Condition Monitoring Tests on Power Transformers Test Report 2009


Customer:

Kind Attn: Mr.

Ref: Work Order No.:

Shanthala, No-24, Priyadarshini Colony, Gokul Road, Hubli - 580 030. Karnataka (India) Phone: +91-0836 - 2332540, 2335936, 2335934,Fax: 0836 2334908, Mobile: 94481-34362, E-mail:mkadappa@sify.com,customercare@shanthalaindia.com. Website: www.shanthalaindia.com

INDEX
SL NO. SL. NO.

Particulars
Make Bharath Bijilee Bharath Bijilee
IDENTIFICATION

Page Nos.

01 02

2698/2 4470/1

Transformer No-02 Transformer No-01

01 of 24 01 of 21

Ref: SPL/CMT-Off Line/ To, M/s.

/2009/

Date: 23/06/2009

Kind Attn: Mr. Dear Sir, Sub: Condition Monitoring Tests on Transformers Test Report Ref: Work Order No.: Test Report No.: 073-2/09-10, Dated: 09-05-2009. Thank you very much for giving us an opportunity to serve you. Please find enclosed here with the Test Report of Condition Monitoring Tests on Two Nos. of Transformers,. We have also enclosed Service Bill and the Bill No. is 0282, for the above work. We request you to settle the same at the earliest. Kindly arrange to send the Cheque/DD in the name of M/s. Shanthala Power Limited, Hubli. Thanking you. Yours faithfully, For Shanthala Power Limited

(Vinoda. N.) Chief Executive Officer Enclosures: I. Test Report: Three Set 1. Transformers Test Report 2. II Bill 1. 2. 3. Calibration Certificates Service Bill Service Tax Certificate Pan No Certificate

: : : : :

21+24=45 Pages Annexure 02 Page(In Duplicate) 02 Page 01 Page

NABL Accredited Laboratory for Transformer Oil Testing (1) BDV (100kV) (2) Water Content (3) Flash Point (4) Tan Delta (5) Resistivity (6) Sludge (7) Acidity (8) IFT (9) DGA (10) Furan Analysis

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 073/09-10 PAGE: 01 OF 24

TRANSFORMER-TEST REPORT -1

Test Report No. Customers Address

: :

073/09-10 & 17/06/2009

Customers Reference Particulars of Equipment Tested Plant Location Serial No. Customer Identification Make Transformer Rating Voltage Vector Group Year of Manufacture Phase Date(s) of Test(s) Winding Temperature Oil Temperature Atmospheric Temperature Weather Condition Particulars of Tests Conducted Customers Requirements Calibration Certificate s : : : : : : : : : : : : : : :

Work Order No.:

Power Transformer-2 Out Door Substation 2698/2 Transformer -2 Bharath Bijilee 15 MVA : YNyn0 1985 3 14th to 15th May 2009 : -450C Dry Condition Monitoring Tests Condition Monitoring Tests : Annexure 450C 132kV/6.9kV

Coordinated By Mr. S. Santhosh Kumar Mr. M. Rama Raju


Sr. Engineer (Elect.,)

Tested Team Mr. Vinod N. CEO Mr. Basavaraj Avali Mr. Dyamanna

Jr. Test Engineer

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030

TEST REPORT NO. 073/09-10

FORMAT NO.: SPL/TR-02

Calibration & Test Report Section


V/S

PAGE: 02 OF 24

MEASUREMENT OF IR TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature Voltage Year of Manufacture : : : : : 2698/2

TIME

Power Transformer -2
14th to 15th May 2009 450C : 1985 132kV/6.9kV

TEST RESULTS

SL NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

TIME 10th Sec 20th Sec 30th Sec 40th Sec 50th Sec 01st Min 02nd Min 03rd Min 04th Min 05th Min 06th Min 07th Min 08th Min 09th Min 10th Min

HV to LV at 5kV 3.0 G 3.2 G 3.8 G 3.9 G 4.0 G 4.0 G 4.2 G 4.5 G 4.5 G 4.5 G 4.5 G 4.5 G 4.5 G 4.5 G 4.5 G

HV to GND at 5kV 1.8 G 2.0 G 2.0 G 2.0 G 2.0 G 2.1 G 2.2 G 2.2 G 2.2 G 2.2 G 2.2 G 2.2 G 2.2 G 2.2 G 2.2 G

LV to GND at 2.5kV 1.5 G 1.6 G 1.8 G 2.0 G 2.1 G 2.2 G 2.5 G 2.5 G 2.5 G 2.5 G 2.5 G 2.5 G 2.5 G 2.5 G 2.5 G

Note: 1) for test conditions please refer page No. 24 of 24 2) *Average Temperature (Winding + Atmospheric) =450+450450C

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030

TEST REPORT NO. 073/09-10

FORMAT NO.: SPL/TR-02

Calibration & Test Report Section

PAGE: 03 OF 24

MEASUREMENT OF IR,PI AND ABSORPTION RATIO TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature Voltage Year of Manufacture : : : : : 2698/2

Power Transformer -2
14th to 15th May 2009 450C : 1985 132kV/6.9kV

TEST RESULTS

SL No.

Mode of Test

Voltage (kV) 30th Sec

IR Values in G PI 60th Sec 600th Sec

DC Absorption Ratio

HV-LV

3.8

4.0

4.5

1.12

1.05

HV-GND

2.0

2.1

2.2

1.04

1.05

LV-GND

2.5

1.8

2.2

2.5

1.13

1.22

Polarization Index 600 Seconds IR Value PI = ------------------------------60 Seconds IR Value

Dielectric Absorption Ratio DA 60 Seconds IR Value = ------------------------------30 Seconds IR Value

Note: 1) for test conditions please refer page No. 24 of 24 2) *Average Temperature (Winding + Atmospheric) =450+450450C

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 073/09-10 PAGE: 04 OF 24

5 4.5 4 IR Values in G 3.5 3 2.5 2 1.5 1 0.5 0

IR Values v/ s Time in (Sec.,) of Transformer, Sl.No.: 2698/ 2 4.5 3.8 4

2 1.8

2.2 2.1

2.5 2.2

HV-LV 30
1

60
2

600
3

HV-GND LV-GND

Time in Seconds

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 073/09-10 PAGE: 05 OF 24

MEASUREMENT OF CAPACITANCE, TAN DELTA AND LEAKAGE CURRENT ON WINDINGS TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature Voltage Year of Manufacture : : : : : 2698/2

Power Transformer -2
14th to 15th May 2009 450C : 1985 132kV/6.9kV

TEST RESULTS Mode of Test Grounded Winding Voltage (kV) 2.5 HV-LV (UST) Nil 5.0 7.5 10.0 2.5 HV-GND (GST) 5.0 LV 7.5 10.0 LV-GND (GST) 2.5 HV 5.0 Current (mA) 6 12 20 25 6 12 20 26 2 24 Capacitance (pF) MRXC 4076.74 4076.84 4076.84 4076.84 7254.67 7255.58 7255.58 7254.97 14170.69 14170.69 Tan Delta (Absolute) 0.00587 0.00520 0.00520 0.00520 0.00660 0.00728 0.00728 0.00728 0.00972 0.00972

Note: 1) for test conditions please refer page No. 24 of 24 2) *Average Temperature (Winding + Atmospheric) =450+450450C

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 073/09-10 PAGE: 06 OF 24

0.012

Voltage v/ s Tan Delta on Transformer, Sl No.: 2698/ 2

0.01 Tan Delta (Absolute)

0.00972

0.00972

0.008 0.00728 0.006 0.0066 0.00587 0.0052 0.004 0.0052 0.0052 0.00728 0.00728

0.002

2.5

7.5

10 HV-LV HV-GND LV-GND

Voltage in kV

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 073/09-10 PAGE: 07 OF 24

MEASUREMENT OF CAPACITANCE, TAN DELTA ON HV BUSHINGS TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature Voltage Year of Manufacture : : : : : 2698/2

Power Transformer -2
14th to 15th May 2009 450C : 1985 132kV/6.9kV

Name Plate R Sl No. 51741 Make: CG R/V: 142kV YOM: 1999 Current: 800A Type: Condenser Y Sl No. 55976 Make: CG R/V: 145kV YOM: 1998 Current: 800A Type: Condenser B Sl No. -Make: -R/V: 145kV YOM: -Current: 800A Type: Condenser

Mode of Test

TEST RESULTS Voltage Capacitance (pF) (kV) 2.5 5.0 7.5 10.0 2.5 244.53 244.49 244.49 244.49 251.54 251.54 251.54 251.54

Tan Delta (Absolute) 0.00669 0.00668 0.00668 0.00668 0.00552 0.00552 0.00552 0.00552

HV to Bushing Tan Delta Point (UST)

5.0 7.5 10.0

**Could not be balanced

Note: 1) for test conditions please refer page No. 24 of 24 2) *Average Temperature (Winding + Atmospheric) =450+450450C 3) ** See the pages enclosed along with report and recommendation.

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 073/09-10 PAGE: 08 OF 24

0.008 0.007 0.006

Voltage v/ s Tan Delta on HV Bushing, Sl No.: 2698/ 2

0.00669 0.00552

0.00668 0.00552

0.00668 0.00552

0.00668 0.00552

Tan Delta (Absolute)

0.005 0.004 0.003 0.002 0.001 0

2.5

7.5

10 R

Voltage in kV

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 073/09-10 PAGE: 09 OF 24

MEASUREMENT OF DC WINDING RESISTANCE TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature Voltage Year of Manufacture : : : : : 2698/2

Power Transformer -2
14th to 15th May 2009 450C : 1985 132kV/6.9kV

OLTC Position 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17

Current (mA) 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

TEST RESULTS Measurement of DC Winding Resistance in m Phase (R-N) 4207 4080 4040 4005 3770 3640 3611 3563 3516 3470 3421 3378 3331 3285 3235 3193 3145 Phase (Y-N) 3901 3850 3804 3765 3712 3660 3615 3568 3522 3470 3430 3380 3335 3290 3238 3199 3154 Phase (B-N) 3886 3837 3789 3747 3701 3657 4016 3581 3537 3474 3425 3386 3339 3287 3259 3201 3197

Measurement of Winding Resistance in m (LV Side) Sl No. Current (A) Phase (r-n) -1 8.3 Phase (y-n) 7.9 Phase (b-n) 8.0

Note: 1) for test conditions please refer page No. 22 of 22 2) *Average Temperature (Winding + Atmospheric) =450+450450C

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 073/09-10 PAGE: 10 OF 24

MEASUREMENT OF HIGH VOLTAGE EXCITATION CURRENT ON HV WINDINGS TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test Atmospheric Temperature Voltage Year of Manufacture : : : : : 2698/2

Power Transformer -2
14th to 15th May 2009 450C : 1985 132kV/6.9kV

Tested Phase

TEST RESULTS Applied Voltage (kV) 0.5

Measured Current (mA) 5.0 7.0 9.0 11.0 12.0 4.0 5.0 7.0 8.0 9.0 5.0 7.0 9.0 10.0 11.0

R-N

1.0 1.5 2.0 2.5 0.5 1.0

Y-N

1.5 2.0 2.5

0.5 B-N 1.0 1.5 2.0 2.5

Note: 1) for test conditions please refer page No. 24 of 24 2) *Average Temperature (Winding + Atmospheric) =450+450450C

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 073/09-10 PAGE: 11 OF 24

MEASUREMENT OF MAGNETIC BALANCE TEST TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature Voltage Year of Manufacture : : : : : 2698/2

Power Transformer -2
14th to 15th May 2009 450C : 1985 132kV/6.9kV

TEST RESULTS

Applied Voltage (V) R-N 226.9 Y-N 239.6 B-N 238.1 Y-N 206.5 R-N 106.1 R-N 26.12

Measured Voltage (V) B-N 26.12 B-N 132.2 Y-N 218.6

Note: 1) for test conditions please refer page No. 24 of 24 2) *Average Temperature (Winding + Atmospheric) =450+450450C

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 073/09-10 PAGE: 12 OF 24

MEASUREMENT OF MAGNETIZATION CURRENT TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature Voltage Year of Manufacture : : : : : 2698/2

Power Transformer -2
14th to 15th May 2009 450C : 1985 132kV/6.9kV

TEST RESULTS

Tested Phase

Measured Voltage (V)

Measured Current (mA)

397

13.85

Y B

399

15.93

399

15.95

Note: 1) for test conditions please refer page No. 24 of 24 2) *Average Temperature (Winding + Atmospheric) =450+450450C

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 073/09-10 PAGE: 13 OF 24

MEASUREMENT OF NEUTRAL FLOATING POINT TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature Voltage Year of Manufacture : : : : : 2698/2

Power Transformer -2
14th to 15th May 2009 450C : 1985 132kV/6.9kV

TEST RESULTS

Voltage Applied Across HV Side (V) R-Y 397 Y-B 399 B-R 399

Voltage Measured (V) HV (Neutral)-GND 1.713

Note: 1) for test conditions please refer page No. 24 of 24 2) *Average Temperature (Winding + Atmospheric) =450+450450C

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 073/09-10 PAGE: 14 OF 24

MEASUREMENT OF TRANSFORMER TURN RATIO TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature Voltage Year of Manufacture : : : : : 2698/2

Power Transformer -2
14th to 15th May 2009 450C : 1985 132kV/6.9kV

TEST RESULTS Measurement of Turn Ratio Meter Correction Turns Ratio Reading factor (CF) (MRxCF) (MR) R 21.16 1.000 21.16 01 Y 21.16 1.000 21.16 B 21.16 1.000 21.16 R 19.88 1.000 19.88 02 Y 19.88 1.000 19.88 B 19.88 1.000 19.88 R 19.64 1.000 19.64 03 Y 19.64 1.000 19.64 B 19.64 1.000 19.64 R 19.24 1.000 19.24 04 Y 19.24 1.000 19.24 B 19.24 1.000 19.24 R 19.12 1.000 19.12 05 Y 19.12 1.000 19.12 B 19.12 1.000 19.12 R 18.90 1.000 18.90 06 Y 18.90 1.000 18.90 B 18.90 1.000 18.90 Note: 1) for test conditions please refer page No. 24 of 24 2) *Average Temperature (Winding + Atmospheric) =450+450450C OLTC Position Phase Angle of Deviation 0.02 0.02 0.02 0.08 0.01 0.01 0.01 0.01 0.01 0.08 0.08 0.08 0.04 0.04 0.04 0.08 0.08 0.08

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T) TEST REPORT NO. 073/09-10 PAGE: 15 OF 24

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

MEASUREMENT OF TRANSFORMER TURN RATIO TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature Voltage Year of Manufacture : : : : : 2698/2

Power Transformer -2
14th to 15th May 2009 450C : 1985 132kV/6.9kV

TEST RESULTS Measurement of Turn Ratio Meter Correction Turns Ratio Reading factor (CF) (MRxCF) (MR) R 18.68 1.000 18.68 07 Y 18.68 1.000 18.68 B 18.68 1.000 18.68 R 18.46 1.000 18.46 08 Y 18.46 1.000 18.46 B 18.46 1.000 18.46 R 18.12 1.000 18.12 09 Y 18.12 1.000 18.12 B 18.12 1.000 18.12 R 17.90 1.000 17.90 10 Y 17.90 1.000 17.90 B 17.90 1.000 17.90 R 17.60 1.000 17.60 11 Y 17.60 1.000 17.60 B 17.60 1.000 17.60 R 17.42 1.000 17.42 12 Y 17.42 1.000 17.42 B 17.42 1.000 17.42 Note: 1) for test conditions please refer page No. 24 of 24 2) *Average Temperature (Winding + Atmospheric) =450+450450C OLTC Position Phase Angle of Deviation 0.08 0.08 0.08 0.08 0.08 0.08 0.08 0.08 0.08 0.08 0.08 0.08 0.06 0.06 0.06 0.06 0.06 0.06

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 073/09-10 PAGE: 16 OF 24

MEASUREMENT OF TRANSFORMER TURN RATIO TRANSFORMER DETAILS:

Serial No. Customer Identification Date of Test *Average Temperature Voltage Year of Manufacture

: : : :

2698/2

Power Transformer -2
14th to 15th May 2009 450C : 132kV/6.9kV

1985

TEST RESULTS Measurement of Turn Ratio OLTC Position Phase R Y B R Y B R Y B R Y B R Y B Meter Reading (MR) 17.22 17.22 17.22 16.84 16.84 16.84 16.70 16.70 16.70 16.50 16.50 16.50 16.28 16.28 16.28 Correction factor (CF) 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 Turns Ratio (MRxCF) 17.22 17.22 17.22 16.84 16.84 16.84 16.70 16.70 16.70 16.50 16.50 16.50 16.28 16.28 16.28 Angle of Deviation 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06

13

14

15

16

17

Note: 1) for test conditions please refer page No. 24 of 24 2) *Average Temperature (Winding + Atmospheric) =450+450450C

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 073/09-10 PAGE: 17 OF 24

OIL-TEST REPORT

Test Report No. Customers Address

: :

073/09-10 & 17/06/2009

Customers Reference

Work Order No.:

Particulars of Sample Tested Date (S) of Test (S) No. Of Samples Tested Customers Requirement

: : : :

Transformer Oil
27th to 30 May 2009

03 (Three) BDV, Moisture Content, Tan Delta, Resistivity, Acidity, IFT, Sludge, Flash Point DGA & Furan Tests.

Whether Tests conducted as per Customers Requirement

Yes

Coordinated By Mr. S. Santhosh Kumar Mr. M. Rama Raju


Sr. Engineer (Elect.,)

Sample Collected By Mr. Vinod N. CEO Mr. Basavaraj Avali Mr. Dyamanna

Jr. Test Engineer

Note: 1. The test results relate only to the sample(s) tested. 2. ND-Not Detected. 3. The Limits for DGA is valid from last date of filtration. 4. If the last date of filtration is not specified the limits for DGA is considered from the Year of Installation. 5. Any Anomaly / Discrepancy in this test report / certificate should be brought to our notice within 60 days from the date of issue. 6. The Test Report Not to be reproduced except in full, without written approval from the laboratory.

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section TRANSFORMER DETAILS:

TEST REPORT NO. 073/09-10 PAGE: 18 OF 24

Serial Number Customer Identification Make Capacity: Voltage (HV/MV/LV) Year of Manufacture Year of Installation Last Date of Filtration Our Reference No. Date of Sample Collection Date of Receipt of the Sample Sample Tested on Appearance of the Oil Top Oil Temperature Winding Temperature Weather Condition Condition on Receipt OIL PARAMETERS: SL NO .

: : : : : : : : : : : : : : : : :

2698/2 Power Transformer -2 Bharath Bijilee 15MVA 132kV/6.9kV 1985 1985 2008 LT-0392/01 (Main Tank-Top) 14th May 2009 25th May 2009 27th to 30th 2009 Bright Yellow Colour 450C -Dry OK Reference Standard IS: 1866: 2000

TEST PARAMETERS Test Method IS: 6792-199250Hz2Hz Electrode Type: Brass Spherical, Electrode gap: 2.5mm IS: 13567-1992 Karl Fisher Titration Method 23010V IS: 6262-1971 50Hz2Hz Three terminal cell 250Vrms\mm: Average voltage gradient in the sample 23010V IS: 6103-1971 Three terminal cell250Vrms\mm: Average voltage gradient in the sample 23010V IS: 1448(P: 2)-1967 IS: 6104-1971 Ring Method

For Oil in Service Limits 72.5kV-170kV B-Class

TEST RESULTS

Break Down Voltage (BDV)/ DiElectric Strength) in kV, at a Temp: 27.90C, RH: 46% Moisture Content (Water Content) in ppm, at a Temp: 27.7 0C , RH:47% Tan Delta (DiElectric Dissipation Factor) in absolute, at a Temp: 900C, RH: 47%

>40kV 40 ppm Max 1.0 Absolute Min 0.1 X 10 -cm

70,72,76,66, 74,68=71.0 11

0.012

Resistivity (Specific Resistance) in -cm, at a Temp: 900C, RH: 47% Acidity (Neutralization Number) in mg KOH/g Interfacial Tension (IFT) in N/m, at a Temp: 271 0C Sludge/Sediment % by weight

12

2 x 1012

5 6 7

Max 0.3 mg KOH/g Min 0.015 Sludge should not be detected Min 140 o C

0.04 0.043 ND 156

IS 1866:2000 Annexure A (Clause-4.3) IS 1448(P: 21)-1992 Pensky 8 Martens closed cup Test Flash Point in 0C Method 23010V DISSOLVED GAS ANALYSIS: IS: 10593:1992 & 9434-1992 SL NO. CHARACTERISTICS 1 Methane PPM 50/70 2 Ethylene PPM 100/150 3 Ethane PPM 30/50 4 Acetylene PPM 20/30 5 Carbon Monoxide PPM 200/300 6 Carbon Dioxide PPM 3000/3500 7 Hydrogen PPM 100/150 8 Total Gas Content %by Volume --

03 04 02 04 34 1999 08 10.54

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 073/09-10 PAGE: 19 OF 24

FURAN ANALYSIS: ASTM D 5837-99


SL NO. 1 2 3 4 5 FURANIC COMPOUNDS (PPB) 5 Hydroxymethyl-2-Furaldehyde Furfuryl Alcohol 2 Furaldehyde 2 Acetyl Furan 5 Methyl 2 Furaldehyde Total

60.473 21.210 91.206 3.417 17.931


194.237

ANALYSIS & RECOMMENDATION:

For Analysis & Recommendation please refer Page No.: 24 OF 24

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report

TEST REPORT NO. 073/09-10 PAGE: 20 OF 24

Section TRANSFORMER DETAILS: Serial Number Customer Identification Make Capacity: Voltage (HV/MV/LV) Year of Manufacture Year of Installation Last Date of Filtration Our Reference No. Date of Sample Collection Date of Receipt of the Sample Sample Tested on Appearance of the Oil Top Oil Temperature Winding Temperature Weather Condition Condition on Receipt OIL PARAMETERS: SL NO . : : : : : : : : : : : : : : : : : 2698/2 Power Transformer -2 Bharath Bijilee 15MVA 132kV/6.9kV 1985 1985 2008 LT-0393/02(Main Tank-Bottom) 14th May 2009 25th May 2009 27th to 30th 2009 Bright Yellow Colour 450C -Dry OK Reference Standard IS: 1866: 2000 TEST PARAMETERS Test Method IS: 6792-199250Hz2Hz Electrode Type: Brass Spherical, Electrode gap: 2.5mm IS: 13567-1992 Karl Fisher Titration Method 23010V IS: 6262-1971 50Hz2Hz Three terminal cell 250Vrms\mm: Average voltage gradient in the sample 23010V IS: 6103-1971 Three terminal cell250Vrms\mm: Average voltage gradient in the sample 23010V IS: 1448(P: 2)-1967 IS: 6104-1971 Ring Method

For Oil in Service Limits 72.5kV-170kV B-Class

TEST RESULTS

Break Down Voltage (BDV)/ DiElectric Strength) in kV, at a Temp: 26.30C, RH: 45% Moisture Content (Water Content) in ppm, at a Temp: 26.9 0C , RH:46% Tan Delta (DiElectric Dissipation Factor) in absolute, at a Temp: 900C, RH: 46%

>40kV 40 ppm Max 1.0 Absolute Min 0.1 X 10 -cm

68,70,78,72,6 6 70=70.6671. 0 11

0.0088

Resistivity (Specific Resistance) in -cm, at a Temp: 900C, RH: 46% Acidity (Neutralization Number) in mg KOH/g Interfacial Tension (IFT) in N/m, at a Temp: 271 0C Sludge/Sediment % by weight

12

3 x 1012

5 6 7

Max 0.3 mg KOH/g Min 0.015 Sludge should not be detected Min 140 o C

0.12 0.032 ND 156

IS 1866:2000 Annexure A (Clause-4.3) IS 1448(P: 21)-1992 Pensky 8 Martens closed cup Test Flash Point in 0C Method 23010V DISSOLVED GAS ANALYSIS: IS: 10593:1992 & 9434-1992 SL NO. CHARACTERISTICS 1 Methane PPM 50/70 2 Ethylene PPM 100/150 3 Ethane PPM 30/50 4 Acetylene PPM 20/30 5 Carbon Monoxide PPM 200/300 6 Carbon Dioxide PPM 3000/3500 7 Hydrogen PPM 100/150 8 Total Gas Content %by Volume --

03 04 01 05 36 2143 08 11.04

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 073/09-10 PAGE: 21 OF 24

FURAN ANALYSIS: ASTM D 5837-99


SL NO. 1 2 3 4 5 FURANIC COMPOUNDS (PPB) 5 Hydroxymethyl-2-Furaldehyde Furfuryl Alcohol 2 Furaldehyde 2 Acetyl Furan 5 Methyl 2 Furaldehyde Total

50.226 47.219 98.771 00 29.431


225.647

ANALYSIS & RECOMMENDATION:

For Analysis & Recommendation please refer Page No.: 24 OF 24

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section TRANSFORMER DETAILS: Serial Number Customer Identification Make Capacity: Voltage (HV/MV/LV) Year of Manufacture Year of Installation Last Date of Filtration Our Reference No. Date of Sample Collection Date of Receipt of the Sample Sample Tested on Appearance of the Oil Top Oil Temperature Winding Temperature Weather Condition Condition on Receipt OIL PARAMETERS: SL NO . : : : : : : : : : : : : : : : : : 2698/2 Power Transformer -2 Bharath Bijilee 15MVA 132kV/6.9kV 1985 1985 2008 LT-0394/03(Main Tank-OLTC) 14th May 2009 25th May 2009 27th to 30th May 2009 Yellow Colour 450C -Dry OK Reference Standard IS: 1866: 2000 TEST PARAMETERS Test Method IS: 6792-199250Hz2Hz Electrode Type: Brass Spherical, Electrode gap: 2.5mm IS: 13567-1992 Karl Fisher Titration Method 23010V IS: 6262-1971 50Hz2Hz Three terminal cell 250Vrms\mm: Average voltage gradient in the sample 23010V IS: 6103-1971 Three terminal cell250Vrms\mm: Average voltage gradient in the sample 23010V IS: 1448(P: 2)-1967 IS: 6104-1971 Ring Method

TEST REPORT NO. 073/09-10 PAGE: 22 OF 24

For Oil in Service Limits 72.5kV-170kV B-Class

TEST RESULTS

Break Down Voltage (BDV)/ DiElectric Strength) in kV, at a Temp: 26.80C, RH: 44% Moisture Content (Water Content) in ppm, at a Temp: 26.6 0C , RH:46% Tan Delta (DiElectric Dissipation Factor) in absolute, at a Temp: 900C, RH: 45%

>40kV 40 ppm Max 1.0 Absolute Min 0.1 X 10 -cm

38,34,42,32 42,34=37.0 27

0.0081

Resistivity (Specific Resistance) in -cm, at a Temp: 900C, RH: 45% Acidity (Neutralization Number) in mg KOH/g Interfacial Tension (IFT) in N/m, at a Temp: 271 0C Sludge/Sediment % by weight

12

8 x 1012

5 6 7

Max 0.3 mg KOH/g Min 0.015 Sludge should not be detected Min 140 o C

0.04 0.042 ND 150

IS 1866:2000 Annexure A (Clause-4.3) IS 1448(P: 21)-1992 Pensky 8 Martens closed cup Test Flash Point in 0C Method 23010V DISSOLVED GAS ANALYSIS: IS: 10593:1992 & 9434-1992 SL NO. CHARACTERISTICS 1 Methane PPM 2 Ethylene PPM 3 Ethane PPM 4 Acetylene PPM 5 Carbon Monoxide PPM 6 Carbon Dioxide PPM 7 Hydrogen PPM 8 Total Gas Content %by Volume

23 38 03 532 30 475 11 12.55

Prepared By

Asst. Manager Analysis

(Gowri M. Patil)

Authorised Signatory

(Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 073/09-10 PAGE: 23 OF 24

FURAN ANALYSIS: ASTM D 5837-99


SL NO. 1 2 3 4 5 FURANIC COMPOUNDS (PPB) 5 Hydroxymethyl-2-Furaldehyde Furfuryl Alcohol 2 Furaldehyde 2 Acetyl Furan 5 Methyl 2 Furaldehyde Total

-------

ANALYSIS & RECOMMENDATION:

For Analysis & Recommendation please refer Page No.: 24 OF 24

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section ANALYSIS & RECOMMENDATION FOR TRANSFORMER SL NO.: 2698/2, ID No: Power Transformer -2

TEST REPORT NO. 073/09-10 PAGE: 24 OF 24

Analysis: Tests on Solid Insulation: The test results of IR Values, PI & DC absorption ratios are normal considering its age. The variation of Capacitance values with respect to voltage is normal and the Tan Delta values are within the permissible limits, i.e. <0.02absolute. Tests on Conductor & OLTC: The DC winding resistance values are normal as comparable with all the phases. The turns ratio measurements are normal as compared to name plate values. Measurement of Neutral Floating point is normal. Tests On Core Magnetization currents are normal. Magnetic Balance test results are normal. Test On Bushings: The variation of Capacitance values with respect to voltage is normal and the Tan Delta values are within the permissible limits, i.e. <0.007absolute for R&Y- phase. B-phase could not be balanced. Oil Parameters: The test parameters of the transformer oil samples are within permissible limits as per IS: 18662000 The maintenance of transformer oil in service. DGA: The gases generated are within the permissible limits as per relevant Standards. Furan Analysis: The total of the Furanic compounds is in the low reliability range. Conclusion: Solid insulation is normal. Conductor and core are normal. The results of Oil & DGA indicate normal internal condition of the Transformer. The total of the Furanic compounds is in low reliability range. B-Phase Bushing could not be balanced. Recommendation: All the tests should be carried out after one year to establish the trend analysis of Transformer & Oil. All the test results may be retained as bench mark for further analysis. One more furan test to be conducted within 6 months to know the increasing trend in the furanic compounds. B-Phase bushing is in good condition. For normal operation the condenser bushing test tap is earthed by screw cap with a centre pin which presses on the test tap for test purpose. The Cap was removed and test tap was connected to C and Tan Delta Bridge for measurement. Most likely this test Cap is grounded even when Cap is removed . So, C and Tan Delta Bridge could not be balanced. So, please refer these results to manufacturer for further action. In the next shutdown one more Megger, Tan Delta and other tests has to be carried out on Bushings. Note: Test conditions 1) Primary side : HV conductor removed from the Breaker side. 2) Secondary side : LT Breaker was made off.

Prepared By (Gowri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

FORMAT NO.: SPL/TR-02

Shanthala Power Limited


Test Inspection Consultancy Anything Anywhere Anytime

Condition Monitoring Tests on Transformers Test Report 2009

Customer: M/s.

Kind Attn: Mr. Ref: P.O. No.:

Shanthala, No-24, Priyadarshini Colony, Gokul Road, Hubli - 580 030. Karnataka (India) Phone: +91-0836 - 2332540, 2335936, 2335934,Fax: 0836 2334908, Mobile: 94481-34362, E-mail:mkadappa@sify.com,customercare@shanthalaindia.com. Website:

www.shanthalaindia.com

Ref: SPL/CMT-Off Line//2009/ To, M/s. Kind Attn: Mr. Dear Sir,

Date:06-10-2009

Sub: Condition Monitoring Test on Transformers, -Test Report. Ref: P.O. No.: Test Report No.: 0232/09-10, Dated: 07-09-2009. Thank you very much for giving us an opportunity to serve you. Please find enclosed here with the Test Report of Condition Monitoring Tests on Four Nos. of Transformers. We have also enclosed Service Bill and the Bill No. is 0635, for the above work. We request you to settle the same at the earliest. Kindly arrange to send the Cheque/DD in the name of M/s. Shanthala Power Limited, Hubli. Thanking you. Yours faithfully, For Shanthala Power Limited (Mr.Vinod. N.) Chief Executive Officer Enclosures: I. Test Report: 2. Transformers Test Report 3. Calibration Certificates II Bill 4. Service Bill 5. Service Tax Certificate 6. Pan No Certificate

: : : : :

17+17+17+22=73Pages Annexure 02 Page(In Duplicate) 02 Page 01 Page

NABL Accredited Laboratory for Transformer Oil Testing (1) BDV (100kV) (2) Water Content (3) Flash Point (4) Tan Delta (5) Resistivity (6) Sludge (7) Acidity (8) IFT (9) DGA (10) Furan Analysis

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section TRANSFORMER-TEST REPORT -1

TEST REPORT NO. 0232/09-10 PAGE: 01 OF 17

Test Report No. Customers Address

: :

0232/09-10 M/s. S

Customers Reference

P. O. No.:

Particulars of Equipment Tested Plant Location Serial No. Customer Identification Make Transformer Rating Voltage Vector Group Year of Manufacture Phase Date(s) of Test(s) Winding Temperature Oil Temperature Atmospheric Temperature Weather Condition Particulars of Tests Conducted Customers Requirements Calibration Certificate Coordinated By Mr. Balasaheb. (E.E) s

: : : : : :

Distribution Transformer Beside of 3MW Power House 2005/1180 Sugar Transformer M/s. Mahati Electricals 3150kVA : 11000V/433V

: : : :

Dyn11 2005 3 28th August- 2009 : 280C

: : : : :

280C 290C Dry Condition Monitoring Tests Condition Monitoring Tests : Annexure

Tested Team Mr. Harshad. Gulannavar.

Test Engineer

SHANTHALA POWER LIMITED HUBLI-580 030 (Gouri M. Patil) NO.: SPL/TR-02 Authorised & Signatory FORMAT Calibration Test Report Section Prepared By

TEST REPORT Asst. ManagerNO. Analysis 0232/09-10 (Shashikala. V. T) PAGE: 02 OF 17

MEASUREMENT OF IR TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature (Winding +Oil+ Atmospheric) Voltage Year of Manufacture : : : :

V/S

TIME

2005/1180 Sugar Transformer 28th August-2009 : : 2005 28.30C 11000V/433V

TEST RESULTS SL NO. 1 2 3 TIME 10th Sec 20th Sec 30th Sec HV to LV at 5kV HV to GND at 5kV LV to GND at 0.5kV 0.48 G 0.49 G 0.49 G

0.90 G 2.00 G 2.50 G 1.20 G 3.00 G 1.50 G 4 40th Sec 1.60 G 3.50 G 0.50 G 5 50th Sec 4.00 G 0.50 G 1.90 G st 6 4.25 G 0.50 G 01 Min 2.25 G 7 02nd Min 3.00 G 5.00 G 0.50 G rd 8 03 Min 5.00 G 0.50 G 3.75 G 9 04th Min 5.50 G 0.50 G 4.00 G th 10 05 Min 4.50 G 5.50 G 0.50 G 11 06th Min 4.50 G 6.00 G 0.50 G th 12 07 Min 4.80 G 6.50 G 0.50 G 13 08th Min 5.00 G 6.50 G 0.50 G 14 09th Min 5.50 G 6.50 G 0.50 G 15 10th Min 6.50 G 7.00 G 0.50 G Note: 1) For test conditions please refer page No. 2) *Average Temperature (Winding + Oil + Atmospheric) =28 0+280+29028.30C

Prepared By (Gouri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 0232/09-10 PAGE: 03 OF 17

MEASUREMENT OF IR TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature (Winding +Oil+ Atmospheric) Voltage Year of Manufacture : : : :

V/S

TIME

2005/1180 Sugar Transformer 28th August-2009 : : 2005 28.30C 11000V/433V

SL No. 1

Mode of Test HV-LV

Voltage (kV) 5

TEST RESULTS IR Values in G 30th Sec 1.50 60th Sec 2.25 600th Sec 6.50

PI

DC Absorption Ratio 1.5

2.88

HV-GND

3.00

4.25

7.00

1.64

1.41

LV-GND

0.5

0.49

0.50

0.50

1.0

1.02

Polarization Index 600- Seconds IR Value PI = ------------------------------60-Seconds IR Value

Dielectric Absorption Ratio DA 60-Seconds IR Value = ------------------------------30-Seconds IR Value

Note: 1) For test conditions please refer page No. 17 of 17 2) *Average Temperature (Winding + Oil + Atmospheric) =28 0+280+29028.30C

Prepared By (Gouri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 0232/09-10 PAGE: 04 OF 17

Prepared By (Gouri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 0232/09-10 PAGE: 05 OF 17

MEASUREMENT OF STEP VOLTAGE TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature (Winding +Oil+ Atmospheric) Voltage Year of Manufacture : : : : 2005/1180 Sugar Transformer 28th August-2009 : : 2005 28.30C 11000V/433V

TEST RESULTS Sl. No. Mode of Test Grounded Winding Voltage (kV) 0.5 1.0 1 HV-LV Nil 2.5 5.0 0.5 1.0 2 HV-GND LV 2.5 5.0 IR in G At 60th Sec 1.2 1.4 2.0 3.0 10.0 3.0 2.75 3.5

Note: 1) For test conditions please refer page No. 17 of 17 2) *Average Temperature (Winding + Oil + Atmospheric) =28 0+280+29028.30C

Prepared By (Gouri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 0232/09-10 PAGE: 06 OF 17

MEASUREMENT OF CAPACITANCE, TAN DELTA AND LEAKAGE CURRENT ON WINDINGS TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature (Winding +Oil+ Atmospheric) Voltage Year of Manufacture : : : : 2005/1180 Sugar Transformer 28th August-2009 : : 2005 28.30C 11000V/433V

Mode of Test HV-LV (UST)

Grounded Winding

Voltage (kV) 2.11

TEST RESULTS Current (mA) 04 09 15 04 09 15

Capacitance (pF) 4089.63 4089.83 4089.94 8195.39 8195.39 8196.40

Tan Delta (Absolute) 0.00654 0.00658 0.00666 0.00739 0.00761 0.00768

Nil

4.23 6.35 2.11

HV-GND (GST)

LV

4.23 6.35

Note: 1) For test conditions please refer page No. 17 of 17 2) *Average Temperature (Winding + Oil + Atmospheric) =28 0+280+29028.30C 3) Because of low voltage on LV side, the LV-GND Tan Delta Test could not be conducted.

Prepared By (Gouri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 0232/09-10 PAGE: 07 OF 17

Prepared By (Gouri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 0232/09-10 PAGE: 08 OF 17

MEASUREMENT OF HIGH VOLTAGE EXCITATION CURRENT ON HV WINDINGS TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature (Winding +Oil+ Atmospheric) Voltage Year of Manufacture : : : : 2005/1180 Sugar Transformer 28th August-2009 : : 2005 28.30C 11000V/433V

Tested Phase

TEST RESULTS Applied Voltage (kV) 0.5 1.0

Measured Current (mA) 10 15 20 25 30 12 20 27 33 39 12 20 27 33 39

R-Y

1.5 2.0 2.5 0.5

Y-B

1.0 1.5 2.0 2.5 0.5

B-R

1.0 1.5 2.0 2.5

Note: 1) For test conditions please refer page No. 17 of 17 2) *Average Temperature (Winding + Oil + Atmospheric) =28 0+280+29028.30C

Prepared By (Gouri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 0232/09-10 PAGE: 09 OF 17

MEASUREMENT OF DC WINDING RESISTANCE TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature (Winding +Oil+ Atmospheric) Voltage Year of Manufacture : : : : 2005/1180 Sugar Transformer 28th August-2009 : : 2005 28.30C 11000V/433V

TEST RESULTS OLTC Position Current (mA) 126.1 04 126.1 126.1 Sl No. Current (A) 1.303 01 1.304 1.287 Measurement of Winding Resistance (HV-Side) Tested Phase Resistance in m R-N Y-N B-N 215.1 215.2 215.0

Measurement of Winding Resistance (LV-Side) Tested Phase Resistance in m (r-n) (y-n) (b-n) 0.5 0.5 0.5

Note: 1) For test conditions please refer page No. 17 of 17 2) *Average Temperature (Winding + Oil + Atmospheric) =28 0+280+29028.30C

Prepared By (Gouri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 0232/09-10 PAGE: 10 OF 17

MEASUREMENT OF VOLTAGE RATIO TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature (Winding +Oil+ Atmospheric) Voltage Year of Manufacture : : : : 2005/1180 Sugar Transformer 28th August-2009 : : 2005 28.30C 11000V/433V

TEST RESULTS
Voltage Ratio Sl. No. Applied Voltage at Primary side in Volts R-Y 407 Y-B 408 B-R 408 Measured Voltage at Secondary side in Volts r-y 15.79 y-b 15.75 b-r 15.83 Calculated Voltage Ratio r-y 25.77 y-b 25.90 b-r 25.77

01

Note: 1) For test conditions please refer page No. 17 of 17 2) *Average Temperature (Winding + Oil + Atmospheric) =28 0+280+29028.30C

Prepared By (Gouri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 0232/09-10 PAGE: 11 OF 17

MEASUREMENT OF MAGNETIZATION CURRENT TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature (Winding +Oil+ Atmospheric) Voltage Year of Manufacture : : : : 2005/1180 Sugar Transformer 28th August-2009 : : 2005 28.30C 11000V/433V

TEST RESULTS Tested Phase Measured Voltage (V) Measured Current (mA)

404

18.7 (R-Y)

408

12.1 (Y-B)

409

22.3 (B-R)

Note: 1) For test conditions please refer page No. 17 of 17 2) *Average Temperature (Winding + Oil + Atmospheric) =28 0+280+29028.30C

Prepared By (Gouri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 0232/09-10 PAGE: 12 OF 17

MEASUREMENT OF NEUTRAL FLOATING POINT TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature (Winding +Oil+ Atmospheric) Voltage Year of Manufacture : : : : 2005/1180 Sugar Transformer 28th August-2009 : : 2005 28.30C 11000V/433V

TEST RESULTS Voltage Applied Across HV Side (V) R-Y 407 Y-B 408 B-R 408 Voltage Measured (V) LV (Neutral)-GND

6.30

Note: 1) For test conditions please refer page No. 17 of 17 2) *Average Temperature (Winding + Oil + Atmospheric) =28 0+280+29028.30C

Prepared By (Gouri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 0232/09-10 PAGE: 13 OF 17

FREQUENCY RESPONSE ANALYSIS TRANSFORMER DETAILS: Serial No. Customer Identification Date of Test *Average Temperature (Winding +Oil+ Atmospheric) Voltage Year of Manufacture : : : : 2005/1180 Sugar Transformer 28th August-2009 : : 2005 28.30C 11000V/433V

TEST RESULTS Frequency Rage Tap Position Method Measured winding a) HV side: U-V, V-W, W-U b) LV Side: n1-u1, n1-v1, n1-w1. PLEASE SEE NEXT PAGE FOR GRAPHS : : : 20Hz-2MHZ 1 Sweep Frequency

Note: 1) For test conditions please refer page No. 17 of 17 2) *Average Temperature (Winding + Oil + Atmospheric) =28 0+280+29028.30C

Prepared By (Gouri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 0232/09-10 PAGE: 14 OF 17

OIL-TEST REPORT Test Report No. Customers Address : : 0232/09-10 M/s.

Customers Reference

P. O. No.

Particulars of Sample Tested Date (S) of Test (S) No. Of Samples Tested Customers Requirement

: : : :

Transformer Oil 7th to 11th September 2009 01(Bottom) BDV, Moisture Content, Tan Delta, Resistivity, Acidity, IFT, Sludge, Flash Point DGA , Kinematic Viscosity, Density Pour Point & Furan Tests. Yes Sample Collected By Mr. Harshad G Test Engineer Mr. Shivappa

Whether Tests conducted as per Customers Requirement Coordinated By Mr. Balasaheb. (E.E)

Note: 1. 2. 3. 4. 5. 6. 7. 8. 9. The test results relate only to the sample(s) tested. ND-Not Detected. NA: Not Applicable. NP: Not Provided. NM: Not Mounted {---}: Customer not confirmed. CCSUT: Customer Confirmed, Sample Under testing. The limits for DGA are valid from the last date of filtration. If the last date of filtration is not specified, the limits for DGA are considered from the year of installation. 10. Any Anomaly / Discrepancy in this test report / certificate should be brought to our notice within 60 days from the date of issue.

11. The Test Report not to be reproduced except in full, without written approval from the laboratory

Prepared By (Gouri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section TRANSFORMER DETAILS:
Serial Number Customer Identification Make Capacity Voltage (HV/LV) Year of Manufacture Year of Installation Last Date of Filtration Our Reference No. Date of Sample Collection Date of Receipt of the Sample Sample Tested on Appearance of the Oil Top Oil Temperature Winding Temperature Weather Condition Condition on Receipt : : : : : : : : : : : : : : :

TEST REPORT NO. 0232/09-10 PAGE: 15 OF 17

2005/1180 Besides of Boiler Sugar Transformer Mahati Electricals 3150kVA 11000V/433V 2005 NP NP : LT-1418/01 (Main Tank-Bottom) 29th August 2009 7th September 2009 : 7th to 11th September 2009 Pale Yellow Colour 280C 280C Dry OK

OIL PARAMETERS:

SL NO . 1 2

TEST PARAMETERS Break Down Voltage (BDV)/ DiElectric Strength) in kV, at a Temp: 29.20C, RH: 40% Moisture Content (Water Content) in ppm, at a Temp:28.10C, RH:47% Tan Delta (DiElectric Dissipation Factor) in absolute, at a Temp: 900C, RH: 47% Resistivity (Specific Resistance) in -cm, at a Temp: 900C, RH: 47% Acidity (Neutralization Number) in mg KOH/g Interfacial Tension (IFT) in N/m, at a Temp: 271 0C Sludge/Sediment % by weight Flash Point in 0C

Reference Standard IS: 1866: 2000 Test Method IS: 6792-199250Hz2Hz Electrode Type: Brass Spherical, Electrode gap: 2.5mm IS: 13567-1992 Karl Fisher Titration Method 23010V IS: 6262-1971 50Hz2Hz Three terminal cell 250Vrms\mm: Average voltage gradient in the sample 23010V IS: 6103-1971 Three terminal cell250Vrms\mm: Average voltage gradient in the sample 23010V IS: 1448(P: 2)-1967 IS: 6104-1971 Ring Method IS 1866:2000 Annexure A (Clause-4.3)

For Oil in Service <72.5kV-C-Class >30kV 40 ppm Max 1.0 Absolute Min 0.1X1012 -cm Max 0.3mg KOH/g Min 0.015 Sludge Should not be detected Min 1400C

TEST RESULTS 66,78,74,68,70 78=72.3372. 0 11

0.0044

49 x 1012

5 6 7

0.02 0.043 ND

IS 1448(P: 21)-1992 Pensky Martens closed cup Test Method 23010V DISSOLVED GAS ANALYSIS: IS: 10593:1992 & 9434-1992 SL NO. CHARACTERISTICS 1 Methane PPM 100/150 2 Ethylene PPM 150/200 3 Ethane PPM 100/150 4 Acetylene PPM 30/50 5 Carbon Monoxide PPM 400/500 6 Carbon Dioxide PPM 4000/5000 7 Hydrogen PPM 200/300 8 Total Gas Content %by Volume ---8
Note: NP- Not Provided, ND-Not Detected

154

02 01 ND ND 07 836 01 10.03

Prepared By (Gouri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED HUBLI-580 030 FORMAT NO.: SPL/TR-02 Calibration & Test Report Section

TEST REPORT NO. 0232/09-10 PAGE: 16 OF 17

FURAN ANALYSIS: ASTM D 5837-99


SL NO. 1 2 3 4 5 FURANIC COMPOUNDS (PPB) 5 Hydroxymethyl-2-Furaldehyde Furfuryl Alcohol 2 Furaldehyde 2 Acetyl Furan 5 Methyl 2 Furaldehyde Total

00 00 7.876 6.824 5.916


20.616

OIL PARAMETERS:

SL NO.

TEST PARAMETERS Kinematic Viscosity (cStr), at 270C Pour Point in 0C Density in kg/cm3 at 29.50C

Reference StandardIS: 1866: 2000

Test Method
IS:1448(P:25)-1976 IS:1448 (P:10)-1970 IS:1448(P:16)1990 27cst

Limits

TEST RESULTS 5 -18 0.825

1 2 3

Max: -60C Max:0.89 g/cm3

ANALYSIS & RECOMMENDATION: For Analysis & Recommendation please refer Page No.: 17 OF 17

Prepared By (Gouri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)

SHANTHALA POWER LIMITED TEST REPORT NO. HUBLI-580 030 0232/09-10 FORMAT NO.: SPL/TR-02 Calibration & Test Report PAGE: 17 OF 17 Section ANALYSIS & RECOMMENDATION FOR TRANSFORMER-1 SL NO.: 2005/1180, ID No: Besides Boiler Sugar Transformer

Analysis: Tests on Solid Insulation: The test results of IR, PI and DC absorption ratios are normal. The variation of Capacitance values with respect to voltage is normal and the Tan Delta values are within the permissible limits, i.e. <0.02absolute. Step Voltage results have variation. Tests on Conductor & OLTC: The DC winding resistance values are normal as comparable with all the phases. The voltage ratio measurements are normal. Neutral Floating point Measurements are normal. Tests on Core: Magnetization Currents are normal. Excitation current results are normal. Frequency Response Analysis: The test results of FRA should be compared with earlier results to arrive at a definite conclusion. How ever taking present test results as benchmark any further changes can be noticed by conducting FRA test at a later date under similar conditions. Oil Parameters: The tested parameters of the oil sample of this Transformer are within the permissible limits as per IS:18662000 The parameter of Transformer Oil in service. DGA: The gases generated are within the permissible limits as per relevant Standards. Furan Analysis: The total of the Furanic compounds is in the normal range. Conclusion: Step Voltage results have variation. Core and Conductor are normal. Oil and DGA results are normal. The total of the Furanic compounds is in the normal range. The test results of FRA may be retained as reference for future guidance. Recommendation: All the Condition Monitoring tests should be carried out after one year to establish the trend analysis of Transformer & Oil. All the test results may be retained as bench mark for further analysis. Since the step voltage results have variation, one more test should be repeated within 6 months or as per your convenience, to know the insulation condition. Note: Test Conditions: 1) The Transformer was Isolated completely from both sides, Primary and secondary sides.

Prepared By (Gouri M. Patil) Authorised Signatory

Asst. Manager Analysis (Shashikala. V. T)