Light Commercial DC INVERTER SERIES MULTI TYPE

Service Manual 2013 LMI-C-1211

CONTENTS 1. General information of Indoor Units .............................................. 1 2. Features........................................................................................... 2 3. Dimensions ..................................................................................... 6 4. Service Space (unit: mm) .............................................................. 14 5. Wiring Diagram ............................................................................. 16 6. Operation temperature range ....................................................... 20 7. Electronic function........................................................................ 21

The specifications, designs, and information in this book are subject to change without notice for product improvement.

1. General information of Indoor Units


New Four-way cassette (compact)

A5 Duct

Ceiling & Floor

Console

Model name MTBI-12HWDN1-M MTBU-12HRDN1-M MTBI-18HWDN1-M MTBU-18HRDN1-M MFAI-12HRDN1-M MFAU-12HRFN1-M MFAI-18HRDN1-M MCA2I-12HRDN1-M MCA2U-12HRFN1-M MCA2I-18HRDN1-M MCA2U-18HRFN1-M MUBI-12HRDN1-M MUBU-12HRFN1-M MUBI-18HRDN1-M MUBU-18HRFN1-M

Dimension (mm) 700x635x210 700x635x210 920x635x210 920x635x210 700x600x210 700x600x210 700x600x210 570x570x260 570x570x260 570x570x260 570x570x260 990x660x203 990x660x203 990x660x203 990x660x203

Net/Gross weight (kg) 20/25 20/25 23/29 23/29 15/20 15/20 15/20 16/19 16/19 18/21 18/21 24/30 24/30 24/30 24/30

2. Features
2.1 New Four-way cassette type(compact)

New panel
360surrounding air outlet design, affords comfortable feeling

Compact design The body size is 570260570mm, its just smaller than the ceiling board, so its very easy for installation and will not damage the decoration. The panel size is 64750647mm. The hooks are designed in the four corners of the body, which can save installation space.

Electric control box built-in design The E-box is simply and safely built inside the indoor unit. Its convenient for installation and maintenance. Can check the control part easily, you only need to open the air return grille.

Fresh air intake function: Fresh air fulfills air quality more healthy and comfortable.

Fresh Air

Dimension:75mm

Air passage function Reserves the space for air outlet from the side of indoor unit; Its availed to connect air duct from the two sides to the nearby small rooms.

2.2 Ceiling & Floor type Two-way installation The rounded design of the ceiling and floor type air conditioner allows either ceiling or floor-level installation. Ceiling installation saves room space, while floor installation helps prevent the loss of warm air.

Brief design Brief design that is suitable for any interior will not only give you cooling and heating performance but also upgrade your lifestyle.

3D airflow Vertical air flow and horizontal airflow can be adjusted by remote controller, the cooperation of the two airflow ways help to spread air comfortably throughout even a large room. With these functions, the whole room can be evenly air-conditioned for both floor-level and ceiling installation.

Optional drainage pipe connection Both right side and left side drainage holes are available to avoid the space limitation for drainage pipe installation. Make you more convenient during installation.

Five panels for optional

Standard Panel

A Panel

B Panel (LED display)

C Panel (LED display)

D Panel

Convenience operating and easy maintenance Remote controller as standard, wired controller for optional. The filter without screw fixed, can be took out easily. Easy installation, save working time The pipes can be connected from bottom, back and right side, makes the installation more easily. The wiring works can be finished before installation.

Outside water pump for optional when ceiling installation

2.3 A5 Duct

Installation accessories: (Optional)


Front Board, Canvas Air Passage, Filter, Panel, for easy installation

Front Board

Canvas Air Passage

Filter

Panel

Easy Installation: Two air inlet styles (Bottom side or Rear side) Air inlet from rear is standard for all capacity; air inlet from bottom is optional. The size of air inlet frame from rear and bottom is same, its very easy to move the cover from bottom to rear side, or from rear to the bottom, in order to matching the installation condition.

Air intake from rear (Standard) Fresh air intake function

Air intake from bottom (Optional)

Install one duct from the reserved fresh-air intake to outdoor. Continually inhale the fresh air to improve the quality of the indoor air, fulfills air quality more healthy and comfortable.

Easy maintenance Clean the filter (Optional, standard product without filter) It is easy to draw out the filter from the indoor unit for cleaning, even the filter is installed in rear side or bottom side.
6

Replace the motor or centrifugal fan Remove the ventilated panel firstly. Remove a half of blower housing and take out the motor with centrifugal fan. Directly remove two bolts, and then replace the motor or centrifugal fan easily.

Motor

Blower Housing Ventilated Panel Reserved remote on-off and central control ports Reserved remote on-off ports and central control ports, can connect the cable of an on-off controller or a central controller to realize remote on-off control function or group control function.

Remote on-off ports

Central control ports

Built-in drain pump (Optional): Built-in drain pump can lift the water to 750mm upmost. Its convenient to install drainage piping under most space condition.

Built-in display board


The standard indoor unit can be controlled by wired controller. There is a display board with a receiver in the E-box. Move out the display, and fix it in other place, even in the distance of 10m. The unit will realized remoter control. The wired controller and the display board can display the error code or production code when the chips detect some failure. Wired Controller (Standard) Remote Controller (Optional)
Display

750mm upmost

2.4 Console Modern and elegant appearance The simple and stylish designs can nicely harmonies with your living space.

Four panels optional

Two air-outlet ways Cooling mode

Quick Cooling

To maintain room temp

Air outlet from top and bottom to make quick cooling ------When the A/C is just switched on, or room temp. is still high, cold air will be blown out from top and bottom air outlet to cool down the room quickly Air outlet from top to maintain room temp. ----When the room has been cooled down, or the A/C has been opened over 1 hour, cold air only from the top outlet to keep constant room temp
9

Heating mode Anti-cold air ------When the AC is just turn on, temperature of evaporator is very low, in this case, in order to prevent cold air direct blowing, only the upper louver is opened in a high position, the lower louver closed.

Four air inlets

Low noise DC indoor fan motor, which has five speeds. Low noise and energy saving.

Advanced centrifugal fan technology makes a fast airflow and reduces the indoor noise lower to 28dB.

Golden fin is optional. Active carbon filter is standard.


10

3. Dimensions
3.1 New Four-way cassette type(compact) (12000Btu/h /18000Btu/h) :

545(Hook-location)

647(Panel)

570(Body)

545(Hook-location) 570(Body) 647(Panel)

3.2 Ceiling & Floor (12000Btu/h /18000Btu/h): a. Wall mounting installation

260

11

b. Ceiling installation

>20mm

Dimension
Capacity(Btu/h) 12000-18000

A 990

B 660

C 206

D 505

E 506

F 907

G 200

H 203

3.3 A5 Duct (12000Btu/h /18000Btu/h)

F A

D C

12

Capacity (Btu) 12000 18000

Outline dimension(mm) A 700 920 B 210 210 C 635 635 D 570 570

Air outlet opening size E 65 65 F 493 713 G 35 35 H 119 119

Air return opening size I 595 815 J 200 200 K 80 80

Size of outline dimension mounted plug L 740 960 M 350 350

3.4 Console (12000Btu/h /18000Btu/h)

13

4. Service Space (unit: mm)


4.1 Four-way cassette (compact)

Ceiling

Outlet
>230

Inlet

Outlet

Ground

4.2 Ceiling & Floor

C 35mm
35mm 35mm

1000mm

4.3 A5 Duct

14

A280

4.4 Console

100mm
100mm 100mm

1000mm

15

5. Wiring Diagram
5.1 MTBI-12HWDN1-M, MTBI-18HWDN1-M

5.2 MTBU-12HRDN1-M

MTBU-18HRDN1-M

16

5.3 MFAI-12HRDN1-MMFAI-18HRDN1-M

5.4 MFAU-12HRFN1-M

17

5.5 MCA2I-12HRDN1-MMCA2I-18HRDN1-M

5.6 MCA2U-12HRFN1-M MCA2U-18HRFN1-M

18

5.7 MUBI-12HRDN1-MMUBI-18HRDN1-M

5.8 MUBU-12HRFN1-M

MUBU-18HRFN1-M

19

6. Operation temperature range


Temperature Mode Room temperature Cooling operation 62 32122 Outdoor temperature 5122For the models with low temperature cooling system 576 32122 Heating operation 88 Drying operation 62

CAUTION: 1. If the air conditioner is used beyond the above conditions, certain safety protection features may come into operation and cause the unit to operate abnormally. 2. The room relative humidity should be less than 80%. If the air conditioner operates beyond this figure, the surface of the air conditioner may attract condensation. Please set the vertical air flow louver to its maximum angle (vertically to the floor), and set HIGH fan mode. 3. The optimum performance will be achieved during this operating temperature zone.

20

7. Electronic function
7.1 Abbreviation
T1: Indoor room temperature T2: Indoor evaporator temperature TS: Setting temperature through the remote controller

7.2 Icon explanation on indoor display board


7.2.1 Four-way cassette (compact)

7.2.2 Ceiling & floor

7.2.3 A5 Duct
PRE-DEF indicator(cooling and heating type) or fan only indicator(cooling only type) Timer indicator Operation lamp Temporary button Alarm indicator Infrared signal receiver Display digital tube

MANUAL OPERATION TIMER DEF./FAN ALARM

7.2.4 Console

21

7.3 Main Protection


7.3.1 Sensor protection at open circuit and breaking disconnection. 7.3.2 The malfunction of correspondence in CMOS chip with EEPROM indication. ---- When the CMOS chip and EEPROM cant communicate during the time of using EEPROM to select parameter, the LED shows information of the malfunction (when use jump to select parameter, it doesnt have this function). After the showing, the unit cant go right to work except turning off. 7.3.3 Indoor fan delayed open function ----When system starts up, the louver will be active immediately, and for cassette & ceiling&floor, the indoor fan will open when the top louver opens 50For console, the indoor fan will open when the top louver opens 15. ----If the system runs in heating mode, the anti-cold wind function has priority. 7.3.5 Fan speed is out of control.Only for console When Indoor fan speed is too low (lower than 300RPM) lasting 60 seconds, the unit stops and LED displays failure information and cant returns to normal operation automatically.

7.4 Operation Modes and Functions


7.4.1 Fan-only mode (1) Outdoor fan and compressor stop. (2) Indoor fan can be set to high/med/low/auto. (3) The louver operates same as in cooling mode. (4) Auto fan in fan-only mode acts as follow: For console T1-24 3.5 3.0 1.5 1.0

High Medium Low

When T1-243, transfer high to medium speed, When T1-241, transfer medium speed to low. When T1-24 >1.5, transfer low to medium speed, When T1-24 >3.5, transfer medium speed to high.

22

For the other types T1-24 4.0 3.0 1.0 Low

High Medium

When T1-243, transfer high to medium speed, When T1-241, transfer medium speed to low. When T1-24 >1, transfer low to medium speed, When T1-24 >4, transfer medium speed to high. (5) Sleep mode is invalid. 7.4.2 Cooling mode (1) Indoor fan keeps running, fan speed can be set in high/mid/low/ Auto by using a remote controller: (2) Auto fan in cooling mode acts as follow: For Console 3.5 3.0 1.5 1.0 For the other types High 4 T1-TS 3 1 Medium Low High

T1-TS

Medium

Low

(3) Anti-freezing control to indoor evaporator in cooling mode


Evaporator Temp. Console The other types T2 4 T2> 8 T2 3 T2> 7 Compressor Off(After 3 minutes) On Off(After 3 minutes) On

(4) Sleep mode can be set by remote controller.. 7.4.3 Dehumidifying mode (1) Indoor fan speed is fixed in low speed and cant be changed.
23

(2) In dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that of cooling mode. (3) Evaporator anti-freezing protection is active. (4) Sleep mode is invalid.

7.4.4 Heating mode (1) Indoor fan actions in heating mode Indoor fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind function prevails. Anti-cold wind control function in heating mode: For console T2 TE2 TE3 TE1 TE5 TE4 Setting fan speed Low Breeze Fan off

E1=28 TE2=32 For the other types:

TE3=30

TE4=15 T2 TE2

TE5=20

Setting fan speed TE3 TE1 Low TE4 Fan off

TE1=28 TE2=32 TE3=30 (2) Auto wind in heating mode For Console:

TE4=15

T1-TS +2.5 Low fan +2.0 Med. fan +1.5 +1.0 High fan

For the other types


24

T1-TS 3C 2C 1C Med. fan Low fan

High fan

(3) High evaporator coil temp.T2 protection:


Condition T2<TE9 TE9<T2< TE7 T2>= TE7 Compressor On Decrease frequency of compressor Off

For consoleTE7=60TE9=48 For the other types: TE7=63TE9=54 7.4.5 Prevent Over-Heating For console: In heating mode, when the indoor unit has no capacity requirement due to indoor room temperature increased, the Indoor fan will run in breeze. (Anti-cold wind function has the priority) For ceiling& floor: In heating mode, when the indoor unit has no capacity requirement due to indoor room temperature increased, the Indoor fan will run in low. (Anti-cold wind function has the priority) For new four-way cassette (compact)&A5 duct: In heating mode, when the indoor unit has no capacity requirement due to indoor room temperature increased, if outdoor fan and compressor stop, the Indoor fan will run in setting fan speed, otherwise, the Indoor fan will run in low. (Anti-cold wind function has the priority)

7.4.6 Defrosting Defrosting operation (Available for heating only). Defrosting Actions: a. Indoor fan switches off, anti-cold wind function is valid. b. After defrosting ends, indoor fan runs according to anti-cold wind function in heating mode. 7.4.7 Auto-mode This mode can be chosen by remote controller and the setting temperature can be changed between 17~30. In auto mode, the machine will choose cooling, heating or fan-only mode according to the difference between T1 and TS. T1-TS T1-TS1 -1< T1-TS1 T1-TS-1 Indoor fan will run in auto fan of the relevant mode. The louver operates the same as in relevant mode.
25

Running mode Cooling Fan-only Heating

If the machine switches mode between heating and cooling, the compressor will keep stopping for 15 minutes and then rechoose mode according to T1-TS. If the setting temperature is modified, the machine will rechoose running function.

7.4.8 Forced operation function 7.4.8.1 Enter forced operation function: Press the touch button continually, the AC will run as below sequence: Forced autoForced coolingOff

When the machine is off, pressing the touch button will carry the machine to forced auto mode, after this, if pressing the button once again, the machine will turn into forced cooling mode. In forced cooling mode, pressing touch button will turn off the machine. 7.4.8.2 In forced operation mode, all general protections and remote control are available. 7.4.8.3 Operation rules: Forced auto mode: The action of forced auto mode is the same as normal auto mode with 24 setting temperature. Forced cooling mode: The indoor fan runs as low(for console, the indoor fan runs as breeze). After running for 30 minutes, AC will turn to auto mode with 24 setting temperature. 7.4.8.4 When theres indoor unit running in forced cooling, it is the master forced cooling unit. Other indoor units will run at forced cooling mode too and they will be the slave forced cooling units. The slave forced cooling units can not quit forced cooling mode until the master forced cooling unit quit, and turn to previous operating mode. 7.4.8.5 The slave forced cooling units will not be controlled by other signals. 7.4.9 Timer Function (1) Timing range is 24 hours, and the minimum resolution is 30 minutes. (2) Timer on. After turning off, the machine will turn on automatically when reaching the setting time. (3) Timer off. After turning on, the machine will turn off automatically when reaching the setting time. (4) Timer on/off. After turning off, the machine will turn on automatically when reaching the setting on time, and then turn off automatically when reaching the setting off time. (5) Timer off/on. After turning on, the machine will turn off automatically when reaching the setting off time, and then turn on automatically when reaching the setting on time. (6) The setting time is relative time. (7) The tolerance of timer is 1 minute per hour.

26

(8) The timer function will not change the AC current operation mode. Suppose AC is off now, it will not start up firstly after setting the timer off function. And when reaching the setting time, the timer LED will be off and the AC running mode has not been changed.

7.4.10 Sleep mode (1) Operation time in sleep mode is 7 hours. After 7 hours the AC quits this mode and turns off. (2) It is available at cooling, heating or auto mode. (3) Operation process in sleep mode is as follow: After pressing ECONOMIC or SLEEP button on controller, the machine will turn into sleep mode. When cooling, the setting temperature rises 1(be lower than 30) every one hour, 2 hours later the setting temperature stops rising and indoor fan is fixed as low speed. When heating, the setting temperature decreases 1(be higher than 17) every one hour, 2 hours later the setting temperature stops decreasing and indoor fan is fixed as low speed.(Anti-cold wind function has the priority) When Auto, the sleep mode running function operates in accordance with selected running mode by auto mode. (4)When user uses timer off function in sleep mode(or sleep function in timer off mode), if the timing time is less than sleep time, sleep function will be cancelled when reaching the timing time. If the timing time is more than sleep time, the machine will stop until reaches the sleep time.(Only for console) (5)When sleep function is cancelled, the indoor unit will not stop except console. 7.4.11 Auto-Restart function The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart module. In case of a sudden power failure, the module memorizes the setting conditions before the power failure. The unit will resume the previous operation setting (not including Swing function) automatically after 3 minutes when power returns. If the memorization condition is forced cooling mode, the unit will turn off.

7.4.12 Mode conflict The indoor units can not work cooling mode and heating at same time. Heating mode has a priority. (1) Definition Cooling mode Cooling mode Heating Mode Fan Off No: No mode conflict; Yes: Mode conflict (2) Unit action In case of one Indoor unit working in cooling mode or fan mode, and another indoor unit is set to heating
27

Heating Mode Yes No Yes No

Fan No Yes No No

Off No No No No

No Yes No No

mode, the indoor unit working in cooling mode or fan mode will change to off. The outdoor unit will change to heating mode after compressor stop 3 minutes. . In case of one Indoor unit working in heating mode, and another indoor unit is set to cooling mode or fan mode, the indoor unit setting to cooling mode or fan mode will change to stand by. The outdoor unit will continue working in heating mode. If heating mode stops (not including the indoor unit in heating mode reaching the set temperature), 3 minutes after the outdoor unit restarts and works in cooling mode or fan-only mode.

Appendix:

10 48 23 74

11 50 24 76

12 52 25 78

13 54 26 80

14 56 27 82

15 16 58 60 28 29 84 86

17 62 30 88

18 64 31 90

19 20 66 68 32 33 92 94

21 70 34 96

22 72 35 98

28