Technical catalogue

SACE Emax DC
Low voltage air circuit-breakers
for direct current applications
ABB SACE 1
1SDC200012D0202
Index
SACE Emax DC circuit-breakers ............................................................................................. 2

SACE Emax DC switch-disconnectors .................................................................................... 6

Versions and connections ....................................................................................................... 7
Dissipated powers ................................................................................................................... 8
Temperature derating .............................................................................................................. 9

Protection trip units and trip curves ...................................................................................... 11
Accessories ........................................................................................................................... 25

Overall dimensions ................................................................................................................ 26

Electric wiring diagrams ........................................................................................................ 35
Selection Emax DC ................................................................................................................ 44

Ordering codes ..................................................................................................................... 50
Ordering examples ................................................................................................................ 88
ABB SACE 2
1SDC200012D0202
1
S
D
C
2
0
0
6
0
1
F
0
0
0
1
Common data
Voltages
Rated service voltage Ue [V] 1000
Rated insulation voltage Ui [V] 1000
Rated impulse withstand voltage Uimp [kV] 12
Operating temperature [C] -25....+70
Storage temperature [C] -40....+70
Number of poles 3 - 4
Versions Fixed - Withdrawable
E2 E3 E4 E6
Levels of performance B N N H S H H
Rated uninterrupted current (at 40 C) Iu [A] 800 800
[A] 1000 1000
[A] 1250 1250
[A] 1600 1600 1600 1600 1600
[A] 2000 2000 2000
[A] 2500 2500 2500
[A] 3200 3200 3200
[A] 4000
[A] 5000
Rated ultimate short-circuit breaking current Icu according to the appli-
cation network
See pages 3, 4 and 5
Rated service short-circuit breaking current Ics [%Icu] [kA] 100% 100% 100% 100% 100% 100% 100%
Rated short-time withstand current Icw (0.5s)
@ 500 V DC (3p) [kA] 35 50 60 65 75 100 100
@ 750 V DC (3p) [kA] 25 25 40 40 65 65 65
@ 750 V DC (4p) [kA] 25 40 50 50 65 65 65
@ 1000 V DC (4p) [kA] 25 25 35 40 50 65 65
Rated short-circuit making current Icm [%Icu] [kA] 100% 100% 100% 100% 100% 100% 100%
Category of use (according to CEI EN 60947-2) B B B B B B B
Isolation behaviour (according to CEI EN 60947-2) Q Q Q Q Q Q Q
Overcurrent protection
Electronic trip units for DC applications Q Q Q Q Q Q Q
Operating times
Closing time (max) [ms] 80 80 80 80 80 80 80
Breaking time for I>Icw (max)
(1)
[ms] 60 60 60 60 60 60 60
Overall dimensions
Fixed: H = 418 mm - D = 302 mm - W (3/4 poles) [mm] 296/386 296/386 404/530 404/530 566/656 566/656 782/908
Withdrawable: H = 461 mm - D = 396.5 mm - W (3/4 poles) [mm] 324/414 324/414 432/558 432/558 594/684 594/684 810/936
Weights
Fixed 3/4 poles [kg] 50/61 50/61 66/80 66/80 97/117 97/117 140/160
Withdrawable 3/4 poles (including the fixed part) [kg] 50/61 50/61 66/80 66/80 147/165 147/165 210/240
SACE Emax DC circuit-breakers
The SACE Emax range of low voltage circuit-breakers is completed by the new SACE Emax
DC series of circuit-breakers for direct current applications complying with the IEC60947-
2 Standard. Thanks to the exclusive technology applied to the new SACE PR123/DC and
PR122/DC trip units, the SACE Emax DC range allows all installation requirements to be met
and protection up to 1000V DC / 5000A.
With connection of three interruption poles in series, the rated voltage which can be reached
is 750V DC, whereas with four poles in series this rises to 1000V DC.
The withdrawable circuit-breakers must be associated with the fixed parts in a special version
for applications at 750/1000V DC.
(1) Without intentional delays.
E2 E3 E4 E6
Iu
800
1000
1250
1600
800
1000
1250
1600 2000 2500 1600 2000
2500
3200
3200 4000 5000
Life with regular maintenance N. operations
Mechanical x 1000 25 25 20 20 20 20 15 15 15 12 12 12
Electrical 1000V DC x 1000 15 10 12 10 9 7 7 7 7 5 4 2
ABB SACE 3
1SDC200012D0202
+
-
L
O
A
D
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
Insulated network
(1)
Rated voltage (Ue) 500 750 1000
isolation Q Q Q Q
protection Q Q Q Q
PR122/DC Q Q Q Q
PR123/DC Q Q Q Q
Icu
(2)
[kA] [kA] [kA] [kA]
E2
B
800
35 25 25 25
1000
1250
1600
N 1600 50 25 40 25
E3
N
800
60 40 50 35
1000
1250
1600
2000
2500
H
1600
65
(3)
40 50 40 2000
2500
E4
S
1600
75 65 65 50
2000
2500
3200
H 3200 100 65 65 65
E6 H
3200
100 65 65 65 4000
5000
(1)
the possibility of a double earth fault is considered negligible with this type of pole connections. For further information, see QT5: ABB circuit-breakers for direct current applications.
(2)
Icu with L/R = 15ms according to IEC 60946-2 Standard. For Icu with L/R = 5ms and L/R = 30ms, ask ABB.
(3)
85kA only if supplied from lower terminals and specifying the following extracode at the ordering stage: 1SDA067148R1. Ics=65kA.
SACE Emax DC circuit-breakers
Rated ultimate short-circuit breaking current Icu
according to the type of network
ABB SACE 4
1SDC200012D0202
+
-
L
O
A
D
+ -
LOAD -
LOAD +
SACE Emax DC circuit-breakers
Rated ultimate short-circuit breaking current Icu
according to the type of network
Network with earthed negative polarity
(1)
Rated voltage (Ue) 500
(2)
isolation Q Q
protection Q Q
PR122/DC Q Q
PR123/DC Q Q
type of fault
(3)
a b a b
poles in series affected by the fault 3 2 4 3
Icu
(4)
[kA] [kA]
E2
B
800
35 20 35 35
1000
1250
1600
N 1600 50 25 50 50
E3
N
800
60 30 60 60
1000
1250
1600
2000
2500
H
1600
65
(5)
40 65
(5)
65
(5)
2000
2500
E4
S
1600
100 50 100 100
2000
2500
3200
H 3200 100 65 100 100
E6 H
3200
100 65 100 100 4000
5000
(1)
for networks with positive earthed polarity, ask ABB.
(2)
for higher voltages, ask ABB.
(3)
for further information, see QT5: ABB circuit-breakers for direct current applications.
(4)
Icu with L/R = 15ms according to IEC 60946-2 Standard. For Icu with L/R = 5ms and L/R = 30ms, ask ABB.
(5)
85kA only if supplied from lower terminals and specifying the following extracode at the ordering stage: 1SDA067148R1. Ics=65kA.
ABB SACE 5
1SDC200012D02202
+
-
2
2
L
O
A
D
+ -
LOAD -
LOAD +
Network with the mid-point earthed
Rated voltage (Ue) 500 500 750 1000
PR122/DC - - - -
PR123/DC Q Q Q Q
type of fault a b c a b c a b c a b c
poles in series affected by the fault 3 2 (U/2) 1 (U/2) 4 2 (U/2) 2 (U/2) 4 2 (U/2) 2 (U/2) 4 2 (U/2) 2 (U/2)
Icu
(1)
[kA] [kA] [kA] [kA]
E2
B
800
35 35 18 35 35 35 25 25 25 25 25 25
1000
1250
1600
N 1600 50 50 25 50 50 50 40 40 40 25 25 25
E3
N
800
60 60 30 60 60 60 50 50 50 35 35 35
1000
1250
1600
2000
2500
H
1600
65
(2)
65 40 65
(2)
65
(2)
65
(2)
50 50 50 40 40 40 2000
2500
E4
S
1600
75 75 35 75 75 75 65 65 65 50 50 50
2000
2500
3200
H 3200 100 100 50 100 100 100 65 65 65 65 65 65
E6 H
3200
100 100 65 100 100 100 65 65 65 65 65 65 4000
5000
(1)
Icu with L/R = 15ms according to IEC 60946-2 Standard. For Icu with L/R = 5ms and L/R = 30ms, ask ABB.
(2)
85kA only if supplied from below and specifying the following extracode at the ordering stage: 1SDA067148R1. Ics=65kA.
ABB SACE 6
1SDC200012D0202
SACE Emax switch-disconnectors
ABB SACE has developed the SACE Emax/E MS range of switch-disconnectors for direct cur-
rent applications up to 1000V complying with the international IEC60947-3 Standard. These
circuit-breakers are particularly suitable for use as bus-ties or main switch-disconnectors in
direct current plants, such as applications in the field of electric traction.
The range makes it possible to cover any installation requirement up to 1000V DC / 6300A.
The circuit-breakers are available in the fixed or withdrawable version and in the three-pole
or four-pole version.
With connection of three breaking poles in series, the rated voltage which can be reached is
750V DC, whereas with four poles in series this rises to 1000V DC.
The switch-disconnectors in the SACE Emax/E MS range keep all the overall dimensions
and fixing points of the circuit-breakers of the standard range unchanged. The withdrawable
circuit-breakers must be associated with the fixed parts in a special version for applications
at 750/1000V DC.
Note: By means of an extreme protection relay with maximum timing of 500 ms, the Icu breaking current is the same as the Icw value (1s).
* The performances at 750 V are:
for E1B/E MS Icw=25kA
for E2N/E MS Icw=40kA
for E3H/E MS Icw=50kA
E1B/E MS E2N/E MS E3H/E MS E4H/E MS E6H/E MS
Rated current (at 40 C) Iu [A] 800 1250 1250 3200 5000
[A] 1250 1600 1600 4000 6300
[A] 2000 2000
[A] 2500
[A] 3200
Poles 3 4 3 4 3 4 3 4 3 4
Rated service voltage Ue [V] 750 1000 750 1000 750 1000 750 1000 750 1000
Rated insulation voltage Ui [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp [kV] 12 12 12 12 12 12 12 12 12 12
Rated short-time withstand current Icw (1s) [kA] 20 20* 25 25* 40 40* 65 65 65 65
Rated making current Icm [%Icw] 100 100 100 100 100 100 100 100 100 100
ABB SACE 7
1SDC200012D0202
Versions and connections
Versions and connections
The Emax DC circuit-breakers are available in the fixed or withdrawable, three-pole or four-
pole versions.
All Emax circuit-breakers for direct current have several poles in series involved in breaking the
fault, for this reason special connections busbar (known as U connection kit) are mounted
on the circuit-breaker terminals.
Selection of the power supply side, from the lower or upper terminals, must only be made at
the time of ordering and cannot be modified later by the customer.
The fixed circuit-breakers are fitted with vertical terminals, whereas it is possible to select
between vertical and horizontal terminals for circuit-breakers in the withdrawable version.
Fixed circuit-breaker
Vertical rear terminals
Withdrawable circuit-breaker
Vertical rear terminals
Horizontal rear terminals
Power supply from lower terminals Power supply from upper terminals
Power supply from lower terminals Power supply from upper terminals
Power supply from lower terminals Power supply from upper terminals
ABB SACE 8
1SDC200012D0202
Power losses
The power losses for Emax DC circuit-breakers are given below according to:
- range;
- trip unit;
- version;
- number of poles;
- Iu.
Emax DC power losses [W]
Iu [A]
Trip unit Version poles 800 1000 1250 1600 2000 2500 3200 4000 5000
E2
PR122/DC
F 3p 42 60 94 136
W 3p 66 98 152 232
F 4p 51 75 117 174
W 4p 83 125 195 302
PR123/DC
F 3p 54 113 176 156
W 3p 78 113 176 252
F 4p 64 140 219 195
W 4p 96 140 219 323
E3
PR122/DC
F 3p 32 61 95 123 216 338
W 3p 47 69 108 207 248 388
F 4p 38 87 123 184 288 450
W 4p 59 87 136 205 320 500
PR123/DC
F 3p 50 68 106 138 216 338
W 3p 60 84 131 179 280 438
F 4p 55 86 134 184 288 450
W 4p 65 102 159 225 352 550
E4
PR122/DC
F 3p 120 188 271
W 3p 195 305 463
F 4p 136 234 348
W 4p 236 391 604
PR123/DC
F 3p 150 234 312
W 3p 225 352 504
F 4p 180 281 389
W 4p 280 438 645
E6
PR122/DC
F 3p 154 304 475
W 3p 276 496 775
F 4p 246 384 600
W 4p 410 640 1000
PR123/DC
F 3p 236 368 575
W 3p 358 560 875
F 4p 287 448 700
W 4p 451 704 1100
ABB SACE 9
1SDC200012D0202
E2 DC 800 1000 1250 1600
C % A % A % A % A
10 100% 800 100% 1000 100% 1250 100% 1600
20 100% 800 100% 1000 100% 1250 100% 1600
30 100% 800 100% 1000 100% 1250 100% 1600
40 100% 800 100% 1000 100% 1250 100% 1600
50 100% 800 100% 1000 100% 1250 100% 1600
55 100% 800 100% 1000 100% 1250 100% 1600
60 100% 800 100% 1000 100% 1250 98% 1567
70 100% 800 100% 1000 100% 1250 94% 1500
E3 DC 800 1000 1250 1600 2000 2500
C % A % A % A % A % A % A
10 100% 800 100% 1000 100% 1250 100% 1600 100% 2000 100% 2500
20 100% 800 100% 1000 100% 1250 100% 1600 100% 2000 100% 2500
30 100% 800 100% 1000 100% 1250 100% 1600 100% 2000 100% 2500
40 100% 800 100% 1000 100% 1250 100% 1600 100% 2000 100% 2500
50 100% 800 100% 1000 100% 1250 100% 1600 100% 2000 100% 2500
55 100% 800 100% 1000 100% 1250 100% 1600 100% 2000 100% 2500
60 100% 800 100% 1000 100% 1250 100% 1600 100% 2000 100% 2500
70 100% 800 100% 1000 100% 1250 100% 1600 100% 2000 94% 2350
The following graphs show derating as a function of temperature for Emax DC circuit-breakers.
20 10 50 30 40 70 55 60
500
1000
1500
2000
0
C
E2 DC
I
u

[
A
]
800
1000
1250
1600
20 10 50 30 40 70 55 60
500
1000
1500
2000
3000
0
C
E3 DC
I
u

[
A
]
800
1000
1250
1600
2000
2500
2500
Temperature derating
ABB SACE 10
1SDC200012D0202
E6 DC 3200 4000 5000
C % A % A % A
0 100% 3200 100% 4000 100% 5000
10 100% 3200 100% 4000 100% 5000
20 100% 3200 100% 4000 100% 5000
30 100% 3200 100% 4000 100% 5000
40 100% 3200 100% 4000 100% 5000
50 100% 3200 100% 4000 100% 5000
55 100% 3200 100% 4000 100% 5000
60 100% 3200 100% 4000 100% 5000
70 100% 3200 100% 4000 96% 4800
E4 DC 1600 2000 2500 3200
C % A % A % A % A
10 100% 1600 100% 2000 100% 2500 100% 3200
20 100% 1600 100% 2000 100% 2500 100% 3200
30 100% 1600 100% 2000 100% 2500 100% 3200
40 100% 1600 100% 2000 100% 2500 100% 3200
50 100% 1600 100% 2000 100% 2500 100% 3200
55 100% 1600 100% 2000 100% 2500 100% 3200
60 100% 1600 100% 2000 100% 2500 100% 3200
70 100% 1600 100% 2000 100% 2500 97% 3100
20 10 50 30 40 70 55 60
500
1000
1500
2000
3500
0
C
E4 DC
I
u

[
A
]
3200
1600
2000
2500
2500
3000
20 10 50 30 40 70 55 60
1000
2000
3000
4000
6000
0
C
E6 DC
I
u

[
A
]
3200
4000
5000
5000
Temperature derating
ABB SACE 11
1SDC200012D0202
1
S
D
C
2
0
0
6
0
7
F
0
0
0
1
Protection trip units and trip curves
PR122/DC
Characteristics
PR122/DC is the new electronic trip unit for the Emax DC series. The wide range of protection
functions, together with the wide variety of trip thresholds and times, make them suitable for
protection of insulated networks or networks with earthed negative polarity. Information about
the unit and programming are particularly simple and intuitive thanks to the LCD graphic display.
The PR122/DC trip unit offers the following protection functions:
over|oad |},
se|eot|ve short-o|rou|t S},
therma| memory for | and S oab|e proteot|on},
|nstantaneous short-o|rou|t l},
overtemperature OT},
zone se|eot|v|ty for S,
|oad oontro| K},
start|ng thresho|d.
ABB SACE 12
1SDC200012D0202
OT
(1) The minimum trip value is 0.5 s, regardless of the type of curve set
(2) These tolerances are valid in the following hypotheses:
- trip unit supplied entirely by the voltage module and/or auxiliary power supply (without start-up)
- trip time set t 100 ms
For all cases not contemplated by the above hypotheses, the following tolerance values are valid:
Protection functions and setting values - PR122/DC
Function Trip
threshold
Threshold
step
Trip time Time
step
Poss. excl. Relation
t=f(I)
Thermal
memory
Zone
selectivity
Protection against
overload I1= 0.4...1 x In 0.01 x In
With current If = 3 x I1
t1= 3 s...102 s
(1)
3 s IEC60255-8 Q
Tolerance
(2)
Trip unit between
1.05 and 1.3 x I1
10%, If d 6 x In
20%, If > 6 x In
Selective protection
against short-circuit
I2= 0.6...10 x In 0.1 x In
With current If > I2
t2= 0.05 s...0.35 s
t2sel= 0.04 s...0.2 s
0.01 s
0.01 s
Q t=k Q
Tolerance
(2)
7%, If d 6 x In
10%, If > 6 x In
The best of the two data:
10% or 40 ms
I2= 0.6...10 x In 0.1 x In
With current If 10 x In
t2= 0.05 s...0.35 s
0.01 s Q t=k/I
2
Q
Tolerance
(2)
7%, If d 6 x In
10%, If > 6 x In
15%, If d 6 x In
20%, If > 6 x In
Protection against
instantaneous
short-circuit I3= 1.5...10 x In 0.1 x In Instantaneous Q t=k
Tolerance
(2)
10% d 30 ms
Protection against
overtemperature Cannot be set Instantaneous t=k
Trip threshold Trip time
L Trip between 1.05 and 1.25 x I1 20%
S 10% 20%
I 15% d 60ms
Protection trip units and trip curves
PR122/DC
ABB SACE 13
1SDC200012D0202
Ue [V] 12 100 250 1000

PR120/LV: PR120/LV + Vaux PR120/LV NO
PR120/V: PR120/V + Vaux PR120/V + Vaux PR120/V

+
With plant voltages higher than or equal to 100V, the PR122/DC electronic trip unit guarantees
protection without the need of an auxiliary power supply (24V DC).
The PR122/DC electronic trip unit can, in fact, always be equipped with the PR120/V module
able to supply the trip unit with plant voltages between 250V DC and 1000V DC.
For voltages between 100V DC and 250V DC, it is necessary to order the PR120/LV module,
specifying the extracode 1SDA066223R1.
The following table shows the cases when it is possible to use the measurement modules
(PR120/V and PR120/LV):
When there is an auxiliary power supply, see the table below for the overall consumption values.
PR122/DC PR120/D-M PR120/K
Auxiliary power supply
(galvanically insulated)
24V DC 20% from PR122/DC from PR122/DC
Maximum ripple 5%
Inrush current @ 24V ~10A for 5 ms
Rated power @ 24V ~3 W +1.5 W +1.5 W
When Emax DC circuit-breakers are used in plants with capacitor banks with possible back-
to-back inrush currents 3xIn, it is necessary to use a 24V DC galvanically insulated auxiliary
power supply.
Emax DC circuit-breakers are normally supplied with power input from lower terminals, i.e. the
PR120/V-PR120/LV internal connection is on the lower terminals, whereas the U connections
are on the upper terminals:
3D rear view
Front view
For power supply from upper terminals, refer to the Code Section for ordering.
Protection is guaranteed even when the electronic trip unit is not powered thanks to the PR120/DC
module which always equips the PR122/DC.
ABB SACE 14
1SDC200012D0202
t = k
I
2
t = k
1
S
D
C
2
0
0
6
0
8
F
0
0
0
1
1
S
D
C
2
0
0
6
0
9
F
0
0
0
1
Functions L-S-I
Functions L-S-I
Protection trip units and trip curves
PR122/DC
ABB SACE 15
1SDC200012D0202
1
S
D
C
2
0
0
6
1
0
F
0
0
0
1
Protection trip units and trip curves
PR123/DC
Characteristics
With the PR123/DC electronic protection trip unit, the range of trip units available for the Emax
DC series of circuit-breakers is completed.
PR123/DC is a high-performing trip unit capable of carrying out a complete set of protections,
measurements, indications, data storage and circuit-breaker control functions.
PR123/DC not only offers protection but also measurement of current and voltage of both
polarities (+ and -), thus being suitable for any type of network.
The front interface of the unit, common to PR122/DC, is extremely simple thanks to the aid
of the LCD graphic display.
The PR123/DC trip unit offers the following protection functions:
over|oad |},
se|eot|ve short-o|rou|t S},
therma| memory for | and S oab|e proteot|on},
|nstantaneous short-o|rou|t l},
earth fau|t w|th adjustab|e de|ay G},
po|ar|ty unba|anoe },
proteot|on aga|nst overtemperature OT},
|oad oontro| K},
undervo|tage v},
overvo|tage Ov},
aot|ve power reversa| RP},
doub|e set of parameters Dua| Sett|ng},
zone se|eot|v|ty for S and G,
start|ng thresho|ds for proteot|on S and l.
ABB SACE 16
1SDC200012D0202
OT
(1) The minimum trip value is 0.5 s, regardless of the type of curve set
(2) These tolerances are valid with the following hypothesis:
- trip unit supplied from the voltage module and/or auxiliary power supply
(without start-up)
- trip time set t 100 ms
For all cases not contemplated by the above hypothesis, the following tolerance values are valid:
Protection functions and setting values - PR123/DC
Function Trip
threshold
Threshold
step
Trip time Time
step
Poss. excl. Relation
t=f(I)
Thermal
memory
Zone
selectivity
Protection against
overload I1 = 0,4...1 x In 0.01 x In
With current I = 3 x I1
t1 = 3 s...102 s
(1)
3 s IEC60255-8 Q
Tolerance
(2)
Trip between
1.05 and 1.3 x I1
10% If d 6 x In
20% If > 6 x In
Selective protection
against short-circuit
I2 = 0.6...10 x In 0,1 x In
With current I > I2
t2 = 0.05 s...0.35 s
t2sel = 0.04 s...0.2 s
0.01 s
0.01 s
Q t=k Q
Tolerance
(2)
7% If d 6 x In
10% If > 6 x In
The best of the two data:
10% or 40 ms
I2 = 0.6...10 x In 0,1 x In
With current I = 10 x I1
t2 = 0.05 s...0.35 s
0.01 s Q t=k/I
2
Q
Tolerance
(2)
7% If d 6 x In
10% If > 6 x In
15% If d 6 x In
20% If > 6 x In
Selective protection
against short-circuit I2 = 0.6...10 x In 0,1 x In
With current I > I2
t2 = 0.05 s...0.35 s 0.01 s Q t=k Q
Tolerance
(2)
7% If d 6 x In
10% If > 6 x In
The best of the two data:
10% or 40 ms
Protection against
instantaneous
short-circuit I3 = 1.5...10 x In 0.1 x In Instantaneous Q t=k
Tolerance
(2)
10% d 30 ms
Protection against
earth fault
I4 = 0.2...1 x In 0.02 x In
With current I > I4
t4 = 0.1 s...1 s
t4sel = 0.04 s...0,2 s
0.05 s
0.01 s
Q t=k Q

Tolerance
(2)
7%
The best of the two data:
10% or 40 ms
I4 = 0.2...1 x In 0.02 x In t4 = 0.1 s...1 s
(with I=4xI4)
0.05 s Q t=k/I
2

Tolerance
(2)
7% 15%
Protection against
phase unbalance
I6 = 5%...90% 5%
t6 = 0.5 s...60 s
The best of the two data:
0.5 s Q t=k
Tolerance
(2)
10% 20% or 100 ms
Protection against
overtemperature Cannot be set Instantaneous t=k
Undervoltage
protection
U8 = 0.5...0.95 x Un 0.01 x In With voltage U < U8
t8 = 0.1 s...5 s
0.1 s Q t=k

Tolerance
(2)
5%
The best of the two data:
20% or 40 ms
Overvo|tage
protection
U9 = 1.05...1.2 x Un 0.01 x In With voltage U < U9
t9 = 0.1 s...5 s
0.1 s Q t=k

Tolerance
(2)
5%
The best of the two data:
20% or 40 ms
Protection against
reversal of power
P11 = -0.3...-0.1 x Pn 0.02 x Pn At power P < P11
t11 = 0.5 s...25 s
0.1 s Q t=k

Tolerance
(2)
10%
The best of the two data:
10% or 100 ms
Trip threshold Trip time
L Trip between 1.05 and 1.3 x I1 20%
S 10% 20%
I 15% d 60ms
G 15% 20%
Altri 20%
U
OV
UV
RP
Protection trip units and trip curves
PR123/DC
ABB SACE 17
1SDC200012D0202
Ue [V] 12 100 250 1000

PR120/LV: PR120/LV + Vaux PR120/LV NO
PR120/V: PR120/V + Vaux PR120/V + Vaux PR120/V

+
With plant voltages higher than or equal to 100V, the PR123/DC electronic trip unit guarantees
protection without the need of an auxiliary power supply (24V DC).
The PR123/DC electronic trip unit is, in fact, always fitted with the PR120/V module able to
supply the trip unit with plant voltages between 250V DC and 1000V DC.
For voltages between 100V DC and 250V DC, it is necessary to request the PR120/LV module,
specifying the extracode 1SDA066223R1.
The following table shows the possible cases of use of the measurement modules (PR120/V
and PR120/LV):
When there is an auxiliary power supply, see the table given below for the overall consumption
values.
PR123/DC PR120/D-M PR120/K
Auxiliary power supply
(galvanically insulated)
24V DC 20% from PR123/DC from PR123/DC
Maximum ripple 5%
Inrush current @ 24V ~10A for 5 ms
Rated power @ 24V ~3 W +1,5 W +1,5 W
When Emax DC circuit-breakers are used in plants with capacitor banks with possible inrush
back-to-back currents 3xIn, it is necessary to use a 24V DC galvanically insulated auxiliary
power supply.
The range of Emax DC circuit-breakers is normally supplied with power input from lower ter-
minals, i.e. the PR120/V-PR120/LV internal connection is on the lower terminals, whereas the
U connections are on the upper terminals:
3D rear view
Front view
For power input to the upper terminals, refer to the ordering Code Section.
Protection is guaranteed even when there is no power supply to the electronic trip unit thanks
to the PR120/DC module, which always equips the PR123/DC.
ABB SACE 18
1SDC200012D0202
t = k
I
2
t = k
1
S
D
C
2
0
0
6
0
8
F
0
0
0
1
1
S
D
C
2
0
0
6
0
9
F
0
0
0
1
Functions L-S-I
Functions L-S-I
Protection trip units and trip curves
PR123/DC
ABB SACE 19
1SDC200012D0202
t =
k
I
2
t = k
U
1
S
D
C
2
0
0
6
1
1
F
0
0
0
1
1
S
D
C
2
0
0
6
1
2
F
0
0
0
1
Function G
Function U
ABB SACE 20
1SDC200012D0202
RP
UV
1
S
D
C
2
0
0
6
1
3
F
0
0
0
1
1
S
D
C
2
0
0
6
1
4
F
0
0
0
1
Function RP
Function UV
Protection trip units and trip curves
PR123/DC
ABB SACE 21
1SDC200012D0202
OV
1
S
D
C
2
0
0
6
1
5
F
0
0
0
1
Function OV
ABB SACE 22
1SDC200012D0202
The PR122/DC and PR123/DC electronic trip units can be fitted with the following optional
modules, which are already available on the PR122/P and PR123/P electronic devices for
alternating current applications.
Code Internal Description
PR122/DC
PR123/DC
1SDA058255R1 PR120/K
Internal indication module
(4 outputs with independent terminals)
Q
1SDA058256R1 PR120/K
Internal indication module
(4 outputs + input with common terminal)
Q
1SDA058254R1 PR120/D-M Modbus RTU communication module Q
1SDA065223R1
(1)
PR120/LV Measurement module for low voltage (100...250V DC) Q
(1)
Extracode to be specified with the circuit-breaker code to order the PR120/LV low voltage measurement module instead of the PR120/LV.
The PR120/LV measurement module and the PR120/DC override protection module are always supplied with the electronic trip units.
Protection trip units and trip curves
PR122/DC and PR123/DC: optional modules
Code External Description
PR122/DC
PR123/DC
1SDA058258R1 PR030/B Power supply unit Q
1SDA058259R1 BT030-USB External wireless communication unit (without wires) Q
1SDA048964R1 PR010/T External test unit Q
1SDA059146R1 PR021/K External indication unit Q
ABB SACE 23
1SDC200012D0202
PR122/DC
The following measurements are available:
Ourrent,
lnstantaneous va|ue of the ourrent over a per|od of t|me data |ogger},
Ma|ntenanoe: Number of operat|ons, peroentage of oontaot wear, storage of open|ng data
(last 20 trips and 80 events);
H|stor|oa| data of the max|mum va|ues of ourrent read|ng.
PR123/DC
Ourrent,
Ma|ntenanoe: Number of operat|ons, peroentage of oontaot wear, storage of open|ng data
(last 20 trips and 80 events);
vo|tage,
lnstantaneous va|ue of the ourrent/vo|tage over a per|od of t|me Data |ogger},
Power,
Energy,
H|stor|oa| data of the max|mum va|ues of ourrent read|ng, the max|mum vo|tage and the
minimum voltage, the total maximum value and the average value of the power.
Protection trip units and trip curves
Measurement
ABB SACE 24
1SDC200012D0202
The functions available on the PR122/DC and PR123/DC electronic trip units fitted with Modbus
PR120/D-M communication module are listed in the following table.
PR122/DC
+ PR120/D-M
PR123/DC
+ PR120/D-M
Communication functions
Protocol Modbus RTU Modbus RTU
Physical layer RS-485 RS-485
Maximum baud rate 19200 bps 19200 bps
Measurement functions
Currents Q Q
Ground ourrent Q
Voltage Q
Power Q
Energy Q
Indication functions
LED: Auxiliary power supply, pre-alarm, alarm Q Q
Temperature Q Q
lnd|oat|on for |, S, l and G on|y w|th PR123/DO} Q Q
Data available
Circuit-breaker status (open-closed) Q Q
Circuit-breaker position (racked-in, racked-out) Q Q
Mode (local, remote) Q Q
Protection parameters set Q Q
Load control parameters Q Q
Alarms
Protection L Q Q
Protection S Q Q
Protection I Q Q
Proteot|on G Q
Fault release mechanism failure Q Q
Under- and overvoltage protection (timing and trip) Q
Reverse power protection (timing and trip) Q
Maintenance
Total number of operations Q Q
Total number of trips Q Q
Number of trip tests Q Q
Number of manual operations Q Q
Number of separate trips for each protection function Q Q
Contact wear (%) Q Q
Recording data of the last 20 trips Q Q
Controls
Circuit-breaker open/close Q Q
Reset alarms Q Q
Setting of curves and protection thresholds Q Q
Synchronize system time Q Q
Events
Status changes in circuit-breaker protections and all alarms Q Q
Protection trip units and trip curves
Functions
ABB SACE 25
1SDC200012D0202
Accessories
Electrical and mechanical accessories
Accessories*
The SACE Emax DC family of circuit-breakers can be fitted with the following electrical and
mechanical accessories, which are already available for the standard family of circuit-breakers
for alternating current applications.
* For further information on the accessories, please consult the Emax catalogue: Circuit-break-
ers \ low voltage air.
CAPTION
Q Opt|ona| aooessory on f|xed o|rou|t-breaker or on mov|ng part
Q Opt|ona| aooessory on f|xed part
Q Opt|ona| aooessory on mov|ng part
Ranges Circuit-breakers
Switch-disconnectors for
applications up to 1000V DC
Circuit-breaker version Fixed Withdrawable Fixed Withdrawable
1a)
Shunt open|ng/o|os|ng re|ease YO/YO}
and seoond open|ng re|ease YO2}
Q Q Q Q
1b) SOR test un|t test un|t} Q Q Q Q
2a) Undervoltage release (YU) Q Q Q Q
2b) Time-delay device for undervoltage release (D) Q Q Q Q
3) Geared motor for automat|o oharg|ng of the o|os|ng spr|ngs M} Q Q Q Q
4a) Electrical signalling of electronic trip unit tripped Q Q
4b)
Electrical signalling of electronic trip unit tripped with remote
resetting control
Q Q
5b)
External supplementary electrical signalling
of circuit-breaker open/closed
Q Q Q Q
5c)
Electrical signalling of circuit-breaker
racked-in/racked-out test/racked-out
Q Q
5d) Signalling contact for closing springs charged Q Q Q Q
5e)
Signalling contact for undervoltage release
de-energised (C. Aux YU)
Q Q Q Q
7) Mechanical operation counter Q Q Q Q
8a) Lock in open position: key Q Q Q Q
8b) Lock in open position: padlocks Q Q Q Q
8c) Circuit-breaker lock in racked-in/racked-out/test isolated position Q Q
8d) Accessories for lock in of racked-out/test isolated position Q Q
8e) Accessory for shutters padlock device Q Q
8f) Mechanical lock for compartment door Q Q Q Q
9a) Protection for opening and closing pushbuttons Q Q Q Q
9b) IP54 door protection Q Q Q Q
10) Interlock between circuit-breakers Q Q Q Q
ABB SACE 26
1SDC200012D0202
E2 - E4 E3 - E6
Iu=1250A
Iu=1600A
Iu=1250A
Iu=1600A
Iu=800A
Iu=1000A
Iu=800A
Iu=1000A
1
S
D
C
2
0
0
6
1
7
F
0
0
0
1
1
S
D
C
2
0
0
6
1
8
F
0
0
0
1
A B C D
E2 386 296 148 148
E3 530 404 202 202
E4 746 566 238 328
E6 1034 782 328 454
4 POLES
3 POLES
4 POLES
3 POLES
Caption
1 Inside edge of compartment
door
2 Partition (where provided)
3 Circuit-breaker xing M10
drilling (use M10 screws)
4 N. 1 M12 screw (E1, E2, E3)
or n. 2 M12 screws (E4, E6)
for earthing (included in the
supply)
5 Insulating or metallic wall
6 For power input to the
UPPER terminals PR120/V
internal connection on the
upper terminals and rear U
connection kit on the lower
terminals
7 For power input to the
LOWER terminals PR120/V
internal connection on the
lower terminals and rear U
connection kit on the upper
terminals
E2 III
View A
E2 IV
View A
Overall dimensions
Fixed circuit-breaker
Basic version with vertical rear terminals
POWER SPP|Y FROM PPER TERMlNA|S 6
POWER SPP|Y FROM |OWER TERMlNA|S 7
ABB SACE 27
1SDC200012D0202
Iu=2500A
Iu=3200A
Iu=1600A
Iu=2000A
Iu=2000A
Iu=2500A
Iu=800A
Iu=1000A
Iu=1250A
Iu=1600A
1
S
D
C
2
0
0
6
1
9
F
0
0
0
1
Iu=2000A
Iu=2500A
Iu=800A
Iu=1000A
Iu=1250A
Iu=1600A
E3 III
View A
E3 IV
View A
E4 III
View A
ABB SACE 28
1SDC200012D0202
1
S
D
C
2
0
0
6
2
0
F
0
0
0
1
Iu=2500A
Iu=3200A
Iu=1600A
Iu=2000A
E4 IV
View A
E6 III
View A
E6 IV
View A
Overall dimensions
Fixed circuit-breaker
Basic version with vertical rear terminals
ABB SACE 29
1SDC200012D0202
1
S
D
C
2
0
0
6
2
1
F
0
0
0
1
A B
E2 400 490
E3 500 630
E4 700 880
E6 1000 1260
Compartment dimensions
N 2 holes for
IP54 protection
Depth
3 POLES
4 POLES
Drilling of compartment door Through-holes for flexible cables for
mechanical interlocks
ABB SACE 30
1SDC200012D0202
E2-E4
E3-E6
Iu=1250A
Iu=1600A
1
S
D
C
2
0
0
6
2
2
F
0
0
0
1
1
S
D
C
2
0
0
6
2
3
F
0
0
0
1
A B C D
E2 414 324 162 162
E3 558 432 216 216
E4 774 594 252 342
E6 1062 810 342 468
3 POLES
3 POLES
4 POLES
4 POLES
Overall dimensions
Withdrawable circuit-breaker
Basic version with rear vertical terminals
Caption
1 Inside edge of compartment
door
2 Segregation (where provided)
3 Circuit-breaker xing M10
drilling (use M10 screws)
4 N. 1 M12 screw (E1, E2, E3)
or n. 2 M12 screws (E4, E6)
for earthing (included in the
supply)
5 Insulating wall or insulated
metal wall
6 For power input to the
UPPER terminals PR120/V
internal connection on the
upper terminals and rear U
connection kit on the lower
terminals
7 For power input to the
LOWER terminals PR120/V
internal connection on the
lower terminals and rear U
connection kit on the upper
terminals
E2 III
View A
E2 IV
View A
POWER SPP|Y FROM PPER TERMlNA|S 6
POWER SPP|Y FROM |OWER TERMlNA|S 7
ABB SACE 31
1SDC200012D0202
1
S
D
C
2
0
0
6
2
4
X
F
0
0
0
1
Iu=2500A
Iu=3200A
Iu=1600A
Iu=2000A
E3 III
View A
E4 III
View A
E6 III
View A
E3 IV
View A
E4 IV
View A
E6 IV
View A
ABB SACE 32
1SDC200012D0202
E2-E4
E3-E6
1
S
D
C
2
0
0
6
2
2
A
F
0
0
0
1
1
S
D
C
2
0
0
6
2
3
A
F
0
0
0
1
A B C D
E2 414 324 162 162
E3 558 432 216 216
E4 774 594 252 342
E6 1062 810 342 468
X X
465
18
8 8 10
264.5
80
71.5
348
X X
465
18
8 8 10
264.5
100
61.5
348
X X
465
18
8 8 10
124.5
348
X X
465
18
348
8 8 10
124.5
1
3
90
60
35
100
143
151 151
90
15
90
100 143
90 90
N
35
60
33
1
3
15
3 POLES
3 POLES
4 POLES
4 POLES
Overall dimensions
Withdrawable circuit-breaker
Basic version with rear horizontal terminals
Caption
1 Inside edge of compartment
door
2 Segregation (where provided)
3 Circuit-breaker xing M10
drilling (use M10 screws)
4 N. 1 M12 screw (E1, E2, E3)
or n. 2 M12 screws (E4, E6)
for earthing (included in the
supply)
5 Insulating wall or insulated
metal wall
6 For power input to the
UPPER terminals PR120/V
internal connection on the
upper terminals and rear U
connection kit on the lower
terminals
7 For power input to the
LOWER terminals PR120/V
internal connection on the
lower terminals and rear U
connection kit on the upper
terminals
E2 III
View A
E2 IV
View A
POWER SPP|Y FROM PPER TERMlNA|S 6
POWER SPP|Y FROM |OWER TERMlNA|S 7
ABB SACE 33
1SDC200012D0202
1
S
D
C
2
0
0
6
2
4
A
F
0
0
0
1
380
435
1
3

126 126
200
240
49
240
70
225
183
1
0

122
84
40
33
370
35 35
96 15
33
6
171
95
158
205
3
2
4
122
84
40
33
N
63
246
561
126 126 126
393,5 393,5
171
325
370
49
240
70
225
1
0

35 35
96
15
33
1
3

95
158
205
4
2
45
180 180
1
3

380
597
528
400
10
393,5
122
84
40
33
530
35 35 35
150
15
33
191
65
280
323
2
4
1
380
393,5
122
84
40
33
191
1
777
708
580
10

180 180 180


700
65
280
323
2
4
45
63
252 252
813
744
620
10

1
3

750
35 35 56 35 35
222
15 33
85
410
457
1
2
4
380
393,5
122
84
40
33
211
1
380
393,5
122
84
40
33
211
63
1065
996
10

252 252 252


996
85
410
457
2
4
866
E3 III
View A
E4 III
View A
E6 III
View A
E3 IV
View A
E4 IV
View A
E6 IV
View A
ABB SACE 34
1SDC200012D0202
1
S
D
C
2
0
0
6
2
7
F
0
0
0
1
1
S
D
C
2
0
0
6
2
6
F
0
0
0
1
A B
E2 400 490
E3 500 630
E4 700 880
E6 1000 1260
A
3 poles 4 poles
E2 180 180
E3 234 234
E4 270 360
E6 360 486
Fixed version
Withdrawable version
Minimum distance between circuit-breaker and switchboard wall Compartment door drilling
Overall dimensions
Circuit-breaker accessories
Mechanical compartment door lock
N 2 holes for
IP54 protection
Depth
3 POLES
4 POLES
Compartment dimensions
Drilling of compartment door Through-holes for flexible cables
for mechanical interlocks
ABB SACE 35
1SDC200012D0202
Warning
Before installing the circuit-breaker, carefully read note F on the circuit diagrams.
Operating status shown
The circuit diagram is for the following conditions:
- withdrawable circuit-breaker, open and racked-in
- circuits de-energised
- releases not tripped
- motor operating mechanism with springs discharged.
Versions
Though the diagram shows a circuit-breaker in withdrawable version, it can be applied to a xed version circuit-breaker
as well.
Fixed version
The control circuits are tted between terminals XV (connector X is not supplied).
With this version, the applications indicated in gures 31 and 32 cannot be provided.
Withdrawable version
The control circuits are tted between the poles of connector X (terminal box XV is not supplied).
Version with PR122/DC electronic trip unit
Version with PR123/DC electronic trip unit
Caption
= Circuit diagram gure number
* = See note indicated by letter
A1 = Circuit-breaker accessories
A3 = Accessories applied to the xed part of the circuit-breaker (for withdrawable version only)
A4 = Example switchgear and connections for control and signalling, outside the circuit-breaker
D = Electronic time-delay device of the undervoltage release, outside the circuit-breaker
F1 = Delayed-trip fuse
K51 = PR122/DO, PR123/DO e|eotron|o tr|p un|t w|th the fo||ow|ng proteot|on funot|ons:
- L overload protection with inverse long time-delay trip - setting I1
- S short-circuit protection with inverse or denite short time-delay trip - setting I2
- I short-circuit protection with instantaneous time-delay trip - setting I3
- G earth fau|t proteot|on w|th |nverse short t|me-de|ay tr|p - sett|ng l4
K51/1...8 = Oontaots of the PR021/K s|gna|||ng un|t
K51/GZ|n = Zone se|eot|v|ty: |nput for proteot|on G on|y w|th aux. and PR123/DO tr|p un|t}
K51/GZout = Zone se|eot|v|ty: output for proteot|on G on|y w|th aux. and PR123/DO tr|p un|t}
K51/lN1 = D|g|ta| programmab|e |nput ava||ab|e on|y w|th aux and PR122/DO or PR123/DO tr|p un|t w|th |nd|oator
modu|e PR120/K}
K51/P1...P4 = Programmab|e e|eotr|oa| s|gna|||ng ava||ab|e on|y w|th aux and PR122/DO or PR123/DO tr|p un|t w|th
|nd|oator modu|e PR120/K}
K51/SZ|n = Zone se|eot|v|ty: |nput for proteot|on S on|y w|th aux. And PR123/DO tr|p un|t}
K51/SZout = Zone se|eot|v|ty: output for proteot|on S on|y w|th aux. And PR123/DO tr|p un|t}
K51/YO = O|os|ng oontro| from PR122/DO or PR123/DO e|eotron|o tr|p un|t w|th oommun|oat|on modu|e PR120/D-M
K51/YO = Open|ng oontro| from PR122/DO or PR123/DO e|eotron|o tr|p un|t w|th oommun|oat|on modu|e PR120/D-M
M = Motor for charging the closing springs
Q = Circuit-breaker
Q/1...27 = Circuit-breaker auxiliary contacts
S33M/1...3 = Limit contacts for spring-charging motor
S43 = Switch for setting remote/local control
S51 = Contact for electrical signalling of circuit-breaker open due to tripping of the overcurrent release.
The circuit-breaker may be closed only after pressing the reset pushbutton, or after energizing the coil for
electrical reset (if available).
S75E/1...4 = Contacts for electrical signalling of circuit-breaker in racked-out position (only with withdrawable circuit-
breakers)
S75I/1...5 = Contacts for electrical signalling of circuit-breaker in racked-in position (only with withdrawable circuit-
breakers)
S75T/1..4 = Contacts for electrical signalling of circuit-breaker in test isolated position (only with withdrawable circuit-
breakers)
SC = Pushbutton or contact for closing the circuit-breaker
SO = Pushbutton or oontaot for open|ng the o|rou|t-breaker
SO1 = Pushbutton or oontaot for open|ng the o|rou|t-breaker w|th de|ayed tr|p
SO2 = Pushbutton or oontaot for open|ng the o|rou|t-breaker w|th |nstantaneous tr|p
SR = Pushbutton or contact for electrical circuit-breaker reset
Electric wiring diagrams
Information for reading
ABB SACE 36
1SDC200012D0202
W1 = Serial interface with control system (external bus): EIA RS485 interface (see note E)
W2 = Serial interface with the accessories of PR122/DC and PR123/DC trip units (internal bus)
X = Delivery connector for auxiliary circuits of withdrawable version circuit-breaker
X1...X7 = Connectors for the accessories of the circuit-breaker
XF = Delivery terminal box for the position contacts of the withdrawable circuit-breaker (located on the xed
part of the circuit-breaker)
K1 = Oonneotor for power o|rou|ts of PR122/DO and PR123/DO tr|p un|ts
K2 - K3 = Oonneotors for aux|||ary o|rou|ts of PR122/DO and PR123/DO tr|p un|ts
K4 = Oonneotor s|gna|||ng open/o|oset oontaot
K5 = Oonneotor for PR120/v modu|e
O = Oonneotor for YO1 re|ease
XV = Delivery terminal box for the auxiliary circuits of the xed circuit-breaker
YC = Shunt closing release
YO = Shunt open|ng re|ease
YO1 = Overourrent shunt open|ng re|ease
YO2 = Seoond shunt open|ng re|ease see note O}
YR = Coil to electrically reset the circuit-breaker
YU = Undervoltage release (see notes B and Q)
Description of figures
Fig. 1 = Motor circuit to charge the closing springs.
Fig. 2 = Circuit of shunt closing release.
Fig. 4 = Shunt opening release.
Fig. 6 = Instantaneous undervoltage release (see notes B and Q).
Fig. 7 = Undervoltage release with electronic time-delay device, outside the circuit-breaker (see notes B and Q)
Fig. 8 = Second shunt opening release (see note Q).
Fig. 11 = Contact for electrical signalling of springs charged.
Fig. 12 = Contact for electrical signalling of undervoltage release energized (see notes B and S).
Fig. 13 = Contact for electrical signalling of circuit-breaker open due to tripping of the overcurrent release.
The circuit-breaker may be closed only after pressing the reset pushbutton.
Fig. 14 = Contact for electrical signalling of circuit-breaker open due to tripping of the overcurrent release and elec-
trical reset coil. The circuit-breaker may be closed only after pressing the reset pushbutton or energizing
the coil.
Fig. 21 = First set of circuit-breaker auxiliary contacts.
Fig. 22 = Second set of circuit-breaker auxiliary contacts (see note V).
Fig. 23 = Third set of supplementary auxiliary contacts outside the circuit-breaker.
Fig. 31 = First set of contacts for electrical signalling of circuit-breaker in racked-in, test isolated, racked-out posi-
tion.
Fig. 32 = Second set of contacts for electrical signalling of circuit-breaker in racked-in, test isolated, racked-out
position.
Fig. 42 = Auxiliary circuits of PR122/DC and PR123/DC trip units (see notes F, M and V).
Fig. 45 = Circuits of the communication module PR120/D-M of the PR122/DC and PR123/DC trip units (optional,
see note E).
F|g. 46 = O|rou|ts of the |nd|oator modu|e PR120/K of the PR122/DO and PR123/DO tr|p un|ts - oonneot|on 1
(optional; see note V).
F|g. 47 = O|rou|ts of the |nd|oator modu|e PR120/K of the PR122/DO and PR123/DO tr|p un|ts - oonneot|on 2
(optional; see note V).
F|g. 62 = O|rou|ts of the PR021/K s|gna|||ng modu|e outs|de the o|rou|t-breaker}
Incompatibilities
The circuits indicated in the following gures cannot be supplied simultaneously on the same circuit-breaker:
6 - 7 - 8
13 - 14
22 - 46 47

Electric wiring diagrams
Information for reading
ABB SACE 37
1SDC200012D0202
Notes
A) The circuit-breaker is only tted with the accessories specied in the ABB SACE order acknowledgement.
Consult this catalogue for information on how to make out an order.
B) The undervoltage release is supplied for operation using a power supply branched on the supply side of the circuit-
breaker or from an independent source. The circuit-breaker can only close when the release is energized (there is
a mechanical lock on closing). If the same power supply is used for the closing and undervoltage releases and the
circuit-breaker is required to close automatically when the auxiliary power supply comes back on, a 30 ms delay
must be introduced between the undervoltage release accept signal and the energizing of the closing release. This
may be achieved using an external circuit comprising a permanent make contact, the contact shown in g. 12 and
a time-delay relay.
E} MODBS map |s ava||ab|e |n the RE1134001 dooument
F) The auxiliary voltage Uaux allows actuation of all operations of the PR122/DC and PR123/DC trip units. Having
requested a Uaux insulated from earth, one must use galvanically separated converters in compliance with IEC
60950 (UL 1950) or equivalent standards that ensure a common mode current or leakage current (see IEC 478/1,
CEI 22/3) not greater than 3.5 mA, IEC 60364-41 and CEI 64-8.
N) With PR122/DC and PR123/DC trip units, the connections to the zone selectivity inputs and outputs must be made
with a two-pole shielded and stranded cable (see user manual), no more than 300 m long. The shield must be
earthed on the selectivity input side.
P} W|th PR122/DO and PR123/DO tr|p un|ts w|th oommun|oat|on modu|e PR120/D-M, the power supp|y for oo||s YO
and YO must not be taken from the ma|n power supp|y. The oo||s oan be oontro||ed d|reot|y from oontaots K51/YO
and K51/ YO w|th max|mum vo|tages of 110-120 v DO and 240-250 v AO.
Q) The second opening release may be installed as an alternative to the undervoltage release.
S) Also available in the version with normally-closed contact
V) If g. 22 is present (second set of auxiliary contacts) simultaneously as PR122/DC or PR123/DC release, the con-
taots for the zone se|eot|v|ty |n fg. 42 K51/Z|n, K51/Zout, K51/Gz|n and K51/Gzout} are not w|red. ln add|t|on, the
|nd|oator modu|e PR120/K |n fgures 46 and 47 oannot be supp||ed
ABB SACE 38
1SDC200012D0202
1
S
D
C
2
0
0
6
2
8
F
0
0
0
1
Electric wiring diagrams
Graphic Symbols (IEC 606 7 and CEI 3- 4 ... 3-26 Standards)
Screen (can be drawn in
any shape)
Timing
Mechanical connection
Manual mechanical
operating mechanism
(general case)
Rotary operating
mechanism
Operat|ng meohan|sm
with pushbutton
Equipotentiality
Terminal or clamp
Socket and plug
(female and male)
Motor
(general symbol)
Current transformer
Changeover make before
break position contact
(limit switch)
Circuit-breaker-isolator
with automatic opening
Switch-disconnector
Control coil
(general symbol)
Instantaneous
overcurrent relay
Overourrent re|ay w|th
adjustab|e short t|me-de|ay
characteristic
Ga|van|oa||y separated
converter
Shielded cable conductors
(e.g. three conductors)
Conductors or corded ca-
bles (e.g. 3 conductors)
Closing contact
Open|ng oontaot
Changeover make before
break position contact
Closing position contact
(limit switch)
Open|ng pos|t|on oontaot
(limit switch)
Overourrent re|ay w|th
short inverse time-delay
characteristic
Overourrent re|ay w|th
long inverse time-delay
characteristic
Overourrent re|ay for earth
fault with short inverse time
characteristic
Fuse
(general symbol)
Connection of conductors
ABB SACE 39
1SDC200012D0202
+
2
Y01
1
XK10
2
> >
> >
>> >
-
Q
>>
XO
XO
1
2
1
A1E
A1I
1
2
XK11
B1I
B1E
PR123/DC
PR122/DC
K51
P
R
1
2
0
/D
C
P
R
1
2
0
/D
C
1
S
D
C
2
0
0
6
2
9
F
0
0
0
1
1
S
D
C
2
0
0
6
3
0
F
0
0
0
1
B1E
B1I
XK11
1
2
A1I
A1E
1
2
1
XO
XO
> >
Q
-
>> >
>>
>>
2
XK10
K51
>
1
Y01
2
+
PR123/DC
PR122/DC
P
R
1
2
0
/D
C
Four-pole circuit-breaker with electronic PR122/DC or PR123/DC trip unit
Three-pole circuit-breaker with electronic PR122/DC or PR123/DC trip unit
Electric wiring diagrams
Circuit-breakers
State of operation
ABB SACE 40
1SDC200012D0202
1
S
D
C
2
0
0
6
3
3
F
0
0
0
1
1
S
D
C
2
0
0
6
3
4
F
0
0
0
1
Motor operator, shunt opening, closing and undervoltage releases
Signalling contacts
Electric wiring diagrams
Circuit-breakers
ABB SACE 41
1SDC200012D0202
1
S
D
C
2
0
0
6
3
5
F
0
0
0
1
1
S
D
C
2
0
0
6
3
6
F
0
0
0
1
Signalling contacts
ABB SACE 42
1SDC200012D0202
PR123/DC
PR122/DC
BUS2
BUS1
PR123/DC
PR122/DC
1
S
D
C
2
0
0
6
3
7
F
0
0
0
1
1
S
D
C
2
0
0
6
3
8
F
0
0
0
1
CAPTION: see note F.
Auxiliary circuits of the PR122/DC and PR123/DC trip units
PR120/D-M communication module
Electric wiring diagrams
Circuit-breakers
ABB SACE 43
1SDC200012D0202
(+)
(+)
(+
)
(-)
(-)
(-
)
PR123/DC
PR122/DC
PR123/DC
PR122/DC
PR123/DC
PR122/DC
BUS2
1
S
D
C
2
0
0
6
3
9
F
0
0
0
1
1
S
D
C
2
0
0
6
4
0
F
0
0
0
1
PR120/K signalling module
PR021/K signalling unit
ABB SACE 44
1SDC200012D0202
1
S
D
C
2
0
0
6
0
5
F
0
0
0
1
1
S
D
C
2
0
0
6
0
6
F
0
0
0
1
Selection of Emax DC
Emax DC circuit-breakers must be selected according to:
1) Type of network;
2) Rated current (Iu);
3) Rated voltage (Ue);
4) Short-circuit current (Icu);
5) Poles;
6) Version (Fixed - F - or Withdrawable - W);
7) Power supply (from the upper or lower terminals).
Plates:
POWER SPP|Y FROM PPER TERMlNA|S
POWER SPP|Y FROM THE |OWER TERMlNA|S
ABB SACE 45
1SDC200012D0202
+
-
L
O
A
D
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
INSULATED
NETWORK
Rated
voltage (Ue)
Ue 500 500V Ue 750V 750V Ue 1000V
POLES 3p 4p 3p 4p 4p
Power supply
from lower
terminals
(Lower Supply)
Front view Front view Front view Front view Front view
3D rear view 3D rear view 3D rear view 3D rear view 3D rear view
Power supply
from upper
terminals
(Upper Supply)
Front view Front view Front view Front view Front view
3D rear view 3D rear view 3D rear view 3D rear view 3D rear view
PR122/DC Q Q Q Q Q
PR123/DC Q Q Q Q Q
ABB SACE 46
1SDC200012D0202
+
-
2
2
L
O
A
D
+ -
LOAD -
LOAD +
+ -
LOAD +
LOAD -
NETWORK WITH
EARTHED
MID-POINT
Rated
voltage (Ue)
Ue 500V 500V Ue 750V 750V Ue 1000V
Poles 3p 4p 4p 4p
Power supply
from lower
terminals
(Lower Supply)
Front view Front view Front view Front view
3D rear view 3D rear view 3D rear view 3D rear view
Power supply
from upper
terminals
(Upper Supply)
Front view Front view Front view Front view
3D rear view 3D rear view 3D rear view 3D rear view
PR123/DC Q Q Q Q
Selection of Emax DC
ABB SACE 47
1SDC200012D0202
The following tables show the possible configurations according to the type of network:
+
-
L
O
A
D
+ -
LOAD -
LOAD +
+ -
LOAD +
LOAD -
NETWORK WITH
EARTHED
NEGATIVE
POLARITY
Rated voltage (Ue) Ue 500
1)
Poles 3p 4p
Power supply
from lower
terminals
(Lower Supply)
Front view Front view
3D rear view 3D rear view
Power supply
from upper
terminals
(Upper Supply)
Front view Front view
3D rear view 3D rear view
PR122/DC Q Q
PR123/DC Q Q
1) For higher voltages, ask ABB SACE
It is necessary to specify the 1SDA068806R1 extracode for the special dedicated configuration with 4 poles.
ABB SACE 48
1SDC200012D0202
+ -
LOAD -
LOAD +
+ -
LOAD +
LOAD -
Selection of Emax DC
Ordering Rules
Fixed circuit-breaker (F)
ABB SACE delivers the circuit-breaker in the standard conguration supplied from lower terminals.
CODE

To change the power supply side from lower terminals to the upper ones, it is necessary to
specify the 1SDA058251R1 extracode.
CODE + 1SDA058251R1

In the case of a network with earthed negative polarity and a four-pole circuit-breaker (4p), it
is always necessary to specify the 1SDA068806R1 extracode
Supplied from lower terminals
CODE + 1SDA068806R1

Supplied from upper terminals
CODE + 1SDA058251R1 + 1SDA068806R1
ABB SACE 49
1SDC200012D0202
+ -
+ -
Withdrawable circuit-breaker (W)
MOVING PART
For the moving part in withdrawable circuit-breakers supplied from lower terminals, it is sufcient to indi-
cate the circuit-breaker code only. The voltage sockets are therefore positioned on the lower terminals.
CODE

If supplied from the upper terminals, it is necessary to have the voltage sockets onto the upper
terminals, specifying the 1SDA058251R1 extracode:
CODE + 1SDA058251R1

In the case of a network with earthed negative polarity and 4p circuit-breaker, the 1SDA068806R1
extracode must be specied in addition in order to have 3 poles in series on the positive pole.
FIXED PART
The conguration of the xed part for Emax DC circuit-breakers must be dened starting with the
xed parts for special applications up to 750/1000V DC and adding the U connection kit:
Power supply from lower terminals

CODE FOR FIXED PART with vertical terminals + 1SDA065169R1
or
CODE FOR FIXED PART with horizontal terminals + 1SDA067149R1

Power supply from upper terminals
CODE FOR FIXED PART with vertical terminals + 1SDA065619R1
or
CODE FOR FIXED PART with horizontal terminals + 1SDA067150R1

In the case of a network with earthed negative polarity and 4p circuit-breaker, the 1SDA068806R1
extracode must be specied in addition in order to have 3 poles in series on the positive pole.
ABB SACE 50
1SDC200012D0202
PR122/DC
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
Ordering codes
Insulated network - Lower power supply
+
-
L
O
A
D
Vertical terminals 1SDA0R1
Size Poles Front view Iu Performance Code
E2
Fixed
F-VR
3p
800 B 64580
1000 B 64581
1250 B 64582
1600
B 64583
N 64584
4p
800 B 64585
1000 B 64586
1250 B 64587
1600
B 64588
N 64589
E3
Fixed
F-VR
3p
800 N 64600
1000 N 64601
1250 N 64602
1600
N 64603
H 64606
2000
N 64604
H 64607
2500
N 64605
H 64608
4p
800 N 64609
1000 N 64610
1250 N 64611
1600
N 64612
H 64615
2000
N 64613
H 64616
2500
N 64614
H 64617
E4
Fixed
F-VR
3p
1600 S 64636
2000 S 64637
2500 S 64638
3200
S 64639
H 64640
4p
1600 S 64641
2000 S 64642
2500 S 64643
3200
S 64644
H 64645
E6
Fixed
F-VR
3p
3200 H 64656
4000 H 64657
5000 H 64658
4p
3200 H 64659
4000 H 64660
5000 H 64661
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
Ordering codes
Insulated network - Lower power supply
ABB SACE 51
1SDC200012D0 02 2
+
-
L
O
A
D
PR123/DC
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
Vertical terminals 1SDA0R1
Size Poles Front view Iu Performance Code
E2
Fixed
F-VR
3p
800 B 64668
1000 B 64669
1250 B 64670
1600
B 64671
N 64672
4p
800 B 64673
1000 B 64674
1250 B 64675
1600
B 64676
N 64677
E3
Fixed
F-VR
3p
800 N 64688
1000 N 64689
1250 N 64690
1600
N 64691
H 64694
2000
N 64692
H 64695
2500
N 64693
H 64696
4p
800 N 64697
1000 N 64698
1250 N 64699
1600
N 64700
H 64703
2000
N 64701
H 64704
2500
N 64702
H 64705
E4
Fixed
F-VR
3p
1600 S 64724
2000 S 64725
2500 S 64726
3200
S 64727
H 64728
4p
1600 S 64729
2000 S 64730
2500 S 64731
3200
S 64732
H 64733
E6
Fixed
F-VR
3p
3200 H 64744
4000 H 64745
5000 H 64746
4p
3200 H 64747
4000 H 64748
5000 H 64749
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
ABB SACE 52
1SDC200012D0202
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
PR122/DC
+ -
LOAD +
LOAD -
+
-
L
O
A
D
Vertical terminals 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode
E2
Fixed
F-VR
3p
800 B 64580
+ 58251
1000 B 64581
1250 B 64582
1600
B 64583
N 64584
4p
800 B 64585
+ 58251
1000 B 64586
1250 B 64587
1600
B 64588
N 64589
E3
Fixed
F-VR
3p
800 N 64600
+ 58251
1000 N 64601
1250 N 64602
1600
N 64603
H 64606
2000
N 64604
H 64607
2500
N 64605
H 64608
4p
800 N 64609
+ 58251
1000 N 64610
1250 N 64611
1600
N 64612
H 64615
2000
N 64613
H 64616
2500
N 64614
H 64617
E4
Fixed
F-VR
3p
1600 S 64636
+ 58251
2000 S 64637
2500 S 64638
3200
S 64639
H 64640
4p
1600 S 64641
+ 58251
2000 S 64642
2500 S 64643
3200
S 64644
H 64645
E6
Fixed
F-VR
3p
3200 H 64656
+ 58251 4000 H 64657
5000 H 64658
4p
3200 H 64659
+ 58251 4000 H 64660
H 64661
Ordering codes
Insulated network - Upper power supply
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
ABB SACE 53
1SDC200012D0202
+
-
L
O
A
D
PR123/DC
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
Vertical terminals 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode
E2
Fixed
F-VR
3p
800 B 64668
+ 58251
1000 B 64669
1250 B 64670
1600
B 64671
N 64672
4p
800 B 64673
+ 58251
1000 B 64674
1250 B 64675
1600
B 64676
N 64677
E3
Fixed
F-VR
3p
800 N 64688
+ 58251
1000 N 64689
1250 N 64690
1600
N 64691
H 64694
2000
N 64692
H 64695
2500
N 64693
H 64696
4p
800 N 64697
+ 58251
1000 N 64698
1250 N 64699
1600
N 64700
H 64703
2000
N 64701
H 64704
2500
N 64702
H 64705
E4
Fixed
F-VR
3p
1600 S 64724
+ 58251
2000 S 64725
2500 S 64726
3200
S 64727
H 64728
4p
1600 S 64729
+ 58251
2000 S 64730
2500 S 64731
3200
S 64732
H 64733
E6
Fixed
F-VR
3p
3200 H 64744
+ 58251 4000 H 64745
5000 H 64746
4p
3200 H 64747
+ 58251 4000 H 64748
H 64749
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
ABB SACE 54
1SDC200012D0202
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
PR122/DC
+
-
L
O
A
D
Vertical terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code Code + Extracode
E2
Withdrawable
W-VR
3p
800 B 64590
59895 + 65169
1000 B 64591
1250 B 64592
1600
B 64593
N 64594
4p
800 B 64595
59906 + 65169
1000 B 64596
1250 B 64597
1600
B 64598
N 64599
E3
Withdrawable
W-VR
3p
800 N 64618
59896 + 65169
1000 N 64619
1250 N 64620
1600
N 64621
H 64624
2000
N 64622
H 64625
2500
N 64623
H 64626
4p
800 N 64627
59907 + 65169
1000 N 64628
1250 N 62629
1600
N 64630
H 64633
2000
N 64631
H 64634
2500
N 64632
H 64635
E4
Withdrawable
W-VR
3p
1600 S 64646
59897 + 65169
2000 S 64647
2500 S 64648
3200
S 64649
H 64650
4p
1600 S 64651
59137 + 65169
2000 S 64652
2500 S 64653
3200
S 64654
H 64655
E6
Withdrawable
W-VR
3p
3200 H 64662
59140 + 65169 4000 H 64663
5000 H 64664
4p
3200 H 64665
59143 + 65169 4000 H 64666
5000 H 64667
Ordering codes
Insulated network - Lower power supply
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
ABB SACE 55
1SDC200012D0202
PR123/DC
+
-
L
O
A
D
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
Vertical terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code Code + Extracode
E2
Withdrawable
W-VR
3p
800 B 64678
59895 + 65169
1000 B 64679
1250 B 64680
1600
B 64681
N 64682
4p
800 B 64683
59906 + 65169
1000 B 64684
1250 B 64685
1600
B 64686
N 64687
E3
Withdrawable
W-VR
3p
800 N 64706
59896 + 65169
1000 N 64707
1250 N 64708
1600
N 64709
H 64712
2000
N 64710
H 64713
2500
N 64711
H 64714
4p
800 N 64715
59907 + 65169
1000 N 64716
1250 N 64717
1600
N 64718
H 64721
2000
N 64719
H 64722
2500
N 64720
H 64723
E4
Withdrawable
W-VR
3p
1600 S 64734
59897 + 65169
2000 S 64735
2500 S 64736
3200
S 64737
H 64738
4p
1600 S 64739
59137 + 65169
2000 S 64740
2500 S 64741
3200
S 64742
H 64743
E6
Withdrawable
W-VR
3p
3200 H 64750
59140 + 65169 4000 H 64751
5000 H 64752
4p
3200 H 64753
59143 + 65169 4000 H 64754
5000 H 64755
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
ABB SACE 56
1SDC200012D0202
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
PR122/DC
+ -
LOAD +
LOAD -
+
-
L
O
A
D
Vertical terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode
E2
Withdrawable
W-VR
3p
800 B 64590 +
58251 59895 + 65619
1000 B 64591 +
1250 B 64592 +
1600
B 64593 +
N 64594 +
4p
800 B 64595 +
58251 59906 + 65619
1000 B 64596 +
1250 B 64597 +
1600
B 64598 +
N 64599 +
E3
Withdrawable
W-VR
3p
800 N 64618 +
58251 59896 + 65619
1000 N 64619 +
1250 N 64620 +
1600
N 64621 +
H 64624 +
2000
N 64622 +
H 64625 +
2500
N 64623 +
H 64626 +
4p
800 N 64627 +
58251 59907 + 65619
1000 N 64628 +
1250 N 62629 +
1600
N 64630 +
H 64633 +
2000
N 64631 +
H 64634 +
2500
N 64632 +
H 64635 +
E4
Withdrawable
W-VR
3p
1600 S 64646 +
58251 59897 + 65619
2000 S 64647 +
2500 S 64648 +
3200
S 64649 +
H 64650 +
4p
1600 S 64651 +
58251 59137 + 65619
2000 S 64652 +
2500 S 64653 +
3200
S 64654 +
H 64655 +
E6
Withdrawable
W-VR
3p
3200 H 64662 +
58251 59140 + 65619 4000 H 64663 +
5000 H 64664 +
4p
3200 H 64665 +
58251 59143 + 65619 4000 H 64666 +
5000 H 64667 +
Ordering codes
Insulated network - Upper power supply
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
ABB SACE 57
1SDC200012D0202
PR123/DC
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+
-
L
O
A
D
Vertical terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode
E2
Withdrawable
W-VR
3p
800 B 64678 +
58251 59895 + 65619
1000 B 64679 +
1250 B 64680 +
1600
B 64681 +
N 64682 +
4p
800 B 64683 +
58251 59906 + 65619
1000 B 64684 +
1250 B 64685 +
1600
B 64686 +
N 64687 +
E3
Withdrawable
W-VR
3p
800 N 64706 +
58251 59896 + 65619
1000 N 64707 +
1250 N 64708 +
1600
N 64709 +
H 64712 +
2000
N 64710 +
H 64713 +
2500
N 64711 +
H 64714 +
4p
800 N 64715 +
58251 59907 + 65619
1000 N 64716 +
1250 N 64717 +
1600
N 64718 +
H 64721 +
2000
N 64719 +
H 64722 +
2500
N 64720 +
H 64723 +
E4
Withdrawable
W-VR
3p
1600 S 64734 +
58251 59897 + 65619
2000 S 64735 +
2500 S 64736 +
3200
S 64737 +
H 64738 +
4p
1600 S 64739 +
58251 59137 + 65619
2000 S 64740 +
2500 S 64741 +
3200
S 64742 +
H 64743 +
E6
Withdrawable
W-VR
3p
3200 H 64750 +
58251 59140 + 65619 4000 H 64751 +
5000 H 64752 +
4p
3200 H 64753 +
58251 59143 + 65619 4000 H 64754 +
5000 H 64755 +
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
ABB SACE 58
1SDC200012D0202
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
PR122/DC
+
-
L
O
A
D
Ordering codes
Insulated network - Lower power supply
Horizontal terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code Code + Extracode
E2
Withdrawable
W-HR
3p
800 B 64590
59891 + 67149
1000 B 64591
1250 B 64592
1600
B 64593
N 64594
4p
800 B 64595
59903 + 67149
1000 B 64596
1250 B 64597
1600
B 64598
N 64599
E3
Withdrawable
W-HR
3p
800 N 64618
59892 + 67149
1000 N 64619
1250 N 64620
1600
N 64621
H 64624
2000
N 64622
H 64625
2500
N 64623
H 64626
4p
800 N 64627
59904 + 67149
1000 N 64628
1250 N 62629
1600
N 64630
H 64633
2000
N 64631
H 64634
2500
N 64632
H 64635
E4
Withdrawable
W-HR
3p
1600 S 64646
59893 + 67149
2000 S 64647
2500 S 64648
3200
S 64649
H 64650
4p
1600 S 64651
59136 + 67149
2000 S 64652
2500 S 64653
3200
S 64654
H 64655
E6
Withdrawable
W-HR
3p
3200 H 64662
59139 + 67149 4000 H 64663
5000 H 64664
4p
3200 H 64665
59142 + 67149 4000 H 64666
5000 H 64667
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
ABB SACE 59
1SDC200012D0202
+
-
L
O
A
D
PR123/DC
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
Horizontal terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code Code + Extracode
E2
Withdrawable
W-HR
3p
800 B 64678
59891 + 67149
1000 B 64679
1250 B 64680
1600
B 64681
N 64682
4p
800 B 64683
59903 + 67149
1000 B 64684
1250 B 64685
1600
B 64686
N 64687
E3
Withdrawable
W-HR
3p
800 N 64706
59892 + 67149
1000 N 64707
1250 N 64708
1600
N 64709
H 64712
2000
N 64710
H 64713
2500
N 64711
H 64714
4p
800 N 64715
59904 + 67149
1000 N 64716
1250 N 64717
1600
N 64718
H 64721
2000
N 64719
H 64722
2500
N 64720
H 64723
E4
Withdrawable
W-HR
3p
1600 S 64734
59893 + 67149
2000 S 64735
2500 S 64736
3200
S 64737
H 64738
4p
1600 S 64739
59136 + 67149
2000 S 64740
2500 S 64741
3200
S 64742
H 64743
E6
Withdrawable
W-HR
3p
3200 H 64750
59139 + 67149 4000 H 64751
5000 H 64752
4p
3200 H 64753
59142 + 67149 4000 H 64754
5000 H 64755
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
ABB SACE 60
1SDC200012D0202
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
PR122/DC
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+
-
L
O
A
D
Ordering codes
Insulated network - Upper power supply
Horizontal terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode
E2
Withdrawable
W-HR
3p
800 B 64590 +
58251 59891 + 67150
1000 B 64591 +
1250 B 64592 +
1600
B 64593 +
N 64594 +
4p
800 B 64595 +
58251 59903 + 67150
1000 B 64596 +
1250 B 64597 +
1600
B 64598 +
N 64599 +
E3
Withdrawable
W-HR
3p
800 N 64618 +
58251 59892 + 67150
1000 N 64619 +
1250 N 64620 +
1600
N 64621 +
H 64624 +
2000
N 64622 +
H 64625 +
2500
N 64623 +
H 64626 +
4p
800 N 64627 +
58251 59904 + 67150
1000 N 64628 +
1250 N 62629 +
1600
N 64630 +
H 64633 +
2000
N 64631 +
H 64634 +
2500
N 64632 +
H 64635 +
E4
Withdrawable
W-HR
3p
1600 S 64646 +
58251 59893 + 67150
2000 S 64647 +
2500 S 64648 +
3200
S 64649 +
H 64650 +
4p
1600 S 64651 +
58251 59136 + 67150
2000 S 64652 +
2500 S 64653 +
3200
S 64654 +
H 64655 +
E6
Withdrawable
W-HR
3p
3200 H 64662 +
58251 59139 + 67150 4000 H 64663 +
5000 H 64664 +
4p
3200 H 64665 +
58251 59142 + 67150 4000 H 64666 +
5000 H 64667 +
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
ABB SACE 61
1SDC200012D0202
PR123/DC
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+
-
L
O
A
D
Horizontal terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode
E2
Withdrawable
W-HR
3p
800 B 64678 +
58251 59891 + 67150
1000 B 64679 +
1250 B 64680 +
1600
B 64681 +
N 64682 +
4p
800 B 64683 +
58251 59903 + 67150
1000 B 64684 +
1250 B 64685 +
1600
B 64686 +
N 64687 +
E3
Withdrawable
W-HR
3p
800 N 64706 +
58251 59892 + 67150
1000 N 64707 +
1250 N 64708 +
1600
N 64709 +
H 64712 +
2000
N 64710 +
H 64713 +
2500
N 64711 +
H 64714 +
4p
800 N 64715 +
58251 59904 + 67150
1000 N 64716 +
1250 N 64717 +
1600
N 64718 +
H 64721 +
2000
N 64719 +
H 64722 +
2500
N 64720 +
H 64723 +
E4
Withdrawable
W-HR
3p
1600 S 64734 +
58251 59893 + 67150
2000 S 64735 +
2500 S 64736 +
3200
S 64737 +
H 64738 +
4p
1600 S 64739 +
58251 59136 + 67150
2000 S 64740 +
2500 S 64741 +
3200
S 64742 +
H 64743 +
E6
Withdrawable
W-HR
3p
3200 H 64750 +
58251 59139 + 67150 4000 H 64751 +
5000 H 64752 +
4p
3200 H 64753 +
58251 59142 + 67150 4000 H 64754 +
5000 H 64755 +
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
ABB SACE 62
1SDC200012D0202
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+
-
2
2
L
O
A
D
Ordering codes
Network mid-point earthed - Lower power supply
Vertical terminals 1SDA0R1
Size Poles Front view Iu Performance Code
E2
Fixed
F-VR
3p
800 B 64668
1000 B 64669
1250 B 64670
1600
B 64671
N 64672
4p
800 B 64673
1000 B 64674
1250 B 64675
1600
B 64676
N 64677
E3
Fixed
F-VR
3p
800 N 64688
1000 N 64689
1250 N 64690
1600
N 64691
H 64694
2000
N 64692
H 64695
2500
N 64693
H 64696
4p
800 N 64697
1000 N 64698
1250 N 64699
1600
N 64700
H 64703
2000
N 64701
H 64704
2500
N 64702
H 64705
E4
Fixed
F-VR
3p
1600 S 64724
2000 S 64725
2500 S 64726
3200
S 64727
H 64728
4p
1600 S 64729
2000 S 64730
2500 S 64731
3200
S 64732
H 64733
E6
Fixed
F-VR
3p
3200 H 64744
4000 H 64745
5000 H 64746
4p
3200 H 64747
4000 H 64748
5000 H 64749
PR123/DC
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
ABB SACE 63
1SDC200012D0202
+
-
2
2
L
O
A
D
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
PR123/DC
Vertical terminals 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode
E2
Fixed
F-VR
3p
800 B 64668 +
58251
1000 B 64669 +
1250 B 64670 +
1600
B 64671 +
N 64672 +
4p
800 B 64673 +
58251
1000 B 64674 +
1250 B 64675 +
1600
B 64676 +
N 64677 +
E3
Fixed
F-VR
3p
800 N 64688 +
58251
1000 N 64689 +
1250 N 64690 +
1600
N 64691 +
H 64694 +
2000
N 64692 +
H 64695 +
2500
N 64693 +
H 64696 +
4p
800 N 64697 +
58251
1000 N 64698 +
1250 N 64699 +
1600
N 64700 +
H 64703 +
2000
N 64701 +
H 64704 +
2500
N 64702 +
H 64705 +
E4
Fixed
F-VR
3p
1600 S 64724 +
58251
2000 S 64725 +
2500 S 64726 +
3200
S 64727 +
H 64728 +
4p
1600 S 64729 +
58251
2000 S 64730 +
2500 S 64731 +
3200
S 64732 +
H 64733 +
E6
Fixed
F-VR
3p
3200 H 64744 +
58251 4000 H 64745 +
5000 H 64746 +
4p
3200 H 64747 +
58251 4000 H 64748 +
5000 H 64749 +
Ordering codes
Network mid-point earthed - Upper power supply
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
ABB SACE 64
1SDC200012D0202
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+
-
2
2
L
O
A
D
PR123/DC
Vertical terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code Code + Extracode
E2
Withdrawable
W-VR
3p
800 B 64678
59895 + 65169
1000 B 64679
1250 B 64680
1600
B 64681
N 64682
4p
800 B 64683
59906 + 65169
1000 B 64684
1250 B 64685
1600
B 64686
N 64687
E3
Withdrawable
W-VR
3p
800 N 64706
59896 + 65169
1000 N 64707
1250 N 64708
1600
N 64709
H 64712
2000
N 64710
H 64713
2500
N 64711
H 64714
4p
800 N 64715
59907 + 65169
1000 N 64716
1250 N 64717
1600
N 64718
H 64721
2000
N 64719
H 64722
2500
N 64720
H 64723
E4
Withdrawable
W-VR
3p
1600 S 64734
59897 + 65169
2000 S 64735
2500 S 64736
3200
S 64737
H 64738
4p
1600 S 64739
59137 + 65169
2000 S 64740
2500 S 64741
3200
S 64742
H 64743
E6
Withdrawable
W-VR
3p
3200 H 64750
59140 + 65169 4000 H 64751
5000 H 64752
4p
3200 H 64753
59143 + 65169 4000 H 64754
5000 H 64755
Ordering codes
Network mid-point earthed - Lower power supply
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
ABB SACE 65
1SDC200012D0202
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
PR123/DC
+
-
2
2
L
O
A
D
Vertical terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode
E2
Withdrawable
W-VR
3p
800 B 64678 +
58251 59895 + 65619
1000 B 64679 +
1250 B 64680 +
1600
B 64681 +
N 64682 +
4p
800 B 64683 +
58251 59906 + 65619
1000 B 64684 +
1250 B 64685 +
1600
B 64686 +
N 64687 +
E3
Withdrawable
W-VR
3p
800 N 64706 +
58251 59896 + 65619
1000 N 64707 +
1250 N 64708 +
1600
N 64709 +
H 64712 +
2000
N 64710 +
H 64713 +
2500
N 64711 +
H 64714 +
4p
800 N 64715 +
58251 59907 + 65619
1000 N 64716 +
1250 N 64717 +
1600
N 64718 +
H 64721 +
2000
N 64719 +
H 64722 +
2500
N 64720 +
H 64723 +
E4
Withdrawable
W-VR
3p
1600 S 64734 +
58251 59897 + 65619
2000 S 64735 +
2500 S 64736 +
3200
S 64737 +
H 64738 +
4p
1600 S 64739 +
58251 59137 + 65619
2000 S 64740 +
2500 S 64741 +
3200
S 64742 +
H 64743 +
E6
Withdrawable
W-VR
3p
3200 H 64750 +
58251 59140 + 65619 4000 H 64751 +
5000 H 64752 +
4p
3200 H 64753 +
58251 59143 + 65619 4000 H 64754 +
5000 H 64755 +
Ordering codes
Network mid-point earthed - Upper power supply
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
ABB SACE 66
1SDC200012D0202
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+
-
2
2
L
O
A
D
PR123/DC
Vertical terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code Code + Extracode
E2
Withdrawable
W-HR
3p
800 B 64678
59891 + 67149
1000 B 64679
1250 B 64680
1600
B 64681
N 64682
4p
800 B 64683
59903 + 67149
1000 B 64684
1250 B 64685
1600
B 64686
N 64687
E3
Withdrawable
W-HR
3p
800 N 64706
59892 + 67149
1000 N 64707
1250 N 64708
1600
N 64709
H 64712
2000
N 64710
H 64713
2500
N 64711
H 64714
4p
800 N 64715
59904 + 67149
1000 N 64716
1250 N 64717
1600
N 64718
H 64721
2000
N 64719
H 64722
2500
N 64720
H 64723
E4
Withdrawable
W-HR
3p
1600 S 64734
59893 + 67149
2000 S 64735
2500 S 64736
3200
S 64737
H 64738
4p
1600 S 64739
59136 + 67149
2000 S 64740
2500 S 64741
3200
S 64742
H 64743
E6
Withdrawable
W-HR
3p
3200 H 64750
59139 + 67149 4000 H 64751
5000 H 64752
4p
3200 H 64753
59142 + 67149 4000 H 64754
5000 H 64755
Ordering codes
Network mid-point earthed - Lower power supply
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
ABB SACE 67
1SDC200012D0202
+
-
2
2
L
O
A
D
PR123/DC
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
Vertical terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode
E2
Withdrawable
W-HR
3p
800 B 64678 +
58251 59891 + 67150
1000 B 64679 +
1250 B 64680 +
1600
B 64681 +
N 64682 +
4p
800 B 64683 +
58251 59903 + 67150
1000 B 64684 +
1250 B 64685 +
1600
B 64686 +
N 64687 +
E3
Withdrawable
W-HR
3p
800 N 64706 +
58251 59892 + 67150
1000 N 64707 +
1250 N 64708 +
1600
N 64709 +
H 64712 +
2000
N 64710 +
H 64713 +
2500
N 64711 +
H 64714 +
4p
800 N 64715 +
58251 59904 + 67150
1000 N 64716 +
1250 N 64717 +
1600
N 64718 +
H 64721 +
2000
N 64719 +
H 64722 +
2500
N 64720 +
H 64723 +
E4
Withdrawable
W-HR
3p
1600 S 64734 +
58251 59893 + 67150
2000 S 64735 +
2500 S 64736 +
3200
S 64737 +
H 64738 +
4p
1600 S 64739 +
58251 59136 + 67150
2000 S 64740 +
2500 S 64741 +
3200
S 64742 +
H 64743 +
E6
Withdrawable
W-HR
3p
3200 H 64750 +
58251 59139 + 67150 4000 H 64751 +
5000 H 64752 +
4p
3200 H 64753 +
58251 59142 + 67150 4000 H 64754 +
5000 H 64755 +
Ordering codes
Network mid-point earthed - Upper power supply
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe1000V PR120/V
ABB SACE 68
1SDC200012D0202
+
-
L
O
A
D
PR122/DC
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
Ordering codes
Network with earthed negative polarity -
Lower power supply
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
Vertical terminals 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode
E2
Fixed
F-VR
3p
800 B 64580 +
-
1000 B 64581 +
1250 B 64582 +
1600
B 64583 +
N 64584 +
4p
800 B 64585 +
68806
1000 B 64586 +
1250 B 64587 +
1600
B 64588 +
N 64589 +
E3
Fixed
F-VR
3p
800 N 64600 +
-
1000 N 64601 +
1250 N 64602 +
1600
N 64603 +
H 64606 +
2000
N 64604 +
H 64607 +
2500
N 64605 +
H 64608 +
4p
800 N 64609 +
68806
1000 N 64610 +
1250 N 64611 +
1600
N 64612 +
H 64615 +
2000
N 64613 +
H 64616 +
2500
N 64614 +
H 64617 +
E4
Fixed
F-VR
3p
1600 S 64636 +
-
2000 S 64637 +
2500 S 64638 +
3200
S 64639 +
H 64640 +
4p
1600 S 64641 +
68806
2000 S 64642 +
2500 S 64643 +
3200
S 64644 +
H 64645 +
E6
Fixed
F-VR
3p
3200 H 64656 +
- 4000 H 64657 +
5000 H 64658 +
4p
3200 H 64659 +
68806 4000 H 64660 +
5000 H 64661 +
ABB SACE 69
1SDC200012D0202
+
-
L
O
A
D
PR123/DC
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
Vertical terminals 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode
E2
Fixed
F-VR
3p
800 B 64668 +
-
1000 B 64669 +
1250 B 64670 +
1600
B 64671 +
N 64672 +
4p
800 B 64673 +
68806
1000 B 64674 +
1250 B 64675 +
1600
B 64676 +
N 64677 +
E3
Fixed
F-VR
3p
800 N 64688 +
-
1000 N 64689 +
1250 N 64690 +
1600
N 64691 +
H 64694 +
2000
N 64692 +
H 64695 +
2500
N 64693 +
H 64696 +
4p
800 N 64697 +
68806
1000 N 64698 +
1250 N 64699 +
1600
N 64700 +
H 64703 +
2000
N 64701 +
H 64704 +
2500
N 64702 +
H 64705 +
E4
Fixed
F-VR
3p
1600 S 64724 +
-
2000 S 64725 +
2500 S 64726 +
3200
S 64727 +
H 64728 +
4p
1600 S 64729 +
68806
2000 S 64730 +
2500 S 64731 +
3200
S 64732 +
H 64733 +
E6
Fixed
F-VR
3p
3200 H 64744 +
- 4000 H 64745 +
5000 H 64746 +
4p
3200 H 64747 +
68806 4000 H 64748 +
5000 H 64749 +
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
ABB SACE 70
1SDC200012D0202
+
-
L
O
A
D
PR122/DC
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
Ordering codes
Network with earthed negative polarity -
Upper power supply
Vertical terminals 1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode + Extracode
E2
Fixed
F-VR
3p
800 B 64580 +
58251
+
-
1000 B 64581 + +
1250 B 64582 + +
1600
B 64583 + +
N 64584 + +
4p
800 B 64585 +
58251
+
68806
1000 B 64586 + +
1250 B 64587 + +
1600
B 64588 + +
N 64589 + +
E3
Fixed
F-VR
3p
800 N 64600 +
58251
+
-
1000 N 64601 + +
1250 N 64602 + +
1600
N 64603 + +
H 64606 + +
2000
N 64604 + +
H 64607 + +
2500
N 64605 + +
H 64608 + +
4p
800 N 64609 +
58251
+
68806
1000 N 64610 + +
1250 N 64611 + +
1600
N 64612 + +
H 64615 + +
2000
N 64613 + +
H 64616 + +
2500
N 64614 + +
H 64617 + +
E4
Fixed
F-VR
3p
1600 S 64636 +
58251
+
-
2000 S 64637 + +
2500 S 64638 + +
3200
S 64639 + +
H 64640 + +
4p
1600 S 64641 +
58251
+
68806
2000 S 64642 + +
2500 S 64643 + +
3200
S 64644 + +
H 64645 + +
E6
Fixed
F-VR
3p
3200 H 64656 +
58251
+
- 4000 H 64657 + +
5000 H 64658 + +
4p
3200 H 64659 +
58251
+
68806 4000 H 64660 + +
5000 H 64661 + +
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
ABB SACE 71
1SDC200012D0202
+
-
L
O
A
D
PR123/DC
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
Vertical terminals 1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode + Extracode
E2
Fixed
F-VR
3p
800 B 64668 +
58251
+
-
1000 B 64669 + +
1250 B 64670 + +
1600
B 64671 + +
N 64672 + +
4p
800 B 64673 +
58251
+
68806
1000 B 64674 + +
1250 B 64675 + +
1600
B 64676 + +
N 64677 + +
E3
Fixed
F-VR
3p
800 N 64688 +
58251
+
-
1000 N 64689 + +
1250 N 64690 + +
1600
N 64691 + +
H 64694 + +
2000
N 64692 + +
H 64695 + +
2500
N 64693 + +
H 64696 + +
4p
800 N 64697 +
58251
+
68806
1000 N 64698 + +
1250 N 64699 + +
1600
N 64700 + +
H 64703 + +
2000
N 64701 + +
H 64704 + +
2500
N 64702 + +
H 64705 + +
E4
Fixed
F-VR
3p
1600 S 64724 +
58251
+
-
2000 S 64725 + +
2500 S 64726 + +
3200
S 64727 + +
H 64728 + +
4p
1600 S 64729 +
58251
+
68806
2000 S 64730 + +
2500 S 64731 + +
3200
S 64732 + +
H 64733 + +
E6
Fixed
F-VR
3p
3200 H 64744 +
58251
+
- 4000 H 64745 + +
5000 H 64746 + +
4p
3200 H 64747 +
58251
+
68806 4000 H 64748 + +
5000 H 64749 + +
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
ABB SACE 72
1SDC200012D0202
+
-
L
O
A
D
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
PR122/DC
Ordering codes
Network with earthed negative polarity -
Lower power supply
Vertical terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode + Extracode
E2
Withdrawable
W-VR
3p
800 B 64590 +
- 59895 + 65169 + -
1000 B 64591 +
1250 B 64592 +
1600
B 64593 +
N 64594 +
4p
800 B 64595 +
68806 59906 + 65169 + 68806
1000 B 64596 +
1250 B 64597 +
1600
B 64598 +
N 64599 +
E3
Withdrawable
W-VR
3p
800 N 64618 +
- 59896 + 65169 + -
1000 N 64619 +
1250 N 64620 +
1600
N 64621 +
H 64624 +
2000
N 64622 +
H 64625 +
2500
N 64623 +
H 64626 +
4p
800 N 64627 +
68806 59907 + 65169 + 68806
1000 N 64628 +
1250 N 62629 +
1600
N 64630 +
H 64633 +
2000
N 64631 +
H 64634 +
2500
N 64632 +
H 64635 +
E4
Withdrawable
W-VR
3p
1600 S 64646 +
- 59897 + 65169 + -
2000 S 64647 +
2500 S 64648 +
3200
S 64649 +
H 64650 +
4p
1600 S 64651 +
68806 59137 + 65169 + 68806
2000 S 64652 +
2500 S 64653 +
3200
S 64654 +
H 64655 +
E6
Withdrawable
W-VR
3p
3200 H 64662 +
- 59140 + 65169 + - 4000 H 64663 +
5000 H 64664 +
4p
3200 H 64665 +
68806 59143 + 65169 + 68806 4000 H 64666 +
5000 H 64667 +
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
ABB SACE 73
1SDC200012D0202
+
-
L
O
A
D
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
PR123/DC
Vertical terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode + Extracode
E2
Withdrawable
W-VR
3p
800 B 64678 +
- 59895 + 65169 + -
1000 B 64679 +
1250 B 64680 +
1600
B 64681 +
N 64682 +
4p
800 B 64683 +
68806 59906 + 65169 + 68806
1000 B 64684 +
1250 B 64685 +
1600
B 64686 +
N 64687 +
E3
Withdrawable
W-VR
3p
800 N 64706 +
- 59896 + 65169 + -
1000 N 64707 +
1250 N 64708 +
1600
N 64709 +
H 64712 +
2000
N 64710 +
H 64713 +
2500
N 64711 +
H 64714 +
4p
800 N 64715 +
68806 59907 + 65169 + 68806
1000 N 64716 +
1250 N 64717 +
1600
N 64718 +
H 64721 +
2000
N 64719 +
H 64722 +
2500
N 64720 +
H 64723 +
E4
Withdrawable
3p
1600 S 64734 +
- 59897 + 65169 + -
2000 S 64735 +
2500 S 64736 +
3200
S 64737 +
H 64738 +
4p
1600 S 64739 +
68806 59137 + 65169 + 68806
2000 S 64740 +
2500 S 64741 +
3200
S 64742 +
H 64743 +
E6
Withdrawable
W-VR
3p
3200 H 64750 +
- 59140 + 65169 + - 4000 H 64751 +
5000 H 64752 +
4p
3200 H 64753 +
68806 59143 + 65169 + 68806 4000 H 64754 +
5000 H 64755 +
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
W-VR
ABB SACE 74
1SDC200012D0202
+
-
L
O
A
D
+ -
LOAD +
LOAD -
PR122/DC
Ordering codes
Network with earthed negative polarity -
Upper power supply
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
Vertical terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode + Extracode Code + Extracode + Extracode
E2
Withdrawable
W-VR
3p
800 B 64590 +
58251
+
- 59895 + 65619 + -
1000 B 64591 + +
1250 B 64592 + +
1600
B 64593 + +
N 64594 + +
4p
800 B 64595 +
58251
+
68806 59906 + 65619 + 68806
1000 B 64596 + +
1250 B 64597 + +
1600
B 64598 + +
N 64599 + +
E3
Withdrawable
W-VR
3p
800 N 64618 +
58251
+
- 59896 + 65619 + -
1000 N 64619 + +
1250 N 64620 + +
1600
N 64621 + +
H 64624 + +
2000
N 64622 + +
H 64625 + +
2500
N 64623 + +
H 64626 + +
4p
800 N 64627 +
58251
+
68806 59907 + 65619 + 68806
1000 N 64628 + +
1250 N 62629 + +
1600
N 64630 + +
H 64633 + +
2000
N 64631 + +
H 64634 + +
2500
N 64632 + +
H 64635 + +
E4
Withdrawable
W-VR
3p
1600 S 64646 +
58251
+
- 59897 + 65619 + -
2000 S 64647 + +
2500 S 64648 + +
3200
S 64649 + +
H 64650 + +
4p
1600 S 64651 +
58251
+
68806 59137 + 65619 + 68806
2000 S 64652 + +
2500 S 64653 + +
3200
S 64654 + +
H 64655 + +
E6
Withdrawable
W-VR
3p
3200 H 64662 +
58251
+
- 59140 + 65619 + - 4000 H 64663 + +
5000 H 64664 + +
4p
3200 H 64665 +
58251
+
68806 59143 + 65619 + 68806 4000 H 64666 + +
5000 H 64667 + +
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
ABB SACE 75
1SDC200012D0202
+
-
L
O
A
D
PR123/DC
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
Vertical terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode + Extracode Code + Extracode + Extracode
E2
Withdrawable
W-VR
3p
800 B 64678 +
58251
+
- 59895 + 65619 + -
1000 B 64679 + +
1250 B 64680 + +
1600
B 64681 + +
N 64682 + +
4p
800 B 64683 +
58251
+
68806 59906 + 65619 + 68806
1000 B 64684 + +
1250 B 64685 + +
1600
B 64686 + +
N 64687 + +
E3
Withdrawable
W-VR
3p
800 N 64706 +
58251
+
- 59896 + 65619 + -
1000 N 64707 + +
1250 N 64708 + +
1600
N 64709 + +
H 64712 + +
2000
N 64710 + +
H 64713 + +
2500
N 64711 + +
H 64714 + +
4p
800 N 64715 +
58251
+
68806 59907 + 65619 + 68806
1000 N 64716 + +
1250 N 64717 + +
1600
N 64718 + +
H 64721 + +
2000
N 64719 + +
H 64722 + +
2500
N 64720 + +
H 64723 + +
E4
Withdrawable
W-VR
3p
1600 S 64734 +
58251
+
- 59897 + 65619 + -
2000 S 64735 + +
2500 S 64736 + +
3200
S 64737 + +
H 64738 + +
4p
1600 S 64739 +
58251
+
68806 59137 + 65619 + 68806
2000 S 64740 + +
2500 S 64741 + +
3200
S 64742 + +
H 64743 + +
E6
Withdrawable
W-VR
3p
3200 H 64750 +
58251
+
- 59140 + 65619 + - 4000 H 64751 + +
5000 H 64752 + +
4p
3200 H 64753 +
58251
+
68806 59143 + 65619 + 68806 4000 H 64754 + +
5000 H 64755 + +
ABB SACE 76
1SDC200012D0202
+
-
L
O
A
D
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
PR122/DC
Ordering codes
Network with earthed negative polarity -
Lower power supply
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
Horizontal terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode + Extracode
E2
Withdrawable
W-HR
3p
800 B 64590 +
- 59891 + 67149 + -
1000 B 64591 +
1250 B 64592 +
1600
B 64593 +
N 64594 +
4p
800 B 64595 +
68806 59903 + 67149 + 68806
1000 B 64596 +
1250 B 64597 +
1600
B 64598 +
N 64599 +
E3
Withdrawable
W-HR
3p
800 N 64618 +
- 59892 + 67149 + -
1000 N 64619 +
1250 N 64620 +
1600
N 64621 +
H 64624 +
2000
N 64622 +
H 64625 +
2500
N 64623 +
H 64626 +
4p
800 N 64627 +
68806 59904 + 67149 + 68806
1000 N 64628 +
1250 N 62629 +
1600
N 64630 +
H 64633 +
2000
N 64631 +
H 64634 +
2500
N 64632 +
H 64635 +
E4
Withdrawable
W-HR
3p
1600 S 64646 +
- 59893 + 67149 + -
2000 S 64647 +
2500 S 64648 +
3200
S 64649 +
H 64650 +
4p
1600 S 64651 +
68806 59136 + 67149 + 68806
2000 S 64652 +
2500 S 64653 +
3200
S 64654 +
H 64655 +
E6
Withdrawable
W-HR
3p
3200 H 64662 +
- 59139 + 67149 + - 4000 H 64663 +
5000 H 64664 +
4p
3200 H 64665 +
68806 59142 + 67149 + 68806 4000 H 64666 +
5000 H 64667 +
ABB SACE 77
1SDC200012D0202
+
-
L
O
A
D
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
PR123/DC
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
Horizontal terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode Code + Extracode + Extracode
E2
Withdrawable
W-HR
3p
800 B 64678 +
- 59891 + 67149 + -
1000 B 64679 +
1250 B 64680 +
1600
B 64681 +
N 64682 +
4p
800 B 64683 +
68806 59903 + 67149 + 68806
1000 B 64684 +
1250 B 64685 +
1600
B 64686 +
N 64687 +
E3
Withdrawable
W-HR
3p
800 N 64706 +
- 59892 + 67149 + -
1000 N 64707 +
1250 N 64708 +
1600
N 64709 +
H 64712 +
2000
N 64710 +
H 64713 +
2500
N 64711 +
H 64714 +
4p
800 N 64715 +
68806 59904 + 67149 + 68806
1000 N 64716 +
1250 N 64717 +
1600
N 64718 +
H 64721 +
2000
N 64719 +
H 64722 +
2500
N 64720 +
H 64723 +
E4
Withdrawable
W-HR
3p
1600 S 64734 +
- 59893 + 67149 + -
2000 S 64735 +
2500 S 64736 +
3200
S 64737 +
H 64738 +
4p
1600 S 64739 +
68806 59136 + 67149 + 68806
2000 S 64740 +
2500 S 64741 +
3200
S 64742 +
H 64743 +
E6
Withdrawable
W-HR
3p
3200 H 64750 +
- 59139 + 67149 + - 4000 H 64751 +
5000 H 64752 +
4p
3200 H 64753 +
68806 59142 + 67149 + 68806 4000 H 64754 +
5000 H 64755 +
ABB SACE 78
1SDC200012D0202
+
-
L
O
A
D
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
PR122/DC
Ordering codes
Network with earthed negative polarity -
Upper power supply
+ -
LOAD +
LOAD -
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
Horizontal terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode + Extracode Code + Extracode + Extracode
E2
Withdrawable
W-HR
3p
800 B 64590 +
58251
+
- 59891 + 67150 + -
1000 B 64591 + +
1250 B 64592 + +
1600
B 64593 + +
N 64594 + +
4p
800 B 64595 +
58251
+
68806 59903 + 67150 + 68806
1000 B 64596 + +
1250 B 64597 + +
1600
B 64598 + +
N 64599 + +
E3
Withdrawable
W-HR
3p
800 N 64618 +
58251
+
- 59892 + 67150 + -
1000 N 64619 + +
1250 N 64620 + +
1600
N 64621 + +
H 64624 + +
2000
N 64622 + +
H 64625 + +
2500
N 64623 + +
H 64626 + +
4p
800 N 64627 +
58251
+
68806 59904 + 67150 + 68806
1000 N 64628 + +
1250 N 62629 + +
1600
N 64630 + +
H 64633 + +
2000
N 64631 + +
H 64634 + +
2500
N 64632 + +
H 64635 + +
E4
Withdrawable
W-HR
3p
1600 S 64646 +
58251
+
- 59893 + 67150 + -
2000 S 64647 + +
2500 S 64648 + +
3200
S 64649 + +
H 64650 + +
4p
1600 S 64651 +
58251
+
68806 59136 + 67150 + 68806
2000 S 64652 + +
2500 S 64653 + +
3200
S 64654 + +
H 64655 + +
E6
Withdrawable
W-HR
3p
3200 H 64662 +
58251
+
- 59139 + 67150 + - 4000 H 64663 + +
5000 H 64664 + +
4p
3200 H 64665 +
58251
+
68806 59142 + 67150 + 68806 4000 H 64666 + +
5000 H 64667 + +
ABB SACE 79
1SDC200012D0202
+
-
L
O
A
D
PR123/DC
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
+ -
LOAD +
LOAD -
1SDA0...R1
Ue
Ue<100V Vaux is compulsory
100VUe250V Specific extracode for PR120/LV 65223
250VUe500V* PR120/V
* For higher voltages, contact ABB
Horizontal terminals
MP Fixed part
1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1 1SDA0R1
Size Poles Front view Iu Performance Code + Extracode + Extracode Code + Extracode + Extracode
E2
Withdrawable
W-HR
3p
800 B 64678 +
58251
+
- 59891 + 67150 + -
1000 B 64679 + +
1250 B 64680 + +
1600
B 64681 + +
N 64682 + +
4p
800 B 64683 +
58251
+
68806 59903 + 67150 + 68806
1000 B 64684 + +
1250 B 64685 + +
1600
B 64686 + +
N 64687 + +
E3
Withdrawable
W-HR
3p
800 N 64706 +
58251
+
- 59892 + 67150 + -
1000 N 64707 + +
1250 N 64708 + +
1600
N 64709 + +
H 64712 + +
2000
N 64710 + +
H 64713 + +
2500
N 64711 + +
H 64714 + +
4p
800 N 64715 +
58251
+
68806 59904 + 67150 + 68806
1000 N 64716 + +
1250 N 64717 + +
1600
N 64718 + +
H 64721 + +
2000
N 64719 + +
H 64722 + +
2500
N 64720 + +
H 64723 + +
E4
Withdrawable
W-HR
3p
1600 S 64734 +
58251
+
- 59893 + 67150 + -
2000 S 64735 + +
2500 S 64736 + +
3200
S 64737 + +
H 64738 + +
4p
1600 S 64739 +
58251
+
68806 59136 + 67150 + 68806
2000 S 64740 + +
2500 S 64741 + +
3200
S 64742 + +
H 64743 + +
E6
Withdrawable
W-HR
3p
3200 H 64750 +
58251
+
- 59139 + 67150 + - 4000 H 64751 + +
5000 H 64752 + +
4p
3200 H 64753 +
58251
+
68806 59142 + 67150 + 68806 4000 H 64754 + +
5000 H 64755 + +
ABB SACE 80
1SDC200012D0202
Ordering codes
SACE Emax switch-disconnectors for applications
up to 1000V DC
1
S
D
C
2
0
0
2
5
9
F
0
0
0
1
1SDA......R1
3 Poles 4 Poles
750V DC 1000V DC
E1B/E MS 08
Fixed (F)
Iu (40 C) = 800 A Icw (1 s) = 20 kA
HR = Horizontal rear terminals 059041 059042
E1B/E MS 12
Fixed (F)
Iu (40 C) = 1250 A Icw (1 s) = 20 kA
HR = Horizontal rear terminals 059043 059044
E1B/E MS 08
Withdrawable (W) - MP
Iu (40 C) = 800 A Icw (1 s) = 20 kA
MP = Moving part 059045 059046
E1B/E MS 12
Withdrawable (W) - MP
Iu (40 C) = 1250 A Icw (1 s) = 20 kA
MP = Moving part 059047 059048
E2N/E MS 12
Fixed (F)
Iu (40 C) = 1250 A Icw (1 s) = 25 kA
HR = Horizontal rear terminals 059049 059050
E2N/E MS 16
Fixed (F)
Iu (40 C) = 1600 A Icw (1 s) = 25 kA
HR = Horizontal rear terminals 059051 059052
E2N/E MS 20
Fixed (F)
Iu (40 C) = 2000 A Icw (1 s) = 25 kA
HR = Horizontal rear terminals 059053 059054
E2N/E MS 12
Withdrawable (W) - MP
Iu (40 C) = 1250 A Icw (1 s) = 25 kA
MP = Moving part 059055 059056
E2N/E MS 16
Withdrawable (W) - MP
Iu (40 C) = 1600 A Icw (1 s) = 25 kA
MP = Moving part 059057 059058
E2N/E MS 20
Withdrawable (W) - MP
Iu (40 C) = 2000 A Icw (1 s) = 25 kA
MP = Moving part 059059 059060
E3H/E MS 12
Fixed (F)
Iu (40 C) = 1250 A Icw (1 s) = 40 kA
HR = Horizontal rear terminals 059061 059062
E3H/E MS 16
Fixed (F)
Iu (40 C) = 1600 A Icw (1 s) = 40 kA
HR = Horizontal rear terminals 059063 059064
E3H/E MS 20
Fixed (F)
Iu (40 C) = 2000 A Icw (1 s) = 40 kA
HR = Horizontal rear terminals 059065 059066
E3H/E MS 25
Fixed (F)
Iu (40 C) = 2500 A Icw (1 s) = 40 kA
HR = Horizontal rear terminals 059067 059068
E3H/E MS 32
Fixed (F)
Iu (40 C) = 3200 A Icw (1 s) = 40 kA
HR = Horizontal rear terminals 059069 059070
E3H/E MS 12
Withdrawable (W) - MP
Iu (40 C) = 1250 A Icw (1 s) = 40 kA
MP = Moving part 059071 059072
E3H/E MS 16
Withdrawable (W) - MP
Iu (40 C) = 1600 A Icw (1 s) = 40 kA
MP = Moving part 059073 059074
E3H/E MS 20
Withdrawable (W) - MP
Iu (40 C) = 2000 A Icw (1 s) = 40 kA
MP = Moving part 059075 059076
E3H/E MS 25
Withdrawable (W) - MP
Iu (40 C) = 2500 A Icw (1 s) = 40 kA
MP = Moving part 059077 059078
E3H/E MS 32
Withdrawable (W) - MP
Iu (40 C) = 3200 A Icw (1 s) = 40 kA
MP = Moving part 059079 059080
E4H/E MS 32
Fixed (F)
Iu (40 C) = 3200 A Icw (1 s) = 65 kA
HR = Horizontal rear terminals 059081 058911
E4H/E MS 40
Fixed (F)
Iu (40 C) = 4000 A Icw (1 s) = 65 kA
HR = Horizontal rear terminals 059082 058913
E4H/E MS 32
Withdrawable (W) - MP
Iu (40 C) = 3200 A Icw (1 s) = 65 kA
MP = Moving part 059083 058912
E4H/E MS 40
Withdrawable (W) - MP
Iu (40 C) = 4000 A Icw (1 s) = 65 kA
MP = Moving part 059084 058914
E6H/E MS 40
Fixed (F)
Iu (40 C) = 4000 A Icw (1 s) = 65 kA
HR = Horizontal rear terminals 058915 058921
E6H/E MS 50
Fixed (F)
Iu (40 C) = 5000 A Icw (1 s) = 65 kA
HR = Horizontal rear terminals 058917 058923
E6H/E MS 63
Fixed (F)
Iu (40 C) = 6300 A Icw (1 s) = 65 kA
HR = Horizontal rear terminals 058919 058925
E6H/E MS 40
Withdrawable (W) - MP
Iu (40 C) = 4000 A Icw (1 s) = 65 kA
MP = Moving part 058916 058922
E6H/E MS 50
Withdrawable (W) - MP
Iu (40 C) = 5000 A Icw (1 s) = 65 kA
MP = Moving part 058918 058924
E6H/E MS 63
Withdrawable (W) - MP
Iu (40 C) = 6300 A Icw (1 s) = 65 kA
MP = Moving part 058920 058926
1
S
D
C
2
0
0
2
6
0
F
0
0
0
1
1
S
D
C
2
0
0
2
6
2
F
0
0
0
1
ABB SACE 81
1SDC200012D0202
Ordering codes
Fixed parts for SACE Emax switch-disconnectors for
applications up to 1000V DC
1SDA......R1
3 Poles 4 Poles
750V DC 1000V DC
E1 MS/E
Withdrawable (W) - FP
FP = Fixed part
HR 059890 059902
VR 059894 059905
FL 059898 059908
E2 MS/E
Withdrawable (W) - FP
FP = Fixed part
HR 059891 059903
VR 059895 059906
FL 059899 059909
E3 MS/E
Withdrawable (W) - FP
FP = Fixed part
HR 059892 059904
VR 059896 059907
FL 059900 059910
E4 MS/E
Withdrawable (W) - FP
FP = Fixed part
HR 059893 059136
VR 059897 059137
FL 059901 059138
E6 MS/E
Withdrawable (W) - FP
FP = Fixed part
HR 059139 059142
VR 059140 059143
FL 059141 059144
HR
VR
FL
ABB SACE 82
1SDC200012D0202
1SDAR1
Ordering codes
SACE Emax DC accessories
Electrical accessories
Undervoltage release - YU (2a)
E2/6 DC 24V DC 038286
E2/6 DC 30V AC / DC 038287
E2/6 DC 48V AC / DC 038288
E2/6 DC 60V AC / DC 038289
E2/6 DC 110...120V AC / DC 038290
E2/6 DC 120127V AC / DC 038291
E2/6 DC 220240V AC / DC 038292
E2/6 DC 240250V AC / DC 038293
E2/6 DC 380400V AC 038294
E2/6 DC 440480V AC 038295
Note: the shunt open|ng YO} and o|os|ng YO} re|eases are oonstruot|ona||y |dent|oa| and therefore |nterohangeab|e. The|r funot|on |s
linked to the assembly position on the circuit-breaker.
Electronic time-delay device for undervoltage release - D (2b)
E2/6 DC 24V DC 050157
E2/6 DC 30V AC / DC 050158
E2/6 DC 48V AC / DC 050159
E2/6 DC 60V AC / DC 050160
E2/6 DC 110...120V AC / DC 050161
E2/6 DC 120127V AC / DC 050162
E2/6 DC 220240V AC / DC 050163
E2/6 DC 240250V AC / DC 050164
E2/6 DC 380400V AC 050165
E2/6 DC 440480V AC 050166
Note: supplied with support for special releases.
Shunt closing release - YC (1a)
E2/6 DC 24V DC 038296
E2/6 DC 30V AC / DC 038297
E2/6 DC 48V AC / DC 038298
E2/6 DC 60V AC / DC 038299
E2/6 DC 110...120V AC / DC 038300
E2/6 DC 120127V AC / DC 038301
E2/6 DC 220240V AC / DC 038302
E2/6 DC 240250V AC / DC 038303
E2/6 DC 380400V AC 038304
E2/6 DC 440480V AC 038305
Note: the shunt open|ng YO} and o|os|ng YO} re|eases are oonstruot|ona||y |dent|oa| and therefore |nterohangeab|e. The|r funot|on |s
linked to the assembly position on the circuit-breaker.
SOR Test Unit - (1b)
E2/6 DC 050228
Undervoltage release - YU (2a)
E2/6 DC 24V DC 038306
E2/6 DC 30V AC / DC 038307
E2/6 DC 48V AC / DC 038308
E2/6 DC 60V AC / DC 038309
E2/6 DC 110...120V AC / DC 038310
E2/6 DC 120127V AC / DC 038311
E2/6 DC 220240V AC / DC 038312
E2/6 DC 240250V AC / DC 038313
E2/6 DC 380400V AC 038314
E2/6 DC 440480V AC 038315
ABB SACE 83
1SDC200012D0202
1SDAR1
Electronic time-delay device for undervoltage release - D (2b)
E2/6 DC 24...30V DC 038316
E2/6 DC 48V AC / DC 038317
E2/6 DC 60V AC / DC 038318
E2/6 DC 110...127V AC / DC 038319
E2/6 DC 220250V AC / DC 038320
Geared motor for automatic charging of the closing springs - M (3)
E2/6 DC 24...30V AC / DC 038321
E2/6 DC 4860V AC / DC 038322
E2/6 DC 100...130V AC / DC 038323
E2/6 DC 220250V AC / DC 038324
Note: it is always supplied with limit contact and microswitch for indication of closing springs charged (accessory 5d)
Overcurrent release trip indication - (4a)
E2/6 DC 058260
Electrical indication of overcurrent release trip by remote control - (4b)
E2/6 DC 220...240V AC/DC 058261
E2/6 DC 110...130V AC/DC 058262
E2/6 DC 24...30V AC/DC 058263
Electrical indication of circuit-breaker open/closed - Q1 ... 10 - (5a)
E2/6 DC - PR122-3/DC 4 aux|||ary oontaots 2NO+2NO+2PR122-3} 068801 (c)
E2/6 DC - PR122-3/DC 4 aux|||ary oontaots 2NO+2NO+2PR122-3} for d|g|ta| s|gna|s 068802
E2/6 DC - PR122-3/DC 10 aux|||ary oontaots 5NO+5NO+2PR122-3 - |nsta||ed} 068803 (a)
E2/6 DC - PR122-3/DC 10 aux|||ary oontaots 5NO+5NO+2PR122-3 - not |nsta||ed} 068804 (b)
E2/6 DC - PR122-3/DC 10 aux|||ary oontaots 5NO+5NO+2PR122-3} for d|g|ta| s|gna|s 068805
Note: (a) Can only be ordered mounted with circuit-breakers.
(b) Can only be ordered loose in the case of circuit-breakers.
(c) Already included for circuit-breakers with PR122/DC and PR123/DC. Can only be ordered as loose accessories.
Additional external electrical indication of circuit-breaker open/closed - Q11 ... 25 - (5b)
E2/6 DC 15 additional auxiliary contacts (version for xed/ withdrawable racked-in) 043475 (a)
E2/6 DC 15 additional auxiliary contacts (version for withdrawable racked-in/ test) 048827
E2/6 DC
15 additional auxiliary contacts for digital signals (version for
xed/withdrawable racked-in)
050145 (a)
E2/6 DC
15 additional auxiliary contacts for digital signals (version for
withdrawable racked-in/ test)
050151
Nota: Outs|de the o|rou|t-breaker. To be requested |n a|ternat|ve to the d|fferent types of |nter|ooks aooessory 10} and to the meohan|oa|
compartment door lock (accessory 8f).
(a) For fixed version, also request the interlock plate (accessory 10.4).
ABB SACE 84
1SDC200012D0202
1SDAR1
3 poles 4 poles
Ordering codes
SACE Emax DC accessories
Electrical indication of circuit-breaker racked-in/isolated test/isolated S75 - (5c)
E2/6 DC 5 auxiliary contacts 038361 038361
E1-E2 10 auxiliary contacts 038360 043467
E3 10 auxiliary contacts 043468 043469
E4-E6 10 auxiliary contacts 043470 043470
E2/6 DC 5 auxiliary contacts for digital signals 050146 050146
E1-E2 10 auxiliary contacts for digital signals 050147 050148
E4-6 10 auxiliary contacts for digital signals 050147 050147
E3 10 auxiliary contacts for digital signals 050149 050150
Signalling contact for closing springs charged S33 M/2- (5d)
E2/6 DC 038325
Note: already supplied with the geared motor for automatic charging of the closing springs.
Contact for signalling undervoltage release de-energised - (5e)
E2/6 DC 1 normally closed contact 038341
E2/6 DC 1 normally open contact 038340
ABB SACE 85
1SDC200012D0202
1SDAR1
Mechanical operation counter - (7)
E2/6 DC 038345
Locks in open position - (8a-8b)
with key (8a)
E2/6 DC for 1 circuit-breaker (different keys) 058271
E2/6 DC for groups of circuit-breakers (same keys N.20005) 058270
E2/6 DC for groups of circuit-breakers (same keys N.20006) 058274
E2/6 DC for groups of circuit-breakers (same keys N.20007) 058273
E2/6 DC for groups of circuit-breakers (same keys N.20008) 058272
E2/6 DC for groups of circuit-breakers (same keys N.20009) 064503
with padlocks (8b)
E2/6 DC 4 mm 038351 (a)
E2/6 DC 8 mm 064504
Note: (a) to be requested in alternative to the opening and closing pushbutton protection (accessory 9a).
Mechanical accessories
Circuit-breaker lock in racked-in/test/racked-out position - (8c)
E2/6 DC for 1 circuit-breaker (different keys and with padlocks 4mm) 058278
E2/6 DC for groups of circuit-breakers (same keys N.2005 and with padlocks 4mm) 058277
E2/6 DC for groups of circuit-breakers (same keys N.2006 and with padlocks 4mm) 058281
E2/6 DC for groups of circuit-breakers (same keys N.2007 and with padlocks 4mm) 058280
E2/6 DC for groups of circuit-breakers (same keys N.2008 and with padlocks 4mm 058279
E2/6 DC for groups of circuit-breakers (same keys N.2009 and with padlocks 4mm) 064505
E2/6 DC for 1 circuit-breaker (same keys N.2009 and with padlocks 6mm) 064506
E2/6 DC for groups of circuit-breakers (same keys N.2005 and with padlocks 6mm) 064507
E2/6 DC for groups of circuit-breakers (same keys N.2006 and with padlocks 6mm) 064508
E2/6 DC for groups of circuit-breakers (same keys N.2007 and with padlocks 6mm) 064509
E2/6 DC for groups of circuit-breakers (same keys N.2008 and with padlocks 6mm) 064510
E2/6 DC for groups of circuit-breakers (same keys N.2009 and with padlocks 6mm) 064511
Padlocks
E2/6 DC 8mm 064512
Preset for key lock
RONIS
Cap preset 058315
Lock in open position 058276
Lock in racked-in/test/racked-out position 058314
CASTELL
Lock in open position 058275
Accessory for lock in test/racked-out position - (8d)
E1/6 038357
Note: to be requested for completion of the circuit-breaker lock in racked-in / test / racked-out position (accessory 8c)
Accessory for shutter padlock lock - (8e)
E2/6 DC 038363
Mechanical compartment door lock - (8f)
E2/6 DC 045039
Note:
- to be requested with interlock for fixed circuit-breaker/moving part of withdrawable circuit-breaker (accessory 10.2)
- for fixed version, also request interlock plate 10.4
- to be ordered in alternative to the cable interlocks (accessory 10.1), and in alternative to the 15 additional auxiliary contacts (accessory 5b).
ABB SACE 86
1SDC200012D0202
1SDAR1
1SDAR1
3 poles 4 poles
Opening and closing pushbutton protection - (9a)
E2/6 DC 038343
Note: to be requested in alternative to the lock with padlocks in open position (accessory 8b).
IP54 Door protection - (9b)
E2/6 DC Different keys 038344
E2/6 DC Same keys 065622
Protection for sealable relay - (9c)
E2/6 DC for PR121 058316
E2/6 DC for PR122/PR123 058317
Mechanical interlock - (10)

10.1 Interlock cables for fixed circuit-breakers or fixed parts
E2/6 DC A - horizontal 038329
E2/6 DC B - horizontal 038330
E2/6 DC C - horizontal 038331
E2/6 DC D - horizontal 038332
E2/6 DC A - vertical 038333
E2/6 DC B - vertical 038334
E2/6 DC C - vertical 038335
E2/6 DC D - vertical 038336
Note: request one type of cable for each interlock. To be requested on one of the fixed circuit-breakers or on one of the fixed parts.
10.3 Interlock for fixed circuit-breaker/moving part of withdrawable circuit-breaker
E1-E2 038366 038366
E3 038367 038367
E4 038368 043466
E6 043466 038369
Note: request an accessory for each fixed circuit-breaker/moving part of withdrawable circuit-breaker.
10.4 Interlock for fixed circuit-breaker/fixed part of withdrawable
E2/6 DC Interlock A / B / D 038364
E2/6 DC Interlock C 038365
Note: request an accessory for each fixed circuit-breaker/moving part of withdrawable circuit-breaker.
10.5 Interlock plate for fixed circuit-breaker
E2/6 DC 038358
Note: only request for fixed circuit-breaker.
10.1 Extended interlock cables for fixed circuit-breakers or fixed parts
E2/6 DC A - horizontal extended cables 066090
E2/6 DC B - horizontal extended cables 066091
E2/6 DC C - horizontal extended cables 066092
E2/6 DC D - horizontal extended cables 066093
E2/6 DC A - vertical extended cables 066094
E2/6 DC B - vertical extended cables 066095
E2/6 DC C - vertical extended cables 066096
E2/6 DC D - vertical extended cables 066097
Note: request one type of cable for each interlock. To be requested on one of the fixed circuit-breakers or on one of the fixed parts.
Ordering codes
SACE Emax DC accessories
ABB SACE 87
1SDC200012D0202
1SDAR1
PR010/T test and programming unit
E2/6 DC PR010/T 048964
PR021/K indication unit
E2/6 DC PR021/K 059146
PR120/K indication module
E2/6 DC PR120/K 4 Outputs w|th |ndependent term|na|s} 058255
E2/6 DC PR120/K 4 Outputs + 1 lnput w|th one term|na| |n oommon} 058256
PR120/LV voltage measurement module for 100VUe250V
E2/6 DC PR120/LV 065223
Note: Each Emax DC circuit-breaker has the PR120/V voltage measurement module included. The PR120/LV is used for 100V<Ue<250V
PR120/D-M (Modbus RTU) communication module
E1/6 PR120/D-M 058254
BT030-USB
E1/6 BT030-USB 058259
Auxiliary units
ABB SACE 88
1SDC200012D0202
+
-
L
O
A
D
+ -
LOAD -
LOAD +
+ -
LOAD -
LOAD +
Ordering Examples
Selection of an Emax DC circuit-breaker depends on the plant requirements:
a. Plant requirements:
- Type of network: insulated network
- Rated current (Iu): 800A
- Rated voltage (Ue): 110V
- Short-circuit current: Icu= 20kA
- Version: Withdrawable (W)
- Power supply: from lower terminals
- Protections required of the trip unit: LSI
- Terminals: horizontal rear (HR)
Insulated network
(1)
Rated voltage (Ue) 500 750 1000
isolation Q Q Q Q
protection Q Q Q Q
PR122/DC Q Q Q Q
PR123/DC Q Q Q Q
Icu
(2)
[kA] [kA] [kA] [kA]
E2
B
800
35 25 25 25
1000
1250
1600
N 1600 50 25 40 25
E3
N
800
60 40 50 35
1000
1250
1600
2000
2500
H
1600
65
(3)
40 50 40 2000
2500
E4
S
1600
75 65 65 50
2000
2500
3200
H 3200 100 65 65 65
E6 H
3200
100 65 65 65 4000
5000
(1)
the possibility of a double earth fault is considered negligible with this type of pole connections. For further information, see QT5: ABB circuit-breakers for direct current applications.
(2)
Icu with L/R = 15ms according to IEC 60946-2 Standard. For Icu with L/R = 5ms and L/R = 30ms, ask ABB.
(3)
85kA only if supplied from below and specifying the following extracode at the ordering stage: 1SDA067148R1. Ics=65kA.
ABB SACE 89
1SDC200012D0202
+
-
LOAD -
LOAD +
Emax DC fixed E2B 3pole with horizontal terminals (HR)
1SDA064590R1 E2B 800 PR122/DC-In=800A MP
+
1SDA065223R1 ETRAOODE for vo|tage 100vUe250V
1SDA059891R1 FIXED PART E2 3p HR
+
1SDA067149R1 ETRAOODE for power supp|y from |ower term|na|s
3D rear view Front view
According to plant requirements, the choice falls on E2B 3p because it has a value of Icu 20kA,
800A rated current and is tted with PR122/DC.
As for all the withdrawable version circuit-breakers, both the moving part and the xed part
must be ordered:
Moving part: as the standard solution, ABB SACE supplies the Emax DC moving parts with
voltage sockets located on the lower terminals, according to power supply from these same
terminals.
Fixed part: The same xed parts with horizontal terminals as the switch-disconnectors are used
for special direct current applications (MS/E) up to 750V DC if they are 3p, up to 1000V DC if
they are 4p.
ABB SACE 90
1SDC200012D0202
+
-
2
2
L
O
A
D
+ -
LOAD -
LOAD +
Network with the mid-point earthed
Rated voltage (Ue) 500 500 750 1000
PR122/DC - - - -
PR123/DC Q Q Q Q
type of fault a b c a b c a b c a b c
poles in series affected by the fault 3 2 (U/2) 1 (U/2) 4 2 (U/2) 2 (U/2) 4 2 (U/2) 2 (U/2) 4 2 (U/2) 2 (U/2)
Icu
(1)
[kA] [kA] [kA] [kA]
E2
B
800
35 35 18 35 35 35 25 25 25 25 25 25
1000
1250
1600
N 1600 50 50 25 50 50 50 40 40 40 25 25 25
E3
N
800
60 60 30 60 60 60 50 50 50 35 35 35
1000
1250
1600
2000
2500
H
1600
65
(2)
65 40 65
(2)
65
(2)
65
(2)
50 50 50 40 40 40 2000
2500
E4
S
1600
75 75 35 75 75 75 65 65 65 50 50 50
2000
2500
3200
H 3200 100 100 50 100 100 100 65 65 65 65 65 65
E6 H
3200
100 100 65 100 100 100 65 65 65 65 65 65 4000
5000
(1)
Icu with L/R = 15ms according to IEC 60946-2 Standard. For Icu with L/R = 5ms and L/R = 30ms, ask ABB.
(2)
85kA only if supplied from below and specifying the following extracode at the ordering stage: 1SDA067148R1. Ics=65kA.
Ordering Examples
Plant requirements:
- Type of network: with mid-point earthed
- Rated current (Iu): 2500A
- Rated voltage (Ue): 1000V
- Short-circuit current (Icu): 30kA
- Version: Fixed (F)
- Power supply: from the vertical upper terminals
ABB SACE 91
1SDC200012D0202
3D rear view Front view
Emax DC E4S /DC 4p power with upper supply
1SDA064702R1 E3N 2500 PR123/DC-In=2500A 4p F VR
+
1SDA058251R1 Extracode for power supply from upper terminals
According to plant requirements, the choice falls on E3N because it has a value of Icu 30kA and
2500A rated current. Since a voltage Ue 750V is required, the version with 4 poles is necessary.

E3N20 PR123/DC 4p power supply from the upper terminals
As the standard solution, ABB SACE supplies xed direct current circuit-breakers supplied from
the lower terminals. In the case of power supply from upper terminals, it is necessary to specify the
1SDA058251R1 extracode at the time of ordering.
ABB SACE 92
1SDC200012D0202
+
-
L
O
A
D
+ -
LOAD -
LOAD +
Ordering Examples
Plant requirements:
- Type of network: with earthed negative polarity
- Rated current (Iu): 1600A
- Rated voltage (Ue): 400V
- Short-circuit current (Icu): 65kA also in the case of type b fault
- Version: Withdrawable (W)
- Power supply: from lower terminals
- Vertical terminals
- Proteot|ons: |SlG
Network with earthed negative polarity
(1)
Rated voltage (Ue) 500
(2)
isolation Q Q
protection Q Q
PR122/DC Q Q
PR123/DC Q Q
type of fault
(3)
a b a b
poles in series affected by the fault 3 2 4 3
Icu
(4)
[kA] [kA]
E2
B
800
35 20 35 35
1000
1250
1600
N 1600 50 25 50 50
E3
N
800
60 30 60 60
1000
1250
1600
2000
2500
H
1600
65
(5)
40 65
(5)
65
(5)
2000
2500
E4
S
1600
100 50 100 100
2000
2500
3200
H 3200 100 65 100 100
E6 H
3200
100 65 100 100 4000
5000
(1)
for networks with positive earthed polarity, ask ABB.
(2)
for higher voltages, ask ABB.
(3)
for further information, see QT5: ABB circuit-breakers for direct current applications.
(4)
Icu with L/R = 15ms according to IEC 60946-2 Standard. For Icu with L/R = 5ms and L/R = 30ms, ask ABB.
(5)
85kA only if supplied from below and specifying the following extracode at the ordering stage: 1SDA067148R1. Ics=65kA.
ABB SACE 93
1SDC200012D0202
According to plant requirements, the choice falls on E3H because it has a value of Icu (up to 500V)
65kA and 1600A rated current, 4 poles.
E3H 16 PR123/DC 4p F VR
As the standard solution, ABB SACE supplies xed direct current circuit-breakers supplied from lo-
wer terminals. The 4-pole conguration for network with earthed negative polarity requires a special
extracode which makes it possible to have 3 poles in series on the positive polarity (not earthed):
1SDA068806R1.
3D rear view Front view
Emax DC E3H 16 PR123/DC 4p power upper supply with horizontal terminals (HR)
1SDA064703R1 E3H 1600 PR123/DC-In=1600 4p F
+
1SDA068806R1 Extracode for special connection with 3 poles in series on the positive polarity (not earthed)
Notes
ABB SACE
1SDC200012D0 02 2
Notes
ABB SACE
1SDC200012D0 02 2
Notes
ABB SACE
1SDC200012D0 02 2
1
S
D
C
2
0
0
0
1
2
D
0
2
0
2

-

0
1
/
1
0

-

5
.
0
0
0

-

C
A
L
Contact us
ABB SACE
A division of ABB S.p.A.
L.V. Breakers
Via Baioni, 35
24123 Bergamo
Phone: +39 035 395.111
Fax: +39 035 395.306-433
www.abb.com
The data and illustrations are not binding. We reserve
the right to modify the contents of this document on the
basis of technical development of the products, without
prior notice.
Copyright 2010 ABB.
All rights reserved.

You might also like