Larsen & Toubro Limited offers a wide range of Microprocessor based State-of-the-art Digital Protective Relays suitable for LV, MV and HV power distribution systems. These Relays are manufactured at L&Ts Mysore works equipped with modern infrastructure and employing latest manufacturing and testing equipments. L&Ts range also include Relays for special applications manufactured by Microelettrica Scientifica, Italy. The applications include Feeder Management, Load Sharing, Load Shedding, Synchronising, Grid Islanding etc. L&T also manufactures a range of Electronic Single Phase Energy Meters, Three Phase Energy Meters and Trivector Meters at the Mysore Works..
Mysore Works
Training Centres
The L&T Switchgear Training Centres at Pune, Lucknow & Coonoor are the only facilities of their kind in India. The Centres have state-of-the-art training facilities, well-equipped workshop & testing systems. Training programmes on Protective Relaying and related subjects are being regularly conducted at above training centres. Kindly contact the nearest Training Centre for further details.
Lucknow
Plot No. C/6-7 Sarojini Nagar Industrial Area Lucknow 226 008 Tel. : 0522-437591, 437728 Fax : 0522-437592 e-mail : stc-lucknow@lntebg.com
Pune
T-156/157, MIDC, Bhosari, Pune 411 026 Tel. : 020-7120037, 7120653 Fax : 020-7122993, 7121221 e-mail : stc-pune@lntebg.com
Coonoor
Ooty-Coonoor Main Road Needle Industries P.O. Ketti, Niligiris 643 243 (T.N.) Tel. : 0423-517158 Fax : 0423-517107 e-mail: stc-coonoor@lntebg.com
Contents
Pages Time - Current Characteristics Over Current relays - MC31A, MC61A, MC61C Current Sensing relays - MC12A, ME12A, SC14S Neutral Displacement relay - MND11 Reverse Power Relay - MRP11 Voltage relay - MV12 Secondary relays - TCS01, PTF03 Power Factor Control relay - PFC8, PFC14, PFR8 Motor Protection relay - MM30, MM30W, MPR300 Generator Protection relays - IM3GV, MG30, MD32G Synchronising relays - SPM21, SCM21. Load Sharing Relay - RRS Voltage Vector shift / Voltage / Frequency relays - UFD34, UM30A Directional Over Current relay - DM33 Transformer Protection relays - MD32T, IM30T, UM30SV Auto Reclosing Relay - IM30DRE Control & Supervision relays - MW33, MU30. Feeder protection - MC20R, MC30, RPM8 Capacitor protection relay - IM 30C 3 4-5 6-7 8-9 10-11 12-13 14-15 16-17 18-19 20-21 22-23 24-25 26-27
21 25 26 27 32 37 38 40 45 46-(61) 47 49 50
Under impedance relay / Distance relay Synchronising and or Synchro-check relay Over or under temperature protection and control relay AC under voltage relay Power directional relay Under current or underpower relay Bearings over temperature relay Field control (loss of field) relay DC over voltage relay Reverse phase or phase balance current relay Phase-sequence or single-phasing voltage relay Machine or transformer thermal relay Instantaneous over current (or rate-of-rise) relay ME12 MC12A MC61C MC61A MC12A MC61A MC61C MC12A MC61A MC31A MC61C MC12A MC61A MC31A MC61C -MV12 ---MV12 MRP11
Voltage restrained over current relay Breaker - failure over current relay Instanteneous earth fault over current relay AC time over current relay
51N-(51G)
-SPM21 SCM21 -UM30 / UM30SV UFD34 MG30 MM30 MW33 -MG30 IM30T MM30 UM30 IM30T IM3GV MM30 ----IM3GV ------------UM30 / UM30SV UFD34 / UM30SV UM30 / UM30SV UM30A / UM30SV UM30 MG30 MG30 UBO / CR DM33 DM33 ---IM30G IM30DR -UM30 / UM30SV UFD34 -MD32G MD32T ----RRS UM30-SV
Rectifier failure relay (rotating diodes) AC over voltage relay Overexcitation relay V/Hz
Voltage balance relay Ground detector (insulation to ground failure of machine or other apparatus) -Machine stator ground fault detector relay -Machine rotor ground fault detector relay -AC directional over current relay -Directional ground fault over current relay -Alarm relay -DC over current relay -Phase angle measuring or out of-step protection relay --Reclosing relay -DC Under voltage relay -Frequency relay --Lock-out relay -Differential protective relay -SC14S Ground fault differential protective relay -Regulating device to adjust a quantity -DC directional voltage relay -DC directional voltage and current relay Automatic active or reactive load sharing relay Vector Surge Protection Relay
100
10
A 1 B C
D 01 1 10 20
For Trip time at TMS other than 1 Trip time = (Trip time at TMS = 1) x TMS OR 50msec whichever is more
A : Normal Inverse 3.0 Sec. B : Normal Inverse 1.3 Sec. C : Very Inverse D : Extreme Inverse
Wiring Diagrams
MC31A
R Y B 1 2 3 4 13 5 6 15 16 7 8 R
R1
N0 9 10
MC31A
PROTECTION R2
NC 11
In = 0n =
1A; 1A;
5A 5A
N/- 26
MC61A
R Y B 1 2 3 4 13 5 6 15 16 7 8 R Y B 1 2 3 4 13 5 F50(Is) 6 15 16 7 8 21 22 In = 0n = 1A; 1A; 5A 5A L/+ N/25 26 PROG ERROR R5 29 30 R Y B E F51(Os) F50(Ihs) F51(Ohs) R4 27 28 18 R3 17 12 MICRO CONTROLLER
R1 9
N0
MC61A
PROTECTION R2
10 NC 11
MC61C
R Y B 1 2 3 4 13 5 6 15 16 7 8 R Y B 1 2 3 4 13 5 F50(Is) 6 15 16 7 8 21 22 L/+ 25 PROG ERROR C SS+ 9 PIN MALE D1 R Y B E D2 D3 30 19 L/R 20 BI* 31 32 F51(Os) F50(Ihs) F51(Ohs) R5 29 R4 MICRO CONTROLLER R2 R1 9 10 11 12 R3 17 18 27 28 NC BKR OPEN BKR CLOSE NO
MC61C
PROTECTION
In = 0n =
1A ; 1A ;
5A 5A
N/- 26
Display of currents, settings, Trip data & Trip history for analysis & trouble shooting Built in self supervision & self testing feature to ensure continuous reliability Separate Indication for power ON & Programming mode or relay fault Separate fault indication In MC61C - Communication with Computer & breaker control through RS 485 Port Four user programmable output relays
121mm
158mm
20
m 4m m 4m 22
Model
Description Device Code Design Functions Available
MC31A
3 Phase O/C + E/F 51 RYBN Numerical Relay Lowset O/C -Is Lowset E/F -Os O/C Is = 20-200% Step 5% E/F Os = 5-80% Step 5% Time Characteristics available NI, VI, EI, or Definite Time TMS 0.1 - 1.6 Step 0.05
MC61A
3 Phase O/C + E/F + Highset
MC61C
Settings
3 Phase O/C + E/F + Highset Communication and breaker control 50/51 RYBN 50/51 RYBN Numerical Relay Numerical Relay Lowset O/C -Is Lowset O/C -Is Highset O/C -Ihs Highset O/C -Ihs Lowset E/F -Os Lowset E/F -Os Highset E/F -Ohs Highset E/F -Ohs O/C Is = 20-200% Step 5% O/C Is = 20-200% Step 5% E/F Os = 5-80% Step 5% E/F Os = 5-80% Step 5% HS O/C = (0.2 to 40) x In step of - HS O/C = (0.2 to 40) x In step of 0.2 In or disable 0.2 In or disable HS E/F = (0.1 to 20) x On step of - HS E/F = (0.1 to 20) x On step of 0.1 On or disable 0.1 On or disable Time Characteristics available Time Characteristics available NI, VI, EI, or Definite Time NI, VI, EI, or Definite Time TMS : 0.1 - 1.6 Step 0.05 TMS : 0.1 - 1.6 Step 0.05 Site selectable Trip time Char. Highset can be disabled Display of Currents, Trip count Self supervision feature on CT/Phase 0.25 VA Not applicable 00C to 600C < 2kg 10 VA 1 N/O Contact for self suprvn Draw out 121 x 158 x 224 113 x 142 20-110V AC / DC or 88-264V AC / DC 1 AMP or 5 AMP (site selectable) 4NO or 2NO + 2NC HS delay:0.1-2 Sec step 0.01 Sec. or Inst. RS 485 Communication Breaker control Auto doubling of highset, (Relay co-ordination) on CT/Phase 0.25 VA Not applicable 00C to 600C < 2kg 10 VA 1 N/O Contact for self suprvn Draw out 121 x 158 x 224 113 x 142 20-110V AC / DC or 88-264V AC / DC 1 AMP or 5 AMP (not site selectable) 4 NO
Other Features
Site selectable Trip time Char. Display of Currents, Trip count Self supervision feature
Burden on CT Burden on PT Operating temp Weight Burden on Auxiliary supply Output Contact Construction Dim W x H x D in mm Panel Cut Out Auxiliary supply Type 1 Type 2 CT rating Output Contacts
on CT/Phase 0.25 VA Not applicable 0 0C to 600C < 2kg 10 VA 1 N/O Contact for self suprvn Draw out 121 x 158 x 224 113 x 142 20-110V AC / DC or 88-264V AC / DC 1 AMP or 5 AMP (site selectable) 4NO or 2NO + 2NC
O R D E R I N G I N F O R M AT I O N
Wiring Diagrams
MC12A / ME12A
COM
10 11 12
COM
MC12A / Me12
SETTING RANGE (Is)
In 1A 5A AUX SUPPLY 24 - 110V AC/DC 95 - 240V AC/DC MC12A (10-40)% In (20-80)% In (50-200)% In ME12 (1-16)% In
SC14S
11 10 9
1 Control Ckt. R 3 5 6
SC14S
In 1A 5A CT OPERATED RELAY NO AUXILIARY SUPPLY REQUIRED SETTING RANGE (Is) (10-40)% IN (20-80)% IN
Easy setting through front panel DIP Switches Indication for Power ON and trip status Test feature - helps maintenance Compact, light weight helps in reducing panel size & thickness.
20 4 22 mm 4m m
158mm
71mm
Model
Description Device Code Design Functions Available
MC12A
1 Ph O/C or E/F 50/51 or 50N/51N Microcontroller Based Lowset O/C -Is Highset O/C -Ihs Lowset E/F -Os Highset E/F -Is O/C Is = 50-200% Step 10% OR E/F Is = 10-40% Step 2% OR E/F Is = 20-80% Step 4% HS O/C = (2-16) xls step 2 Is HS E/F = (2-16) xls step 2 Is Time Characteristics availableNl, VI, EI, or Definite Time 3 ranges of def Time (1, 10,100) TMS : 0.1 - 1.6 Step 0.1 Site selectable Trip time Char. Highset can be disabled
ME12A
1 Ph Sensitive E/F 50N/51N Microcontroller Based Lowset S E/F -Is Highset S E/F -Ihs.
SC14S
Instantaneous current relay 87N/64R Static
Settings
S E/F = 1-16% step 1% HS S E/F = (2-16) xls in steps of 2 ls Time Characteristics availableNI, VI, EI or Definite Time 3 ranges of def Time (1, 10, 100) TMS : 0.1 - 1.6 Step 0.1 Site selectable Trip time Char. Highset can be disabled Harmonic rejection on CT 0.25 VA Not applicable 00C to 600C < 1.5kg 5.5 VA 2 C/O Contacts (S/R) Draw out 71 x 158 x 224 62 x 142
Other Features
Time Characteristics availableInstantaneous (25ms) OR time delayed 100ms / 200ms Self Powered Relay testing possible by ext.24V Supply Flag indication / LED indication 6VA Not Applicable 00C to 600C < 1.5kg Not Applicable 2 C/O Contacts (S/R) Draw out 71 x 158 x 224 62 x 142
Burden on CT Burden on PT Operating temp Weight Burden on Auxiliary supply Output Contacts Construction Dim W x H x D in mm Panel Cutout
on CT 0.25 VA Not applicable 00C - 600C < 1.5kg 5.5 VA 2 C/O Contacts (S/R) Draw out 71 x 158 x 224 62 x 142
O R D E R I N G I N F O R M AT I O N Auxiliary supply Type 1 Type 2 CT rating Range Setting 20-110V AC / DC or 88-264V AC / DC 1 AMP or 5 AMP 10-40% OR 20-80% OR 50-200% Site Selectable 20-110V AC / DC or 88-264V AC / DC 1 AMP or 5 AMP Not Applicable 1 AMP or 5 AMP 10-40% OR 20-80%
Wiring Diagrams
MND11
1 R1
6 7 L /+ Aux. Supply N /5 9
2 R Y B 3 4 11 12
R2
10
MND11
PT VOLTAGE : 110V AC
MRP11
R Y B
2 3 11
7 8 6
MRP11
MV12
MV12
Neutral Displacement Relay Reverse Power Relay Under Voltage OR Over Voltage Relay
Easy setting through front panel DIP Switches LED indication for Power ON and trip status Test feature - helps maintenance Compact, light weight helps in reducing panel size & thickness.
20 4 22 mm 4m m
158mm
71mm
Model
Description Device Code Design Functions Available
MND11
Neutral Displacement 59 Vo Microcontroller Based Voltage relay for E/F Protection of generator earthed thro neutral earthing transformer Fault voltage Vs 2% - 32% of Vn step 2% Alarm voltage Vis 2% - 32% of Vn step 2% Time Characteristics availableInverse time or Definite time TMS : 0.1 - 1.6 Step 0.1
MRP11
Reverse Power 32 Microcontroller Based Reverse Power Level
MV12
1 Ph U/V OR O/V
Settings
27 OR 59 Microcontroller Based Lowset U/V - Vs Highset U/V - Vhs OR Lowset O/V - Vs Highset O/V - Vhs PT input Vn 110V, 240V, 415V AC U/V Vs = 95-20% step 5% CT input In 1 A / 5 A U/V Vhs = 90-20% step 10% Pick up level 1% - 15% O/V Vs = 105-180% step 5% Min. setting 0.5% O/V Vhs = 110-180% step 10% TMS 0 to 1.5 step 0.1 Time Characteristics availableInverse time or Definite time Definite time characteristics TMS : 0.1 - 1.6 Step 0.1 LED indication Test feature Site selectable U/V OR O/V Site selectable Trip time Char. Highset can be disabled VA on PT 0.075 Not Applicable 0 0 C to 600C < 1.5 kg 5.5 VA 2 C/O Contacts (S/R) Draw out 71 x 158 x 224 62 x 142
LED indication for power ON, time characteristics, trip Test feature Third harmonics rejection 26db 0.25 VA Burden on PT Not Applicable Burden on CT 0 0 C to 600C Operating temp < 1.5 kg Weight 5.5 VA Burden on Auxiliary supply 1 N/O +1C/O Contacts (S/R) Output Contacts Draw out Construction 71 x 158 x 224 Dim W x H x D in mm 62 x 142 Panel Cutout Other Features
< 0.25VA < 0.25VA 00C to 600C < 1.5 kg < 8VA 1 N/O+1 C/O Draw out 71 x 158 x 224 62 x 142
O R D E R I N G I N F O R M AT I O N Auxiliary supply Type 1 Type 2 CT Rating PT Rating 20-110V AC / DC 88-264V AC / DC Not Applicable 110V AC 20-110V AC / DC 88-264V AC / DC 1AMP OR 5 AMP Upto 380V AC 20-110V AC / DC 88-264V AC / DC Not Applicable 110V/240V/415V (site selectable)
Wiring Diagrams
Secondary Relays
TCS 01
L /+ TRIP COIL SUPPLY (20 - 264V AC / DC 1 2 3 4 13 15 BKR. AUX. CONT. 12 11 14 TC Aux. Supply N/ TCS CKT. L /+ Aux. Supply N/ R1 7 9 10 8 5
TCS 01
20-110V AC/DC 88-264V AC/DC
PTF 03
1
2 11 12 FUSE R FUSE Y FROM PT SEC. 110V AC PH. -PH. B FUSE N LOAD 16 17 LOAD 13 14 15 R1 7 9 10 8 6 5
LOAD
PTF CKT.
PTF 03
10
Secondary Relays
Trip Circuit Supervision Relay PT Fuse Failure Relay
Easy setting through front panel DIP Switches Indication for Power ON and trip status
158mm
Test feature - helps maintenance Compact, light weight - in reducing panel size & thickness. Low power Burden
71mm
Model
Description Device Code Design Functions Available Rating Settings
TCS 01
Trip Circuit supervision 95 ABC Static Post Close Supervision Pre Close Supervision Not Applicable Trip coil supply 110 - 220V AC OR 24 - 48 - 110 - 220V DC Operation time 500+/-100mS Reset time < 150 mS Same Relay for all Rating Trip supply U/V indication CB ON/OFF status indication
PTF 03
PT Fuse Failure Relay 60 Static 3 Phase PT fuse failure 110V AC PT Not Applicable Operation time 7mS LED Indication for each phase Relay trip status Self powered High speed operation Not Applicable <0.5 VA per phase on PT 00C to 550C < 1.5 kg Not Applicable 2 C/O Contacts (S/R) Draw out 71 x 158 x 224 62 x 142
Other Features
Burden on CT Burden on PT Operating temp Weight Burden on Auxiliary Output Contacts Construction Dim W x H x D in mm Panel Cutout Auxiliary supply Type 1 Type 2
Not applicable Not applicable 00C to 550C < 1.5 kg 10 VA 2 C/O Contacts (S/R) Draw out 71 x 158 x 224 62 x 142 20-110V AC / DC or 80-264V AC / DC
O R D E R I N G I N F O R M AT I O N
20 4 22 mm 4m m
11
Wiring Diagrams
PFC-8
PFC-8
1 2 3 4 5 6 7 8 9 10 11 12 R1 R2 R3 R4 R5 R6 R7 R8 NC NC NC C 13 NC 14 NC 15 NC 16 17 18 19 20 + 21 + 22 23 24 230VAC 50Hz
ALARM
BANK #1
PFC-14
PFC-14
1 2 3 4 5 6 7 8 9 10 11 12 R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11 C 13 14 15 16 17 18 19 S2 S1(1A) 20 S1(5A) 21 22 415V 23 E 24 R12 R13 R14 ALARM 230VAC 50Hz
BANK #1 + +
PFR-8
PFR-8
1 R1 13 14 15 17 18 S2 S1(1A) S1(5A) 415V C 19 20 21 22 23 E 24 BANK #8 R Y B N TO LOAD ALARM 16 230VAC 50Hz 2 R2 3 R3 4 R4 5 R5 6 R6 7 R7 8 9 10 11 12 R8
BANK #1
12
On line display of system PF Easy setting of power factor C/K ratio from front panel LED indication for Alarm code, No. of Banks selected, PF statuslead / lag / unity, Auto / Manual mode DIP switches selection for No. of banks / time delay / bank ratios Display of system current KVAR valves.
144mm
144mm
0 11
m m
Model
Description Device Code Design Functions Available Settings
PFC-8
Power Factor Controller Microcontroller Based Automatic PF controller Can control upto8 Capacitor Banks PF : 0.8 Lag - 0.95 Lead Switching time 10-20-40-60 S Threshold reactive current Setting 0.5 - 1 A reactive Capacitor Bank Selection4-5-6-7-8 Banks Display of PF Measurement Auto / Manual Selection Disconnection of Capacitors during over voltage & Power failure Alarm contact for under / over compensation, over voltage, under load 1 A / 5 A field selectable 0.3 VA 10 VA 00C to 600C < 2kg 8 N/O
PFC-14
Power Factor Controller Microcontroller Based Automatic PF controller Can control upto14 Capacitor Banks PF : 0.8 Lag - 0.95 Lead Switching time 10-20-40-60 s Threshold reactive current setting 0.5 - 1 A Reactive Capacitor Bank Selection4-5-6-7-8-10-12-14 Banks Display of PF Measurement Auto / Manual Selection Disconnection of Capacitors during over voltage & Power failure Alarm contact for under/over compensation,over voltage,under load 1 A / 5 A field selectable 0.3 VA 10 VA 00C to 600C < 2kg 14 N/O 144 x 144 x 110 138 x 138 O R D E R I N G I N F O R M AT I O N 415V AC
PFC-14
IntelligentPower Factor Controller Microcontroller Based Automatic PF controller 8 stages Switching time 5-1200 sec. Auto C/K setting Can accept unequal banks Fault indication Display of PF. V. I. KVAR LED indications for faults PF status-lead / lag. Lead PF alarm 1 A / 5 A field selectable 0.5 VA 10 VA 00C to 600C <2kg 8 N/O 144 x 144 x 110 138 x 138 110V AC
Other Features
Dim W x H x D in mm 144 x 144 x 100 Panel Cutout 138 x 138 Auxiliary supply 415V AC
13
Wiring Diagrams
MM30
A B C 25 26 27 28 39 29 41 30 32 43 31 42 33 In=5A In=1A A B C 25 26 27 28 39 29 41 30 32 43 31 42 33 44 PRESA/TAP 31:Ion=5A PRESA/TAP 33:Ion=1A DISPLAY MICROP. R1 21 10 11 22 7 9 8 18 20 19 4 6 5 15 17 16 14 3 2 1 34/38 23 24
IEC 255
MM30
FUNCTION
R2
R3
F37 F46 F49 F51 F51R F64 St.No.> AI.0> Itr PROGR. INT. FAULT
R1 R2 R3 R4
R4
R5
MM30-W
A B C 25 26 A B C
25 26
1/5A
A B C DISPLAY MICROP R1
21 (10) 10 11 22 N.O. 7 9 N.C. 8 18 (21) 20 19 N.O. 4 6
MM30-W
27 28 39 29 30 41 32 43 33 27 28 39 29 30 41 32 43 33
27 28 39 29 30 41 32 43 33
1/5A
R2
R3
R4
N.C.
1/5A
BT 2 50
R5
5 15 17 16 14 3 2 1 37(b)
c ss+
BT
50
9 PIN MALE
CE MS - SCE 1630 - R0
MPR300
R Y B N
Stop (N/C)
2 NC
4 NO
8 Aux. Supply
MPR300
Typical connection diagram for 'Direct Starting' application
14
Display of various parameters, trip count and trip data on 8 digit alphanumeric display Separate LEDs for individual fault indication Four user programmable output relays Built in self supervision & self testing feature helps maintenance Easy operation by 5 push buttons RS 485 Port for serial communication with MSCOM user friendly software
158mm
m 4m m 20 24m 2
121mm
Model
Description Device Code Design Functions Available
MM30
Motor Protection 49, 51LR, 46, 37, 50/51, 64, StNo, Itr
MM-30W
Motor Protection
MPR300
Motor Protection 49, 51LR, 64, 46, 37 Numeric Thermal overload Locked Rotor Earth fault Single phasing No load running
Other Features
Burden on CT Burden on PT Operating temp Weight Burden on Auxiliary Output Contacts Construction Dim W x H x D in mm Panel Cutout Auxiliary supply
12/14, 27/59, 37, 46, 47, 48 49, 50/51, 51LR, 55, 64, 66, 68, 81 Numeric Numeric Thermal O/L and Pre-alarm Thermal O/L and Pre-alarm Locked Rotor Locked Rotor Current unbalance, phase reversal, Current unbalance, phase reversal, phase loss phase loss Over Current Over Current Earth Fault Earth Fault Repeat and prolonged starts Repeat and prolonged starts Restart Inhibition Restart Inhibition No load running No load running Blocking Function Blocking Function Under frequency / over frequency Under voltage / over voltage Running hours Low PF Auto setting Auto setting 1 A or 5 A site selectable (Default 5 AMP) 1 A or 5 A site selectable (Default 5 AMP) Selectable motor time constant (1 - 60 min) Selectable motor time constant (1 - 60 min) Display of parameters Display of parameters Built in self supervision Built in self supervision RS 485 port RS485 port 0.2 VA for 5 A, 0.01 VA for 1 A 0.2 VA for 5 A, 0.01 VA for 1 A Not Applicable 100C to 600C < 2kg 8.5 VA 4 C/O + 1 C/O for self supervision Draw out 121 x 158 x 224 113 x 142 20-110V AC / DC or 88-264V AC / DC Not Applicable 100C to 600C < 2kg 8.5 VA 4 C/O + 1 C/O for self supervision Draw out 121 x 158 x 224 113 x 142 20-110V AC / DC or 88-264V AC / DC
up to 88 A Trip time characteristics as per IEC947 No RS 485 port (Non-CommunicationRelay) Not Applicable 00C to 600C < 0.5kg. < 8VA Back panel monitor 70 x 85 x 106 Not applicable Motor rated current 240V AC
O R D E R I N G I N F O R M AT I O N
15
Wiring Diagrams
IM3G-V
A B C 25 26 27 28 39 29 41 30 33 Un 32 43 Un 31 42 44
1/5A 1/5A
DISPLAY MICROP.
R1
21 10 11 22 7 9 8 18 20 19 4 6 5 15 17 16 14 3 2 1
C SS+
IM3G-V
FUNZIONI FUNCTION
R2
R3 R1 R2 R5 R3 R4 4 3 2
1/5A
F27/59 F32 F40 F46 F49 F50/51V F81 PROGR. INT. FAULT KEYBOARD TASTIERA
R4
R5
34/38 23 24
13
9 PIN MALE
In = 5A
In = 1A
Un = 100V
MG30
25 DISPLAY
1/5A
R1
21 10 11 22
26
1/5A
MICROP.
MG30
FUNZIONI FUNCTION
27
1/5A
R2 R3
7 9 8 18 20 19 4 6 5 15 17 16
28 39 29
1/5A
R1 R2
R4
30 41 31 42 32 43 33
R5
1/5A
14 3 2
1/5A
44
12 13
KEYB0ARD TASTIERA
9 PIN MALE
MD32-G
A 87G + 87N B C I1A I1B I1C 26
1/5A
25
1/5A
DISPLAY MICROP.
R1
21 10 11 22 7 9 8 18 20 19 4 6 5 15 17 16 14 3
27 28 39 G 29
1/5A 1/5A
MD32-G
FUNCTION F187G F287G F87N R1 R2 R3 R4
R2
R3
R4
I2A I2B
R5
30 41 31 42 32 43 Z R 33
1/5A
I2C
B3
1/5A
R5
B2 B1
C SS+
1/5A
50-60
L/+ 12 N/- 13
KEYBOARD
2 1 34/38 23 24
16
9 PIN MALE
Display of various parameters, trip count & trip data on 8 digit alphanumeric display Separate LEDs for various fault indication
158mm
Four user programmable output relays Built in self supervision & self testing feature help maintainance Easy operation by 5 push buttons RS 485 Port for serial communication with MSCOM User friendly software
m 4m m 20 24m 2
121mm
Model
Description Device Code Design Functions Available
IM3G-V
Generator Protection
MG30
Generator Protection
MD32-G
Generator Differential 87, 50/51, 50LBB, 64S/87N Numeric Generator Differential Bias % with dual adjustable slope Over Current Stator E/F CB Failure protection
Other Features
50/51V, 49,46,27,59,81,40,32, 37 21, 24, 27/59, 32, 37, 40, 46, 49, 50/27, 50V/51V, 51BF, 60FL, 64S, 68, 81 Numeric Numeric Voltage rest. O/C Highset Voltage rest. O/C Highset Trip time char. NI, Def time Trip time char. NI, Def time Thermal Image Thermal Image Lowset Negative sequence Lowset Negative sequence Highset Negative sequence Highset Negative sequence Under voltage, Over voltage Under voltage, Over voltage Under frequency, Over frequency Under frequency, Over frequency Loss of Field, Reverse Power Loss of Field, Reverse Power Low forward power, Low forward power, CB Failure protection CB Failure protection 100% E/F 95% E/F PT fuse failure Over excitation 1 A or 5 A site selectable 1 A or 5 A site selectable Display of Parameters Display of Parameters Built in Self supervision Built in Self supervision RS485 Port, Blocking Function RS485 Port, Blocking Function 0.2 VA for 5 A, 0.01 VA for 1 A 0.04 VA 8.5 VA 100C to 600C < 2kg 4 C/O, S/R or H/R or Time del 1 C/O for self supervision Draw out 121 x 158 x 224 113 x 142 20-110V AC / DC or 88-264V AC / DC 0.2 VA for 5 A, 0.01 VA for 1 A 0.04 VA 8.5 VA 100C to 600C < 2kg 4 C/O, S/R or H/R or Time del 1 C/O for self supervision Draw out 121 x 158 x 224 113 x 142 20-110V AC / DC or 88-264V AC / DC
Burden on CT Burden on PT Burden on Auxiliary supply Operating temp Weight Output Contacts Construction Dim W x H x D in mm Panel Cutout Auxiliary supply Type 1 Type 2
1 A or 5 A site selectable Display of Parameters Wave form capture feature Built in Self supervision, RS485 Port 0.2 VA for 5 A, 0.01 VA for 1 A Not Applicable 8.5 VA -100C to 600C < 2kg 4 C/O, S/R or H/R or Time del 1 C/O for self supervision Draw out 121 x 158 x 224 113 x 142 20-110V AC / DC or 88-264V AC / DC
O R D E R I N G I N F O R M AT I O N
17
Wiring Diagrams
SPM21
DISPLAY 25 UG MICROP. 26
R1
21 10 11 22 7 9 8 18 20 19 4 6 5 15 17 16
52 C
SPM21
FUNCTION F25SX PROGR. INT. FAULT F+
R2
29 UB 30 41 R1
R3
R4 R2 R3 R4 R5
BX BR SX C SS+
G1
R5
UG
SPM21
U B.I. BR 52 (N.O.)
F44 U+ UB UL/+ 12
52
14 3 2 1 34/38 23 24
KEYBORD
IEC 255
N/- 13
9 PIN MALE
SCM21
FUNCTION
R2
UL SCM21
F81 <
44
R5
BU
L/+ 12 N/- 13
KEYBORD
IEC 255
RRS
+
15 12 INCREASE
R1
13 SETTINGS
T
VOIOCOS
Operation + R2 1 2 DECREASE
OPTO R3
17 OVER POWER 18
Lood Shedding 22 2
Freq. control 21 11 10 3 1 Open Open Open Open 2 Open Open Open Open Lood Shedding Yes Yes Yes Yes 3 Open Close Freq. control Yes No
18
Synchronising Relays
Generator Synchronising / Synchrocheck Relays Loadl sharing Relays
Display of various parameters, event count & event data on 8 digit alphanumeric display Separate LEDs for various fault indication
158mm
Four user programmable output relays Built in self supervision & self testing feature help maintainance Easy operation by 5 push buttons RS 485 Port for serial communication with MSCOM User friendly software
m 4m m 20 24m 2
121mm
Model
Description Device Code Design Functions Available
SPM21
Auto Synchronising Relay 25 Numeric Auto Synchronising with Adjustable Voltage, Adjustable Frequency, Adjustable Phase angle Adjustable Reclose time, Bus Live / Dead operation, Speed Regular Control, Voltage Regulator Control, Digital inputs to monitor CB position 110V - 125V PT input Display of Parameters, Built in self supervision, RS485 Port 0.04 VA 100C to 600C < 2kg 8.5 VA 5 C/O Draw out 121 x 158 x 224 113 x 142
SCM21
Synchronising Check Relay 25 Numeric Synchro Check with Adjustable Voltage, Adjustable Frequency, Adjustable Phase angle Adjustable Reclose time, Check Synch/ Dead line / Dead bus modes of operation, Over voltage protection, Under voltage protection, Over Frequency Protection, Under frequency protection, Digital inputs to monitor CB position 110V - 125V PT input Display of Parameters, Built in self supervision, RS485 Port 0.04 VA 100C to 600C < 2kg 8.5 VA 5 C/O Draw out 121 x 158 x 224 113 x 142
RRS
Generator load sharing 95 Solid starter Active / reactive power Over power Load sharing Frequency control
Rating Other Features Burden on PT Operating temp Weight Burden on Auxiliary Output Contacts Construction Dim W x H x D in mm Panel Cutout
110V PT input 1 A / 5 A CT input < 5VA 100C to 600C <1.5kg 8.5 VA 3 N/O Draw out 71 x 158 x 224 62 x 142
O R D E R I N G I N F O R M AT I O N
Auxiliary Supply
20-110V AC / DC or 88-264V AC / DC
20-110V AC / DC or 88-264V AC / DC
19
Wiring Diagrams
UFD34
(21) N.O. N.C. (10) N.O. N.C.
25 26
DISPLAY MICROP.
R1
21 10 11 22 7 9 8 18 20 19 4 6 5 15 17 16 14 3 2 1 34/38 23 24
27 28 39 29 41 30
UFD34
FUNCTION F81 - 1 F81 - 2 F81 - 3 F81 - 4 Fdf / dt F27 / 59 PROGR. INT. FAULT R1 R2 R3 R4 R5
R2
R3
R4
R5
L/+ 12
IEC 255
N/- 13
KEYBOARD
9 PIN MALE
UM30A
25 26 B 27 28 39 29 41 30 R1 (21) 21 10 N.O. 11 22 N.C. 7 9 (10) 8 18 N.O. 20 19 N.C. 4 6 5 15 17 16 14 3 2 1 34/38 23 24
DISPLAY MICROP.
UM30A
FUNCTION F27 / 59 F27d / 59d F59s F59U F81 F59 / 81 PROGR. INT. FAULT KEYBOARD R1 R2 R3 R4 R5
R2 R3 R4 R5
14 BI< BI> C SS+
EA UC EC UB Uo UA EB
L/+ 12 N/- 13 44
BT 2 50
9 PIN MALE
IEC 255
DM33
A B C A B C
29 30 41 31 42 32 43 33 28 39 27 26 25
29
1/5A
30 41 31 42 32 43 33 28 39 27 26 25
DISPLAY MICROP.
R1
1/5A
1/5A
DM33
Io
R2 R3 R4 R1 R2 R3 R4 B4 B3 B2 R5
1/5A
50-60
19 4 6 N.C. 5 15 17 16 14 3 2 1
Uo
50-60
PROGR. R5 INT.FAULT
C SS+
MS - SCE 1621 - R1
KEYBOARD TASTIERA
RS485
38 23 24
20
Display of various parameters, trip count & trip data on 8 digit alphanumeric display Separate LEDs for various fault indication Four user programmable output relays Built in self supervision & self testing feature help maintainance Easy operation by 5 push buttons RS 485 Port for serial communication with MSCOM User friendly software
m 4m m 20 24m 2
158mm
121mm
Model
Description Device Code Design Functions Available
UFD34
3 Ph Voltage & Freq. Relay 81, 27, 59, df/dt, de/dt Numeric Frequency-4 stages selectable as under or over or under/over Voltages - 2 stages selectable Rate of change of frequency protection df / dt - 2 Stages Rate of change of voltage protection de /dt - 1 Stage Blocking function
UM30A
3 Ph Voltage & Freq. Relay 81, 27, 59, V/Hz, 59d, 59s, 59Uo Numeric Over exitation-2 stages Frequency-2 stages selectable as under or over or under/over Voltages - 2 stages selectable as under or over Direct Sequence Negative Sequence Zero Sequence - 2 Stages Blocking function 100 - 125V PT input Display of Parameters Built in self supervision RS485 Port Communication Not applicable 0.04 VA 100C to 600C < 2kg 8.5 VA 4 C/O, S/R or H/R or Time del 1 C/O for self supervision Draw out 121 x 158 x 224 113 x 142
UM30A
3 Ph Dir O/C & E/F + Highset 50/67 RYBN, 50 LBB Numeric Low Set Dir O/C Highset Dir O/C Low Set Dir E/F Trip time Char : NI, VI, EI, Def time CB Failure Function Auto Doubling of Highset Blocking Function MTA Setting = 0-359 1 A or 5 A site selectable 100 - 125V PT input Display of Parameters Built in Self supervision RS485 Port Communication 0.2 VA for 5 A, 0.01 VA for 1 A 8.5 VA 100C to 600C < 2kg 0.04 VA 4 C/O, S/R or H/R or Time Del 1 C/O for self supervision Draw out 121 x 158 x 224 113 x 142
100 - 125V PT input Display of Parameters Built in self supervision RS485 Port Communication Burden on CT Not applicable Burden on PT 0.04 VA Operating temp 100C to 600C Weight < 2kg BurdenonAuxiliary 8.5 VA Output Contacts 4 C/O, S/R or H/R or Time del 1 C/O for self supervision Construction Draw out Dim W x H x D in mm 121 x 158 x 224 Panel Cutout 113 x 142
21
Wiring Diagrams
MD32T
A 87T + 87N In1 B C I1A I1B I1C 26
1/5A
25
1/5A
DISPLAY MICROP.
R1
21 10
(21) N.O.
27 V1 V2
V1 V2 Kv = V1 V2
MD32T
FUNCTION
F187T F287T F87N
R2
28 39
1/5A
R3
29
1/5A
R1 R2 R3 R4
R4
I2A
R5
I2B
30 41 31 42 32 43 Z R 33 L/+ 12
1/5A
I2C
B3
1/5A
B2 B1
C SS+
1/5A
50-60
KEYBOARD
IEC 255
N/- 13
9 PIN MALE
IM30T
A B C 25 26 27 28 39 29 41 30 32 43 31 42 33 A B C 25 26 27 28 39 29 41 30 32 43 31 42 33 A B C 25 DISPLAY
1/5A
R1
21 10
(21) N.O.
26 27
1/5A
MICROP. R2
IM30T
FUNCTION R3
28 39 29 41 30 32 43 31 42 33
1/5A
1/5A
BT 2 50
R1 R2 R3 R4
R4
R5
RT
14 3 2 1
C SS+
44 In = 5A In = 1A L/+ 12
IEC 255
PROGR. INT.FAULT
_
BIO
R5
BIF
N/- 13
KEYBOARD
34/38 23 24
9 PIN MALE
UM30SV
25 DISPLAY 26 B 27 28 39 29 41 30 MICROP. 21 10 11 22 7 9 8 18 20 19 4 6 5 15 17 16 14 3 2 1 38 23 24 (21) N.O. N.C. (10) N.O. N.C.
R1
UM30SV
FUNZIONI FUNCTION F27/59 F27d/59d F59s F59Uo R3 R4 F81 Uo R1 R2
R2
R3
R4
EA UC EC UA EB
12 AUXILIARY SUPPLY 13
BT 2 50
R5
R5
UB
22
Display of various parameters, trip count & trip data on 8 digit alphanumeric display Separate LEDs for individual fault indication Four user programmable output relays Built in self supervision & self testing feature help maintainance Easy operation by 5 push buttons RS 485 Port for serial communication with MSCOM User friendly software
121mm
158mm
m 4m m 20 24m 2
Model
Description Device Code Design Functions Available
MD32T
Transformer Differential + Restricted E/F 87 RYB, 87N Numeric Lowset Differential Lowset Op time : <=30mS Highset Differential Highset Op time : 6-20mS Restricted Earth Fault Dual slope Bias Highset can be Biased / Unbiased 2nd harmonic restraint setting 5th harmonic restraint setting Auto correction of CT Ratio Zero sequence compensation Blocking Function Display of parameters Built in self supervision RS485 Port 1 A OR 5 A site selectable Waveform capture feature 0.2 VA for 5 A, 0.01 VA for 1 A 100C to 600C < 2kg 8.5 VA 5 C/O, S/R or H/R or Time del Draw out 121 x 158 x 224 113 x 142 20-110V AC / DC
IM30T
3 Ph O/C, E/F + Thermal 50/51 RYBN, 49, 46, I2t Numeric Lowset O/C Highset O/C Lowset E/F Highset E/F Thermal Overload Lowset current unbalance with Definate / Inverse time tripping Highset current unbalance Inrush Energy protection CB Failure function Blocking function Display of Parameters Built in self supervision RS485 Port 1 A OR 5 A site selectable 0.2 VA for 5 A, 0.01 VA for 1 A 100C to 600C < 2kg 8.5 VA 5 C/O, S/R or H/R or Time del Draw out 121 x 158 x 224 113 x 142 20-110V AC / DC
UM30SV
3 ph voltage and frequency relay 24, 27d/59d, 47, 59, 59Uo, 78, 81 Over Fluxing O/V + U/V O/F + U/F Zero seq. voltage Voltage unbalanced Vector surge
Other Features
Burden on CT Operating temp Weight Burden on Auxiliary supply Output Contacts Construction Dim W x H x D in mm Panel Cutout Auxilary Supply
100C to 600C < 2kg 8.5VA 5% Panel monitoring 121 x 158 x 224 113 x 142 20-110V AC / DC
O R D E R I N G I N F O R M AT I O N
23
Wiring Diagrams
MW33
25 26 27 28 39 29 41
30
1/5A 1/5A
DISPLAY MICROP.
R1
MW33
FUNZIONI FINCTION
R2 R3 R1 R2 R3 R4 R4 R5
1/5A
Un Un
32 43 31 42 33 44
14 3 2
C SS+
In = 5A
In = 1A
Un = 100V
L/+12 L/- 13
9 PIN MALE
IEC 255
MU30
29
1/5A
DISPLAY MICROP.
1/5A
R1
21 10
(21)
30 41 31 42 32 43
MU30
FUNCTION U I F P.F. P/E S Q/R R1 R2 R3 R4
R2
1/5A
R3
R4
R5
14 PROGR. R5 OMT.FAULT 3 2
KEYBOARD
34/38 23 24
9 PIN MALE
IEC 255
IM30-DRE
A B C 25 26 27 28 39 29 30 41 A B C 25 26 27 28 39 29 30 41 A B C 25
1/5A
DISPLAY MICROP.
R1
21 10
(21) N.O.
26 27
1/5A
IM30-DRE
FUNZIONI FUNCTION
R2
11 22 7 N.C. 9
(10)
28 39 29
1/5A
R3
8 18 N.O. 20 19 N.C. 4 6 5 15 17 16 14 3 2 1
C S S+
30 41
1/5A
R1 R2 R3 R4
R4
31 42 32 43 33
31 42 32 43 33
31 42 32 43 33
R5
BIR
1/5A
BT 2 50
PROGR. R5 INT.FAULT
BI C/B
12 13
KEYBOARD TASTIERA
38 23 24
9 PIN MALE
CE
MS-SCE 1573-R0
In=5A In=1A
24
Display of various parameters, event count & event data on 8 digit alphanumeric display Separate LEDs for various fault indication Four user programmable output relays Built in self supervision & self testing feature help maintainance Easy operation by 5 push buttons RS 485 Port for serial communication with MSCOM User friendly software
m 4m m 20 24m 2
158mm
121mm
Model
Description Device Code Design Functions Available
MW33
Power management 81, 27, 59, PF, P, QL, QC Numeric Frequence 2 stages, Voltage 2 stage, Power factor 2 stage, Active power 2 stage, Capacitor reactive power 2 stage. Actual measurement of Freq, V, I, PF, active power, reactive power. Display of parameters MD recording & data logging RS485 Port, Event recording O.2 VA for 5 A, 0.01 VA for 1 A 0.04 VA 100C to 600C < 2kg 8.5 VA max 5 C/O Draw out 121 x 158 x 224 113 x 142 20-110V AC / DC 88-264V AC / DC
MU30
Measurment Measure Numeric Actual measurements of Freq, I, V, PF, Power - Active / Reactive / Apparent Energy - Active / Reactive Maximum Demand Display of Parameters Record of last event RS485 Port, Event recording, Event counter, MD recording, Oscillographic wave form capture 0.2 VA for 5 A, 0.01 VA for 1 A 0.04 VA 100C to 600C < 2kg 8.5 VA max 5 C/O Draw out 121 x 158 x 224 113 x 142 20-110V AC / DC 88-264V AC / DC
Other Features
Display of Parameters Last trip data RS485 Port 0.2 VA Not Applicable
Burden on CT Burden on PT Operating temp Weight Burden on Auxiliary supply Output Contacts Construction Dim W x H x D in mm Panel Cutout Auxiliary supply Type 1 Type 2
100C to 600C < 2kg 8.5 VA 5 C/O Draw out 121 x 158 x 224 113 x 142 20-110V AC / DC 88-264V AC / DC
O R D E R I N G I N F O R M AT I O N
25
Wiring Diagrams
MC30
4 5 6 7 8 9
1/5A 1/5A 1/5A
DISPLAY MICROP.
R1 R2 R3 R4
R1 R2 R3
MC30
FUNZION FUNCTIONS F50 F51 F50N F51N R1 R2 R3
1/5A
D3 D2 D1
D3 D2 D1
20 21 19 22
L H C
R4 PROGR. INT.FAULT
In=
1A
5A
AUXILARY SUPPLY
10 11
RS232
KEYBOARD TASTIERA
C A (S+) B (S-)
3 2 1
RS485
A (S+) B (S-)
MC20-R
6 7
6 7
1/5A
DISPLAY MICROP.
R1 R2 R3 R4
R1 R2 R3
MC20-R
4 5 8 9 4 5 8 9
1/5A 1/5A
D3
In = Ion =
1A 1A
5A 5A Auxilariy supply10 11
MS-SCE2021-RO
D3 D2
D1
20 21 19 22
D2 D1
20 21 19 22
H L C
A (S+) B (S-)
C A (S+) B (S-)
3 2 RS-485 1
RPM-8
Ph 230V AC 1 2 3 ALARM 4 5 6 S1(5A) S1(1A) S2 7 8 9 10 11 12 13 14 15 16 R8 R7 R6 R5 R4 R3 R2 R1 17 18 19 20 21 22 23 24 BANK #1 R Y B N TO LOAD BANK #8 50 Hz N
+ + -
26
158mm
m 4m m 20 24m 2
121mm
Model
Description Device Code Design Functions Available
IM30AB
MC30
3 Phase OC + EF relay with thermal image element 50/51, 50N/51N, 51BF Numeric 3 Phase fault levels 3 Earth fault levels 1 Thermal image element breaker failure protection (LBB) 1 A or 5 A site selectable Time tagged multiple event recording Oscillographic wave form capture Blocking O/Ps and Inputs for better coordination 16 (8x2) character LCD display
MC20-R
3 Phase OC + EF relay with Autoreclosing 50/51, 50N/51N, 51BF, 79 Numeric 3 Phase fault levels 3 Earth fault levels 4 Shots programmable reclosing Reclosure sequence coordination breaker failure protection (LBB) 1 A or 5 A site selectable Time tagged multiple event recording Oscillographic wave form capture Blocking O/Ps and Inputs for better coordination 16 (8x2) character LCD display 1 Rip circuit breaker control via serial port RS232 and RS485 Ports available Modbus RTU / IEC 870-5-103 communication protocol 0.1VA for 1 A CT & 0.3VA for 5 A CT NA < 7VA -100C to 550C 4 N/O Draw out 83 x 164 x 225 62 x 142 24-110V AC or 24-125V DC 80-220V AC or 90-250V DC
Do not change RS232 and RS485 Ports available Modbus RTU / IEC 870-5-103 communication protocol Burden on CT Burden on PT Burden on Aux. Supply Operating Temp Weight Output Contacts Construction Dim Panel Cutout Aux. Supply Type 1 Type 2 0.1VA for 1 A CT & 0.3VA for 5 A CT NA < 7VA -100C to 550C 4 N/O Draw out 83 x 164 x 225 62 x 142 O R D E R I N G I N F O R M AT I O N 24-110V AC or 24-125V DC 80-220V AC or 90-250V DC
27
Notes
Notes
For selection and product demonstration, please contact any of our branch offices listed below:
REGISTERED OFFICE AND HEAD OFFICE L&T House, Ballard Estate P. O. Box 278 Mumbai 400 001 Tel: 022-67525656 Fax: 022-67525858 Website: www.Larsentoubro.com ELECTRICAL STANDARD PRODUCTS (ESP) 501, Sakar Complex Opp. Gandhigram Rly. Station Ashram Road Ahmedabad 380 009 Tel: 079-66304007-11, 55304000/1 Fax: 079-26580491 e-mail: esp-ahm@Lntebg.com 38, Cubbon Road, Post Box 5098 Bangalore 560 001 Tel: 080-25020100 / 25583613 Fax: 080-25580525 e-mail: esp-blr@Lntebg.com 131/1, Zone II Maharana Pratap Nagar Bhopal 462 011 Tel: 0755-6454906 / 7 / 8 / 9 Fax: 0755-2769264 e-mail: esp-bho@Lntebg.com Plot No. 559, Annapurna Complex Lewis Road Bhubaneswar 751 014 Tel: 0674-2537301, 2436696 Fax: 0674-2537309 e-mail: esp-bbi@Lntebg.com SCO 32, Sector 26-D Madhya Marg, P. O. Box 14 Chandigarh 160 026 Tel: 0172-4646841 / 2 / 3 / 4 / 5 / 6 / 7 Fax: 0172-4646802 e-mail: esp-chd@Lntebg.com 10, Club House Road Chennai 600 002 Tel: 044-28462072 / 4 Fax: 044-28462102 e-mail: esp-maa@Lntebg.com 67, Appuswamy Road Post Bag 7156 Opp. Nirmala College Coimbatore 641 045 Tel: 0422-2588120, 2588121 / 3 Fax: 0422-2588148, e-mail: esp-cbe@Lntebg.com
L&T House Group MIG - 5 Padmanabhpur Durg 491 001 Tel: 0788-2213833 / 14 / 28 / 29 Fax: 0788-2213820 A1/11, Astronauts Avenue Bidhan Nagar Durgapur 713 212 Tel: 0343-2536493 / 39 Fax: 0343-2536493 e-mail: esp-dgp@Lntebg.com (Faridabad Switchgear Works) 12/4, Delhi-Mathura Road Faridabad 121 003 Tel: 0129-2565147 / 8 Fax: 0129-2275405 e-mail: esp-fbd@Lntebg.com Milanpur Road, Bamuni Maidan Guwahati 781 021 Tel: 0361-2550565 Fax: 0361-2551308 e-mail: esp-gau@Lntebg.com 5-10-173, Fateh Maidan Road P. O. Box 12 Hyderabad 500 004 Tel: 040-66720251 Fax: 040-23242356 e-mail: esp-hyd@Lntebg.com D-24, Prithvi Raj Road C-Scheme Jaipur 302 001 Tel: 0141-2377374 / 2361064 Fax: 0141-2373280 e-mail: esp-jai@Lntebg.com Akashdeep Plaza, 2nd Floor P. O. Golmuri Jamshedpur 831 003 Jharkhand Tel: 0657-2340864, 2340308 Fax: 0657-2341250 e-mail: esp-jam@Lntebg.com Skybright Bldg. M. G. Road Ravipuram Junction Ernakulam Kochi 682 016 Tel: 0484-4409422 / 23 / 24 / 25 / 26 / 27 Fax: 0484-4409430 e-mail: esp-cok@Lntebg.com 3-B, Shakespeare Sarani Kolkata 700 071 Tel: 033-44002301 / 2 / 3 / 4 / 5, 44002572 Fax: 033-22821025 e-mail: esp-ccu@Lntebg.com
A28,Indira Nagar Faizabad Road Lucknow 226 016 Uttar Pradesh Tel: 0522-4040905 / 903 / 904 Fax: 0522-2311671 e-mail: esp-Lko@Lntebg.com Plot No. 518 4th Main Road K. K. Nagar Madurai 625 020 Tel: 0452-2537404 / 303 Fax: 0452-2537552 e-mail: esp-mdu@Lntebg.com North Wing, Level II, Gate 7, Powai Mumbai 400 072 Tel: 022-67050505 Fax: 022-67051112 e-mail: esp-bom@Lntebg.com 8B, Farmland, Ramdaspeth Behind Hotel Radhika Nagpur 440 010 Tel: 0712-2420641 / 24 Fax: 0712-2420619 e-mail: esp-ngp@Lntebg.com 32, Shivaji Marg, P.O. Box 6223 New Delhi 110 015 Tel: 011-51419500 / 1 , 51419515 Fax: 011-51419600 e-mail: esp-del@Lntebg.com L&T House, P.O. Box 119 191/1, Dhole Patil Road Pune 411 001 Tel: 020-66033395 / 88 / 89 Fax: 020-26129586 e-mail: esp-pnq@Lntebg.com 3rd Floor, Vishwakarma Chambers Majura Gate, Ring Road Surat 395 002 Tel: 0261-2473726 Fax: 0261-2477078 e-mail: esp-sur@Lntebg.com Radhadaya Complex Old Padra Road Near Charotar Society Vadodara 390 015 Tel: 0265-6613611 Fax: 0265-2336184 e-mail: esp-bar@Lntebg.com 48-8-16, Dwarakanagar Visakhapatnam 530 016 Tel: 0891-2755493, 2704928 Fax: 0891-2746075 e-mail: esp-viz@Lntebg.com
Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.
SP 50297 R1
210507