Roof System KS1000 RW Range

3.

Product Data
Application
The KS1000 RW is a trapezoidal form roof system with
a standard fastening method (a through x), which is
suitable for all building applications, where the roof slope
is:
Higher than 4 (7%) for roofs with one panel in the
slope direction;
Higher than 6 (10%) for roofs with two or more panels
in the slope direction.
The KS1000 RW panel is universal and can be also used
for wall cladding.

Dimensions & Weight

Internal Facing Prole

d core thickness (mm)

25

D overall dimension (mm)

sheet 0.5/0.4 mm

Product Tolerances

4 mm
6 mm
8 mm

100

120

60

75

85

95

105

115

135

155

9.34

9.94

10.34

10.74

11.14

11.54

12.34

13.14

Panel width

3 mm

Thickness
Panel thickness d 50 mm
Panel thickness 50 mm < d < 100 mm
+3 mm
Panel thickness d 100 mm
+3 mm
Squarness of the cut end 0.5% of the panel width.
Panel bow (1 + 2) / 2 10 mm

Please contact local Kingspan Technical department.

Panel End Lap Cut Back

2 mm
2 mm
3 mm

The standard panel length is between 2 and 14.5


meters. It is possible to deliver panels shorter than 2 m
and longer than 14.5 m, but this should be discussed
with Kingspan rst.

If the project requires panels to be connected in the


direction of the roof slope, the panels must have an

overlap. Depending on the overlap length, the insulating


core at the panel end under the overlap must be
removed during mounting. For these situations, we can

deliver panels with cut backs already made. These panels


are normally delivered with a cut back up to 250 mm, but

other cutback lengths are possible (see below). Cut backs


for all types
of panels (roof, wall, PUR, mineral wool) can

be ordered.
The minimum length of a panel on which a cut back
can normally be made is 2,700 mm. Cut backs on shorter
length panels are possible by special arrangement.

CUT BACK 1
CUT BACK 2
CUT BACK 3

can be divided into three types:


Panel cut-backs for roong and wall
panels

80

Certication Reference

Panel length
For panel length under 6 m
Panel length is equal or over 6 m and under 12 m
Panel length is equal or over 12 m

Available Lengths

70

60

Weight (kg/m2)

50

40

unseparated cut backs


separated cut back with insulation not
removed
separated cut back with insulation removed

50250 mm
50, 80, 150, 200 and 250 mm
50, 80, 150, 200 and 250 mm

3.01

03_uk.indd 1

30.5.2005 10:48:23

3.

Roof System KS1000 RW


Product Data
5. Celestia (by Corus)
Celestia is a metallic-nish cladding steel with a
120 m (nominal thickness) high performance Plastisol
coating. The standard product has a high performance
polyester coating on the reverse side. The metallic nish
captures light and movement, giving depth and life to
the cladding surfaces.

Internal Coating Options


1. Polyester

Steel
Galvanic protection options
1. Hot-dip zinc coated steel with a total of 275 g/m2 of
zinc, according to EN 10147:2000. This can be finished
with a number of coatings polyester, PVDF, Plastisol
and Foodsafe finishes.
2. Galvatite coated steel in accordance with EN 10147 for
Celestia finishes.
3. Galvalloy (hot-dip coated with eutectic alloy of approx.
95% Zn, 5% Al and other elements) in accordance with
EN 10214 for coated steel HPS200.
Substrate thicknesses
Standard external sheet thickness 0.50 mm.
Standard internal sheet thickness 0.40 mm.
Other thicknesses are available by arrangement with
Kingspan.

Polyester coating with a nominal thickness of 15 m.


The standard colour is grey white, (similar RAL 9002).
2. Lining enamel
Lining enamel with a nominal thickness of 22 m with
a white nish.
3. Foodsafe
The surface of this 150 m thick polymer coating
is non-toxic and resistant to mould, durable and easy
to clean. It is chemically inert and safe for continuous
contact with unpacked food. The standard colour is
white. Consult Kingspan about the availability of other
colours.
Other coating systems are available by discussion with
Kingspan.
Plain and coloured aluminium is available on a project
specic basis. Contact Kingspan Technical Services.

External Coating Options

Insulation Core

1. Standard Polyester PES

Rigid polyurethane closed-cell foam is the standard


insulating core used.

Polyester is a universal, economic coating system


suitable for exterior and interior applications. The nominal
coating thickness is 25 m.
2. PVDF
PVDF oers unequalled colour and gloss retention and
good corrosion resistance. The nominal coating thickness
is 25 m. It can be used in climates with extremely high
UV radiation combined with extreme temperatures and
relative humidity. The standard colour range includes
metallic silver.

It is made to a non-deleterious specication and is


CFC/HCFC free.

Seals
Factory Applied Side Joint Tape
All side joints have factory applied anti-condensation
tape.

3. HPS200 (by Corus)


HPS200 is a premium architectural coating system,
tested in the laboratory and on site in severe climates,
for use worldwide. Its tough, 200 m (nominal thickness)
coating has the unique Scintilla nish and is available
in bright or subtle hues, providing architects with an
extensive palette of colours.
4. Plastisol 200 m
Plastisol is a high performance coating system with a
grain nish and a nominal thickness of 200 m. Typical
properties of Plastisol are excellent abrasion, high
corrosion resistance, excellent exibility and therefore
very good scratch resistance.

3.02

03_uk.indd 2

30.5.2005 10:48:24

Roof System KS1000 RW

3.

Product Data
Performance

Guarantees & Warranties

Thermal Insulation

Kingspan will provide external coating and product


guarantees on a project by project basis.
U value (W/m2K)

Panel Thickness
(mm)

HCFC Free
= 0.022

25
40
50
60
70
80
100
120

0.77
0.50
0.41
0.35
0.30
0.26
0.21
0.18

U Thermal transmittance W/m2K


Long-term Thermal conductivity W/mK

Packing
Standard packing road transportation
KS1000 RW panels are stacked weather side to weather
side (to minimise palette height). The top, bottom, sides
and ends are protected with foam and timber packing
and the entire palette is wraped in plastic.
The number of panels in each pack depends on panel
thickness and length. The table below is shown as a
guide. Quantities are reduced for exceptionally long
panels. Typical palette height is 1,100 mm.
Maximum palette weight is 3,500 kg.

Biological
Kingspan insulated sandwich panels are immune to
attack from mould, fungi, mildew and vermin. No urea
formaldehyde is used in the construction, and the panels
are non-deleterious.
Fire
KS1000 RW insulated sandwich panels have been
tested and approved and comply with National Building
Regulations and Norms. The panels do not propagate re
spread.
Panel Thickness
(mm)

Fire rating

25/60
40/75
50/85
60/95
70/105
80/115
100/135
120/155

For detailed information please contact local


Kingspan Technical department.

Panel core
thickness
(mm)

25

40

50

60

70

80

100

120

Number of
panels in
package

23

17

15

13

11

Delivery
All deliveries (unless indicated otherwise) are by road
transport to project site. O loading is the responsibility
of the client.

Site Installation
Site assembly instructions are available from Kingspan.
Kingspan will arrange training of the site tters and
supervisors if requested.

Acoustics
All KS1000 RW panels have a single gure weighted
sound reduction Rw = 25 dB.

Building Regulations
Kingspan KS1000 RW insulated sandwich panels
conform to the National Building Regulations and
standards.

Quality
Kingspan insulated sandwich panels are manufactured
from the highest quality materials, using state of the
art production equipment to rigorous quality control
standards, complying with ISO9001:2000 standards,
ensuring long term reliability and service life.

3.03

03_uk.indd 3

30.5.2005 10:48:25

3.

Roof System KS1000 RW


Load Span Table (kN/m2) max. sag L/100
Outer sheet

type
tn(mm)
colour

Panel thickness
(mm)

RW
0.5
1

Inner sheet

1.5

type
tn(mm)

MB
0.4

2.5

Span (m)
3.5
4

4.5

5.5

0.47
1.11
0.60
1.35
0.73
1.54
0.87
1.73
1.00
1.92
1.29
2.31

0.37
0.90
0.48
1.04
0.59
1.18
0.71
1.33
0.83
1.48
1.08
1.78

0.28
0.71
0.38
0.83
0.48
0.94
0.58
1.06
0.69
1.18
0.90
1.41

0.25
0.68
0.36
0.77
0.47
0.87
0.57
0.96
0.77
1.16

0.23
0.65
0.32
0.73
0.42
0.81
0.64
0.97

0.13
0.55
0.21
0.62
0.29
0.69
0.47
0.83

0.37
0.51
0.48
0.61
0.57
0.63
0.65
0.69
0.83
0.92
0.93
1.06

0.29
0.44
0.38
0.52
0.45
0.56
0.51
0.61
0.69
0.75
0.79
0.90

0.23
0.40
0.31
0.46
0.36
0.50
0.42
0.55
0.57
0.67
0.71
0.81

0.18
0.37
0.25
0.41
0.29
0.46
0.34
0.50
0.47
0.59
0.63
0.73

0.14
0.33
0.20
0.38
0.23
0.42
0.26
0.46
0.36
0.51
0.51
0.67

0.37
0.66
0.48
0.74
0.59
0.81
0.71
0.88
0.83
1.05
1.08
1.18

0.29
0.58
0.38
0.65
0.48
0.70
0.58
0.77
0.69
0.90
0.90
1.01

0.23
0.50
0.31
0.57
0.39
0.66
0.48
0.72
0.57
0.82
0.77
0.93

0.18
0.46
0.25
0.51
0.32
0.61
0.40
0.65
0.48
0.72
0.65
0.85

0.14
0.41
0.20
0.49
0.27
0.54
0.34
0.59
0.41
0.64
0.56
0.80

SINGLE SPAN
25
40
50
60
70
80
100
120

Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
amin (mm)

1.74
3.64
1.96
4.27
2.19
4.92
2.41
5.58
2.64
6.25
3.10
7.59

1.15
2.50
1.35
3.03
1.55
3.57
1.75
4.13
1.95
4.69
2.36
5.84

0.83
1.84
1.00
2.27
1.17
2.72
1.35
3.18
1.53
3.65
1.89
4.59

0.62
1.41
0.76
1.76
0.92
2.11
1.07
2.36
1.23
2.63
1.55
3.15

40
DOUBLE SPAN

25
40
50
60
70
80
100
120

Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
a; bmin (mm)

1.74
2.19
1.96
2.29
2.19
2.47
2.41
2.65
2.64
2.87
3.10
2.98

1.15
1.38
1.35
1.50
1.55
1.63
1.75
1.70
1.95
1.96
2.36
2.35

0.83
0.98
1.00
1.10
1.17
1.18
1.35
1.27
1.53
1.52
1.70
1.80

0.62
0.76
0.76
0.84
0.92
0.91
1.07
1.07
1.23
1.31
1.34
1.46

0.47
0.63
0.60
0.69
0.73
0.75
0.83
0.84
1.00
1.03
1.11
1.21

40
TRIPLE SPAN

25
40
50
60
70
80
100
120

Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
Pressure (kN/m2)
Suction (kN/m2)
a; bmin (mm)

1.74
2.67
1.96
2.72
2.19
2.88
2.41
3.02
2.64
3.34
3.10
3.65

1.15
1.67
1.35
1.84
1.55
1.95
1.75
2.01
1.95
2.30
2.36
2.40

0.83
1.26
1.00
1.36
1.17
1.46
1.35
1.50
1.53
1.78
1.89
2.07

0.62
0.97
0.76
1.05
0.92
1.17
1.07
1.32
1.23
1.52
1.55
1.65

0.47
0.78
0.60
0.88
0.73
0.98
0.87
1.05
1.00
1.21
1.29
1.39

40

Notes:
The calculations have been made in accordance with the European standards and recommendations contained in ECCS 66 1991.
The table contains allowed standard values for the variable loading of the given span.
Consult with Kingspan for the table values of other profiles, as well as dark colors.
Allowed deflection considered in the table values is L/100. If required otherwise, special calculations must be made.
The table is to be applied for common, short, variable loads (for instance wind) and considers the influence of common winter and summer
temperatures. If other ways of loading (long-term loads, special thermal load in for instance cold stores) are applicable, special calculations must be
made.
The minimum intermediate support width bmin has been determined assuming one screw of 6.3 mm diameter is used for the support width. If arranged
otherwise, this width is to be adjusted accordingly.
The above-mentioned calculations apply to panels with standard steel skin strength specification of the fv = 220 MPa.
The minimum end support with amin is 40 mm.

3.04

03_uk.indd 4

30.5.2005 10:48:26

Roof System KS1000 RW

3.

Fastener Selection SFS intec


Product: STEEL KS1000 RW Roof System, Fixing position: CROWN (19 mm diameter sealing washer)

Building Classication
Support
Steel
Thickness
(mm)

Insulation
Core
Thickness
(mm)

Carbon Steel
Case Hardened

Austenitic Stainless
Steel, Grade 304

Self-Drilling Fasteners to Steel Structure

Carbon Steel
Case Hardened

Austenitic Stainless
Steel, Grade 304

Self-Tapping Fasteners to Steel Structure

SFS intec Code Number


Cold Rolled
min. 1.5
max. 5.0

Hot Rolled
min. 3.0
max. 14.0

25

SDT5-A19-5.5 97

SXC5-S19-5.5 107

TDA-T-T19-6.5 90*

TDA-S-S19-6.5 90*

40

SDT5-A19-5.5 112

SXC5-S19-5.5 107

TDA-T-T19-6.5 100*

TDA-S-S19-6.5 100*

50

SDT5-A19-5.5 112

SXC5-S19-5.5 130

TDA-T-T19-6.5 115*

TDA-S-S19-6.5 100*

60

SDT5-A19-5.5 137

SXC5-S19-5.5 130

TDA-T-T19-6.5 115*

TDA-S-S19-6.5 115*

70

SDT5-A19-5.5 137

SXC5-S19-5.5 154

TDA-T-T19-6.5 127*

TDA-S-S19-6.5 115*

80

SDT5-A19-5.5 137

SXC5-S19-5.5 154

TDA-T-T19-6.5 152*

TDA-S-S19-6.5 152*

100

SDT5-A19-5.5 182

SX5-S19-5.5 207*

TDA-T-T19-6.5 178*

TDA-S-S19-6.5 178*
TDA-S-S19-6.5 200*

120

SDT5-A19-5.5 226

SX5-S19-5.5 207*

TDA-T-T19-6.5 200*

25

SDT14-A19-5.5 93

SXC14-S19-5.5 114

TDB-T-T19-6.3 90*

TDB-S-S19-6.3 90*

40

SDT14-A19-5.5 113

SXC14-S19-5.5 114

TDB-T-T19-6.3 100*

TDB-S-S19-6.3 100*

50

SDT14-A19-5.5 132

SXC14-S19-5.5 134

TDB-T-T19-6.3 115*

TDB-S-S19-6.3 115*

60

SDT14-A19-5.5 132

SXC14-S19-5.5 134

TDB-T-T19-6.3 115*

TDB-S-S19-6.3 115*

70

SDT14-A19-5.5 132

SXC14-S19-5.5 134

TDB-T-T19-6.3 127*

TDB-S-S19-6.3 127*

80

SDT14-A19-5.5 132

SXC14-S19-5.5 165

TDB-T-T19-6.3 152*

TDB-S-S19-6.3 152*

100

SDT14-A19-5.5 160

SX12-S19-5.5 191*

TDB-T-T19-6.3 178*

TDB-S-S19-6.3 178*

120

SDT14-A19-5.5 186

SX12-S19-5.5 191*

TDB-T-T19-6.3 200*

TDB-S-S19-6.3 200*

* Fasteners without dual thread + saddle washers

Product: STEEL KS1000 RW Roof System, Fixing position: VALLEY (19 mm diameter sealing washer)

Building Classication
Support
Steel
Thickness
(mm)

Insulation
Core
Thickness
(mm)

Carbon Steel
Case Hardened

Austenitic Stainless
Steel, Grade 304

Self-Drilling Fasteners to Steel Structure

Carbon Steel
Case Hardened

Austenitic Stainless
Steel, Grade 304

Self-Tapping Fasteners to Steel Structure

SFS intec Code Number


Cold Rolled
min. 1.5
max. 5.0

Hot Rolled
min. 3.0
max. 14.0

25

SDT5-A19-5.5 55

SXC5-S19-5.5 62

40

SDT5-A19-5.5 67

SXC5-S19-5.5 77

50

SDT5-A19-5.5 77

SXC5-S19-5.5 87

60

SDT5-A19-5.5 97

SXC5-S19-5.5 107

70

SDT5-A19-5.5 97

SXC5-S19-5.5 107

80

SDT5-A19-5.5 112

SXC5-S19-5.5 107

100

SDT5-A19-5.5 137

SXC5-S19-5.5 130

120

SDT5-A19-5.5 162

SXC5-S19-5.5 154

25

SDT14-A19-5.5 64

40

SDT14-A19-5.5 76

SXC14-S19-5.5 76

50

SDT14-A19-5.5 93

SXC14-S19-5.5 95

60

SDT14-A19-5.5 113

SXC14-S19-5.5 95

70

SDT14-A19-5.5 113

SXC14-S19-5.5 114

80

SDT14-A19-5.5 113

SXC14-S19-5.5 134

100

SDT14-A19-5.5 132

SXC14-S19-5.5 130

120

SDT14-A19-5.5 160

SXC14-S19-5.5 165

3.05

03_uk.indd 5

30.5.2005 10:48:28

3.

Roof System KS1000 RW


Fastener Selection SFS intec
Product: CONCRETE KS1000 RW Roof System, Fixing position: CROWN (19 mm diameter sealing washer)

Building Classication
Support
Concrete

Insulation Core
Thickness
(mm)

Carbon Steel Case Hardened


Self-Tapping Fasteners to Concrete Purlins
SFS intec Code Number

25

TBT-T-A19-6.3 110

TI-A19-6.3 115*

40

TBT-T-A19-6.3 110

TI-A19-6.3 115*

50

TBT-T-A19-6.3 120

TI-A19-6.3 125*

60

TBT-T-A19-6.3 130

TI-A19-6.3 135*

70
80
100

TI-A19-6.3 155*
TI-A19-6.3 155*

TI-A19-6.3 175*

120

TI-A19-6.3 195*

* Fasteners without dual thread + saddle washers

Product: CONCRETE KS1000 RW Roof System, Fixing position: VALLEY (19 mm diameter sealing washer)

Building Classication
Support
Concrete

Carbon Steel Case Hardened

Insulation Core
Thickness (mm)

Self-Tapping Fasteners to Concrete Purlins


SFS intec Code Number

25

40

TBT-T-A19-6.3 110

TI-A19-6.3 115*

50

TBT-T-A19-6.3 120

TI-A19-6.3 125*

60

TBT-T-A19-6.3 130

70
80
100
120

TI-A19-6.3 135*
TI-A19-6.3 155*

TI-A19-6.3 155*
TI-A19-6.3 175*

* Fasteners without dual thread + saddle washers

3.06

03_uk.indd 6

30.5.2005 10:48:30

Roof System KS1000 RW

3.

Fastener Selection SFS intec


Product: TIMBER KS1000 RW Roof System, Fixing position: CROWN (19 mm diameter sealing washer)

Building Classication
Support
Timber

Insulation
Core
Thickness
(mm)

Carbon Steel
Case Hardened

Austenitic Stainless
Steel, Grade 304

Self-Drilling Fasteners to Timber Structure

Carbon Steel
Case Hardened

Austenitic Stainless
Steel, Grade 304

Self-Tapping Fasteners to Timber Structure

SFS intec Code Number


25

SDTW-A19-6,5 115

SXCW-S19-6,5 115

TDA-T-T19-6.5 100*

TDA-S-S19-6.5 100*

40

SDTW-A19-6,5 125

SXCW-S19-6,5 135

TDA-T-T19-6.5 115*

TDA-S-S19-6.5 115*

50

SDTW-A19-6,5 125

SXCW-S19-6,5 155

TDA-T-T19-6.5 127*

TDA-S-S19-6.5 127*

60

SDTW-A19-6,5 135

SXCW-S19-6,5 155

TDA-T-T19-6.5 152*

TDA-S-S19-6.5 152*

70

SXCW-S19-6,5 185

TDA-T-T19-6.5 152*

TDA-S-S19-6.5 152*

80

SXCW-S19-6,5 185

TDA-T-T19-6.5 178*

TDA-S-S19-6.5 178*

SXCW-S19-6,5 185

TDA-T-T19-6.5 178*

TDA-S-S19-6.5 178*

TDA-T-T19-6.5 200*

TDA-S-S19-6.5 200*

100

120
* Fasteners without dual thread + saddle washers

Product: TIMBER KS1000 RW Roof System, Fixing position: VALLEY (19 mm diameter sealing washer)

Support
Timber

Insulation
Core
Thickness
(mm)

Building Classication
Carbon Steel Case Hardened

Austenitic Stainless Steel, Grade 304

Self-Drilling Fasteners to Timber Structure


SFS intec Code Number

25

40

SDTW-A19-6,5 75

SXCW-S19-6,5 105

50

SDTW-A19-6,5 115

SXCW-S19-6,5 105

60

SDTW-A19-6,5 115

SXCW-S19-6,5 115

70

SDTW-A19-6,5 115

SXCW-S19-6,5 135

80

SDTW-A19-6,5 125

SXCW-S19-6,5 135

100

SDTW-A19-6,5 135

SXCW-S19-6,5 155

120

SXCW-S19-6,5 185

3.07

03_uk.indd 7

30.5.2005 10:48:31

3.

Roof System KS1000 RW


Fastener Selection EJOT
Product: STEEL KS1000 RW Roof System, Fixing position: CROWN (19 mm diameter sealing washer and storm
washer 32/25)

Support
Steel
Thickness
(mm)

Cold Rolled
min. 1.5
max. 5.0

Hot Rolled
min. 3.0
max. 12.0

EJOT Code Numbers

Insulation
Core
Thickness
(mm)

Carbon Steel
Case Hardened

25

JT2-D-6H-5.5 82 V19

JT3-D-6H-5.5 107 E19

JZ2-6.3 80 V19*

JZ3-6.3 80 E19*

40

JT2-D-6H-5.5 102 V19

JT3-D-6H-5.5 107 E19

JZ2-6.3 100 V19*

JZ3-6.3 100 E19*

50

JT2-D-6H-5.5 122 V19

JT3-D-6H-5.5 127 E19

JZ2-6.3 125 V19*

JZ3-6.3 115 E19*

60

JT2-D-6H-5.5 122 V19

JT3-D-6H-5.5 127 E19

JZ2-6.3 125 V19*

JZ3-6.3 125 E19*

70

JT2-D-6H-5.5 152 V19

JT3-D-6H-5.5 147 E19

JZ2-6.3 150 V19*

JZ3-6.3 135 E19*

80

JT2-D-6H-5.5 152 V19

JT3-D-6H-5.5 147 E19

JZ2-6.3 150 V19*

JZ3-6.3 150 E19*

100

JT2-D-6H-5.5 172 V19

JT3-D-6H-5.5 167 E19

JZ2-6.3 175 V19*

JZ3-6.3 175 E19*

120

JT2-D-6H-5.5 192 V19

JT3-D-6H-5.5 197 E19

JZ2-6.3 175 V19*

JZ3-6.3 175 E19*

25

JT2-D-12H-5.5 95 V19

JT3-D-12H-5.5 115 E19

JZ2-6.3 80 V19*

JZ3-6.3 80 E19*

40

JT2-D-12H-5.5 125 V19

JT3-D-12H-5.5 115 E19

JZ2-6.3 100 V19*

JZ3-6.3 100 E19*

50

JT2-D-12H-5.5 125 V19

JT3-D-12H-5.5 135 E19

JZ2-6.3 115 V19*

JZ3-6.3 115 E19*

60

JT2-D-12H-5.5 155 V19

JT3-D-12H-5.5 135 E19

JZ2-6.3 125 V19*

JZ3-6.3 125 E19*

70

JT2-D-12H-5.5 155 V19

JT3-D-12H-5.5 155 E19

JZ2-6.3 150 V19*

JZ3-6.3 135 E19*

80

JT2-D-12H-5.5 155 V19

JT3-D-12H-5.5 155 E19

JZ2-6.3 150 V19*

JZ3-6.3 150 E19*

100

JT2-D-12H-5.5 195 V19

JT3-D-12H-5.5 175 E19

JZ2-6.3 175 V19*

JZ3-6.3 175 E19*

120

JT2-D-12H-5.5 195 V19

JT3-D-12H-5.5 195 E19

JZ2-6.3 200 V19*

JZ3-6.3 200 E19*

Austenitic Stainless Steel,


Grade 304

Self-Drilling Fasteners to Steel Structure

Carbon Steel
Case Hardened

Austenitic Stainless Steel,


Grade 304

Self-Tapping Fasteners to Steel Structure

For colorfast integral plastic heads, prefix code with C19 and omit washer code (V19 E19).
* Fasteners without dual thread

Product: STEEL KS1000 RW Roof System, Fixing position: VALLEY (19 mm diameter sealing washer)
Support
Steel
Thickness
(mm)

Cold Rolled
min. 1.5
max. 5.0

Hot Rolled
min. 3.0
max. 12.0

EJOT Code Numbers

Insulation
Core
Thickness
(mm)

Carbon Steel
Case Hardened

25

JZ2-6.3 50 V19*

JZ3-6.3 50 E19*

40

JT2-D-6H-5.5 62 V19

JT3-D-6H-5.5 67 E19

JZ2-6.3 64 V19*

JZ3-6.3 64 E19*

50

JT2-D-6H-5.5 82 V19

JT3-D-6H-5.5 87 E19

JZ2-6.3 80 V19*

JZ3-6.3 80 E19*

60

JT2-D-6H-5.5 82 V19

JT3-D-6H-5.5 107 E19

JZ2-6.3 80 V19*

JZ3-6.3 80 E19*

70

JT2-D-6H-5.5 102 V19

JT3-D-6H-5.5 107 E19

JZ2-6.3 90 V19*

JZ3-6.3 90 E19*

80

JT2-D-6H-5.5 102 V19

JT3-D-6H-5.5 127 E19

JZ2-6.3 100 V19*

JZ3-6.3 100 E19*

100

JT2-D-6H-5.5 122 V19

JT3-D-6H-5.5 147 E19

JZ2-6.3 125 V19*

JZ3-6.3 125 E19*

120

JT2-D-6H-5.5 152 V19

JT3-D-6H-5.5 167 E19

JZ2-6.3 150 V19*

JZ3-6.3 150 E19*

25

JZ2-6.3 50 V19*

JZ3-6.3 50 E19*

40

JT2-D-12H-5.5 80 V19

JT3-D-12H-5.5 75 E19

JZ2-6.3 64 V19*

JZ3-6.3 64 E19*

50

JT2-D-12H-5.5 95 V19

JT3-D-12H-5.5 95 E19

JZ2-6.3 80 V19*

JZ3-6.3 80 E19*

60

JT2-D-12H-5.5 95 V19

JT3-D-12H-5.5 115 E19

JZ2-6.3 80 V19*

JZ3-6.3 80 E19*

70

JT2-D-12H-5.5 125 V19

JT3-D-12H-5.5 115 E19

JZ2-6.3 90 V19*

JZ3-6.3 90 E19*

80

JT2-D-12H-5.5 125 V19

JT3-D-12H-5.5 135 E19

JZ2-6.3 100 V19*

JZ3-6.3 100 E19*

100

JT2-D-12H-5.5 155 V19

JT3-D-12H-5.5 155 E19

JZ2-6.3 125 V19*

JZ3-6.3 125 E19*

120

JT2-D-12H-5.5 155 V19

JT3-D-12H-5.5 175 E19

JZ2-6.3 150 V19*

JZ3-6.3 150 E19*

Austenitic Stainless Steel,


Grade 304

Self-Drilling Fasteners to Steel Structure

Carbon Steel
Case Hardened

Austenitic Stainless Steel,


Grade 304

Self-Tapping Fasteners to Steel Structure

3.08

03_uk.indd 8

30.5.2005 10:48:33

Roof System KS1000 RW

3.

Fastener Selection EJOT


Product: CONCRETE KS1000 RW Roof System, Fixing position: CROWN (19 mm diameter sealing washer)

EJOT Code Numbers

Insulation Core
Thickness
(mm)

Concrete, Full Brick Masonry

25

SDF-KB-8 120V (E)

SDP-KB-8 180V (E)

40

SDF-KB-8 140V (E)

SDP-KB-8 200V (E)

50

SDF-KB-8 140V (E)

SDP-KB-8 220V (E)

60

SDF-KB-8 160V (E)

70

SDF-KB-8 160V (E)

80

SDF-KB-8 180V (E)

100

SDF-KB-8 200V (E)

120

SDF-KB-8 200V (E)

25

SDF-KB-10 120V (E)

SDF-KB-10L 160V (E)

SDP-KB-10S 140V (E)

40

SDF-KB-10 140V (E)

SDF-KB-10L 180V (E)

SDP-KB-10S 160V (E)

50

SDF-KB-10 140V (E)

SDF-KB-10L 180V (E)

SDP-KB-10S 160V (E)

60

SDF-KB-10 160V (E)

SDF-KB-10L 200V (E)

SDP-KB-10S 180V (E)

70

SDF-KB-10 180V (E)

SDF-KB-10L 220V (E)

SDP-KB-10S 180V (E)

80

SDF-KB-10 180V (E)

SDF-KB-10L 220V (E)

SDP-KB-10S 200V (E)

100

SDF-KB-10 200V (E)

SDP-KB-10S 220V (E)

120

SDF-KB-10 220V (E)

Type of Masonry Material


Hollow Brick Masonry

Gas Concrete

SDP-KB-8 220V (E)


SDP-KB-8 220V (E)

All fasteners must be used with the correct sealing washer.


Storm washers and 16 mm dia sealing washers are recommended with these fasteners for fixing through crown.

Product: CONCRETE KS1000 RW Roof System, Fixing position: VALLEY (19 mm diameter sealing washer)

EJOT Code Numbers

Insulation Core
Thickness
(mm)

Concrete, Full Brick Masonry

25

SDF-KB-8 80V (E)

SDP-KB-8 160V (E)

40

SDF-KB-8 100V (E)

SDP-KB-8 160V (E)

50

SDF-KB-8 100V (E)

SDP-KB-8 180V (E)

60

SDF-KB-8 120V (E)

70

SDF-KB-8 120V (E)

80

SDF-KB-8 140V (E)

SDP-KB-8 200V (E)

100

SDF-KB-8 160V (E)

SDP-KB-8 220V (E)

120

SDF-KB-8 160V (E)

25

SDF-KB-10 80V (E)

SDF-KB-10L 120V (E)

SDP-KB-10S 100V (E)

40

SDF-KB-10 100V (E)

SDF-KB-10L 140V (E)

SDP-KB-10S 120V (E)

50

SDF-KB-10 100V (E)

SDF-KB-10L 140V (E)

SDP-KB-10S 120V (E)

60

SDF-KB-10 120V (E)

SDF-KB-10L 160V (E)

SDP-KB-10S 140V (E)

70

SDF-KB-10 120V (E)

SDF-KB-10L 160V (E)

SDP-KB-10S 140V (E)

80

SDF-KB-10 140V (E)

SDF-KB-10L 180V (E)

SDP-KB-10S 160V (E)

100

SDF-KB-10 160V (E)

SDF-KB-10L 200V (E)

SDP-KB-10S 180V (E)

120

SDF-KB-10 180V (E)

SDF-KB-10L 220V (E)

SDP-KB-10S 200V (E)

Type of Masonry Material


Hollow Brick Masonry

Gas Concrete

SDP-KB-8 180V (E)


SDP-KB-8 200V (E)

SDP-KB-8 220V (E)

All fasteners must be used with the correct sealing washer.

3.09

03_uk.indd 9

30.5.2005 10:48:35

3.

Roof System KS1000 RW


Fastener Selection EJOT
Product: TIMBER KS1000 RW Roof System, Fixing position: CROWN (16 mm diameter sealing washer and storm
washer 32/25)

Support
Timber

EJOT Code Numbers

Insulation
Core
Thickness
(mm)

Carbon Steel
Case Hardened

25

JA2-6.3 100 V19*

JA3-6.3 100 E19*

40

JA2-6.3 125 V19*

JA3-6.3 125 E19*

50

JA2-6.3 125 V19*

JA3-6.3 125 E19*

60

JA2-6.3 150 V19*

JA3-6.3 150 E19*

70

JA2-6.3 150 V19*

JA3-6.3 150 E19*

80

JA2-6.3 150 V19*

JA3-6.3 150 E19*

100

JA2-6.3 175 V19*

JA3-6.3 175 E19*

120

JA2-6.3 200 V19*

JA3-6.3 200 E19*

Austenitic Stainless Steel, Grade 304


Self-Tapping Fasteners to Timber Structure

For colorfast integral plastic heads, prefix code with C19 and omit washer code (V19 E19).
* Fasteners without dual thread

Product: TIMBER KS1000 RW Roof System, Fixing position: VALLEY (19 mm diameter sealing washer)

Support
Timber

EJOT Code Numbers

Insulation
Core
Thickness
(mm)

Carbon Steel
Case Hardened

25

JA2-6.3 75 V19*

JA3-6.3 75 E19*

40

JA2-6.3 90 V19*

JA3-6.3 90 E19*

50

JA2-6.3 90 V19*

JA3-6.3 90 E19*

60

JA2-6.3 100 V19*

JA3-6.3 100 E19*

70

JA2-6.3 125 V19*

JA3-6.3 125 E19*

80

JA2-6.3 125 V19*

JA3-6.3 125 E19*

100

JA2-6.3 150 V19*

JA3-6.3 150 E19*

120

JA2-6.3 175 V19*

JA3-6.3 175 E19*

Austenitic Stainless Steel, Grade 304


Self-Tapping Fasteners to Timber Structure

For colorfast integral plastic heads, prefix code with C19 and omit washer code (V19 E19).
* Fasteners without dual thread

3.10

03_uk.indd 10

30.5.2005 10:48:36

Overall Panel
Thickness (D)
60
75
85
95
105
115
135
155

Overall Panel Width

All dimensions in milimetres

Note:
External sheet thickness of 0.5 mm to 0.9 mm
Internal sheet thickness of 0.4 mm to 0.9 mm

25
40
50
60
70
80
100
120

Insulation Core (d)

Available Panel Thicknesses

03_uk.indd 11

Roof System KS1000 RW


3.

Panel Dimensions

3.11

30.5.2005 10:48:37

3.

Roof System KS1000 RW


Recommended Fastener Locations
Valley Positions
Standard*

Ridge / Eaves*

High Wind Load* (depending on wind loading / building location & size)

Crown Positions
Standard*

Ridge / Eaves*

* Number of fasteners to be specified by structural / static engineer

3.12

03_uk.indd 12

30.5.2005 10:48:39

Roof System KS1000 RW

3.

Recommended Fastener Locations


Roof Purlin System Options
Hot Rolled

Multibeam Cold Formed

Zed Cold Formed

Concrete structure

Concrete structure

Wooden structure

Steel concrete structure + Halfen


HTU

Purlin Design Service


Kingspan Technical Services Department can provide a
roof purlin design service on a project basis.

3.13

03_uk.indd 13

30.5.2005 10:48:41

3.

Roof System KS1000 RW


Side & End Lap Detail
D10.1. Panel Side Lap

D11.1. Panel End Lap

Note:
P Cut back dimensions:
for roof slope > 10% 200 mm (supplied / delivered to site with cut
backs)
for roof slope 10% 250 mm (supplied / delivered to site with cut
backs)
Maximum cut backs available on panels from Kingspan is 250 mm.
a according to structural / static requirements

3.14

03_uk.indd 14

30.5.2005 10:48:43

Roof System KS1000 RW

3.

Ridge & Gable Detail


D1.1. Ridge

Note:
a according to structural / static requirements
P12 for roof slope 10% 4 pcs / m
> 10% 2 pcs/m

D2.1. Gable

3.15

03_uk.indd 15

30.5.2005 10:48:44

3.

Roof System KS1000 RW


Mono Ridge & Parapet Detail
D3.1. Mono Ridge

D4.1. Side Wall Parapet


Note:
a according to structural / static requirements
P12 for roof slope 10% 4 pcs / m
> 10% 2 pcs/m

3.16

03_uk.indd 16

30.5.2005 10:48:46

Roof System KS1000 RW

3.

Gable Wall Parapet


D5.1. Parapet in Slope Single

D5.16. Parapet in Slope Double

Note:
L/X specify dimension to define
flashing K130 and K105

3.17

03_uk.indd 17

30.5.2005 10:48:48

3.

Roof System KS1000 RW


Eaves Detail
D6.1. Eaves Parapet Gutter Prefabricated

Note:
The prefabricated gutter is recommend to support by 2,000 mm.

D6.2. Eaves Parapet Gutter Membrane Lined


Note:
a
according to structural / static requirements
L
specify dimension to define flashing K135
P33, Z07, K123 when required

3.18

03_uk.indd 18

30.5.2005 10:48:50

Roof System KS1000 RW

3.

Eaves Detail
D6.20. Eaves Gutter Parapet Prefabricated

Note:
a
according to structural / static requirements
X
specify dimension to define flashing K130
The prefabricated gutter is recommend to support by 2,000 mm.

3.19

03_uk.indd 19

30.5.2005 10:48:51

3.

Roof System KS1000 RW


Eaves Detail
D7.1. External Gutter

D7.2. External Gutter

Note:
a
according to structural / static requirements
To order eaves gutters systems and accessory
components please contact Kingspan technical Services
Department.

3.20

03_uk.indd 20

30.5.2005 10:48:53

Roof System KS1000 RW

3.

Eaves Detail
D7.3. External Gutter

D8.1. Valley Gutter

Note:
a, b according to structural / static requirements
The prefabricated gutter is recommend to support by 2,000 mm.
To order eaves gutters systems and accessory components please contact Kingspan technical Services Department.

3.21

03_uk.indd 21

30.5.2005 10:48:56

03_uk.indd 22

The prefabricated gutter is recommend to support by


2,000 mm.
It is necessary to site assemble roof and wall panels in
conjunction with each other to ensure end laps fit together.

Note:
a
according to structural / static requirements

3.
Roof System KS1000 RW

Eaves Detail

D9.1. Curved Eaves with Gutter Roof to Vertical Wall

3.22

30.5.2005 10:48:57

03_uk.indd 23

The prefabricated gutter is recommend to support by


2,000 mm.

Note:
a
according to structural / static requirements

Roof System KS1000 RW


3.

Eaves Detail

D9.2. Curved Eaves with Gutter Roof to Horizontal Wall

3.23

30.5.2005 10:49:00

3.

Roof System KS1000 RW


Roof to Wall Junction
D14.1. Roof to Wall Junction

Note:
a according to structural / static requirements
P12 for roof slope 10% 4 pcs / m
> 10% 2 pcs/m

D15.1. Roof to Wall Junction in Slope

3.24

03_uk.indd 24

30.5.2005 10:49:02

Roof System KS1000 RW

3.

Roof to Brickwork Junction


D16.1. Roof to Brickwork

Note:
a
according to structural / static requirements
P12 for roof slope 10% 4 pcs / m
> 10% 2 pcs/m

D17.1. Roof to Brickwork Junction in Slope

3.25

03_uk.indd 25

30.5.2005 10:49:04

3.

Roof System KS1000 RW


Expansion Joint
D20.1.

Note:
This joint allows for up to 30 mm expansion.

Roof Penetration Extractor Flue


D21.1.

3.26

03_uk.indd 26

30.5.2005 10:49:06

Roof System KS1000 RW

3.

Roof Pipe Extractor Flue

D22.1.

Note:
Complete installation contents:
passage piping packing
sealing material
necessary quantity of fasteners
Piping sleeves for better additional sealing of passages can be ordered
according to diameter of piping.
See to the section of the Accessories or contact Kingspan Technical
Service Department for range of piping sleeves.

3.27

03_uk.indd 27

30.5.2005 10:49:08

3.

Roof System KS1000 RW


Roof / Skylights
D23.1. Ridge Roof / Skylight

Note:
a
according to structural / static requirements
P12 for roof slope 10% 4 pcs / m
> 10% 2 pcs/m

D24.1. Ridge Roof / Skylight Downslope

3.28

03_uk.indd 28

30.5.2005 10:49:09

Roof System KS1000 RW

3.

Roof / Skylights
D25.1. Dome Type Roof / Skylight

Note:
a
according to structural / static requirements

D47.1. Snow-fence

Note:
Fasteners included.
For technical informations see brochure Kingspan Accessories.

3.29

03_uk.indd 29

30.5.2005 10:49:12