KISADEVRE HESAP YAPRAI ( CALCULATION SHEET OF SHORT-CIRCUIT CURRENTS)


Parameters ebeke Network Sistemi gerilimi YG ('kV) Sistemi gerilimi OG(''kV) Sb(MVA) S'' k(MVA) 154 34.5 100 7256 %r %x z% R() jX() Z( )

0.013781698

0.1804

0.1804

Trafo Power Transformer

Str (MVA) Pk(Kw)

uk % ur % ux %
Type of conductor letken cinsi RL( /km ) XL( /km) ) L km

100 272 12.1 0.2720 12.10 0.0027 0.1210 0.1210 0.0324 1.4398 1.4402

Havai Hat Overhead Transmission Lines

477 MCM 0.3427 0.13416 5.3 0.0509

0.0199

0.0546

0.6054

0.2370

0.6502

Nr.of paralel cables and cross-section Paralel Kablo says ve kesiti Yeralt XLPE Kablo Lc( mH/km ) Rc( /km ) Underground XLPE cable L km Xc( /km) ) Elektrik daresi DM 20224

XLPE 240 0.1885 0.0754 0.25 0.059189

0.0008

0.0006

0.0010

0.0094

0.0074

0.0120

Electricity company MV D.Center 20224 Nr.of paralel cables and cross-section Paralel Kablo says ve kesiti Lc( mH/km ) Rc( /km ) XLPE Kablo XLPE cable L km Xc( /km) ) XLPE 150 0.2011 0.124 0.32 0.063145 2 23 6 1.1500 5.88876 0.4 0.5750 2.9444 3.0000 0.00092 0.0047 0.0048 0.5750 2.9444 3.0000 6.84394 35.0455 35.7075

0.0033

0.0017

0.0037

0.0397

0.0202

0.0445

B
Mteri Trafosu Custemor Transformer Sn (MVA) Pk(Kw)

uk % ur % ux %

R+X referred to LV side (0,4kV) AG tarafnda indirgenmi trafo R+X'i

AG Baras LV Bus bar

A noktasndan bakldnda toplam empedens Sum of empedance before Point A B noktasndan bakldnda toplam empedens Sum of empedance before Point B O.G tarafndaki empedansn AG tarafna indirgenmesi HV side Empedance referred to LV side C noktasndan bakldnda toplam empedans Sum of empedance before Point C

0.6988 0.6327

0.8788 1.1227 0.0990

0.5132

0.5227 37.6904

3.1014 3.1652 7.5309 36.9304

0.0001 0.5751

0.0004 0.0004 0.0010 2.9448 3.0004 0.0019

0.0050 0.0097

0.0051 0.0099

page-sayfa-1

no (Job No ) : in ad (Job Name) :

KISADEVRE HESAP YAPRAI ( CALCULATION SHEET OF SHORT-CIRCUIT CURRENTS) 34,5kV baradaki ksa devre deerleri (Short-circuit currents at several points) Ik"= 3.52 kA A noktasnda/at Point A Ik"= 0.05 kA B noktasnda/at Point B Ik"= 25.75 kA C noktasnda/at Point C xsistem 0.1804 XA 0.5132 xsistem/XA= 0.3515833 <0,5 generatrden uzak ksadevre Short-circuit far form generator Dolaysyla (in this case) I"k=Ik=Ia Maksimum asimetrik ksadevre akm ( Calculation of Max. asymmetrical short-circuit current) veya Darbe ksa devre akm hesab rA/xA= 0.7951611 Grafikten c=1,2 bulunur From grafic Is=c. 2 . I"k Is= 5.98 Is=c. 2 . I"k 'Ka

A noktasnda Kesici Ksa devre ama gc ( Short-circuit breaking power of circuit breaker At Point A) Sa= 3 . Un . Ia Sa= 210.45 MVA

TEDA tarafnda seilen Kesici gc 1000MVA dr. Selected Circuit Breaker Breaking Power is 1000MVA at TEDA side