Professional Documents
Culture Documents
Location :
: : : :
-1-
-2-
INDEX
Sl.No 1. 2. 3. Topics Page No.
15. 16.
Introduction 5 Key Performance Index (KPI) 5 Basic Trouble Shooting Tips. 9 i. NSN Ultra BTS ... 10 ii. NSN Metro BTS. 18 iii. NSN Flexi BTS.. 22 iv. NSN Flexi Hopper. 29 v. BSC 3i Frequently used Commands 32 vi. Ceragon SDH Radio. 33 vii. NEC SDH Radio 34 viii. Tejas Mux 37 ix. ECI Mux.......... 42 Log in Cable Pin Configuration 48 BTS External Alarm Details... 51 Fault Severity Definition. 52 Outage Restoration Priority.. 52 Site Acceptance Process 53 PT 4 Process.. 55 Fleet Management Process .. 56 OHS Process and Safety Tips.. 57 Spare Management Overview.. 59 Test and Measurement Equipment Handling Tips. 665 Standard Templates and Checklist 76 i. Preventive Maintenance Checklist ii. Pre-monsoon Checklist iii. Daily Activity Record iv. Site Asset Database v. Acceptance Testing Checklist Site Details. 77 Network Diagram and PCM Plan. 79
-3-
-4-
Introduction
This handbook is intended to serve the purpose of reference to engineers in his location and will be a ready reckoner for locating his site, network details and contains basis trouble shooting tips for NEs in his location area, log-in cable pin configuration, various process overview and escalation matrix. Also this handbook contains various operational checklists which need to be updated as per schedule mentioned in the JFLM Service Level Agreement (SLA). The handbook will be handed over to all field engineers in a circle on his joining and needs to be handed over to CTL or new engineer on his leaving the organization, location, cluster or circle.
-5-
Retainability Network Wide Retainability (NBH) Cell Wise Retainability(BBH) Quality Data Network Availability Network Accessibility Retainability Quality GPRS
EDGE
-6-
-7-
-8-
Object affected
Object state
The state of the affected object at the time the alarm is issued. The options are: Enabled Disabled
Unit
Instruction This field gives instructions for the operator (at the NMS/NetAct or at the BSC) how to correct the fault reason causing the alarm.
Alarm cancelling This field describes how the alarm is cancelled. The options are: Automatic Manual
Steps 1 Check the alarm number and alarm name and refer to Alarms list for UltraSite, MetroSite, Flexi EDGE BTS to find the correct alarm description table. 2 Find the fault reason in the Fault reason field in the alarm description table. 3 Follow the instructions in the proposed order given in the Instruction field. See also alarm cancelling information in the Cancelling field. 4 If the fault reason cannot be found in the Fault reason field, follow the instructions given for Other faults . 5 If there is no fault reason text with the alarm, refer to the correct alarm description table and follow the possible instructions given in the Instruction field.
-9-
Other faults.
Automatic
Automatic
Automatic
Automatic
- 10 -
Other faults
Automatic
BCF
Enabled
Instruction 1. Ensure that the ambient temperature of the base station is within specified limits. 2. Check that the heater is working properly if equipped. 3. Replace the PWSx. 1. Ensure that the ambient temperature of the base station is within specified limits. 2. Check that the heater is working properly if equipped. 3. Replace the transmission unit. 1. If another slot in the cabinet is empty, move the power unit into the empty slot. 2. The temperature sensor is probably broken. Temperature changes cannot be measured. Replace the power unit. 1. Temperature sensor is probably broken. Temperature changes cannot be measured. Replace the transmission unit. 1. Open the Nokia UltraSite BTS Hub Manager and check the active alarms. If this base station or other base stations beyond it otherwise operate properly, there is no need for an immediate repair. However, the transmission alarms for the faulty unit are not reported to the BSC or the Nokia BTS Manager. 2. Reset the faulty transmission unit. 3. If the alarm reappears after the transmission unit reset, switch the cabinet power off and on. If the alarm reappears after the recovery actions above, replace the faulty transmission plug-in unit.
Automatic
Power unit has lost connection to temperature sensor. Transmission unit has lost connection to temperature sensor.
Automatic
Automatic
Automatic
- 11 -
Automatic
. If the fan still does not rotate after the first TSxx was
replaced, reinsert the original TRX and replace the second TSxx in front of the same fan unit. If the fan starts rotating, the second TSxx is broken.
. If the fan does not work after the TSxx removal test, the
fan is broken and must be replaced. 4. For other fan alarms, replace the corresponding fan unit. 5. Otherwise, replace the BOI. Note: This alarm is related to fans located in the back of the cabinet. 1. Check that the fan cable is connected to the door switch box. 2. If something has jammed the cabinet fan unit, remove the jamming object. Otherwise, replace the fan unit. 3. Replace the door switch box. 4. Otherwise, replace the BOI. Note: This alarm is related to door fan (Outdoor BTS only). 1. If the fan is dirty, clean the fan unit. Cooling fan speed has reduced from the set speed. 2. If something has jammed the cooling fan unit, remove the jamming object. Otherwise, replace the fan unit. Note: This alarm is related to fans located in the back of the cabinet. 1. If the fan is dirty, clean the fan unit. 2. If something has jammed the cabinet fan unit, remove the jamming object. Otherwise, replace the fan unit. Note: This alarm is related to door fan. 1. Replace the faulty power unit. The cabinet has more than one power supply unit. The other power units are still functioning. 1. Ensure that the input voltage is correct. 2. Replace the faulty power unit. The cabinet has more than one power supply unit. The other power units are still functioning. 1. Give a one-minute power reset to the whole BTS cabinet. 2. Check the power unit(s) and power backplane connectors, and replace if faulty. 1. Give a one-minute power reset to the whole BTS cabinet. 2. Reset the BCF. 3. If the cabling between the BOI and the Interface board on the top side of the cabinet is OK, replace the Interface board. Automatic
Automatic
Automatic
Automatic
- 12 -
Automatic
Mismatch between BSC/MMI configuration file and the actual configuration. BSS synchronization failed.
Automatic Automatic
Automatic
Other faults.
Instruction 1. Check whether either of the following alarms is active: 7606 TRX FAULTY 7607 TRX OPERATION DEGRADED and follow the instructions given for the active alarm(s).
Automatic
Instruction 1. Check the RSSI measurements by BTS Manager. Note: From BTS Manager, open the RSSI Comparison Values dialog box or Site Information dialog box to pinpoint the alarming RSSI value and antenna. From CX5 CD1.0 onwards the history of last active RSSI alarms will provide the information of which antenna line was detected faulty. Note: There is a hysteresis of 2 dB in the cancellation of the alarm. The alarm is cancelled when the RSSI measurement result is less than RXDL -2 dB. 2. Check and measure the antenna lines. 3. Check the BTS RF cables and connections. 4. Replace the combiner unit. Check that the RXDL parameter at the BSC is set to a reasonable value,taking into account the site conditions to prevent unnecessary alarms. Replace the TSxx unit.
Automatic
- 13 -
Other faults.
Automatic
Failure in 26 MHz clock input. Interface problems between O&M and DSP SW. 1st branch LNA in dual variable gain duplex unit is faulty. 2nd branch LNA in dual variable gain duplex unit is faulty. BB2x temperature is dangerously high.
Instruction 1. Check the TSxx TX cable. Replace if faulty and reset TRX to cancel the alarm. 2.If the TX cable is OK, the TSxx is faulty. Replace the TSxx. 1. Check the antenna line and Bias-T cabling. 2. Reset the sector. 3. Check all RF cabling between the TSxx's TX output connector and top of the cabinet (including WCDx and DVxx or RTxx units). 4. Replace the Bias-T. 5. Replace TSxx. 1. Check whether the TSxx/DVxx/RTxx frequency is compatible with the BSC network parameters. 2. Reset the TRX/sector. 3. Replace the TSxx. 1. Check the BTS configuration and install the BB2x if it is missing. 2. Replace the BB2x. Reset the TRX/sector. Note: This alarm refers to the connection between BOIA and BB2x. Do not replace TSxx in this case. 1. If all TRXs indicate this fault, replace the BOI. 2. If only one TRX indicates this fault, replace the BB2x. 1. Reset the TRX/sector. 2. If the fault reappears, replace the BB2x. 1. Replace the DVxx.
Automatic.
Automatic.
1. Replace the DVxx. Automatic. 1. Ensure that the ambient temperature of the base station is within specified limits. 2. Check the cabinet fans. 3. Replace the BB2x. 1. Ensure that the ambient temperature of the base station is within specified limits. 2. If air filters are used, check that they are not clogged. 3. If outdoor cabinet is used, check the door fan. 4. Check the cabinet fans. 5. Replace the TSxx. Automatic. Automatic. Automatic.
Automatic.
- 14 -
Automatic
Non EDGE TRX device used accidentally in EDGE capable mode. TRX is stuck in waiting for system information state. FBUS HW failure. The transmitter output of TRX is overdriven. The transmitter output power has dropped at least 3 dB. The transmitter output power is too low. Fault in RF module transmitter interface. Fault in RF module receiver interface. RF module initialization has failed. The RF transmitter synthesizer is not locked. The RF transmitter frequency hopping synthesizer 1 is not locked. The RF transmitter frequency hopping synthesizer 2 is not locked. The RF receiver synthesizer is not locked The RF receiver frequency hopping synthesizer 1 is not locked. The RF receiver frequency hopping synthesizer 2 is not locked. Severity ** Fault reason 1st branch LNA in dual variable gain duplex unit is faulty.
Automatic
Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic
Automatic Automatic
Automatic
Instruction 1. Replace the DVxx. 2nd branch is still working and calls are getting through.
- 15 -
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
- 16 -
Automatic
1. No actions required.
Mentioned above are few of the most common alarm which is visible in NSN system. For complete details of all alarms, refer to NED.
- 17 -
1. No actions required.
Automatic
Unit VTxx, HVxx, WTxx, CTxx, VSxx, HVSx, CVSx, VIFA Alarm cancelling Automatic
Instruction 1. Check the synchronisation cabling. 2. If the cabling is OK, replace the master TRX (TRX-1). 3. Reset the BCF. 1. If the power supply unit LED is green, check the TRXs and replace the faulty TRX. TRX connectors are probably broken. 2. If the power supply unit LED is red, replace the power supply unit. 1. Replace the VIFA unit. 1. Check whether the following alarm is active: 7621 INTOLERABLE CONDITIONS ON SITE and follow the instructions given for the alarm. 2. Even if alarm 7621 is not active, and there is only one TRX in the cabinet, follow the instructions given for alarm 7621.
Automatic Automatic
Automatic
3. If alarm 7621 is not active and the cabinet has more than one TRX, replace the master TRX. 1. Check whether either of the following alarms is active: 7606 TRX FAULTY Other faults. 7603 BTS FAULTY and follow the instructions given for the active alarm(s). 7601 BCF OPERATION DEGRADED Severity Object affected Object state ** Fault reason Cabinet I2 C bus is jammed. Difference between PCM and base station frequency reference. BCF Enabled
Instruction 1. Switch the site power Off and On. 2. Check the fan unit, the power supply unit and the TRXs. If necessary, replace the faulty unit(s). 3. If the fault reappears, replace the cabinet. The units inside the cabinet can be reused in the new cabinet. 1. Check the cabling.
Automatic
- 18 -
Automatic
Automatic
Automatic
Automatic
1. Check whether the following alarm is active: 7606 TRX FAULTY and follow the instructions given for the alarm. 7604 BTS OPERATION DEGRADED Severity Object affected Other faults. ** Fault reason BTS
Automatic
Instruction 1. Check the RSSI measurements with BTS Manager. 2. Check and measure the antenna lines. 3. Check the BTS RF cables and connections. 4. Check that the RXDL parameter at the BSC is set to a reasonable value, taking into account the site conditions in order to prevent unnecessary alarms. 5. Replace the TRX unit.
Automatic
Automatic
- 19 -
Other faults.
Automatic
7605 BTS NOTIFICATION Severity Object affected Object state * BTS Enabled Fault reason Instruction Fan unit operation 1. If something has jammed the fan unit, remove the jamming object. degraded. Otherwise replace the fan unit. 7606 TRX FAULTY Severity Object affected Object state ** Fault reason TRX Disabled
Unit VMFA, HVMF Alarm cancelling Automatic. Unit VTxx, HVxx, WTxx,CTxx Alarm cancelling
Instruction 1. The TRX is either faulty or its frequency band is different from the one that was configured into BSC. Replace the TRX with a functional TRX or with another TRX with correct frequency band. 2. There is an incompatible TRX power type in baseband hopping sector. A mixture of High and Low Power TRXs is used in a BB hopping enabled sector. Replace the incompatible TRX power type.
Automatic
Non EDGE TRX device type used accidentally in Edge Capable Mode.
1.Replace the Non-EDGE TRX with an EDGE TRX (STIRC sector enabled).
Automatic
1. Check the antenna and RX cabling. If the antenna and RX cabling are faulty, correct the problem and run TRX test to cancel the alarm. 2. If RX diversity is in use, check that the diversity RX cabling and/or Antenna connection termination is done properly. faulty. 3. If the antenna and RX cabling are OK, the TRX is faulty. Replace the faulty TRX. Note: An alarm reports only if the PMAX value is 0 or 2 (two highest power levels). Other faults. 1. Replace the TRX. 7607 TRX OPERATION DEGRADED Severity Object affected Object state ** Fault reason TRX Instruction 1. Check the antenna and RX cabling. If the antenna and RX cabling are faulty, correct the problem and run TRX test to cancel the alarm. 2. If RX diversity is in use, check that the diversity RX cabling and/or termination is done properly. 3. If the antenna and RX cabling are OK, the TRX is faulty. Replace the faulty TRX. Note: An alarm reports only if the PMAX value is 0 or 2 (two highest power levels). 1. Replace the TRX. Enabled
Other faults.
- 20 -
Manual/Automatic
4. If the alarm reappears after the recovery actions above, replace the faulty transmission plug-in unit. 7616 OSCILLATOR ADJUSTMENT TEMPORARILY INTERRUPTED Severity Object affected Object state * BCF Enabled Fault reason Instruction Oven oscillator 1. Check the Abis connection. adjustment function interrupted. 2. If the Abis connection is OK, replace the faulty VIFA unit.
- 21 -
Instruction An object (TRX, Sector or BCF) is locally blocked by a BTS Manager command.No repair actions required, alarm is cancelled when object is locally deblocked by BTS Manager. Object affected BCF Instruction Object state Disabled Unit ESEA, ESMA
Air i/f reference clock 26 MHz not available. ESMA System module detected that its Oven Controlled 26 MHz Oscillator is not generating the frequency reference.. 1. If 7600 - BCF FAULTY "ESMA System module temperature dangerously high" is also active, follow the fault instructions to resolve. 2. Issue HW Reset to ESMA from Remote BTS Manager. 1. Make sure that ambient temperature of the site is within normal operating temperature range (-35 +50C/-31+122F). 2. Issue a HW Reset to ESMA from (remote) BTS Manager. Note: This site's bypass transmission will be cut for 1-2 minutes. 3. Replace ESMA. ESMA System module detected no synchronisation signal at synchronisation input (SIN) port at startup. 1. Check that the BCF synchronisation related settings are correct at the BSC via MML command(s) (ZEFO...). 2.If another BTS is the synchronisation master, check if that it is up and alive. 3. Check that the synchronisation cabling is correctly mated between the units Replace ESMA. ESMA System module detected that a hardware failure has occurred in the ESEA System Extension module. 1. Issue HW reset to ESEA from BTS Manager. 2. If fault persists, replace ESEA and reset the BCF. ESEA System Extension module does not respond to polling command from ESMA System module. 1. Check the power distribution to ESEA. 2. Check that the bus cable is correctly mated between ESMA and ESEA. 3. Replace ESEA. 4. Replace ESMA. Internal temperature of ESMA System module has exceeded +95C/+203F. 1. Ensure that the ambient temperature of the base station is below +50C/+122F. 2. Check if any fan alarms are also active. If active, refer to fan alarm instructions to resolve. 3. Replace ESMA. 1. SCF contains ESEA, but it is not detected in the actual configuration. 2. SCF does not contain ESEA, but it was detected to port 6 of ESMA 3. If cabling source is 'AUTODETECTED' in the SCF, do BCF reset with RFCAD. 4.a) Modify the SCF to match the actual configuration. OR 4.b) Modify the actual configuration to match the SCF. 5. Replace ESEA.
ESMA System module has lost connection to ESEA System Extension module.
- 22 -
- 23 -
Instruction: ESMA System module has lost synchronisation signal at synchronisation input (SIN) port. 1.If another BTS is the synchronisation master, check if that it is up and alive. 2. Replace ESMA. ESEA System Extension module is not connected to port 6 of ESMA System Module. 1. Connect ESEA to port 6 of ESMA, and issue a BCF reset. Internal temperature of ESEA System Extension module has exceeded +85C/+185F. 1. Ensure that the ambient temperature of the base station is below +50C/+122F. 2. Check if fan alarm is also active. If active, refer to fan alarm instructions to resolve. 3. Replace ESEA. The cooling fan speed has reduced substantially from the commanded fan speed. 1. Check that nothing obstructs the fan(s) from rotating. 2. Clean the fan unit of dust and/or dirt. 3. Replace the fan unit. 4. Replace ESMA. ESMA System module has detected that its internal temperature has exceeded +90C/+194F. 1. Ensure that the ambient temperature of the base station is below +50C/+122F. 2. Check if any fan alarms are also active. If active, refer to fan alarm instructions to resolve. 3. Replace the ESMA. EXxx TRX Module is not connected to ESEA System Extension module. 1. Connect EXxx module to ESEA. Object affected BTS Instruction Object state Disabled Unit DDU, ECxx, Erxx
ESMA System module cooling fan speed has reduced from the set speed.
EXxx TRX module connected to wrong port. 7603 BTS FAULTY Severity Critical Fault reason Other faults.
1. Check whether either of the following alarms is active: 7606 TRX FAULTY 7607 TRX OPERATION DEGRADED and follow the instructions given for the active alarm(s). 7604 BTS OPERATION DEGRADED Severity Object affected Object state Major Fault reason Other faults. BTS Instruction 1. Check whether either of the following alarms is active: 7606 TRX FAULTY 7607 TRX OPERATION DEGRADED and follow the instructions given for the active alarm(s). Disabled
- 24 -
Instruction There is a conflict in the antenna cabling (RF source unit) between the SCF and the actual configuration. 1. Check that the antenna cabling information in the SIR (found under "Cabling information" section) refers to the correct and existing ERxx. 1. Run TRX test for all TRX objects connected to the TxA input. 2. Check the whole Tx cabling chain between EXxx, EWxx (if used) and ERxx modules. 3. Check that the RF cables are not damaged or bent too sharply. 4. Replace ERxx. 5. Replace EXxx. There is no Tx power detected at TxB input of ERxx DDU module. 1. Run TRX test for all TRX objects connected to the TxB input. 2. Check the whole Tx cabling chain between EXxx, EWxx (if used) and ERxx modules. 3. Check that the RF cables are not damaged or bent too sharply. 4. Replace ERxx. 5. Replace EXxx. At startup ERxx DDU module reported internal HW failure. 1. Replace ERxx. EXxx TRX module does not respond to polling command from ESMA System module. EXxx TRX module can be connected to ESMA either directly or via ESEA System Extension module. If the alarm is suddenly seen on many or all TRX objects on a site where ESEA System Extension module is used, it indicates a hardware failure in the ESEA. 1.Issue ESMA HW reset 2. Toggle PDU port from BTS Manager. 3. Check the bus cable chain from EXxx TRX module to ESMA/ESEA. 4. If the EXxx TRX module LED is off, replace the power cable. 5. Replace EXxx. 6. Replace ESEA if alarming TRX is connected to it. 7. Replace ESMA. ERxx DDU module is not responding to poll command from EXxx TRX module. 1. Check that the ERxx cable is correctly mated between EXxx and ERxx. 2. Replace ERxx. 3. Replace EXxx. Rx fixed frequency synthesizer in EXxx TRX module was unable to (maintain) lock to the given channel. 1. Reset TRX/Sector. 2. Replace EXxx. Rx hopping synthesizer 1 in EXxx TRX module was unable to (maintain) lock to the given channel. 1. Issue a TRX lock/unlock. 2. Issue DTRX HW reset from BTS Manager. 3. Toggle PDU port 4. Replace EXxx. Rx hopping synthesizer 2 in EXxx TRX module was unable to (maintain) lock to the given channel. 1. Issue a TRX lock/unlock. 2. Issue DTRX HW reset from BTS Manager. 3. Toggle PDU port 4. Replace EXxx.
EXxx TRX module has lost connection to ERxx DDU module EXxx TRX module Rx fixed frequency synthesizer fails to lock.
- 25 -
- 26 -
EXxx TRX module Tx power is at least 3dB less than expected at DPC.
- 27 -
Instruction The cooling fan speed of TRX module has increased substantially from the commanded fan speed. EXxx TRX module cooling 1. Check the ESMA operational voltage as an increased ESMA voltage could lead to fan speed has increased overspeeding of the fans. from the set speed. 2. Replace the fan unit. 3. Replace EXxx. The cooling fan speed has reduced substantially from the commanded fan speed. 1. Check that nothing obstructs the fan(s) from rotating. EXxx TRX module cooling fan speed has reduced from 2. Clean the fan unit of dust and/or dirt. the set speed. 3. Replace the fan unit. 4. Replace ECxx. EXxx TRX module has detected that its internal temperature has exceeded +90C/+194F. 1. Ensure that the ambient temperature of the base station is below +50C/+122F. EXxx TRX module 2. Check if any fan alarms are also active. If active, refer to fan alarm instructions to temperature high. resolve. 3. Replace the EXxx. 7616 OSCILLATOR ADJUSTMENT TEMPORARILY INTERRUPTED Severity Object affected Object state Unit Minor BCF Enabled ESMA Fault reason Instruction Oven oscillator DAC word is within 5% of the min/max limit. Alarm is activated if the DAC word is between 0-204 or 3891-4095. This alarm can be activated due to incorrect synchronisation settings in transmission network. 1. Check the Abis synchronisation that there are valid Rx clock sources available. a) If the reference clock is ok, tune the ESMA clock to the correct frequency. b) If the reference clock is not ok, check the alarm history for 8xxx alarms for the possible reason for the incorrect reference clock. Follow the instructions on 8xxx alarms. After correcting the reference clock tune ESMA clock to the correct frequency.
- 28 -
8048 Loss of incoming signal Severity Object affected Object state Module/Unit Critical TRE Enabled BOIA,VIFA,ESMA,FIU Fault reason Instruction External Q1 device does not receive signal at its interface Field not used. 1. Find out the alarming Q1 device and refer to its product documentation for more details on this alarm. 8050 Loss of incoming 2 M signal Severity Critical Fault reason Object affected TRE Object state Module/Unit
Enabled BOIA,VIFA,ESMA,FIU Instruction FIxx PIU has detected no incoming signal on E1 interface. Far End Alarm bit indication (TS0/b3) is sent in Tx direction. 1. Check that interface settings are the same at both ends of the link.
2. Check that the E1 cable is connected to right interface and cable is correctly mated to the PIU. Check the condition of cables, connectors and in case VXTB/FIPA/FIU is used, check the correct polarities of the wire pairs. 3. Replace port/LIF or VXRB/Fixx/FIU 8064 Alarm signal is received Severity Object affected Object state Module/Unit Major TRE Enabled BOIA,VIFA,ESMA,FIU Fault reason Instruction The TDM signal is cut, deteriorated or a equipment loop is set in the TDM farend equipment. Field not used. 1. Check the TDM transmission path to find where the AIS insertion occurs. 2. Check the alarms at the TDM far-end. Refer to the product documentation of the TDM far-end equipment. 3. Replace VXRB/Fixx/FIU . 8066 AIS 2 M Severity Object affected Object state Module/Unit Major TRE Enabled BOIA,VIFA,ESMA,FIU Fault reason Instruction The signal is cut, deteriorated or a equipment loop is set in the far-end equipment. 1. Check the transmission path to find where AIS insertion occurs. 2. Check the alarms at the far-end. Refer to the product documentation of the far-end equipment. Field not used. 3. In case VXTB/VXRB/FIU/FIFA PIU is used, check that the microwave link is commissioned and operational. Check that 2M cross connections are configured Refer to the FIFA product documentation for further instructions. 3. Replace VXRB/Fixx/FIU .
- 29 -
Flexi-Hopper
Severity
Critical
Location:
Alarm number
0
FIU
Severity
Critical
Alarm
Fault in power supply
Alarm
Fault in power supply
1.Check the operating temperature 2.Monitoring supply power levels 3.Check Flex-bus cable quality 4.Replace the unit 21-22 Major Loop to interface / equipment
1.Check the operating temperature 2.Monitoring supply power levels 3.Check Flex-bus cable quality 4.Replace the unit 21-23 / 25 Major Loop to interface/ equipment, Test Mode Active, Test generator on
This indication is consequence for user action 45 Critical No outgoing radio signal
This indication is consequence for user action 48 Critical Loss of incoming signal
1.Check Tx/Rx-frequencies and TX-power level settings 2. If settings are matching the planning values then try Txpower restart (off/on) 3. Replace the unit.
Monitoring Rx-level, if Rx-level is less than expected value then 1) Check antenna alignment and LOS on both ends and 2) Find a reason for extra attenuation (cross-polarization, water in waveguide, rain, etc) 3) Check the common settings of the link ends 4) Replace the unit. 64 Critical Alarm signal is received (AIS)
59
Critical
Monitoring Rx-level, if it is ok then 1) Check the alarm thresholds and 2) Check hop frequencies and Tx. power value and status from far-end 3) if Rx-level is less than expected value then 4) Check antenna alignment and LOS on both ends and 5) Find a reason for extra attenuation (cross-polarization, water in waveguide, rain, etc) 60 / 96 Critical No incoming radio signal, Excessive error rate
81 / 99 / 262
Critical
Monitoring Rx-level, if Rx-level is less than expected value then 1) check antenna alignment and LOS on both ends and 2) find a reason for extra attenuation (cross-polarization, water in waveguide, rain, etc) This indication is also consequence from bad quality of received signal furthermore Check the common settings of the link ends Replace the unit 128 Replace the unit 141 Forced control on Critical This indication is consequence for user action Major Fault in equipment
This indication is consequence from OU trouble or poor quality of received signal otherwise Flex-bus cabling has damaged, Check cable quality anyway Error rate > 1 E4 / > 1 E5 / > 1 E6 This indication is consequence from OU trouble or poor quality of received signal otherwise Flex-bus cabling has damaged, Check cable quality anyway Buffer overflow (or 113 Critical underflow) This indication is consequence from poor quality of received signal by link 100-102 Major 128 Replace the unit Major Fault in equipment
- 30 -
Flexi-Hopper
Severity
Critical
Location:
Alarm number
137
FIU
Severity
Critical
Alarm
Fault in installation of equipment
Alarm
Fault in oscillator
Upgrade the latest SW if it won't help then Replace the unit 148 / 162 Warning Equipment reset, Database full
Recalibrate the oscillator Replace the unit 141 Critical Forced control on
This indication is consequence and an other alarm might tell the specific reason for a trouble 150 Critical Fault in unit
This indication is consequence for user action 142 Critical Fault in installation of equipment
Check that Flex-bus has set in use or 1) Upgrade the latest SW if alarm information is SW incompatibility or 2) Replace module or fill in missing identifications when alarm information is one of the HW module 144 Replace the unit Equipment reset, Database full This indication is consequence and an other alarm might tell the specific reason for a trouble 165 Real time lost fault Major This indication is consequence and an other alarm might tell the specific reason for a trouble 148 / 162 Warning 179 Major Far-end alarm Critical Operating error
165 Real time lost fault Major This indication is consequence and an other alarm might tell the specific reason for a trouble 179 Trouble exists on far-end 184 Warning Real time updated Major Far-end alarm
This alarm is consequence from an auto-function 185 Warning Connection or settings have changed
This indication is consequence for user action 186 Minor Configuration error
Check that Tx power value and status are correct ones Trouble exists on far-end 184 Warning Real time updated
This alarm is consequence from an auto-function Connection or settings have 185 Warning changed This indication is consequence for user action 186 Minor Configuration error
Fill in missing identifications or Replace the unit 15 min / 24 h G826 ES / SES Alarm number severity / BBE threshold crossed 256-261 Each of these indications are consequence from OU trouble or poor quality of received signal otherwise Flex-bus cabling has damaged, Check cable quality anyway 263 Statistics reset Warning This indication is consequence for user action
- 31 -
ZD
ZE
ZE
- 32 -
FLM Engineer Handbook Trouble Shooting Tips for Ceragon SDH Radio
Sr. No.
1
Alarms
Loss of Signal on Fiber Tx Level out of Range Loss of frame on Radio Raised
Alarm Severity
Service affecting alarm
Corrective Action
Check Fiber cable connectivity Clean Fiber cable Replace fiber cable Replace IDM Replace ODU Switch over to other ODU Check Rx Level if its ok then Check for interference, If no interference Check RF loop back to identify the problem Check Rx Level if its OK then Verify inband settings Clean IDC ,If problem still persists Replace IDC Replace IDM,If problem still persists Clean IDC ,If problem still persists Check If cable connectivity Replace IDC ,If problem still persists Replace ODU Check RF loop back both at Near end and Far end to identify the problem Check for Link Misalignment Check frequency setting ,If frequency in both the drawers are different, make it correct and then check the connectorisation of frequency changed ODU Check Wayside cable Check Rx Level if its OK then Check Interference, If no interference found then Switch over the Far end transmitting ODU ,If it solves the problem then check the ODU and connectorisation of Far end ODU otherwise check the Near end ODU connectorisation and IF cable Check Fiber cable connectivity Clean Fiber cable Replace fiber cable Replace IDM Disable J0 operation Check for Link Fading Use copy configuration command to copy the configuration from Drawer to IDC
Link will start toggling Normally this alarm comes when there is interference in the link/Link Misaligned/Water entered into IF cable/Improper connectorisation
Signal Degrade on Fiber Raised TIM on Fiber Raised RFU Rx level Path out of Range Raised Configuration Mismatch Raised
Results Link Fluctuation, Service affecting alarm Non Service affecting alarm Service affecting alarm
10 11
12
- 33 -
FLM Engineer Handbook Trouble Shooting Tips for NEC SDH Radios
Alarm Description Alarm Items Items to Check Input STM-1 signal is lost (From MUX) 1 MAIN INTFC LOS (MUX) a) b) Equipment where Alarm is from Possible Cause of Failure or Action to Take IDU IDU No 1/2
Check data input cable and connector failure Data input cable and connector from MUX (Short-circuit) failure Check MUX MUX IDU IDU No 1/2
Frame synchronization of input STM-1 signal (From MUX) is lost 2 MAIN INTFC LOF (MUX) a) b)
Check data input cable and connector failure Data input cable and connector from MUX (Short-circuit) failure Check MUX
-3 -5
IDU
IDU No 1 /2
a) Check data input cable and connector failure Data input cable and connector from MUX (Short circuit/Loose connect) failure b) Check MUX BER is worse than preset value (10 to 10 , selectable)
-5 -9
4 SD (MUX)
a) Check data input cable and connector failure Data input cable and connector from MUX (Short circuit/Loose connect) failure b) Check MUX MUX IDU IDU No 1 /2
Input STM-1 signal is lost (From Radio) a) Check IDU and INTFC card Frame synchronization of input STM-1 signal (From Radio) is lost
IDU/INTFC
BER is worse than preset value (10 to 10 , selectable) 7 E-BER (DMR) a) Check RX LEVEL, if lower>> b) Check opposite Station c) Check IDU and INTFC card BER is worse than preset value (10 to 10 , selectable) 8 SD (DMR) a) b) Check RX LEVEL, if lower>> Check opposite Station
-5 -9
IDU
IDU No 1 /2
Antenna system or natural fading Opposite station IDU/INTFC IDU (Replace IDU)
IDU No 1 /2
- 34 -
Link of LAN (10/100 BASE-T INTFC) and associated equipment is not established a) 10 LINK b) c)
Check data input cable and connector failure Data input cable and connector from/to DTE failure Check DTE Check LAN card inside IDU DTE LAN INTFC IDU) (Replace
11 SUB INTFC
WS INTFC,WS/ALM INTFC, ALM INTFC or LAN WS, WS/ALM, ALM INTFC or CARD(DSC) module failure LAN Card a) Check each Sub Module Sub INTFC Sub Intfc) IDU IDU No 1/ 2 (Replace
12 MD CPU ALM
Modulator failure 13 MOD ALM a) b) Check Atmosphere Temperature If continues MOD alarm on,
Demodulator failure and input IF signal is lost a) 14 DEM ALM b) c) d) Check Frame ID using LCT or PNMT/S Check Atmosphere Temperature If continues MOD alarm on,
-4 -6
Antenna system or natural fading IDU Setting Improve environment condition of IDU IDU(Replace IDU) IDU IDU No 1/2
BER is worse than preset value (10 to 10 , selectable) a) 15 High BER ALM b) c) Check opposite Station Check IDU
-6 -12
Antenna system or natural fading Opposite station IDU(Replace IDU) IDU Antenna system or natural fading Opposite station
BER is worse than preset value (10 to 10 , selectable) 16 Low BER ALM a) b) Check RX LEVEL, if lower>> Check opposite Station
- 35 -
Transmit RF power increases/decreases approx ODU ODU No 1/2 3dB from normal 19 TX PWR ALM a) b) Check Atmosphere Temperature If continues TX PWR ALM alarm on, Improve environment condition of ODU Replace ODU ODU ODU No 1/2 IF cable and connector failure IF cable loss ODU ODU No 1 /2
TX IF input signal from the IDU is lost 20 TX INPUT ALM a) b) Check IF Cable and Connector Check IF Cable Loss
21 RX LEVEL ALM
Receiver input level decreases below squelch level as shown below 32QAM : -81dBm 128QAM : -72dBm a) b) Check RX LEVEL, if lower>> Check opposite site
Antenna system or natural fading Opposite site ODU ODU No 1/2 Improve ODU temperature Replace ODU IF CBL Cable No 1 /2
22 APC ALM
23 CABLE ALM
Communication between the ODU and IDU is lost a) Check IF cable and connector
24 MAINT
The equipment is in maintenance mode. In this mode, the following control can be performed. ATPC manual control Loopback TX mute ALS manual restart CW
MAINT
- 36 -
LOGIN
3: - How to Login to the Node? To Login to the node: Suppose the IP address of your node is 192.168.1.254 Set the IP address of your Laptop to IP : - 192.168.1.100 Subnet mask : - 255.255.255.0 Default Gateway: - 192.168.1.254 this is the Ethernet IP address of node. Once the IP is set, open the Internet Explorer and in the address bar type the following line http://192.168.1.254:20080 and Press enter Username: - tejas Password: - j72e#05t 4: - How to Login to Remote Node? To Login to remote node check the following setting in the node: Set the gateway in the laptop, the gateway should be the Ethernet IP of the Local Node. Now in Local node, go to Fault Management Diagnosis OSPF Monitoring Page Neighbor. This page should show the Router ID of the remote node and the state should be FULL. In the Address bar of Internet explorer Page, type the Router ID of the remote node Example: - if the remote node Router ID is 192.168.200.2 then type the following line http://192.168.200.2:20080 Username: - tejas Password: - j72e#05t 5: - How to create a cross connect? Click on Configuration (main menu) -----> Click on Cross connect --->Click on Add Cross connect Cross connect capacity =VC12 Circuit Identifier =User dependent Source port =STM1-3-1 Source time slot (K, L, M) =select from the menu (TUG Structure) Destination port =E1-4-1 (If trib card is in 4th slot and we are using 1st port) Destination time slot = --Enable Source protection and select the TUG Structure. Submit the changes and accept the modifications.
- 37 -
Alarm Clearance
PDH Port: Type Alarm Color Alarm Name Alarm Description Alarm Indication Major Orange Loss Of Signal The TX from the other node is not getting received on the PDH port (a) On Alarm Window, it will show major alarm with Particular PDH port as Object. (b) On the alarm display, Orange Major LED should glow. (a) Check the cable connectivity from the other node (b) Check the Cable connecting the E1 card and the DDF (c) Check the patch panels, if there is any problem, replace the DDF if possible.
Alarm Clearance
LOF: Type Alarm Color Alarm Name Alarm Description Alarm Indication Major Orange Loss Of Frame LOF will come due to hardware failure or Signal Degrade condition on STM port. (a) On Alarm Window, it will show major alarm with Particular SDH port as Object. (b) On the alarm display, Orange Major LED should glow. (a) Put Self Loop to the SDH Port and Check for Port failure (b) Check Optical Power and Performance for Particular SDH port (c) Check the Patch Cord
Alarm Clearance
- 38 -
For TU Type Alarm Color Alarm Name Alarm Description Alarm Indication Alarm Clearance Major Orange TU-AIS (Tributary Unit Alarm Indication Signal) This Alarm is raised when LOS, MS-AIS, AU_LOP, TU, TIM, Signal Label exists on an upstream neighboring Node, having Cross connecting on the same level. (a) On the alarm view, TU-AIS will appear on that particular Object (b) On the Alarm display, an Orange Major will appear. (a) If this alarm is present, that means there is some alarm in the neighboring node, which has be cleared. (b) Check the Optical port or TU12 Loop back with Loop back
RDI Line RDI / MS-RDI Type Alarm Color Alarm Name Alarm Description Alarm Indication Alarm Clearance AU- RDI Type Alarm Color Alarm Name Alarm Description Alarm Indication Alarm Clearance Major Orange Remote Defect Indication AU This Alarm indicates that the Remote system has LOF/AIS/LOP on the AU of the particular Port. (a) On the alarm view, RDI will appear on that particular Object (b) On the Alarm display, an Orange-Major will appear. (a) Check the Other end node for alarms on that particular AU (b) Check the Optical port Loop back Critical RED Remote Defect Indication Line This Alarm indicates that the Remote system has LOS/LOF/Exec Error rate on the STM Port. (a) On the alarm view, RDI-Line will appear on that particular Object (b) On the Alarm display, a RED Critical will appear. (a) Check the Other end node for Loss on STM Port. (b) Check the Optical port Loop back
- 39 -
(7) PLM Type Alarm Color Alarm Name Alarm Description Alarm Indication Alarm Clearance Major Orange Path Label Mismatch The received and Transmitted Signal label does not matches (a) On the alarm view, PLM on that particular Object (b) On the Alarm display, a orange Major (a) Set the Transmit Signal label to desired value on the node 2 (b) Contact Tejas TAC support.
(8) Signal Label Uneq Type Alarm Color Alarm Name Alarm Description Alarm Indication Alarm Clearance Major Orange Received Signal Label is Unequipped Path label received is Unequipped (a) On the alarm view, Uneq on the particular Object would be observed. (b) On the Alarm display, a orange Major (a) Set the Transmit Signal label to desired value on the node 2 (b) Contact Tejas TAC support.
- 40 -
8: - How to make Diag Cable? DIAG port follows RS232 standard and has RJ45 connector. It can take null-modem console cable provide that RJ45 (M) connector on one side.
Pin RJ45 1 2 3 6 5 4 7 8 9
Color Code White/Orange Orange White/Green Green White/Blue Blue White/Brown Brown
Pin DSub 1 3 2 4 5 6 7 8
9: -- How to see neighbors? Click on Maintainance(Main Menu) ----> Diagnostics -----> OSPF Monitor- Neighbors (If Neighbors RI is showing full state is FULL and remote login is not possible, check the LAPTOP settings.)
- 41 -
List area
The list area is where the notifications appear. Each line or record represents one alarm, TCA, or other event. The column headings are either textual or represented by an icon. The first column displays a line number for each record. You select a record by clicking it. You can also display shortcut menus by right-clicking a record. Menu options that are not available are disabled.
Status bar
The status bar displays the total number of records in a list and the number of records that match a selected filter criterion.
- 42 -
- 43 -
4. Encapsulation Mismatch
Severity: Major The Encapsulation Mismatch alarm indicates that the GFP/HDLC encapsulation hardware revision does not support the configured Encapsulation Type.
Verify that the Encapsulation Type attribute is configured correctly for the GEoS sink object. This attribute is set in the object Info window.
Seek out the source of the problem on the far-end GFP equipment and proceed accordingly.
The Header Mismatch alarm indicates a mismatch between the expected and received extension headers in the GFP layer. This alarm typically indicates an interoperability problem with other vendor equipment.
Seek out the source of the problem on the far-end GFP equipment and proceed accordingly.
The Link Down alarm indicates an Ethernet link that is down or loss of carrier (as defined in IEEE 802.3).
Check the GFP layer for a loss of signal or other high-level alarms and clear accordingly.
- 44 -
11.Partner Offline
Severity: Minor The Partner Offline alarm indicates that the remote partner is offline or out of service. To clear a Partner Offline alarm: 1. Verify that the customer configuration is set up properly. 2. Check the fibers and cables on the customer device. 3. If the configuration is correct on both sides of the link, check the EIS/EISM card and the customer device for defects. Replace components, such as the EIS/EISM card or the customer device, if required.
Seek out the source of the problem on the respective equipment and proceed accordingly.
The Port Over Quota alarm indicates that there is a port with a quota exceeding an event on at least one of the S-VIDs. To clear a Port Over Quota alarm: Seek out the source of the problem on the respective equipment and proceed accordingly.
- 45 -
Follow the relevant alarm clearing procedure for the specific alarm detected on the VC members.
Seek out the source of the problem on the respective equipment and proceed accordingly.
- 46 -
Follow the relevant alarm clearing procedure for the specific alarm detected on the VC member.
Follow the relevant alarm clearing procedure for the specific alarm detected
- 47 -
1. ULTRA BTS LOGIN CABLE MATERIAL REQUIRED: D9 PIN FEMALE CONNECTOR, D9 PIN FEMALE CONNECTOR, 4 METER 2 PAIR PCM CABLE CONFIGURATION D9 MALE 2 3 5 2. METRO BTS and FIU 19 LOGIN CABLE MATERIAL REQUIRED: BQ MALE CONNECTOR, D9 PIN FEMALE CONNECTOR, 4 METER 2 PAIR PCM CABLE (60 Mtr cable will be required for accessing Tower Top BTS) CONFIGURATION BQ MALE 3 1 4 LMP OUT LMP IN GROUND D9 FEMALE 2 3 5 D9 FEMALE 3 2 5
3. FLEXI BTS, TEJAS MUX,CERAGON IDU,RADWIN LOGIN CABLE MATERIAL REQUIRED: 2 RJ 45 CONNECTOR,4 METER 4 PAIR PCM CABLE/CAT-5 CABLE CONFIGURATION RJ 45 (1) 1 2 3 4 5 6 7 8 RJ 45 (2) 3 6 1 4 5 2 7 8
- 48 -
- 49 -
9. The pin diagram of the Slip cable used to login ECI XDMs is as follows 9-pin female 1-4-6 7-8 5 2 3 9-pin male straight 1-4-6 7-8 5 3 2 Remarks Short Short Connect Connect Connect
- 50 -
Bharti
Alarm Description
ASCOM URGENT ALARM ASCOM NONURGENT ALARM MAINS FAIL AC1 FAIL LOW BATTERY LOAD ON DG DG FAIL TO START SMOKE AND FIRE ALARMS DG FAIL TO STOP LOW FUEL TMA FAULT RADWIN FAULT ASCOM URGENT ALARM ASCOM NONURGENT ALARM MAINS FAIL INTRUDER ALARM LOW BATTERY LOAD ON DG DG FAIL TO START SMOKE AND FIRE ALARMS DG FAIL TO STOP LOW FUEL TMA FAULT RADWIN FAULT ASCOM URGENT ALARM ASCOM NONURGENT ALARM MAINS FAIL INTRUDER ALARM LOW BATTERY LOAD ON DG DG FAIL TO START SMOKE AND FIRE ALARMS DG FAIL TO STOP LOW FUEL TMA FAULT RADWIN FAULT
Uninor
Severity
CRITICAL MINOR CRITICAL MINOR MAJOR CRITICAL MAJOR CRITICAL CRITICAL CRITICAL CRITICAL CRITICAL CRITICAL MINOR CRITICAL MINOR MAJOR CRITICAL MAJOR CRITICAL CRITICAL CRITICAL CRITICAL CRITICAL CRITICAL MINOR CRITICAL MINOR MAJOR CRITICAL MAJOR CRITICAL CRITICAL CRITICAL CRITICAL CRITICAL
Alarm Description
MAINS FAILURE LOAD ON DG DG FAILS TO START BATTERY DISCHARGE RECTIFIER FAIL DOOR OPEN FIRE AND SMOKE ROOM TEMP. HIGH
FLEXI
ULTRA
METRO
- 51 -
Operator
Vodafone,Bharti,Maxis,Idea, Uninor,Tata,Videocon Maxis Vodafone Bharti Tata Uninor Idea Videocon Vodafone Bharti Tata Maxis Uninor Idea Videocon Vodafone,Bharti,Maxis,Idea, Uninor,Tata,Videocon >= 15 sites. >= 15 sites. >= 25 sites. >= 10 sites. >= 10 sites.
Outage Classification
BSC Isolation
CRITICAL
MAJOR
5 < Sites < 15 5 < Sites < 25 5 < Sites < 10 5 < Sites < 15 5 < Sites < 9
MINOR
< 5 Sites
- 52 -
1.2
1.3
Sub Process 3 RF AT
NPO Team will perform RF AT on sites with 24 hrs KPI availability. Theyll first perform the parameter level check to make sure that the integration of the site took place with Planned Parameters. The Details of the planned setup could be downloaded from the Planning database (TND/RND & Site Integration Package) from the Site Plus Tool. In case there is some deviation, then the NPO Team will raise a CR as per Change Management Process. If everything is as per Planning, theyll plan for physical AT and Drive test of that site. During the course of Physical Visit, NPO team will perform SCFT i.e. MOC, MTC, emergency calls, Incoming and Outgoing SMSs. If SCFT is Ok then proceed else prepare the punch point and pass it on to NI team for rectification via FLM Manager. After successful SCFT, NPO team will perform Physical RF Audit of the site i.e. Antenna Setup, height, orientation, beam width etc. If Physical RF Audit is Ok then proceed else prepare the punch point and pass it on to NI team for rectification via FLM Manager. After successful Physical RF Audit, NPO team will perform Drive Test and desired Optimization. During Optimization they may seek support of Performance Management Process. It may lead to multiple attempts and to obtain better output and more efficient delivery we may seek joint visit of TI Partner from NI Team. After Successful completion of RF AT, NPO Team will submit RF AT document Annexure II to FLM Manager, which will then be incorporated into Site folder for Customer submission.
1.4
- 53 -
1.6
- 54 -
WO: TSK-00000275034 KEY: 114E ACC:Bharti Maharastra 1 PRI: P4 SITEID: NAGAON_ODF ET: 18/04/10 22:01 SLA: 18/04/10 23:01 TSK-TTL: BSC18BST-NAGAON_ODF BTS O&M LINK FAILURE AddlInfo: Unknown service NE TITL: NAGAON_ODF/BSC18BST:NAGAON_ODF
WO Work Order TSK-00000275034 Work order Number WO Key 114E (This is followed as reference till the time WO is closed) Priority P4 Site Name - NAGAON_ODF
- 55 -
FM:VehicleID:UserNSNID:UsageDate(dd/mm/yyyy):KMs:ActivityCode:
Activity codes are given below,
ACTIVITY CODE
CC PM TA PS
DESCRIPTION
CUSTOMER COMPLAINT PREVENTIVE & CORRECTIVE MAINTENANCE-O&M TRX ADDITION/DELETION PROJECT SUPPORT
FM: MHG_BH_VAS_71:61285058:18/04/2010:80:PM:
Vehicle ID
NSN ID
Date
KM Run
- 56 -
- 57 -
Consider that accidents at the workplace can be caused by, Inadequate planning, with hazard misses. Incorrect tool selection. Incorrect grounding Touching a live wire and electrical ground Touching a live wire and another wire at a different voltage Lack of proper plant/equipment maintenance. Failure of personnel to carry out safe working procedures. Absence of adequately trained personnel. Ensure that all required equipments are properly earthed. Routine check up for earth resistance values should be done regularly. Always use anti-static wrist belt while working on telecom equipments. Do not use metal ladders. Use ladders made of wood or fibreglass with rubber footings. Be aware of overhead power lines Never overload a circuit. Use MCBs, EB meters of proper ratings as per standards.
- 58 -
Circle Andhra Pradesh Assam Bihar & Jharkhand Chennai Delhi Gujarat Haryana Himachal Pradesh Jammu & Kashmir Karnataka Kerala Kolkata Madhya Pradesh & Chhattisgarh Maharashtra & Goa Mumbai North East Orissa Punjab Rajasthan Rest of Tamil Nadu Uttar Pradesh-E Uttar Pradesh-W & Uttaranchal Rest of West Bengal
Background Color of Sticker Remark Red Pink Dark Green Dark Blue Yellow Idea Cellular Light Blue Light Green Suggested
- 59 -
As an Exception, get the Spare card from Project Team and inform circle Head of inadequate
- 61 -
- 62 -
SWH to Site
Start
Caller need to specify part code/ serial number and agree on delivery address. Issue escalated to NSN HWS team/ Circle Manager Initiate emergency delivery Check stock at nearest site Yes
No
No
Arrange delivery to delivery point from locally held stock. Also arrange pick up of faulty part
End
Shipment advice contains: Item code shipped Quantity of that item shipped Origin the SWH location Shipment tracking number Serial no. and item code of faulty unit against which replacement is done
- 63 -
No
No
Wait no more than 2 days before arranging shipment
Yes
Yes
End
- 64 -
Battery Charging Illuminates when the battery is being charged. The indicator automatically shuts off when the battery is fully charged. External Power Illuminates when the Site Master is being powered by the external charging unit. Serial Interface RS232 DB9 interface to a COM port on a personal computer (for use with the Anritsu Handheld Software Tools program) or to a supported printer. RF Out/Reflection 50_ RF output, 50 impedance, for reflection measurements. Maximum input is +23 dBm at _50 Vdc.
- 65 -
- 66 -
Power on Procedure
Step 1. Press the ON/OFF front panel key Step 2. The Site Master will display the model number, the firmware revision, the internal temperature and voltage, and then perform a five second self test. At completion of the self-test, the screen displays a prompt to press ENTER to continue. If enter is not pressed, the Site Master will continue after a five second timeout. Step 3. Press ENTER to continue. The Site Master is now ready for operation.
- 67 -
Step 1. Press the FREQ/DIST key. Step 2. Press the Signal Standard soft key. Step 3.Use the Up/Down arrow key to highlight the desired standard, then press the ENTER key to select. To manually select the frequency range for an OSL or FlexCal calibration: Step 1. Press the FREQ/DIST key. Step 2. Press the F1 soft key. Step 3. Enter the desired start frequency using the key pad or the Up/Down arrow key. Step 4. Press ENTER to set F1 to the desired frequency. Step 5. Press the F2 soft key. Step 6. Enter the desired stop frequency using the keypad or the Up/Down arrow key. Step 7. Press ENTER to set F2 to the desired frequency. Step 8. Check that the start and stop frequencies displayed match the desired measurement range.
Calibration
Step 1. Select OSL Cal by pressing the SYS key, followed by the Application Options soft key. The currently selected calibration method is indicated at the bottom of the status window. Use the CAL Mode soft key to select the OSL calibration method. Step 2. Select the appropriate frequency range Step 3. Press the START CAL key. The message Connect OPEN or InstaCal to RF Out port will appear in a message box, with the calibration type in the message box title bar. Step 4. Connect the InstaCal module to the RF Out port
- 68 -
Amplitude Scale
The following procedure sets the top and bottom scale display. Step 1. Press the AMPLITUDE key to call up the Scale Menu. Step 2. Press the Top soft key and use the keypad or Up/Down arrow key to edit the top scale value. Press ENTER to set. Step 3. Press the Bottom soft key and use the keypad or Up/Down arrow key to edit the bottom scale value. Press ENTER to set.
- 69 -
Figure 1 User Key Identification 1. Soft keys Activates the function described directly to the right of the key. 2. Hard Keys Mode Activtes the mode menu. Use this to select Measure Match, Fault Location, Measure Power, or Utilities mode. Config Activates the configuration menu for the current mode. Use this to set variable parameters (e.g. frequency band, distance, and units). Calibrate Activates the calibration menu. Marker Activates the marker menu. Use this to turn markers on or off and to move the active marker. 3. Numeric Keys Enters numeric data into the selected item, or as defined by the function description. 4. Escape Key During: Menu Use Backs up one menu level. Data Entry Exits data entry without changing the value.
- 70 -
charged
Graphic display of the measurement. Indicates the position and value of a trace point. Identifies the trace point displayed in the marker value. Indicates the calibration status.
- 71 -
Step Action 1 Press the Calibrate key 2 Connect the Cal Combo Open connector to the unit antenna port 3 Press the Open softkey then wait for the unit to beep and display Done 4 Connect the Cal Combo Short connector to the unit antenna port 5 Press the Short softkey then wait for the unit to beep and display Done 6 Connect the Cal Combo Load connector to the unit antenna port 7 Press the Load softkey then wait for the unit to beep and display Done 8 Remove the Cal Combo from the unit The Site Master is now ready for operation. When calibrated, the Site Analyzers main screen will display Calibration: FULL. When un-calibrated, the Site Analyzers main screen will display Calibration: OFF. Select the Measure Match Mode
- 72 -
Step Action 1 Turn On the Site Analyzer. Press ON/ OFF key for second. 2 Press the MODE key 3 Press the Measure Match key Setting the Measurement Frequency You must be in the Measure Match mode to set a frequency. Note: Changing the frequency settings will automatically turn calibration off. Always set the frequency before calibrating the unit.
Step 1 2 3 4 5
Action Press the Config key Press the Freq softkey Use the left or right scroll keys to select Start, Stop, Center or Span Use the keypad keys to enter a value and press Enter when finished. Press the Esc key to exit the configuration screen. 6
Select the Measurement Units You can select units before or after making a measurement. When making a match measurement, you can select one of three units for the Y (vertical) scale, VSWR (ratio) Rtn Loss (dB) Cbl Loss (dB) 1. Make sure that the instrument is turned on and in the Measure Match mode. 2. Select Frequency (refer to Setting the Measurement Frequency) 3. Make sure that the instrument is calibrated (refer to Calibration)
- 73 -
Step 1 2 3 4 5 6 7 8
Action Press the Config key Press the Scale softkey Press the left or right scroll keys to select units Press the up or down scroll keys to open the units list menu. Press the up or down scroll keys to select the desired units. Press the Enter key to accept the selection. Press the Esc key to exit the configure screen. Remove the Cal Combo from the unit
Step 1 2 3 4 5 6
Action Press the Config key Press the Scale softkey To enter a manual value, skip this step. Use the left or right scroll keys to select Auto Scale then press Enter If you selected Auto Scale, skip this step. Use the left or right scroll keys to select Min then enter your value or enter 60 and press Enter If you selected Auto Scale, skip this step. Use the left or right scroll keys to select Max then enter your value or enter 0 and press Enter Press the Esc key to exit the configure screen.
- 74 -
Step 1 2 3 4
5 6 7 8
Action Press the Marker key to enter marker setup Press the Mark softkey to select a marker (1-6) Press the Active / Off softkey to turn ON the selected marker (active) or turn OFF the selected marker (off) Press the Type softkey to select triangle marker (4 in figure) or line marker (1 in figure) Repeat Step 2 through Step 4 to select and activate up to six markers and set the mark style Press the right or left arrow keys to move the marker right or left, or enter a frequency value on the keypad and press Enter Press the up arrow keys to move the marker to the highest point on the trace Press the down arrow key to move the marker to the lowest point on the trace Press Esc to return to the test screen
Cable Loss Measurement To measure cable loss, make sure that the cable being tested is unterminated
(not connected to anything at the far end).
Step 1. Check the power of cable to be. Make sure that the cable does not have power greater than +22 dBm. Step 2. Make sure that you have the correct adaptors and connectors and a Bird Calibration Combination (cal
combo). Also make sure that you know the frequency band of the system Step 3. Turn on the Site Analyzer and enter the Measure Match mode Step 4. Set up the Site Analyzer to measure cable loss. Step 5. Select the Freq softkey and set the frequency start and stop to a range that is well beyond the normal range of the antenna Step 6. Connect a phase stable cable to the Site Analyzer antenna test port and connect a Cal Combo to the other end of the cable.
- 75 -
Pre-monsoon Checklist
Pre Monsoon Checklist
- 76 -
- 77 -
- 78 -
CTL to ensure availability of Network Diagram (Mapinfo Tabs) and Site wise PCM Plan (Ater, Abis and 3rd Party Lease Line) on monthly basis from Network Transmission Planning Team. Also has to check if the details are available on site plus tool.
- 79 -