Absorption Water Chillers

A Trane Air Conditioning Clinic

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

ChilledWater System

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

absorption

centrifugal

helical-rotary
American Standard Inc. 2000 Air Conditioning Clinic TRG-TRC011-EN

Absorption Water Chillers


period one

Absorption Refrigeration Cycle

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Vapor-Compression Cycle
reject heat D condenser expansion device evaporator absorb heat C compressor energy in A B

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Absorption Refrigeration Cycle


reject heat D condenser C heat energy in generator pump

expansion device A
American Standard Inc. 2000

evaporator B absorb heat

absorber

reject heat

Air Conditioning Clinic TRG-TRC011-EN

Refrigerant

Distilled water
Stable Nontoxic Low

cost available friendly

Readily

Environmentally High

latent heat of vaporization

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Absorbent

Lithium Bromide (LiBr)


High In

affinity for water (refrigerant) solution, higher boiling point than water

Nontoxic

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Solution Concentration

dilute solution
American Standard Inc. 2000

intermediate solution

concentrated solution
Air Conditioning Clinic TRG-TRC011-EN

Absorption Refrigeration Cycle


steam or hot water generator condens er cooling water

evaporator

chilled water

heat exchang er absorber


American Standard Inc. 2000 Air Conditioning Clinic TRG-TRC011-EN

Boiling Point of Water


115F temperatur e
[46.1C]

45F 0.15 psia


[1.034 kPa]

[7.2C]

1.5 psia
[10.34 kPa]

pressure
American Standard Inc. 2000 Air Conditioning Clinic TRG-TRC011-EN

Generator
steam or hot water generator refrigera nt vapor

American Standard Inc. 2000

dilute solutio n

concentrate d solution
Air Conditioning Clinic TRG-TRC011-EN

Condenser
refrigera nt vapor condens er cooling water liquid refrigera nt

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Expansion Device
evaporat or liquid refrigera nt

American Standard Inc. 2000

expansio n device

Air Conditioning Clinic TRG-TRC011-EN

Evaporator
refrigera nt vapor evaporat or

chilled water

absorber

liquid refrigera nt evaporato r spray

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Absorber
refrigera nt vapor absorber intermedia te solution concentrat ed solution

absorber spray pump cooling water

dilute solution

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Heat Exchanger

concentrat ed solution

heat exchanger dilute solution


American Standard Inc. 2000

generator pump

Air Conditioning Clinic TRG-TRC011-EN

Equilibrium Chart
15 psia

e r u ss 5 psia e r rp o [34.5 kPa] p a v


1 psia
[6.9 kPa]

[103.4 kPa]

40

50 55

concentrati on
60 65

A C B
100F
[37.8C]

0.1 psia
[0.69 kPa]

50F
[10C]
American Standard Inc. 2000

150F
[65.6C]

200F
[93.3C]

solution

LiBr solution
Air Conditioning Clinic TRG-TRC011-EN

Absorption Refrigeration Cycle


steam or hot water generator D evaporator B heat exchang er absorber
American Standard Inc. 2000

condens er cooling water C chilled water expansio n device


Air Conditioning Clinic TRG-TRC011-EN

Absorption Refrigeration Cycle


15 psia

e r u ss 5 psia e r rp o [34.5 kPa] p a v


1 psia
[6.9 kPa]

[103.4 kPa]

40

50 55

concentrati on
60 65

1.5 psia
[10.3 kPa]

0.1 psia
[0.69 kPa]

A
50F
[10C]

E
150F
[65.6C]

100F
[37.8C]

200F
[93.3C]

American Standard Inc. 2000

solution

LiBr solution
Air Conditioning Clinic TRG-TRC011-EN

Absorption Water Chillers


period two

Absorption Chiller Types

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Single-Effect Chiller
condens er evaporator generator

absorber

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Single-Effect Chiller
steam or hot water generator condens er cooling water

evaporator heat exchang er absorber absorber spray pump


American Standard Inc. 2000

chilled water expansio n device evaporator spray pump generator pump

Air Conditioning Clinic TRG-TRC011-EN

Double-Effect Chiller
lowtemperature generator condens er evaporator hightemperature generator

absorber

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Double-Effect Chiller
hightemperature generator steam or hot water refrigera nt vapor refrigera nt vapor condens ed refrigera nt

to absorber
American Standard Inc. 2000

lowtemperature generator

condens er
Air Conditioning Clinic TRG-TRC011-EN

Double-Effect Chiller
lowtemperature generator evaporator lowtemperature heat absorber exchanger absorber spray pump
American Standard Inc. 2000

condens cooling er water

chilled water expansio n device evaporator spray pump low-temperature generator pump

Air Conditioning Clinic TRG-TRC011-EN

Double-Effect Chiller
steam-fired hightemperature generator hightemperature generator pump

condensat e heat exchanger hightemperature heat

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Reverse-Series Solution Flow


hightemperature generator lowtemperature generator

hightemperature generator pump absorber


American Standard Inc. 2000

low-temperature generator

Air Conditioning Clinic TRG-TRC011-EN

Series Solution Flow


hightemperature generator lowtemperature generator

absorber

American Standard Inc. 2000

generator pump

Air Conditioning Clinic TRG-TRC011-EN

Parallel Solution Flow


hightemperature generator lowtemperature generator

absorber

American Standard Inc. 2000

generator pump

Air Conditioning Clinic TRG-TRC011-EN

Direct-Fired Chiller
condens er evaporator lowtemperature generator

absorber high-temperature generator

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Direct-Fired Chiller
hightemperatu re generator refrigerant vapor refrigera nt vapor lowtemperature generator condens ed refrigera nt condens er

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Direct-Fired Chiller
lowtemperature generator evaporator lowtemperature heat absorber exchanger absorber spray pump
American Standard Inc. 2000

condens er cooling water

chilled water expansio n device evaporator spray pump low-temperature generator pump

Air Conditioning Clinic TRG-TRC011-EN

Direct-Fired Chiller
hightemperature generator hightemperature generator pump

American Standard Inc. 2000

hightemperature heat h

Air Conditioning Clinic TRG-TRC011-EN

Chiller/Heater
refrigera nt vapor hot water auxiliary heating bundle hightemperature generator
American Standard Inc. 2000 Air Conditioning Clinic TRG-TRC011-EN

Chiller/Heater Operating Modes


Cooling only Heating only Simultaneous cooling/heating cooling priority Simultaneous heating/cooling heating priority

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Chiller/Heater
changeov er valve refrigera nt vapor hot water evaporat or hightemperature generator absorber
Air Conditioning Clinic TRG-TRC011-EN

American Standard Inc. 2000

Higher-Effect Chillers

Higher COPs Difficulties with implementation include:


Problems Increased More

with solution stability risk of corrosion problems

expensive pressure vessel design requirements first cost due to added components physical size

Greater Larger

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Absorption Water Chillers


period three

Capacity Control

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Equilibrium Chart
15 psia

e r u ss 5 psia e r rp o [34.5 kPa] p a v


1 psia
[6.9 kPa]

[103.4 kPa]

40

50 55

concentrati on
60 65

A C B
100F
[37.8C]

0.1 psia
[0.69 kPa]

50F
[10C]
American Standard Inc. 2000

150F
[65.6C]

200F
[93.3C]

solution

LiBr solution
Air Conditioning Clinic TRG-TRC011-EN

Part-Load Operation
15 psia

e r u ss 5 psia e r rp o [34.5 kPa] p a v


1 psia
[6.9 kPa]

[103.4 kPa]

40

50 55

concentrati on
60 65

B A A F E

0.1 psia
[0.69 kPa]

50F
[10C]
American Standard Inc. 2000

100F
[37.8C]

150F
[65.6C]

200F
[93.3C]

solution

LiBr solution
Air Conditioning Clinic TRG-TRC011-EN

Vary Solution Flow to Generator

adjustablefrequency drive absorber spray pump


American Standard Inc. 2000

generator pump

Air Conditioning Clinic TRG-TRC011-EN

Vary Heat Input to Generator


energy valve generator

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Crystallization
15 psia

e r u ss 5 psia e r rp o [34.5 kPa] p a v


1 psia
[6.9 kPa]

[103.4 kPa]

40

50 55

concentrati on
60 65

0.1 psia
[0.69 kPa]

123F
[50.6 C]

crystallizati on line
200F
[93.3C]

50F
[10C]
American Standard Inc. 2000

100F
[37.8C]

150F
[65.6C]

solution

LiBr solution
Air Conditioning Clinic TRG-TRC011-EN

Crystallization
15 psia

e r u ss 5 psia e r rp o [34.5 kPa] p a v


1 psia
[6.9 kPa]

[103.4 kPa]

40

50 55

concentrati on
60 65

B A

0.1 psia
[0.69 kPa]

crystallizati on line
150F
[65.6C]

50F
[10C]
American Standard Inc. 2000

100F
[37.8C]

200F
[93.3C]

solution

LiBr solution
Air Conditioning Clinic TRG-TRC011-EN

Causes of Crystallization

Air and noncondensables leaking into the chiller Cooling water that is too cold or fluctuates in temperature too rapidly Electric power failure

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Air Leaking Into the Chiller


Increases evaporator pressure and temperature Decreases chiller capacity Increases heat input Increases concentration Especially under high-load conditions, could cause crystallization

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Cooling Water That is Too Cold

Lower cooling water temperature combined with high load...


Decreases Results

temperature of dilute solution traveling to generator in lower temperature of concentrated solution returning to absorber concentrated solution inside heat exchanger to crystallize
Air Conditioning Clinic TRG-TRC011-EN

Causes

American Standard Inc. 2000

Electric Power Failure

Normal shutdown allows for dilution cycle, which reduces the concentration throughout the chiller Electric power failure does not allow dilution cycle Chiller could experience crystallization as it cools off

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

De-Crystallization
generator heat exchanger bypass heat exchanger absorber
American Standard Inc. 2000 Air Conditioning Clinic TRG-TRC011-EN

evaporator

Low-Load Controls

evaporator pan

refrigerant storage tank


American Standard Inc. 2000 Air Conditioning Clinic TRG-TRC011-EN

Purge System
purge

condens er

vacuum pump
American Standard Inc. 2000 Air Conditioning Clinic TRG-TRC011-EN

Purge Operation
isolation valve vacuum pump purge evaporator coil refrigerant vapor from chiller condenser liquid refrigerant returning to chiller d
American Standard Inc. 2000

purge tank

Air Conditioning Clinic TRG-TRC011-EN

Absorption Water Chillers


period four

Maintenance Considerations

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Operating Log

Chilled water inlet and outlet temperatures and pressures Cooling water inlet and outlet temperatures and pressures Absorber inlet and outlet solution temperatures and concentrations Absorber spray solution temperature Generator inlet and outlet solution temperatures Evaporator refrigerant temperature Condenser refrigerant temperature

Crystallization margin Purge pump-out activity Gas supply pressure (directfired)

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Mechanical Components

Recommended maintenance
Pump

teardown and inspection every 5 to 10 years no maintenance or calibration required inspect overall unit safety controls and electrical components

Controls: Visually Inspect

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Purge System

Weekly maintenance
Check Check

level of liquid refrigerant in purge condensing unit vacuum pump oil

Semiannual maintenance
Inspect

purge condensing coil and clean as necessary vacuum pump oil as needed

Change

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Direct-Fired Burner

Daily maintenance
Verify

proper operation

Seasonal maintenance
Inspect

burner firing rate, blower, linkage, and safety controls run with alternate fuel, if dual-fuel burner

Test

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Heat Transfer Surfaces

Recommended maintenance
Use

a qualified water treatment specialist absorber and condenser tubes as needed waterside strainers tubes every 3 years

Clean

Clean Test

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Corrosion Inhibitors

Absorbent solution analysis


Conduct Verifies Verifies

annually or semiannually corrosion inhibitor levels performance additive

levels

Refrigerant analysis
Conduct

annually

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Absorption Water Chillers


period five

Application Considerations

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Cooling-Water Temperature Limitations

cooling tower bypass diverting valve

condenser
American Standard Inc. 2000 Air Conditioning Clinic TRG-TRC011-EN

Combination Chiller Plants


operate absorption chiller cooling load operate electric chiller operate electric chiller

9 10 11 12 1

9 10 11 12

American Standard Inc. 2000

on -peak on-peak period

Air Conditioning Clinic TRG-TRC011-EN

Combination Chiller Plants


absorption chiller electric chiller

58F
[14.4C]

50F
[10C]

42F
[5.6C]

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Direct-Fired Chiller Considerations


cooling tower flue stack exhaust duct

direct -fired direct-fired absorption chiller


American Standard Inc. 2000 Air Conditioning Clinic TRG-TRC011-EN

ASHRAE Standard 151994

Open-flame devices
Combustion Refrigerant

air ducted from outside the machinery room vapor detector to shut down combustion process in the event of a refrigerant leak

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Equipment Rating Standards

Purpose
Establish

definitions, testing, and rating requirements and double-effect absorption chillers and direct-fired absorption chillers bromide solution

Scope
Single-

Indirect-

Water-and-lithium

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

Absorption Water Chillers


period six

Review

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

ReviewPeriod One
steam or hot water generator condens er

evaporator

chilled water expansio n device cooling water

heat exchanger absorber


American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

ReviewPeriod Two

single-effect

double-effect

direct-fired
American Standard Inc. 2000 Air Conditioning Clinic TRG-TRC011-EN

ReviewPeriod Three

Part-load capacity control


Vary Vary

solution flow to generator heat input to generator construction controls devices

Crystallization prevention
High-quality Microelectronic Automatic

purge systems

De-crystallization

Purge system
Air Conditioning Clinic TRG-TRC011-EN

American Standard Inc. 2000

ReviewPeriod Four

Maintenance considerations
Operating

log components

Mechanical Heat

transfer surfaces

Absorbent

solution analysis (corrosion inhibitor and performance additive levels)

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN

ReviewPeriod Five

Application considerations
Cooling-water Combination Special

temperature limitations

gas-and-electric chiller plants

considerations for direct-fired chillers rating standards

Equipment

American Standard Inc. 2000

Air Conditioning Clinic TRG-TRC011-EN