"

Drive Method

Belt Driven

Belt Driven

Belt Driven

Belt Driven

Belt Driven

Belt Driven

Belt Driven

Evaporator Coils, (Both DX & Free-Cooling Respectively) - Aluminum Fin, Copper Tube

- DX Glycol Cooled w/ FC (1 to 5 Ton Systems)

Total

Performance Data

OHS Model

DX Coil:
Rows/ Face Area (Ft2)

3/ 2.1

3/ 2.1

3/ 2.1

3/ 2.8

3/ 2.8

4/ 5.0

4/ 5.0

4/ 2.1

4/ 2.1

4/ 2.1

4/ 2.8

4/ 2.8

4/ 5.0

4/ 5.0

FC Coil:
Rows/Face Area (Ft2)

Air Technology Systems, Inc.

4-18

DX Glycol Cooled w/ Free-Cooling - 1 to 5 Ton "OHS"

Performance Data

OHS Model

012-HG-FC

018-HG-FC

024-HG-FC

032-HG-FC

040-HG-FC

048-G-FC

060-G-FC

Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)


ELECTRIC REHEAT / HEAT - BTU/H (Kw)
@ 208V

17,135 (5.0)

17,135 (5.0)

17,135 (5.0)

17,425 (5.1)

17,955 (5.3)

37,350 (10.9)

38,900 (11.4)

@ 230V

18,840 (5.5)

18,840 (5.5)

18,840 (5.5)

19,130 (5.6)

19,660 (5.8)

43,140 (12.6)

44,690 (13.1)

@ 460V

17,355 (5.1)

17,355 (5.1)

17,355 (5.1)

17,645 (5.2)

18,175 (5.3)

37,350 (10.9)

38,900 (11.4)

@ 277/480V

18,065 (5.3)

18,065 (5.3)

18,065 (5.3)

18,355 (5.4)

18,885 (5.5)

38,835 (11.4)

40,385 (11.8)

Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)


Lbs/Hr, (Kw Input)

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

4-10, (3.4)

4-10, (3.4)

Cycling

Cycling

Cycling

Cycling

Cycling

Cycling

Cycling

Std Control

Compressor - Heat pump duty rated, HCFC Ozone Safe R-22


Type, (Qty.)

Recip., (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Watts Input

1,442

1,729

2,227

2,882

3,027

4,699

5,290

DX Glycol Condenser Data - Based on 40% ethylene glycol solution


Tot. Heat of Reject.

17,270 Btu/h

23,990 Btu/h

31,305 Btu/h

40,340 Btu/h

43,625 Btu/h

68,360 Btu/h

75,390 Btu/h

- DX Glycol Cooled w/ FC (1 to 5 Ton Systems)

GPM @ 110F EGT

3.8 GPM

5.3 GPM

6.9 GPM

8.9 GPM

9.7 GPM

15.1 GPM

16.7 GPM

Total Unit PD (Ft. of H2O)

11.8 Ft.

21.1 Ft.

38.4 Ft.

28.1 Ft.

34.3 Ft.

20.1 Ft.

24.9 Ft.

Type

Coaxial

Coaxial

Coaxial

Coaxial

Coaxial

Coaxial

Coaxial

DX-Head Pressure & Free-Cooling Coil Control Valve Combinations


DX Hd Pr. Valve Type - - - - - - - - 3-way, 150 psig DX Condenser Source Regulating Valve - field installed - - - - - - - Free-Cooling Valve - 3-way, Spring Actuated (Open/Close):

Air Technology Systems, Inc

4-19

FC Valve Size / (Cv)

1/2" / (5.0 Cv)

3/4" / (5.0 Cv)

3/4" / (5.0 Cv)

3/4" / (5.0 Cv)

3/4" / (5.0 Cv)

1" / (7.0 Cv)

1" / (7.0 Cv)

300 psig

300 psig

300 psig

300 psig

300 psig

300 psig

300 psig

Valve Pressure Rating

Optional Valve Combinations - Please refer to page 3-9 for Higher Pressure Rated and Modulating (0-10 Vdc) Valve Combination Options!
Connection Sizes - Copper
Condensate Drain

3/4" FPT

3/4" FPT

3/4" FPT

3/4" FPT

3/4" FPT

3/4" FPT

3/4" FPT

Humidifier Inlet

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

Source Glycol In/Out

5/8" OD

7/8" OD

7/8" OD

7/8" OD

7/8" OD

1-1/8" OD

1-1/8" OD

20x20, (1)

20x20, (1)

20x20, (1)

20x20, (1)

20x16, (2)

20x16, (2)

300 lbs

310 lbs

500 lbs

510 lbs

Filters - 1" deep throwaway


Nom. Size (in.), (Qty.)

20x20, (1)

Physical Size - (Please refer to Section 6 for detailed dimensional data.)


Approx. Weight 245 lbs

265 lbs

275 lbs

DRYCOOLER DATA - Please refer to Glycol Pump / Drycooler Engineering Manual


105F Amb. Selections - Optional - Please refer to Glycol Pump / Drycooler Engineering Manual
Glycol Pump Packages - Optional - Please refer to Glycol Pump / Drycooler Engineering Manual

Air Technology Systems, Inc.

DX Glycol Cooled w/ Free-Cooling - 4 to 10 Ton "OHS" (Dual)


048-DG-FC

072-DG-FC

084-DG-FC

120-DG-FC

NET DX COOLING CAPACITY - BTU/H, (includes standard DX w/ FC evaporator motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
51,260

70,230

87,445

123,970

Sensible

39,730

61,010

69,465

95,280

Total

46,840

64,090

79,565

113,045

Sensible

39,230

60,180

69,420

93,920

Total

44,600

60,990

75,580

107,490

Sensible

38,400

58,520

68,115

91,925

Total

49,150

67,340

83,055

118,680

Sensible

43,340

65,360

77,390

104,065

Total

45,500

62,635

76,640

109,590

Sensible

41,840

61,750

73,350

100,420

Total

43,320

59,880

73,150

104,185

Sensible

41,000

59,635

71,130

98,400

75FDB/62.5FWB, 50% RH

72FDB/60FWB, 50% RH

80FDB/65FWB, 45% RH

75FDB/61FWB, 45% RH

72FDB/58.5FWB, 45% RH

FREE-COOLING CAPACITY - BTU/H @ 45F Entering Glycol Temperature, 40% Ethylene Glycol Solution
80FDB/67FWB, 50% RH
Total

54,105

89,015

105,970

119,730

Sensible

42,715

72,360

83,255

99,390

Total

43,290

72,275

85,820

95,730

Sensible

39,055

66,680

76,665

90,850

Total

37,290

62,365

74,595

82,130

Sensible

36,180

61,770

71,425

82,130

Total

50,780

84,960

100,770

112,260

Sensible

45,670

78,090

89,680

106,340

Total

39,925

68,360

81,685

92,370

Sensible

39,925

68,360

81,685

92,370

Total

36,260

61,260

71,495

82,820

Sensible

36,260

61,260

71,495

82,820

13.7 GPM

18.7 GPM

23.8 GPM

33.0 GPM

75FDB/62.5FWB, 50% RH

72FDB/60FWB, 50% RH

80FDB/65FWB, 45% RH

75FDB/61FWB, 45% RH

72FDB/58.5FWB, 45% RH

Flow Rates, Free-Cooling Coil


Flow Rate

Evaporator Blower / Motor, DX w/ Free-Cooling - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Horsepower
CFM @ ext. st. press.
Drive Method

1 Hp

1-1/2 Hp

2 Hp

3 Hp

1,800 @ 0.5"

3,000 @ 0.5"

3,350 @ 0.5"

4,400 @ 0.5"

Belt Driven

Belt Driven

Belt Driven

Belt Driven

Evaporator Coils, (Both DX & Free-Cooling Respectively) - Aluminum Fin, Copper Tube

- DX Glycol Cooled w/ FC (4 to 10 Ton Dual Systems)

Total

Performance Data

OHS Model

DX Coil:
Rows/ Face Area (ft2)

4/ 4.1 ft2

4/ 6.7 ft2

4/ 6.7 ft2

4/ 10.0 ft2

Rows/Face Area (ft2)

4/ 4.1 ft2

4/ 6.7 ft2

4/ 6.7 ft2

4/ 10.0 ft2

FC Coil:

Air Technology Systems, Inc.

4-20

DX Glycol Cooled w/ Free-Cooling - 4 to 10 Ton "OHS" (Dual)

Performance Data

OHS Model

048-DG-FC

072-DG-FC

084-DG-FC

120-DG-FC

Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)


ELECTRIC REHEAT / HEAT - BTU/H (Kw)
@ 208V/460V

36,810 (10.9)

38,900 (11.4)

40,510 (11.9)

43,580 (12.8)

@ 230V

42,600 (12.5)

44,690 (13.1)

46,300 (13.6)

49,370 (14.5)

@ 480V

38,295 (11.2)

40,385 (11.8)

41,995 (12.3)

45,065 (13.2)

Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)


Lbs/Hr, (Kw Input)

- DX Glycol Cooled w/ FC (4 to 10 Ton Dual Systems)

4-10, (3.4)

4-15, (5.1)

4-15, (5.1)

4-15, (5.1)

Cycling

Cycling

Cycling

Cycling

Scroll, (2)

Scroll, (2)

Scroll, (2)

Scroll, (2)

2,188

2,973

4,103

5,290

61,775 Btu/h

84,385 Btu/h

107,570 Btu/h

149,155 Btu/h

13.7 GPM

18.7 GPM

23.8 GPM

33.0 GPM

Total Unit Pressure Drop (Ft. of H2O)

37.8 Ft.

34.8 Ft.

41.0 Ft.

29.5 Ft.

Type

Coaxial

Coaxial

Coaxial

Coaxial

Std Control

Compressor - Heat pump duty rated, HCFC Ozone Safe R-22


Type, (Qty.)
Watt Input (per compressor)

DX Glycol Condenser Data - Based on 40% ethylene glycol solution


Total Heat of Rejection
GPM @ 110F EGT

DX-Head Pressure & Free-Cooling Coil Control Valve Combinations


DX Head Pressure Regulating Valves:
DX Hd Pr. Valve Type - - - - - - - - - - -3-way, 150 psig DX Condenser Source Regulating Valve - factory installed - - - - - - - - - - - Free-Cooling Valve - 3-way, Spring Actuated (Open/Close):

Air Technology Systems, Inc

4-21

FC Valve Size / (Cv)

Valve Pressure Rating

1" / (7.0 Cv)

1" / (14.0 Cv)

1" / (14.0 Cv)

1" / (14.0 Cv)

300 psig

400 psig

400 psig

400 psig

Optional Valve Combos - Please refer to page 3-9 for Higher Pressure Rated and Modulating (0-10 Vdc) Valve Combination Options!

Connection Sizes - Copper

Condensate Drain, (w/ In-Pan Pump)


Humidifier Inlet
Source Glycol In/Out

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1-1/8" OD

1-1/8" OD

1-3/8" OD

1-3/8" OD

16x20, (2)

20x20, (2)

20x20, (2)

24x24, (2)

660 lbs

745 lbs

Filters - 1" deep throwaway


Nominal Size (in.), (Qty.)

Physical Size - (Please refer to Section 6 for detailed dimensional data.)


Approx. Weight

550 lbs

570 lbs

DRYCOOLER DATA - Please refer to Glycol Pump / Drycooler Engineering Manual


105F Amb. Selections - Optional - Please refer to Glycol Pump / Drycooler Engineering Manual
Glycol Pump Packages - Optional - Please refer to Glycol Pump / Drycooler Engineering Manual

Air Technology Systems, Inc.

DX Water Cooled w/ Free-Cooling - 1 to 5 Ton "OHS"


012-HW-FC

018-HW-FC

024-HW-FC

032-HW-FC

040-HW-FC

048-W-FC

060-W-FC

DX COOLING CAPACITY - BTU/H, (includes standard DX w/ FC evaporator motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
16,394

21,125

27,990

35,550

39,115

64,250

70,665

Sensible

11,675

16,000

20,455

24,575

29,500

49,240

54,100

Total

14,850

19,345

25,750

32,700

35,830

58,820

64,690

Sensible

11,340

15,625

20,100

24,265

28,800

48,580

53,445

Total

14,000

18,380

24,560

31,150

34,109

56,070

61,650

Sensible

11,050

16,400

19,680

23,775

28,093

47,600

52,345

Total

15,570

20,430

26,840

34,170

37,355

61,635

67,730

Sensible

12,440

17,645

21,825

26,300

31,600

53,560

58,955

Total

14,380

18,950

24,920

31,600

35,120

57,130

62,760

Sensible

12,250

17,040

21,075

25,360

30,560

51,780

56,975

Total

13,620

18,065

23,685

30,060

33,460

54,460

59,795

Sensible

12,010

16,710

20,700

24,820

30,470

50,820

55,910

75FDB/62.5FWB, 50% RH

72FDB/60FWB, 50% RH

80FDB/65FWB, 45% RH

75FDB/61FWB, 45% RH

72FDB/58.5FWB, 45% RH

FREE-COOLING CAPACITY - BTU/H @ 45F Entering Water Temperature, 0% Glycol Solution


80FDB/67FWB, 50% RH
Total

20,595

27,790

32,980

39,210

48,040

75,585

83,475

Sensible

14,380

20,050

23,810

28,095

35,960

55,990

62,325

Total

16,240

22,100

26,160

31,060

38,605

60,370

66,790

Sensible

12,975

18,215

21,605

25,280

32,710

51,050

56,895

Total

14,010

19,125

22,600

26,820

33,565

52,360

57,970

Sensible

12,040

16,935

20,075

23,400

30,390

47,520

52,960

Total

19,030

25,895

30,615

36,395

45,190

70,785

78,305

Sensible

15,130

21,250

25,190

29,490

38,160

59,610

66,435

Total

15,350

20,985

24,750

29,390

36,840

57,550

63,570

Sensible

13,565

19,090

22,605

26,325

34,220

53,600

59,650

Total

13,295

18,050

21,240

25,440

30,250

48,250

53,590

Sensible

12,620

17,640

20,880

24,400

30,250

48,250

53,590

4.9 GPM

6.4 GPM

8.3 GPM

9.0 GPM

14.1 GPM

15.6 GPM

75FDB/62.5FWB, 50% RH

72FDB/60FWB, 50% RH

80FDB/65FWB, 45% RH

75FDB/61FWB, 45% RH

72FDB/58.5FWB, 45% RH

Flow Rates, Free-Cooling Coil


Flow Rate

3.8 GPM

Evaporator Blower / Motor, DX w/ Free-Cooling - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
1/4 Hp

1/3 Hp

1/2 Hp

1/2 Hp

3/4 Hp

1-1/2 Hp

2 Hp

CFM @ ext. st. press.

Horsepower

500 @ 0.5"

750 @ 0.5"

900 @ 0.5"

1,000 @ 0.5"

1,415 @ 0.5"

2,200 @ 0.5"

2,500 @ 0.5"

Drive Method

Belt Driven

Belt Driven

Belt Driven

Belt Driven

Belt Driven

Belt Driven

Belt Driven

- DX Water Cooled w/ FC (1 to 5 Ton Systems)

Total

Performance Data

OHS Model

Evaporator Coils, (Both DX & Free-Cooling Respectively) - Aluminum Fin, Copper Tube
DX Coil:
Rows/ Face Area (ft2)

3/ 2.1

3/ 2.1

3/ 2.1

3/ 2.8

3/ 2.8

4/ 5.0

4/ 5.0

4/ 2.1

4/ 2.1

4/ 2.1

4/ 2.8

4/ 2.8

4/ 5.0

4/ 5.0

FC Coil:
Rows/Face Area (ft2)

Air Technology Systems, Inc.

4-22

DX Water Cooled w/ Free-Cooling - 1 to 5 Ton "OHS"

Performance Data

OHS Model

012-HW-FC

018-HW-FC

024-HW-FC

032-HW-FC

040-HW-FC

048-W-FC

060-W-FC

Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)


ELECTRIC REHEAT / HEAT - BTU/H (Kw)
@ 208V

17,135 (5.0)

17,135 (5.0)

17,135 (5.0)

17,425 (5.1)

17,955 (5.3)

37,350 (10.9)

38,900 (11.4)

@ 230V

18,840 (5.5)

18,840 (5.5)

18,840 (5.5)

19,130 (5.6)

19,660 (5.8)

43,140 (12.6)

44,690 (13.1)

@ 460V

17,355 (5.1)

17,355 (5.1)

17,355 (5.1)

17,645 (5.2)

18,175 (5.3)

37,350 (10.9)

38,900 (11.4)

@ 277/480V

18,065 (5.3)

18,065 (5.3)

18,065 (5.3)

18,355 (5.4)

18,885 (5.5)

38,835 (11.4)

40,385 (11.8)

Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)


Lbs/Hr, (Kw Input)
Std Control

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

2-5, (1.7)

4-10, (3.4)

4-10, (3.4)

Cycling

Cycling

Cycling

Cycling

Cycling

Cycling

Cycling

Compressor - Heat pump duty rated, HCFC Ozone Safe R-22


Type, (Qty.)

Recip., (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Scroll, (1)

Watts Input

1,245

1,239

1,633

2,118

2,222

3,451

3,867

DX Water Cooled Condenser Data - Based on 0% glycol solution

- DX Water Cooled w/ FC (1 to 5 Ton Systems)

Tot Heat of Reject.

18,900 Btu/h

24,350 Btu/h

32,145 Btu/h

41,325 Btu/h

44,865 Btu/h

70,600 Btu/h

77,890 Btu/h

GPM @ 85F EWT

3.8 GPM

4.9 GPM

6.4 GPM

8.3 GPM

9.0 GPM

14.1 GPM

15.6 GPM

Total Unit PD (Ft. of H2O)

12.1 Ft.

16.3 Ft.

26.9 Ft.

21.6 Ft.

25.1 Ft.

16.5 Ft.

22.7 Ft.

Type

Coaxial

Coaxial

Coaxial

Coaxial

Coaxial

Coaxial

Coaxial

DX-Head Pressure & Free-Cooling Coil Control Valve Combinations


DX Head Pressure Control Valve Type - - - - - - - - 3-way, 150 psig DX Condenser Source Regulating Valve - field installed - - - - - - - Free-Cooling Valve - 3-way, Spring Actuated (Open/Close):
FC Valve Size / (Cv)

1/2" / (5.0 Cv)

3/4" / (5.0 Cv)

3/4" / (5.0 Cv)

3/4" / (5.0 Cv)

3/4" / (5.0 Cv)

1" / (7.0 Cv)

1" / (7.0 Cv)

Air Technology Systems, Inc

4-23

Valve Pressure Rating

300 psig

300 psig

300 psig

300 psig

300 psig

300 psig

300 psig

Optional Valve Combinations - Please refer to page 3-9 for Higher Pressure Rated and Modulating (0-10 Vdc) Valve Combination Options!

Connection Sizes - Copper


Condensate Drain

3/4" FPT

3/4" FPT

3/4" FPT

3/4" FPT

3/4" FPT

3/4" FPT

3/4" FPT

Humidifier Inlet

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1/4" OD

Source Water In/Out

5/8" OD

7/8" OD

7/8" OD

7/8" OD

7/8" OD

1-1/8" OD

1-1/8" OD

20x20, (1)

20x20, (1)

20x20, (1)

20x20, (1)

20x20, (1)

20x16, (2)

20x16, (2)

300 lbs

310 lbs

500 lbs

510 lbs

Filters - 1" deep throwaway


Nom. Size (in.), (Qty.)

Physical Size - (Please refer to Section 6 for detailed dimensional data.)


Approx. Weight

245 lbs

265 lbs

275 lbs

Air Technology Systems, Inc.

DX Water Cooled w/ Free-Cooling - 4 to 10 Ton (Dual) "OHS"


048-DW-FC

072-DW-FC

084-DW-FC

120-DW-FC

NET DX COOLING CAPACITY - BTU/H, (includes standard DX w/ FC evaporator motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
57,200

79,165

98,760

139,210

Sensible

42,320

63,770

73,735

101,715

Total

52,580

72,510

90,475

127,660

Sensible

41,620

63,225

72,760

100,040

Total

50,100

69,035

86,090

121,610

Sensible

40,820

62,045

71,400

98,010

Total

54,890

75,840

94,300

133,265

Sensible

45,740

70,425

81,160

110,080

Total

50,960

70,200

87,050

123,460

Sensible

44,180

67,685

78,670

106,285

Total

48,620

66,785

82,760

117,645

Sensible

43,390

65,220

77,320

104,340

75FDB/62.5FWB, 50% RH

72FDB/60FWB, 50% RH

80FDB/65FWB, 45% RH

75FDB/61FWB, 45% RH

72FDB/58.5FWB, 45% RH

FREE-COOLING CAPACITY - BTU/H @ 45F Entering Water Temperature, 0% Glycol Solution


80FDB/67FWB, 50% RH
Total

65,040

114,520

129,450

155,760

Sensible

47,200

82,710

92,855

114,040

Total

51,715

92,810

103,815

124,035

Sensible

42,900

75,940

84,740

103,790

Total

44,720

81,270

90,630

107,260

Sensible

39,870

71,045

79,175

96,470

Total

60,530

108,660

121,700

145,395

Sensible

50,020

88,545

98,880

121,150

Total

49,015

89,840

99,690

117,850

Sensible

44,910

80,380

89,360

108,830

Total

42,040

78,890

87,155

100,940

Sensible

41,440

75,090

83,385

100,300

12.7 GPM

17.5 GPM

22.2 GPM

30.8 GPM

75FDB/62.5FWB, 50% RH

72FDB/60FWB, 50% RH

80FDB/65FWB, 45% RH

75FDB/61FWB, 45% RH

72FDB/58.5FWB, 45% RH

Flow Rates, Free-Cooling Coil


Flow Rate

Evaporator Blower / Motor, DX w/ Free-Cooling - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Horsepower
CFM @ ext. st. press.
Drive Method

1 Hp

1-1/2 Hp

2 Hp

3 Hp

1,800 @ 0.5"

3,000 @ 0.5"

3,350 @ 0.5"

4,400 @ 0.5"

Belt Driven

Belt Driven

Belt Driven

Belt Driven

Evaporator Coils, (Both DX & Free-Cooling Respectively) - Aluminum Fin, Copper Tube

- DX Water Cooled w/ FC (4 to 10 Ton Dual Systems)

Total

Performance Data

OHS Model

DX Coil:
Rows/ Face Area (ft2)

4/ 4.1

4/ 6.7

4/ 6.7

4/ 10.0

Rows/Face Area (ft2)

4/ 4.1

4/ 6.7

4/ 6.7

4/ 10.0

FC Coil:

Air Technology Systems, Inc.

4-24

DX Water Cooled w/ Free-Cooling - 4 to 10 Ton (Dual) "OHS"

Performance Data

OHS Model

048-DW-FC

072-DW-FC

084-DW-FC

120-DW-FC

Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)


ELECTRIC REHEAT / HEAT - BTU/H (Kw)
@ 208V/460V

36,810 (10.9)

38,900 (11.4)

40,510 (11.9)

43,580 (12.8)

@ 230V

42,600 (12.5)

44,690 (13.1)

46,300 (13.6)

49,370 (14.5)

@ 480V

38,295 (11.2)

40,385 (11.8)

41,995 (12.3)

45,065 (13.2)

Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)


Lbs/Hr, (Kw Input)

- DX Water Cooled w/ FC (4 to 10 Ton Dual Systems)

4-10, (3.4)

4-15, (5.1)

4-15, (5.1)

4-15, (5.1)

Cycling

Cycling

Cycling

Cycling

Scroll, (2)

Scroll, (2)

Scroll, (2)

Scroll, (2)

2,188

2,973

4,103

5,290

63,525 Btu/h

87,405 Btu/h

110,770 Btu/h

154,060 Btu/h

12.7 GPM

17.5 GPM

22.2 GPM

30.8 GPM

Press. Drop (Ft. of H2O)

26.8 Ft.

25.2 Ft.

28.3 Ft.

25.7 Ft.

Type

Coaxial

Coaxial

Coaxial

Coaxial

Std Control

Compressor - Heat pump duty rated, HCFC Ozone Safe R-22


Type, (Qty.)
Watt Input (per compressor)

DX Water Cooled Condenser Data - Based on 0% glycol solution


Total Heat of Reject.
GPM @ 85F EWT

DX-Head Pressure & Free-Cooling Coil Control Valve Combinations


DX Hd Pr. Valve Type - - - - - - - - - - 3-way, 150 psig DX Condenser Source Regulating Valve - factory installed - - - - - - - - - Free-Cooling Valve - 3-way, Spring Actuated (Open/Close):
FC Valve Size / (Cv)

1" / (7.0 Cv)

1" / (14.0 Cv)

1" / (14.0 Cv)

1" / (14.0 Cv)

300 psig

400 psig

400 psig

400 psig

Air Technology Systems, Inc


Valve Pressure Rating

Optional Valve Combos - Please refer to page 3-9 for Higher Pressure Rated and Modulating (0-10 Vdc) Valve Combination Options!

Connection Sizes - Copper

Condensate Drain, (w/ In-Pan Pump)

Humidifier Inlet
Source Water In/Out

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

3/4" FPT, (1/2"OD)

1/4" OD

1/4" OD

1/4" OD

1/4" OD

1-1/8" OD

1-1/8" OD

1-3/8" OD

1-3/8" OD

16x20, (2)

20x20, (2)

20x20, (2)

24x24, (2)

660 lbs

745 lbs

Filters - 1" deep throwaway


Nominal Size (in.), (Qty.)

Physical Size - (Please refer to Section 6 for detailed dimensional data.)


Approx. Weight

4-25

550 lbs

570 lbs

Air Technology Systems, Inc.

Alternate Water Source


012-AWS

018-AWS

024-AWS

032-AWS

040-AWS

(45F EWT)

048-AWS

060-AWS

83,430

90,800

COOLING CAPACITY - BTU/H @ 45F EWT, 0% Glycol Solution (includes motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
High Flow
(8F Tw)

Total
Sens.
GPM / (pd. Ft.)

22,970

31,040

35,250

40,690

51,820

15,340

21,380

24,650

28,610

37,500

58,940

64,920

5.8 / (19.6)

7.8 / (34.0)

8.8 / (43.1)

10.2 / (23.3)

13.0 / (36.8)

20.9 / (18.6)

22.8 / (21.9)
84,490

Med. Flow

Total

21,200

29,000

32,920

37,920

48,510

77,020

(10F Tw)

Sens.

14,560

20,470

23,600

27,310

35,930

56,080

62,060

4.3 / (11.2)

5.8 / (19.8)

6.6 / (25.1)

7.6 / (13.6)

9.7 / (21.5)

15.5 / (10.7)

17.1 / (12.7)

GPM / (pd. Ft.)


Low Flow

Total

19,390

26,780

30,740

34,840

45,270

69,650

76,840

(12F Tw)

Sens.

13,760

19,470

22,600

25,870

34,360

52,730

58,530

3.3 / (6.8)

4.5 / (12.2)

5.2 / (15.8)

5.8 / (8.3)

7.6 / (13.4)

11.7 / (6.4)

13.0 / (7.7)

16,460

22,790

25,940

30,060

38,720

60,970

67,120

GPM / (pd. Ft.)


75FDB/62.5FWB, 50% RH
High Flow
(8F Tw)

Total
Sens.
GPM / (pd. Ft.)

18,450

21,330

24,610

32,550

50,870

56,430

5.7 / (19.4)

6.5 / (24.6)

7.6 / (13.4)

9.7 / (21.5)

15.4 / (10.6)

17.0 / (12.7)
60,770

Med. Flow

Total

15,110

21,030

24,210

27,600

36,030

54,830

(10F Tw)

Sens.

12,340

17,550

20,420

23,310

31,050

47,630

53,000

3.1 / (6.0)

4.2 / (11.1)

4.9 / (14.5)

5.6 / (7.6)

7.3 / (12.5)

11.1 / (5.8)

12.4 / (7.1)

GPM / (pd. Ft.)


Low Flow

Total

13,840

19,360

22,320

25,360

33,140

48,820

54,020

(12F Tw)

Sens.

11,690

16,640

19,340

22,060

29,340

44,100

48,950

2.3 / (3.7)

3.3 / (6.8)

3.8 / (8.9)

4.3 / (4.7)

5.6 / (7.6)

8.3 / (3.4)

9.2 / (4.1)

13,510

18,750

21,580

24,820

32,320

49,770

54,740

GPM / (pd. Ft.)


72FDB/60FWB, 50% RH
High Flow
(8F Tw)

Total
Sens.
GPM / (pd. Ft.)

11,700

16,630

19,340

22,120

29,440

45,580

50,480

3.4 / (7.5)

4.7 / (13.6)

5.5 / (17.8)

6.3 / (9.5)

8.1 / (15.4)

12.6 / (7.4)

13.9 / (8.8)

Med. Flow

Total

12,390

17,180

19,740

22,710

29,420

42,980

47,200

(10F Tw)

Sens.

11,080

15,690

18,190

20,860

27,580

41,330

45,670

2.5 / (4.2)

3.5 / (7.7)

4.0 / (10.0)

4.6 / (5.4)

6.0 / (8.6)

8.7 / (3.7)

9.6 / (4.5)

Low Flow

GPM / (pd. Ft.)


Total

11,120

15,320

17,510

20,120

25,810

33,790

37,580

(12F Tw)

Sens.

10,300

14,460

16,680

19,170

25,100

33,790

37,580

1.9 / (2.2)

2.6 / (4.5)

3.0 / (5.7)

3.4 / (3.1)

4.4 / (4.9)

5.8 / (1.6)

6.4 / (2.1)

GPM / (pd. Ft.)

Alternate Water Source Control Valve - Sized for Medium Flow @ 75FDB/62.5FWB EAT Conditions
2-way (standard) - Spring Actuated (Open/Close)
Size / (Cv)
Pressure Rating
Total Unit PD

1/2" / (3.5)

3/4" / (3.5)

3/4" / (3.7)

3/4" / (3.7)

3/4" / (3.7)

1.0" / (8.0)

1.0" / (8.0)

300 psig

300 psig

300 psig

300 psig

300 psig

300 psig

300 psig

8.0 Ft.

14.6 Ft.

19.4 Ft.

14.2 Ft.

22.6 Ft.

10.4 Ft.

12.7 Ft.

1/2" / (5.0)

3/4" / (5.0)

3/4" / (5.0)

3/4" / (5.0)

3/4" / (5.0)

1.0" / (7.0)

1.0" / (7.0)

300 psig

300 psig

300 psig

300 psig

300 psig

300 psig

300 psig

7.1 Ft.

12.9 Ft.

17.0 Ft.

11.2 Ft.

17.5 Ft.

11.8 Ft.

14.4 Ft.

4 / 2.8 ft2

4 / 2.8 ft2

4/ 5.0 ft2

4/ 5.0 ft2

3-way (optional) - Spring Actuated (Open/Close)


Size / (Cv)
Pressure Rating
Total Unit PD

- Alternate Water Source (45F EWT)

13,000
4.2 / (10.7)

Performance Data

OHS Model

- 1 to 5 Ton "OHS"

Evaporator Coil, Alternate Water Source - Aluminum Fin, Copper Tube


Rows/Face Area (ft2)

4 / 2.1 ft2

4 / 2.1 ft2

4 / 2.1 ft2

Evaporator Blower / Motor, Alternate Water Source - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
1/4 Hp

1/3 Hp

1/2 Hp

1/2 Hp

3/4 Hp

1-1/2 Hp

2 Hp

CFM @ ext. st. press.

Horsepower

500 @ 0.5"

750 @ 0.5"

900 @ 0.5"

1,000 @ 0.5"

1,415 @ 0.5"

2,200 @ 0.5"

2,500 @ 0.5"

Drive Method

Belt Driven

Belt Driven

Belt Driven

Belt Driven

Belt Driven

Belt Driven

Belt Driven

1-1/8" OD

1-1/8" OD

Connection Sizes, Alternate Water Source - Copper, (@ 75FDB/62.5FWB EAT flow rate conditions.)
Chilled Water In/Out

5/8" OD

7/8" OD

7/8" OD

Air Technology Systems, Inc.

7/8" OD

7/8" OD

4-26

Alternate Water Source


Performance Data

OHS Model

048D()-AWS

- 4 to 10 Ton "OHS"

072D()-AWS

084D()-AWS

(45F EWT)

120D()-AWS

NET COOLING CAPACITY - BTU/H @ 45F EWT, 0% Glycol Solution (includes motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
High Flow

Total

(8F Tw)

Sensible
GPM / (pd. Ft.)

70,490

134,100

144,440

166,850

49,290

90,760

98,710

117,880

17.6 / (43.1)

33.5 / (46.3)

36.1 / (53.2)

41.8 / (18.6)

Med. Flow

Total

65,830

125,560

135,080

154,030

(10F Tw)

Sensible

47,200

87,010

94,600

112,150

13.2 / (25.1)

25.2 / (27.5)

27.1 / (31.5)

31.0 / (10.7)

61,480

117,370

126,560

139,290

GPM / (pd. Ft.)


Low Flow

Total

(12F Tw)

Sensible
GPM / (pd. Ft.)

45,200

83,420

90,820

105,460

10.4 / (15.8)

19.6 / (17.4)

21.2 / (20.1)

23.4 / (6.4)

51,880

99,080

106,720

121,940

75FDB/62.5FWB, 50% RH
High Flow

Total

(8F Tw)

Sensible
GPM / (pd. Ft.)

42,660

78,510

85,490

101,740

13.0/ (24.6)

24.8 / (26.9)

26.8 / (30.8)

30.8 / (10.6)

- Alternate Water Source (45F EWT)

Med. Flow

Total

48,420

93,260

100,560

109,650

(10F Tw)

Sensible

40,30

75,670

82,420

95,250

9.8 / (14.5)

18.8 / (16.1)

20.3 / (18.5)

22.2 / (5.8)

44,630

87,270

94,830

97,640

GPM / (pd. Ft.)


Low Flow

Total

(12F Tw)

Sensible

38,670

72,610

79,360

88,190

7.6 / (8.9)

14.6 / (10.2)

15.9 / (11.9)

16.6 / (3.4)

43,150

83,050

89,560

99,540

Air Technology Systems, Inc


GPM / (pd. Ft.)

72FDB/60FWB, 50% RH

Total

High Flow
(8F Tw)

Sensible

GPM / (pd. Ft.)

38,670

71,570

77,990

91,150

11.0 / (17.8)

20.9 / (19.6)

22.5 / (22.6)

25.2 / (7.4)

Med. Flow

Total

39,480

78,610

84,870

85,960

(10F Tw)

Sensible

36,380

69,090

75,240

82,660

8.0 / (10.0)

15.8 / (11.9)

17.2 / (13.7)

17.4 / (3.7)

Low Flow

GPM / (pd. Ft.)


Total

35,020

71,630

77,770

67,580

(12F Tw)

Sensible

33,360

64,930

70,840

67,580

6.0 / (5.7)

12.0 / (7.2)

13.1 / (8.4)

11.6 / (1.6)

GPM / (pd. Ft.)

Alternate Water Source Control Valve - Sized for Medium Flow @ 75FDB/62.5FWB EAT Conditions
2-way (standard) - Spring Actuated (Open/Close)
Size / (Cv)

1" / (8.0)

1" / (14.0)

1" / (14.0)

1" / (14.0)

Pressure Rating

300 psig

400 psig

400 psig

400 psig

Total Unit Pressure Drop

19.4 Ft.

20.7 Ft.

24.1 Ft.

12.5 Ft.

3-way (optional) - Spring Actuated (Open/Close)


Size / (Cv)

1" / (7.0)

1" / (14.0)

1" / (14.0)

1" / (14.0)

Valve Pressure Rating

300 psig

400 psig

400 psig

400 psig

Total Unit Pressure Drop

17.0 Ft.

20.7 Ft.

24.1 Ft.

12.5 Ft.

4/ 6.7 ft2

4/ 6.7 ft2

4/ 10.0 ft2

Evaporator Coil, Alternate Water Source - Aluminum Fin, Copper Tube


Rows/Face Area (ft2)

4/ 4.1 ft2

Evaporator Blower / Motor, Alternate Water Source - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Horsepower
CFM @ ext. st. press.
Drive Method

1 Hp

1-1/2 Hp

2 Hp

3 Hp

1,800 @ 0.5"

3,000 @ 0.5"

3,350 @ 0.5"

4,400 @ 0.5"

Belt Driven

Belt Driven

Belt Driven

Belt Driven

Connection Sizes, Alternate Water Source - Copper, (@ 75FDB/62.5FWB EAT flow rate conditions.)
Chilled Water In/Out

4-27

1-1/8" OD

1-1/8" OD

Air Technology Systems, Inc.

1-1/8" OD

1-3/8" OD

Alternate Water Source -

42F/50F EWT

012-AWS

018-AWS

024-AWS

032-AWS

040-AWS

048-AWS

060-AWS

072-AWS

084-AWS

120-AWS

High Flow

Total

26,260

35,660

40,630

46,540

59,330

96,270

104,840

153,410

165,430

191,860

(8F Tw)

Sensible

16,820

23,440

27,080

31,360

40,970

64,660

71,110

99,310

107,930

128,640

GPM/(Ft.)

6.6/(25.0)

8.9/(43.9)

10.1/(55.8)

11.6/(29.8)

14.8/(47.2)

24.0/(24.2)

26.2/(28.4)

38.3/(59.6)

41.3/(68.6)

42.0/(24.2)

Med Flow

Total

24,550

33,500

38,180

43,710

55,750

89,650

97,830

144,620

155,710

178,610

(10F Tw)

Sensible

16,030

22,450

25,960

30,010

39,270

61,650

67,920

95,310

103,520

122,630

GPM/(Ft.)

4.9/(14.8)

6.7/(25.8)

7.6/(32.9)

8.7/(17.6)

11.1/(27.7)

17.9/(14.1)

19.6/(16.6)

28.9/(35.7)

31.2/(41.0)

35.8/(14.1)

Low Flow

Total

22,660

31,170

35,790

40,430

52,300

81,320

59,560

135,610

146,250

161,960

(12F Tw)

Sensible

15,180

21,390

24,860

28,450

37,600

57,910

64,180

91,260

99,260

115,150

GPM/(Ft.)

3.8/(9.1)

5.2/(16.1)

6.0/(20.8)

6.7/(10.9)

8.7/(17.6)

13.6/(8.4)

15.0/(10.1)

22.6/(22.7)

24.5/(26.3)

27.2/(8.4)

012-AWS

018-AWS

024-AWS

032-AWS

040-AWS

048-AWS

060-AWS

072-AWS

084-AWS

120-AWS

75FDB/62.5FWB
Total

19,450

26,760

30,590

35,200

45,190

72,100

79,070

115,660

124,650

143,530

(8F Tw)

Sensible

14,380

20,310

23,570

27,140

35,750

56,180

62,130

86,120

93,710

111,680

GPM/(Ft.)

4.9/(14.5)

6.7/(25.9)

7.6/(33.2)

8.8/(17.9)

11.3/(28.4)

18.1/(14.3)

19.9/(17.1)

28.9/(35.8)

31.2/(41.1)

Total

17,880

24,830

28,560

32,460

42,280

65,300

72,010

108,750

117,090

129,920

Sensible

13,620

19,360

22,540

25,730

24,220

52,790

58,560

82,780

90,030

104,910

GPM/(Ft.)

3.6/(8.2)

5.0/(15.1)

5.7/(19.3)

6.5/(10.2)

8.5/(16.7)

13.1/(7.9)

14.5/(9.6)

21.8/(21.4)

23.5/(24.5)

26.2/(7.9)

Total

16,370

22,860

26,690

29,890

39,060

58,870

65,240

101,470

110,240

117,060

Sensible

12,880

18,360

21,440

24,390

32,470

49,420

54,950

79,230

86,610

98,170

GPM/(Ft.)

2.8/(5.0)

3.8/(9.2)

4.4/(11.9)

5.0/(6.3)

6.5/(10.2)

9.9/(4.7)

11.0/(5.7)

17.0/(13.6)

18.5/(15.8)

19.8/(4.7)

012-AWS

018-AWS

024-AWS

032-AWS

040-AWS

048-AWS

060-AWS

072-AWS

084-AWS

120-AWS

Med Flow
(10F Tw)
Low Flow
(12F Tw)
72FDB/60FWB

36.2/(14.3)

High Flow

Total

16,130

22,430

25,760

29,550

38,380

59,940

65,890

97,760

105,340

119,190

(8F Tw)

Sensible

12,960

18,450

21,470

24,590

32,650

50,840

56,300

78,590

85,540

100,990

GPM/(Ft.)

4.1/(10.4)

5.7/(19.0)

6.4/(24.0)

7.4/(13.0)

9.6/(21.0)

15.1/(10.2)

16.6/(12.3)

24.5/(26.4)

26.4/(30.3)

30.2/(10.2)

Med Flow

Total

14,790

20,650

23,870

27,110

35,430

53,890

59,500

91,990

99,230

107,110

(10F Tw)

Sensible

12,270

17,500

20,430

23,230

30,950

47,500

52,690

75,630

82,350

94,310

GPM/(Ft.)

3.0/(5.9)

4.2/(10.8)

4.8/(14.0)

5.4/(7.4)

7.1/(12.1)

10.8/(5.6)

12.0/(6.8)

18.5/(15.8)

20.0/(18.2)

Low Flow

Total

13,530

18,980

21,970

24,850

32,490

47,370

52,240

84,910

92,170

94,070

(12F Tw)

Sensible

11,590

16,540

19,310

21,920

29,140

43,510

48,160

71,880

78,490

86,340

GPM/(Ft.)

2.3/(3.4)

3.2/(6.6)

3.7/(8.6)

4.2/(4.5)

5.4/(7.3)

8.0/(3.2)

8.8/(3.8)

14.2/(9.9)

15.5/(11.4)

16.0/(3.2)

21.6/(5.6)

Cooling Capacities (BTU/H) for 50F Chilled Water Entering the Cooling Coil
80FDB/67FWB

012-AWS

018-AWS

024-AWS

032-AWS

040-AWS

048-AWS

060-AWS

072-AWS

084-AWS

120-AWS

High Flow

Total

17,340

23,720

27,070

31,550

40,300

64,160

69,840

102,640

110,880

127,640

(8F Tw)

Sensible

12,970

18,360

21,350

24,670

32,580

51,150

56,420

77,640

84,770

101,610

GPM/(Ft.)

4.4/(11.6)

6.0/(20.6)

6.8/(26.0)

7.9/(14.5)

10.1/(22.7)

16.1/(11.4)

17.6/(13.4)

25.7/(28.3)

27.9/(32.7)

32.2/(11.4)

Med Flow

Total

15,870

22,110

25,390

29,130

36,840

58,670

64,760

96,430

103,990

116,670

(10F Tw)

Sensible

12,330

17,620

20,530

23,520

31,310

48,530

53,880

74,920

81,700

96,380

GPM/(Ft.)

3.2/(6.5)

4.5/(12.0)

5.1/(15.3)

5.8/(8.2)

7.6/(13.4)

11.8/(6.4)

13.1/(7.8)

19.4/(16.9)

21.0/(19.5)

23.6/(6.4)

Low Flow

Total

14,570

20,410

23,660

26,770

35,130

52,860

58,460

91,030

97,870

105,040

(12F Tw)

Sensible

11,730

16,780

19,640

22,320

29,840

45,480

50,480

72,410

78,760

90,280

GPM/(Ft.)

2.5/(4.0)

3.4/(7.4)

4.0/(9.7)

4.5/(5.1)

5.9/(8.3)

8.9/(3.8)

9.9/(4.6)

15.3/(10.9)

16.4/(12.5)

17.8/(3.8)

012-AWS

018-AWS

024-AWS

032-AWS

040-AWS

048-AWS

060-AWS

072-AWS

084-AWS

120-AWS

75FDB/62.5FWB
High Flow

Total

12,100

16,730

19,200

22,380

28,770

43,580

45,430

75,480

80,860

86,480

(8F Tw)

Sensible

10,990

15,610

18,170

20,880

27,580

42,410

45,430

67,760

73,570

84,150

GPM/(Ft.)

3.1/(6.1)

4.2/(10.9)

4.8/(14.0)

5.7/(7.8)

7.2/(12.3)

11.0/(5.6)

11.5/(6.1)

19.0/(16.3)

20.4/(18.6)

Med Flow

Total

10,900

14,880

16,960

19,860

23,400

36,050

39,970

71,720

76,250

71,430

(10F Tw)

Sensible

10,270

14,430

16,690

19,290

23,400

36,050

39,970

65,350

70,550

71,430

GPM/(Ft.)

2.2/(3.3)

3.0/(5.8)

3.4/(7.4)

4.0/(4.2)

4.8/(5.7)

7.3/(2.7)

8.2/(3.3)

14.4/(9.9)

15.4/(11.2)

22.0/(5.6)

14.6/(2.7)

Low Flow

Total

8,710

12,380

14,420

15,370

20,380

30,000

33,350

54,330

59,290

59,330

(12F Tw)

Sensible

8,710

12,380

14,420

15,370

20,380

30,000

33,350

54,330

59,290

59,330

GPM/(Ft.)

1.5/(1.3)

2.1/(2.9)

2.4/(3.9)

2.6/(1.7)

3.5/(3.1)

5.1/(1.2)

5.7/(1.6)

9.2/(4.4)

10.0/(5.1)

10.2/(1.2)

012-AWS

018-AWS

024-AWS

032-AWS

040-AWS

048-AWS

060-AWS

072-AWS

084-AWS

120-AWS

72FDB/60FWB
High Flow

Total

8,950

12,720

14,820

16,220

21,520

33,560

37,150

55,560

60,470

66,440

(8F Tw)

Sensible

8,950

12,720

14,820

16,220

21,520

33,560

37,150

55,560

60,470

66,440

GPM/(Ft.)

2.3/(3.5)

3.2/(6.6)

3.7/(8.7)

4.1/(4.3)

5.5/(7.3)

8.5/(3.5)

9.5/(4.3)

14.1/(9.5)

15.4/(11.1)

17.0/(3.5)

Med Flow

Total

7,930

11,260

13,120

14,070

18,640

27,890

30,910

49,330

53,790

55,100

(10F Tw)

Sensible

7,930

11,260

13,120

14,070

18,640

27,890

30,910

49,330

53,790

55,100

GPM/(Ft.)

1.6/(1.6)

2.3/(3.5)

2.7/(4.6)

2.9/(2.1)

3.8/(3.7)

5.7/(1.6)

6.4/(2.0)

10.0/(5.1)

11.0/(6.0)

- Alternate Water Source @ 42F / 50F EWT

High Flow

Performance Data

Cooling Capacities (BTU/H) for 42F Chilled Water Entering the Cooling Coil
80FDB/67FWB

11.4/(1.6)

Low Flow

Total

6,690

9,550

11,140

11,500

15,340

20,870

23,350

41,390

45,320

41,060

(12F Tw)

Sensible

6,690

9,550

11,140

11,500

15,340

20,870

23,350

41,390

45,320

41,060

GPM/(Ft.)

1.1/(0.7)

1.6/(1.6)

1.9/(2.3)

2.0/(0.8)

2.6/(1.7)

3.6/(0.5)

4.1/(0.7)

7.0/(2.7)

7.7/(3.2)

7.2/(0.5)

(Note: The above Net Cooling capacities include standard motor heat @ standard CFM/e.s.p. as shown on page 4-24 & 4-25, Evaporator Blower/Motor.)

Air Technology Systems, Inc.

4-28

Electrical Data - Index


Electrical Data

CeilAiR Ceiling AC's


FLA / MCA / MFS
INDEX
MODEL TYPE ...........................................page

DX - Compressorized Systems

Free-Cooling & Alternate Water Source

- Index

Single Compressor Systems:

Single Circuit Systems:

OHS-012 thru 040-AS........................................................ 5-2

OHS-012 thru 040-HAR, HW, HG-FC/AWS......................... 5-7


OHS-048 thru 060-AR, W, G-FC/AWS................................. 5-7

OHS-012 thru 024-AR, W & G............................................ 5-2


OHS-032 thru 060-AR, W & G............................................ 5-3
Dual Compressor Systems:

Dual Circuit Systems:


OHS-048 thru 120-DAR, DW, DG-FC/AWS......................... 5-8

OHS-048 thru 120-DAR, DW & DG.................................... 5-4

Air Technology Systems, Inc


DX - Air Handling Units

Chilled Water Systems

Single Circuit Systems:

OHS-012 thru 120-C.......................................................... 5-9

OHS-012 thru 060-AHU..................................................... 5-5


Dual Circuit Systems:
OHS-048 thru 120-DAHU................................................... 5-6

<< Electrical Data Notes >>


1) Electrical Data is based on standard performance and component selection per Section 4 of this brochure.

Please consult your local Sales Representative for "special" equipment electrical data.

2) High Static Pressure Belt-Drive Option - Electrical Data in the pages to follow are based on Standard CFM's

and External Static Pressures. Please Consult your local Sales Representative for component and electrical rating data

for this Option.

5-1

Air Technology Systems, Inc.

Electrical Data
OHS-012-AS
FLA

MCA

MFS

OHS-018-AS
FLA

MCA

OHS-024-AS

MFS

FLA

MCA

OHS-032-AS

MFS

OHS-040-AS

FLA

MCA

MFS

FLA

MCA

MFS

OHS-048-AS

OHS-060-AS

FLA

FLA

MCA

MFS

MCA

COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60

11.7

14.4

20

13.2

17.6

25

15.4

23.0

30

19.2

27.2

35

20.0

29.5

40

N/A

N/A

277/1/60

9.8

12.2

15

11.0

14.7

20

13.7

20.2

25

16.5

24.0

30

18.0

25.2

35

N/A

N/A

208/3/60

N/A

N/A

12.5

16.8

25

15.0

20.1

30

15.8

21.4

30

N/A

N/A

460/3/60

N/A

N/A

7.4

9.5

15

8.3

10.9

15

9.9

12.6

15

N/A

N/A

COOLING and ELECTRIC REHEAT/HEAT, with or without Humidifier


208/1/60

34.4

42.8

45

35.9

46.0

50

38.1

51.4

60

41.9

55.6

60

42.7

57.9

70

N/A

N/A

277/1/60

27.8

34.8

35

29.9

38.3

40

31.8

42.7

45

34.5

46.5

50

36.1

47.7

50

N/A

N/A

208/3/60

N/A

N/A

25.6

33.2

35

28.1

36.5

40

28.9

37.8

45

N/A

N/A

460/3/60

N/A

N/A

13.6

17.3

20

14.5

18.7

20

16.1

20.5

25

N/A

N/A

COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60

19.9

22.6

25

21.4

25.8

35

23.6

31.2

45

27.4

35.4

50

28.2

37.7

50

N/A

N/A

277/1/60

16.0

18.4

20

17.9

21.5

25

19.9

26.4

35

22.7

30.2

40

24.2

31.4

45

N/A

N/A

208/3/60

N/A

N/A

20.7

25.0

30

23.2

28.3

35

24.0

29.6

40

N/A

N/A

460/3/60

N/A

N/A

11.1

13.2

15

12.0

14.6

20

13.6

16.3

20

N/A

N/A

208/1/60

25.4

31.8

35

25.4

31.8

35

25.4

31.8

35

26.1

32.7

35

26.5

33.2

35

N/A

N/A

277/1/60

20.6

25.7

30

21.2

26.5

30

20.6

25.7

30

20.8

25.9

30

22.0

27.4

30

N/A

N/A

208/3/60

N/A

N/A

15.8

19.8

20

16.5

20.7

20

16.9

21.4

25

N/A

N/A

460/3/60

N/A

N/A

7.9

9.8

15

8.3

10.9

15

9.9

12.6

15

N/A

N/A

Model

FLA (OEM Rated)

OHS-012-AR, W, & G
AR

MCA

OHS-018-AR, W, & G
MFS

FLA (OEM Rated)


AR

OHS-024-AR, W, & G

MCA

MFS

FLA (OEM Rated)


AR

MCA

MFS

COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60

8.8

8.0

9.0

11.5

15

9.9

8.3

10.4

14.3

20

12.1

10.1

12.7

19.7

30

277/1/60

7.6

6.9

7.7

10.0

15

8.3

7.0

8.7

12.0

15

10.3

8.6

10.8

16.8

25

208/3/60

N/A

N/A

9.3

8.2

9.6

13.5

20

460/3/60

N/A

N/A

4.9

4.4

5.1

7.0

15

COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier)


208/1/60

31.5

30.7

31.7

39.9

40

32.6

31.0

33.1

42.7

45

34.8

32.8

35.4

48.1

50

277/1/60

25.6

24.9

25.8

32.6

35

27.2

25.8

27.6

35.6

40

28.4

26.7

28.9

39.3

45

208/3/60

N/A

N/A

22.4

21.3

22.7

29.9

35

460/3/60

N/A

N/A

11.2

10.6

11.3

14.8

15

COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60

17.0

16.2

17.2

19.7

25

18.1

16.5

18.6

22.5

30

20.3

18.3

20.9

27.9

277/1/60

13.8

13.1

13.9

16.2

20

15.1

13.8

15.5

18.8

25

16.5

14.8

17.0

23.0

40
30

208/3/60

N/A

N/A

17.5

16.4

17.8

21.7

30

460/3/60

N/A

N/A

8.6

8.1

8.8

10.7

15

- DX Compressorized Systems

COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier)

MFS

Electrical Data

Model

- DX Compressorized Systems

COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier)


208/1/60

25.4

25.4

25.4

31.8

35

25.4

25.4

25.4

31.8

35

25.4

25.4

25.4

31.8

35

277/1/60

20.6

20.6

20.6

25.7

30

21.2

21.2

21.2

26.5

30

20.6

20.6

20.6

25.7

30

208/3/60

N/A

N/A

15.8

15.8

15.8

19.8

20

460/3/60

N/A

N/A

7.9

7.9

7.9

9.8

15

34.8

33.6

35.4

48.1

50

COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER


208/1/60

33.6

33.6

33.6

42.0

45

33.6

33.6

33.6

42.7

45

277/1/60

26.8

26.8

26.8

33.4

35

28.0

28.0

28.0

35.6

40

28.4

26.8

28.9

39.3

45

208/3/60

N/A

N/A

24.0

24.0

24.0

30.0

35

460/3/60

N/A

N/A

11.6

11.6

11.6

14.8

15

Air Technology Systems, Inc.

(*) Current Draws are given


in the following order:

FLA

MCA

MFS

FLA = Full Load Amps


MCA = Minimum Circuit Amps

(wire size amps)
MFS = Maximum Fuse Size

5-2

Electrical Data
Electrical Data

Model

- DX Compressorized Systems

OHS-032-AR, W, & G
FLA (OEM Rated)
AR

MCA

OHS-040-AR, W, & G
MFS

FLA (OEM Rated)


AR

OHS-048-AR, W, & G

MCA

MFS

FLA (OEM Rated)


AR

MCA

OHS-060-AR, W, & G
MFS

FLA (OEM Rated)


AR

MCA

MFS

COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60

15.9

13.4

16.6

23.9

35

16.7

14.1

17.5

26.2

40

N/A

277/1/60

13.1

11.0

13.7

20.6

30

14.6

12.4

15.3

21.8

30

N/A

N/A

208/3/60

11.7

10.5

12.1

16.8

25

12.5

11.3

12.9

18.1

25

17.1

15.0

17.8

24.4

45

19.9

17.5

20.7

31.2

45

460/3/60

5.8

5.2

6.0

8.4

15

7.4

6.8

7.6

10.1

15

8.7

7.4

9.1

12.5

15

10.2

9.0

10.6

15.4

25

N/A

COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier)


208/1/60

38.6

36.1

39.3

52.3

60

39.4

36.8

40.2

54.6

60

N/A

277/1/60

31.1

29.1

31.7

43.1

50

32.7

30.5

33.3

44.3

50

N/A

N/A

208/3/60

24.8

23.6

25.2

33.2

40

25.6

24.4

26.0

34.5

40

43.3

41.2

44.0

57.2

70

46.1

43.7

46.9

64.0

70

460/3/60

12.0

11.4

12.2

16.2

20

13.6

13.0

13.8

18.0

20

21.3

20.0

21.7

28.1

30

22.8

21.6

23.2

31.1

35

N/A

COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60

24.1

21.6

24.8

32.1

45

24.9

22.3

25.7

34.4

50

N/A

277/1/60

19.3

17.2

19.9

26.8

40

20.8

18.6

21.5

28.0

40

N/A

N/A

208/3/60

19.9

18.7

20.3

25.0

35

20.7

19.5

21.1

26.3

35

33.5

31.4

34.2

40.8

60

36.3

33.9

37.1

47.6

60

460/3/60

9.5

8.9

9.7

12.1

15

11.1

10.5

11.3

13.8

15

16.1

14.8

16.5

19.9

25

17.6

16.4

18.0

22.8

30

N/A

- DX Compressorized Systems

COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier)


208/1/60

26.1

26.1

26.1

32.7

35

26.5

26.5

26.5

33.2

35

N/A

277/1/60

20.8

20.8

20.8

25.9

30

22.0

22.0

22.0

27.4

30

N/A

N/A

208/3/60

16.5

16.5

16.5

20.7

25

16.9

16.9

16.9

21.2

25

30.1

30.1

30.1

37.7

40

31.5

31.5

31.5

39.4

40

460/3/60

7.9

7.9

7.9

9.8

15

9.3

9.3

9.3

11.6

15

14.8

14.8

14.8

18.4

20

15.5

15.5

15.5

19.3

20

N/A

COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER


208/1/60

38.6

36.1

39.3

52.3

60

39.4

36.8

40.2

54.6

60

N/A

277/1/60

31.1

29.1

31.7

43.1

50

32.7

30.5

33.3

44.3

50

N/A

N/A

208/3/60

24.8

24.7

25.2

33.2

40

25.6

25.1

26.0

34.5

40

46.5

46.5

46.5

58.2

70

47.9

47.9

47.9

64.0

70

460/3/60

12.0

11.6

12.2

16.2

20

13.6

13.0

13.8

18.0

20

22.2

22.2

22.2

28.1

30

22.9

22.9

23.2

31.1

35

Air Technology Systems, Inc

5-3

Air Technology Systems, Inc.

N/A

Electrical Data

- DUAL DX

FLA (OEM rated)


DAR

DW

DG

MCA

OHS-072-DAR, DW, & DG


MFS

FLA (OEM rated)


DAR

DW

DG

MCA

OHS-084-DAR, DW, & DG


MFS

FLA (OEM rated)


DAR

DW

DG

MCA

OHS-120-DAR, DW, & DG


MFS

FLA (OEM rated)


DAR

DW

DG

MCA

MFS

Electrical Data

OHS-048-DAR, DW, & DG


Model

COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A
N/A

208/3/60

16.7

14.5

17.3

22.9

30

22.7

20.3

23.5

31.0

40

29.3

25.7

30.5

40.7

50

37.9

33.1

39.5

55.3

70

460/3/60

8.6

7.5

8.9

11.7

15

11.6

10.4

12.0

15.7

20

14.9

13.1

15.5

20.6

30

19.2

16.8

20.0

27.1

35

COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier)


208/1/60

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A
N/A

208/3/60

36.3

35.2

36.6

47.1

50

40.2

39.0

40.6

52.4

60

44.3

42.5

44.9

58.5

70

49.5

47.1

50.3

67.4

80

460/3/60

17.9

17.3

18.0

23.1

25

19.8

19.2

20.0

25.7

30

21.9

21.0

22.2

28.8

35

24.5

23.3

24.9

32.8

40

COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A
N/A

208/3/60

33.1

30.9

33.7

39.3

45

36.9

34.5

37.7

45.2

50

43.5

39.9

44.7

54.9

60

52.1

47.3

53.7

69.5

80

460/3/60

16.0

14.9

16.3

19.1

20

18.0

16.8

18.4

22.1

25

21.3

19.5

21.9

27.0

35

25.6

23.2

26.4

33.5

40

208/1/60

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A
N/A

208/3/60

29.7

29.7

29.7

37.2

40

31.5

31.5

31.5

39.4

45

33.1

33.1

33.1

41.4

45

37.9

34.9

39.5

55.3

70

460/3/60

14.6

14.6

14.6

18.2

20

15.5

15.5

15.5

19.3

25

16.3

16.3

16.3

20.6

25

19.2

17.2

20.0

27.1

35

COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER


208/1/60

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A
N/A

208/3/60

46.1

46.1

46.1

57.7

60

45.7

45.7

45.7

57.2

60

47.3

47.3

47.3

59.2

70

52.1

49.1

53.7

69.5

80

460/3/60

22.0

22.0

22.0

27.4

30

21.9

21.9

21.9

27.3

30

22.7

22.7

22.7

26.7

35

25.6

23.6

26.4

33.5

40

Dual Compressor Systems with C-Tech-10 Microprocessor (see Note-1)


OHS-048-DAR, DW, & DG
Model

FLA (OEM rated)


DAR

DW

DG

MCA

OHS-072-DAR, DW, & DG


MFS

FLA (OEM rated)


DAR

DW

DG

MCA

OHS-084-DAR, DW, & DG


MFS

FLA (OEM rated)


DAR

DW

DG

MCA

OHS-120-DAR, DW, & DG


MFS

FLA (OEM rated)


DAR

DW

DG

MCA

MFS

COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier)


208/1/60

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A
N/A

208/3/60

42.9

40.7

43.5

55.7

60

48.9

46.5

49.7

63.8

70

55.5

51.9

56.7

73.5

80

64.1

59.3

65.7

88.1

100

460/3/60

21.2

20.1

21.5

27.4

30

24.2

23.0

24.6

31.4

35

27.5

25.7

28.1

36.3

40

31.8

29.4

32.6

42.8

45

COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER


208/1/60

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A
N/A

208/3/60

46.1

46.1

46.1

57.7

60

48.9

46.5

49.7

63.8

70

55.5

51.9

56.7

73.5

80

64.1

59.3

65.7

88.1

100

460/3/60

22.0

22.0

22.0

27.4

30

24.2

23.0

24.6

31.4

35

27.5

25.7

28.1

36.3

40

31.8

29.4

32.6

42.8

45

Note-1: Dual compressor systems incorporating C-Tech-10 controls provide 2(two) compressor stages of Cooling and 2(two) compressor stages of
Dehumidification. The A-Tech-1.2 and A-Tech-20 controls provide 2(two)
compressor stages of Cooling and 1(one) compressor stage of Dehumidification. Therefore, electrical data for dual compressor systems with
dehumidification mode (reheat) is controller dependent as shown above.

Air Technology Systems, Inc.

(*) Current Draws are given


in the following order:

FLA

MCA

- Dual DX & Remote Air Cooled Condensers

COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier)

MFS

FLA = Full Load Amps


MCA = Minimum Circuit Amps

(wire size amps)
MFS = Maximum Fuse Size

5-4

Electrical Data
Electrical Data

Model

OHS-012-AHU
FLA

MCA

- Air Cooled "AHU / RCU"


OHS-018-AHU

MFS

FLA

MCA

OHS-024-AHU
MFS

OHS-032-AHU

FLA

MCA

MFS

FLA

MCA

MFS

COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60

2.7

3.4

15

2.7

3.4

15

2.7

3.4

15

3.4

4.3

15

277/1/60

2.5

3.1

15

2.5

3.1

15

2.5

3.1

15

2.7

3.4

15

208/3/60

2.7

3.4

15

2.7

3.4

15

2.7

3.4

15

3.4

4.3

15

460/3/60

1.6

2.0

15

1.6

2.0

15

1.6

2.0

15

1.6

2.0

15

COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier)


208/1/60

25.4

31.8

35

25.4

31.8

35

25.4

31.8

35

26.1

32.7

35

277/1/60

20.6

25.7

30

20.6

25.7

30

20.6

25.7

30

20.8

25.9

30

208/3/60

15.8

19.8

20

15.8

19.8

20

15.8

19.8

20

16.5

20.7

25

460/3/60

7.9

9.8

15

7.9

9.8

15

7.9

9.8

15

7.9

9.8

15

COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60

10.9

13.6

15

10.9

13.6

15

10.9

13.6

15

11.6

14.5

15

277/1/60

8.7

10.9

15

8.7

10.9

15

8.7

10.9

15

8.9

11.1

15

208/3/60

10.9

13.6

15

10.9

13.6

15

10.9

13.6

15

11.6

14.5

15

460/3/60

5.3

6.6

15

5.3

6.6

15

5.3

6.6

15

5.3

6.6

15

COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier)

- Air Cooled ("AHU / RCU")

208/1/60

25.4

31.8

35

25.4

31.8

35

25.4

31.8

35

26.1

32.7

35

277/1/60

20.6

35.7

30

20.6

25.7

30

20.6

25.7

30

20.8

25.9

30

208/3/60

15.8

19.8

20

15.8

19.8

20

15.8

19.8

20

16.5

20.7

25

460/3/60

7.9

9.8

15

7.9

9.8

15

7.9

9.8

15

7.9

9.8

15

COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER


208/1/60

33.6

42.0

45

33.6

42.0

45

33.6

42.0

45

34.3

42.9

45

277/1/60

26.8

33.4

35

26.8

33.4

35

26.8

33.4

35

27.7

33.7

35

208/3/60

24.0

30.0

30

24.0

30.0

30

24.0

30.0

30

24.7

30.9

35

460/3/60

11.6

14.5

15

11.6

14.5

15

11.6

14.5

15

11.6

14.5

15

Air Technology Systems, Inc


Model

OHS-040-AHU

FLA

MCA

OHS-048-AHU

MFS

FLA

MCA

OHS-060-AHU

MFS

FLA

MCA

MFS

COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60

3.8

4.8

15

N/A

277/1/60

3.9

4.9

15

N/A

N/A

208/3/60

3.8

4.8

15

3.9

4.9

15

5.3

6.6

15

460/3/60

3.0

3.8

15

2.2

2.8

15

2.9

3.6

15

N/A

COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier)


208/1/60

26.5

33.2

35

N/A

N/A

277/1/60

22.0

27.4

30

N/A

N/A

208/3/60

16.9

21.2

25

30.1

37.7

40

31.5

39.4

40

460/3/60

9.3

11.6

15

14.8

18.4

20

15.5

19.3

20

COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60

12.0

15.0

20

N/A

N/A

277/1/60

10.1

12.6

15

N/A

N/A

208/3/60

12.0

15.0

20

20.3

25.4

30

21.7

27.1

30

460/3/60

6.7

8.4

15

9.6

12.0

15

10.3

12.9

15

(*) Current Draws are given


in the following order:

COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier)


N/A

26.5

33.2

35

N/A

277/1/60

22.0

27.4

30

208/3/60

16.9

21.2

25

30.1

37.7

40

31.5

39.4

40

460/3/60

9.3

11.6

15

14.8

18.4

20

15.5

19.3

20

N/A

COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER

5-5

208/1/60

34.7

43.4

45

N/A

277/1/60

28.2

35.2

40

N/A

N/A

208/3/60

25.1

31.4

35

46.5

58.2

60

47.9

59.9

60

460/3/60

13.0

16.2

20

22.2

27.7

30

22.9

28.6

30

N/A

Air Technology Systems, Inc.

MCA

MFS

FLA = Full Load Amps


MCA = Minimum Circuit Amps

(wire size amps)
MFS = Maximum Fuse Size

208/1/60

N/A

FLA

Electrical Data
OHS-048-DAHU
FLA

MCA

OHS-072-DAHU

MFS

FLA

MCA

OHS-084-DAHU

MFS

FLA

MCA

OHS-120-DAHU

MFS

FLA

MCA

Electrical Data

Model

- Air Cooled "DAHU / DRCU


MFS

COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60

N/A

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A

208/3/60

3.5

4.4

15

5.3

6.6

15

6.9

8.6

15

8.7

10.9

15

460/3/60

2.0

2.5

15

2.9

3.6

15

3.7

4.6

15

4.6

5.8

15

COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier)


208/1/60

N/A

277/1/60

N/A

N/A

N/A

N/A

N/A

N/A

N/A

208/3/60

29.7

37.2

40

31.5

39.4

45

33.1

41.4

45

34.9

43.7

45

460/3/60

14.6

18.2

20

15.5

19.3

25

16.3

20.3

25

17.2

21.4

25

COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60

N/A

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A

19.9

24.9

25

19.5

24.4

30

21.1

26.4

30

22.9

28.6

30

460/3/60

9.4

11.8

15

9.3

11.6

15

10.1

12.6

15

11.0

13.8

15

- Air Cooled ("DAHU / DRCU")

208/3/60

COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier)


208/1/60

N/A

277/1/60

N/A

N/A

N/A

N/A

N/A

N/A

N/A

208/3/60

29.7

37.2

40

31.5

39.4

45

33.1

41.4

45

34.9

43.7

45

460/3/60

14.6

18.2

20

15.5

19.3

25

16.3

20.3

25

17.2

21.4

25

COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER


208/1/60

N/A

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A

208/3/60

46.1

57.7

60

45.7

57.2

60

47.3

59.2

60

49.1

61.4

70

460/3/60

22.0

27.4

30

21.9

27.3

30

22.7

28.3

30

23.6

29.4

30

(*) Current Draws are given


in the following order:

FLA

MCA

MFS

FLA = Full Load Amps


MCA = Minimum Circuit Amps

(wire size amps)
MFS = Maximum Fuse Size

Air Technology Systems, Inc.

5-6

Electrical Data

- Free-Cooling & Alternate Water Source

Electrical Data

OHS-012-HAR, HW, & HG AWS or FC

Model

FLA (OEM rated)


HAR

HW

HG

MCA

OHS-018-HAR, HW, & HG AWS or FC


MFS

FLA (OEM rated)


HAR

HW

HG

9.1

11.2

OHS-024-HAR, HW, & HG AWS or FC

MCA

MFS

15.1

20

FLA (OEM rated)


HAR

HW

HG

14.1

12.1

14.7

MCA

MFS

21.7

30

COOLING ONLY, with or without Hot Water or Steam Reheat


208/1/60

9.1

8.3

9.3

11.8

15

10.7

277/1/60

N/A

N/A

N/A

208/3/60

N/A

N/A

8.7

7.6

9.0

12.9

20

460/3/60

N/A

N/A

4.6

4.1

4.8

6.7

15

36.8

34.8

37.4

50.1

60

COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier)


208/1/60

31.8

31.0

32.0

40.2

45

33.4

31.8

33.9

43.5

45

277/1/60

N/A

N/A

N/A

208/3/60

N/A

N/A

21.8

20.7

22.1

29.3

30

460/3/60

N/A

N/A

10.9

10.3

11.0

14.5

15

COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60

17.3

16.5

17.5

20.0

25

18.9

17.3

19.4

23.3

30

22.3

20.3

- Free-Cooling & Alternate Water Source

277/1/60

N/A

N/A

208/3/60

N/A

N/A

16.9

15.8

460/3/60

N/A

N/A

8.3

7.8

27.4

27.4

22.9

29.9

40

17.2

21.1

25

8.5

10.4

15

27.4

34.3

35

N/A

COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier)


208/1/60

25.7

25.7

25.7

32.2

35

26.2

26.2

26.2

32.8

35

277/1/60

N/A

N/A

N/A

208/3/60

N/A

N/A

15.2

15.2

15.2

19

20

460/3/60

N/A

N/A

7.6

7.6

7.6

9.5

15

(*) Current Draws are given


in the following order:

COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER

FLA

MCA

MFS

Air Technology Systems, Inc


208/1/60

33.9

33.9

33.9

42.4

45

34.4

34.4

34.4

43.5

45

36.8

35.6

277/1/60

N/A

N/A

208/3/60

N/A

N/A

23.4

23.4

460/3/60

N/A

N/A

11.3

11.3

Model

OHS-032-HAR, HW, & HG AWS or FC

FLA (OEM rated)


HAR

HW

HG

MCA

FLA (OEM rated)


HAR

HW

HG

50.1

60

23.4

29.3

30

11.3

14.5

15

N/A

OHS-040-HAR, HW, & HG AWS or FC

MFS

37.4

FLA = Full Load Amps


MCA = Minimum Circuit Amps

(wire size amps)
MFS = Maximum Fuse Size

OHS-048-AR, W, & G AWS or FC

MCA

MFS

28.0

45

FLA (OEM rated)


AR

MCA

OHS-060 AR, W, & G AWS or FC

MFS

FLA (OEM rated)


AR

MCA

MFS

COOLING ONLY, with or without Hot Water or Steam Reheat


208/1/60

17.2

14.7

277/1/60

17.9

25.2

40

18.5

15.9

N/A

19.3

N/A

N/A

N/A

N/A

N/A

208/3/60

10.4

9.2

10.8

15.5

25

12.2

11.0

12.6

17.8

25

18.5

16.4

19.2

25.8

40

21.5

19.1

22.3

32.8

50

460/3/60

5.5

4.9

5.7

8.1

15

6.4

5.8

6.6

9.1

15

9.4

8.1

9.8

13.5

20

11.0

9.8

11.4

16.2

25

42.0

56.4

60

COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier)


208/1/60

39.9

37.4

277/1/60

40.6

53.6

60

41.2

38.6

N/A

N/A

N/A

N/A

N/A

N/A

208/3/60

23.5

22.3

23.9

31.9

35

25.3

24.1

25.7

34.2

40

44.7

42.6

45.4

58.6

60

47.7

45.3

48.5

65.6

70

460/3/60

11.7

11.1

11.9

15.9

20

12.6

12.0

12.8

17.0

20

22.0

20.7

22.4

28.8

30

23.6

22.4

24.0

31.9

35

COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60

25.4

22.9

277/1/60

26.1

33.4

45

26.7

24.1

N/A

27.5

36.2

50

N/A

N/A

N/A

N/A

N/A

208/3/60

18.6

17.4

19.0

23.7

30

20.4

19.2

20.8

26.0

35

34.9

32.8

35.6

42.2

50

37.9

35.5

38.7

49.2

60

460/3/60

9.2

8.6

9.4

11.8

15

10.1

9.5

10.3

12.8

15

16.8

15.5

17.2

20.6

25

18.4

17.2

18.8

23.6

30

35.4

45

COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier)


208/1/60

27.4

27.4

277/1/60

27.4

34.3

40

28.3

28.3

N/A

28.3

N/A

N/A

N/A

N/A

N/A

208/3/60

15.2

15.2

15.2

19.0

25

16.6

16.6

16.6

20.8

25

31.5

31.5

31.5

39.4

40

33.1

33.1

33.1

41.4

50

460/3/60

7.6

7.6

7.6

9.5

15

8.3

8.3

8.3

10.3

15

15.5

15.5

15.5

19.3

20

16.3

16.3

16.3

20.3

25

38.6

42.0

56.4

60

COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER


208/1/60

39.9

37.4

277/1/60

5-7

40.6

53.6

60

41.2

N/A

N/A

N/A

N/A

N/A

N/A

208/3/60

23.5

23.4

23.9

31.9

35

25.3

24.8

25.7

34.2

40

47.9

47.9

47.9

59.9

60

49.5

49.5

49.5

65.6

70

460/3/60

11.7

11.3

11.9

15.9

20

12.6

12.0

12.8

17.0

20

22.9

22.9

22.9

28.8

30

23.7

23.7

24.0

31.9

35

Air Technology Systems, Inc.

Electrical Data
OHS-048-DAR, DW, & DG AWS or FC
FLA (OEM rated)
DAR

DW

DG

MCA

OHS-072-DAR, DW, & DG AWS or FC


MFS

FLA (OEM rated)


DAR

DW

DG

MCA

OHS-084-DAR, DW, & DG AWS or FC


MFS

FLA (OEM rated)


DAR

DW

DG

MCA

OHS-120-DAR, DW, & DG AWS or FC


MFS

FLA (OEM rated)


DAR

DW

DG

MCA

MFS

COOLING ONLY, with or without Hot Water or Steam Reheat


208/1/60

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A
N/A

208/3/60

17.1

14.9

17.7

23.3

30

22.7

20.3

23.5

31.0

40

29.3

25.7

30.5

40.7

50

37.9

33.1

39.5

55.3

70

460/3/60

8.8

7.7

9.1

11.9

15

11.6

10.4

12.0

15.7

20

14.9

13.1

15.5

20.6

25

19.2

16.8

20.0

27.1

35

COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier)


208/1/60

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A
N/A

208/3/60

36.7

35.6

37.0

47.5

50

40.2

39.0

40.6

52.4

60

44.3

42.5

44.9

58.5

60

49.5

47.1

50.3

67.4

80

460/3/60

18.1

17.5

18.2

23.3

25

19.8

19.2

20.0

25.7

30

21.9

21.0

22.2

28.8

30

24.5

23.3

24.9

32.8

35

COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A
N/A

208/3/60

33.5

31.3

34.1

39.7

40

36.9

34.5

37.7

45.2

50

43.5

39.9

44.7

54.9

60

52.1

47.3

53.7

69.5

90

460/3/60

16.2

15.1

16.5

19.3

20

18.0

16.8

18.4

22.1

25

21.3

19.5

21.9

27.0

30

25.6

23.2

26.4

33.5

40

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A
N/A

208/3/60

30.1

30.1

34.4

37.7

40

31.5

31.5

42.4

39.4

40

33.1

33.1

33.1

41.4

50

37.9

34.9

39.5

55.3

70

460/3/60

14.8

14.8

16.9

18.4

20

15.5

15.5

21.4

19.3

20

16.3

16.3

16.3

20.6

25

19.2

17.2

20.0

27.1

35

COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER


208/1/60

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A
N/A

208/3/60

46.5

46.5

46.5

58.2

60

45.7

45.7

57.2

57.2

60

47.3

47.3

47.3

59.2

60

52.1

49.1

53.7

69.5

90

460/3/60

22.2

22.2

22.2

27.7

30

21.9

21.9

28.3

27.3

30

22.7

22.7

22.7

28.8

30

25.6

23.6

26.4

33.5

40

Dual Compressor Systems with C-Tech-10 Microprocessor (see Note-1)


Model

OHS-048-DAR, DW, & DG AWS or FC


FLA (OEM rated)
DAR

DW

DG

MCA

OHS-072-DAR, DW, & DG AWS or FC


MFS

FLA (OEM rated)


DAR

DW

DG

MCA

OHS-084-DAR, DW, & DG AWS or FC


MFS

FLA (OEM rated)


DAR

DW

DG

MCA

OHS-120-DAR, DW, & DG -AWS or FC

MFS

FLA (OEM rated)


DAR

DW

DG

MCA

MFS

COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier)


208/1/60

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A
N/A

208/3/60

43.3

41.1

43.9

56.1

60

48.9

46.5

49.7

63.8

70

55.5

51.9

56.7

73.5

80

64.1

59.3

65.7

88.1

100

460/3/60

21.4

20.3

21.7

27.6

30

24.2

23.0

24.6

31.4

35

27.5

25.7

28.1

36.3

40

31.8

29.4

32.6

42.8

45

COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER


208/1/60

N/A

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A

208/3/60

46.5

46.5

46.5

58.2

60

48.9

46.5

68.6

63.8

70

55.5

51.9

56.7

73.5

80

64.1

59.3

65.7

88.1

100

460/3/60

22.2

22.2

22.2

27.7

30

24.2

23.0

34.0

31.4

35

27.5

25.7

58.1

36.3

40

31.8

29.4

32.6

42.8

45

Note-1: Dual compressor systems incorporating C-Tech-10 controls provide 2(two) compressor stages of Cooling and 2(two) compressor stages of
Dehumidification. The A-Tech-1.2 and A-Tech-20 controls provide 2(two)
compressor stages of Cooling and 1(one) compressor stage of Dehumidification. Therefore, electrical data for dual compressor systems with
dehumidification mode (reheat) is controller dependent as shown above.

Air Technology Systems, Inc.

- Free-Cooling & Alternate Water Source

COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier)


208/1/60

Electrical Data

Model

- Free-Cooling & Alternate Water Source

(*) Current Draws are given


in the following order:

FLA

MCA

MFS

FLA = Full Load Amps


MCA = Minimum Circuit Amps

(wire size amps)
MFS = Maximum Fuse Size

5-8

Electrical Data
Electrical Data

Model

OHS-012-C
FLA

MCA

- Chilled Water Systems

OHS-018-C
MFS

FLA

MCA

OHS-024-C
MFS

FLA

MCA

OHS-032-C

OHS-040-C

MFS

FLA

MCA

MFS

FLA

MCA

MFS

COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60

2.7

3.4

15

2.7

3.4

15

2.7

3.4

15

3.4

4.3

15

3.8

4.8

15

277/1/60

2.5

3.1

15

2.5

3.1

15

2.5

3.1

15

2.7

3.4

15

3.9

4.9

15

208/3/60

2.7

3.4

15

2.7

3.4

15

2.7

3.4

15

3.4

4.3

15

3.8

4.8

15

460/3/60

1.6

2.0

15

1.6

2.0

15

1.6

2.0

15

1.6

2.0

15

3.0

3.8

15

COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier)


208/1/60

25.4

31.8

35

25.4

31.8

35

25.4

31.8

35

26.1

32.7

35

26.5

33.2

35

277/1/60

20.6

25.7

30

20.6

25.7

30

20.6

25.7

30

20.8

25.9

30

22.0

27.4

30

208/3/60

15.8

19.8

20

15.8

19.8

20

15.8

19.8

20

16.5

20.7

25

16.9

21.2

25

460/3/60

7.9

9.8

15

7.9

9.8

15

7.9

9.8

15

7.9

9.8

15

9.3

11.6

15

COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60

10.9

13.6

15

10.8

13.6

15

10.9

13.6

15

11.6

14.5

15

12.0

15.0

20

277/1/60

8.7

10.9

15

8.7

10.9

15

8.7

10.9

15

8.9

11.1

15

10.1

12.6

15

208/3/60

10.9

13.6

15

10.9

13.6

15

10.9

13.6

15

11.6

14.5

15

12.0

15.0

20

460/3/60

5.3

6.6

15

5.3

6.6

15

5.3

6.6

15

5.3

6.6

15

6.7

8.4

15

COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier)

- Chilled Water Sysetms

208/1/60

25.4

31.8

35

25.4

31.8

35

25.4

31.8

35

26.1

32.7

35

26.5

33.2

35

277/1/60

20.6

25.7

30

20.6

25.7

30

20.6

25.7

30

20.8

25.9

30

22.0

27.4

30

208/3/60

15.8

19.8

20

15.8

19.8

20

15.8

19.8

20

16.5

20.7

25

16.9

21.2

25

460/3/60

7.9

9.8

15

7.9

9.8

15

7.9

9.8

15

7.9

9.8

15

9.3

11.6

15

33.6

42.0

45

34.3

42.9

45

34.7

43.4

45

COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER


208/1/60

33.6

42.0

45

33.6

42.0

45

Air Technology Systems, Inc


277/1/60

26.8

33.4

35

26.8

33.4

35

26.8

33.4

35

27.0

33.7

35

28.2

35.2

40

208/3/60

24.0

30.0

30

24.0

30.0

30

24.0

30.0

30

24.7

30.9

35

25.1

31.4

35

460/3/60

11.6

14.5

15

11.6

14.5

15

11.6

14.5

15

11.6

14.5

15

13.0

16.2

20

MFS

FLA

MFS

FLA

MFS

FLA

MFS

FLA

Model

OHS-048-C

FLA

MCA

OHS-060-C
MCA

OHS-072-C
MCA

OHS-084-C
MCA

OHS-120-C
MCA

MFS

COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60

N/A

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A

N/A
N/A

208/3/60

3.9

4.9

15

5.3

6.6

15

5.3

6.6

15

6.9

8.6

15

8.7

10.9

15

460/3/60

2.2

2.8

15

2.9

3.6

15

2.9

3.6

15

3.7

4.6

15

4.6

5.8

15

COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier)


208/1/60

N/A

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A

N/A
N/A

208/3/60

30.1

37.7

40

31.5

39.4

40

31.5

39.4

45

33.1

41.4

45

34.9

43.7

45

460/3/60

14.8

18.4

20

15.5

19.3

20

15.5

19.3

25

16.3

20.3

25

17.2

21.4

25

COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60

N/A

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A

N/A
N/A

208/3/60

20.3

25.4

30

21.7

27.1

30

19.5

24.4

30

21.1

26.4

30

22.9

28.6

30

460/3/60

9.6

12.0

15

10.3

12.9

15

9.3

11.6

15

10.1

12.6

15

11.0

13.8

15

COOLING and ELECTRIC HEAT only, (No Electric Reheat or Humidifier)


208/1/60

N/A

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A

N/A
N/A

208/3/60

30.1

37.7

40

31.5

39.4

40

31.5

39.4

45

33.1

41.4

45

34.9

43.7

45

460/3/60

14.8

18.4

20

15.5

19.3

20

15.5

19.3

25

16.3

20.3

25

17.2

21.4

25

COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER

5-9

208/1/60

N/A

N/A

N/A

N/A

277/1/60

N/A

N/A

N/A

N/A

N/A
N/A

208/3/60

46.5

58.2

60

47.9

59.9

60

45.7

57.2

60

47.3

59.2

60

49.1

61.4

70

460/3/60

22.2

27.7

30

22.9

28.6

30

21.9

27.3

30

22.7

28.3

30

23.6

29.4

30

Air Technology Systems, Inc.

(*) Current Draws are given


in the following order:

FLA

MCA

MFS

FLA = Full Load Amps


MCA = Minimum Circuit Amps

(wire size amps)
MFS = Maximum Fuse Size

Dimensional Data -

Standard "OHS" Configurations

(Drwg. #)

MODEL TYPE .................page

Physical Data / Connection Sizes

Water / Glycol Cooled Systems

Unit Net Weights (lbs) Table ......................................... 6-2

DX - Refrigerant Connection Sizes ............................... 6-3


Source Water/Glycol Connection Sizes ......................... 6-3
Chilled Water Connection Sizes . .................................. 6-3

Air Cooled Systems


OHS-012/032-AS
"Spot Cooler Configuration"................................ 6-4
"Ducted Configuration"....................................... 6-4
OHS-040-AS
"Spot Cooler Configuration"................................ 6-4
"Ducted Configuration"....................................... 6-5
OHS-012/032-AR
"Spot Cooler Configuration"................................ 6-5
"Ducted Configuration"....................................... 6-5
OHS-040-AR
"Spot Cooler Configuration"................................ 6-6
"Ducted Configuration (direct-drive)"................... 6-6

(8)
(9)

OHS-012/040-HAR (Ducted, belt-drive).................... 6-6


OHS-040/060-AR ..................................................... 6-6

(10)
(11)

OHS-048/084-DAR . ................................................. 6-7


OHS-120-DAR . ........................................................ 6-7

OHS-012/032-W/G
"Spot Cooler Configuration"................................ 6-10
"Ducted Configuration"....................................... 6-10
OHS-040-W/G
"Spot Cooler Configuration"................................ 6-10
"Ducted Configuration (direct-drive)"................... 6-11
OHS-012/040-HW/HG & FC
"Ducted Configuration (belt-drive)"...................... 6-11

(22)

OHS-048/060-W/G & FC .......................................... 6-11

(23)
(24)

OHS-048/084-DW/DG & FC ..................................... 6-12


OHS-120-DW/DG . ................................................... 6-12

(25)

OHS-120-DW/DG-FC ............................................... 6-13

Chilled Water Systems



(26)
(27)

(28)

OHS-012/040-C
"Spot Cooler Configuration"................................ 6-14
"Ducted Configuration"....................................... 6-14
OHS-012/040-HC
"Belt-Driven Ducted Configuration"..................... 6-14

(29)
(30)
(31)

OHS-048/060-C ........................................................ 6-15


OHS-072/084-C ........................................................ 6-15
OHS-120-C ............................................................... 6-15

- Index

(1)
(2)

(3)
(4)

(5)
(6)

(7)
(8)


(18)
(19)

(20)
(21)

(21)

Dimensional Data

"Index"

DX - Air Handling Units



(12)
(13)

(14)

OHS-012/040-AHU
"Spot Cooler Configuration"................................ 6-8
"Ducted Configuration"....................................... 6-8
OHS-012/040-HAHU
"Belt-Driven Ducted Configuration"..................... 6-8

(15)

OHS-048/060-AHU ................................................ 6-9

(16)
(17)

OHS-048/084-DAHU . .............................................. 6-9


OHS-120-DAHU . ..................................................... 6-9

Air Technology Systems, Inc.

6-1

Physical Data Dimensional Data


- Physical Data (Unit Weight lbs.)

OHS-( )-( )
OHS-( )-AS
OHS-( )-AR
OHS-( )-HAR
OHS-( )-AHU
OHS-( )-HAHU
OHS-( )-DAR
OHS-( )-DAHU
OHS-( )-W
OHS-( )-HW
OHS-( )-DW
OHS-( )-G
OHS-( )-HG
OHS-( )-DG
OHS-( )-C
OHS-( )-HC
OHS-( )-( )-FC
OHS-( )-( )-AWS

Unit Weights (lbs.)

Approximate Unit Physical Weight


(Cooling Only! Please see notes, given in lbs.)
012
018
024
032
040
048
060
210
215
220
255
265
160
165
170
205
215
370
380
185
190
195
230
240
120
120
120
155
165
270
280
135
140
145
180
190
420
320
180
200
210
245
260
395
405
205
225
235
265
285
440
180
200
210
245
260
395
405
205
225
235
265
285
440
120
125
125
160
170
280
290
140
145
150
185
190
245
265
275
300
310
500
510
225
230
235
270
280
460
470

072
450
350
470
470
365
570
550

084
510
410
550
550
415
660
610

120
580
480
625
625
495
745
705

Air Technology Systems, Inc

6-2

Table Legend:
Note-1: ----- means unit not available in this configuration
and/or size.
Note-2: Model "OHS" weights shown above are for Cooling
Only Evaporator units without receivers. If Humidity Options
(steam humidifier; electric, hot gas, hot water or steam reheat)
and/or -30F flooded receiver(s) are applicable, please add the
following approximate weights to the Cooling Only model
"OHS" weights shown above:


Features/Options

Model Sizes
012/040 048/060 048/120-D( )

Adding Features:

Net Additions

Steam Humidifier

+ 20 lbs

+ 25 lbs

+ 25 lbs

Electric Reheat
Hot Gas Reheat
Hot Water Reheat
Steam Reheat

+ 15 lbs
+ 30 lbs
+ 30 lbs
+ 30 lbs

+ 25 lbs
+ 35 lbs
+ 35 lbs
+ 35 lbs

+ 25 lbs
+ 45 lbs
+ 45 lbs
+ 45 lbs

-30 Flooded
Condensate Pump

+ 30 lbs
+ 10 lbs

+ 50 lbs
+ 10 lbs

+ 100 lbs
+ 10 lbs

Air Technology Systems, Inc.

Piping Connection Sizes


Model

OHS-018-( )

OHS-024-( )

OHS-032-( )

OHS-040-( )

OHS-048-( )

OHS-060-( )

"A"

"B'

"C"

"A"

"B'

"C"

"A"

"B'

"C"

"A"

"B'

"C"

"A"

"B'

"C"

"A"

"B'

"C"

"A"

"B'

"C"

OHS-( )-AR

----

3/8

1/2

----

3/8

1/2

----

3/8

5/8

----

1/2

5/8

----

1/2

7/8

----

1/2

7/8

----

1/2

7/8

OHS-( )-AHU

5/8

3/8

----

3/4

3/8

----

3/4

3/8

----

3/4

1/2

----

7/8

1/2

----

7/8

1/2

----

7/8

1/2

----

Legend:

Refrigerant Piping connection Sizes Dual Compressor / Circuit Systems


Sizes giver are per circuit OD
Model

OHS-048-( )

OHS-072-( )

OHS-084-( )

OHS-120-( )

"A"

"B'

"C"

"A"

"B'

"C"

"A"

"B'

"C"

"A"

"B'

"C"

OHS-( )-DAR

----

3/8

5/8

----

1/2

5/8

----

1/2

7/8

----

1/2

7/8

OHS-( )-DAHU

3/4

3/8

----

7/8

1/2

----

7/8

1/2

----

7/8

1/2

----

"A"
"B"
"C"

= Suction Line, inches OD Copper


= Liquid Line, inches OD Copper
= Hot Gas, inches OD Copper

Notes:
Note-1: ----- means connection type not applicable
to this unit configuration.
Note-2: Dimensions shown represent the "pipe
connection size" only! For information detailing the
sizing of the interconnecting refrigerant and water
lines, please refer to the CeilAiR Installations, Operations and Maintenance Manual.

(Single Compressor / Single Circuit Systems)


012

018

024

032

040

048

060

IN/OUT

IN/OUT

IN/OUT

IN/OUT

IN/OUT

IN/OUT

IN/OUT

OHS-( )-W/G

5/8

7/8

7/8

7/8

7/8

1-1/8

1-1/8

OHS-( )-W/G-FC

5/8

5/8

5/8

7/8

7/8

1-1/8

1-1/8

Model

Chilled Water / Alternate Water Souce Piping Connection Sizes


Model
OHS-( )-C & AWS

Model
OHS-( )-C & AWS

012

018

024

032

040

048

060

IN/OUT

IN/OUT

IN/OUT

IN/OUT

IN/OUT

IN/OUT

IN/OUT

5/8

7/8

7/8

7/8

7/8

1-1/8

1-1/8

048

072

084

120

IN/OUT

IN/OUT

IN/OUT

IN/OUT

1-1/8

1-1/8

1-1/8

1-3/8

- Piping Connection Sizes

Source Water / Glycol Piping Connection Sizes

Dimensional Data

Refrigerant Piping Connection Sizes - Single Compressor / Circuit Systems


OHS-012-( )

Legend:
IN
OUT

= Inlet Connection, inches OD Copper


= Outlet Connection, inches OD Copper

Air Technology Systems, Inc.

6-3

Air Cooled -

SINGLE Compressor Systems


DIMENSIONAL DATA

Dimensional Data

(1) OHS-012 thru 032-AS


Self-Contained, Air Cooled
("Ductless" Spot Cooler)

- Air Cooled (SINGLE Compressor Systems)

DIMENSIONAL DATA
"C"

"D"

"E"

"F"

15.5"

5.75"

18.0"

19.75"

16.13"

21.5"

10.88"

23.0"

15.63"

19.75"

MODEL

"A"

"B"

OHS-012, 018,& 024-AS

20.38"

OHS-032-AS

26.38"

MODEL

"A"

"B"

"C"

"D"

OHS-012, 018,& 024-AS

20.38"

15.5"

5.50"

18.0"

OHS-032-AS

26.38"

21.5"

10.50"

23.0"

(2) OHS-012 thru 032-AS


Self-Contained, Air Cooled
("Ducted" Evap - Direct Driven)

Air Technology Systems, Inc

6-4

(3) OHS-040-AS
Self-Contained, Air Cooled
("Ductless" Spot Cooler)

Air Technology Systems, Inc.

Air Cooled -

SINGLE Compressor Systems

Dimensional Data

(4) OHS-040-HAS
Self-Contained, Air Cooled
("Ducted" Version - Direct Driven)

MODEL

"A"

OHS-012, 018,& 024-AR

20.38"

OHS-032-AR

26.38"

(5) OHS-012 thru 032-AR


Remote Air Cooled, Evaporator
("Ductless" Spot Cooler)

(6) OHS-012 thru 032-AR

DIMENSIONAL DATA

Remote Air Cooled, Evaporator


("Ducted" Version - Direct Driven)

Air Technology Systems, Inc.

MODEL

"A"

"B"

"D"

"F"

OHS-012, 018,& 024-AR

20.38"

15.5"

19.75"

16.13"

OHS-032-AR

26.38"

21.5"

15.63"

19.75"

- Air Cooled (SINGLE Compressor Systems)

DIMENSIONAL DATA

6-5

Air Cooled -

SINGLE Compressor Systems

Dimensional Data

(7) OHS-040-AR
Remote Air Cooled, Evaporator
("Ductless" Spot Cooler)

DIMENSIONAL DATA

- Air Cooled (SINGLE Compressor Systems)

MODEL

"A"

"B"

"C"

"L"

"M"

OHS-012, 018, & 024-HAR

20.0"

16.0"

see
note

see
note

see
note

OHS-032- & 040-HAR

24.0"

20.0"

see
note

see
note

see
note

OHS-040-HAR @ 0.3" esp


(direct drive blower)

24.0"

(8) OHS-012 thru 040-HAR


Remote Air Cooled, Evaporator
"H-Series Ducted Version"
(040 - Direct Driven) & (012/040 - Belt Driven)

Air Technology Systems, Inc

6-6

20.0"

6.62"

11.38"

10.5"

Note: Consult your local Sales Representative for blower outlet dimensional data for
"High-Static Pressure Blower Option".

DIMENSIONAL DATA

(9) OHS-040 thru 060-AR

MODEL

Remote Air Cooled, Evaporator


(Ducted Only!)

OHS-040 & 060-AR

Air Technology Systems, Inc.

"C"

"L"

"M"

6.62"

11.38"

13.12"

Air Cooled -

DUAL Compressor Systems


DIMENSIONAL DATA

Remote Air Cooled, Evaporator


(DUAL Compressors)

MODEL

"M"

11.38"

13.12"

OHS-072 & 084-DAR

7.62"

13.44"

15.62"

"C"

"L"

"M"

7.25"

13.44"

15.62"

Remote Air Cooled, Evaporator


(DUAL Compressors)

Air Technology Systems, Inc.

- Air Cooled (DUAL Compressor Systems)

MODEL

"L"

6.62"

(11) OHS-120-DAR

DIMENSIONAL DATA
OHS-120-DAR

"C"

OHS-048-DAR

Dimensional Data

(10) OHS-048 thru 084-DAR

6-7

DX - Air Handling Units


DIMENSIONAL DATA

Dimensional Data

(12) OHS-012 thru 040-AHU

MODEL

DX - Air Handling Unit


("Ductless" Spot Cooler)

20.7"

OHS-032 & 040-AR

26.7"

- DX - Air Handling Units

(13) OHS-012 thru 040-AHU

DIMENSIONAL DATA
MODEL

"A"

OHS-012, 018, & 024-AHU

"A"

"B"

"E"

"F"

OHS-012, 018, & 024-AHU

20.7"

15.5"

19.88"

15.75"

OHS-032 & 040-AHU

26.7"

21.5"

15.75"

19.88"

DX - Air Handling Unit


("Ducted Version" - Direct Driven)

Air Technology Systems, Inc

DIMENSIONAL DATA

(14) OHS-012 thru 040-HAHU


DX - "H-Series", Air Handling Unit
("Ducted Version" - Belt Driven)

MODEL

"A"

"E"

"F"

"C"

"L"

"M"

OHS-012, 018, & 024-AHU

20.0"

19.75"

15.63"

see note

see note

see note

OHS-032 & 040-AHU

24.0"

19.75"

19.75"

see note

see note

see note

Note: Consult your local Sales


Representative for blower outlet
dimensional data for "High-Static
Pressure Blower Option".

6-8

Air Technology Systems, Inc.

DX - Air Handling Units


MODEL

DX - Air Handling Unit


(Ducted Only!)

OHS-048 & 060-AHU

MODEL

"C"

"L"

"M"

6.62"

11.38"

13.12"

OHS-072 & 084-AHU

7.62"

13.44"

15.62"

"M"

11.38"

13.12"

(16) OHS-048 thru 084-DAHU

Std CFM @ 0.5" esp

OHS-048-DAHU

"L"

6.62"

DUAL Circuit, DX - Air Handling Unit


(Ducted Only!)

- DX - Air Handling Units

DIMENSIONAL DATA

Std CFM @ 0.5" esp


"C"

Dimensional Data

DIMENSIONAL DATA

(15) OHS-048 thru 060-AHU

DIMENSIONAL DATA

(17) OHS-120-DAHU

MODEL

DUAL Circuit, DX - Air Handling Unit


(Ducted Only!)

OHS-120-DAHU

Air Technology Systems, Inc.

Std CFM @ 0.5" esp


"C"

"L"

"M"

7.38"

13.5"

15.69"

6-9

Water / Glycol Cooled -

SINGLE Compressor Systems

Dimensional Data

DIMENSIONAL DATA

(18) OHS-012 thru 032-W / G


Self-Contained, Water/Glycol Cooled
("Ductless" Spot Cooler)

- Water / Glycol Cooled (SINGLE Compressor Systems)

DIMENSIONAL DATA
MODEL

"A"

"B"

"E"

"F"

OHS-012, 018, & 024-W/G

20.4"

15.5"

19.75"

16.13"

OHS-032-W/G

26.4"

21.5"

15.63"

19.75"

MODEL

"A"

OHS-012, 018, & 024 W/G

20.4"

OHS-032-W/G

26.4"

(19) OHS-012 thru 032-W / G


Self-Contained, Water/Glycol Cooled
("Ducted Version" - Direct Drive)

Air Technology Systems, Inc

6-10

(20) OHS-040-W / G
Self-Contained, Water/Glycol Cooled
("Ductless" Spot Cooler)

Air Technology Systems, Inc.

Water / Glycol Cooled -

SINGLE Compressor Systems

DIMENSIONAL DATA

& optional

OHS-012 thru 040-HW/HG-FC


"H-Series Ducted Version"
(040 - Direct Driven) & (012/040 - Belt Driven)

MODEL

"A"

"B"

"C"

"L"

"M"

OHS-012, 018, & 024-HW/HG


(& HW/HG-FC)

20.0"

16.0"

see note

see note

see note

OHS-032, & 040-HW/HG


(& HW/HG-FC)

24.0"

20.0"

see note

see note

see note

OHS-040-HW/G @ 0.3" esp


(Direct-Drive Blower)

24.0"

20.0"

6.62"

11.38"

10.5"

Note: Consult your local Sales Representative for


blower outlet dimensional data for "High-Static Pressure Blower Option".

MODEL

& optional

Std CFS @ 0.5" esp


"C"

"L"

"M"

OHS-048, & 060-W/G

6.62"

11.38"

13.12"

OHS-048, & 060-W/G-FC

see note

see note

see note

OHS-048 thru 060-W/G-FC


Self-Contained, Water/Glycol Cooled
(Ducted Only!)

Note: Consult your local Sales Representative for blower outlet dimensional data for "High-Static Pressure
Blower Option".

Air Technology Systems, Inc.

- Water / Glycol Cooled (SINGLE Compressor Systems)

(22) OHS-048 thru 060-W / G

DIMENSIONAL DATA

Dimensional Data

(21) OHS-012 thru 040-HW / HG

6-11

Water / Glycol Cooled -

DUAL Compressor Systems

Dimensional Data

(23) OHS-048 thru 084-DW / DG

DIMENSIONAL DATA

& optional
OHS-048 thru 084-DW/DG-FC

MODEL

Self-Contained, Water/Glycol Cooled


(DUAL Compressors)

Std CFS @ 0.5" esp


"C"

"L"

"M"

OHS-048-DW/DG

6.62"

11.38"

13.19"

OHS-072-084-DW/DG

7.62"

13.5"

15.69"

OHS-048/084-DW/DG-FC

see note

see note

see note

Note: Consult your local Sales Representative for blower outlet dimensional
data for "High-Static Pressure Blower
Option".

- Water / Glycol Cooled (DUAL Compressor Systems)

Air Technology Systems, Inc


(24) OHS-120-DW / DG

DIMENSIONAL DATA
MODEL
OHS-120-DW/DG

6-12

Std CFS @ 0.5" esp


"C"

"L"

"M"

7.25"

13.5"

15.69"

Self-Contained, Water/Glycol Cooled


(DUAL Compressors)

Air Technology Systems, Inc.

Water / Glycol Cooled -

"10-ton Free-Cooling Version"

MODEL

"FREE-COOLING Version"
Self-Contained, Water/Glycol Cooled
(DUAL Compressors)

OHS-120-DW/DG-FC

Std CFS @ 0.5" esp


"C"

"L"

"M"

7.62"

13.5"

15.69"

Dimensional Data

DIMENSIONAL DATA

(25) OHS-120-DW / DG-FC

- Water/Glycol Cooled (Optional "Free-Cooling")

Air Technology Systems, Inc.

6-13

Chilled Water Systems -

1 thru 3 Ton Systems


DIMENSIONAL DATA

Dimensional Data

(26) OHS-012 thru 040-C

MODEL

Chilled Water System


("Ductless" Spot Cooler)

DIMENSIONAL DATA

- Chilled Water Systems (1 to 3 Ton Systems)

MODEL

"A"

"B"

"E"

"F"

OHS-012, 018, & 024-C

20.4"

15.5"

19.75"

15.63"

OHS-032, & 040-C

26.4"

21.5"

15.63"

19.75"

"A"

OHS-012-, 018, & 024-C

20.7"

OHS-032 & 040-C

26.7"

(27) OHS-012 thru 040-C


Chilled Water System
("Ducted Version" - Direct Driven)

Air Technology Systems, Inc

6-14

(28) OHS-012 thru 040-HC

DIMENSIONAL DATA
MODEL

"H-Series", Chilled Water System


("Ducted Version" - Belt Driven)

OHS-012, 018, & 024-HC


OHS-032, & 040-HC

"A"

"E"

"F"

"C"

"L"

"M"

20.0"

19.75"

15.63"

SEE NOTE

SEE NOTE

SEE NOTE

24.0"

19.75"

19.75"

SEE NOTE

SEE NOTE

SEE NOTE

Note: Consult your local Sales Representative for blower outlet dimensional data for
"High-Static Pressure Blower Option".

Air Technology Systems, Inc.

Chilled Water Systems -

4 thru 10 Ton Systems


MODEL

Chilled Water System


("Ducted" - Belt Driven)

OHS-048 & 060-C

MODEL
OHS-072 & 084-C

"C"

"L"

"M"

13.5"

15.69"

"M"

11.38"

13.12"

(30) OHS-072 thru 084-C

Std CFS @ 0.5" esp


7.62"

"L"

6.62"

Chilled Water System


("Ducted" - Belt Driven)

DIMENSIONAL DATA

(31) OHS-120-C

MODEL

Chilled Water System


("Ducted" - Belt Driven)

OHS-120-C

Air Technology Systems, Inc.

Std CFS @ 0.5" esp


"C"

"L"

"M"

7.38"

13.5"

15.7"

- Chilled Water Systems (4 to 10 Ton Systems)

DIMENSIONAL DATA

Std CFS @ 0.5" esp


"C"

Dimensional Data

DIMENSIONAL DATA

(29) OHS-048 thru 060-C

6-15

www.stulz-ats.com
Air Technology
Systems, Inc
the greener way of cooling your data center.

1572 Tilco Drive, Frederick, Maryland 21704


Phone: 301.620.2033, Fax: 301.662.5487
E-mail: info@stulz-ats.com
Air Technology Systems, Inc.

Registered

ISO9001

Quality System

ISO-9001:2001 Quality Registered


Copyright, September 2008
QE-OHS0023 Rev Specifications subject to change without notice.

This document was printed on recycled paper, with


ecosmarttm environmentally responsible ink products.
Air Technology Systems, Inc.

You might also like