You are on page 1of 54

The essential guide TeSys

for power control & protection

2012

Motor control
The TeSys range provides more simplicity, compactness, openness and exibility ... so many evolutions and new items to aid your productivity. Accurate and reliable control of motors

Increase your productivity, adopt our solutions which help to simplify setting-up.

Motor starters p Ready-to-use component combinations, designed to work together in perfect harmony. p Safe operation and level of coordination guaranteed by a major manufacturer. Power circuit control p A wide range of components. p Solutions for a variety of power control applications: lighting, capacitor switching, heating, changeover contactor pairs, resistive loads, upstream protection.

Contents
Motor control components
New

TeSys Motor starters up to 65 A

TeSys contactors .................................................................... 2 to 11 p Contactors, TeSys K, D, F, B p Variable composition contactors, TeSys CV TeSys protection components ........................................... 12 to 33 p Thermal-magnetic circuit-breakers p Magnetic circuit-breakers p Fuse carriers, switch-disconnector-fuses p Thermal overload relays p Electronic thermal overload relays p Electronic overload relays p Starter-controller, TeSys T p Multifunction protection relays p Switch disconnectors Mini Vario and Vario TeSys starters ..................................................................... 34 to 41 p Combination motor starters p Starter-controller, TeSys U p Controller, TeSys U p Enclosed motor starters TeSys installation system ................................................... 42 to 43 p For motor starter components with spring terminals, TeSys Quickt technology

The new TeSys GV3 circuit-breakers, LC1D 40/50/65 contactors, LRD3 thermal relays are equipped with the new terminal block:

EverLink
Long lasting connection quality. Schneider Electric patented technology.

TeSys T Motor management system

TeSys protected
TeSys T is an advanced motor management and protection system. It is able to guard against all motor malfunctions: overland, current peak, excessive consumption, etc.

p Lighting, capacitor switching, heating, changeover contactor pairs

Components for power control applications ........................................ 44 to 50

TeSys U Communication modules

With open communication across CANopen, Probus DP, Modbus, AS-Interface, Modicon STB, DeviceNet and Ethernet networks, TeSys U has openness in mind.

TeSys K

Contactors
0.065.5 kW

Connections
N screw clamp terminals Rated operational current Rated operational power in category AC3 Contactor type (1)* Reversing contactor type * with mechanical interlock b spring terminals Add the gure 3 before the voltage code. Example: LC1K0610 becomes LC1K06103 b Faston connectors, 1 x 6.35 or 2 x 2.8 Add the gure 7 before the voltage code. Example: LC1K0610 becomes LC1K06107 b solder pins for printed circuit boards Add the gure 5 before the voltage code. Example: LC1K0610 becomes LC1K06105 (1) Basic reference, to be completed by adding 01 for NC auxiliary contact, or 10 for NO auxiliary contact. * Basic reference to be completed by adding the coil voltage code Ie max AC-3 (Ue 440 V) Ie AC-1 ( 40 C) 220/240 V 380/400 V415/440 V 660/690 V500 V a c a c 6A 1.5 kW 2.2 kW 3 kW LC1K06 LP1K06 or LP4K06 LC2K06 LP2K06 or LP5K06 9A 20 A 2.2 kW 4 kW 4 kW LC1K09 LP1K09 or LP4K09 LC2K09 LP2K09 or LP5K09 12 A 3 kW 5.5 kW 4 kW LC1K12 LP1K12 or LP4K12 LC2K12 LP2K12 or LP5K12

Standard control circuit voltages


a supply Contactors LC1K (0.81.15 Uc) (0.851.1 Uc) Volts 50/60 Hz Volts 50/60 Hz c supply Contactors LP1K (0.81.15 Uc) Volts Code 12 JD 20 ZD 24 BD 36 CD 48 ED 60 ND 72 SD 100 KD 110 FD 125 GD 155 PD 174 QD 200 LD 220 MD 230 MPD 240 MUD 250 UD 12 J7 256 W7 20 Z7 277 UE7 24 B7 380/400 Q7 36 C7 42 D7 400 V7 48 E7 400/415 N7 110 F7 115 FE7 440 R7 120 G7 480 T7 127 FC7 500 S7 200/208 L7 575 SC7 600 X7 220/230 M7 660/690 Y7 230 P7 230/240 U7

Example of complete reference: LC1K0910P7

Coil with integral suppression device available, add 3 to the code required. Example: JD3 Low consumption Contactors LP4K (0.71.30 Uc), coil suppression as standard Volts Code 12 JW3 20 ZW3 24 BW3 48 EW3 72 SW3 110 FW3 120 GW3

Example of complete reference: LC1K0910BD

Other versions: please consult our Customer Care Centre.

Auxiliary contact blocks


N instantaneous, screw clamp connections N for LC1, LP1K, LP4 N for LC1, LP1K

Composition Reference
N electronic time delay

2NO LA1KN20

2NC

1NO 1NC LA1KN11

4NO LA1KN40

3NO 1NC LA1KN31

2NC 2NC LA1KN22

1NO 3NC LA1KN13

4NC

LA1KN02

LA1KN04

Relay outputs, with common point changeover contact, a or c 2448, 2 A maximum Control voltage 0.851.1 Uc Maximum switching capacity 250 VA or 150 W Operating temperature -10+ 60C Reset time: 1.5 s during the time delay period, 0.5 s after time delay period Type Timing range Composition Voltage Reference On-delay 130 s 1 a or c 2448 V LA2KT2E a 110240 LA2KT2U

Suppressor modules
For LC1, LP1-K Type Voltage Reference Varistor (a and c) 1224 V LA4KE1B 3248 V LA4KE1E 50129 V LA4KE1FC 130250 V LA4KE1UG Diode (c) + Zener 1224 V LA4KC1B 3248 V LA4KC1E RC (a) 220250 V LA4KA1U

Other versions: please consult our Customer Care Centre.

TeSys D

Contactors
0.0675 kW

Connections
screw clamp terminals or connectors

Rated operational voltage Rated operational current Rated operational power in category AC3 Ie max AC-3 (Ue 440 V) Ie AC-1 ( 60 C) 220/240 V 380/400 V 415/440 V 500 V 660/690 V 1000 V Contactor type * Reversing contactor type * with mechanical interlock
N spring terminals (1)

690 V 9A 25 A 2.2 kW 4 kW 4 kW 5.5 kW 5.5 kW LC1D09 LC2D09 3 kW 5.5 kW 5.5 kW 7.5 kW 7.5 kW LC1D12 LC2D12 12 A 18 A 32 A 4 kW 7.5 kW 9 kW 10 kW 10 kW LC1D18 LC2D18 25 A 40 A 5.5 kW 11 kW 11 kW 15 kW 15 kW LC1D25 LC2D25 32 A 50 A 7.5 kW 15 kW 15 kW 18.5 kW 18.5 kW LC1D32 LC2D32 9 kW 18.5 kW 18.5 kW 18.5 kW 18.5 kW LC1D38 LC2D38 38 A

Add the gure 3 before the voltage code. Example: LC1D09P7 becomes LC1-093P7
N lug-clamps (2)

Add the gure 6 before the voltage code. Example: LC1D09P7 becomes LC1-096P7
N Faston connectors (3) 2 x 6.35 (power) and 1 x 6.35 (control) up to D12 only

Add the gure 9 before the voltage code. Example: LC1D09P7 becomes LC1-099P7 * Basic reference to be completed by adding the coil voltage code

(1)

(2)

(3)

Standard control circuit voltages


a supply Volts 50/60 Hz Contactors LC1D80D115 50 Hz 60 Hz c supply Volts U 0.751.25 Uc Contactors LC1D80D95 U 0.851.1 Uc U 0.751.2 Uc U 0.751.2 Uc Low consumption Contactors LC1D09D38 (coils with integral suppression device tted as standard) Volts c U 0.71.25 Uc Example of complete reference: LC1D09P7
Other versions: please consult our Customer Care Centre.

24 B7 B5 B6 12 JD JD JW -

42 D7 D5 24 BD BD BW BD

48 E7 E5 E6 36 CD CD CW -

110 F7 F5 F6 48 ED ED EW ED

115 FE7 FE5 60 ND ND ND

220 M7 M5 M6 72 SD SD SW SD

230 P7 P5 110 FD FD FW FD

240 U7 U5 U6 125 GD GD GD

380 Q7 Q5 Q6 220 MD MD MW MD

400 V7 V5 250 UD UD UD

415 N7 N5 440 RD RD RD

440 R7 R5 R6

500 S7 S5 -

Contactors LC1D09D150 (coils D115 and D150 with integral suppression device tted as standard)

Contactors LC1D09D65A (coils with integral suppression device tted as standard)

Contactors LC1D115 and D150 (coils with integral suppression device tted as standard)

5 AL

12 JL

20 ZL

24 BL

48 EL

110 FL

120 ML

250 UL

690 V 40 A 60 A 11 kW 18.5 kW 22 kW 22 kW 30 kW LC1D40A LC2D40A 50 A 80 A 15 kW 22 kW 25 kW 30 kW 33 kW LC1D50A LC2D50A 65 A 80 A 18.5 kW 30 kW 30 kW 37 kW 37 kW LC1D65A LC2D65A

1000 V on a supply, 690 V on c supply 80 A 125 A 22 kW 37 kW 45 kW 55 kW 45 kW 45 kW LC1D80 LC2D80 25 kW 45 kW 45 kW 55 kW 45 kW 45 kW LC1D95 LC2D95 95 A 115 A 200 A 30 kW 55 kW 59 kW 75 kW 80 kW 75 kW LC1D115 LC2D115 40 kW 75 kW 80 kW 90 kW 100 kW 90 kW LC1D150 LC2D150 150 A

Mounting accessories for 3-pole reversing contactors


2 identical contactors with screw clamp terminals or connectors, horizontally mounted Mechanical interlock
N with an electrical interlocking kit for the contactors

Set of connections LAD-9R1V LA9D8069 LA9D8069 LA9D11569 LA99R1 LAD9R3 LA9D8069 LA9D8069

Mechanical interlock included LA9D4002 LA9D8002 LA9D11502 included included LA9D50978 LA9D80978

LC1-D09D38
N with integral electrical interlocking

LC1-D80 and D95 (a) LC1-D80 and D95 (c) LC1-D115 and D150
N without electrical interlocking

LC1-D09D38 LC1-D40AD65A LC1-D80 and D95 (a) LC1-D80 and D95 (c)

Mechanical latch blocks


Clip-on front mounting, manual or electrical unlatching control For use on contactor LC1D09D65A a or c, LC1DT20DT80 a or c LC1D80D150 3P a, LC1D80 and D115 3P a, LC1D115 4P c Reference LAD6K10 LA6DK20 Standard control circuit voltages BEFMQ BEFMQ

Other versions: please consult our Customer Care Centre.

TeSys D

Contactors
Auxiliary contacts

Contact type
Block mounting References Contact 1 NO 1 NC 1 NO + 1 NC 2 NO 2 NC 2 NO + 2 NC 1 NO + 3 NC 3 NO + 1 NC 4 NO 4 NC

instantaneous, connection by screw terminals


Front mounting LADN10 LADN01 LADN11 LADN20 LADN02 LADN22 LADN13 LADN31 LADN40 LADN04 Side mounting LAD8N11 LAD8N20 LAD8N02

Contact type
Block mounting Temporisation References On-delay Off-delay

Time delay, connection by screw terminals


Front mounting 0.13 s LADT0 LADR0 0.130 s LADT2 LADR2 10180 s LADT4 LADR4

Maximum number of auxiliary contacts that can be tted Instantaneous


Type AC Number of poles and size 3P LC1D09D38 LC1D40AD65A LC1D8095 (50/60 Hz) LC1D8095 (50 or 60 Hz) LC1D115 and D150 4P LC1DT20DT40 LC1DT60AD80A LC1D115 DC 3P LC1D09D38 LC1D40AD65A LC1D80 and 95 LC1D115 and D150 4P LC1DT20DT40 LC1DT60AD80A LC1D115 DC low consumption 3P 4P LC1D09D38 LC1DT20DT40 Side mounting on left side 1 1 1 1 1 1 1 1 1 1 1 on right side or 1 1 1 or 1 1 or 1 1 and and and and or and and and and and Front mounting 1 contact 2 2 1 1 2 contacts 1 1 and 1 and 1 1 1 1 or 1 1 1 or 1 1 1 1 and 1 1 1 4 contacts or 1 or 1 or 1 or 1 or 1 or 1 or 1 or 1 or 1 or 1 or 1 or 1 or 1 or 1 or 1

Time delay
Front mounting or 1 or 1 or 1 or 1 or 1 or 1 or 1 or 1 or 1 or 1 or 1 or 1 or 1 or 1 or 1

Other versions: please consult our Customer Care Centre.

TeSys D

Contactors
Suppressor modules

Type of module
Mounting For use with contactor References Voltage 2448 VAC 50127 VAC 110240 VAC 380415 VAC

RC circuits (Resistor-Capacitor)
Side clip-on D09D38(3P) DT20DT40(4P) LAD4RCE LAD4RCG LAD4RCU Front clip-on LAD4RC3E LAD4RC3G LAD4RC3U LAD4RC3N Screw xing LA4DA2E LA4DA2G LA4DA2U LA4DA2N

D40AD65A(3P) DT60ADT80A(4P) D80D150(3P) D40D115(4P)

Type of module
Mounting For use with contactor References Voltage 2448 VAC 50127 VAC 110240 VAC 2448 VDC 50127 VDC 110240 VDC

Varistors (peak limiting)


Side clip-on D09D38(3P) DT20DT40(4P) LAD4VE LAD4VG LAD4VU Front clip-on LAD4V3E LAD4V3G LAD4V3U Screw xing LA4DE2E LA4DE2G LA4DE2U LAD4DE3E (AC and DC) LAD4DE3G (AC and DC) LAD4DE3U (AC and DC)

D40AD65A(3P) DT60ADT80A(4P) D80D150(3P) D40D115(4P)

Type of module
Mounting For use with contactor References Voltage 24250 VDC

Flywheel diodes
Side clip-on D09D38(3P) DT20DT40(4P) LAD4DDL Front clip-on LAD4D3U Screw xing LAD4DC3U

D40AD65A(3P) DT60ADT80A(4P) D80D150(3P) D40D115(4P)

Type of module
Mounting For use with contactor References Voltage 24 VAC 24 VDC 72 VAC 72 VDC 125 VDC 250 VDC 600 VDC

Bidirectional peak limiting diode


Side clip-on D09D38(3P) DT20DT40(4P) LAD4TB LAD4TBDL LAD4TS LAD4TSDL LAD4TGDL LAD4TUDL LAD4TXDL Front clip-on LAD4T3B LAD4T3B LAD4T3S LAD4T3S LAD4T3G (AC and DC) LAD4T3U (AC and DC) LAD4T3R (AC and DC) Screw xing LA4DB2B LA4DB2S LA4DB3B LA4DB3S

D40AD65A(3P) DT60ADT80A(4P) D80D150(3P) D40D115(4P)

Other versions: please consult our Customer Care Centre.

TeSys F

Contactors
90450 kW

Rated operational current Rated operational voltage Number of poles Rated operational power in category AC3

Ie max AC-3 (Ue 440 V) Ie AC-1 ( 40 C)

185 A 275 A 1 000 V 3 or 4

225 A 315 V 1 000 V 3 or 4 63 kW 110 kW 110 kW 110 kW 129 kW 129 kW 100 kW LC1F225 LC2F225

265 A 350 A 1 000 V 3 or 4 75 kW 132 kW 140 kW 140 kW 160 kW 160 kW 147 kW LC1F265 LC2F265

330 A 400 A 1 000 V 3 or 4 100 kW 160 kW 180 kW 200 kW 200 kW 220 kW 160 kW LC1F330

220/240 V 380/400 V 415 V 440 V 500 V 660/690 V 1000 V

55 kW 90 kW 100 kW 100 kW 110 kW 110 kW 100 kW LC1F185 LC2F185

Contactor type* Reversing contactor type* * Basic reference to be completed by adding the coil voltage code

Standard control circuit voltages


a supply Volts Contactors LC1F115F225 (0.851.1 Uc) 50 Hz (coil LX1) 60 Hz (coil LX1) 40400 Hz (coil LX9) Contactors LC1F265F330U7 40400 Hz (coil LX1) Contactors LC1F400F630U7 40400 Hz (coil LX1) Contactor LC1F780U7 40400 Hz (coil LX1) Contactor LC1F800U7 40400 Hz (coil LX1) c supply Volts Contactors LC1F115F330 (0.851.1 Uc) (coil LX4-F) Contactors LC1F400F630 (0.851.1 Uc) (coil LX4-F) Contactor LC1F780 (0.851.1 Uc) (coil LX4-F) Contactor LC1F800 (0.851.1 Uc) (coil LX4-F) Contactor LC1F1250 (coil LX4F) Contactor LC1F1400 (coil LX4F) FD GD MD UD RD Example: For a 630 A contactor with a 110 V a coil, order LC1F630F7 (1) F7 for LC1-F630 ED FD MD UD FW FW MW MW QW FD GD MD UD RD ED FD GD MD UD RD BD ED FD GD MD MD UD RD 24 48 110 125 220 230 250 400 440 FE7 FE7 FE7 P7 P7 P7 V7 V7 V7 V7Y7 F7 FE7 F7 L7 M7 P7 U7 Q7 V7 N7 R7 E7 F7 FE7 G7 (1) L7 M7 P7 U7 Q7 V7 N7 R7 B7 E7 F7 FE7 G7 L7 M7 P7 U7 Q7 V7 N7 R7 B5 E5 E6 E7 F5 F6 F7 FE5 FE7 G6 G7 L6 L7 M5 M6 M7 P5 P7 U5 U6 U7 Q5 Q6 Q7 V5 V7 N5 N7 R6U7 R7 24 48 110 115 120 208 220 230 240 380 400 415 440

Other versions: please consult our Customer Care Centre.

400 A 500 A 1 000 V 2, 3 or 4 110 kW 200 kW 220 kW 250 kW 257 kW 280 kW 185 kW LC1F400

500 A 700 A 1 000 V 2, 3 or 4 147 kW 250 kW 280 kW 295 kW 355 kW 335 kW 335 kW LC1F500 For customer assembly

630 A 1 000 A 1 000 V 2, 3 or 4 200 kW 335 kW 375 kW 400 kW 400 kW 450 kW 450 kW LC1F630

780 A 1 600 A 1 000 V 3 or 4 220 kW 400 kW 425 kW 425 kW 450 kW 475 kW 450 kW LC1F780

800 A 1 000 A 1 000 V 3 250 kW 450 kW 450 kW 450 kW 450 kW 475 kW 450 kW LC1F800

1260 1000 3 Sans objets en AC1 LC1F1250 -

1400 1000 3 Sans objets en AC1 LC1F1400 -

Auxiliary contact blocks


N instantaneous

dust & damp protected contacts Composition NO NC 1 2 1 2 Reference LADN11 LADN20 LADN02 Composition NO NC 2 1 4 3 2 2 3 4 1 2 LADN22 LADN13 LADN40 LADN04 LADN31 LADC22 Reference Composition NO NC 2 2 2 2 2 2 1 1 LA1DX20 LA1DY20 LA1DZ40 LA1DZ31 Reference

N time delay 1 NO + 1 NC

Composition Reference NO NC 1 1 LADN10 LADN01

Type On-delay

Range 0.13 s 0.130 s 10180 s 130 s

Reference LADT0 LADT2 LADT4 LADS2 LADR0 LADR2 LADR4

Off-delay

0.13 s 0.130 s 10180 s

Mounting accessories for 3-pole reversing contactors for motor control


2 identical contactors, horizontally mounted Mechanical interlock with an electrical interlocking kit for the contactors Contactor type LC1F115 LC1F150 LC1F185 LC1F225 LC1F265 LC1F330 LC1F400 LC1F500 LC1F630 or LC1F800 LCIF1250 LCIF1400 Set of connections LA9FF976 LA9F15076 LA9FG976 LA9F22576 LA9FH976 LA9FJ976 LA9FJ976 LA9FK976 LA9FL976 Mechanical interlock LA9FF970 LA9FF970 LA9FG970 LA9FG970 LA9FJ970 LA9FJ970 LA9FJ970 LA9FJ970 LA9FL970 -

Other versions: please consult our Customer Care Centre.

TeSys B

Contactors
400900 kW

Rated operational current Rated operational voltage Number of poles Rated operational power in category AC3

Ie max AC-3 (Ue 440 V) Ie AC-1 ( 40 C)

750 A 800 A 1 000 V 1 to 4

1000 A 1250 V 1 000 V 1 to 4 280 kW 500 kW 530 kW 560 kW 600 kW 670 kW 530 kW

1500 A 2000 A 1 000 V 1 to 4 425 kW 750 kW 800 kW 800 kW 700 kW 750 kW 670 kW

1800 A 2750 A 1 000 V 1 to 4 500 kW 900 kW 900 kW 900 kW 900 kW 900 kW 750 kW

220/240 V 380/400 V 415 V 440 V 500 V 660/690 V 1000 V

220 kW 400 kW 425 kW 450 kW 500 kW 560 kW 530 kW

4 instantaneous contact congurations 2 NC + 2 NO, 3 NO + 1 NC, 1 NO + 3 NC or 4 NO Contactor type* LC1BL LC1BM LC1BP LC1BR * Basic reference to be completed by adding the coil voltage code, followed by the instantaneous contact conguration.

Standard control circuit voltages (for other voltages, please consult your Regional Sales Ofce) Volts 48 110 125 127 220 a 50400 Hz c ED F FD GD G M MD

230 P -

240 U -

380 Q -

400 V -

415 N -

440 R RD

500 S -

Example: To order a 1500 A contactor with 127 V c coil with 3 NO + 1 NC, select LC1BP33G31

Mounting accessories
Description Bar support bracket for mounting on 120 or 150 mm centres Mechanical interlock and locking device components LC1B EZ2LB0601 For contactor LC1BL to BR Reference LA9B103

Other versions: please consult our Customer Care Centre.

10

TeSys
CV1-B, CV3-B
Reference to compiled by the customer
Contactor type, according to required use a supply 690 V, c supply 220 V/pole a supply 1000 V, c supply 440 V/pole Contactor rating CV1: 80 A CV1: 200 A CV1: 300 A CV1: 470 A CV1: 630 A CV1: 1000 A Number of poles (PN1 main poles for CV1 and PA3 main poles for CV3) Normally Open main poles 1 NO 2 NO 3 NO 4 NO 5 NO Normally Closed main poles 1 NC 2 NC 3 NC No main poles Operational current 10 A 20 A 40 A 80 A 125 A 170 A 200 A 250 A 300 A 320 A 470 A 500 A 630 A 1000 A Control circuit voltage 48 V 110 V 120 V 208 V 220 V 230 V 240 V 380 V 400 V 440 V Operating frequency 50 Hz 60 Hz 50/60 Hz c c + economy resistor Instantaneous auxiliary contacts Normally Open 1 NO 2 NO 3 NO 4 NO Normally Closed 1 NC 2 NC 3 NC 4 NC Without instantaneous contact On-delay Off-delay 1 CO 1 CO CV3: 80 A CV3: 170 A CV3: 250 A CV3: 320 A CV3: 500 A

Contactors, variable composition


CV1-B: 801000 A, CV3-B: 80500 A

CV1B CV3B F G H J K L 1 2 3 4 5 1 2 3 0 Z E N P F R W G S H T J V K L 0 Z E N P F R W G S H T J V K L E F K L M P U Q V R 5 6 7 D R 1 2 3 4 1 2 3 4 0 0 J N

Example 1/ for single-phase capacitor switching: 400 V - 80 A - 1 NO pole - Control circuit 220 V / 50 Hz, 1 NO and 1 NC auxiliary contacts: CV1BF1F0ZM511. 2/ for heating circuits, d.c. supply 800 V - 150 A - 2 NO poles - Control circuit 48 V c , 1 NO + 1 NO On-delay auxiliary contacts: CV3BG2W0ZED10J
Other versions: please consult our Customer Care Centre.

11

TeSys
GV2-ME, GV2-P

Thermal-magnetic circuit-breakers
0.0615 kW

Thermal-magnetic circuit-breakers GV2-ME and GV2-P for connection by screw clamp terminals
GV2-ME with pushbutton control, GV2-P control by rotary knob Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V P kW 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 0.75 1.1 1.1 1.5 1.5 2.2 2.2 3 3 4 4 5.5 5.5 7.5 7.5 9 9 11 11 15 15 H > 100 kA (1) as % of Icu (2) combined with a recommended contactor Icu kA ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( 15 ( 15 50 15 50 15 50 10 50 ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( 50 ( 50 50 40 50 40 50 50 50 Ics (1) 500 V P kW 0.37 0.55 0.75 1.1 1.1 1.5 1.5 2.2 2.2 3 3 4 4 5.5 5.5 7.5 7.5 9 9 11 11 15 15 18.5 18.5 Icu kA ( ( ( ( ( ( ( ( ( 50 ( 10 50 10 50 6 42 6 10 4 10 4 10 4 10 ( ( ( ( ( ( ( ( ( 100 ( 100 100 100 100 75 75 75 75 75 75 75 75 75 75 Ics (1) 690 V P kW 0.37 0.55 0.75 1.1 1.5 1.5 2.2 2.2 3 3 4 4 5.5 5.5 7.5 7.5 9 9 11 11 15 15 18.5 18.5 22 22 Icu kA ( ( ( ( 3 8 3 8 3 3 3 6 3 6 3 6 3 6 3 6 3 4 3 4 3 4 ( (( ( 75 100 75 100 75 100 75 100 75 100 75 100 75 100 75 100 75 100 75 100 75 100 Ics (1) Setting range of thermal trips A 0.10.16 0.160.25 0.250.40 0.400.63 0.400.63 0.631 11.6 11.6 11.6 1.62.5 1.62.5 2.54 2.54 2.54 2.54 46.3 46.3 610 610 610 610 914 914 914 914 1318 1318 1723 1723 2025 2025 2432 2432 Magnetic tripping current A (d 20%) 1.5 2.4 5 8 8 13 22.5 22.5 22.5 33.5 33.5 51 51 51 51 78 78 138 138 138 138 170 170 170 170 223 223 327 327 327 327 416 416 GV2ME32 GV2P32 GV2ME22 (2) GV2P22 GV2ME21 GV2P21 GV2ME20 GV2P20 GV2ME16 GV2P16 GV2ME16 GV2P16 GV2ME14 GV2P14 GV2ME14 GV2P14 GV2ME10 GV2P10 GV2ME08 GV2P08 GV2ME08 GV2P08 GV2ME01 GV2ME02 GV2ME03 GV2ME04 GV2ME04 GV2ME05 GV2ME06 GV2ME06 GV2ME06 GV2ME07 GV2P07 GV2P01 GV2P02 GV2P03 GV2P04 GV2P04 GV2P05 GV2P06 GV2P06 GV2P06 Reference

Thermal-magnetic circuit-breakers GV2-ME for connection by spring terminals


Add the gure 3 to the end of the reference. Example: GV2ME22 becomes GV2ME223

Thermal-magnetic circuit-breakers GV2-ME for connection by ring terminals


Add the gure 6 to the end of the reference. Example: GV2ME32 becomes GV2ME326

TeSys extended rotary handles


These handles are suitable for the following products Kit IP54 black handle IP54 kit red handle and yellow front IP65 kit red handle and yellow front Common accessories GV2 / GV3, see page 5/15
Other versions: please consult our Customer Care Centre.

GV2 -P et GV2 - L GV2APN01 GV2APN02 GV2APN04

GV3-P et GV3 - L GV3APN01 GV3APN02 GV3APN04

TeSys U LU9APN21 LU9APN22 LU9APN24

12

TeSys
GV2-L, GV2-LE

Magnetic circuit-breakers
0.06 to 15 kW

Magnetic circuit-breakers GV2-LE and GV2-L for connection by screw clamp terminals
GV2-LE control by rocker lever, GV2-L control by rotary knob Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V P kW 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 0.75 1.1 1.5 1.5 2.2 2.2 3 3 4 5.5 5.5 7.5 7.5 9 9 11 11 15 15 Icu kA ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( 15 50 15 50 15 50 15 50 10 50 ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( 50 50 50 50 40 50 40 50 50 50 Ics (1) 500 V P kW 0.37 0.55 0.75 1.1 1.1 1.5 1.5 2.2 3 3 4 4 5.5 7.5 7.5 9 9 11 11 15 15 18.5 18.5 Icu kA ( ( ( ( ( ( ( ( 50 ( 10 10 10 6 10 6 10 4 10 4 10 4 10 ( ( ( ( ( ( ( ( 100 ( 100 100 100 75 75 75 75 75 75 75 75 75 75 Ics (1) 690 V P kW 0.37 0.55 0.75 1.1 1.5 1.5 3 3 4 4 5.5 5.5 7.5 7.5 9 9 11 11 15 15 18.5 18.5 22 22 Icu kA ( ( ( ( 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 ( ( ( ( 75 100 75 100 75 100 75 100 75 100 75 100 75 100 75 100 75 100 75 100 Ics (1) Magnetic protection rating A 0.4 0.4 0.63 0.63 1 1 1 1 1.6 1.6 2.5 2.5 2.5 4 4 4 6.3 6.3 10 10 10 10 10 14 14 14 14 18 18 25 25 25 25 32 32 Tripping current d 20% A 5 5 8 8 13 13 13 13 22.5 22.5 33.5 33.5 33.5 51 51 51 78 78 138 138 138 138 138 170 170 170 170 223 223 327 327 327 327 416 416 LR2K0302 LR2K0304 or LRD03 LR2K0304 or LRD04 LR2K0305 or LRD04 LR2K0305 or LRD05 LR2K0306 or LRD05 LR2K0306 or LRD06 LR2K0306 or LRD05 LR2K0307 or LRD06 LR2K0307 or LRD06 LR2K0308 LRD07 LR2K0308 or LRD08 LR2K0310 LRD08 LR2K0312 or LRD08 LR2K0312 LRD10 LR2K0314 LRD12 LR2K0316 or LRD14 LRD14 LRD14 LRD16 LRD16 LR2K0321 LRD16 LRD21 LRD21 LRD22 LRD22 LRD22 LRD22 LRD32 LRD32 GV2LE03 GV2LE03 GV2L03 GV2LE04 GV2L04 GV2LE04 GV2L04 GV2LE05 GV2L05 GV2LE05 GV2L05 GV2LE05 GV2L05 GV2LE05 GV2L05 GV2LE06 GV2L06 GV2LE06 GV2L06 GV2LE07 GV2L07 GV2LE08 GV2L08 GV2LE08 GV2L08 GV2LE08 GV2L08 GV2LE10 GV2L10 GV2LE14 GV2L14 GV2LE14 GV2L14 GV2LE14 GV2L14 GV2LE16 GV2L16 GV2LE16 GV2L16 GV2LE20 GV2L20 GV2LE22 GV2L22 GV2LE22 GV2L22 GV2LE32 GV2L32 Use in association with thermal overload relay Reference

H > 100 kA (1) as % of Icu Common accessories GV2 / GV3, see page 5/15
Other versions: please consult our Customer Care Centre.

13

TeSys
GV3-P/GV3-L

Circuit-breakers
Thermal-magnetic 5.530 kW with EverLink terminal blocks

Thermal-magnetic circuit-breakers GV3-P for connection by EverLink terminal blocks (2)


Control by rotary knob Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V P kW 5.5 7.5 11 15 18.5 22 Icu kA 100 100 100 100 50 50 50 50 50 50 50 50 50 Ics (1) 500 V P kW 7.5 11 15 18.5 22 30 37 Icu kA 12 12 12 12 10 10 10 50 50 50 50 50 50 50 Ics (1) 660/690 V P kW 11 15 18.5 22 30 37 45 Icu kA 6 6 6 6 5 5 5 50 50 50 50 60 60 60 Ics (1) Setting range of thermal trips A 913 1218 1725 2332 3040 3750 4865 GV3P13 GV3P18 GV3P25 GV3P32 GV3P40 GV3P50 GV3P65 Reference

30 50 (1) as % of lcu

Thermal-magnetic circuit-breakers GV3-P for connection by ring terminals


Add the gure 6 to the end of the reference. Example: GV3-P13 becomes GV3-P136

Thermal-magnetic circuit-breakers GV3-P for connection by only 1 EverLink terminal block


Add the gure 1 to the end of the reference. Example: GV3P65 becomes GV3P651

Magnetic 1130 kW with EverLink terminal blocks


Magnetic circuit-breakers GV3-L for connection by EverLink terminal blocks (2)
Control by rotary knob Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V P kW 11 15 18.5 22 30 Icu kA 100 100 50 50 50 50 50 50 50 50 Ics 500 V P kW 15 18.5 22 30 37 Icu kA 12 12 10 10 10 50 50 50 50 50 Ics 690 V P kW 18.5 22 30 45 45 Icu kA 6 6 5 5 5 50 50 60 60 60 Ics Associated equipment Thermal overload relay LRD325 LRD332 LRD340 LRD350 LRD365 Circuit-breaker Short-circuit protection Rating A 25 32 40 50 65 Reference GV3L25 GV3L32 GV3L40 GV3L50 GV3L65

Magnetic circuit-breakers GV3-L for connection by ring terminals


Add the gure 6 to the end of the reference. Example: GV3-L25 becomes GV3-L256

Magnetic circuit-breakers GV3-L for connection by only 1 EverLink terminal block


Add the gure 1 to the end of the reference. Example: GV3L65 becomes GV3L651 (2) 4 mm BTR screw

Add-on blocks and accessories (3)


Add-on blocks (front)
Contact type References (4)

Fault signalling contact + instantaneous auxiliary contact


NO (fault) + NC GV-AED011 NO (fault) + NO GV-AED101

Accessories
Type

Cover
IP20 for lug type terminals IP20 for lug type terminals when used with contactor Wide spacing UL 508 type E

Busbars
Set of 3-pole 115 A busbars for 2 circuit-breakers GV3G264 Set of 3-pole 115 A busbars for 3 circuit-breakers GV3G364 S form for side by side mounted circuit-breaker/ contactor GV3G66 GV3S

References (3) Common add-on blocks and accessories GV2 / GV3, see page 5/15

LAD96570

LAD96575

(4) For spring terminal version add 3 to the end of the reference. Example: GV-AED011 becomes GV-AED0113
Other versions: please consult our Customer Care Centre.

14

TeSys
GV2/GV3

Circuit-breakers
Accessories

(TeSys rotating handles)

Combination block GV2


For mounting on Sets of 3-pole busbars GV2 63 A Number of tap-offs Pitch 2 3 4 5 Protective end cover GV2 For unused busbar outlets Terminal blocks GV2 For supply to one or more GV2-G busbar sets Padlockable external operator for GV2 and GV3 (150 to 290 mm) Padlocking Handle Legend plate IP 54 For GV2-ME/P/L For GV2-LE For GV3-P/L TeSys rotating handles for Kit IP54 black handle IP54 kit red/yellow handle IP65 kit red/yellow handle In On and Off position black blue GV2AP01 GV2AP03 GV3AP01 In Off position red yellow GV2AP02 GV3AP02 connection from the top GV1G09 can be tted with current limiter GV1-L3 (GV2-ME and GV2-P) GV1G05 GV1G10 45 mm GV2G245 GV2G345 GV2G445 54 mm GV2G254 GV2G354 GV2G454 GV2G554 GV2G472 72 mm GV2G272 LC1-K or LP1-K GV2AF01 LC1-D09D38 GV2AF3 LAD-31 and LC1-D09D38 GV2AF4

GV2-P
GV2APN01 GV2APN02 GV2APN04

GV3-P
GV3APN01 GV3APN02 GV3APN04

Contact blocks common to GV2 / GV3


NO + NC Instantaneous auxiliary contacts Mounting front LH side Fault signalling contact + instantaneous auxiliary contact LH side Short-circuit signalling contact LH side Electric trips for GV2 and GV3 : undervoltage or shunt (1) Side mounting (1 block on RH side of circuit-breaker) Voltage 24 V 48 V 100 V 100110 V 110115 V 120127 V 127 V 200 V 200220 V 220240 V 380400 V 415440 V 415 V Padlocking device For use with up to 4 padlocks (padlocks not supplied) 6 mm shank max GV2V03 (1) Undervoltage trips: replace the with U, shunt trips: replace the with S
Other versions: please consult our Customer Care Centre.

NO + NC GVAE11 GVAN11

NO + NO GVAE20 GVAN20

(fault) + NC

(fault) + NO

CO common point

GVAE1

NO (fault) NC (fault)

GVAD1001 GVAD0101

GVAD1010 GVAD0110 GVAM11

50 Hz GVA025 GVA055 GVA107

60 Hz GVA026 GVA056 GVA107

GVA115 GVA125

GVA116 GVA115

GVA207 GVA207 GVA225 GVA385 GVA415 GVA416 GVA226 GVA386

15

TeSys
GV7-R

Thermal-magnetic circuit-breakers
0.7590 kW

Thermal-magnetic circuit-breakers GV7-R for connection by screw clamp terminals


Control by rocker lever Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V P kW 7.5 9 7.5 9 9 11 9 11 18.5 18.5 22 37 37 45 45 55 75 55 75 90 110 90 Icu kA 25 25 70 70 25 25 70 70 25 70 25 25 70 25 70 35 70 70 70 35 35 70 100 100 100 100 100 100 100 50 100 100 100 100 100 100 100 100 100 100 100 100 100 100 Ics (1) 500 V P kW 9 11 9 11 11 15 11 15 18.5 22 18.5 30 45 55 45 55 75 90 75 90 110 132 160 110 (1) as % of Icu Icu kA 18 18 50 50 18 18 50 50 18 18 50 18 18 18 50 50 18 50 30 30 50 50 30 30 30 50 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 160 10 100 132220 GV7RS220 75 75 90 110 90 110 160 200 8 10 8 8 10 10 8 8 100 100 100 100 100 100 100 100 132220 GV7RE220 90150 GV7RS150 60100 60100 90150 GV7RE100 GV7RS100 GV7RE150 55 10 100 4880 GV7RS80 22 30 55 10 8 8 100 100 100 2540 3050 4880 GV7RS40 GV7RE50 GV7RE80 Ics (1) 660/690 V P kW 11 15 11 15 15 18.5 15 18.5 22 Icu kA 8 8 10 10 8 8 10 10 8 100 100 100 100 100 100 100 100 100 2540 GV7RE40 1525 GV7RS25 1525 GV7RE25 1220 GV7RS20 Ics (1) Setting range of thermal trips A 1220 GV7RE20 Reference

Other versions: please consult our Customer Care Centre.

16

Add-on blocks
Contact blocks Auxiliary contacts Contact type Thermal or magnetic fault discrimination z 2448 V or c 2472 V GV7AD111 Electric trips Voltage Undervoltage trip (1) Shunt trip (1) (1) For mounting of a GV7-AD or a GV7-AU or AS 50/60 Hz 50 Hz GV7AU055 GV7AS055 GV7AU107 GV7AS107 GV7AU207 GV7AS207 GV7AU387 GV7AS387 48 V 110 130 V 200 240 V 380440 V 525 V GV7AU525 GV7AS525 z 110240 V GV7AD112 CO GV7AE11

Accessories
Terminal shields IP 405 Supplied with sealing accessory Phase barriers Safety accessories used when tting of shields is impossible Insulating screens Ensure insulation between the connections and the backplate Kit for combination with contactor Allowing link between the circuit-breaker and the contactor Rotary handles Handle Legend plate
N direct N extended

GV7AC01 GV7AC04

GV7AC05

LC1-F115 to F185 GV7AC06 black black

LC1-F225 and F26 GV7AC07

LC1-D115 and D150 GV7AC08 red yellow GV7AP04 GV7AP02

IP 40 IP 55 IP 43

GV7AP03 GV7AP01 GV7AP05 GV7V01

Conversion accessory for mounting on enclosure door Locking device For circuit-breaker not tted with a rotary handle

Other versions: please consult our Customer Care Centre.

17

TeSys
GV3-ME

Thermal-magnetic circuit-breakers
37 kW

Thermal-magnetic circuit-breakers GV3-ME for connection by screw clamp terminals


Pushbutton control Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V P kW 37 Icu kA 15 50 Ics (1) 500 V P kW 45 Icu kA 4 100 Ics (1) 660/690 V P kW 55 Icu kA 2 100 Ics (1) Setting range of thermal trips A 5680 GV3ME80 Reference

(1) as % of Icu

Add-on blocks for GV3-ME


Contact blocks Instantaneous auxiliary contacts (1 per breaker) Normal early break type contacts Fault signalling contact Normal early break type contacts Electric trips Voltage Undervoltage trip Shunt trip Padlocking device Start button (for bare device) (1) + 2 volt free terminals GV1V02 50 Hz 60 Hz 110, 120, 127 V 120, 127 V GV3B11 GV3D11 220, 240 V 277 V GV3B22 GV3D22 380, 415 V 440, 480 V GV3B38 GV3D38 NC GV3A08 NO GV3A09 NC + NO GV3A01 NO + NO GV3A02 NC + NO + NO GV3A03 NO + NO + NO GV3A05 NO + NO (1) GV3A06 NC + NO (1) GV3A07

Other versions: please consult our Customer Care Centre.

18

TeSys
GK3-EF

Magnetic circuit-breakers
37 kW

Magnetic circuit-breakers GK3-EF for connection by screw clamp terminals


Control by rotary knob Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V P kW 37 Icu kA 35 25 Ics 500 V P kW 45 Icu kA 15 30 Ics 690 V P kW Icu kA Ics Associated equipment Thermal overload relay min. size LRD-3363 Circuit-breaker Short-circuit protection Rating A 80 Reference GK3EF80

Add-on blocks for GK3


Contact blocks Contact type On-Off signalling contacts and Control circuit test function (1 or 2 blocks per device) mounted on RH side of GK3-EF Instantaneous fault signalling contacts (1 or 2 blocks per device) mounted on LH side of GK3-EF Fault signalling contact (1) (1) 1 trip OR 1 fault signalling contact to be tted inside the circuit-breaker. GV3A08 GV3A09 GK2AX12 GK2AX22 GK2AX52 NO GK2AX10 NO + NO GK2AX20 NC + NO GK2AX50 NC NO

Accessories for GK3


Padlocking device for padlocking the operator with up to 3 padlocks (padlocks not supplied) External operator for mounting on enclosure door. Red 40 pushbutton on yellow plate, can be locked in position O by means of up to 3 padlocks with door locked in position I, and door locked in position O when padlocked GK3AP03 GK3AV01

Other versions: please consult our Customer Care Centre.

19

TeSys DF

Fuse carriers
0125 A

Type
Rated insulation voltage (Ui) Fuse size Conventional thermal current (Ith) References Number of poles 1P N 1P+N 2P 3P 3P+N

Fuse carriers without blown fuse indicator


500 V 8.5 x 31.5 mm 25 A DF81 DF10N DF81N DF82 DF83 DF83N 690 V 10 x 38 mm 32 A DF101 DF10N DF101N DF102 DF103 DF103N 14 x 51 mm 50 A DF141 DF14N DF141N DF142 DF143C DF143NC 22 x 58 mm 125 A DF221 DF22N DF221N DF222 DF223C DF223NC

Type
Rated insulation voltage (Ui) Fuse size Conventional thermal current (Ith) References Number of poles 1P 1P + N 2P 3P 3P + N

Fuse carriers with blown fuse indicator


500 V 8.5 x 31.5 mm 25 A DF81V DF81NV DF82V DF83V DF83NV 690 V 10 x 38 mm 32 A DF101V DF10NV DF102V DF103V DF103NV 14 x 51 mm 50 A DF141V DF14NV DF142V DF143VC DF143NVC 22 x 58 mm 125 A DF221V DF22NV DF222V DF223VC DF223NVC

Accessories
Type
Fuse carrier to be equipped Fuse size Number of poles Number of contacts References

Auxiliary early break and blown fuse signalling contacts


DF14 14 x 51 mm 3P or 3P + N 1 DF14AM1 2 DF14AM2 DF22 22 x 58 mm 3P or 3P + N 1 DF22AM1 2 DF22AM2

Type
Fuse carrier to be assembled Fuse size Kit contents References

Fuse carrier assembly kits


DF8 8.5 x 31.5 mm 1 pin, 2 clips DF10AP DF10 10 x 38 mm DF14 14 x 51 mm 1 pin, 3 clips DF14AP DF22AP DF22 22 x 58 mm

Other versions: please consult our Customer Care Centre.

20

TeSys
LS1, GK1

Fuse carriers
0125 A

Type
Rated insulation voltage (Ui) Rating Fuse size Connection Single-phase protection device Number of early break contacts Reference Number of early break contacts Reference

3-pole fuse carriers


690 V 25 A 10 x 38 Spring terminals Without LS1D323 32 A 10 x 38 Without LS1D32 50 A 14 x 51 Without 1 GK1K 2 GK1ES GK1EW GK1EV With 125 A 22 x 58 Without 1 GK1FK 2 GK1FS GK1FW GK1FV With

Screw clamp terminals or connectors

Type
Rated insulation voltage (Ui) Rating Fuse size Connection Single-phase protection device Number of early break contacts Reference Number of early break contacts Reference

4-pole fuse carriers


690 V 32 A 10 x 38 Without LS1D32 + LA8D324 50 A 14 x 51 Without 1 GK1EM 2 GK1ET GK1EX GK1EY With 125 A 22 x 58 Without 1 GK1FM 2 GK1FT GK1FX GK1FY With

Screw clamp terminals or connectors

Other versions: please consult our Customer Care Centre.

21

TeSys
LS1, GK1

Fuse carriers
Accessories

Type
Fuse carrier rating For use with fuse carrier Contact type References

Early break auxiliary contact blocks


32 A LS1D32 NO + NC GVAE11 NO + NO GVAE20 25 A LS1D323 NO + NC GVAE113 NO + NO GVAE203

Type
Fuse carrier rating For mounting on References

Direct operator handle


125 A RH side GK1AP07 LH side GK1AP08 32, 50, 125 A Front Fitted as standard

Type
Fuse carrier rating For mounting on References

External operator handle


32 A RH side LS1D32005 LH side LS1D32006 50 A RH side GK1AP05 LH side GK1AP06 125 A RH side GK1AP07 LH side GK1AP08

Type
Fuse carrier rating Number of poles Single-phase protection device References

Padlocking devices
32 A 3 or 4 Without Integrated 50 A 3 Without GK1AV07 With GK1AV08 4 Without GK1AV08 With GK1AV09

Type
Fuse carrier rating References

Tubular link
32 A DK1CB92 50 A DK1EB92 125 A DK1FA9

Other versions: please consult our Customer Care Centre.

22

TeSys GS

Switch-disconnector-fuses
Handles

Type
Switch rating References Black/grey Red/yellow

IP65 handles for external front-mounted operators


3263 A GS2AH510 (1) GS2AH520 (1) 100400 A GS2AH530 (1) GS2AH540 (1) 630800 A GS2AH550 GS2AH560 1250 A GS2AH570 GS2AH580

(1) For external front operators with Test facility, insert the letter T in the reference. Example: GS2AH510 becomes GS2AHT510

Type
Switch rating References Black/grey Red/yellow

IP65 handles for external RH side-mounted operators (2)


3263 A GS2AH210 GS2AH220 100400 A GS2AH230 GS2AH240 6301250 A GS2AH250 GS2AH260

(2) For external LH side-mounted operators, replace the number 2 in the reference by 3. Example: GS2AH210 becomes GS2AH310

Type
Switch rating References Length of shaft 200 mm 320 mm 400 mm

Shafts for external operators


32 A GS2AE82 GS2AE8 GS2AE81 50400 A GS2AE22 GS2AE2 GS2AE21 6301250 A GS2AE52 GS2AE5 GS2AE51

Type
Switch rating Type of operator References

Handles for direct operators


32 A Front GS1AH103 50 and 63 A RH side GS1AH01 100400 A RH side GS1AH02 630 and 800 A Front GS2AH104 1250 A Front GS2AH105

Other versions: please consult our Customer Care Centre.

23

TeSys GS

Switch-disconnector-fuses
321250 A

Type
Rated insulation voltage (Ui) Conventional thermal current (Ith) Fuse size External front-mounted and RH side-mounted operator External LH side-mounted operator Direct RH side-mounted operator (1) Compact fuse for German market (2) 3-pole + switched neutral (3) Direct front-mounted operator 3-pole 4-pole 3-pole 4-pole 3-pole 4-pole

Switch-disconnector-fuse switch bodies for use with NF C or DIN fuses Handle to be ordered separately (see previous page)
690 V 32 A 10 x 38 GS1DD3 GS1DD4 (2) GS1DD3 GS1DD4 (2) GS1DD3 (3) GS1DD4 (2) (3) 50 A 14 x 51 GS2F3 GS2F4 GS2FG3 GS2FG4 GS1FD3 GS1FD4 63 A Size 00C (1) GS2G3 GS2G4 GS2GG3 GS2GG4 GS1GD3 GS1GD4 100 A 22 x 58 GS2J3 GS2J4 GS2JG3 GS2JG4 GS1JD3 GS1JD4

Type
Rated insulation voltage (Ui) Conventional thermal current (Ith) Fuse size External front-mounted and RH side-mounted operator 3-pole 4-pole

Switch-disconnector-fuse switch bodies for use with BS fuses Handle to be ordered separately (see previous page)
690 V 32 A A1 GS1DDB3 GS1DDB4 (2) 32 A A1 GS2DB3 GS2DB4 63 A A2-A3 GS2GB3 GS2GB4 100 A A4 ( 31 mm) GS2JB3 GS2JB4

Accessories

Type
Switch rating Number of contacts Operator external front-mounted or RH side-mounted external LH side-mounted direct RH side-mounted direct front-mounted

Auxiliary contacts
Early break and/or O, I and Test signalling O and I signalling
321250 A 1 NO GS1AM110 GS1AM110 1 NC GS1AM101 GS1AM101 501250 A 1 NO + NC GS1AN11 GS1AN11G GS1AN11 2 NO + 2 NC GS1AN22 GS1AN22G GS1AN22

Type
Number of contacts Switch rating Fuse size References 3-pole 4-pole

Auxiliary blown fuse signalling contacts for use with NF C and DIN fuses
1 NO/NC 50 A 14 x 51 GS1AF1 GS1AF1 100 and 125 A 22 x 58 GS1AF23 GS1AF24 160 A Size 0 GS1AF33 GS1AF34 250 and 400 A Size 1 and Size 2 GS1AF43 GS1AF44

Other versions: please consult our Customer Care Centre.

24

125 A 22 x 58 GS2K3 GS2K4 GS2KG3 GS2KG4 GS1KD3 GS1KD4 Size 00 GS2KK3 GS2KK4 GS2KKG3 GS2KKG4 GS1KKD3 GS1KKD4

160 A Size 00 GS2LL3 GS2LL4 GS2LLG3 GS2LLG4 GS1LLD3 GS1LLD4 Size 0 GS2L3 GS2L4 GS2LG3 GS2LG4 GS1LD3 GS1LD4

250 A Size 1 GS2N3 GS2N4 GS2NG3 GS2NG4 GS1ND3 GS1ND4

400 A Size 2 GS2QQ3 GS2QQ4 GS2QQG3 GS2QQG4 GS1QQD3 GS1QQD4

630 A Size 3 GS2S3 GS2S4 GS2SG3 GS2SG4 GS2S3 (3) GS2S4 (3)

1250 A Size 4 GS2V3 GS2V4 GS2VG3 GS2VG4 GS2V3 (3) GS2V4 (3)

160 A A4 GS2LLB3 GS2LLB4 B1-B2 GS2LB3 GS2LB4

200 A B1-B2 GS2MMB3 GS2MMB4

250 A B1B3 GS2NB3 GS2NB4

315 A B1B3 GS2PPB3 GS2PPB4

400 A B1B4 GS2QQB3 GS2QQB4

630 A C1-C2 GS2SB3 GS2SB4

800 A C1C3 GS2TB3 GS2TB4

1250 A D1 GS2VB3 GS2VB4

O, I and Test signalling


50400 A 1 NO + NC GS1ANT11 2 NO + 2 NC GS1ANT22

Early break and O and I signalling


32 A 1 NO/NC GS1AM111 2 NO/NC GS1AM211 50400 A 1 NO/NC GS1AM1 2 NO/NC GS1AM2

2nd NO/NC 630 A Size 3 GS2AF63 GS2AF64 1250 A Size 4 GS2AF73 GS2AF74 501250 A GS1AF GS1AF
Other versions: please consult our Customer Care Centre.

25

TeSys K

Thermal overload relays


0.1111.5 A

Thermal overload relays, TeSys K


adjustable from 0.11 to 12 A Connection by screw clamp terminals, direct mounting on contactors LC1-K, manual or automatic reset Relay setting range Class 10A 0.110.16 A 0.160.23 A 0.230.36 A 0.360.54 A 0.540.8 A 0.81.2 A 1.21.8 A 1.82.6 A 2.63.7 A 3.75.5 A 5.58 A 811.5 A Example: LR7-K0310. Fuses to be used with selected relay aM 0.25 A 0.25 A 0.5 A 1A 1A 2A 2A 2A 4A 6A 8A 10 A gG 0.5 A 0.5 A 1A 1.6 A 2A 4A 6A 6A 10 A 16 A 20 A 25 A BS88 6A 6A 10 A 16 A 16 A 20 A 20 A LR2K0301 LR2K0302 LR2K0303 LR2K0304 LR2K0305 LR2K0306 LR2K0307 LR2K0308 LR2K0310 LR2K0312 LR2K0314 LR2K0316 Reference

Thermal overload relays for use on class 10A unbalanced loads: for above references LR2-K0305 to LR2-K0316 only, replace the prex LR2 with LR7.

Accessories
Prewiring kit Allowing direct connection of the NC contact of relay LRD-0135 or LR3-D01 D35 to the contactor Terminal blocks (1) For clip-on mounting on 35 mm mounting rail (AM1-DP200) or screw xing For independent mounting of the relay EverLink Terminal blocks Separate terminal block Terminal block adapter For mounting a relay beneath an LC1-D115 or D150 contactor Stop or electrical reset Remote (3) Tripping or electrical reset device Remote (3) All relays except LRD0135 and LR3D01D35 LA7D03 (4) (1) Terminal blocks are supplied with terminals protected against direct nger contact and screws in the open ready-to-tighten position. (2) To order a terminal block for connection by lug-clamps, the reference becomes LA7-D30646. (3) The time for which the coil of remote tripping or electrical resetting device LA7-D03 or LAD-703 can remain energised depends on its rest time: 1 s pulse duration with 9 s rest time; maximum pulse duration of 20 s with a rest time of 300 s. Minimum pulse time 200 ms. (4) Reference to be completed by adding the code indicating the control circuit voltage. LRD0135 and LR3D01D35 LAD703 (4) LRD3, LR3D3, LRD35 LA7D3058 LRD313 LRD365 LAD9R3 LRD0135 and LR3D01D35 LRD3, LR3D3, LRD35 LR2K LAD7B10 LA7D3064 (2) LA7K0064 For use on LC1D09D18 LC1D25D38 LAD7C1 LAD7C2

Standard control circuit voltages


a supply Volts 50/60 Hz. Consumption, inrush and sealed < 100 VA c supply Consumption, inrush and sealed < 100 W J B E DD F M 12 24 B 48 E 96 110 F 220/230 M 380/400 Q 415/440 N

Other versions: please consult our Customer Care Centre.

26

TeSys D

Thermal overload relays


0.1140 A

Thermal overload relays, TeSys D


adjustable from 0.1 to 140 A Compensated relays with manual or automatic reset, with relay trip indicator, for a.c. or d.c. Relay setting range Fuses to be used with selected relay Connection by screw clamp terminals or connectors aM gG Class 10A 0.100.16 A 0.25 A 2A 0.160.25 A 0.5 A 2A 0.250.40 A 1A 2A 0.400.63 A 1A 1.6 A 0.631 A 2A 4A 11.7 A 2A 4A 1.62.5 A 4A 6A 2.54 A 6A 10 A 46 A 8A 16 A 5.58 A 12 A 20 A 710 A 12 A 20 A 913 A 16 A 25 A 1218 A 20 A 35 A 1624 A 25 A 50 A 2332 A 40 A 63 A 3038 A 50 A 80 A 5570 A 80 A 125 A 6380 A 80 A 125 A 80104 A 100 A 160 A 80104 A 125 A 200 A 95120 A 125 A 200 A 110140 A 160 A 250 A 80104 A 100 A 160 A 95120 A 125 A 200 A 110140 A 160 A 250 A Class 20 6A 10 A 16 A 46 A 8A 16 A 5.58 A 12 A 20 A 710 A 16 A 20 A 913 A 16 A 25 A 1218 A 25 A 35 A 1725 A 32 A 50 A 2328 A 40 A 63 A 2532 A 40 A 63 A 5570 A 100 A 125 A 6380 A 100 A 160 A Connection by EverLink terminal blocks, with BTR screws Class 10A 913 A 16 A 25 A 1218 A 20 A 32 A 1725 A 25 A 50 A 2332 A 40 A 63 A 3040 A 40 A 80 A 3750 A 63 A 100 A 4865 A 63 A 100 A Class 20 913 A 20 A 32 A 1218 A 25 A 40 A 1725 A 32 A 50 A 2332 A 40 A 63 A 3040 A 50 A 80 A 3750 A 63 A 100 A 4865 A 80 A 125 A Class 10A with connection by lug-clamps: Select overload relay with screw clamp terminals or connectors from the table above and add one of the following suffixes: b gure 6 for relays LRD01 to LRD35 and LRD313 to LRD365. b A66 for relays LRD3361 to LRD3365. Relays LRD43 are suitable as standard, for use with lug-clamps. (1) For independent mounting on a DIN rail, order an EverLink LAD7B106 terminal block. With contactor BS88 6A 10 A 16 A 16 A 20 A 20 A 25 A 32 A 50 A 63 A 80 A 125 A 125 A 160 A 160 A 200 A 200 A 160 A 200 A 200 A 16 A 20 A 25 A 25 A 40 A 50 A 63 A 63 A 125 A 125 A 25 A 35 A 50 A 63 A 80 A 100 A 100 A 35 A 40 A 50 A 63 A 80 A 100 A 125 A LC1D09D38 LC1D09D38 LC1D09D38 LC1D09D38 LC1D09D38 LC1D09D38 LC1D09D38 LC1D09D38 LC1D09D38 LC1D09D38 LC1D09D38 LC1D12D38 LC1D18D38 LC1D25D38 LC1D25D38 LC1D32 and D38 D50D95 D65D95 D80 and D95 D115 and D150 D115 and D150 D150 Independent mtg. Independent mtg. Independent mtg. LC1D09D32 LC1D09D32 LC1D09D32 LC1D09D32 LC1D12D32 LC1D18D32 LC1D25 and D32 LC1D25 and D32 LC1D25 and D32 D65D95 D80 and D95 LC1D40AD65A LC1D40AD65A LC1D40AD65A LC1D40AD65A LC1D40AD65A LC1D40AD65A LC1D40AD65A LC1D40AD65A LC1D40AD65A LC1D40AD65A LC1D40AD65A LC1D40AD65A LC1D40AD65A LC1D40AD65A Reference LRD01 (1) LRD02 (1) LRD03 (1) LRD04 (1) LRD05 (1) LRD06 (1) LRD07 (1) LRD08 (1) LRD10 (1) LRD12 (1) LRD14 (1) LRD16 (1) LRD21 (1) LRD22 (1) LRD32 (1) LRD35 (1) LRD3361 (1) LRD3363 (1) LRD3365 (1) LRD4365 (1) LRD4367 (1) LRD4369 (1) LRD33656 (1) LRD33676 (1) LRD33696 (1) LRD1508 (1) LRD1510 (1) LRD1512 (1) LRD1514 (1) LRD1516 (1) LRD1521 (1) LRD1522 (1) LRD1530 (1) LRD1532 (1) LR2D3561 (1) LR2D3563 (1) LRD313 (2) LRD318 (2) LRD325 (2) LRD332 (2) LRD340 (2) LRD350 (2) LRD365 (2) LRD313L (2) LRD318L (2) LRD325L (2) LRD332L (2) LRD340L (2) LRD350L (2) LRD365L (2)

Thermal overload relays for use with unbalanced loads Class 10A with connection by screw clamp terminals and lug-clamp terminals:
In the reference selected above, change LRD(except LRD4ppp) to LR3D Example: LRD01 becomes LR3D 01 Example with EverLink terminals: LRD340 becomes LR3D 340 Example with lug-clamp terminals: LRD3406 becomes LR3D 3406 (2) For independent mtg. on a DIN rail, order an EverLink LAD96560 terminal block.
Other versions: please consult our Customer Care Centre.

27

TeSys
LR9

Electronic thermal overload relays


60630 A

For use with contactor Motor current Basic reference, to be completed

LC1-D 60150 A LR9D

LC1-F 30630 A LR9F

Relay setting range

Fuse to be used with selected relay aM gG 160 250 80 125 200 250 315 500 800 800

For mounting beneath contactor LC1-

Compensated and differential Class 10 Class 20 LR9D5567 LR9F5569 LR9F5557 LR9F5563 LR9F5567 LR9F5569 LR9F5571 LR9F7575 LR9F7579 LR9F7581

With alarm Class 10 or 20

60100 90150 3050 4880 60100 90150 132220 200330 300500 380630

100 160 50 80 100 160 250 400 500 630

D115 and D150 D115 and D150 F115F185 F115F185 F115F185 F115F185 F185F400 F225F500 F225F500 F400F630 and F800

LR9D5367 LR9D5369 LR9F5357 LR9F5363 LR9F5367 LR9F5369 LR9F5371 LR9F7375 LR9F7379 LR9F7381

LR9F57 LR9F63 LR9F67 LR9F69 LR9F71 LR9F75 LR9F79 LR9F81

Accessories
Remote control Function Electrical reset (1) Reset by exible cable (length 0.5 m) Adapter for door interlock mechanism Operating head for pushbutton Spring return Rod with snap-off end Adjustable from 17 to 120 mm Insulated terminal blocks For relays LR9-F557, F563, F567, F569, F57, F63, F67 and F69 Set of 2 blocks LA9F103 (1) The time for which the coil of remote electrical reset device LA7-D03 can remain energised depends on its rest time: 1 s pulse with 9 s rest time; 5 s pulse duration with 30 s rest time; 10 s pulse duration with 90 s rest time: maximum pulse duration 20 s with rest time of 300 s. Minimum pulse time: 200 ms. (2) Reference to be completed by adding the coil voltage code, see page 5/27
Other versions: please consult our Customer Care Centre.

Reset LA7D03 (2) LA7D305

Stop and/or Reset

LA7D1020 ZA2BL639 ZA2BZ13 ZA2BL432

28

TeSys
LR/LT

Electronic overcurrent relays


0.338 A

Relay type
Relay setting range For use with contactor References 200 240 VAC 100 120 VAC 24 VAC/DC 48 VAC/DC

Electronic overcurrent relays


TeSys LR97D 0.31.5 A LC1D09D38 LR97D015M7 LR97D015F7 LR97D015B LR97D015E LR97D07M7 LR97D07F7 LR97D07B LR97D07E LR97D025M7 LR97D025F7 LR97D025B LR97D025E 1.27 A 525 A 2038 A LC1D25D38 LR97D038M7 LR97D038F7 LR97D038B LR97D038E

0.560 A

Relay type
Relay setting range References 200 240 VAC 100 120 VAC 24 VAC/DC 48 VAC/DC

Electronic overcurrent relays


TeSys LT47 with manual reset 0.56 A LT4706M7S LT47D06F7S LT47D06BS LT47D06ES 330 A LT47D30M7S LT47D30F7S LT47D30BS LT47D30ES 560 A LT4760M7S LT4760F7S LT4760BS LT4760ES

Relay type
Relay setting range References 200 240 VAC 100 120 VAC 24 VAC/DC 48 VAC/DC Accessories: please consult your Schneider Electric agency.

Electronic overcurrent relays


TeSys LT47 with automatic reset 0.56 A 330 A LT4706M7A LT47D06F7A LT47D06BA LT47D06EA LT47D30M7A LT47D30F7A LT47D30BA LT47D30EA 560 A LT4760M7A LT4760F7A LT4760BA LT4760EA

Other versions: please consult our Customer Care Centre.

29

TeSys T

Motor management system


Controllers

Type of eldbus
Supply voltage References Current range 0.48 A 1.3527 A 5100 A

Ethernet
24 VDC LTMR08EBD LTMR27EBD LTMR100EBD 100240 VAC LTMR08EFM LTMR27EFM LTMR100EFM

Modbus
24 VDC LTMR08MBD LTMR27MBD LTMR100MBD 100240 VAC LTMR08MFM LTMR27MFM LTMR100MFM

Probus DP
24 VDC LTMR08PBD LTMR27PBD LTMR100PBD 100240 VAC LTMR08PFM LTMR27PFM LTMR100PFM

Type of eldbus
Supply voltage References Current range 0.48 A 1.3527 A 5100 A

CANopen
24 VDC LTMR08CBD LTMR27CBD LTMR100CBD 100240 VAC LTMR08CFM LTMR27CFM LTMR100CFM

DeviceNet
24 VDC LTMR08DBD LTMR27DBD LTMR100DBD 100240 VAC LTMR08DFM LTMR27DFM LTMR100DFM

Extension module

Type of module
Inputs voltage References

Extension 4 additional inputs + voltage measuring


24 VDC LTMEV40BD 100240 VAC LTMEV40FM

Ethernet external port Modbus RTU / Modbus TCP/IP


24 VDC TCSEQM113M13M

Control unit

Type of terminal
Supply voltage Reference

Compact display
24 VDC LTMCU

Other versions: please consult our Customer Care Centre.

30

TeSys T

Motor management system


Current transformers

Type of transformer
Operational current References primary secondary

External
100 A 1A LT6CT1001 LT6CT2001 LT6CT4001 LT6CT8001 200 A 400 A 800 A

Earth fault toroids


Type of toroid
Maximum current Internal diameter References

Closed
65 A 30 TA30 85 A 50 PA50 160 A 80 IA80 250 A 120 MA120 400 A 200 SA200 630 A 300 GA300

Split
85 A 46 POA 250 A 110 GOA

PTC thermistor probe


Type of probe
Operating temperature References

Triple
90C 110C 120C DA1TT120 130C 140C 150C 160C 170C

DA1TT090 DA1TT110

DA1TT130 DA1TT140 DA1TT150 DA1TT160 DA1TT170

Accessories (1)

Type of accessory
Length of cable References

Connecting cable
Controller / Extension module 0.04 m LTMCC004 0.3 m LU9R03 1m LU9R10

Type of accessory
Length of cable References (1) For other connection accessories, see www.schneider-electric.com

Connecting cable
Controller/ Display 1m 3m 5m

Connection kit
PC serial port

VW3A1104R10 VW3A1104R30 VW3A1104R50 VW3A8106

Other versions: please consult our Customer Care Centre.

31

TeSys
LT3, LT6

Electronic protection relays for use with PTC thermistor probes


0800 A

Relay type
For use with contactor Motor current Basic reference, to be completed

PTC thermistor probes


LC1-D or LC1-F No limit LT3S LC1-D or LC1-F 15 A LT6P0M05FM

Protection unit

Type
without fault memory Connection by cage connectors a 50/60 Hz c On front panel: fault and voltage signalling indicator a 50/60 Hz c a 50/60 Hz or c with fault memory

with automatic reset with thermistor short-circuit detection Voltage 115 V 230 V 24 V 115/230 V 24/48 V 24230 V Output contact NC NC NC NC + NO NC + NO 2 CO Reference LT3SE00F LT3SE00M LT3SE00F LT3SA00M LT3SA00ED LT3SA00MW

On front panel: fault and voltage signalling indicator, Test and Reset button a 50/60 Hz 400 V 24/48 V 115/230 V c a 50/60 Hz or c 24/48 V 24230 V NC + NO NC + NO NC + NO NC + NO 2 CO LT3SM00V LT3SM00E LT3SM00M LT3SM00ED LT3SM00MW

Accessories
Type
Normal operating temperature (NOT) Integrated triple probes Normal operating temperature (NOT) Surface probes PTC thermistor probes for LT3 relays 90 C DA1TT090 60 C DA1TS060 110 C DA1TT110 70 C DA1TS070 120 C DA1TT120 80 C DA1TS080 130 C DA1TT130 90 C DA1TS090 140 C DA1TT140 100 C DA1TS100 150 C DA1TT150 160 C DA1TT160 170 C DA1TT170

Other versions: please consult our Customer Care Centre.

32

TeSys
Vario

Switch disconnectors
12175 A

1/L1

3/L2 4/T2

2/T1

Type
Colour: Handle / Front plate Front plate dimensions (mm) Fixing Degree of protection Rated insulation voltage (Ui) Thermal current in open air (Ith) 12 A 20 A

6/T3

5/L3

Mini-Vario for standard applications


Door mounting Red / Yellow 60 x 60 22.5 mm IP 20 690 V VCDN12 VCDN20 VBDN12 VBDN20 Black / Black Backplate mounting in enclosure Red / Yellow 60 x 60 22.5 mm IP 20 690 V VCCDN12 VCCDN20

1/L1

3/L2 4/T2

2/T1

Type
Colour: Handle / Front plate Front plate dimensions (mm) Fixing Degree of protection Rated insulation voltage (Ui) Thermal current in open air (Ith) 12 A 20 A 25 A 32 A 40 A 63 A 80 A 125 A 175 A

6/T3

5/L3

Vario for high performance applications


Door mounting Red / Yellow Black / Black Red / Yellow Black / Black Red / Yellow 60 x 60 22.5 mm IP 20 690 V VCD02 VCD01 VCD0 VCD1 VCD2 VBD02 VBD01 VBD0 VBD1 VBD2 60 x 60 4 screws IP 20 690 V VCF02 VCF01 VCF0 VCF1 VCF2 VCF3 VCF4 VBF02 VBF01 VBF0 VBF1 VBF2 VBF3 VBF4 90 x 90 4 screws IP 20 690 V VCF5 VCF6 Backplate mounting in enclosure Red / Yellow 60 x 60 22.5 mm 4 screws IP 20 690 V VCCD02 VCCD01 VCCD0 VCCD1 VCCD2 IP 20 690 V VCCF02 VCCF01 VCCF0 VCCF1 VCCF2 VCCF3 VCCF4 90 x 90 4 screws IP 20 690 V VCCF5 VCCF6

Add-on modules
Main pole modules Switch rating References Neutral pole module with early make and late break contacts Switch rating References Earthing module Switch rating References Auxiliary contact block modules Contact type References

For mini-Vario
12 A VZN12 1220 A VZN11 1220 A VZN14 NO VZN05 NC VZN06 20 A VZN20

For Vario
12 A VZ02 1240 A VZ11 1240 A VZ14 NO + NC VZ7 20 A VZ01 25 A VZ0 32 A VZ1 40 A VZ2 63 A VZ3 80 A VZ4

63 and 80 A VZ12 63 and 80 A VZ15 NO + NO VZ20

125 and 175 A VZ13 125 and 175 A VZ16

Other versions: please consult our Customer Care Centre.

33

TeSys
GV2, LC

Combination motor starters


0.0615 kW

D.O.L. starters
with circuit-breaker Level of service Power at 400 V Type of components Basic reference, to be completed Coordination: Up to: Type 1 5.5 kW incorporated in the circuit-breaker GV2ME GV2DM GV2DP 15 kW Combination automatic motor starter with overload protection with fuse protection Type 2 37 kW Fuse carrier + plate-mounted contactor LC4D

Starters GV2-ME
Non-reversing Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 (kW) 400/415 V 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 440 V 0.37 0.55 0.75 1.1 1.5 2.2 4 5.5 500 V 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 914 170 GV2ME16 LC1K12 GV2ME16K1 GV2ME16K2 610 138 GV2ME14 LC1K09 GV2ME14K1 GV2ME14K2 46.3 78 GV2ME10 LC1K06 GV2ME10K1 GV2ME10K2 2.54 51 GV2ME08 LC1K06 GV2ME08K1 GV2ME08K2 1.62.5 33.5 GV2ME07 LC1K06 GV2ME07K1 GV2ME07K2 11.6 Setting range of thermal trips Fixed magnetic tripping current 13 Irth 22.5 GV2ME06 LC1K06 GV2ME06K1 GV2ME06K2 For customer assembly Motor circuit-breaker Contactor Factory assembled Basic reference, to be completed with code indicating control circuit voltage Reversing

Standard control circuit voltages (for other voltages, please consult your Regional Sales Ofce) Volts a 50400 Hz c (1) 24 B7 BW3 110 F7 220/230 M7 230 P7 230/240 U7 380/400 Q7 -

(1) Low consumption coil (1.5 W), wide range (0.71.3 Uc) and with integral suppression device as standard.

Other versions: please consult our Customer Care Centre.

34

D.O.L. starters GV2DM and GV3-DP


Non-reversing Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 (kW) 400/415 V 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 440 V 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 500 V 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 1318 1723 2025 2432 223 327 327 416 914 170 610 138 46.3 78 2.54 51 1.62.5 33.5 GV2ME07 GV2P07 GV2ME08 GV2P08 GV2ME10 GV2P10 GV2ME14 GV2P14 GV2ME16 GV2P16 GV2ME20 GV2P20 GV2ME21 GV2P21 GV2ME22 GV2P22 GV2ME32 GV2P32 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D12 LC1D25 LC1D18 LC1D25 LC1D25 LC1D25 LC1D25 LC1D25 LC1D32 LC1D32 GV2DM107 GV2DP107 GV2DM108 GV2DP108 GV2DM110 GV2DP110 GV2DM114 GV2DP114 GV2DM116 GV2DP116 GV2DM120 GV2DP120 GV2DM121 GV2DP121 GV2DM122 GV2DP122 GV2DM132 GV2DP132 GV2DM207 GV2DP207 GV2DM208 GV2DP208 GV2DM210 GV2DP210 GV2DM214 GV2DP214 GV2DM216 GV2DP216 GV2DM220 GV2DP220 GV2DM221 GV2DP221 GV2DM222 GV2DP222 GV2DM232 GV2DP232 11.6 22.5 0.631 13 0.400.63 8 0.160.25 0.250.40 Setting range of thermal trips Fixed magnetic tripping current 13 Irth 2.4 5 GV2ME02 GV2P02 GV2ME03 GV2P03 GV2ME04 GV2P04 GV2ME05 GV2P05 GV2ME06 GV2P06 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 LC1D09 GV2DM102 GV2DP102 GV2DM103 GV2DP103 GV2DM104 GV2DP104 GV2DM105 GV2DP105 GV2DM106 GV2DP106 GV2DM202 GV2DP202 GV2DM203 GV2DP203 GV2DM204 GV2DP204 GV2DM205 GV2DP205 GV2DM206 GV2DP206 For customer assembly Motor circuit-breaker Contactor Factory assembled Basic reference, to be completed with code indicating control circuit voltage Reversing

D.O.L. starters GV3 + LC1D


Non-reversing Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 (kW) 400/415 V 18,5 22 30 440 V 18,5 22 30 500 V 22 30 37 3040 3040 3750 4865 Setting range of thermal trips Fixed magnetic tripping current 13 Irth 560 560 700 910 GV3P401 (1) GV3P401 (1) GV3P501 (1) GV3P651 (1) LC1D40A LC1D40A LC1D50A LC1D65A LAD9R3 LAD9R3 LAD9R3 LAD9R3 For customer assembly Motor circuit-breaker Contactor Reference of accessory to be ordered for assembly of motor starter (2) Reversing

(1) Circuit-breaker GV3P without downstream EverLink terminal block. A standard GV3P can also be used by removing the downstream terminal block. (2) For side by side circuit-breaker/contactor mounting, order accessory GV3S.

Standard control circuit voltages (for other voltages, please consult your Regional Sales Ofce) Volts 24 220 a 50400 Hz c (3) B7 BD M7

230 P7

(3) Low consumption coil, wide range (0.7 to 1.25 Uc) and with suppression device as standard (bidirectional peak limiting diode).
Other versions: please consult our Customer Care Centre.

35

TeSys U

Starter-controller for 3-phase motors


STANDARD motor starter

=
Function characteristics, LUB + LUCA Maximum motor power
< 400/415 V - Thermal overload protection against: short-circuit, overcurrent, phase failure or imbalance, insulation breaks (equipment only). - Manual reset following thermal fault. 0.09 kW 0.25 kW 1.5 kW 5.5 kW 7.5 kW 15 kW LUB12 LUB12 LUB12 LUB12 LUB32 LUB32

+
Power base
Non-reversing Reversing (1) LU2B12pp LU2B12pp LU2B12pp LU2B12pp LU2B32pp LU2B32pp

Standard control unit


Class 10 (2) LUCA6Xpp LUCA1Xpp LUCA05pp LUCA12pp LUCA18pp LUCA32pp 0.150.6 A 0.351.4 A 1.255 A 312 A 4.518 A 832 A Setting range

ADVANCED motor starter

Function characteristics, LUB + LUCA

Maximum motor power


< 400/415 V 0.09 kW 0.25 kW 1.5 kW 5.5 kW 7.5 kW 15 kW

Power base
Non-reversing LUB120 LUB120 LUB120 LUB120 LUB320 LUB320

Advanced control unit


Class 10 (2) (3) LUCB6Xpp LUCB1Xpp LUCB05pp LUCB12pp LUCB18pp LUCB32pp Class 20 (2) LUCD6Xpp LUCD1Xpp LUCD05pp LUCD12pp LUCD18pp LUCD32pp 0.150.6 A 0.351.4 A 1.255 A 312 A 4.518 A 832 A Setting range

- Thermal overload protection against: short-circuit, overcurrent, phase failure or imbalance, insulation breaks (equipment only). - Manual reset following thermal fault. - Thermal overload test function. (3) For single-phase-motors, replace LUCBpppp by LUCCpppp.

MULTIFUNCTION motor starter

Function characteristics, LUB + LUCA

Maximum motor power


< 400/415 V 0.09 kW 0.25 kW 1.5 kW 5.5 kW 7.5 kW 15 kW

Power base
Non-reversing LUB120 LUB120 LUB120 LUB120 LUB320 LUB320

Multifunction control unit


Class 5 to 30 LUCM6XBL LUCM1XBL LUCM05BL LUCM12BL LUCM18BL LUCM32BL Setting range 0.150.6 A 0.351.4 A 1.255 A 312 A 4.518 A 832 A

- Thermal overload protection against: short-circuit, overcurrent, phase failure or imbalance, insulation breaks (equipment only). - Manual, automatic or remote reset, - Thermal overload test function, - Overtorque and no-load running, alarm, - Motor operation log, - Motor parameters display on LUCM.., PC or HMI, - Integrated Modbus communication.

(1) Complete the references of the power bases according to the following table. (2) Complete the references of the control units according to the following table. Standard control circuit voltages 24 V DC 24 V AC 48 V AC / 4872 V DC 110240 V AC / 110220 V DC

Example: LU2B12 Example: LUCA/B/D/M6X

pp pp BL B ES FU

Other versions: please consult our Customer Care Centre.

36

TeSys U

Starter-controller for 3-phase motors


Function modules

+
Type of optional function
Compatible with LUCA Compatible with LUCL Compatible with LUCB, LUCD Compatible with LUCM Output signal Reset References

=
Thermal overload alarm
NO NO YES NO 1 NO NA LUFW10

Thermal fault signalling


NO NO YES NO 1 NO +1 NC Manual LUFDH11 NO NO YES NO 1 NC Automatic or remote LUFDA01 LUFDA10 NO NO YES NO 1 NO

Motor load indication


NO NO YES YES 420 mA NA LUFV2

Communication modules

Type of communication
Only compatible with 24 V DC control units LUCA..BL, LUCB..BL, LUCD..BL, LUCM..BL Transfer speed Number of slaves Pre-wired coil connection (A1 A2) Connecting cable to PC References (1) Network Interface Module.

Modbus
YES 19.2 Kbps 31 per Modbus master LU9BN11C, LU9MRC

Modicon STB
YES

Probus DP CANopen
YES YES 20 K1 Mbps module LU9BN11L, LU9MRL TSXCANCpp LULC08

DeviceNet
YES

AS-Interface Parallel wiring


YES YES NA splitter box LU9Rxx TSXCDPppp LUFC00

Dpg. on NIM (1) 9.612 Mbps Dpg. on Network LU9BN11L, LU9MRL LU9RDDpp Interface Module module LU9BN11L, LU9MRL TSXPBSCApp LULC07

125500 Kbaud 167 Kbps 63 per DeviceNet module LU9BN11L, LU9MRL DeviceNet standard LULC09 ASILUFC51 master LU9BN11C, LU9MRC XZCG0142

125 per Probus DP 128 per CANopen

62 per AS-Interface 8 per LU9GC02

VW3 A8 306 Rpp LU9RCDpp, LUFC033 LULC15

Information carried by the Modbus, Modicon STB or CANopen bus


Type of control unit Start and Stop commands Starter status (ready, running, fault) Thermal alarm Remote reset via the bus Indication of motor load Signalling and fault differentiation Alarms (overcurrent, ) Remote programming and monitoring of all the functions Log function Monitoring function LUCAppBL X X LUCBppBL, LUCDppBL X X X X X X LUCMppBL X X X X X X X X X X

Contact blocks
Type of contact block
Signalling contacts 2 auxiliary contacts module References Screw clamp terminals Without connections of any fault position of control handle

Add-on
NC (95-96) NO (17-18) LUA1C11 LUA1C110 NO (97-98) NO (17-18) LUA1C20 LUA1C200

Auxiliary
NO (33-34) NO (43-44) LUFN20 NC (31-32) NO (43-44) LUFN11 NC (31-32) NC (41-42) LUFN02

Other versions: please consult our Customer Care Centre.

37

TeSys
LUTM
TeSys GV3L Circuit-breakers

Controller for 3-phase motors


MULTIFUNCTION protection

TeSys LC1D Contactor

=
Control base for use with contactors
TeSys D (LC1D..) LUTM10BL

+
Multifunction control unit
TeSys F (LC1F..) LUTM20BL Class 5 to 35 LUCMT1BL

Function characteristics

- Thermal overload protection against: short-circuit, overcurrent, phase failure or imbalance, insulation breaks (equipment only). - Manual, automatic or remote reset, - Thermal overload test function, - Overtorque and no-load running, alarm, - Motor operation log, - Motor parameters display on LUCM.., PC or HMI, - Integrated Modbus communication.

ADVANCED protection

Function characteristics

Control base for use with contactors


TeSys D (LC1D..) TeSys F (LC1F..) LUTM20BL LUTM10BL

Advanced control unit


Class 10 LUCBT1BL Class 20 LUCDT1BL

- Thermal overload protection against: short-circuit, overcurrent, phase failure or imbalance, insulation breaks (equipment only). - Manual reset following thermal fault. - Thermal overload test function.

Current transformers

Type of transformer
Supply voltage Operating current References Primary Secondary 24 V DC 30 A 1A LUTC0301 LUTC0501 LUTC01001 LUTC02001 LUTC04001 LUTC05001 50 A 100 A 200 A 400 A 800 A

Above 32 A, the TeSys U controller provides a motor starter management system solution identical to that provided by the TeSys U starter-controller. Used in conjunction with a short-circuit protection device and a contactor, it provides a motor starter whose functions are the same as those of a TeSys U starter-controller and, in particular, provides the following functions: overload protection, motor starter control and application monitoring. It comprises a control unit, whose adjustment range is compatible with the secondary of current transformers, and a control base that also enables the tting of a function module or communication module. It requires a 24 V DC external power supply.
Other versions: please consult our Customer Care Centre.

38

TeSys
LUTM

Controller for 3-phase motors


Function modules

+
Type of optional function
Compatible with LUCA Compatible with LUCL Compatible with LUCB, LUCD Compatible with LUCM Output signal Reset References

=
Thermal overload alarm
NO NO YES NO 1 NO NA LUFW10

Motor load indication


NO NO YES YES 420 mA NA LUFV2

TeSys rotating handles for Kit IP54 black handle IP54 kit red handle and yellow front IP65 kit red handle and yellow front

TeSys U LU9APN21 LU9APN22 LU9APN24

Communication modules

Type of communication
Only compatible with 24 V DC control units LUCA..BL, LUCB..BL, LUCD..BL, LUCM..BL Transfer speed Number of slaves Pre-wired coil connection (A1 A2) Connecting cable to PC References

Modbus
YES 19.2 Kbps 31 per Modbus master LU9BN11C, LU9MRC VW3 A8 306 Rpp LU9RDDpp LUFC033

Modicon STB
YES Dpg. on NIM (1) Dpg. on Network Interface Module LU9BN11L, LU9MRL LU9RCDpp LULC15

CANopen
YES 20 K1 Mbps 128 per CANopen module LU9BN11L, LU9MRL TSXCANCpp LULC08

DeviceNet
YES 125500 Kbaud 63 per DeviceNet module LU9BN11L, LU9MRL DeviceNet standard LULC09

Parallel wiring
YES NA 8 per LU9GC02 splitter box LU9Rxx TSXCDPppp LUFC00

Information carried by the Modbus, Modicon STB or CANopen bus


Type of control unit Start and Stop commands Starter status (ready, running, fault) Thermal alarm Remote reset via the bus Indication of motor load Signalling and fault differentiation Alarms (overcurrent, ) Remote programming and monitoring of all the functions Log function Monitoring function LUCBT1BL, LUCDT1BL X X X X X X LUCMT1BL X X X X X X X X X X
Other versions: please consult our Customer Care Centre.

39

TeSys

Enclosed motor starters


0.06132 kW

Starters
N

D.O.L.
0.0637 kW L L L L GV2ME GV3PC GV3CE LE2K LE2D 0.5530 kW L L L GV2LC GV-NGC 0.375.5 kW L L L L LE1GVME 0.2545 kW L L LE1M LE1D

N standard

Standard power ratings of 3-phase motors in category AC3 400/415 V Starters Isolating device manual auto switch-disconnector-fuse circuit-breaker fuse carrier Protection Communication Basic reference Non-reversing short-circuit overload

437 kW L L VFGE VCFNGE VFXGE

Reversing

Other versions: please consult our Customer Care Centre.

40

N safety applications N AS-Interface bus

2 stage
7.575 kW L L L L LE6D LE3D

standard star-delta 5.5132 kW L L LE3K LE3D LE3F

2.245 kW L L L L LE4K LE4D LE8K LE8D LE2D

0.0611 kW L L L L GV2ME

0.069 kW L L L L L LG1K LG1D

0.069 kW L L L L LG7K LG7D LJ7K LG8K LJ8K

0.065.5 kW L L L L L LF3M LF3P LF7P LF4M LF4P LF8P

Other versions: please consult our Customer Care Centre.

41

TeSys
Quickt

Installation system
Presentation

TeSys Quickt is a modular system which standardises and simplies the implementation of motor starters with its pre-wired control and power circuits. Installation of a motor starter becomes quick, simple, safe and exible. In addition, this system: b enables the motor starter to be customised at a later date, b reduces maintenance time and b optimises panel space by reducing the number of terminals and intermediate interfaces and the amount of ducting. The motor starters concerned are those created by combining: GV2 ME or GV3 P circuit-breakers, with an operating limit of 80% of the maximum current at an ambient temperature of 60 C, up to 690 V with 9 to 65 A TeSys D (LC1) contactors. This offer comprises components for pre-wiring b the power part, b the control part.

Components for pre-wiring the power part


b a power kit comprising, for each starter, a plate for mounting the contactor and the circuit-breaker, and two power connection modules, b a power splitter box for 2 or 4 starters, b an upstream terminal block for a power supply up to 60 A (16 mm2), b a downstream terminal block for connecting the motor power supply cables and the earth cables (6 mm2).

Components for pre-wiring the control part


b a control circuit connection module that mounts directly on the contactor and the circuit-breaker of each starter. This module integrates the status and control information of this particular motor starter. b a parallel wiring module enabling grouping of the information relating to each motor starter: v HE 10, intended for centralised applications. The information is transmitted to the PLC via the Modicon pre-wired system. v STB, intended for decentralised automation architectures. This module is integrated in an Modicon STB conguration for connection to the PLC via a eldbus.

925 A power pre-wiring components

Type
Maximum c.s.a. of connection Use Number of starters Reference

Terminal block Upstream


16 mm2 Splitter boxes supply LAD3B1

Downstream
6 mm2 Motor cables LAD331

60 A power splitter box Extension by LAD32p


2 LAD322 4 LAD324

Type
Composition Reference (1) For a reversing starter order 2 connection kits LAD252

Connection kit For D.O.L. starter (1)


1 mounting plate LAD311 for GV2ME 2 power connection modules LAD341 LAD252

Mounting plate for Power connection GV2 ME & contactor module


For 1 motor starter LAD311 LAD341

Other versions: please consult our Customer Care Centre.

42

Control-command pre-wiring components

Type
TeSys D coil voltage Type of coil control relay Type of motor starter Reference

Connection module
12250 V AC or 5130 V DC Electronic Direct LAD9AP31 Reversing LAD9AP32 24 V DC Without relay Direct LAD9AP3D1 Reversing LAD9AP3D2

Type
PLC/motor starter side connectors Reference

24 V DC parallel wiring module Splitter box


2 x HE10/8 x RJ45 LU9G02

Modicon STB parallel interface module


/4 x RJ45 STBEPI2145

Accessories

Type
Connectors Gauge / c.s.a. Reference L = 0.3 m 0.5 m 1m 2m 3m 5m

Connecting cables (1) From splitter box LU9G02 to the PLC


2 x RJ45 LU9R03 LU9R10 LU9R30 2 HE10 22 / 0.324 mm2 TSXCDP053 TSXCDP103 TSXCDP203 TSXCDP303 TSXCDP503 28 / 0.080 mm2 ABFH20H100 ABFH20H200 ABFH20H300 Bare wires and HE10 22 / 0.324 mm2 TSXCDP301 TSXCDP301

(1) From connection module LAD9AP3p to splitter box LU9G02 or module STBEPI2145

Type
Use Reference

Connectors Spring terminals

Connecting cable Self-stripping


Between communication module APP1Cp and splitter box LU9GG02 APP2AH40H060

External contact, auxiliary power supply APE1PRE21 APE1PAD21

Other versions: please consult our Customer Care Centre.

43

Components
Sodium vapour lamps
N low pressure

Lighting applications (AC5)

Non-corrected P (W) IB (A) C (F) Max. number of lamps 31.2 6 12 15 21 27 35 50 100 140 152 174 198 250 338 496
N high pressure

With parallel compensation 90 2.4 3 5 6 7 10 13 17 25 50 70 76 88 98 124 168 248 400 5 1 2 3 3 5 6 8 12 24 34 36 42 48 60 80 118 135 3.1 2 3 4 6 8 10 13 19 38 54 58 68 76 96 130 192 700 8.8 1 1 2 2 3 4 6 12 18 20 24 26 34 46 68 150 3.2 2 3 4 5 8 10 13 18 36 52 56 66 74 94 126 186 1000 12.4 1 1 2 2 3 4 8 14 16 18 20 24 32 48 180 3.3 2 3 4 5 7 10 12 18 36 50 54 64 72 90 122 180 200 3.4 2 3 4 5 7 9 12 17 34 48 54 62 70 88 118 174 35 0.3 17 40 50 63 86 110 140 200 400 560 606 700 792 1002 1352 1982 150 0.84 20 17 22 30 39 50 71 142 200 216 250 282 358 482 708 55 0.4 17 30 37 47 65 82 105 150 300 420 454 524 594 752 1014 1488 250 1.4 32 13 18 23 30 42 84 120 130 150 170 214 290 424 90 0.6 25 25 31 43 55 70 100 200 280 302 350 396 502 676 992 400 2.2 48 8 11 15 19 27 54 76 82 94 108 136 184 270 135 0.9 36 21 28 36 46 66 132 186 202 232 264 334 450 660 700 3.9 96 6 8 10 15 30 42 46 54 60 76 104 152 150 1 36 19 26 33 42 60 120 168 182 210 238 300 406 594 1000 5.5 120 6 7 10 20 30 32 38 42 54 74 108 LC1K09 D09, D12 D18 D25 D32, D38 D40A D50A, D65A D80, D95 D115, D150 F185 F225 F265 F330 F400 F500 F630, F800 180 1.2 36 15 21 27 35 50 100 140 152 174 198 250 338 496 200 1.3 36 14 20 25 32 46 92 128 140 162 182 252 312 458 LC1K09 D09, D12 D18 D25 D32, D38 D40A D50A, D65A D80, D95 D115, D150 F185 F225 F265 F330 F400 F500 F600, F800

55 1.6 5 7 9 11 16 20 26 37 75 104 114 130 148 188 254 372 250 3.2 2 3 4 5 8 10 13 18 36 52 56 66 74 94 126 186

according to P (W), per contactor 10

P (W) IB (A) C (F) Max. number of lamps

150 1.9 4 7 10 13 17 22 31 62 88 96 110 124 158 214 312

according to P (W), per contactor 6

Metal iodine vapour lamps


P (W) IB (A) C (F) Max. number of lamps 250 2.5 3 6 7 10 13 16 24 48 66 72 84 94 120 162 238 400 3.6 2 3 4 5 7 9 11 16 32 46 50 58 66 84 112 164 1000 9.5 1 1 2 2 3 4 6 12 18 20 22 24 32 42 62 2000 20 1 1 2 3 6 8 10 12 14 16 20 30 250 1.4 32 13 18 23 30 42 84 120 130 150 170 214 290 424 400 2 32 9 13 16 21 30 60 84 90 104 118 150 202 298 1000 5.3 64 4 6 7 11 22 32 34 40 44 56 76 112 2000 11.2 140 5 10 14 16 18 20 26 36 52 LC1K09 D09, D12 D18 D25 D32, D38 D40A D50A, D65A D80, D95 D115, D150 F185 F225 F265 F330 F400 F500 F630, F800

according to P (W), per contactor 4

Other versions: please consult our Customer Care Centre.

44

Incandescent and halogen lamps


P (W) IB (A) Max. number of lamps 60 0.27 35 77 92 129 163 207 296 430 466 710 770 888 1006 1274 1718 2328 2776 75 0.34 28 47 61 73 103 129 164 235 340 370 564 610 704 800 1010 1364 1850 2204 100 0.45 21 35 46 55 77 97 124 177 256 280 426 462 532 604 764 1030 1396 1666 150 0.68 14 23 30 36 51 64 82 117 170 184 282 304 352 400 504 682 924 1102 200 0.91 10 17 23 27 38 48 62 88 126 138 210 228 262 298 378 508 690 824 300 1.40 6 11 15 18 25 31 40 57 82 90 136 148 170 194 244 330 448 534 500 2.30 4 7 9 11 15 19 24 34 50 54 82 90 104 118 148 200 272 326 750 3.40 2 4 6 7 10 13 16 23 34 36 56 60 70 80 100 136 184 220 1000 4.60 2 3 4 5 7 9 12 17 24 26 40 44 52 58 74 100 136 162 LC1K09 D09, D12 D18 D25 D32, D38 D40A D50A, D65A D80, D95 D115 D150 F185 F225 F265 F330 F400 F500 F600 F800

according to P (W), per contactor 59

Fluorescent lamps with starter N single tting


Non-corrected P (W) IB (A) C (F) Max. number of lamps 20 0.39 24 53 66 89 112 143 205 410 492 532 614 696 882 1190 1612
twin tting

With parallel correction 65 0.70 13 22 30 37 50 62 80 114 228 274 296 342 388 490 662 698 2x65 2x7 2x10 2x14 2x18 2x26 2x32 2x40 2x58 2x118 2x142 2x154 2x178 2x202 2x256 2x346 2x468 80 0.80 12 20 26 32 43 55 70 100 200 240 260 300 340 430 580 786 2x80 2x5 2x8 2x12 2x14 2x20 2x26 2x34 2x48 2x96 2x116 2x126 2x146 2x166 2x210 2x282 2x384 110 1.2 8 13 17 21 29 36 46 66 132 160 172 200 226 286 386 524 2x110 2x4 2x6 2x8 2x10 2x14 2x18 2x24 2x36 2x72 2x86 2x94 2x108 2x124 2x156 2x210 2x286 20 0.17 5 56 94 123 152 205 258 329 470 940 1128 1224 1412 1600 2024 2728 3700 2x20 2x36 2x60 2x80 2x100 2x134 2x168 2x214 2x306 2x614 2x738 2x800 2x922 40 0.26 5 36 61 80 100 134 169 215 367 614 738 800 922 1046 1322 1724 2418 2x40 2x20 2x32 2x42 2x54 2x72 2x90 2x116 2x166 2x332 2x400 2x432 2x500 65 0.42 7 22 38 50 61 83 104 133 190 380 456 490 570 648 818 1104 1498 2x65 2x12 2x20 2x26 2x32 2x44 2x56 2x70 2x102 2x204 2x246 2x266 2x308 2x348 2x440 2x594 80 0.52 7 18 30 40 50 67 84 107 153 306 368 400 462 522 662 892 1210 2x80 2x10 2x16 2x20 2x26 2x36 2x44 2x58 2x82 2x166 2x200 2x216 2x250 2x282 2x358 2x482 2x654 110 0.72 16 22 29 36 48 61 77 111 222 266 288 332 378 478 644 874 2x110 LC1K09 D09, D12 D18 D25 D32, D38 D40A D50A, D65A D80, D95 D115, D150 F185 F225 F265 F330 F400 F500 F630, F800 2x7 2x12 2x16 2x20 2x26 2x32 2x42 2x60 2x122 2x148 2x160 2x184 2x208 2x264 2x356 2x484 LC1K09 D09, D12 D18 D25 D32, D38 D40A D50A, D65A D80, D95 D115, D150 F185 F225 F265 F330 F400 F500 F630, F800

40 0.45 21 35 46 57 77 97 124 177 354 426 462 532 604 764 1030 1398 2x40 2x11 2x18 2x24 2x30 2x42 2x52 2x68 2x96 2x194 2x234 2x254 2x292 2x332 2x420

according to P (W), per contactor 41

P (W) IB (A) Max. number of lamps

2x20 2x0.22 2x21 2x46 2x58 2x78 2x100 2x126 2x180 2x360 2x436 2x472 2x544 2x618 2x782

2x0.41 2x0.67 2x0.82 2x1.1

2x0.13 2x0.24 2x0.39 2x0.48 2x0.65

according to P (W), per contactor 2x36

2x1046 2x566 2x1322 2x716 2x1784 2x966

2x1054 2x566 2x1430 2x766

2x2418 2x1310 2x806

Other versions: please consult our Customer Care Centre.

45

Components

Capacitor switching
01000 kVAR

On-load capacitor switching


for bar-mounted contactors, a.c. control circuit Without damping resistor Rated operational voltage (V) Number of poles Max. operational current (A) 50 Hz 1300 1 80 160 240 2 80x2 160x2 240x2 3 80x3 160x3 240x3 1500 2 poles in series 2 x 2 poles in series 2000 3000 2 poles in series 2 x 2 poles in series 3 poles in series 160 280 280x2 240 240x2 280 180 Hz 60 125 190 60x2 125x2 190x2 60x3 125x3 190x3 125 220 220x2 190 190x2 220 CE5FB1111 CE5GB1111 CE5HB1111 CE5FB2111 CE5GB2111 CE5HB2111 CE5FB3111 CE5GB3111 CE5HB3111 CE5GB1211 CE5HB1211 CE5HB2211 CS5HB1211 CS5HB2211 CS5HB1311 1 + 3 staggered poles 280 220 CS6HB1411 1 + 2 staggered poles 240 190 CS6HB1311 1 + 2 staggered poles 160 280 125 220 CE6GB1311 CE6HB1311 2 + 2 staggered poles 240x2 190x2 CE6HB2211 1 + 1 staggered pole Basic reference, to be completed With damping resistor Number of poles Max. operational current (A) 50 Hz 80 160 240 180 Hz 60 125 190 CE6FB1211 CE6GB1211 CE6HB1211 Basic reference, to be completed

Standard control circuit voltages


a supply Volts 50 Hz (coil LX1) 110 F 125 127 G 200 L 220 M 240 U 250 380 Q 415 N 440 R 500 S

Other versions: please consult our Customer Care Centre.

46

Maximum operational power of contactors


N standard contactors

Operational power at 50/60 Hz 40 C 220 V 240 V kVAR 6 9 11 14 17 22 22 35 50 60 70 80 90 100 125 180 250 250 200 300 500 600
N special contactors

55 C 400 V 440 V kVAR 11 15 20 25 30 40 40 60 90 110 125 140 160 190 220 300 400 400 350 550 8350 1100 600 V 690 V kVAR 15 20 25 30 37 50 50 75 125 135 160 190 225 275 300 400 600 600 500 650 950 1300 220 V 240 V kVAR 6 9 11 14 17 22 22 35 38 40 50 60 75 85 100 125 190 190 180 250 400 500 400 V 440 V kVAR 11 15 20 25 30 40 40 60 75 85 100 110 125 140 160 220 350 350 350 500 750 1000 600 V 690 V kVAR 15 20 25 30 37 50 50 75 80 90 100 110 125 165 200 300 500 500 500 600 750 1000

Peak current

Contactor size

A 560 850 1600 1900 2160 2160 3040 3040 3100 3300 3500 4000 5000 6500 8000 10000 12000 14200 25000 25000 25000 25000 LC1D09, D12 LC1D18 LC1D25 LC1D32, D38 LC1D40A LC1D50A LC1D65A LC1D80, D95 LC1D115 LC1D150 LC1F185 LC1F225 LC1F265 LC1F330 LC1F400 LC1F500 LC1F630 LC1F800 LC1BL LC1BM LC1BP LC1BR

Operational power at 50/60 Hz 55 C 220 V 240 V kVAR 6.7 8.5 10 15 20 25 40 400 V 440 V kVAR 12.5 16.7 20 25 33.3 40 60 660 V 690 V kVAR 18 24 30 36 48 58 92 NO 1 1 1 1 1 1 1 NC 1 2 1 2 1 2 1 2 2 2 2 N.m 1.2 1.2 1.7 1.7 1.9 1.9 2.5 2.5 5 5 9 LC1DFK11 LC1DFK02 LC1DGK11 LC1DGK02 LC1DLK11 LC1DLK02 LC1DMK11 LC1DMK02 LC1DPK12 LC1DTK12 LC1DWK12 Instantaneous auxiliary contacts Tightening torque on cable end Basic reference, to be completed

Standard control circuit voltages


a supply Volts 50/60 Hz (coil LX1) 24 B7 42 D7 48 E7 110 F7 115 FE7 220 M7 230 P7 240 U7 380 Q7 400 V7 415 N7 440 R7

Other versions: please consult our Customer Care Centre.

47

Components

Heating applications and changeover contactor pairs


02750 A

Maximum operational current (device in open air)


Contactors
N 3-pole N 4-pole

LC1-/LP1- LC1-/LP1- LC1K09 K12 K09004 A A kW kW kW kW kW kW kW 20 20 8 8 14 14 15 17 22 20 20 8 8 14 14 15 17 22 D09

LC1DT20

LC1D12 DT25 DT20 25 25 9 9 15 17 18 20 27

LC1D18 DT32 DT25 32 32 11 12 20 21 23 23 34

LC1D25 DT40 DT32 40 40 14 15 25 27 29 33 43

LC1D32 DT40 50 50 18 19 31 34 36 41 54

LC1D38

LC1D40A DT60A

LC2- changeover contactor pairs, factory assembled Operational current in AC-1, in A, according to ambient temperature Maximum operational power 60C 40C 60C 70C 220/230 V 240 V 380/400 V 415 V 440 V 500 V 660/690 V

K12004 25 25 9 9 15 17 18 20 27 20 20 8 8 14 14 15 17 22

50 50 18 19 31 34 36 41 54

60 60 21 23 37 41 43 49 65

Increase in operational current by parallel connection of poles Apply the following coefcients to the currents or powers above; these coefcients take into account an often unbalanced distribution of current between the poles: N 2 poles in parallel K = 1.6 N 3 poles in parallel K = 2.25 N 4 poles in parallel K = 2.8

Connection accessories for heating applications


Paralleling links for:
N TeSys K

Reference 2 poles 4 poles 2 poles with screw clamp terminals with screw clamp terminals D09D38 DT20 and DT25 (4P) DT32DT40 (4P) D40AD65A D80 3 poles D09D38 D40AD65A D80 4 poles DT20DT25 D40AD65A D80 LA9E01 LA9E02 LA9D2561 LA9D1261 LADD96061 LAD9P32 LA9D80961 LAD9P3 (1) LAD9P33 LA9D80962 LA9D1263 2 x LAD-9P33 LA9D80963 LA9FF602 LA9FG602 LA9FH602 LA9FK602 LA9FL602

N TeSys D

N TeSys F

2 to 2

LC1F1154 LC1F1504, F1854 LC1F2254, F2654, F3304, F4004 LC1F5004 LC1F6304

(1) Link that can be split, allowing parallel connection of 2 poles

Other versions: please consult our Customer Care Centre.

48

LC1D50A

LC1D65A DT80A

LC1D80 D80004 125 125 45 49 78 85 90 102 135

LC1D115

LC1F185

LC1F225 F2254 315 280 200 100 110 175 185 200 220 300

LC1F265 F2654 350 300 250 120 125 210 220 230 270 370

LC1F330

LC1F400

LC1F500

LC1F630

LC1F780

LC1F800

LC1BL

LC1BM

LC1BP

LC1BR

D115004 F1854 250 200 80 83 135 140 150 170 235 275 275 180 90 100 165 170 180 200 280

80 80 29 31 50 54 58 65 86

80 80 29 31 50 54 58 65 86

400 360 290 145 160 250 260 290 320 400

500 430 340 170 180 300 310 330 380 530

700 580 500 240 255 430 445 370 660 740

1000 850 700 350 370 600 630 670 750 1000

1600 1350 1100 550 570 950 1000 1050 1200 1650

1000 850 700 350 370 600 630 670 750 1000

800 700 600 300 330 500 525 550 600 800

1250 1100 900 425 450 800 825 850 900 1100

2000 1750 1500 700 800 1200 1250 1400 1500 1900

2750 2400 2000 1000 1100 1600 1700 2000 2100 2700

Other versions: please consult our Customer Care Centre.

49

Components

Accessories for changeover contactor pairs


02750 A

Mounting accessories for changeover contactor pairs


(for customer assembly) Contactor type 2 contactors, vertically mounted
N 4-pole changeover pairs with locking device components

Set of power connections

Mechanical interlock

Contactor type

Set of power connections

Mechanical interlock

LC1B

EZ2LB0601

2 identical contactors, horizontally mounted


N with electrical interlocking kit for the contactors

LC1DT20DT40 LP1D80004
N without electrical interlocking (2)

LAD-T9R1V (1) LA9D8070 LAD-T9R1 (2)

LA9D8002 LAD4CM (3)

LC1D115004 LP1D80004

LA9D11570 LA9D8070

LA9D11502 LA9D80978

N mechanical interlock with integral electrical interlocking

LC1DT20DT40 LC1DT60A & LC1DT80A


N 4-pole changeover pairs

2 contactors of identical rating, horizontally mounted LC1F1154 LC1F1854 LC1F2654 LC1F4004 LC1F6304 LC1D115 et D150 LA9FF977 LA9FG977 LA9FH977 LA9FJ977 LA9FL977 LA9D11571 LA9FF970 LA9FG970 LA9FJ970 LA9FJ970 LA9FL970 LA9D11502 LC1F1504 LC1F2254 LC1F3304 LC1F5004 LA9F15077 LA9F22577 LA9FJ977 LA9FK977 LA9FF970 LA9FG970 LA9FJ970 LA9FJ970

N 3-pole changeover pairs with electrical interlocking

reversers assembled using 2 contactors, vertically mounted


N 4-pole changeover pairs using contactors of identical rating (3) N 3 or 4-pole changeover pairs using contactors of different rating

At bottom LC1F1154 or F1505 LC1F1854 LC1F2254 LC1F2654 or F3304 LC1F4004 LC1F5004 LC1F6304 LC1F7804 (3) (3) (3) (3) (3) (3) (3) (4) LA9FF4F LA9FG4G LA9FG4G LA9FH4H LA9FJ4J LA9FK4K LA9FL4L LA9FX971 (4) LC1F185 or F1854 or LC1F225 or F2254 LC1F115 or F1154 or LC1F150 or F1504

At top LC1F185 or F1854 LC1F225 or F2254 LC1F265 or F2654 LC1F300 or F3304 LC1F400 or F4004 LC1F500 or F5004 LC1F630, F6304 or F800 LC1F265 or F2654 LC1F330 or F3304 LC1F400 or F4004 LC1F500 or F5004 LC1F630, F6304 or F800 LA9FG4F LA9FG4F LA9FH4F LA9FH4F LA9FJ4F LA9FK4F LA9FL4F LA9FH4G LA9FH4G LA9FJ4G LA9FK4G LA9FL4G LA9FJ4H LA9FK4H LA9FL4H LA9FK4J LA9FL4J LA9FL4K

LC1F265 or F2654 or LC1F330 or F3304 LC1F400 or F4004 LC1F500 or F5004 (1) Including mechanical interlock. (2) Order separately 2 auxiliary contact blocks LAD-N1 t o obtain electrical interlocking between the two contactors. (3) Power connections to be made by the customer. (4) Double mechanical interlock mechanism with 2 interlock connecting rods and 4 power connecting links.

LC1F400 or F4004 LC1F500 or F5004 LC1F630, F6304 or F800 LC1F500 or F5004 LC1F630, F6304 or F800 LC1F630, F6304 or F800

Other versions: please consult our Customer Care Centre.

50

TeSys

Notes

Other versions: please consult our Customer Care Centre.

51

Schneider Electric Industries SAS


Head Ofce 35, rue Joseph Monier - CS 30323 F92500 Rueil-Malmaison Cedex France The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specic user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specic application or use thereof. Neither Schneider Electric nor any of its afliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. Design : IGS-CP Photos : Schneider Electric Print : ART. 005006 01/2012 - V9.0

www.schneider-electric.com

DIA1ED2040401EN