Agent Release Control Panel
GENERAL INFORMATION
S/N 70201602 (120VAC Input) S/N 70101603 (220VAC Input) The Micro 1012 is a six zone conventional control panel for single and dual hazard agent releasing applications. The Micro 1012 provides reliable fire detection, signaling and protection for commercial, industrial and institutional buildings requiring agent-based releasing. The control panel is compatible with conventional input devices such as Hochiki two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. Refer to the Device Compatibility Document for a complete listing of compatible devices. Four outputs are programmable as NACs (Notification Appliance Circuits) or releasing circuits. Three programmable Form-C relays (factory programmed for Alarm, Trouble and Supervisory) and 24 VDC special application resettable and non-resettable power outputs are also included on the main circuit board. The Micro 1012 supervises all wiring, AC voltage, battery charger and battery level. Activation of a compatible smoke detector or any normally-open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicator, display alarm information on the panels LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate an optional module used to notify a remote station or initiate an auxiliary control function. The Micro 1012E offers the same features as the Micro 1012 but allows connection to 220/240 VAC. Unless otherwise specified, the information in this data sheet applies to both the 110/120 VAC and 220/240 VAC versions of the panels.
Micro 1012
FEATURES
Designed for agent releasing standards NFPA 12, 12A, and 2001 Disable/Enable control per input zone and output zone Extensive transient protection Dual hazard operation Adjustable predischarge, discharge and waterflow delay timers Cross-zone (double interlock) capability Six programmable Style B (Class B) IDCs (Initiating Device Circuits) Four programmable Style Y (Class B) output circuits (special application power) Strobe synchronization Three programmable Form-C relays 7.0 amps total 24 VDC output current Resettable and non-resettable output power Built-in programmer ANN-BUS for connection to optional (up to 8 total of any of the following): N-ANN-80 Remote LCD Annunciator (S/N 70101604) N-ANN-I/O LED Driver (S/N 70101605) N-ANN-S/PG Printer Module (S/N 70101606) N-ANN-RLY Relay Module (S/N 70101627) N-ANN-LED Annunciator Module (S/N 70101628)
2008 Chemetron Fire Systems All rights reserved (2/08). 4801 Southwick Drive, 3rd Floor Matteson, IL 60443 708/748-1503 FAX 708/748-2847
Page 1
History log with 256 event storage 24 volt operation Low AC voltage sense Outputs programmable for: Releasing circuits or NACs
Control Buttons
ACKNOWLEDGE ALARM SILENCE SYSTEM RESET (lamp test) DRILL
AC Power - TB1:
Micro 1012: 120 VAC, 50/60 Hz, 2.3 amps Micro 1012E: 240 VAC, 50 Hz, 1.15 amps Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation Supervised, nonpower-limited
User Interface:
Integral 80-character LCD display with backlighting Real-time clock/calendar with automatic daylight savings time adjustment and control ANN-Bus for connection to remote annunciators Audible or silent walk test capabilities Piezo sounder for alarm, trouble and supervisory
2008 Chemetron Fire Systems All rights reserved (2/08). 4801 Southwick Drive, 3rd Floor Matteson, IL 60443 708/748-1503 FAX 708/748-2847
Page 2
NOTE
TWO CLASS A CONVERTER MODULES ARE REQUIRED TO CONVERT ALL FOUR OUTPUT CIRCUITS AND SIX INITIATING DEVICE CIRCUITS. 4XTM (S/N 70100777): Transmitter Module provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. N-ANN-80 (S/N 70101604): LCD Annunciator is a remote LCD annunciator that mimics the information displayed on the FACP LCD display. N-ANN-RLY (S/N 70101627): Relay Module, which can be mounted inside or outside the cabinet, provides 10 programmable Form-C relays. N-ANN-S/PG (S/N 70101606): Serial/Parallel Printer Gateway module provides a connection for a serial or parallel printer. N-ANN-I/O (S/N 70101605): LED Driver Module provides connections to a user supplied graphic annunciator. DP-51050 (S/N 70101608): Dress panel (red) is available as an option. The dress panel restricts access to the system wiring while allowing access to the membrane switch panel. TR-CE (S/N 70101609):Trim Ring (red) is available as an option. The trim ring allows semi-flush mounting of the cabinet. BB-26 (S/N 70101612): Battery box, holds up to two 26 Amp Hour batteries and CHG-75. PRN-6 (S/N 70101611): UL listed compatible event printer. Dot-matrix, tractor-fed paper, 120 VAC. PRT-PK-CABLE (S/N 70101607): Programming cable. Used to update the FACPs flash firmware. (Also requires an RS485 to RS232 converter.)
NOTE
TOTAL CURRENT FOR RESETTABLE POWER, NONRESETTABLE POWER AND OUTPUT CIRCUITS MUST NOT EXCEED 7.0 AMPS.
2008 Chemetron Fire Systems All rights reserved (2/08). 4801 Southwick Drive, 3rd Floor Matteson, IL 60443 708/748-1503 FAX 708/748-2847
Page 3
SYSTEM SPECIFICATIONS
System Capacity:
Annunciators = 8
Electrical Specifications:
Micro 1012: 120 VAC, 50/60 Hz, 2.3 amps Micro 1012E: 240 VAC, 50 Hz, 1.15 amps Wire size: minimum 14 AWG (2.0 mm2) with 600 V insulation, supervised, nonpower-limited
NFPA Standards:
The Micro 1012(E) complies with the following NFPA 72 Fire Alarm Systems requirements: NFPA 12 - CO2 Extinguishing Systems NFPA 12A - Halon 1301 Extinguishing Systems NFPA 72 - National Fire Alarm Code for Local Fire Alarm Systems and Remote Station Fire Alarm Systems (requires an optional Remote Station Output Module) NFPA 2001 - Clean Agent Fire Extinguishing Systems
Cabinet Specifications:
Door: 19.26" high x 16.82" wide x 0.72" deep (48.92 cm x 42.73 cm x 1.82 cm) Backbox: 19.00" high x 16.65" wide x 5.25" deep (48.26 cm x 42.29 cm x 13.34 cm) Trim Ring: 22.00" high x 19.65" wide (TR-CE) (55.88 cm x 49.91 cm)
Shipping Specifications:
Dimensions: Height = 22.00" (50.80 cm) Width = 22.50" (57.15 cm) Depth = 8.50" (21.59 cm)
4801 Southwick Drive, Third Floor Matteson, Illinois 60443 (708) 748-1503 FAX (708) 748-2847 web: www.chemetron.com email: info@chemetron.com
THIS DOCUMENT IS NOT INTENDED TO BE USED FOR INSTALLATION PURPOSES. All specifications are subject to change without notice. The seller makes no warranties, express or implied, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose, except as expressly stated in seller's sales contract or sales acknowledgment form. MANUFACTURED BY HONEYWELL FIRE SOLUTIONS