Kidde AEGIS

Kiddes New Conventional Control Panel is Everything But Conventional!


The Kidde AEGISTM is a fully featured single hazard conventional control panel that is ideal for small- to mid-sized special hazard suppression environments. The AEGIS can be used to control Kiddes full line of suppression systemsFM-200, Carbon Dioxide, 3MTM NovecTM 1230 Fire Protection Fluid, ArgoniteTM, FE-13TM, Halon 1301, WHDRTM Wet Chemical and INDTM Dry Chemical, as well as sprinkler supervisory, deluge/pre-action, foam and foam/water systems. This new sleek panel easily fits between studs of a 16-inch standard wall, yet it is large enough to house two 12 VDC, 12 AH batteries with two-inches of wiring and finger space between the circuit board and cabinet wall access. The AEGIS also works well with in-cabinet applications and can be used in conjunction with the Kidde In-Cabinet Suppression System.

Kidde AEGIS

The AEGIS was engineered to be easy to install, fully robust, yet economical as well. Manual Releases and Abort Switches can be mounted directly onto the panel, avoiding the additional expense of wall mounting these items. A range of circuits has been incorporated to allow programming flexibility to handle all types of special hazard extinguishing systems. These features, as well as the many others packed into this control panel, make the AEGIS the most advanced conventional control panel available to the suppression industry today. All backed with a full five-year warranty from Kidde-the most recognized name in fire protection.

Kidde AEGIS Agency Approvals: cFMus to NFPA 72, ANSI/UL 864, 9th edition and ULC-S527-99 CSFM Approved MEA Approved cULus to ANSI/UL 864, 9th edition and ULC-S527-99

Kidde Fire SystemsWe Are the Right Protection... Every Time, Everywhere, Every Application.

www.kiddefiresystems.com

Kidde AEGIS Features:


Programming Flexibility
The range of circuits on the AEGIS allow to program special cases: Combination Clean Agent plus Double-Interlocked Deluge/Pre-Action Systems Third Detection Circuit is programmable for either Water flow Input or as a suppression independent detection circuit A 5.4 Amp PSU! The battery charger is able to charge upto a 68 AH battery thereby allowing for 90-hours of standby supervision plus 10-minutes of alarmas required by some authorities. This ensures continuous fire protection in the event of downtime due to a power failure. All circuits, excluding the Agent Release Circuits, are power-limited thereby allowing the installer to run all wiring through the same conduit, cutting down the cost of extra materials. Optionally, the Agent Release circuits can also be converted to power-limited when not using AH Intitators. The two Agent Release Circuits can be programmed with independent time delays and abort modes to fire combinations of two of the following releasing devices: 1 or 2 Control Heads (Up to 4 Control Heads with both Agent Release Circuits) 1 FM Sprinkler Solenoid (2 FM Sprinkler Solenoids with both Agent Release Circuits) 1 Metron Head This triple redundancy process safeguards the system by ensuring no inadvertent activation of the suppression can occur in case of microprocessor failure. As required by many applications, the AEGIS has built-in Class A supervision fo all circuits. Furthermore, Class A wiring can be achieved without any additional hardware. All three NACs use a protocol that enables silenceable horns and non-silenceable strobes to be used on the same NAC, which can significantly reduce costs.

A Robust Power Supply Unit (PSU)

Power Limited Circuits

Independently Programmable Agent Releasing Circuits

Triple-RTM Protection

Class A Circuitry

Sophisticated Notification Appliance Circuits (NACs)

Release Countdown Timer

An easy-to-read release countdown timer lets you know exactly when the system is going to discharge. Read the open circuit battery voltage and the battery charging current on a working panel without disconnecting the batteries or using external multi-meters! Set a password when you install the panel it ensure the system isnt tampered with before you stop back to service the panel. If a password is forgotten, simply call the factory for a temporary daily password. Kidde stands behind the AEGIS, which is why were extending a five-year warranty for this product.

Battery Voltage and Charging Display

Password Protection

A Five Year Warranty

Kidde is registered trademark of Kidde-Fenwal, Inc. AEGIS is a trademark of Kidde-Fenwal, Inc. SS K-012 November 2007 Kidde-Fenwal, Inc. All Rights Reserved.

AEGIS
Conventional Fire Alarm-Suppression Control Unit
A UTC Fire & Security Company

Effective: November 2007 K-84-100

FEATURES
Agency Approvals cFMus Approved to NFPA 72, ANSI 864, 9th edition and ULC-S527-99 CSFM Approved MEA Approved cULus Listed to ANSI 864, 9th edition and ULC-S527-99 Suppression focused Control Unit Listed for a Wide Range of Suppression Systems Kidde FM-200, FE13TM, CO2, 3MTM Novec 1230TM Input and Output 3 Detection Circuits 2 Supervisory Circuits 1 Manual Release Circuit 1 Abort Input Circuit 3 Notification Appliance Circuits 2 Release Circuits 4 Form-C Relays Programmable Relays Robust Power Supply Elegant User-Interface Simple Configuration Password Protected Digital Release Countdown Battery Voltage and Charging Current Display Extensive Diagnostics Backwards Compatible Improved and Enlarged Cabinet Design 5-Year Warranty

Fire Protection Fluid, ArgoniteTM, and Halon Clean Agents TM TM Kidde IND Dry Chemical & WHDR Wet Chemical Systems Sprinkler Supervisory Service Deluge, Preaction, Foam, Foam-Water Systems Combination Clean Agent plus Pre-Action System Built-in Class-A and Class-B Circuitry Sophisticated Programmable Notification Appliance Circuits Independently Programmable Agent Releasing Circuits with Triple-R Protection

DESCRIPTION
The Kidde AEGIS is the technologically most advanced Conventional Single Hazard Agent Releasing Unit available to the Fire-Alarm Suppression industry today. It combines the high quality, system reliability, and flexibility required by modern commercial, high-tech and industrial applications in an aesthetically pleasing and physically robust package. The AEGIS is well equipped to handle all special hazard extinguishing systems due to the high degree of programming flexibility provided and the following full complement of input and output circuits:
Three (3) Class A or Class B Detection Circuits Two (2) Class A or Class B Supervisory Circuits One (1) Class A or Class B Manual Release Circuit One (1) Class A or Class B Abort Input Circuit Three (3) Class A or Class B Notification Appliance Circuits Two (2) Class B Agent Release Circuits Four (4) Form-C Relays

DETECTION CIRCUITS The Detection Circuits can support up to 25 Conventional CPD-705x Ionization Smoke, PSD-715x Photoelectric Smoke, or THD-705x Heat Detectors each as well as Normally Open contact closure type devices. Two circuits are dedicated to the main suppression function and can be programmed to activate the release circuits by either single-shot or cross-zone input. The user-configuration allows automatic release via detection to be delayed from 0 to 60 seconds in 10-second intervals and also allows a choice of which of the two Agent Release Circuits to activate. The third Detection Circuit is programmable for either Waterflow or as an independent Detection circuit. When programmed for Waterflow, Notification Appliance Circuits can be programmed as Non-Silenceable as required by certain jurisdictions. SUPERVISORY CIRCUITS The Supervisory Circuits accept Normally Open contact closure type devices such as pressure switches on the agent cylinders or on the water or air pipe network. The system configuration enables the supervisory input to be a participant in the suppression function. For example, low air supervisory can be included with detection for release of pre-action systems as required by certain jurisdictions.

MANUAL RELEASE AND ABORT CIRCUITS Both the Manual Release and Abort Circuits accept Normally Open contact closure type devices. Activation of the Agent Release Circuits can either be instantaneous or delayed up to 30 seconds (maximum) upon receipt of Manual Release input. Agent release can be temporarily delayed by activating the Abort Circuit. The Abort input can be programmed for 5 modes of operation. These include the UL 10-second mode, the full-delay mode, the IRI mode, the NYC mode, or the abort can be disabled. Aborts can also be programmed to be applicable for either one or both Agent Release Circuits thereby allowing use with Deluge/Pre-Action systems. NOTIFICATION APPLIANCE CIRCUITS (NAC) The three Notification Appliance Circuits are rated 1.5 Amps each and accept polarized 24 Vdc Notification Appliances. Each circuit is driven independently and is user configurable for First Alarm, Pre-Release, and Releasing as well as for 60 BPM, 120 BPM, Temporal, or Continuous pattern. The MT and NS series appliances provide the option to use silenceable horns and non-silenceable strobes on the same NAC. Multiple NAC circuits (connected to audible devices only) programmed with the same master code pattern are synchronized, regardless of any differing starting times that preceded their concurrent operation. The NACs configuration includes a userselectable intelligent synchronization feature which allows a silenceable horn to be shut off while the strobe continues to flash in synchronized fashion.
MANUAL WATERFLOW/ ABORT RELEASE DETECTOR 3 DETECTOR 2

SUPERVISORY 2

SUPERVISORY 1

TB7 TROUBLE RELAY 3 RELAY 2 RELAY 1 TB8

TB6

TB5

TB4

TB3

TB2 TB1 DETECTOR 1

TB9 TB10 TB11

BATT OUT

TB12

AC SUPPLY SELECT SWITCH (S6)


TB19

NAC 1

AC IN TB13

TB14

TB15

TB16

TB17

TB18

NAC 2

RELEASE 1 ARC 1

RELEASE 2 ARC 2

AUX 24 VDC

NAC 3

Figure 1. Printed Circuit Board (PCB)

-2-

BUILT-IN CLASS A AND B CIRCUITRY For the input and NAC circuits, the choice of Class A or Class B supervision is made at site on the board itself by selecting the terminals used for wiring. Neither conversion boards nor additional hardware nor jumper selection is required for this purpose. AGENT RELEASE CIRCUITS (ARC) The two circuits can be programmed for activation by different inputs, with independent time delays and abort modes to fire combinations of two of the following releasing devices: 1 or 2 Kidde Continuous and Momentary Solenoid Control Heads 1 Kidde Initiator 1 Factory Mutual Group A, B, D, E, F, G, I, J, or K Solenoid

POWER-LIMITED CIRCUITRY All circuits, excluding ARCs are inherently power-limited. Agent Release Circuits, except when firing Initiators, can also be made power-limited by a field located inline releasing diode device thereby allowing cost effective installation with all wiring in the same conduit. ROBUST POWER SUPPLY UNIT (PSU) The AEGIS features a universal 120/240 V, 50/60 Hz AC Power Supply Unit with a robust 5.4 Amps of 24 Vdc power. Input voltage selection is via a slider switch with no jumper cutting required. The on-board battery charger is able to charge 24 Vdc (2 x 12) batteries of capacity up to 68 Ah thereby allowing from 24 hours of supervision plus 5 minutes of alarm to 90 hours of supervision plus 10 minutes of alarm required by some jurisdictions. AUXILIARY POWER SUPPLY Up to 1 Amp of auxiliary power at 24 Vdc is available to power external 4-wire devices such as Flame Detectors, AlarmLine modules, Duct Detectors, etc. ELEGANT USER-INTERFACE The user-interface consists of an array of LED Indicators, Control Switches, a Digital Display, and Buzzer. Over and above the System, Power Supply status, Input circuit Fire and Trouble and Output circuit Trouble LEDs, the AEGIS annunciates its suppression state-of-alarm via three additional Pre-Release, Releasing and Post Release LEDs. Four switches are provided, one each for Acknowledge, Signal Silence, System Reset and Output Disable. The 3-digit display provides a countdown of impending agent release. On command from the userinterface switches, it also indicates the battery open circuit voltage and charging current. SIMPLE SITE-SPECIFIC CONFIGURATION Accessed via the digital display and user-interface switches, site-specific configuration is simple, yet detailed and can typically be performed in a matter of minutes. To prevent unauthorized use, the configuration menu is protected by a user-changeable password. Factory technical support can provide assistance with lost or forgotten passwords. Apart from the input voltage selection performed on both the PSU and main board via a slider switch, no other onboard settings or jumper cuttings are required. EXTENSIVE DIAGNOSTICS Also initiated via the digital display and user-interface switches, the troubleshooting function displays diagnostic codes that assist in determining causes of trouble. A complete list of diagnostic codes and their meaning ships factory installed on the inside of the enclosure door for easy reference.

In other words, operating in tandem, the two circuits can release: 1 or 2 Control Heads on ARC1 and 1 or 2 Control Heads on ARC2 1 or 2 Control Heads on ARC1 and 1 Initiator on ARC2 or vice-versa 1 or 2 Control Heads on ARC1 and 1 FM Sprinkler Solenoid on ARC2 or vice-versa 1 Initiator on ARC1 and 1 Initiator on ARC2 1 FM Solenoid on ARC1 and 1 FM Solenoid on ARC2

This configurability is useful for those jurisdictions where the gaseous suppression agent is required to be supplemented with a pre-action system. TRIPLE-R PROTECTION FOR AGENT RELEASING CIRCUITS (ARC) The two ARCs feature a triple failure redundancy safeguard system to protect them from inadvertent activation by the main microprocessor. The Triple-R system requires that in order to activate an ARC, the main microprocessor issues two release commands of opposing polarity via separate channels and that these commands be combined with a third signal from the panel watchdog timer to confirm the microprocessor operation. The Triple-R system ensures that electrical transients or disturbances such as power surges that could interfere with the operation of the main microprocessor will not inadvertently activate the connected suppression system. The result is a more robust and reliable suppression-focused panel. PROGRAMMABLE RELAYS Of the 4 relays, three are user-programmable for a variety of alarm related conditions and the fourth is a dedicated trouble relay. All relay contacts are rated 3.0 Amps at 30 Vdc/120 Vac (resistive).

-3-

BACKWARDS COMPATIBILITY Consistent with previous generation Kidde control equipment, the AEGIS is listed to be backwards compatible with the full range of Kidde-Fenwal conventional detectors, alarm devices and suppression accessories. Going forward, this will allow older generation panels to be replaced with relative ease. IMPROVED AND ENLARGED CABINET DESIGN The cabinet design allows for easy installation by fitting between the studs of a standard 16 inch studded wall. It is large enough to house two 12 Vdc, 12 Ah Batteries and provides up to 2 inches (51 mm) of wiring and finger space between the circuit board and the cabinet wall. An optional door design features a Manual Release and Abort switch for applications with space constraints. Both switches incorporate guards that prevent their inadvertent activation. Other cabinet options include a flush mounting trim-ring and a dead-front plate required for Canadian applications.

TECHNICAL SPECIFICATIONS (contd)


One (1) Abort Circuit - Compatible with normally open contact-closure type devices - Configurable as Class A/Style D or Class B/Style B - Supervised for ground faults and open circuits - Power-limited Two (2) Supervisory Circuits - Compatible with normally open contact-closure type devices - Configurable as Class A/Style D or Class B/Style B - Supervised for ground faults and open circuits - Power-limited Three (3) Notification Appliance Circuits (NACs) - Compatible with polarized 24 VDC Audio-Visual devices - Rated at 1.5 Amps each - Configurable as Class A/Style Z or Class B/Style Y - Supervised for ground faults, shorts, and open circuits - Power-limited - Common NAC/ARC output disconnect switch Two (2) Agent Release Circuits - Each compatible with 1 or 2 control heads, or 1 initiator, or 1 FM sprinkler solenoid - Circuits electrically capable of simultaneously releasing any combination of two of the above devices - Factory configured as Class B/Style Y - Supervised for ground faults and open circuits - Non-power-limited. May be power-limited (except with initiators) and supervised for short circuit using inline releasing resistor-diode device - Common NAC/ARC output disconnect switch Four (4) Relays - 3 independently programmable, normally deenergized Form-C - 1 dedicated normally energized Form-C Trouble Relay - Relay contacts rated 3 Amps at 30 Vdc/120 Vac (resistive)

TECHNICAL SPECIFICATIONS
Hazards Protected - One Power Supply - 120/240 Vac, 50/60 Hz (90 to 264 Vrms, 47 to 63 Hz) AC Main Input - 5.4 Amps at 27 Vdc Output - Battery capacity up to 68 Ah @ 24 Vdc - Auxiliary power output rated at 1 Amp at 18.8 - 27.6 Vdc (resettable) Three (3) Detection Circuits - Compatible with up to 25 CPD-705x, PSD-715x, and THD-705x detectors and normally open contact-closure type devices - Configurable as Class A/Style D or Class B/Style B - Supervised for ground faults and open circuits - Power limited - DET 1 and DET 2 used for suppression - DET3/WF configurable for detection or waterflow One (1) Manual Release Circuit - Compatible with normally open contact-closure type devices - Configurable as Class A/Style D or Class B/Style B - Supervised for ground faults and open circuits - Power limited

-4-

TECHNICAL SPECIFICATIONS (contd)


Enclosure - NEMA 1 rated 18 gauge sheet steel with door - Red color - Suitable for wall and surface mounting - Optional Trim Ring - Optional Dead-Front Panel - Optional door with Manual Release and Abort switches - Dimensions: - with Standard Door: 14-1/4 in. W x 5 in. D x 19 in. H (362 mm x 127 mm x 483 mm) - with Switch Door: 14-1/4 in. W x 6 in. D x 19 in. H (362 mm x 152 mm x 483 mm) Environmental Criteria - Indoor/Dry use only - Operating temperature range: 32F to 120F (0C to 49C) - Humidity: 93 2% RH at 90 3F (32 2C) Packaging/Shipping - Enclosure, PCB, and PSU packaged in individual cartons - Accessories shipped include mounting hardware, battery leads, IOM manual on CD-ROM, operating instruction sheet, and EOL resistor kit - Order inline releasing resistor-diode device (if required) and batteries separately

ORDERING INFORMATION
Description Kidde AEGIS Control Panel Kidde AEGIS Control Unit with Switches In-Line Releasing Diode (10K) Kit Trim Ring Dead-Front Panel* Battery Enclosure Kidde AEGIS Conventional Fire Alarm-Suppression Control Unit IOM Manual Kidde AEGIS Users CD Installation/Configuration Kit Operating Instructions Replacement Hardware Installation Kit Replacement Enclosure Assembly Replacement Enclosure Assembly (with Switches) Replacement Switch Kit Replacement PCB Assembly Replacement Power Supply Replacement Bezel Assembly Spare Key Spare Keylock with Keys EOL Backbox (Canadian applications only) Battery Harness Part Number 84-732001-001 84-732001-201 06-220023-001 76-600000-007 06-220175-001 76-100010-001 06-236716-001

06-236727-001 06-220148-002 06-236719-002 06-220149-001 06-220172-002 06-220174-002 06-220176-001 06-220150-001 06-118394-002 06-220151-001 06-118013-001 06-129924-001 06-129963-002 06-129925-002

*For Canadian applications, order Control Unit and Dead-Front Panel separately.

-5-

Kidde is a registered trademark of Kidde-Fenwal, Inc. AEGIS and Gemini are trademarks of Kidde-Fenwal, Inc. FM-200 is a registered trademark of Chemtura. FE-13 is a registered trademark of DuPont. 3MTM NovecTM 1230 Fire Protection Fluid is a trademark of 3M. ArgoniteTM is a registered trademark of Ginge Kerr.

For detailed installation, operation, and configuration information, refer to the Kidde AEGIS Conventional Fire Alarm-Suppression Conventional Unit Installation, Operation, and Maintenance Manual P/N 06-236716-001.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the products suitability for a particular application. The product must be properly applied to work correctly. If you need more information on this product, or if you have a particular problem or question, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000. K-84-100 Rev AC 2007 Kidde-Fenwal Inc. Printed in USA

A UTC Fire & Security Company


400 Main Street Ashland, MA 01721 Ph: 508.881.2000 Fax: 508.881.8920 www.kiddefiresystems.com

Advanced Ionization Smoke Detectors


Models CPD-7054 and CPD-7054D
FEATURES
Approvals/Listing US and Canadian UL Listed (cULus) FM Approved CSFM Approved NYC MEA Accepted Dual Ionization Chamber Technology Nominal Sensitivity CPD-7054: 1.30% per ft. Obscuration CPD-7054D: 1.00% per ft. Obscuration Sensitivity Measurement/Testing Wireless Measurement in %/ft. Obscuration Remote and Local Functional Test Capability Wide Range of Input Voltage 10.2 to 36.8 Vdc Low Current Design Dual Response LEDs Allow 360-degree Viewing Trouble Indication Low Profile Appearance Using Surface Mount Technology Electrically and Mechanically Compatible with all Fenwal Smoke and Electronic Heat Detectors and Bases Interchangeable 2-Wire and 4-Wire Bases Universal Relay Modules Non Polarized Locking Feature for Vandal Resistance Fine Mesh Insect Screen EMI and RFI Resistant

A UTC Fire & Security Company

Effective: September 2008 70-01

DESCRIPTION
The Advance Models CPD-7054 & CPD-7054D are dual chamber Ionization Smoke Detectors designed to sense both visible and invisible products of combustion. The Detectors have advanced solid-state, low-voltage, surface-mount circuitry and are designed for 2-Wire and 4-Wire installation using the appropriate Detector base. The characteristic 360-degree detector design permits smoke entry from any direction. A unique sensing chamber design permits the operation of the Models CPD-7054 and CPD-7054D in open areas with air velocities from 0 to 300 fpm and 0 to 500 fpm, respectively. The Model CPD-7054D is also suitable for duct housing applications in air velocities from 500 to 4000 fpm. The Detectors are designed for open area/ duct housing applications per UL268/UL268A and may be installed in systems intended for Releasing Device Service through use of compatible Fire Alarm Control Panels.

Two red Light Emitting Diodes (LEDs) are located diametrically opposite each other so as to allow 360degree viewing. Both LEDs continuously indicate the operating condition of the Detector. During standby, the LEDs flash once every six seconds. During alarm, both LEDs light steady at full brilliance. A double flash every six seconds indicates a detector with a sensitivity threshold outside acceptable limits. A unique gated output circuit design provides improved stability and transient suppression. Special signal processing techniques verify the presence of smoke before the detector will alarm. A fine mesh insect screen protects the chamber area and is used to avoid potential nuisance alarms. The detector head is installed into its mounting base with a simple twist-lock action. A locking feature is provided for vandal resistant security. Table 1 lists the Technical Specifications for Models CPD7054 and CPD-7054D Ionization Smoke Detectors.

CONTROL UNITS
The Models CPD-7054 and CPD-7054D Detectors are designed to operate with control units and releasing devices having specific voltage and current characteristics that are compatible with the detector circuitry. Both models are compatible with the Fenwal 732 control unit. The Fenwal 732 has three detection circuits which can support up to 25 detectors per circuit.

Table 1: Technical Specification Model Number


Part Number Detection Approvals UL Compatibility I.D. Listed Spacing Radioactive Source Material Activity Nominal Sensitivity Standby Voltage (Vdc) Using 2WB: Using 4WRB: Maximum Current Standby: Alarm: Response Indicators Quantity: Standby Condition: Thermistor Trouble: Alarm Condition: Operating Environment Operating Temperature: Storage Temperature: Relative Humidity: Air Velocity Open Area: Duct Housing: Altitude: Physical Characteristics Material and Finish: Weight: Dimensions Detector Height: Detector Diameter: Base Height: Base Diameter: 1-3/8 in. (35 mm) 3-29/32 in. (99 mm) 3/64 in. (11 mm) 5-29/32 in. (150 mm) 1-3/8 in. (35 mm) 3-29/32 in. (99 mm) 3/64 in. (11 mm) 5-29/32 in. (150 mm) 0 to 300 fpm (0 to 1.5 m/s) N/A Up to 7,500 feet (2,286 m) High-impact, flame-retardant plastic, off white 35.3 oz. (110g) w/o base 35.3 oz. (110g) w/o base 0 to 500 fpm (0 to 2.5 m/s) 500 to 4000 fpm (2.5 to 20 m/s) Up to 7,500 feet (2,286 m) High-impact, flame-retardant plastic, off white 70 A 100 mA 2 external LEDs One flash every 9 seconds Double flash every 9 seconds Steady at full brilliance 32 to 120F (0 to 49C) -20 to 180F (-29 to 82C) 0 to 93% Non-condensing 70 A 100 mA 2 external LEDs One flash every 9 seconds Double flash every 9 seconds Steady at full brilliance 32 to 120F (0 to 49C) -20 to 180F (-29 to 82C) 0 to 93% Non-condensing

CPD-7054
70-540000-001 Dual Ionization Chamber cULus, FM, CSFM, MEA-NYC, USNRC, CNSC I51FE1 30 ft. (9.1 m) centers or 900 ft.2 (83.6 m2) Americium 241 (sealed) 0.8 Ci (29.6 kBq) 1.30% + 0.25% - 0.42% per foot Obscuration 10.2 to 36.8 16.8 to 36.8

CPD-7054D
70-540000-002 Dual Ionization Chamber cULus, FM, CSFM, MEA-NYC, USNRC, CNSC I51FE1 30 ft. (9.1 m) centers or 900 ft.2 (83.6 m2) Americium 241 (sealed) 0.8 Ci (29.6 kBq 1.00% + 0.10% - 0.12% per foot Obscuration 10.2 to 36.8 16.8 to 36.8

-2-

DETECTOR BASE OPTIONS


The Models CPD-7054 and CPD-7054D can be used with the detector base options and accessories in Table 2. Various base options are available to provide auxiliary relay and/or remote indication and remote test feature. The Model CPD-7054 and CPD-7054D Ionization Smoke Detectors may be interchanged with other Fenwal Series THD-705X Electronic Heat Detector and Series PSD715X Photoelectric Smoke Detectors when using multifunction base configuration.

without removing the detector from its base. A go/no-go test can be performed using a test magnet. The recommended requirement for detector maintenance consists of an annual cleaning of dust from the detector head by using the suction of a vacuum cleaner. Cleaning programs should be geared to the individual environment in conformance with NFPA 72.

SPACING (OPEN AREA LOCATION)


The Models CPD-7054 and CPD-7054D Detectors are listed to be installed on maximum 30 ft. (9.1 m) centers, typically on smooth ceilings up to 15 ft. (4.6 m) high and will operate with minimum air circulation. Resultant maximum 900 square foot (83.6 m2) spacing may be used as a reasonable guide for comparable applications. Where special conditions exist (ceiling obstructions, high air exchange rates, etc.), reduced spacing must be used to achieve adequate protection. Computer rooms and other such installations may require spacing with a maximum of 200 ft.2 (18.6 m2) due to high air exchange rates. Detectors should not be located in areas with excessive exhaust fumes, kitchen areas, near fireplaces or furnace rooms and within three (3) ft. (0.9 m) of air supply ducts or air diffusers. For additional information, consult the Fenwal Automatic Fire Detection Application Engineering Manual MC-402, NFPA-72 and the local Authority Having Jurisdiction. CAUTION

Do not attempt disassembly of the factory sealed smoke detector. This assembly is sealed for your protection and should not be opened for servicing. Opening of the detector will void its warranty.

SPARE PARTS
The Models CPD-7054 and CPD-7054D Detectors are factory repairable only and have no field serviceable spare parts. No field repair should therefore be attempted. For service, return detector head intact to Fenwal.

RADIOACTIVE MATERIAL/DISPOSAL
The Americium 241 radioactive material used is shielded by a stainless steel housing and has a maximum activity of 0.8 microcuries (29.6 kBq). The United States Nuclear Regulatory Commission (USNRC) allows the user of Americium 241 filled smoke detectors to dispose of them without obtaining a license. Under the Code of Federal Regulations, Part 10 (10CFR), Paragraph 30.20, any person receiving, using, owning, etc., by-product material in detectors designed to protect life or property from fires or airborne hazards is automatically granted a general license which, conversely, exempts them from a specific license, thereby allowing them to both receive and dispose of smoke detectors without returning to the manufacturer.

WIRING DIAGRAMS
For detailed wiring diagrams with Fenwal 2- and 4-wire bases, please refer Fenwal Document 06-235056-001.

INSTALLATION
Detector bases are directly mounted on the electrical junction boxes (3-inch, 3-1/2-inch and 4-inch octagonal, 3-inch round or 4-inch2) (76 mm, 89 mm, 102 mm octagonal, 76 mm round or 102 mm2) without the need for any mechanical adapter required. Refer Fenwal Document 06-235056-001 for additional details.

ARCHITECT/ENGINEER SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, UL268/UL268A listed dual-chamber, Ionization Smoke Detectors, Fenwal Models CPD-7054 and CPD-7054D. Ionization Smoke Detectors containing a radioactive source of strength greater than 0.8 microcuries (29.6 kBq) shall not be acceptable. The combination detector head and twist-lock base shall be UL Listed compatible with a UL Listed fire alarm control unit. The Models CPD-7054 and CPD-7054D Ionization Smoke Detectors shall share interchangeable bases with the PSD-7157 and PSD-7157D Photoelectric Smoke Detectors and the THD-7052 and THD-7053 Heat Detectors.The Fenwal Models CPD-7054 and CPD7054D Ionization Smoke Detectors shall have two Red LEDs located diametrically opposite each other so as to

TESTING AND MAINTENANCE


Testing shall be performed upon installation of the detector and once a year thereafter as stated in NFPA-72 latest edition. Detector sensitivity shall be checked within one year of installation and every alternative year thereafter as stated in NFPA 72. Refer Fenwal Documents 06-236514-001 and 06-235056-001 for details on using the Infrared Wireless Sensitivity Tester Model DST-003. The tester provides direct readout in percent per foot obscuration from a distance of 15 ft.

-3-

allow 360-degree viewing. The LEDs shall continuously indicate the operating condition of the Detector. During standby, the LEDs shall flash once every six seconds. During alarm, both LEDs shall light steady at full brilliance. If the sensitivity of the detector drifts outside acceptable limits, the LEDs shall double flash every six seconds. The detector may be reset by actuating the control panel reset switch. The vandal-resistant security locking feature shall be used in those areas as indicated on the drawings. The locking feature shall be field removable when not required. It shall be possible to measure the sensitivity of the Fenwal Models CPD-7054 and CPD-7054D Ionization Smoke Detectors from a distance of up to 15 ft. (4.6 m) without removal from the base. Measurement shall be accomplished with a wireless infrared Fenwal Sensitivity Tester (DST-003) allowing direct measurement in percent per foot obscuration. Sensitivity measurement techniques requiring wiring between the Detector-Base combination and the Tester shall not be acceptable. It shall also be possible to perform a functional test of the detector without the need for generating smoke.

The Fenwal Models CPD-7054 and CPD-7054D Ionization Smoke Detectors shall operate over an input voltage range from 10.2 to 36.8 Vdc. Voltage and RF transient suppression techniques to withstand up to 20 volt/meter shall be employed to minimize susceptibility to false alarms. Supplementary SPDT relays, remote test, and/or remote LED alarm indicators shall be installed where indicated.

-4-

Table 2: Ordering Information Part Number Model Description

Detector Heads - Ionization Smoke 70-540000-001 70-540000-002 CPD-7054 CPD-7054D Ionization Advanced Smoke Detector (cULus) Ionization Advanced Smoke Detector (cULus)

Detector Heads - Photoelectric Smoke 71-570000-001 71-570000-002 Detector Heads - Heat 70-520000-001 70-530000-001 Detector Bases 70-501000-001 70-501000-002 2-Wire 2WRLT 2-Wire Standard Base. Connects to circuit via screw terminals. (CID = FE51A) 2-Wire Base w/ Remote LED & Test capabilities. Connects to circuit via screw terminals. Minimum Alarm Current 15 mA @ 24 Vdc. (CID = FE52A) 2-Wire Base w/ 2WRM, Remote LED & Test capabilities. Connects to circuit via pigtail leads. Minimum Alarm Current 19 mA @ 24 Vdc. (CID = FE55A) 4-Wire Base w/ 4WRM, Remote LED & Test capabilities. Connects to circuit via pigtail leads. Minimum Alarm Current 35 mA @ 24 Vdc. Spare SPDT Relay for 2WRB Bases. Contacts rated 1.0 A, 30 Vdc/0.5 A, 125 Vac. THD-7052 THD-7053 135F (57C) Fixed Heat Detector, 15F (-9C) Rate of Rise (cULus) 135F (57C) Fixed Heat Detector (cULus) PSD-7157 PSD-7157D Photoelectric Advanced Smoke Detector (cULus) Photoelectric Advanced Smoke Detector (cULus)

70-501000-005

2WRB

70-501000-101

4WRB

70-500000-004 Detector Accessories 06-117883-001 29-116788-001 70-200000-911 70-200000-914 70-500000-003 70-501000-003

2WRM

Test Magnet EOL Supervisory Relay RA-911 RA-914 DST-003 MA-001 Remote Alarm Indicator Remote Alarm Indicator with Smoke Detector Switch Advanced Handheld Wireless Smoke Detector Sensitivity Tester Mechanical Retrofit Adapter. Allows CPD-705X and PSD-715X Detectors to physically connect to Base P/Ns 70-201000-001, -002, -003, -005 & DH-22. (CID = MAFE1)

-5-

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the products suitability for a particular application. The product must be properly applied to work correctly. If you need more information on this product, or if you have a particular problem or question, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000. 70-01 Rev AD 2008 Kidde-Fenwal Inc. Printed in USA

A UTC Fire & Security Company


400 Main Street Ashland, MA 01721 Ph: 508.881.2000 Fax: 508.881.8920 www.kiddefiresystems.com

Advanced Photoelectric Smoke Detectors


Models PSD-7157 and PSD-7157D
FEATURES
Approvals/Listing US and Canadian UL Listed (cULus) FM Approved CSFM Approved NYC MEA Accepted Nominal Sensitivity PSD-7157: 3.25% per ft. Obscuration PSD-7157D: 2.40% per ft. Obscuration Sensitivity Measurement/Testing Wireless Measurement in %/ft. Obscuration Remote and Local Functional Test Capability Wide Range of Input Voltage 10.2 to 36.8 Vdc Low Current Design Dual Response LEDs Allow 360-degree Viewing Trouble Indication Low Profile Appearance Using Surface Mount Technology Electrically and Mechanically Compatible with all Fenwal Smoke and Electronic Heat Detectors and Bases Interchangeable 2-Wire and 4-Wire Bases Universal Relay Modules Non Polarized Locking Feature for Vandal Resistance Fine Mesh Insect Screen EMI and RFI Resistant

A UTC Fire & Security Company

Effective: September 2008 70-02

DESCRIPTION
The Advance Models of PSD-7157 and PSD-7157D Photoelectric Smoke Detectors respond to a broad spectrum of both flaming and smoldering fire conditions. The Detectors have advanced solid-state, low-voltage, surface-mount circuitry and are designed for 2-Wire and 4-Wire installation using the appropriate Detector base. The characteristic 360-degree detector design permits smoke entry from any direction. A unique sensing chamber design permits the operation of the Models PSD-7157 and PSD-7157D in open areas with air velocities from 0 to 300 fpm and 0 to 4000 fpm respectively. The Model PSD-7157D is also suitable for duct housing applications in air velocities from 500 to 4000 fpm. The Detectors are designed for open area/ duct housing applications per UL268/UL268A and may be installed in systems intended for Releasing Device Service through use of compatible Fire Alarm Control Panels.

Two Red Light Emitting Diodes are located diametrically opposite each other so as to allow 360-degree viewing. Both LEDs continuously indicate the operating condition of the Detector. During standby, the LEDs flash once every six seconds. During alarm, both LEDs light steady at full brilliance. A double flash every six seconds indicates a detector with a sensitivity threshold outside acceptable limits. A unique gated output circuit design provides improved stability and transient suppression. Special signal processing techniques verify the presence of smoke before the detector will alarm. A fine mesh insect screen protects the chamber area and is used to avoid potential nuisance alarms. The detector head is installed into the base with a simple twist-lock action. A locking feature is provided for vandal resistant security. Table 1 lists the Technical Specifications for Models PSD7157 and PSD-7157D Photoelectric Smoke Detectors.

CONTROL UNITS
The Models PSD-7157 and PSD-7157D Detectors are designed for operation with control units and releasing devices having specific voltage and current characteristics that are compatible with the detector circuitry. The Detectors are compatible with the Fenwal 732 control unit. The Fenwal 732 has three detection circuits which can support up to 26 detectors per circuit.

Table 1: Technical Specification Model Number


Part Number Detection Approvals UL Compatibility I.D. Listed Spacing Nominal Sensitivity Standby Voltage (Vdc) Using 2WB: Using 4WRB: Maximum Current Standby: Alarm: Response Indicators Quantity: Standby Condition: Thermistor Trouble: Alarm Condition: Operating Environment Operating Temperature: Storage Temperature: Relative Humidity: Air Velocity Open Area: Duct Housing: Altitude: Physical Characteristics Material and Finish: Weight: Dimensions Detector Height: Detector Diameter: Base Height: Base Diameter: 1-3/8 in. (35 mm) 3-29/32 in. (99 mm) 3/64 in. (11 mm) 5-29/32 in. (150 mm) 1-3/8 in. (35 mm) 3-29/32 in. (99 mm) 3/64 in. (11 mm) 5-29/32 in. (150 mm) 0 to 300 fpm (0 to 1.5 m/s) N/A Up to 7,500 feet (2,286 m) High-impact, flame-retardant plastic, off white 35.3 oz. (110g) w/o base 0 to 4000 fpm (0 to 20 m/s) 500 to 4000 fpm (2.5 to 20 m/s) Up to 7,500 feet (2,286 m) High-impact, flame-retardant plastic, off white 35.3 oz. (110g) w/o base 70 A 100 mA 2 external LEDs One flash every 11 seconds Double flash every 11 seconds Steady at full brilliance 32 to 120F (0 to 49C) -20 to 180F (-29 to 82C) 0 to 93% Non-condensing 70 A 100 mA 2 external LEDs One flash every 11 seconds Double flash every 11 seconds Steady at full brilliance 32 to 120F (0 to 49C) -20 to 180F (-29 to 82C) 0 to 93% Non-condensing

PSD-7157
71-570000-001 Photoelectric cULus, FM, CSFM, MEA-NYC P55FE1 30 ft. (9.1 m) centers or 900 ft.2 (83.6 m2) 3.25% + 0.45% - 1.78% per foot Obscuration 10.2 to 36.8 16.8 to 36.8

PSD-7157D
71-570000-002 Photoelectric cULus, FM, CSFM, MEA-NYC P55FE1 30 ft. (9.1 m) centers or 900 ft.2 (83.6 m2) 2.40% + 0.04% - 1.34% per foot Obscuration 10.2 to 36.8 16.8 to 36.8

DETECTOR BASE OPTIONS


The Models PSD-7157 and PSD-7157D can be used with the detector base options and accessories in Tables 2. Various base options are available to provide auxiliary relay and/or remote indication and remote test feature.

The Models PSD-7157 and PSD-7157D Photoelectric Smoke Detectors may be interchanged with other Fenwal Series THD-705X Electronic Heat Detectors and Series CPD-705X Ionization Smoke Detectors when using multifunction base configuration.

-2-

SPACING (OPEN AREA LOCATION)


The Models PSD-7157 and PSD-7157D Detectors are listed to be installed on maximum 30 ft. (9.1 m) centers, typically on smooth ceilings up to 15 ft. (4.6 m) high and will operate with minimum air circulation. Resultant maximum 900 square foot (83.6 m ) spacing may be used as a reasonable guide for comparable applications. Where special conditions exist (ceiling obstructions, high air exchange rates, etc.), reduced spacing must be used to achieve adequate protection. Computer rooms and other such installations may require spacing with a maximum of 200 ft.2 (18.6 m2) due to high air exchange rates. Detectors should not be located in areas with excessive exhaust fumes, kitchen areas, near fireplaces or furnace rooms and within three (3) ft. (.9 m) of air supply ducts or air diffusers. For additional information, consult the Fenwal Automatic Fire Detection Application Engineering Manual MC-402, NFPA-72 and the local Authority Having Jurisdiction.
2

CAUTION

Do not attempt disassembly of the factory sealed smoke detector. This assembly is sealed for your protection and should not be opened for servicing. Opening of the detector will void its warranty.

SPARE PARTS
The Models PSD-7157 and PSD-7157D Detectors are factory repairable only and have no field serviceable spare parts. No field repair should therefore be attempted. For service, return detector head intact to Fenwal.

ARCHITECT/ENGINEER SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, UL268/UL268A listed Photoelectric Smoke Detectors, Fenwal Models PSD-7157 and PSD-7157D. The combination detector head and twist-lock base shall be UL Listed compatible with a UL Listed fire alarm control unit. The Models PSD-7157 and PSD-7157D Photoelectric Smoke Detectors shall share interchangeable bases with the CPD-7054 and CPD7054D Ionization Smoke Detectors and the THD-7052 and THD-7053 Heat Detectors. The Fenwal Models PSD-7157 and PSD-7157D Photoelectric Smoke Detectors shall have two Red LEDs located diametrically opposite each other so as to allow 360-degree viewing. The LEDs shall continuously indicate the operating condition of the Detector. During standby, the LEDs shall flash once every six seconds. During alarm, both LEDs shall light steady at full brilliance. If the sensitivity of the detector drifts outside acceptable limits, the LEDs shall double flash every six seconds. The detector may be reset by actuating the control panel reset switch. The vandal-resistant security locking feature shall be used in those areas as indicated on the drawings. The locking feature shall be field removable when not required. It shall be possible to measure the sensitivity of the Fenwal Models PSD-7157 and PSD-7157D Photoelectric Smoke Detectors from a distance of up to 15 feet (4.6 m) without removal from the base. Measurement shall be accomplished with a wireless infrared Fenwal Sensitivity Tester (DST-003) allowing direct measurement in percent per foot obscuration. Sensitivity measurement techniques requiring wiring between the Detector-Base combination and the Tester shall not be acceptable. It shall also be possible to perform a functional test of the detector without the need for generating smoke.

WIRING DIAGRAMS
For detailed wiring diagrams with Fenwal 2- and 4-wire bases, please refer Fenwal Document 70.104

INSTALLATION
Detector bases are directly mounted on the electrical junction boxes (3-inch, 3-1/2-inch and 4-inch octagonal, 3-inch round or 4-inch square) (76 mm, 89 mm, 102 mm octagonal, 76 mm round or 102 mm square) without the need for any mechanical adapter required. Refer Fenwal Document 06-235056-001 for additional details. The detector bases also include a locking feature that prevents removal of the detector without use of a tool.

TESTING AND MAINTENANCE


Testing shall be performed upon installation of the detector and once a year thereafter as stated in NFPA-72 latest edition. Detector sensitivity shall be checked within one year of installation and every alternative year thereafter as stated in NFPA 72. Refer Fenwal Documents 06-236524-001 and 06-235056-001 for details on using the Infrared Wireless Sensitivity Tester Model DST-003. The tester provides direct readout in percent per foot obscuration from a distance of 15 ft. without removing the detector from its base. A go/no-go test can be performed using a test magnet. The recommended requirement for detector maintenance consists of an annual cleaning of dust from the detector head by using the suction of a vacuum cleaner. Cleaning programs should be geared to the individual environment in conformance with NFPA 72.

-3-

The Fenwal Models PSD-7157 and PSD-7157D Photoelectric Smoke Detectors shall operate over an input voltage range from 10.2 to 36.8 Vdc. Voltage and RF transient suppression techniques to withstand up to 20 volt/meter shall be employed to minimize susceptibility to false alarms.

Supplementary SPDT relays, remote test, and/or remote LED alarm indicators shall be installed where indicated .

Table 2: Ordering Information Part Number Model Description

Detector Heads - Ionization Smoke 70-540000-001 70-540000-002 CPD-7054 CPD-7054D Ionization Advanced Smoke Detector (cULus) Ionization Advanced Smoke Detector (cULus)

Detector Heads - Photoelectric Smoke 71-570000-001 71-570000-002 Detector Heads - Heat 70-520000-001 70-530000-001 Detector Bases 70-501000-001 70-501000-002 2-Wire 2WRLT 2-Wire Standard Base. Connects to circuit via screw terminals. (CID = FE51A) 2-Wire Base w/ Remote LED & Test capabilities. Connects to circuit via screw terminals. Minimum Alarm Current 15 mA @ 24 Vdc. (CID = FE52A) 2-Wire Base w/ 2WRM, Remote LED & Test capabilities. Connects to circuit via pigtail leads. Minimum Alarm Current 19 mA @ 24 Vdc. (CID = FE55A) 4-Wire Base w/ 4WRM, Remote LED & Test capabilities. Connects to circuit via pigtail leads. Minimum Alarm Current 35 mA @ 24 Vdc. Spare SPDT Relay for 2WRB Bases. Contacts rated 1.0 A, 30 Vdc/0.5 A, 125 Vac. THD-7052 THD-7053 135F (57C) Fixed Heat Detector, 15F (-9C) Rate of Rise (cULus) 135F (57C) Fixed Heat Detector (cULus) PSD-7157 PSD-7157D Photoelectric Advanced Smoke Detector (cULus) Photoelectric Advanced Smoke Detector (cULus)

70-501000-005

2WRB

70-501000-101

4WRB

70-500000-004 Detector Accessories 06-117883-001 29-116788-001 70-200000-911 70-200000-914 70-500000-003 70-501000-003

2WRM

Test Magnet EOL Supervisory Relay RA-911 RA-914 DST-003 MA-001 Remote Alarm Indicator Remote Alarm Indicator with Smoke Detector Switch Advanced Handheld Wireless Smoke Detector Sensitivity Tester Mechanical Retrofit Adapter. Allows CPD-705X and PSD-715X Detectors to physically connect to Base P/Ns 70-201000-001, -002, -003, -005 & DH-22. (CID = MAFE1)

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the products suitability for a particular application. The product must be properly applied to work correctly. If you need more information on this product, or if you have a particular problem or question, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000. 70-02 Rev AE 2008 Kidde-Fenwal Inc. Printed in USA

A UTC Fire & Security Company


400 Main Street Ashland, MA 01721 Ph: 508.881.2000 Fax: 508.881.8920 www.kiddefiresystems.com