Professional Documents
Culture Documents
CONCRETE STRUCTURES
methods of designing reinforced concrete structures to resist fires information on thermal and mechanical properties of concrete briefly composite steel-concrete structures
Winter 2003
Concrete Structures
7-1
Winter 2003
Concrete Structures
7-2
High-strength Concrete
Recently, interest in high-strength concrete has increased High-strength concrete contains additives which result in compressive strength of 50 - 120 MPa High-strength concrete shows a higher rate of strength loss than normal concrete at temp. up to 400C and explosive spalling Kodur (1997) reported fire tests on high-strength columns Tomasson (1998) gave design recommendations
Winter 2003 Concrete Structures 7-5
Lightweight Concrete
Lightweight concrete is usually made with normal cement and some form of lightweight aggregate Lightweight concrete has good fire resistance due to low thermal conductivity compared with normal weight concrete
Winter 2003
Concrete Structures
7-6
Spalling
In concrete structures, design methods are often based on concrete remaining intact in fires This is not always valid due to spalling in fires Tests and real fires have shown that most normal concrete members do not show serious spalling The spalling phenomenon is not well understood because it is a function of many factors Spalling often occurs when water vapour is driven off from the cement paste during heating
Winter 2003 Concrete Structures 7-8
Spalling
Tests have shown that spalling results from high moisture content concrete High-strength concrete is more susceptible to spalling than normal concrete A method of preventing spalling is to add fine polypropylene fibres to concrete mix (0.15-0.3%) The fibres melt during fire exposure, increasing the porosity in the concrete for vapour escape
Masonry
Concrete masonry consists of hollow concrete blocks mortared together (often used in walls) Concrete masonry blocks are often manufactured from lightweight concrete Unfilled unreinforced masonry has demonstrated excellent fire resistance Brick masonry also behaves well in fires Thermal bowing of tall unreinforced cantilever masonry walls can lead to collapse during a fire
Winter 2003 Concrete Structures 7-10
Winter 2003
Concrete Structures
7-9
Prestressed Concrete
Prestressed concrete means concrete structures stressed prior to applying external loads Two types: pre-tensioned and post-tensioned Pre-tensioned prestressed concrete is often used for precast components for flooring (flat panels) Post-tensioning is used within large components (beams or slabs) Full-scale fire tests have shown that bond failures of pre-tensioned tendons failed prematurely
Winter 2003 Concrete Structures 7-11
FIRE-RESISTANCE RATINGS
Verification Methods Generic Ratings
Winter 2003
Concrete Structures
7-12
Verification Methods
The design for fire resistance requires that:
provided fire resistance > design fire severity
Generic Ratings
Very few proprietary ratings for concrete structures Generic ratings are often used Many codes list generic ratings for concrete members (min. sizes and concrete cover to steel) Some ratings distinguish between concrete types Information applies to standard fire exposure only Table below shows generic fire resistance ratings for reinforced concrete members (BSI, 1985) Min. thickness of floors/walls are based on the insulation criterion
Winter 2003 Concrete Structures 7-14
In time domain, compare fire resistance ratings with code-specified fire resistance (often used) In strength domain, compare load-bearing capacity with expected loads at time of fire In temp. domain, compare critical temp. with max. reached temp. in fires (not usually used)
Winter 2003 Concrete Structures 7-13
Generic Ratings
Min. width (mm) and min. cover (mm) for generic fire resistance rating of reinforced concrete members
0.5 hours 1.0 hours 1.5 hours 2 hours 3 hours 4 hours Width Cover Width Cover Width Cover Width Cover Width Cover Width Cover Beams 80 20 120 30 150 40 200 50 240 70 280 80 Columns 150 20 200 25 250 30 300 35 400 35 450 35 Slabs 75 15 95 20 110 25 125 35 150 45 170 55 Walls 75 15 75 15 100 25 100 25 150 25 180 25
Generic Ratings
Appendix D gives generic approvals from 10 different sources from around the world Concrete structures show good fire resistance, thus many will meet the generic approvals with no increase in cover from normal temp. design Calculations may be useful for members which are thin or slender and members with little concrete cover to the reinforcing
Winter 2003
Concrete Structures
7-15
Winter 2003
Concrete Structures
7-16
Fire Exposure
To design concrete structures under fire, temp. of concrete and reinforcing steel must be known The fire exposure may be standard or real curve Design charts are available giving thermal gradients in beams, columns and slabs exposed to the standard fire It is better to use computer programs to calculate temperature gradients in concrete members exposed to realistic fires
Winter 2003
Concrete Structures
7-17
Winter 2003
Concrete Structures
7-18
Calculation Methods
Thermal calculations in reinforced or prestressed concrete members usually assume that:
heat transfer is a function of thermal properties of concrete alone temperature of the reinforcing is the same as the temperature of the surrounding concrete
Calculation Methods
For simple members of normal-weight concrete, empirical hand calculation methods are available Wickstrom proposed a method of calculating the temp., Tw, in a normal weight concrete slab exposed to a standard fire on its surface as: Tw = w Tf w = 1 - 0.0616 th-0.88 Tf is the fire temperature (C) th is the time (hours)
Winter 2003 Concrete Structures 7-20
Different thermal conductivity is not a factor since most steel is parallel to the fire-exposed surfaces Only accurate way to calculate temperatures is to use a 2-D finite-element computer program
Winter 2003 Concrete Structures 7-19
Calculation Methods
Temp. Tc (C) at any depth x (m) into the slab is: Tc = x w Tf x = 0.18 ln(th/x2) - 0.81 The method can be used for corners of beams where heat is conducted in 2 directions, using y calculated in the same way as x so that Tc is: Tc = [w (x + y 2 x y) + x y] Tf Wickstrom stated that these equations can be modified for other types of concrete
Winter 2003 Concrete Structures 7-21
Thermal Properties
To calculate temp. in structural assemblies, thermal properties of materials must be known Concrete density depends on aggregate and mix design (typical concrete density of 2300 kg/m3) When heated to 100C, density of concrete reduces by up to 100 kg/m3 (water evaporation) Limestone aggregate concrete decomposes over 800C with a corresponding decrease in density Thermal conductivity of concrete varies with temperature in a broad range (see figure below)
Winter 2003 Concrete Structures 7-22
Thermal Properties
Thermal conductivity of concrete
Thermal Properties
Values for design purposes in Eurocode:
1.6 W /m-K for siliceous concrete 1.3 W /m-K for limestone aggregate concrete 0.8 W /m-K for lightweight concrete
Specific heat of concrete varies in a broad range with temperatures (see Figure below) Peak between 100 and 200C allows for water being driven off during the heating process Values for design purposes in Eurocode:
1000 J/kg-K for siliceous/limestone aggregate concrete 840 J/kg-K for lightweight concrete
Winter 2003 Concrete Structures 7-23 Winter 2003 Concrete Structures 7-24
Thermal Properties
Specific heat of concrete
Published Temperatures
There is good published information available on temperatures within concrete members exposed to the standard fire The availability of this information makes it much easier to design for standard fire exposure especially for the simple hand calculated design methods
Winter 2003
Concrete Structures
7-25
Winter 2003
Concrete Structures
7-26
Winter 2003
Concrete Structures
7-27
Winter 2003
Concrete Structures
7-28
Winter 2003
Concrete Structures
7-29
Winter 2003
Concrete Structures
7-30
Winter 2003
Concrete Structures
7-31
Winter 2003
Concrete Structures
7-32
Components of Strain
The deformation of concrete is described by the total strain as: = th(T) + (,T) + cr(,T,t) + tr(,T) th(T) is the thermal strain (,T) is the stress related strain cr(,T,t) is the creep strain tr(,T) is the transient strain
Components of Strain
Under heat and load, strains described above produce deformations as shown in Figure below For simple structures such as S.S. beams, only the stress-related strain needs to be considered For more complex systems, all strains must be considered (using structural analysis programs)
Winter 2003
Concrete Structures
7-33
Winter 2003
Concrete Structures
7-34
Thermal Strain
Approximate expressions for thermal elongation L/L of concrete from Eurocode are given by:
L/L = 18 x c for siliceous aggregate concrete L/L = 12 x 10-6 Tc for calcareous aggregate concrete L/L = 8 x 10-6 Tc for lightweight concrete 10-6 T
Winter 2003
Concrete Structures
7-35
Winter 2003
Concrete Structures
7-36
Stress-related Strain
Stress-related strains (elastic and plastic) result from applied loads Figures below show:
typical stress-strain curves for concrete at elevated temperatures reduction in ultimate compressive strength with temp. for typical structural concrete
Ultimate compressive strength drops and strain at peak stress increases with increasing temp.
Winter 2003
Concrete Structures
7-37
Winter 2003
Concrete Structures
7-38
Stress-related Strain
Stress-strain relationships for concrete at elevated temperatures
Stress-related Strain
Reduction in compressive strength with temp.
Winter 2003
Concrete Structures
7-39
Winter 2003
Concrete Structures
7-40
Winter 2003
Concrete Structures
7-41
Winter 2003
Concrete Structures
7-42
for T < 350C for T > 350C for T < 500C for T > 500C
Winter 2003
Concrete Structures
7-43
Winter 2003
Concrete Structures
7-44
Winter 2003
Concrete Structures
7-45
Winter 2003
Concrete Structures
7-46
Complex structures should be designed using general calculation methods (computer program) Simplified method is useful for single members, using hand calculations (used for normal temp.) Temp. profile within the members is essential
Winter 2003 Concrete Structures 7-48
Winter 2003
Concrete Structures
7-47
Another approach is to ignore concrete over 750C and assign a single strength to remaining concrete core based on its average temp. These simplified methods give similar results The first method is recommended (500C limit)
Winter 2003
Concrete Structures
7-50
Member Design
Verification in the strength domain requires that: U*fire Rfire * U fire is the design force from applied loads (code) and Rfire is the load-bearing capacity U*fire may be axial force N*fire, bending moment M*fire or shear force V*fire Rfire may be calculated as axial force Nf, bending moment Mf or shear force Vf Calculations of Rfire are based on the mechanical properties of concrete/steel at elevated temp.
Winter 2003 Concrete Structures 7-51
Member Design
Below is a description of design of members using the simple method with zero strength for concrete above 500C The design method uses normal assumptions for reinforced concrete design, assuming:
concrete has no tensile strength parabolic compressive stress block in the concrete can be approximated by an equivalent rectangle
The stress block is calculated assuming that the characteristic strength is 85% x crushing strength For beams/slabs, ignore compression reinforcing
Winter 2003 Concrete Structures 7-52
Winter 2003
Concrete Structures
7-54
Winter 2003
Concrete Structures
7-55
Winter 2003
Concrete Structures
7-56
Winter 2003
Concrete Structures
7-57
Winter 2003
Concrete Structures
7-58
WORKED EXAMPLE 1
SIMPLY SUPPORTED REINFORCED CONCRETE SLAB (Refer to Figure page 7-55) For a simply supported reinforced concrete slab with known span, load, geometry and reinforcing, check the flexural capacity after 60 minutes exposure to the standard fire. Use Wickstrom's formula to calculate the reinforcing temperature. Given information: Dead load (excluding self weight) G1 = 0.5 kN/m Live load Q = 2.5 kN/m Slab span L = 7.0 m
Winter 2003 Concrete Structures 7-59
WORKED EXAMPLE 1
Slab thickness h = 200 mm Concrete density = 24 kN/m3 Concrete strength fc = 30 MPa Yield stress fy = 300 MPa Bars:
diameter Db = 16 mm spacing s = 125 mm bottom cover cv = 15 mm
Design a 1 m wide strip - b = 1000 mm Self weight G2 = h b = 4.8 kN/m Total dead load G = G1+G2 = 0.5+4.8 = 5.3 kN/m Steel area As = n r2 b/s = 1608 mm2
Winter 2003 Concrete Structures 7-60
10
WORKED EXAMPLE 1
Effective depth d = h - cv - Db/2 = 177 mm Effective cover ce = cv + Db/2 = 23 mm = 0.023 m COLD CALCULATIONS (for a 1 m wide strip) Strength reduction factor = 0.85 Stress block depth a = Asfy/0.85fc b a = 1608x300/0.85x30x1000 = 18.9 mm Internal lever arm jd =d-a/2=177-18.9/2=168 mm Design load (cold) wc = 1.2G+1.6Q= 10.4 kN/m Bending moment M*cold = wcL2/8 = 10.4x7.02/8 = 63 kNm
Winter 2003 Concrete Structures 7-61
WORKED EXAMPLE 1
Bending strength Mn = Asfy jd = 1608x300x168/106 = 81 kNm Mn = 69 kNm Mn > M*cold so design is OK. FIRE CALCULATIONS Revised strength reduction factor = 1.0 Design load (fire) wf = G1+G2+0.4Q = 6.3 kN/m Bending moment M*fire = wf L2/8 = 6.3x7.02/8 = 38.6 kNm
Winter 2003 Concrete Structures 7-62
WORKED EXAMPLE 1
After 60 minutes of standard fire exposure t = 60 min (th = 1.0 hour) Fire temperature Tf = 20+345 log(8t+1) = 945C Surface temperature Tw = [1-0.0616 th-0.88] Tf Tw = [1-0.0616x1.0-0.88] x 945 = 887C Concrete temperature Tc =[0.18 In(th/ce2)-0.81] Tw Tc = [0.18 In(1.0/0.0232)-0.81] x 887 = 486C Steel temperature Ts = Tc = 486C Reduced yield stress fy,T = fy(720-Ts)/470=300(720-486)/470= 149 MPa
Winter 2003 Concrete Structures 7-63
WORKED EXAMPLE 1
Stress block depth a = As fy,T / 0.85 fc b a = 1608x149/0.85x30x1000 = 9.4 mm Internal level arm jd = d-a/2 = 177-9.4/2 = 172 mm Bending strength Mnf = As fy,T jd = 1608x149x172/106 = 41.2 kNm Mnf = 1.0x41.2 = 41.2 kN.m Mnf > M*fire so design is OK.
Winter 2003
Concrete Structures
7-64
Shear Strength
Shear is not usually a problem in fire-exposed concrete structures For shear design, Eurocode recommends using normal temp. design methods with mechanical properties reduced with temp. and the cross section reduced to the 500C contour
Winter 2003
Concrete Structures
7-65
Winter 2003
Concrete Structures
7-66
11
Winter 2003
Concrete Structures
7-68
Winter 2003
Concrete Structures
7-69
Winter 2003
Concrete Structures
7-70
Axial Restraint
Axial restraint can have a significant influence on fire resistance of reinforced concrete members Hot concrete members tend to undergo larger horizontal displacements with lower vertical deflections (large horizontal restraint forces) Axial restraint is beneficial for reinforced or prestressed concrete slabs or beams The line of thrust must be below the compressive stress block to utilize the benefits of axial restraint
Winter 2003
Concrete Structures
7-71
12
Winter 2003
Concrete Structures
7-74
Winter 2003
Concrete Structures
7-76
Winter 2003
Concrete Structures
7-77
Winter 2003
Concrete Structures
7-78
13
WORKED EXAMPLE 2
AXIAL RESTRAINT Consider a reinforced concrete floor constructed from precast concrete tee-beams as shown in the Figure below. The slabs are simply supported over a span of 6.0 m, carrying a live load of 3.0 kPa. The dead load is 4.8 kPa (including the self weight). Calculate the restraint condition necessary to give a fire-resistance rating of 120 minutes.
WORKED EXAMPLE 2
Beam for Worked Example 2
Winter 2003
Concrete Structures
7-79
Winter 2003
Concrete Structures
7-80
WORKED EXAMPLE 2
Given information: Slab span L = 6.0 m Concrete strength fc = 25 MPa Overall depth h = 300 mm Steel strength fy = 350 MPa Web width bw = 200 mm Concrete MOE E = 25 GPa Overall width bf = 1200 mm Cross-sectional area A = 185000 mm2 Heated perimeter s = 1550 mm
Winter 2003 Concrete Structures 7-81
WORKED EXAMPLE 2
Load combinations: Dead load per metre G = 1.2x4.8 = 5.76 kN/m Live load per metre Q = 1.2x3.0 = 3.6 kN/m Load combination for cold conditions: wc = 1.2G+1.6Q = 12.7 kN/m Load combination for fire conditions: wf = G + 0.4Q = 7.20 kN/m Reinforcing: Number of bars n = 4
Winter 2003 Concrete Structures 7-82
WORKED EXAMPLE 2
Bar diameter Db = 16 mm Single bar area As1 = (Db/2)2 = 201 mm2 Total bar area As = n As1 = 804 mm2 Cover cv = 20 mm Effective depth d = h - cv - Db/2 = 272 mm
WORKED EXAMPLE 2
Stress block depth a = As fy/0.85 fc bf a = 804x350/0.85x25x1200 = 11.0 mm Internal lever arm jd = d-a/2 = 272-11/2 = 266 mm Flexural strength Mc =As fy jd Mc =804x350x266/106 = 75.0 kNm Mc = 0.85x75.0 = 63.8 kNm Mc > M*cold so cold design is OK. FIRE CALCULATIONS Strength reduction factor = 1.0 Mid span bending moment M*fire = wfL2/8 = 7.2x6.02/8 = 32.4 kNm
7-83 Winter 2003 Concrete Structures 7-84
Effective cover ce = cv + Db/2 = 28 mm COLD CALCULATIONS Strength reduction factor = 0.85 Mid-span bending moment M*cold = wcL2/8 = 12.7x6.02/8 = 57.2 kNm
Winter 2003 Concrete Structures
14
WORKED EXAMPLE 2
Steel bar temperature from the isotherms on Figure 7-31: Bar group (1) (corner bars) Ts1 = 830C Bar group (2) (corner bars) Ts2 = 640C Reduced yield strength
fy,T1 = 350 x (720-830)/470 = 0 MPa fy,T2 =350 x (720-640)/470 = 59.5 MPa
WORKED EXAMPLE 2
Internal lever arm jdf = d-af/2 = 272-0.93/2 =271.5 mm Flexural strength Mf = Mf = Asfy,T jdf = 24x271.5/106 = 6.4 kNm Mf < M*fire so slab will fail unless restraint or continuity is provided. Provide axial restraint (numbers in brackets are steps from notes) (4) Estimate the mid-span deflection: Mid-span deflection of the reference specimen 0 = 65 mm (from Figure 7-74)
Winter 2003 Concrete Structures 7-86
As fy,T = (2 As1 fy,T1+ 2 As2 fy,T2) = (2x201x0+2x201x59.5)/1000 = 23.9 kN Stress block depth af = As fy,T/0.85f'c bf af = 23.9x1000/(0.85x25x1200) = 0.93 mm
Winter 2003
Concrete Structures
7-85
WORKED EXAMPLE 2
Heated length L = 6000 mm Distance from neutral axis to extreme bottom fibre yb = 290 mm (assume that neutral axis is 10 mm from top of slab) Mid-span deflection = L2 0/89000 yb = 60002 x 65/(89000 x 290) = 90.7 mm Distance to line of thrust from top of beam dT = 0.9h = 280 mm (assume that the slab is built-in to the surrounding construction, thrust 0.1h from bottom.)
WORKED EXAMPLE 2
(6) Calculate the required thrust to prevent collapse T = 1000 (M*fire-Mf)/(dT-af/2-) T = 1000 (32.4-6.4)/(270-0.9/2-90.7) = 145 kN (7) Recalculate af af = (T+ As fy,T)/0.85 fc bf af =(14500+ 23700)/(0.85x25x1200) = 6.6 mm Recalculate T T = 1000 (32.4-16.1)/(270-6.6/2-90.7) = 148 kN (8) Non-dimensional thrust parameter T/AE = 147700/(185000x25000) = 32 x 10-6
Winter 2003
Concrete Structures
7-87
Winter 2003
Concrete Structures
7-88
WORKED EXAMPLE 2
Shape parameter z = A/S = 185000/1550 = 119 mm Strain parameter L/L = 0.0065 (from Figure 7-77) Maximum permitted displacement L = 0.0065x6000 = 39 mm So, this slab will have a fire resistance of 120 min if the surrounding structure at each end is capable of resisting an axial thrust of 148 kN with an axial elongation of less than 39 mm.
Winter 2003 Concrete Structures 7-89
Columns
Columns are more difficult to design than flexural members due to possible instability problems As a simple method, minimum dimensions and cover, as shown in Tables below, can be used The recommended conservative design approach is to use the simplified method assuming zero strength for all concrete above 500C
Winter 2003
Concrete Structures
7-90
15
Columns
Minimum width (mm) and minimum cover (mm) for generic fire-resistance rating of reinforced concrete members
0.5 hours 1.0 hours 1.5 hours 2 hours 3 hours 4 hours Width Cover Width Cover Width Cover Width Cover Width Cover Width Cover Beams 80 20 120 30 150 40 200 50 240 70 280 80 Columns 150 20 200 25 250 30 300 35 400 35 450 35 Slabs 75 15 95 20 110 25 125 35 150 45 170 55 Walls 75 15 75 15 100 25 100 25 150 25 180 25
Columns
Generic fire-resistance ratings for concrete columns
Load ratio Width (mm) 150 150 180 200 240 300 0.2 Cover (mm) 10 10 10 40 50 50 Column exposed on more than one side 0.5 0.7 Width Cover Width Cover (mm) (mm) (mm) (mm) 150 10 150 10 180 10 200 10 210 10 240 35 250 40 280 40 320 50 360 50 400 50 450 50 Exposed on one side 0.7 Width Cover (mm) (mm) 100 10 120 10 140 10 160 45 200 60 300 60
Width is the minimum dimension of the column and cover is the location of the centre line of the reinforcing relative to the outside of the column. Cover required for durability will control in some cases
Winter 2003
Concrete Structures
7-91
Winter 2003
Concrete Structures
7-92
Walls
Non-load-bearing concrete walls or partitions do not require structural design (provide thickness to meet insulation criterion) Previous Table shows some ratings Load-bearing walls are usually axial load-carrying members that should be designed as slender columns (using columns methods) The main difference is fire exposure, columns are often designed for exposure on all sides, but most walls are exposed to fire on one side only
Winter 2003 Concrete Structures 7-93
Winter 2003
Concrete Structures
7-94
Composite slabs
Composite steel-concrete slabs are popular Fire behaviour of composite slabs is discussed under the three categories:
integrity insulation stability
Winter 2003
Concrete Structures
7-95
Winter 2003
Concrete Structures
7-96
16
Winter 2003
Concrete Structures
7-97
Winter 2003
Concrete Structures
7-98
Composite beams
Hot-rolled steel beams Light steel joists
Winter 2003
Concrete Structures
7-99
Winter 2003
Concrete Structures
7-100
Composite columns
The concrete filling has three beneficial effects:
it acts as a heat sink to slow the rise in temp. of steel it provides lateral stability to prevent local buckling of the column wall it carries some of axial load as steel strength reduces
NRC has carried out research on concrete filling in hollow steel columns exposed to standard fires using the column furnace Lie and Kodur developed a design formula that is used in National Building Code of Canada
Winter 2003 Concrete Structures 7-102
Winter 2003
Concrete Structures
7-101
17
Composite columns
The empirical equation gives fire resistance tr (min) of circular/square steel columns completely filled with concrete as: tr = (f (fc + 20) d2.5) / ((KL 1000) N) f is a factor from Table below fc is the strength of the filling concrete (MPa) d is the outside diameter/width of column (mm) L is the unsupported length of the column (mm) KL is the effective length of the column (mm) N is the applied load on the column (kN)
Winter 2003 Concrete Structures 7-103
Composite columns
Value of factor f for fire resistance of concrete-filled steel columns
Filling concrete Plain concrete Bar-reinforced concrete Fibre-reinforced concrete Square columns 0.06 0.065 0.065 Circular columns 0.07 0.075 0.075
Note that tabulated values of f may be increased cumulatively as follows Tabulated values are for siliceous aggregate concrete For carbonate aggregate concrete, add 0.01. Bar-reinforced concrete values are for cover < 25 mm For cover 25 mm, add 0.005. Bar-reinforced concrete values are for reinforcing < 3% For reinforcing 3%, add 0.005
Winter 2003 Concrete Structures 7-104
Composite columns
This formula is valid for:
fire-resistance times up to 2 hours for plain concrete and 3 hours for reinforced concrete for column sizes from about 140 to 410 mm, except that bar reinforcing cannot be used in columns smaller than about 200 mm
WORKED EXAMPLE 3
Calculate the fire resistance of a circular steel column filled with concrete. Given information: Column length L = 4800 mm Effective length factor K = 0.67 (fixed-fixed end conditions) Axial load N = 1344 kN Concrete strength fc = 40 MPa (carbonate aggregate concrete)
Winter 2003
Concrete Structures
7-105
Winter 2003
Concrete Structures
7-106
WORKED EXAMPLE 3
Column size HSS 324x6.4 Column diameter d = 324 mm Bar reinforcing 3% Cover 25 mm From Table 7-104, f = 0.095. From Eq. (7-103) the fire resistance is given by tf = f(fc + 20) d2.5/(KL-1000) N tf = 0.095 (40+20) 3242.5(0.67x4800-1000)1344 = 133 minutes
Winter 2003
Concrete Structures
7-107
18