You are on page 1of 2

Sealed Lead-Acid Battery

Absorbant Glass Mat (AGM) technology for superior performance. Valve regulated, spill proof construction allows safe operation in any position. Approved for transport by air. D.O.T., I.A.T.A., F.A.A. and C.A.B. certified. U.L. r ecognized under file number MH 20567.

UPG No. 40658

UB12150
Maintenance-Free

Specication
Nominal Voltage Nominal Capacity 20-hr. (0.75A) 10-hr. (1.395A) 5-hr. (2.55A) 1-hr. (9.0A) Approximate Weight Internal Resistance (approx.) Shelf Life (% of normal capacity at 77 F (25 C) 3 Months 6 Months 91% 82% Temperature Dependancy of Capacity 32 F 104 F 77 F 102% 100% 85% 12 volts (6 cells) 15.0 AH 13.95 AH 12.75 AH 9.0 AH 9.2 lbs. (4.2 kg) 18m

12 Months 64% 5 F 65%

Charge Method (Constant Voltage) Cycle Use (Repeating Use) 4.5 A or smaller Initial Current Control Voltage 14.5 - 14.9 V Float Use Control Voltage 13.6 - 13.8 V

Physical Dimensions: in (mm)


151 (5.94)

Terminals
L: 5.95in (151 mm) W: 3.89in (99 mm) H: 3.71in (94 mm) TH: 3.94in (100 mm) Tolerances are +/- 0.04 in. (+/- 1mm) and +/- 0.08 in. (+/- 2mm) for height dimensions. All data subject to change without notice.
0.31 inch tab with a hole for a 4mm screw
94 (3.71) 100 (3.94)

TP
(Thread Pitch)

99 (3.89)

D
12.8 7.8 5.00 4.00

TP
0.70

Discharge Time vs. Discharge Current

Discharge Characteristics

Cell voltage ( V/Cell )

( Minute )
Discharge time

( Hour )

www.upgi.com
1720 Hayden Drive Carrollton, Texas 75006 P 469.892.1122 T 866.892.1122 F 469.892.1123

VR082511

sales@upgi.com

UPG No. 40658

UB12150
Maintenance-Free

Battery Charging Characteristics for Standby Use

Battery Charging Characteristics for Cyclic Use

Cell charge voltage Cell charge voltage ( V/Cell )


Cell charge voltage ( V/Cell ) Charge current (CA) Charge volume (%)

Cell charge voltage


Charge volume

Charge volume (%)

Charge current (CA)

Charge volume

1 Discharge 100 % (0.1CA*10h) --50 % (0.1CA*5h) 2 Constant voltage charging Charge voltage : 2.275V/cell Charge current : 0.1CA (77 ) 3 Temperature : 25

1 Discharge 100 % (0.1CA*10h) -- 50 % (0.1CA*5h) 2 Constant voltage charging Charge voltage : 2.45V/cell Charge current : 0.3CA 3 Temperature : 25 (77 )

Charge current

Charge current
Charge Time (hr)

Charge Time (hr)

Shelf Life & Storage

Cycle Life vs Depth of Discharge

Open Circuit Voltage vs Residual Capacity

Effect of Temperature on Capacity

Charge Current & Final Discharge Voltage


Application Cycle Use Standby Charge Voltage(V/Cell) Temperature 25 (77 ) 25 (77 ) Set Point 2.45 2.30 Allowable Range 2.40~2.50 2.27~2.30 Max.Charge Current 0.25C

Final Discharge Voltage V/Cell Discharge Current(A)

1.75 0.2C>(A)

1.70 0.2C<(A)<0.5C

1.60 0.5C<(A)<1.0C

1.30 (A)>1.0C

Let UPG Power Your Life.

www.upgi.com
1720 Hayden Drive Carrollton, Texas 75006 P 469.892.1122 T 866.892.1122 F 469.892.1123 sales@upgi.com