BOILER TRIP PROTECTION

MASTER FUEL TRIP PROTECTIONS:


SL NO PARAMTR TRIP CONDN ALARM TRIP TIME DELAY REMARKS

Both ID Fans

OFF

--

--

--

Both FD Fans

OFF

--

--

--

3 hardwired contacts for each ID fan (2/3) (HT Switchgear) 3 hardwired contacts for each FD fan (2/3) (HT Switchgear)

4 5 6 7 8 9 10

UCP: EMG PB MFT1 and MFT 2 Any OWS: EMG trip command Furnace Pressure Furnace Pressure Drum Level Drum Level Total Air Flow

Pressed together Initiated & Confirmed V LO V HI V LO V HI V LO

---100 +75 -125 +125 --

---175 +150 -225 +225 < 30%(3 24 T/Hr) --

----5 sec 10 sec 2/3 Pressure Switches 2/3 Pressure Switches 2/3 Transmitter 2/3 Transmitter Flow Transmitters

11 12

Loss of Reheat Protection Unit 220V DC

Acted Not Available

--

10 sec 2 sec

Arming: 220V DC for LOTV/ HOTV and HORV solenoids & Scanner air Emergency Damper 24V for MFT Panel Hardwired trip 110V AC for nozzle valve solenoids Arming: All feeders off Arming: Any feeder proven Arming: Any LO/HO nozzle valve not closed

13 14

Unit 24V DC (FSSS internal) Loss of FB & loss of AC in any elevation i/s Unit Flame Failure Trip Loss of All Fuel Trip

Not Available Loss of 110V AC Activated Activated

---

---

-2 sec

15 16

---

---

---

NOTE: All Trip Conditions are individually sensed by each MFT panel. Final 2/3 Logic for Master Fuel Trip is hardwired in Purge Panel.

TURBINE TRIP PROTECTION

Sl.No. 01. 02. 03. 04. 05. 06. 07. 08. 09. 10. 11. 12. 13. 14. 15. 16. 17.

Description Emergency push button trip from desk & OWS Fire Protection 1 & 2 from control desk & OWS and MBLD 1 & 2 (from MOT room & TG 17m) FCS trip optd 2/3. (arming > 540rpm) Lub Oil pressure very low 2/3. HP exhaust steam temp. Very high 2/3. Axial shift Very high 2/3. Cold gas temp. after H2 cooler high AB 2/3. Cold gas temp. after H2 cooler CD 2/3. Seal oil temp. after cooler high 2/3. Liquid level in main leads high 2/3. Hot air temp. exciter high 2/3. Turbine / Generator brg Temp ATRS Trip Over Speed Trip Boiler trip to Turbine trip. Generator trip to Turbine trip. MOT level very low (2/3) (Through Fire Protection logic)

Set Value < -0.7 kg/cm2 < 1.2 kg/cm2 > 450oC > .5 mm > 55oC > 55oC > 55oC > 90 mm > 85oC >90 deg / > 130 deg

>3210 rpm < 1050 mm