Professional Documents
Culture Documents
Fig. 1: Relationship between system voltage drop, reactor short circuit voltage, and power factor.
voltage drop in the network. In general, this does not represent a particular problem for the grid operation since the voltage drop at the reactor is geometrically subtracted from the supply voltage, and is therefore a function of the power factor. The system voltage drop as the result of a series reactor is calculated as a function of cos as follows:
with time, and it decays due to the armature reaction of the generators. The AC component reduces towards the end of the short-circuit duration to become: Steady-state short-circuit current: I KD T h e r e l a t i o n s h i p b e t w e e n I K" a n d I KD depends (among other factors) on the type of the fault, the location of the fault, and the type of generator. The steady-state short-circuit current determines the thermal loading of the system components in the event of a short circuit. Peak short-circuit current: l KS If the short-circuit begins at an instant near to the voltage zero crossing, a DC component is present in addition to the AC current. This,together with the initial symmetrical short-circuit current form the peak short-circuit current, which is reached at the first maximum of the AC current after the short-circuit has occurred. The peak short-circuit current determines the dynamic loading of the system components through which the short-circuit current passes. Peak factor: k This is the ratio between IKS and 2.IK" and is called the peak factor. It depends on the ratio of the reactance to the resistance in the short-circuit loop and is usually
where U k is the short-circuit voltage of the reactor For example, a short-circuit voltage of a reactor of 5% and a power factor of 0,9 leads to a drop insystem voltage of only 2,23%. Fig. 1 shows the relationship between the system voltage drop, the short-circuit voltage of the reactor, and the power factor. Main parameters of short-circuit current and of the current-limiting reactor Short-circuit current parameters are given in national and international standards (e.g. IEC 60909-0 or DIN EN 60909-0) and are listed briefly here Initial symmetrical short-circuit current: IK" The AC component of the current flowing at the beginning of a short-circuit is called the initial symmetrical short-circuit current. The AC component is not constant energize - October 2009 - Page 45
(1)
assumed to have a value of 1,8. Short-circuit power: N K The short-circuit power in a network is calculated by:
Short-circuit voltage of a reactor U K The short-circuit voltage of a reactor, which is usually given as a percentage is calculated by:
(2)
where
X is the reactance of the reactor. UN is the rated voltage of the network (see IEC 60038: IEC Standard voltages). IN is the rated continuous current of the coil. Types of fault For the calculation of short-circuit currents, information on the type of the fault is required in addition to the network parameters. Faults are classified into various types: Symmetrical or asymmetrical fault An asymmetrical fault is present when the symmetrical short-circuit current is of a different magnitude in the three phases. All single and two-phase faults a r e a s y m m e t r i c a l f a u l t s, w h e r e a s a three-phase short-circuit is a symmetrical fault. This is the most easily calculated case and is specifically considered for network planning and dimensioning of the current-limiting reactor. For networks with an isolated or resonance grounded neutral the three-phase short-circuit results in the highest short-circuit current (except for special cases of double line-to-ground faults.) Neartogenerator or farfromgenerator short-circuit Armature reaction of the generators results in a reduction of the AC current provided by the generator. If there is sufficient impedance between the location of
(3)
Once the inductance L , the initial or the steady-state short-circuit current, I K" or I KD, the short-circuit duration and the peak short-circuit current l KS are set, the design of the series reactor is fully determined. Reactors are designed according to IEC 60076-6: "Reactors" and they must withstand the rated short-circuit currents. If the short-circuit power of the supply network is large compared to the shortcircuit power after the coil, the symmetrical short-circuit current is solely determined by the reactance of the coil and is calculated by:
4)
where
(6)
(7)
u' = reduced, percentage voltage drop U K =short-circuit voltage in percent Nn =rated transmission power in MVA N K =short-circuit power in MVA Values of the reduced percentage voltage drop in series are summed, values in par al l el are cal cu l ated l i ke parallel connected resistors. Series connection
If the short-circuit power of the supply network is of the same order of magnitude as that of the network to be protected, the short-circuit impedance of the supply network may be taken into consideration for dimensioning the reactor. Precise calculation of short-circuit currents is not particularly easy because of several system parameters which may have an influence, and for this reason simplified c a l c u l a t i o n m e t h o d s a r e u s e d. T h e approximate calculation of the shortcircuit current is described in detail in IEC 60909-0: " Short-circuit currents in threeenergize - October 2009 - Page 46
(5)
Parallel connection
(8)
(9)
For calculation of the short-circuit power at the 30 kV busbar u'1 and u'2 are added:
using equation (7)
The following example illustrates the calculation of the design parameters of a current-limiting reactor by this method. (See Fig. 2). The short-circuit power of a 30 kV feeder at a 30 kV busbar (Fig. 2) must not exceed 200 MVA. The short-circuit power of the 220 kV system is 1000 MVA, the transformer has a rated power of 40 MVA and a short-circuit voltage of 10%. The required short-circuit voltage of the reactor is unknown, the rated current of the feeder is 400 A corresponding to 20,8 MVA . The following symbols are used: U n = nominal voltage, in kV NK1 220 kV network short-circuit power, in MVA N nT rated power of the transformer, in MVA U K T transformer short-circuit voltage, in percent NK2 short-circuit power at the 30 kV busbar, in MVA UKD short-circuit voltage of the reactor, in percent NnD rated through-put power of the reactor, in MVA N K3 short-circuit power after the reactor, in MVA u' 1 ...u' 5 reduced percentage voltage drop at the corresponding locations, in percent Applying equation (7) for the 220 kV network:
The short-circuit power at the feeder after of the reactor must not exceed 200 MVA; thus:
winding which can withstand the forces occurring during a short-circuit. Fig. 3 shows the layout of a typical air-core dry-type current-limiting reactor. The main advantages of an air-core reactor are as follows:
l
Constant inductance, even for the short-circuit current, with no saturation effects No insulating oil and therefore no risk of a possible contamination of the ground, and negligible fire hazard when compared to oil immersed reactors Simple insulation to ground, provided by support insulators
20,8=3,95%
This corresponds to 3850/400 = 9,65 times the rated current. Design of current-limiting reactors Air-core, dry-type current-limiting reactors, being robust and having a simple design have been used almost exclusively for decades. Compared to oil-immersed coils with an iron-core, an air-core reactor requires considerably lower investment costs. An air-core reactor is a cylindrical winding mounted on a number of insulators. Since windings made of copper are heavier and more expensive and do not offer any technical advantages vs. aluminum windings, aluminum is used almost exclusively as the material for the windings. The turn's insulation consists of a combination of insulation film and glass cloth tape. Impregnation with epoxy resin results in a compact, self-supporting energize - October 2009 - Page 48
3,85 A
Since dry type reactors do not have an ironcore or an iron screen, the magnetic field spreads into the surrounding environment. This must be taken into account particularly for three-phase air-core reactance coils with stacked phase windings. Three-phase stacked reactors will exhibit time var ying axial forces between the phase coils during a two-phase or threephase short-circuit. As the short-circuit force depends on the distance between the coils, the force from the center to the outward coils is much higher than between the two outward coils. Reversing the winding direction of the center coil with respect to the outward coils, causes the neighboring coils to be attracted to each other when the time varying force reaches its maximum during a threephase short-circuit. This contraction force is absorbed by the supporting insulators between the coils. Further, the magnetic coupling between the coils results in an increase of the effective inductance of the center coil. This
can be compensated for by a reduction of the self inductance of the center phase by reducing the number of turns accordingly. Examples of application of current-limiting reactors The application of current-limiting reactors is illustrated in a simple circuit. Three arrangements of the reactor are shown (Fig. 5a, 5b, 6, 7a, 7b). The short-circuit power at the outgoing feeders of the simple circuit consisting of a feeder transformer and a busbar with eight outgoing feeders should be reduced accordingly. Depending on the location of the reactor, the following cases are classified: The reactor in the supply feeder This has the lowest investment cost, as a large unit is cheaper than several smaller units. Further advantages are a lower space requirement and thus less installation cost. A disadvantage compared to the other options is higher losses and larger voltage variations at the busbar between full load and reduced load. This option should not be employed if a large power consumer with strongly varying load is connected at one of outgoing lines, which would reduce the voltage quality for all other consumers. The options shown in Fig. 5a and Fig. 5b only differ in the location of the reactor, either upstream or downstream of the transformer. If a possible fault between the coil and the transformer is considered and the transformer is not short-circuit-proof (e.g. autotransformer), the reactor has to be installed upstream of the transformer. If the transformer is short-circuit-proof the choice of location of the coil is open and be may be made according to space or best price conditions. Reactors in outgoing feeders (Fig. 6) The possible impact on the quality of the busbar voltage can be avoided by providing reactors in the individual outgoing feeders. However, it must be ensured that the equipment before the feeder reactors is short-circuit-proof. Further it may be noted that the unit power of all feeder reactors together is less than the unit power rating of one single reactor at the incoming line. If the short-circuit power should be the same at any outgoing
feeder, the same reactance (not the same short-circuit voltage) must be provided in each short-circuit path, i.e. the inductance of the reactor in the incoming feeder and that of each outgoing feeder must be the same. As the unit power rating of a reactor is proportional to the square of the current (N = X IN2), the total power of n reactors (of identical power) is only the nth part of the unit power rating of a single reactor applied in the incoming feeder. Furthermore, splitting into several reactors with lower current but the same reactance leads to lower voltage variations at the consumers, and less impact by one feeder on the voltage of other feeders. Coils in busbars (Fig. 7a and 7b). A further option for reducing the shortcircuit power in the sample circuit is the installation of bus tie reactors (Fig. 7a). If the two coils are combined to form a joint reactor with the center terminal connected to the supply transformer, one obtains a socalled duplex-coil. If the busbar sections
If each busbar is supplied by a separate transformer, the reliability of voltage supply may be improved by coupling the two busbars with a bus tie reactor. Assuming that the two busbars are loaded symmetrically, no current flows in the bus tie reactor and therefore no losses and voltage drops occur. If one of the transformers fails, the associated busbar is still live but it is supplied at reduced power through the bus tie reactor. The short-circuit power of each busbar is of course higher due the connection via the bus tie reactor as compared to fully separated busbars. It is, however, less than the short-circuit power of firmly connected busbars. Usually the specified current rating of the bus tie reactors is approx. 50% of the rated current of the transformers. References
[1] P Steglich, "Kurzschlussberechnung mit Hilfe von reduzierten prozentualen Spannung-sabfllen" (Short-circuit calculation by means of reduced percentage voltage drops), in German, ETZ Nr. 63, Heft 43/44