Professional Documents
Culture Documents
1. Fit the installation plate horizontally on more to wall structural parts of the wall withspaces Left rear side around the installation plate. refrigerant 2. If the wall is made of brick, concrete pipe hole 65 or the like, drill five or eight 5mm diameter holes in the wall. Insert clip anchor for appropriate mounting screws. 3. Fit the installation plate on the wall 120mm or with five or eight type A screws. more to wall
120mm or
750
Model A
140
NOTE:
Mount the Installation Plate and drill holes in the wall according to the wall structure and corresponding mounting points on the installation plate. The installation plate providedwith the machine differ from appliance to appliance.(Dimensions are in " mm " unless otherwise stated)
Cor rect ori entat ion of Instal lation Pl ate
835
Model B
SAFETY P RECAUTIONS
Please read these safety precautions carefully before installation Be sure to follow all the precautions below, they are all important for ensuring safety.
W ARNI NG CAUTION
This symbol indicates the pos sibili ty of death or serious inju ry. This symbol indicates the pos sibili ty of injury or da mage to property.
Left rear side refrigerant pipe hole 65
260 135
990
Model C
WA RNING
1) Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock,or fire. 2) Use the included accessories parts and specified parts for installation. otherwise, it will cause the set to fall, water leakage, electrical shock fire. 3) Install at a strong and firm location which is able to withstand the set s weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury. 4) For electrical work, follow the local national wiring standard, regulation and this installation instructions. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock fire. 5) Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection. 6) Wiring routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will overheat at connection point of terminal, fire or electrical shock. 7) When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury. 8) Do not modify the length of the power supply cord or use of extension cord, and do not share the single outlet with other electrical appliances. Otherwise, it will cause fire or electrical shock.
Indoor unit outline 275
150mm or more to ceiling
Installation plate
275
1186
Model D
C AUT ION
1) This equipment must be grounded and installed with ground leakage current breaker. It may cause electrical shock if grounding is not perfect. 2) Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fire. 3) Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.
I N D O O R U N I T
N OTE :
The cable size and the cur rent of the fus e or swi tch ar e d etermined by the maxi mum cur rent indi cat ed on th e n amep lat e which located o n the sid e p an el of t he un it. Ple ase refer to the n amep late b efore selecting the c able, fuse a nd switc h.
25 30
Connect th e cable t o the ind oor unit NO TE: Before performing any electrical work, turn off the main power to the system. 1. The inside and outside connecting cable can be connected without removing the front grille. 2. The indoor power cord type is H05VV-F or H05V2V2-F, the outdoor power cord and interconnected cord type is H07RN-F. 3. Lift the indoor unit panel up, remove the electrical box cover by loosening the screw. 4. Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor s respectively. 5. Wrap those cables not connected with terminals with insulation tapes, so that they will not touch any electrical components. Secure the cable onto the control board with the cord clamp.
Fr ont Panel
Electronic box cover
Q ty
1 5-8(d epending on mo d els) 5-8(d epending on mo d els)
Se lf-tapp ing Screw A ST3.9x 25 1 Seal(For cooling & heating models only) Drain Joint(For cooling & heating models only 1 6.35 C onn ec tin g Li qu id side Parts you must purchase. The pipe 9.52 p ip e size differ from appliance to appliance. 9.52 A ss embl y Consult the technician for the proper size. Gas si de 12.7 16 Remote controller optio nal Self-tapping Screw B ST2.9x10 parts Remote controller holder Air freshening filter(used to install on Air filter) 1 2 1 1
To outdoor unit
7 8 9 10
Except the above parts provided,the other parts needed during installation you must purchase.
Righ t
W rong
Cover
I N D O O R U N I T
L1 L2 S L1 L2
Screw
To indoor unit
Power supply
CAUT ION
Connect the indoor un it first, th en the outdoor unit. Do n ot allow the pipin g to let o ut from th e back of the in door uni t. Be c areful not to let th e drain hose slac k. Heat insulati on should be done to the extension dr ain hose of indoor unit. Be s ure that the drain hose is l ocated at the lowest side of the bundle. L ocating at the upper sid e can cause drain pan to overflow insi de the un it. Nev er intercr oss nor i ntertwist the power wire with any other wi ring.
. . .
. . . . .
For the R410A refrigerant model, make sure the refrigerant added into air conditioner is liquid form in any cases. When relocating the unit to another place, using vacuum pump to perform evacuation.
CAUTION
Refrigerant Outdoor uni t A
B Gas side Liquid side
Open the va lve stem until it hits against the stopper. Do not try to open it further. Securely tighten the valve stem cap with a spanner or the like. Valve stem c ap tightening torque . See Tightening torque table.
Packed valve
Flare nut
O U T D O O R U N I T
Co rrect
1. Completel y tighten the flare nuts, A, B, C, D, connect the manifold valve cha rge hose to a ch arge port of the Manifold valve packed va lve on the gas pi pe side. Compound meter Pressure gauge 2. Connect the charge hose connection to the vacuum pump. -76cmHg 3. Fully open the handle Lo o f the manifold valve. 4. Operate the vacuum p ump to evacuate. After starti ng Handle Hi Handle L o evacuation, slightly loose t he flare nut of the packed Charge ho se valve on the gas pipe side and che ck that the air is Charge hose entering. (Operation noise of t he vacu um pump changes Vacuum pump and a com pound mete r indicates 0 instead of minus) 5. After the e vacuation is complete, fully close the handle Lo of the manifold valve and st op the operation of t he vacuum pump. Make evacuation f or 15 mi nutes and more and check Packed valve that th e compound meter indicates -76cmHg(-1.0x10 5Pa). O 6. Turn the stem of the packed valve B about 45 counterclockwise for 6~7 seconds after the gas coming ou t, then tighten the flare nut ag ain. Make sure t he pressure display in the pressure indicator is a lit tle higher than the atmosphere pressure. 7. Remove the charg e hose f rom the Low pressure charge hose. 8. Fully open the packed valve stems B a nd A. 9. Securely t ighten the cap of the packed valve.
Cover
Seal
Drain joint
(A )
CAUTION
(B)
A: Lo p acked valve B: Hi packed valve C and D are ends o f indoor unit connect ion.
90
Handle
Bar
Bar
Copper pipe
Clamp handle
. . .
A lign pip es t o be conne cted . S uffi cien tly t ight en t he f lare nut with fin gers, and then tigh ten it with a sp anner and t orque wrench as shown. E xce ssive torqu e can break nut depending on in stal latio n condition s.
Outer diam.
Tightening torque(N.cm)
1500 (153kgf.cm) 2500 (255kgf.cm) 3500 (357kgf.cm) 4500 (459kgf.cm)