Written dimensions on these drawings shall have precedence over scaled dimensions. Contractor shall verify and be responsible for all dimensions and conditions on the job. OB+Architecture Inc. must be notified immediately in writing of any variation from the dimensions and conditions shown on these drawings. Field verify all conditions prior to laying out or fabricating associated work. Bring to the architect's attention any deviation from designed conditions and field conditions prior to ordering
FACTORY-INSTALLED
materials and installing work, and cooperate with architect to modify such conditions at no additional cost to the owner, architect or architect's consultants. Shop details must be submitted to the architect's office and reviewed by the architect prior to ordering materials, fabrication and delivery to the job site, unless otherwise provided for under the specific contractual agreement between the architect and client. OB+Architecture Inc. expressly reserves its common law copyright and other
SA DUCT SMOKE
DETECTOR W/ AC #2
M
7
M M , 3 4" M M , 1"
7 7 4
4
M
M 5
5 AC-2
AC-3 AC-1 AC-4
24"Ø (OUTDOOR UNIT)
M , 3/4" (BELOW GRADE)
8 AC-5
(OUTDOOR UNIT)
24"Ø 14x24 20x24 28x33
1"
3/4" 3/4"
M
7
property rights in these documents. These documents are not to be reproduced, changed, or copied in any form or manner whatsoever, nor are they to be assigned to a third party without first obtaining the written permission and written consent of OB+Architecture Inc. In the event of unauthorized use of these documents by a third party, the third party shall hold OB+Architecture Inc. harmless and agrees to remunerate OB+Architecture Inc.
M
EF-1 20x16 28x14
1012 CFM
M AC-5 (INDOOR UNIT)
MOUNT TOP
10
WEIGHT 26 LBS
WEIGHT 26 LBS
@ 8'-0" AFF±
MOUNT TOP
HVAC SOFFIT
16 x12 CD-2
4"Ø
CD-2 CD-1 32
16 x12 18 x16 6"Ø 8"Ø CD-2
60 135 4"Ø
CD-3 CD-3 33
8"Ø 8"Ø 18x16 TG-2
197 13 x 9 197 TG-2
5"Ø 5"Ø
CD-3 (2) RG-1 32 33
8"Ø 12"Ø TG-2 TG-1
9x9 16 x 9 197 400 10"Ø
7"Ø
60 135 28x14 RG-1 TG-1
14"Ø 16"Ø
M 733 775
TG-1
T 3
#3
T 10"Ø
#2 195
issued: ADVANCE REVIEW 21 JULY 2008
20x16
18 x 16 TG-1
10"Ø
195 TG-2 revised:
GRV-1 7"Ø
RG-1 RG-1 55 CD-2
CD-3 16"Ø 16"Ø (2) RG-1 6"Ø
8"Ø 12"Ø 910 910 14"Ø 55
197 733 CD-1
CD-3 CD-1 CD-1 8"Ø
8"Ø 8"Ø 8"Ø 205
M 210 170 170
1 EF-2
CD-1
24" x 16" M M (2) DG-1 8"Ø
TOP @ 8'-0" AFF 2 6 12"x12" 170 TG-1
506 CFM M 340 14"Ø 3/4" DOOR
CFM 8x8 14 x 8 14 x 12 14 x 12 460 UNDERCUT
(MAX)
CD-1
6"Ø
45 GRV-3
8"Ø
CENTRAL
CD-4
TG-1 6"Ø
10"Ø 10 x 12 90
6"Ø
190
TG-1
18"Ø
1335
TG-1
18"Ø
1335
CD-1
6"Ø
50
TG-1
10"Ø
190
CD-1
8"Ø
160
CD-1
8"Ø
230
CD-1
8"Ø
230 EF-7
FLORIDA
CD-1 CD-1 CD-1
6"Ø 8"Ø 8"Ø T
70 145 145 #1
TG-2 TG-2 TG-2 TG-2
CD-1 8"Ø 8"Ø CD-1 CD-1 8"Ø 8"Ø CD-1
6"Ø
95
95 95
18 x 13
6"Ø
95
6"Ø
95
95
18 x 16
95 6"Ø
95
CD-1
10"Ø
ANIMAL
9 x 13 14 x 13
250
HOSPITAL
TG-1
CD-1 12"Ø
6"Ø address: 1201 ALAFAYA TRAIL
250
50
OVIEDO, FLORIDA
GRV-2 32765
TG-1 NORTH
16"Ø
515
HVAC PLAN
1
project
number: 2007-12
SCALE: 1/4" = 1'-0"
UNDERCUT
3/4" DOOR
3/4" DOOR
3/4" DOOR
UNDERCUT UNDERCUT
12"Ø
CD-2 CD-2
6"Ø 6"Ø TG-1
CD-2
for such use in an amount equal to the original fee for the original documents, plus legal fees, court costs, collection fees and other costs.
85 85 12"Ø
6"Ø
85 3/4" DOOR 265
UNDERCUT
CD-1 CD-1
10"Ø 10"Ø CD-1 MECHANICAL ENGINEER
CD-1 10"Ø
415 415 8"Ø 265 A. PETER TANKEL, P.E.
175
EF-6 EF-5 EF-4 EF-3 702 DENTON ROAD
WINTER PARK, FL 32792
PE 41231
title:
M5: PROVIDE AND INSTALL A 24" DIA. AND 24" HIGH DRYWELL WITH PEA GRAVEL FILL ACCEPTABLE HVAC PLAN
HVAC KEY NOTES : TO THE AHJ.
M8: ROUTE CONDENSATE PIPING FROM AHU DOWN IN WALL, OUT WALL AND BELOW GRADE, AND
OB / RG
M2: PROVIDE AND INSTALL NEW RUSKIN OR EQUAL GALVANIZED STEEL 2 POSITION OPEN CLOSED
TERMINATE IN DRYWELL. date:
MOTOR OPERATED DAMPER. 120 VAC. SIZE TO MATCH LOUVER OPENING AS NOTED ON PLAN.
INTERLOCK BOTH DAMPERS, EF-1, AND EF-2 WITH WALL SWITCH AS SHOWN ON PLAN. 21 JULY 2008
M9: INSTALL 4" DRYER EXHAUST CAP WITH DAMPER AND WITHOUT SCREEN. PREFAB LISTED
lman:
DRYER WALL CAP FOR USE WITH RESIDENTIAL ELECTRIC CLOTHES DRYER INSTALLED PS-M2.3
M3: PROVIDE WALL SWITCH LABELED FAN AND T'STAT LABELED AC-3 ADJACENT TO EACH OTHER.
APPROX. . 9'4" TO TOP OF CAP. ROUTE 4" GALV. STEEL ELECTRIC CLOTHES DRYER VENT
PROVIDE ADJACENT PERMANENT WEATHER PROOF WALL SIGNAGE TO READ " DO NOT
DUCT (WITH NO PROTRUDING FASTENERS AND WITH OVERLAPPED JOINTS THAT PREVENT sheet setup:
OPERATE VENTILATION FANS AND AIR CONDITIONING AT THE SAME TIME." NOTE: INTERLOCK MOJA-HVAC
LINT BUILD UP FROM CLOTHES DRYER TO WALL CAP) FROM RESIDENTIAL ELECTRIC CLOTHES
BOTH MOTOR OPERATED DAMPERS, EF-1, AND EF-2 WITH WALL SWITCH.
DRYER TO WALL CAP. MAX. LENGTH OF STRAIGHT DUCT SHALL BE 15' WITH MAX. OF 2 sheet
ELBOWS TO MEET. SECTION 504 OF 2004 FMC. number:
M4: PROVIDE AND INSTALL SOLVENT WELDED SCHEDULE 40 PVC CONDENSATE PIPE WITH A 4" P
TRAP AND CLEANOUT AT AC UNIT AND ROUTE TO DRYWELL. PIPE SIZE IS NOTED.
M10: ROUTE REF. TUBES FROM INDOOR TO OUTDOOR UNITS IN 4" PVC CONDUIT BELOW GRADE.
M2.1