MECON LIMITED

50, Chowringhee Road, Kolkata 700 071 FAX MESSAGE To M/s. Nicco Corporation Nicco House,1st Floor, Hare Street, Kolkata 700001 Fax No. (033) 2220 9443 Ref. No. 19.56.9399/ Dear Sir, Please furnish us budgetary estimations and detailed catalougue of the following equipments for the provided specification as earliest as possible. The equipments will be installed in various 33/11 kV Distribution Substations of WBSEB scattered all over West Bengal. You are requested to indicate applicable taxes & duties separately. Please also indicate delivery time of each equipment. S.N. 1. EQUIPMENTS Capacitive Duty VCB (Indoor Type) SPECIFICATION 12 kV, 50 Hz, 3 Ph., 800 A, Bus Bar Short Time Rating = 16 kA for 3s , Short Time Rating of Vacuum Interrupter is minimum 25 kA for 3s ,shall be suitable foe 100 Nos. of safe operations at 25kA, Capacitive Switching Duty = 800 A Dead Front Sheet steel (2mm) enclosed floor mounted horizontal draw out type. Inclusive of side entry cable extension box. Current Transformer Specification 11 kV, 50 Hz, 3 Ph., 15 VA, 200-100/1-1 A or 50-25/1-1 A (As per requirement), Cast resin, Dual core, Dual ratio, Acc.Class1.0/5P10. (1) Electronic Annunciator: Multiway microprocessor based to indicate over current, earth fault and other trouble trip/alarm operation. (2) Voltmeter: 96 mm, 90 scale flush type shall be provided on each breaker panel suitable for direct reading of 0 15 kV. (3) Ammeter: 96 mm, 90 scale (nominal current: 1A) flush type for each phase, shall be provided on each breaker panel. (4) Voltmeter Selector Switch: with wing type knob and positions marked RY YB BR - OFF shall be provided in each breaker panel against each Voltmeter.
TEN TNO.

Date : 03/02/2007 | Page : 1 of 4 From : Rupak Biswas, General Manager MECON, Kolkata Ph. (O) : (033) 2282-2381/83 e-mail : meconnb@yahoo.com Fax no. (033) 2282-4441

250

Page 1 of 5

S.N.

EQUIPMENTS

SPECIFICATION (5) Test Terminal Block with cover having sealing arrangement for 3phase system shall be provided in breaker panel.

TEN TNO.

(6) The panel should consist of the following relays: (a) Over current relay : i) High Set Element Current Setting 500 2000% Operating Time Instantaneous ii) IDMT Element Current Setting 50 200% Operating Time 0 3sec (b) Earth fault relay : 10 - 40% nominal current 1A (c) Over voltage IDMT Static relay with setting range 100 170% (d) Under voltage relay : with provision for Cut-off at 30% (e) Time Delay Relay : 10 min (f) Unbalance Relay : Neutral Voltage Displacement Static Relay in conjunction with RVT. Alternatively, Unbalance Relay in conjunction with split neutral CT for double star arrangement. The relaying scheme shall have: i) Alarm for low level of unbalance: Overvoltage on good units is less less than 110%. Delay is greater than 4s. ii) Tripping for higher level of unbalance: Overvoltage on good units is greater than 110%. Delay is 0.3s to 0.5s. This shall be coordinated to maximum fuse clearing time. 2. Capacitive Duty VCB (Outdoor Type) with integrally bushing mounted Porcelain Clad C.T. 12 kV, 50 Hz, 3 Ph., 800 A, Short Time Rating = 16 kA for 3 sec, Porcelain Clad, structure mounted. Short Circuit Rating of Vacuum Interrupter is minimum 25 kA for 100 Nos. operations., Capacitive Switching Duty = 800 A Terminal connectors suitable for 1 Al pipe bus. Current Transformer Specification 11 kV, 50 Hz, 3 Ph., 15 VA, 200-100/1-1 A or 50-25/1-1 A (As per requirement), Cast resin, Dual core, Dual ratio, Acc.Class1.0/5P10. (1) Electronic Annunciator: Multiway microprocessor based to indicate over current, earth fault and other trouble trip/alarm operation. (2) Voltmeter = 96 mm, 90 scale flush type shall be provided on each breaker panel suitable for direct reading of 0 15 kV. (3) Ammeter = 96 mm, 90 scale (nominal current: 1A) flush type for each phase, shall be provided on each breaker panel. (4) Voltmeter Selector Switch = with wing type knob and positions marked RY YB BR - OFF shall be provided in each breaker panel against each Voltmeter. (5) Test Terminal Block = with cover having sealing arrangement for 3phase system shall be provided in breaker panel. 10 10

3.

Control & Relay Panel for outdoor type VCB

Page 2 of 5

S.N.

EQUIPMENTS

SPECIFICATION (6) The panel should consist of the following relays: (a) Over current relay : i) High Set Element Current Setting 500 2000% Operating Time Instantaneous ii) IDMT Element Current Setting 50 200% Operating Time 0 3sec (b) Earth fault relay : 10 - 40% nominal current 1A (c) Over voltage IDMT Static relay with setting range 100 170% (d) Under voltage relay : with provision for Cut-off at 30% (e) Time Delay Relay : 10 min (f) Unbalance Relay: Neutral Voltage Displacement Static Relay in conjunction with RVT. Alternatively, Unbalance Relay in conjunction with split neutral CT for double star arrangement. The relaying scheme shall have: i) Alarm for low level of unbalance: Overvoltage on good units is less than 110%. Delay is greater than 4s. ii) Tripping fir higher level of unbalance: Overvoltage on good units is greater than 110%. Delay is 0.3s to 0.5s. This shall be coordinated to maximum fuse clearing time.

TEN TNO.

4.

Neutral Current Transformer (Outdoor Type)


Potential Transformer

11 kV, 50 Hz, 3 Ph ., 15 VA, 20/1 A, Acc. Class 1.0 Porcelain Clad, structure mounted.

100

5.

& RVT (Outdoor Type) XLPE Cable

11 kV, 50 Hz, 3 Ph ., 50 VA per Ph. Acc.Class - 1/3P/6P 11 kV/3 / 110 V/3 / 110 V, Structure mounted. 3C x 95/185/200 Sq. mm 6.35 kV/11 kV Stranded compacted circular Aluminium (H4 Grade) conductor, XLPE insulated, core shielded with black extruded semi conducting compound, black semi conducting tape and copper tape, coloured strips having red, yellow and blue for core identification, shielded cores laid up with fillers, binder taped and black PVC (type ST-2) inner sheath, single layer of round galvanized steel strip armoured and black extruded PVC (Type ST2) overall sheathed. (a) 3 C x 95 sq. mm. (b) 3 C x 185 sq. mm. (c) 3 C x 240 sq. mm.

300

6.

--

Page 3 of 5

S.N. 7.

EQUIPMENTS Isolator

SPECIFICATION 11 kV, 3 Pole, 2 Post, 200 A, 16 kA for 1 sec. Rocking type outdoor isolator (Structure mounted) with earth switch on the side of capacitor. 12 kV, 10 kA Class, M.C.O.V. of 10 kV, LDC 2, Heavy Duty Gapless Metal Oxide Station Class, Structure mounted with disconnecting device and fault indicator. 11 kV, 50 Hz, 3 Ph ., Short Current Rating 16kA for 2 sec Outdoor type, Unshielded Air Cored Reactor Air cooled, single / multilayer, cylindrical wound units made upon weather resistant fiberglass epoxy tubes. Reactor coil winding of aluminum with insulated conductor. The ratings of reactors and their tentative nos. are as below: Rated O/P Tentative No. Rated O/P Tentative No. 4 kVAR 50 50 kVAR 20 10 kVAR 50 60 kVAR 20 20 kVAR 50 80 kVAR 20 30 kVAR 50 100 kVAR 20 40 kVAR 30 120 kVAR 20 12.1 kV, 50 Hz, 3 Ph. Star (Single or Double as per manufacturers design, please specify), Floating neutral in case of double star. Individual units rated for 12.1/3 kV Fuse : Internal / External as per manufacturers practice Dielectric : Polypropylene Electrode : Aluminum Foil Element : Extended foil type Impregnant : NPCB, Non toxic, biodegradable Discharge device : Built in The ratings of the capacitor banks and their tentative nos. are as below: Rated O/P 100 kVAR 250 kVAR 500 kVAR 750 kVAR 1000 kVAR Tentative No. 50 50 50 50 30 Rated O/P 1250 kVAR 1500 kVAR 2000 kVAR 2500 kVAR 3000 kVAR Tentative No. 20 20 20 20 20

TEN TNO.

300

8.

Lightning Arrester

300

9.

Reactor

300

10.

Capacitor Bank

300

Please treat the matter as urgent. Thanking you,

Page 4 of 5

Yours faithfully, for MECON Limited,

( RUPAK BISWAS )

Page 5 of 5