You are on page 1of 4

Cable Schedule

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029 Engineer: ARNEL CORPUZ Rev Date :
Document No: CCB-DBP-001 Created On: 08/10/2008 Modified By: Rev No:

Id No: Connected From: Cores CSA Cable Type Length CPC (mm2 ): Volt Drop Protective Device
Name: Connected To: (mm2 ) (m) Separate % Ir(A) In(A) Type RCD
Integral

(E) Cbl_SM-1 MDB-CCB-DBP/1/L1,L2,L3 1 x 4 x 1c 6 Single-core, 90°C thermosetting, 10 1.5 1.10 40 40 MCCB N/A
DB-P1 insulated, non-arm Cu Table 4E1 0

(G) Cbl_SM-2 MDB-CCB-DBP/2/L1,L2,L3 1 x 4 x 1c 25 Single-core, 90°C thermosetting, 10 2.5 0.77 80 80 MCCB N/A
DB-P2 insulated, non-arm Cu Table 4E1 0

CKT P101 DB-P1/1/L1 1 x 2 x 1c 2.5 Single-core, 90°C thermosetting, 24 1 1.44 10 10 MCB N/A
P101 insulated, non-arm Cu Table 4E1 0

CKT P102 DB-P1/2/L1 1 x 2 x 1c 2.5 Single-core, 90°C thermosetting, 73 1.5 2.85 10 10 MCB N/A
P102 insulated, non-arm Cu Table 4E1 0

CKT P103 DB-P1/1/L2 2 x 2 x 1c 4 Single-core, 90°C thermosetting, 37 1 1.35 32 32 MCB N/A


P103 insulated, non-arm Cu Table 4E1 0

CKT P104 DB-P1/2/L2 1 x 2 x 1c 2.5 Single-core, 90°C thermosetting, 57 1 1.94 10 10 MCB N/A
P104 insulated, non-arm Cu Table 4E1 0

CKT P106 DB-P1/2/L3 1 x 2 x 1c 2.5 Single-core, 90°C thermosetting, 40 1 1.53 10 10 MCB N/A
P106 insulated, non-arm Cu Table 4E1 0

CKT P107 DB-P1/3/L1 2 x 2 x 1c 4 Single-core, 90°C thermosetting, 29 1 1.14 32 32 MCB N/A


P107 insulated, non-arm Cu Table 4E1 0

CKT P108 DB-P1/4/L1 1 x 2 x 1c 4 Single-core, 90°C thermosetting, 24 1 2.31 20 20 MCB N/A


P108 insulated, non-arm Cu Table 4E1 0

CKT P109 DB-P1/3/L2 1 x 2 x 1c 4 Single-core, 90°C thermosetting, 13 1 1.72 20 20 MCB N/A


P109 insulated, non-arm Cu Table 4E1 0

CKT P110 DB-P1/4/L2 1 x 2 x 1c 4 Single-core, 90°C thermosetting, 19 1 2.03 20 20 MCB N/A


P110 insulated, non-arm Cu Table 4E1 0

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 1 of 4 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Schedule

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029 Engineer: ARNEL CORPUZ Rev Date :
Document No: CCB-DBP-001 Created On: 08/10/2008 Modified By: Rev No:

Id No: Connected From: Cores CSA Cable Type Length CPC (mm2 ): Volt Drop Protective Device
Name: Connected To: (mm2 ) (m) Separate % Ir(A) In(A) Type RCD
Integral

CKT P111 DB-P1/3/L3 1 x 2 x 1c 2.5 Single-core, 90°C thermosetting, 38 1 1.75 10 10 MCB N/A
P111 insulated, non-arm Cu Table 4E1 0

CKT P112 DB-P1/4/L3 1 x 2 x 1c 4 Single-core, 90°C thermosetting, 13 1 1.78 20 20 MCB N/A


P112 insulated, non-arm Cu Table 4E1 0

CKT P113 DB-P1/5/L1 1 x 2 x 1c 4 Single-core, 90°C thermosetting, 19 1 2.05 20 20 MCB N/A


P113 insulated, non-arm Cu Table 4E1 0

CKT P117 DB-P1/5/L3 1 x 2 x 1c 4 Single-core, 90°C thermosetting, 21 1 2.19 20 20 MCB N/A


P117 insulated, non-arm Cu Table 4E1 0

CKT P201 DB-P2/1/L1 2 x 2 x 1c 4 Single-core, 90°C thermosetting, 65 1.5 1.14 32 32 MCB N/A
P201 insulated, non-arm Cu Table 4E1 0

CKT P202 DB-P2/2/L1 2 x 2 x 1c 4 Single-core, 90°C thermosetting, 56 1.5 1.23 32 32 MCB N/A
P202 insulated, non-arm Cu Table 4E1 0

CKT P203 DB-P2/1/L2 2 x 2 x 1c 4 Single-core, 90°C thermosetting, 57 1.5 1.04 32 32 MCB N/A
P203 insulated, non-arm Cu Table 4E1 0

CKT P204 DB-P2/2/L2 2 x 2 x 1c 4 Single-core, 90°C thermosetting, 33 1 1.00 32 32 MCB N/A


P204 insulated, non-arm Cu Table 4E1 0

CKT P205 DB-P2/1/L3 2 x 2 x 1c 4 Single-core, 90°C thermosetting, 51 1 1.06 32 32 MCB N/A


P205 insulated, non-arm Cu Table 4E1 0

CKT P206 DB-P2/2/L3 2 x 2 x 1c 4 Single-core, 90°C thermosetting, 72 1.5 1.17 32 32 MCB N/A
P206 insulated, non-arm Cu Table 4E1 0

CKT P207 DB-P2/3/L1 1 x 2 x 1c 2.5 Single-core, 90°C thermosetting, 116 4 4.70 10 10 MCB N/A
P207 insulated, non-arm Cu Table 4E1 0

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 2 of 4 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Schedule

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029 Engineer: ARNEL CORPUZ Rev Date :
Document No: CCB-DBP-001 Created On: 08/10/2008 Modified By: Rev No:

Id No: Connected From: Cores CSA Cable Type Length CPC (mm2 ): Volt Drop Protective Device
Name: Connected To: (mm2 ) (m) Separate % Ir(A) In(A) Type RCD
Integral

CKT P208 DB-P2/4/L1 1 x 2 x 1c 2.5 Single-core, 90°C thermosetting, 72 4 4.38 16 16 MCB N/A
P208 insulated, non-arm Cu Table 4E1 0

CKT P209 DB-P2/3/L2 1 x 2 x 1c 2.5 Single-core, 90°C thermosetting, 68 1.5 2.14 10 10 MCB N/A
P209 insulated, non-arm Cu Table 4E1 0

CKT P210 DB-P2/4/L2 1 x 2 x 1c 2.5 Single-core, 90°C thermosetting, 33 1 2.54 16 16 MCB N/A
P210 insulated, non-arm Cu Table 4E1 0

CKT P211 DB-P2/3/L3 1 x 2 x 1c 2.5 Single-core, 90°C thermosetting, 76 1.5 2.53 10 10 MCB N/A
P211 insulated, non-arm Cu Table 4E1 0

CKT P212 DB-P2/4/L3 1 x 2 x 1c 4 Single-core, 90°C thermosetting, 27 1 2.18 20 20 MCB N/A


P212 insulated, non-arm Cu Table 4E1 0

CKT P213 DB-P2/5/L1 1 x 2 x 1c 4 Single-core, 90°C thermosetting, 41 2.5 2.80 20 20 MCB N/A
P213 insulated, non-arm Cu Table 4E1 0

CKT P214 DB-P2/6/L1 1 x 2 x 1c 4 Single-core, 90°C thermosetting, 32 1.5 2.33 20 20 MCB N/A
P214 insulated, non-arm Cu Table 4E1 0

CKT P215 DB-P2/5/L2 1 x 2 x 1c 4 Single-core, 90°C thermosetting, 43 2.5 2.97 20 20 MCB N/A
P215 insulated, non-arm Cu Table 4E1 0

CKT P216 DB-P2/6/L2 1 x 2 x 1c 2.5 Single-core, 90°C thermosetting, 50 2.5 2.72 16 16 MCB N/A
P216 insulated, non-arm Cu Table 4E1 0

CKT P217 DB-P2/5/L3 1 x 2 x 1c 4 Single-core, 90°C thermosetting, 51 2.5 3.44 20 20 MCB N/A
P217 insulated, non-arm Cu Table 4E1 0

CKT P218 DB-P2/6/L3 1 x 2 x 1c 4 Single-core, 90°C thermosetting, 65 4 4.17 20 20 MCB N/A


P218 insulated, non-arm Cu Table 4E1 0

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 3 of 4 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008
Cable Schedule

Project Reference: CCB - ALAOJI 504MW PP Job Number: RK-117-E-2020-2029 Engineer: ARNEL CORPUZ Rev Date :
Document No: CCB-DBP-001 Created On: 08/10/2008 Modified By: Rev No:

Id No: Connected From: Cores CSA Cable Type Length CPC (mm2 ): Volt Drop Protective Device
Name: Connected To: (mm2 ) (m) Separate % Ir(A) In(A) Type RCD
Integral

CKT P220 DB-P2/8/L1 1 x 2 x 1c 2.5 Single-core, 90°C thermosetting, 116 4 4.67 10 10 MCB N/A
P220 insulated, non-arm Cu Table 4E1 0

CKT P221 DB-P2/7/L2 1 x 2 x 1c 4 Single-core, 90°C thermosetting, 54 2.5 3.55 20 20 MCB N/A
P221 insulated, non-arm Cu Table 4E1 0

CKT P222 DB-P2/8/L2 1 x 2 x 1c 4 Single-core, 90°C thermosetting, 46 2.5 3.13 20 20 MCB N/A
P222 insulated, non-arm Cu Table 4E1 0

CKT P223 DB-P2/7/L3 1 x 2 x 1c 4 Single-core, 90°C thermosetting, 46 2.5 3.18 20 20 MCB N/A
P223 insulated, non-arm Cu Table 4E1 0

CKT P224 DB-P2/8/L3 1 x 2 x 1c 2.5 Single-core, 90°C thermosetting, 64 4 4.45 16 16 MCB N/A
P224 insulated, non-arm Cu Table 4E1 0

CKTP105 DB-P1/1/L3 2 x 2 x 1c 4 Single-core, 90°C thermosetting, 46 1.5 1.40 32 32 MCB N/A


P105 insulated, non-arm Cu Table 4E1 0

Project: D:\My Documents\ALAOJI\SERVICE BLDGS\CentralControlBldg\CCB-DBP.p17 Page 4 of 4 Printed on: 11/12/2008


Created using: 15.0.0(BS7671:2008) - Rockson Engineering Ltd Copyright © AMTECH Power Software Ltd 2008