You are on page 1of 14

21, rue dArtois, F-75008 PARIS http: //www.cigre.

org

A3-211 2011

2011 SC A3 Technical Colloquium

SUMMARY OF RESULTS OF THE 2004 - 2007 INTERNATIONAL ENQUIRY ON RELIABILITY OF HIGH VOLTAGE EQUIPMENT M. RUNDE1, on behalf of CIGR WG A3.062

SUMMARY CIGR WG A3.06 has completed a survey of reliability and failures of in-service high voltage equipment. The equipment types considered are SF6 circuit breakers, disconnectors, earthing switches, instrument transformers and gas insulated switchgear (GIS). 90 utilities from 30 countries have contributed failure and population data, making this the most comprehensive reliability survey for high voltage apparatus ever carried out. The overall major failure frequency for circuit breakers is found to be 0.30 major failures per 100 circuit breaker years of service, which is lower than in a previous survey. Shunt reactor switching is associated with substantial higher failure frequencies than other switching duties. For disconnectors and earthing switches the overall major failure frequency is determined to be 0.21 failures per 100 equipment years of service. A 3:1 ratio between the number of failures caused by the operating mechanisms and failures caused by the primary components of the disconnectors and earthing switches is observed. Instrument transformers show an overall failure frequency of about 0.053 major failures per 100 single phase instruments transformer years of service. In general, individual equipment installed in GIS appears to have lower failure frequencies than equipment in air insulated substations. The overall major failure frequency for GIS bays is about 0.37 major failures per 100 GIS circuit breaker bay years of service. (A GIS circuit breaker bay includes one circuit breaker and all associated disconnectors, instrument transformers, interconnecting busducts and/or parts of busbars and associated terminals.) Six very comprehensive CIGR Technical Brochures containing all results with commentaries, information concerning how the survey was conducted, methods used for statistical analyses, recommendations for utilities and manufacturers, etc. are to be published shortly.

KEYWORDS SF6 circuit breakers; disconnector switches; earthing switches, instrument transformers; gas insulated switchgear; reliability; failure rates; service experience; major failures.
magne.runde@sintef.no Members of WG A3.06 are: M. Runde (NO) Convener, C. E. Slver (SE) Past Convener, B. Bergman (CA), A. Carvalho (BR), M. L. Cormenzana (ES), H. Furuta (JP), W. Grieshaber (FR), A. Hyrczak (PL), D. Kopejtkova (CZ), J. G. Krone (NL), M. Kudoke (CH), D. Makareinis (DE), J. F. Martins (PT), K. Mestrovic (HR), I. Ohno (JP), J. stlund (SE), K.-Y. Park (KR), J. Patel (IN), C. Protze (DE), J. Schmid (DE), J. E. Skog (US), B. Sweeney (UK), S. Tsukao (JP), F. Waite (UK).
2 1

1. INTRODUCTION
CIGR considers collecting, analyzing and publishing reliability data important tasks, and in 2002 WG A3.06 Reliability of high voltage equipment was established. The WG was instructed to organize and carry out a worldwide enquiry on service experience with circuit breakers, disconnectors, earthing switches, instrument transformers and gas insulated switchgear (GIS). The time period covered by the survey is 2004 - 2007, and the enquiry comprises equipment rated for voltages greater than or equal to 60 kV. For circuit breakers only single pressure SF6 technology is included, therefore in practice equipment installed before around 1970 is excluded. For disconnectors, earthing switches and instrument transformers there are no limitations in age or technology. Both equipment installed in air insulated and gas insulated substations are covered. Information has been collected by asking utilities to complete and return questionnaires. 90 utilities from 30 countries have contributed, and the analyses of the results have now been completed. This paper presents a short summary, with emphasis on major failure frequencies. Far more extensive and detailed results, commentaries, comparisons with previous surveys, information concerning how the survey was conducted, statistical analyses, recommendations for utilities and manufacturers, etc. can be found in six comprehensive CIGR Technical Brochures [1] - [6] that will be published shortly.

2. METHODS AND PROCEDURES USED IN THE SURVEY


2.1 Questionnaires To be able to determine failure frequencies, the numbers and details of the equipment populations that are covered by the survey has to be recorded. Thus for each of the four equipment types included, the enquiry has employed two types of forms/cards/questionnaires: one for equipment populations and one for failures. Population cards were completed annually (i.e., one for each year 2004 - 2007); whereas a failure card was filled in each time a failure occurred within this time span. For GIS, there was also included a GIS maintenance card collecting information about different practices in GIS high voltage testing, diagnostics, monitoring, major maintenance, extension and servicing. The data collection was carried out by means of a specially developed spreadsheet tool, containing the four population cards, the four failure cards and the GIS maintenance card. All questions were of the tick box types, or they required numbers or dates as input. The tool was multi-lingual; with eleven different languages, and it was even possible to switch between them. The population cards asked for the age and number of components being covered, grouped by voltage level, application, technology, design and maintenance strategy. The failure cards requested the same type of information about the failed component, together with information describing the failure itself, such as its origin and cause, what sub-assembly failed, whether this was a minor or major failure, if environmental stress contributed, etc. The questionnaire spreadsheet tool was distributed by e-mail to utilities worldwide willing to participate in the survey. They filled in the forms, and returned a file with the answers to the working group member responsible for that country. After a quality check, the responses were forwarded and compiled in a database for subsequent statistical analysis. The information has been collected directly and solely from the utility sector, not from manufacturers or others as in some previous reliability surveys. All incoming information has been treated as confidential.

2.2 Failure definitions A main objective of the survey is to identify trends by comparing the findings from the present survey with those from the previous ones. Consequently, the majority of the definitions and questions are completely or nearly identical to those applied in earlier surveys. In particular, failure definitions are very important in the present context, and the terms major (MaF) and minor failures (MiF) as defined in the IEC circuit breaker standard [7] have been adopted for all the component types. A switchgear major failure is defined as failure of a switchgear and control gear which causes the cessation of one or more of its fundamental functions. A major failure will result in an immediate change in the system operating conditions, e.g. the backup protective equipment will be required to remove the fault, or will result in mandatory removal from service within 30 minutes for unscheduled maintenance. Correspondingly, a switchgear minor failure is failure of an equipment other than a major failure or any failure, even complete, of a constructional element or a sub-assembly which does not cause a major failure of the equipment. Only major failures will be dealt with in the present summary.

3. SF6 CIRCUIT BREAKERS


3.1 Participation and surveyed service experience The survey includes 281 090 circuit breaker (CB) years of service experience. This is more than four times as much as the previous circuit breaker survey carried out around 1990 [8]. Population and failure cards were received from 30 countries, but the size of the contribution from the individual countries varies a lot. 39% of the surveyed service experience originates from one dominating country. 45% of the experience relates to live tank circuit breakers, 31% to GIS, and the remaining 24% to dead tank circuit breakers. Figure 1 shows the surveyed service experience sorted by voltage level and kind of service. Equipment rated for above 700 kV constitutes only 0.14% of the surveyed population and is not visible in the chart.
Bus coupler 10% Capacitor 3% Cable 6% Shunt reactor 1% 100<=U<200 kV 36.6% 200<=U<300 kV 15.3%

Overhead line 56% Transformer 24%

300< =U<500 kV 11. 8% 500<=U<700 kV 1. 9% 60<=U<100 kV 34.2%

Figure 1. Circuit breaker service experience according to kind of service (left) and voltage (right).

There is a significant shift in operating mechanism technology in the populations in the present compared to the previous survey, see Figure 2. The fraction of the circuit breakers that are equipped with hydraulic drives is reduced from 51% to 26%, while the portion with spring drives has increased from 18% to 52%. Pneumatic drives still account for a much as 22% of the surveyed experience.

Spring 18%

Spring 52%

Hydraulic 51%

Other 1%

Pneumatic 30% Pneumati c 22% Hydraulic 26%

Figure 2. Comparison between the previous and present surveys with regard to type of operation mechanism used.

3.2 Failure frequencies and characteristics The overall major failure frequency is calculated to be 0.30 MaF per 100 CB-years of service. In the previous survey the corresponding number was 0.67, indicating that SF6 circuit breaker reliability has improved significantly during the some 16 years between the surveys. The failure frequency, still however, increases substantially with increasing voltage level, see Figure 3.
5

MaF frequency [per 100 CB-years]

Previous survey 4 Present survey

0 60<=U< 100 kV 300<=U <500 kV 100<=U<200 kV 200<=U<300 kV 500<=U<700 kV >=700 kV Total

Figure 3. Major failure frequency as a function of voltage level for the present and the previous survey.

Live tank SF6 circuit breakers show an approximately three times higher major failure frequency as GIS or metal enclosed units; 0.48 and 0.14 MaF per 100 CB-years of service, respectively. This is approximately the same ratio as in the previous survey. For the first time failure frequencies have been correlated to the breakers kind of service; i.e., whether it switches overhead lines, cables, transformers, reactors, etc. The results are shown in Figure 4. Large differences are observed. The major failure frequencies for circuit breakers operating on shunt reactors are around one order of magnitude higher than for line and transformer breakers. It is assumed that this partly, but not entirely, attributed to the former ones in general are operated more frequently. Figure 5 shows major failure frequency as a function of year of installation. Hence, general aging effects but also changes in design and quality are expected to influence this relationship.

MaF frequency [per 100 CB-years]

6 5 4 3 2 1 0 Overhead line Transformer Shunt reactor Capacitor Bus coupler Cable Ot her

Live tank Dead tank GIS

Figure 4. Circuit breaker major failure frequencies for different kinds of service.
1

MaF frequency [per 100 CB-years]

Live tank 0.8 Dead tank GIS 0.6

0.4

0.2

0 1984-1988 1999-2003 1979-1983 1989-1993 Before 1979 1994-1998 2004-2007

Figure 5. Major failure frequencies as function of year of installation for the different SF6 circuit breaker technologies.

For AIS and GIS there is a tendency that newer equipment has less major failures than older equipment, and the difference is substantial. For the surveyed dead tank population no such relationship is visible. The major failure mode distribution is shown in the left part of Figure 6. Does not close on command and Locking in open or closed position are the most common major failure modes.
Loss of mechanical integrity 8% Locking in open or close position 25% Other 17% Operating mechanism 50%

Opens without command 5%

Does not open on command 16%

Does not close on command 28%

Electrical control and aux. circuits 30%

Total

Components at service voltage 20%

Figure 6. Distribution of circuit breaker major failure modes (left) and sub components responsible for the major failure (right).

When identifying the sub component responsible for the major failures the distribution becomes as shown in the right part of Figure 6. Roughly half of the major failures occur in the operating mechanism, and a large portion is caused by malfunctions in the electrical control and auxiliary circuit. These findings are approximately the same as in the previous survey.

4. DISCONNECTORS AND EARTHING SWITCHES


4.1 Participation and surveyed service experience Large international service experience enquiries have not previously been performed for disconnectors and earthing switches, so there is no earlier results for comparison. The survey includes 935 204 years of disconnector and earthing switch (DE) years of service collected from 25 countries. Of this, 77% relate to disconnectors (DC) and 23% to earthing switches (ES). AIS equipment constitutes approximately 67%, the rest being GIS equipment. Figure 7 and Figure 8 show the distribution of the surveyed service experience.
250000

AIS service experience [DE-years]

Centre break 200000 Double break Knee type Vertical break 150000 Semi-pantograph Pantograph Earthing switch 100000

50000

0 100<=U<200 kV 300<=U<500 kV 60<=U<100 kV 500<=U<700 kV 200<=U<300 kV >=700 kV >=700 kV

Figure 7. Distribution of AIS earthing switch and disconnector designs at the different voltage ranges.
160000

GIS service experience [DE-years]

Earthing switches Other 120000 Disconnectors Combined DS ES

80000

40000

0 100<=U<200 kV 300<=U<500 kV 60<=U<100 kV 500<=U<700 kV 200<=U<300 kV

Figure 8. GIS disconnector and earthing switch surveyed service experience.

As can be seen in the graphs above, the AIS disconnector designs used at the different voltage levels differ substantially. The double break technology dominates below 100 kV.

4.2 Failure frequencies and characteristics The overall major failure frequency is found to be 0.29 and 0.05 MaF per 100 DE years of service for AIS and GIS equipment, respectively. As opposed to for circuit breakers, there is no obvious influence of voltage level, see Figure 9. Equipment rated for greater than 700 kV is not included in this figure, as the surveyed population is very small.
0.4

MaF frequency [per 100 DE-years]

AIS GIS 0.3

0.2

0.1

0 100<=U<200 kV 300<=U<500 kV 200<=U<300 kV 500<=U<700 kV 60<=U<100 kV Total


AIS GIS 0.3 Total

Figure 9. Major failure frequency for disconnectors and earthing switches as a function of voltage.

The age of the equipment, or more precisely the year of installation seems to have some impact on the failure frequencies, see Figure 10. In general, older disconnectors and earthing switches have more failures than new ones, but the observed difference is small. Much of the equipment that has been in service for 40 or more years shows a very modest failure frequency.
0.4

MaF frequency [per 100 DE-years]

0.2

0.1

0 1984 - 1993 1974 - 1983 1994 - 2003 Before 1974 2004 - 2007

Figure 10. Major failure frequency as a function of disconnectors and earthing switches year of installation.

When disregarding the (rather small) population of knee type devices, the many different designs used for AIS disconnectors show failure frequencies that are within a factor of two, see Figure 11. As for circuit breakers the most common failure mode for disconnectors and earthing switches is Does not operate on command, accounting for roughly three out of four major failures, see Figure 12. Moreover, as could be expected, Dielectric breakdown constitutes a larger portion of the failures in GIS than in AIS and for Loss of mechanical integrity the opposite is seen. 7

1.2

MaF frequency [per 100 DE-years]

0.8

0.4

0 Vertical break Pantograph Earthing switches Double break Knee type Semi-pantograph C entre break

Figure 11. Major failure frequency for the different AIS disconnector designs.
Locking in open or close position 4% Dielectrical breakdown 13% Loss of mechancial integrity 13% Other 4% Loss of mechancial integrity 1%

Other 6% Dielectrical breakdown 2% Locking in open or close position 7%

Does not operate on command 72%

Does not operate on command 79%

Figure 12. Distribution of major failure modes for AIS (left) and GIS (right) disconnectors and earthing switches.

5. INSTRUMENT TRANSFORMERS
5.1 Participation and surveyed service experience The survey includes 1 290 335 instrument transformers (IT) years of service experience. As opposed to the other component types, instrument transformers are reported as single phase units. The reason for this is that it is possible to have an instrument transformer on one phase only or to have different designs on different phases. Population and failure cards were received from 73 utilities in 25 countries. Figure 13 shows how the surveyed experience distributes with regard to voltage and kind. As can be seen, the majority of the information is obtained from voltages below 200 kV. Around 40% come from GIS installations. The majority of AIS instrument transformers service experience reported is for sealed oil impregnated paper instrument transformers. Very few optical and electronic instrument transformers were reported in the survey, and it was not possible to do any detailed analysis on these kinds of instrument transformers.

500000

IT service experience [IT-years]

400000

GIS Current transformers GIS Combined current and voltage transformers GIS Voltage transformers

300000

AIS Current transformers AIS Combined current and voltage transformer AIS Capacitive voltage transformers

200000

AIS Magnetic voltage transformers

100000

0 100<=U<200 kV 300<=U<500 kV 60<=U<100 kV 200<=U<300 kV 500<=U<700 kV >=700 kV

Figure 13. Instrument transformer surveyed service experience (counted as single phase unit years).

5.2 Failure frequencies and characteristics The overall major failure frequency is found to be 0.053 failures per 100 IT-years of service. As can be seen from Figure 14, GIS instrument transformers are found to be significantly more reliable than those installed in AIS.
0.16

MaF frequency [per 100 IT-years]

AIS GIS 0.12

0.08

0.04

0 300<=U<500 kV 100<=U<200 kV 200<=U<300 kV 500<=U<700 kV 60<=U<100 kV Total

Figure 14. Major failure frequencies for AIS and GIS instrument transformers.

The failure frequencies are less than the failure frequencies reported in a previous survey carried out around 1990 [9]. The previous study had a significantly different population that was surveyed (for example the previous survey did not include many GIS instrument transformers and the countries where the instrument transformers were installed were different). It is likely these differences in population have a significant affect and would have caused the previous survey to report a higher failure frequency. Figure 15 shows the major failure frequencies for the different kinds of instrument transformers. For GIS, current transformers appear more reliable compared with voltage transformers. This is anticipated as voltage transformers for GIS are generally more complex than current transformers. For AIS, the failure frequencies calculated seem to be a bit mixed, with current transformers and combined current and voltage transformers having a lower major failure frequency than voltage transformers.

0.12

MaF frequency [per 100 IT-years]

0.08

MVT: Magnetic voltage transformer CVT: Capacitive voltage transformer CCVT: Combined current and voltage transformer CT: Current transformer VT: Voltage transformer

0.04

0 MVT CVT CCVT CT VT CT

AIS

GIS

Figure 15. Major failure frequencies grouped after kind of instrument transformer for AIS equipment (green) and GIS equipment (pink).

Major failure frequency as a function of year of manufacture is shown in Figure 16. There is indication that instrument transformers manufactured prior to 1988 have a higher failure frequency than those manufactured after 1988. However there is no dramatic increase, and the increase in failure frequency reported is unlikely in general to require the user to significantly change maintenance or consider replacement.
0.16

MaF frequency [per 100 IT-years]

AIS GIS 0.12

0.08

0.04

1984-1988

1999-2003

1979-1983

1989-1993

Figure 16. Instrument transformer major failure rate as a function of year of manufacture.

For AIS oil impregnated paper instrument transformers, there are a number of reports of failures that caused fire and explosion. These failures are generally reported as internal dielectric failure. Additionally, the largest proportion of major failures for oil impregnated paper instrument transformers is due to internal dielectric failure. This suggests that manufacturers and users should concentrate on improving the dielectric performance of oil impregnated paper instrument transformers. For SF6 insulated instrument transformers the major failures reported were generally leaks.

6. GAS INSULATED SWITCHGEAR


6.1 Participation and surveyed service experience Failure information from a total of 88 971 GIS circuit breaker bay years of service experience have been collected from 55 utilities in 24 countries. The contribution from the different countries is quite

Before 1979

1994-1998

2004-2007

10

uneven, as two dominating countries account for as much as 92% of the surveyed experience. The results are compared with a previous GIS survey [10] covering service experience up to 1995. The portion of hybrid GIS installations is still relatively small, representing only about 8% of the collected GIS service experience. Outdoor installations slightly prevail over indoor at rated voltages of 300 kV and above, and are used more frequently than in the past. The utilities in countries other than the two dominant ones prefer indoor installations at all voltage classes, except for 700 kV and above. 6.2 Failure frequencies and characteristics Figure 17 shows a comparison between the failure frequencies determined in the present and previous survey. As for the circuit breakers there seems to be an increased failure frequency with increasing voltage. Moreover, reliability seems to have improved a little, with the overall failure frequency reduced from 0.53 to 0.37 major failures per 100 circuit breaker bay years of service. However, it should be kept in mind that the populations considered in the two surveys differ significantly, and that the number of failures is low in some of the categories (e.g., only four major failures are recorded for GIS rated for 700 kV and above).
MaF frequency [per 100 CB-bay-years]
6 Previous survey Present survey 4

0 60<=U<100 kV 100<=U <200 kV 200<=U<300 kV 300<=U<500 kV 500<=U<700 kV >=700 kV Total

Figure 17. GIS major failure frequencies as a function of voltage for the present and a previous survey.

Figure 18 reveals the influences of age on GIS reliability. For most of the voltage levels a shape resembling the well-known bathtub curve appears. The failure frequencies increase (with different steepness) the older the GIS are, and in the first years after installation some infant mortality failures appear. As expected, the switching equipment are responsible for most of the major failure in the GIS, see Figure 19. GIS instrument transformers are only responsible for some 5%.

11

MaF frequency [per 100 CB-bay-years]

4 60 U < 100 kV 100 U < 200 kV 3 200 U < 300 kV 300 U < 500 kV 500 U < 700 kV 2

0 1984-1988 1999-2003 1979-1983 1989-1993 Before 1979 1994-1998 2004-2007

Figure 18. GIS major failure frequency for the different voltage levels, sorted after year of installation.

100

GIS MaF distribution [%]

80 Other Instrument transformers Disconnectors and earthing switches Circuit breakers 40

60

20

0 60<=U<100 kV 200<=U<300 kV 100<= U<200 kV 300<=U<500 kV 500<=U<700 kV >=700 kV All

Figure 19. GIS major failures sorted after voltage level and after the component that failed.

The prevailing GIS major failure modes are Failing to perform requested operation or function (63%) and Dielectric breakdown (23%). The portion of the former rises with increasing age of the GIS and reaches a maximum at an age of about 15 to 20 years old. This most probably illustrates that most overhauls of operating mechanisms are scheduled to this age span, and that this timing is sometimes too late. With regard to sub assemblies responsible for major failures, Component in primary circuit, Component in control, auxiliary or monitoring circuit and Component in operating mechanism share the responsibility by about one third each.

7. GIS PRACTICES
Completed GIS maintenance cards were received from 20 utilities from 12 countries. Among the findings from analyzing the various topics addressed are:

12

Commissioning: Power frequency voltage testing with simultaneous partial discharge (PD) measurement is the most frequently used high voltage test during GIS commissioning. Impulse voltage testing, as a complimentary method to power frequency high voltage test, is not widely used. Condition monitoring and diagnostics: There is still little confidence in GIS continuous monitoring techniques. This also concerns PD measurement that is widely used for diagnostic testing. Various other diagnostic test methods commonly used on AIS are commonly used on GIS as well. Major maintenance (overhaul) experience: Only a third of the received cards indicate any experience with major maintenance. The prevailing reasons for performing major maintenance are that a fixed time has elapsed and that corrective maintenance is required. Predictive major maintenance based on equipment condition or on reliability centered studies is mentioned in only about one fifth of the responses. Extensions: Most responders indicated experience with GIS extensions. All reported GIS extensions were made by their original manufacturers, and in one third of cases there was not even a need for an adapter. Application of new technologies: Network operating requirements is the dominating factor when deciding on the single line diagram for new GIS. The responses indicate that most utilities do not apply different approaches for GIS and AIS. The experience with combined function GIS apparatus is small. The experience with turnkey projects is positive in more than a half of the responses. In general utilities still do not have much confidence in functional specifications.

8. CONCLUSIONS
Analyses of population of failure data covering the time period 2004 - 2007 and collected from 90 utilities in 30 countries yielded the following overall major failure frequencies: SF6 circuit breakers: Disconnectors and earthing switches: Instrument transformers: Gas insulated switchgear: 0.30 MaF per 100 CB years of service; 0.21 MaF per 100 DE years of service; 0.053 MaF per 100 IT years of service (single phase units); 0.37 MaF per 100 GIS CB bay years of service.

All results and findings from the WG A3.06 survey, including commentaries, information about how the survey was conducted, methods used for statistical analyses, recommendations for utilities and manufacturers, are presented in six comprehensive CIGR Technical Brochures that will be published shortly.

9. BIBLIOGRAPHY
[1] CIGR WG A3.06: Final Report of the 2004 - 2007 International Enquiry on Reliability of High Voltage Equipment, Part 1 - Summary and General Matters, CIGR Technical Brochure, 2011. (to be published) CIGR WG A3.06: Final Report of the 2004 - 2007 International Enquiry on Reliability of High Voltage Equipment, Part 2 - SF6 Circuit Breakers, CIGR Technical Brochure, 2011. (to be published) CIGR WG A3.06: Final Report of the 2004 - 2007 International Enquiry on Reliability of High Voltage Equipment, Part 3 - Disconnectors and Earthing Switches, CIGR Technical Brochure, 2011. (to be published)

[2]

[3]

13

[4]

CIGR WG A3.06: Final Report of the 2004 - 2007 International Enquiry on Reliability of High Voltage Equipment, Part 4 - Instrument Transformers, CIGR Technical Brochure, 2011. (to be published) CIGR WG A3.06: Final Report of the 2004 - 2007 International Enquiry on Reliability of High Voltage Equipment, Part 5 - Gas Insulated Switchgear CIGR Technical Brochure, 2011. (to be published) CIGR WG A3.06: Final Report of the 2004 - 2007 International Enquiry on Reliability of High Voltage Equipment, Part 6 - GIS practices, CIGR Technical Brochure, 2011. (to be published) IEC 60694:2002: Common specifications for high-voltage switchgear and control gear standards. CIGR WG 13.06: Final report of the second international enquiry on high voltage circuitbreaker failures and defects in service, CIGR Technical Brochure no. 83, 1994. CIGR SC A3: State of the art of instrument transformers, CIGR Technical Brochure no. 394, 2009.

[5]

[6]

[7] [8] [9]

[10] CIGR WG 23.02: Report on the second international survey on high voltage gas insulated substations (GIS) service experience, CIGR Technical Brochure no. 150, 2000.

14

You might also like