PMC :

PROJECT : OWNER : INSTALLATION, OPERATION AND MAINTENANCE OF CRUDE AND FINISHED PRODUCTS TANKAGES FACILITY AT PARADIP REFINERY PROJECT, PARADIP ON BUILD-OWN-OPERATE-TRANSFER (BOOT) BASIS

CAUSE AND EFFECT CHART (UNIT-203)

O3 O2 O1
Rev.

13.09.11 21.04.11 01.09.10


Date
IOT Utkal Energy Services Ltd.

Re-Issued For Comments Re-Issued For Comments Issued For Comments


Description

AVS AVS MA
Prepared by

SHV PKD NT
Checked by

SHV SHV SHV


Approved by

BOOT OPERATOR :

Document Number CAUSE AND EFFECT CHART

Rev.

EPC CONTRACTOR :

IOT Infrasturture & Energy Services Ltd. ENGINEERING ASSOCIATE :

UNIT: 203

PDRP8005-8110-24-203-0001

O3

Sheet 1 of 5
IOT Design & Engineering Ltd.New Delhi

This document and the design it covers are the property of IOT DESIGN & ENGINEERING LIMITED. They are merely loaned and on the borrower's express agreement that they will not be reproduced, copied, loaned, exhibited or used except in limited way and private use permitted by written consent given by the lender to the borrower.

PMC:

PROJECT : INSTALLATION, OPERATION AND MAINTENANCE OF CRUDE AND FINISHED PRODUCTS TANKAGES FACILITY AT PARADIP REFINERY PROJECT, PARADIP ON BUILD-OWN-OPERATE-TRANSFER (BOOT) BASIS
UNIT : 203
REV. NO.

P& ID NO.: PDRP8005-8110-25-203-0009

LEGEND:
0009 0009

O = OPEN VALVE S= SHUTDOWN MACHINERY ESD = EMERGENCY SHUTDOWN ST= START THE MACHINERY
A = ALARM

ESD Valve at Inlet of Tank 203-TK-017

0009

HDT HSD Supply Pump (Note 1,2)

DESCRIPTION

1. All instruments tag no.s are preceded by area Unit numbers 2. Vendor to confirm Shutdown actions. 3. Trips associated with F&G causes and inherent equipment protect will be provided seperately. 4. All P &ID no.s Preceded by PDRP8005-8110-25-203. SPECIFIC NOTES: 1. IOCL/Foster Wheeler has to take neccesary action on Unit-212(ETP) on Pump(203-P-0006A/B) Shutdown. 2. Motor temperature alarms to be confirmed later. 3. Low low pressure at running pump discharge will trip the running pump. Operator to start the standby pump in that case.

HDT HSD Supply Pump (Note 1,2)

GENERAL NOTES:

ESD Valve at Outlet of Tank 203-TK017

EFFECT

0009

C = CLOSE VALVE

P&ID NO.

TAG NO.

XZV-5001

CAUSE
REV. NO TAG NO. LIAHH-0130 LIALL-0130 LIAH-0130 LIAL-0130 TIAH-0130 TIAL-0130 TIAHH-0130 TIALL-0130 LIAHH-0058 LIALL-0058 LIAH-0058 LIAL-0058 TIAH-0058 TIAL-0058 TIAHH-0058 TIALL-0058 PIAH-0092 PIAL-0092 PIALL-0092 NOTES Service On Tank 203-TK-017 On Tank 203-TK-017 On Tank 203-TK-017 On Tank 203-TK-017 On Tank 203-TK-017 On Tank 203-TK-017 On Tank 203-TK-017 On Tank 203-TK-017 On Tank 203-TK-017 On Tank 203-TK-017 On Tank 203-TK-017 On Tank 203-TK-017 On Tank 203-TK-017 On Tank 203-TK-017 On Tank 203-TK-017 On Tank 203-TK-017 On Pump (203-P-006) Discharge On Pump (203-P-006) Discharge On Pump (203-P-006) Discharge ESD Actuation at HDT HSD Storage Area ESD Actuation at Pump House PH-8 Alarm generated because of Power Failure Closure of ESD Valve at Outlet of Tank 203-TK-017 At Pump 203-P-0006A/B Min. flow line At Pump 203-P-0006A/B Discharge Header At Pump 203-P-0006A/B Discharge Header At Pump 203-P-0006A/B Discharge Header At Pump 205-P-006 A Discharge line At Pump 205-P-006 B Discharge line At Pump 205-P-006 A Discharge line At Pump 205-P-006 B Discharge line P&ID NO. 0009 0009 0009 0009 0009 0009 0009 0009 0009 0009 0009 0009 0009 0009 0009 0009 0009 0009 0009 IZ-0021 IZ-0030 IZ-0031 IZ-0050 IZ-0002 IZ-0004 Interlock No. IZ-0001 IZ-0003 SET UNITS POINT

C S S C

XZV-5002

P-006A

P-006B

C S S C

S S S

S S S C C C

O3 XZV-5002 FIAH-0031 O3 FICAH-0006 FICAL-0006 FCIALL0006 PIAHH-6095 PIAHH-6096 PIALL-6095 PIALL-6096 3 3

IZ-0032 0009 0009 0009 0009 0009 0009 0009 0009 IZ-0051 IZ-0052 IZ-0053 IZ-0054

S S S S

BOOT OPERATOR: IOT UTKAL ENERGY SERVICES LTD EPC CONTRACTOR:

O3 O2 O1 Rev.

13.09.2011 21.04.2011 01.09.2010

Date

RE-ISSUED FOR COMMENTS RE-ISSUED FOR COMMENTS ISSUED FOR COMMENTS Issue Description

AVS AVS MA Prpd.by

SHV PKD NT Vrfd.by

SHV SHV SHV Appr. By

CAUSE AND EFFECT CHART


IOT Infrastructure & Energy Services Ltd ENGINEERING ASSOCIATE: DOCUMENT NUMBER JOB CODE Sheet 2 of 5

ALARM A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A

This document and the design it covers are the property of IOT DESIGN & ENGINEERING LIMITED. They are merely loaned and on the borrower's express agreement that they will not be reproduced, copied, loaned, exhibited or used except in limited way and private use permitted by written consent given by the lender to the borrower.

PMC:

PROJECT : INSTALLATION, OPERATION AND MAINTENANCE OF CRUDE AND FINISHED PRODUCTS TANKAGES FACILITY AT PARADIP REFINERY PROJECT, PARADIP ON BUILD-OWN-OPERATE-TRANSFER (BOOT) BASIS
UNIT : 203
REV. NO.

P& ID NO.: PDRP8005-8110-25-203-0033

LEGEND:
0033

O = OPEN VALVE S= SHUTDOWN MACHINERY ESD = EMERGENCY SHUTDOWN ST= START THE MACHINERY
A = ALARM

GENERAL NOTES:
DESCRIPTION

1. All instruments tag no.s are preceded by area Unit numbers 2. Vendor to confirm Shutdown actions. 3. Trips associated with F&G causes and inherent equipment protect will be provided seperately. 4. All P &ID no.s Preceded by PDRP8005-8110-25-203. SPECIFIC NOTES: 1. At high level one Pump will start. In the event of failure of duty pump to start, the standby pump will start at high-high level. O3 2. At low level, the running pump shall stop. An additional trip at low-low level has been provided for safety.
O3

Oily Water Transfer Pump

Oily Water Transfer Pump

EFFECT

0033

C = CLOSE VALVE

P&ID NO.

TAG NO.

CAUSE
REV. NO TAG NO. LZIALL-0109 LIAH-0110 LIAL-0110 O3 LIAHH-0110 FICAH-0026 FICAL-0026 LZIAHH0109 O3 TIAH-0110 1 NOTES 2 1 2 Service On Sump 203-V-002 On Sump 203-V-002 On Sump 203-V-002 DELETED On Pump (203-P024A/B) Discharge On Pump (203-P024A/B) Discharge On Sump 203-V-002 On Sump 203-V-002 0033 0033 0033 0033 IZ-0055 P&ID NO. 0033 0033 0033 Interlock No. IZ-0005 IZ-0006 IZ-0008 IZ-0007 SET UNITS POINT

S ST S

P-024B

P-024A

S ST S

ST

ST

BOOT OPERATOR: IOT UTKAL ENERGY SERVICES LTD EPC CONTRACTOR:

O3 O2 O1 Rev.

13.09.2011 21.04.2011 01.09.2010

Date

RE-ISSUED FOR COMMENTS RE-ISSUED FOR COMMENTS ISSUED FOR COMMENTS Issue Description

AVS AVS MA Prpd.by

SHV PKD NT Vrfd.by

SHV SHV SHV Appr. By

CAUSE AND EFFECT CHART


IOT Infrastructure & Energy Services Ltd ENGINEERING ASSOCIATE: DOCUMENT NUMBER PDRP8005-8110-24-203-0001 JOB CODE Sheet 3 of 5 PDRP8005

ALARM A A A A A A A

PMC:
This document and the design it covers are the property of IOT DESIGN & ENGINEERING LIMITED. They are merely loaned and on the borrower's express agreement that they will not be reproduced, copied, loaned, exhibited or used except in limited way and private use permitted by written consent given by the lender to the borrower.

PROJECT : INSTALLATION, OPERATION AND MAINTENANCE OF CRUDE AND FINISHED PRODUCTS TANKAGES FACILITY AT PARADIP REFINERY PROJECT, PARADIP ON BUILD-OWN-OPERATE-TRANSFER (BOOT) BASIS
UNIT : 203
REV. NO.

P& ID NO.:

PDRP8005-8110-25-203-0034

LEGEND: O = OPEN VALVE S= SHUTDOWN MACHINERY ESD = EMERGENCY SHUTDOWN ST= START THE MACHINERY
A = ALARM Water Transfer Pump DESCRIPTION Water Transfer Pump 0034 0034

C = CLOSE VALVE

1. All instruments tag no.s are preceded by area Unit numbers 2. Vendor to confirm Shutdown actions. 3. Trips associated with F&G causes and inherent equipment protect will be provided seperately. 4. All P &ID no.s Preceded by PDRP8005-8110-25-203. SPECIFIC NOTES: 1. Operator to bring second tank inline & isolate the tank under evacuation between Low and Low Low levels from pump suction. 2 Pump shutdown will take place if there is no certified product tank 3. At high level one Pump will start. In the event of failure of duty pump to start, the standby pump will start at high-high level. O3 4. At low level, the running pump shall stop. An additional trip at low-low level has been provided for safety.
O3

EFFECT

GENERAL NOTES:

P&ID NO.

TAG NO.

CAUSE
REV. NO TAG NO. LIAHH-0066 LIALL-0066 LIAH-0066 LIAL-0066 TIAH-0066 TIAL-0066 TIAHH-0066 TIALL-0066 ILIAHH-0111 ILIALL-0111 ILIAH-0111 ILIAL-0111 TIAH-0111 TIAL-0111 TIAHH-0111 TIALL-0111 LIAHH-0121 LIALL-0121 LIAH-0121 LIAL-0121 TIAH-0121 TIAL-0121 TIAHH-0121 TIALL-0121 ILIAHH-0112 ILIALL-0112 ILIAH-0112 ILIAL-0112 TIAH-0112 TIAL-0112 TIAHH-0112 TIALL-0112 TICH-0113 TICL-0113 O3 O3 O3 O3 O3 O3 O3 O3 O3 O3 FICAL-0027 FICAH-0027 LIAHH-0302 LIAH-0302 LIALL-0302 LIAL-0302 LIAHH-0301 LIAH-0301 LIALL-0301 LIAL-0301
3 3 4 4 3 3 4 4

NOTES

Service

Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted Deleted On Condensate to TPI Header On Condensate to TPI Header At Pump 203-P-025 A/B discharge header At Pump 203-P-025 A/B discharge header On TPI 203-A-001 On TPI 203-A-001 On TPI 203-A-001 On TPI 203-A-001 On TPI 203-A-002 On TPI 203-A-002 On TPI 203-A-002 On TPI 203-A-002

P&ID NO. 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 0034

Interlock No.

SET UNITS POINT

IZ-0010 IZ-0012

IZ-0013 IZ-0015

P-025A

P-025A

0034 0034 0034 0034 0034 0034 0034 0034 0034 0034 IZ-0060 IZ-0061 IZ-0062 IZ-0063 IZ-0064 IZ-0065 IZ-0066 IZ-0067 ST ST S S ST ST S S ST ST S S ST ST S S

BOOT OPERATOR: IOT UTKAL ENERGY SERVICES LTD EPC CONTRACTOR:

O3 O2 O1 Rev.

13.09.2011 21.04.2011 01.09.2010

Date

RE-ISSUED FOR COMMENTS RE-ISSUED FOR COMMENTS ISSUED FOR COMMENTS Issue Description

AVS AVS MA Prpd.by

SHV PKD NT Vrfd.by

SHV SHV SHV Appr. By

CAUSE AND EFFECT CHART


IOT Infrastructure & Energy Services Ltd ENGINEERING ASSOCIATE: DOCUMENT NUMBER PDRP8005-8110-24-203-0001 JOB CODE Sheet 4 of 5 PDRP8005

ALARM A A A A A A A A A A A A

PMC:
This document and the design it covers are the property of IOT DESIGN & ENGINEERING LIMITED. They are merely loaned and on the borrower's express agreement that they will not be reproduced, copied, loaned, exhibited or used except in limited way and private use permitted by written consent given by the lender to the borrower.

PROJECT : INSTALLATION, OPERATION AND MAINTENANCE OF CRUDE AND FINISHED PRODUCTS TANKAGES FACILITY AT PARADIP REFINERY PROJECT, PARADIP ON BUILD-OWN-OPERATE-TRANSFER (BOOT) BASIS
UNIT : 203
REV. NO.

P& ID NO.:

PDRP8005-8110-25-203-0035

LEGEND:
0035

O = OPEN VALVE S= SHUTDOWN MACHINERY ESD = EMERGENCY SHUTDOWN ST= START THE MACHINERY
A = ALARM

Skimmed Oil Transfer Pump

GENERAL NOTES:
DESCRIPTION

1. All instruments tag no.s are preceded by area Unit numbers 2. Vendor to confirm Shutdown actions. 3. Trips associated with F&G causes and inherent equipment protect will be provided seperately. 4. All P &ID no.s Preceded by PDRP8005-8110-25-203. SPECIFIC NOTES: 1. At high level one Pump will start. In the event of failure of duty pump to start, the standby pump will start at high-high level. O3 2. At low level, the running pump shall stop. An additional trip at low-low level has been provided for safety.
O3

Skimmed Oil Transfer Pump

EFFECT

0035

C = CLOSE VALVE

P&ID NO.

TAG NO.

CAUSE
REV. NO TAG NO. LZALL-0115 LZAHH0115 LIAH-0116 O3 LIAHH-0116 LIAL-0116 FICAH-0028 FICAL-0028 O3 LIAHH-0115 XZV-5002 O3 TIAH-0116 2 NOTES 2 1 1 Service On Sump 203-V-003 On Sump 203-V-003 On Sump 203-V-003 DELETD On Sump 203-V-003 On Pump (203-P-006) Discharge On Pump (203-P-006) Discharge DELETED Closure of ESD Valve at Outlet of Tank 203-TK-017 On Sump 203-V-003 P&ID NO. 0035 0036 0035 0035 0035 0035 0035 0035 0009 Interlock No. IZ-0017 IZ-0056 IZ-0019 IZ-0018 IZ-0020 SET UNITS POINT

S ST ST

P-026B

P-026A

S ST ST

BOOT OPERATOR: IOT UTKAL ENERGY SERVICES LTD EPC CONTRACTOR:

O3 O2 O1 Rev.

13.09.2011 21.04.2011 01.09.2010

Date

RE-ISSUED FOR COMMENTS RE-ISSUED FOR COMMENTS ISSUED FOR COMMENTS Issue Description

AVS AVS MA Prpd.by

SHV PKD NT Vrfd.by

SHV SHV SHV Appr. By

CAUSE AND EFFECT CHART


IOT Infrastructure & Energy Services Ltd ENGINEERING ASSOCIATE: DOCUMENT NUMBER PDRP8005-8110-24-203-0001 JOB CODE Sheet 5 of 5 PDRP8005

ALARM A A A A A A A A