Operation Manual

Model MPM4700 Intelligent Level Transmitter

MICRO SENSOR CO.,LTD.

Content
1 Brief Introduction ...........................................................................................................................................1 2 Specification ..................................................................................................................................................1 3 Construction and Outline dimension ..........................................................................................................2 4 Unpacking, Storage and Shipment Enclosed ...........................................................................................2 5 Installation ......................................................................................................................................................2 6 Operation, Maintenance and Failure Identification ..................................................................................7

Our company keeps the modification right for the update of product technology and craftwork. If anything is changed, no more information will be noticed. Please pay attention to the latest version.( V09.06.1)

MPM4700 Intelligent Level Transmitter

1 Brief Introduction
MPM4700 transmitter is full-sealed submersible intelligent level instrument. It is made up by building-in OEM pressure sensor with good stability & reliability and high accuracy intelligent circuit board into the stainless steel housing. The transmitter parameters could be adjusted and calibrated through RS485 interface and software. The integrated construction and standard output signal provide convenience for worksite operation and automatically controlling.

The product is manufactured in conformity to License for Manufacturing Measurement Instrument Shaanzhi No. 03000112 of P. R. China.

2 Specification
Basic range 3.5 7 10 20 35 70 100 200 mH2O Overpressure 5 10 15 30 50 100 150 300 mH2O If the ordered pressure range is not indicated on the above table, it would be achieved by shrinking the basic range. The least shrinking range is 1/5 basic range. For example, 8MPa is ordered, 10MPa will be chosen for shrinking. --------------------------------------------------------------------------------------------------------------------------Environment Environment Temperature-1080 Atmosphere86106kPa Compensated Temperature Range050 Accuracy0.1%FS (min.), 0.25%FS (typ.), 0.5%FS (max.) Notethe accuracy is the total accuracy of basic range in the compensated temperature range Resolution0.01%FS Long-term Stability0.25%FS (typ.) ---------------------------------------------------------------------------------------------------------------------------Output Signal420mADC 2-wire Power Supply828VDC Load Resistance U8V0. 02A Cable7.2mm PVC or polyurethane cable with vented tube Interface: RS 4852-wire Baud rate: 1200240048009600 are optional Insulation100M50V Endurance1x107 pressure cycle0~100%FS@25 Vibration20g (20~5000)Hz Shock20g 11ms ProtectionIP68 Material met with media1Cr18Ni9Ti stainless steelviton Weight~ 160g
1

MPM4700 Intelligent Level Transmitter

3 Construction and Outline dimension


3.1 Construction Material HousingStainless Steel 1Cr18Ni9Ti O-ringViton Diaphragmstainless steel 316L Rubber casingPolyurethane rubber Cable7.2mm PCV special cable Connection BoxAluminium-alloy (ZL102) 3.2 Construction and Outline Dimension

Chart 1

4 Unpacking, Storage and Shipment Enclosed


4.1 Unpacking Attentions: (1) Please be sure that the package is complete, and the package is put as the sign UP; (2) Please be sure do not knock at the package violently, and protect the housing jacket and rubber bushing. 4.2 Shipment Enclosed MPM4700 Intelligent Level Transmitter 1 PVC special Cableconnect to transmitter the length due to the order Connection Boxconnect to transmitter due to the order Indicator( mounted in connection box A due to the order User s Manual 1 Product Qualification Certificate 1 Qualification Tracking Card 1 Converted Interface due to the order Software due to the order 4.3 Storage The transmitter should be stored in dry & ventilate room with environment temperature -40 80, relative humility 85%, and no corrosive gas.

5 Installation
5.1 Checking before Installation
2

MPM4700 Intelligent Level Transmitter Attention before installation 1 Please be sure the liquid static pressure brought at the operation place will not exceed the transmitter measurement range 2 Please be sure the measuring liquid is compatible with the construction material 3 Please be sure the liquid will not jam the liquid leading hole 5.2 Installation Method The transmitter should be mounted vertical down. In the flowing water, please be sure the sensing face is parallel with the water flowing direction. 5.2.1 Installation in Static Water The installation method in the pool to see chart 2: Connection Box

H Static Water h

Sediment

H0 Chart 2

To protect the transmitter, it should be mounted far away from the pumping in/out source to prevent the pumping impact; the transmitter also could be mounted as Chart 3, protected by steel pipe. The installation method in the deep well to see chart 3: Steel pipe inserting method could be used. The steel pipe could not be bent, the internal diameter 30mm. Several little holes could be made at different heights of the pipe for lifting up and down conveniently and making the water going through unobstructed. If necessary, the transmitter could be wrapped by steel wire. Lift up and down with the steel wire to protect the cable. Connection Box

Pipe Clamp Little Hole Steel Pipe Chart 3


3

MPM4700 Intelligent Level Transmitter

5.2.2 Installation in the flowing water (e.g. river-way or reservoir) need water calming device Method 1Inserting steel pipe in the water channel (to see chart 4

Connection Box Control Room Connection Box Control Room Water Flowing Direction

Little Holes

Chart 4

Chart 5

The steel pipe should be thicker, and several little holes should be made at different heights of the pipe to damp wave and reduce water moving effect. Method 2Superficial burying is better in the sand and stone channelto see chart 5 Method 3to see chart 6 This method not only can dispel water flowing pressure and wave influence, but also can filter the sand and mud.

Air Pocket Damper

Chart 6 5.3 Electric Connection The transmitter could be connected with the external circuit through socket, cable or connection box. Functions Wire Terminal Black 2 V OUT/GND Red 1 RS 485B White 4 RS 485A Yellow 3

Terminals Chart

MPM4700 Intelligent Level Transmitter The electric connection method of transmitter with 2-wire, 420mADC output to see chart 7: Black/+U Transmitter P Input P I Red/+OUT

828VDC

U
Load

A
Output I

DC mA meter 4~20mADC

Chart 7 The electric connection method of transmitter with 4 20mADC output and RS485 communication (calibration)to see chart 8: Black/+U 8~28VDC

P Input

Transmitter P

U R

A
DC mA meter 4~20mADC

Red/+OUT Yellow/RS485A

Load Output I

Interface White / RS485B

Computer and software

Chart 8 Note: when 420mADC output and RS485 are used at the same time, signal 485 may interfere 4 20mADC output signal. The influence is related to communication speed and frequency. Setonline control software could be downloaded from our website. The electric connection method of transmitter only with RS485 communication to see chart 9: Black/+U 8~28VDC

P Input

Transmitter P

Red/+OUT Yellow/RS485A Interface White / RS485B

Computer and software

Chart 9 There is a plastic tube inside the cable, it is used to connect gauge sensor with the atmosphere. In the installation and operation, please be sure the vented tube connected with the atmosphere unobstructed. Please do not jam the vented tube with mud or sand, especially do not make water or other liquid going through the vented tube.

MPM4700 Intelligent Level Transmitter

2-wire 4~20mA supplied through safe barrier output intrinsically safe system to see Figure 10.

Transmitter explosion proof parameter: Safe barrier output explosion proof parameter: Ui28VDC Ii93mADC Uo28VDC Io93mADC Li0mH Ci0.02F Po=0.65W Pi=0.65W The biggest permitted distributed capacitance for the cable between the transmitter and safe barrier connection is Cp=Co-Ci, the biggest permitted distributed inductance Lp=Lo-Li. Users can buy a safe barrier by yourself, only need to take care its specs are as above-mentioned requirements and have an explosion-proof certificate. The installation of safe barrier is in accordance with its operating instructions. Note Uithe highest input voltage, the highest voltage which could work on transmitter input terminals. Uo the highest output voltage, the highest voltage on intrinsically safe circuit when safe barrier s output side is open. Iithe max. input current, the max. current which could work on transmitter input terminals. Io the max. output current, the max. current on intrinsically safe circuit which could be got from safe barrier output terminals. Cithe max. internal capacitance, the internal equal total capacitance which could exist on transmitter input terminals. Cothe max. external capacitance, the max. intrinsically safe capacitance which could be connected with safe barrier output terminals. Lithe max. internal inductance, the internal equal total inductance which could exist on transmitter input terminals. Lothe max. external inductance, the biggest inductance which could be connected with safe barrier s terminals.

MPM4700 Intelligent Level Transmitter

6 Operation, Maintenance and Failure Identification


6.1 Operation The user could operate the transmitter without any adjustment. Please check the installation and make sure the correct electric connection before operation. Then connect the power and operate. 6.2 Maintenance MPM4700 intelligent level transmitter does not need regular maintenance. However, please pay attention to the following items for better operation. (1) Please check the cable connection often and make sure the cable connection reliably and no aging. (2) Please clean the steel cap and diaphragm cavity according to the measuring media. (take care!) (3) Please do not pull the cable violently or press the diaphragm with sharp or hard metal, etc. (4) Please be sure the vented tube connected with the atmosphere unobstructed. Please do not jam the vented tube to prevent make additional error. 6.3 Failure Identification If the transmitter is failure, such as no output or output unstable, ect. Please shut the power first, then check if the installation and cable connection conform to manual, power voltage is correct or not, vented tube is unobstructed or not and the system works well or not. If something is abnormal, please try to get rid of the failure. If the failure can not be dealt with, please contact with our company promptly.