technical data

air conditioning systems


RYP-L7/B7 Twin/Triple/ Double Twin Application

Split Sky Air

Split - Sky Air

ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment

Daikin units comply with the European regulations that guarantee the safety of the product.

Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.

Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory.

Specifications are subject to change without prior notice.

Zandvoordestraat 300 B - 8400 Ostend Belgium Internet: http://www.daikineurope.com

EEDE05-1/2 05/2005 Prepared in Belgium by Goekint Graphics

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

TABLE OF CONTENTS RYP-L7/B7


1 2 Features 2 3

.................................................................................

Specifications

.......................................................................

Technical specifications Electrical specifications

3 4 5 6 7 8 9

Combination table Capacity tables

.............................................................

5 7 10 10 11 14 14

...................................................................

Dimensional drawings Operation range Piping diagrams Wiring diagrams Sound level

.....................................................

.................................................................

..................................................................

.................................................................

..........................................................................

Sound level data Sound pressure spectrum

10

Accessories

..........................................................................

14

Standard accessories Optional accessories

11 12 13

Center of gravity

................................................................

14 14 15

Safety device settings Installation

......................................................

............................................................................

Split - Sky Air Outdoor Units

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

Features

1
1

Outdoor units for twin/triple/double application. + It is possible to connect 2, 3 or 4 indoor units to one single outdoor unit. The indoor units can be of different types (e.g. ceiling mounted cassette, wall mounted, ...) and even different capacities. All indoor units operate within the same mode (cooling or heating) from one remote control. This allows an equal air distribution in larger rooms, even if they are irregularly shaped. + Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an outside wall. + They are fitted with a scroll compressor, renowned for low noise and high energy efficiency. + The piping connections can be accessed from underneath, front, side or rear. + The service valves are hidden inside the casing. + A special acryl precoated fin for anti-corrosion treatment on the heat exchanger ensures greater resistance against severe weather conditions.

Split - Sky Air Outdoor Units

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

Specifications

1
TECHNICAL SPECIFICATIONS
OUTDOOR UNITS DIMENSIONS Unit H W D mm mm mm kg

WEIGHT MATERIAL COLOUR SOUND LEVEL

FAN

HEAT EXCHANGER

REFRIGERANT CIRCUIT

Unit Unit Sound pressure (1) high (cooling/heating) Sound power (2) high (cooling) Air flow rate high (cooling/heating) Speed steps Qty x model Qty x motor output Type Rows x stages x fin pitch Face area Refrigerant type Refrigerant charge Minimum/maximum allowable distance between indoor and outdoor Maximum allowable level difference Additional refrigerant charge Refrigerant control Type Qty x model Motor output x no Speed Oil type Oil charge volume Crankcase heater

dB(A) dB(A) m /min


3

RYP71L7V1/W1 RYP100L7V1/W1 RYP125L7W1 RYP200B7W1 770 1,170 1,220 900 900 1,290 320 320 700 80/79 102/101 106 196 Painted galvanised steel plate Ivory white 50/52 53/56 53/56 57/57 63 48/43 1xP47L11S 66 55/50 3 steps 67 89/80 2xP47L11S 85 + 65 77/78 170/-

RYP250B7W1 1,440 1,290 700 210

57/57 77/78 175/-

W mm m2 kg m m g/m

1 x 90 Hi-XSS cooling tube, non sym. waffle fin 2 x 34 x 2.0 2 x 52 x 2.0 2 x 52 x 2.0 0.634 0.983 0.983 R-407C 2.8 3.7 5/70 30 30 30 Please refer to item 13 Installation of this chapter

1 x 65

2 x 40 x 2 1;57 7.5

1 step 1xP55J11F 1 x (230+190) J8 Sealing

2 x 50 x 2 1.97 9.2

-/50 (70 m equivalent)

COMPRESSOR

W rpm ! W mm mm mm

PIPING CONNECTIONS

INSULATION MATERIAL

Heat insulation Safety devices

liquid gas drain

Expansion valve (electronic type) Hermetically sealed scroll type 1xJT90FA-V1N 1xJT125FA-V1NX 1xJT160FA-YE 1xJT23DA-YE@2 1xJT300DA-YE@2 2,200 x 1 3,000 x 1 3,750 x 1 5,500 x 1 7,500 x 1 2,900 2,900 DAPHNE FVC68D 1,200 1,500 4 4 50 72 9.5 12.7 x 0.90 15.9 x 0.95 15.9 19.1 28.6 x 1.15 28.6 x 1.15 26 x 3 26 x 6 26 x 6 Both liquid and gas pipes High and low pressure switch, thermal protection High and low pressure switch, thermal protector for indoor and outdoor fan for indoor and outdoor fan motor, overcurrent motor, overcurrent relay (compressor), reverse phase protector, fuse relay (compressor), fuse
3TW25141-1B 3TW25181-1B 3TW25151-1A 3TW25191-1A 3TW25201-1A 3TW23631-1A 3TW23641-1A

30 30 100 g/m for total piping 140 g/m for total piping length > 30 m length > 30 m Expansion valve

Split - Sky Air Outdoor Units

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

Specifications

1
2
ELECTRICAL SPECIFICATIONS
OUTDOOR UNITS CURRENT Nominal running current Max. running current Starting current Phase Frequency Voltage cooling/heating A cooling/heating A cooling/heating A RYP71L7V1/W1 RYP100L7V1/W1 RYP125L7W1 RYP200B7W1 Please refer to electrical data 14.4/Please refer to electrical data 17.9/Please refer to electrical data V1/W1 V1/W1 W1 W1 1/3N 1/3N 3N 3N 50 50 50 50 230/400 230/400 400 400 RYP250B7W1 17.2/27.5/W1 3N 50 400

POWER SUPPLY NOMINAL DISTRIBUTION SYSTEM VOLTAGE

Hz V

NOTES
1 2 The sound pressure level is measured via a microphone at 1m distance from the unit. It is a relative value, depending on the distance and acoustic environment. For measuring conditions: please refer to item 9 of this chapter. The sound power level is an absolute value indicating the power which a sound source generates.

ELECTRICAL DATA

See chapter RYP-L7/B7 for the electrical data ofRYP71-100-125L7V1/W1RYP200-250B7W1

Split - Sky Air Outdoor Units

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

Combination table

Possible combinations and standard capacity for twin and triple operation
RYP71-125L7
Possible indoor combination Simultaneous operation Twin Outdoor models
In Out

1
3

Triple
Out

In

In

In

In

RYP71L7V1/W1 RYP100L7V1/W1 RYP125L7W1

35-35 (KHRQ22M20T7) 45-45 (KHRQ22M20T7) 60-60 (KHRQ22M20T7) 45-60 (KHRQ22M20T7) 45-71 (KHRQ22M20T7) 35-71 (KHRQ22M20T7) 35-35-35 (KHRP127HB7) 45-45-45 (KHRP127HB7)
3TW25149-3A

NOTES
1 2 3 4 5 6 Possible indoor units: FHYCP35-71, FUYP71, FHYKP35-71, FAYP71, FHYP35-71, FHYBP35-71, FDYMP71 Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room). When different indoor models are used in combination, designate the infrared remote controller that is equipped with the most functions as the main unit. Note 1 mentions the indoor units in order of the possible function (most functions are on FHYCP, less functions are on FDYP). Between brackets are the required Refnet kits mentioned, that are necessary to install the combination. For unit specification of the outdoor units and the indoor units refer to the unit specifications mentioned for pair systems. Nominal cooling capacities are based on the following conditions: Indoor air temperature: 27CDB, 19.0CWB, outdoor temperature 35CDB. Nominal heating capacities are based on the following conditions: Indoor air temperature : 20CDB, outdoor temperature : 7CDB, 6CWB.

Split - Sky Air Outdoor Units

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

Combination table

1
3

Possible combinations for twin, triple and double twin application


RYP200-250B7
Possible indoor combination Simultaneous operation Capacity [kW] Outdoor models Twin
Out
In In

Triple
Out

Double twin
Out

Cooling

Heating

In

In

In

In

In

In

In

RYP200B7W1 RYP250B7W1

19.5 25.0

23.1 27.0

100-100 71-125 71-71-71 60-60-60 45-71-71 45-45-100 35-71-100 35-35-125 45-60-100 71-60-60 (KHRQ22M64T7) (KHRQ22M64T7) (KHRP127HB7) (KHRP127HB7) (KHRP127HB7) (KHRP127HB7) (KHRP127HB7) (KHRP127HB7) (KHRP127HB7) (KHRP127HB7)

45-45-45-45 (2 x KHRQ22M20T7 + KHRQ22M64T7) 60-60-60-60 (2 x KHRQ22M20T7 + KHRQ22M64T7)


3TW23619-1A

125-125 (KHRQ22M64T7)

45-100-100 (KHRP127HB7)

60-60-125 (KHRP127HB7)

125-45-71 (KHRP127HB7)

100-71-71 (KHRP127HB7)

NOTES
1 2 3 4 5 6 Possible indoor units: FHYCP35-125, FUYP71-125, FHYKP35-71, FAYP71-100, FHYP35-60, FHYP71-125, FHYBP35-125, FDYP125. Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room). When different indoor models are used in combination, designate the infrared remote controller that is equipped with the most functions as the main unit. Note 1 mentions the indoor units in order of the possible function (most functions are on FHYCP, less functions are on FDYP). Between brackets are the required Refnet kits mentioned, that are necessary to install the combination. For unit specification of the outdoor units and the indoor units refer to the unit specifications mentioned for pair systems. Nominal cooling capacities are based on the following conditions:Indoor air temperature: 27CDB, 19.0CWB, outdoor temperature 35CDB. Nominal heating capacities are based on the following conditions:Indoor air temperature : 20CDB, outdoor temperature : 7CDB, 6CWB.

Split - Sky Air Outdoor Units

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

Capacity tables

Simultaneous operation RYP71-100-125L7 Cooling capacity V1: 230V [50Hz] W1: 400V [50Hz]

1
4
25 Outdoor temperature (CDB) 32 35 PI TC 2.17 5.5 2.25 5.9 2.25 6.3 2.33 6.8 2.33 7.1 2.33 7.2 2.42 7.9 2.50 8.4 3.13 7.8 3.13 8.4 3.23 8.9 3.23 9.6 3.32 10.0 3.32 10.1 3.42 11.0 3.51 11.6 3.76 9.7 3.85 10.4 3.85 11.1 3.94 11.8 4.04 12.2 4.04 12.4 4.13 13.4 4.23 14.3 40 46

Outdoor

RYP71

RYP100

RYP125

EWB (C) 12.0 14.0 16.0 18.0 19.0 19.5 22.0 24.0 12.0 14.0 16.0 18.0 19.0 19.5 22.0 24.0 12.0 14.0 16.0 18.0 19.0 19.5 22.0 24.0

Indoor

EDB (C) 18.0 20.0 22.0 25.0 27.0 27.0 30.0 32.0 18.0 20.0 22.0 25.0 27.0 27.0 30.0 32.0 18.0 20.0 22.0 25.0 27.0 27.0 30.0 32.0

TC 6.2 6.6 7.2 7.7 8.0 8.0 8.7 9.4 8.4 8.9 10.1 10.8 11.1 11.2 12.2 13.0 11.1 11.8 12.7 13.3 13.6 13.8 15.1 15.9

20

PI 1.75 1.83 1.83 1.92 1.92 1.92 2.00 2.00 2.56 2.66 2.66 2.66 2.66 2.66 2.75 2.85 3.19 3.29 3.29 3.38 3.47 3.47 3.57 3.57

TC 6.1 6.5 7.0 7.5 7.7 7.9 8.5 9.1 8.3 8.8 9.8 10.5 10.8 11.0 11.8 12.7 10.8 11.4 12.1 13.0 13.3 13.5 14.6 15.5

PI 2.00 2.08 2.08 2.08 2.08 2.08 2.17 2.17 2.75 2.75 2.85 2.85 2.94 2.94 2.94 3.04 3.47 3.47 3.57 3.57 3.66 3.66 3.66 3.76

TC 5.7 6.0 6.5 7.2 7.3 7.4 8.0 8.6 8.1 8.7 9.1 9.8 10.1 10.3 11.2 11.9 10.0 10.7 11.4 12.1 12.7 12.8 13.7 14.6

PI 2.33 2.33 2.42 2.50 2.50 2.50 2.58 2.58 3.32 3.32 3.42 3.42 3.51 3.51 3.60 3.70 4.04 4.13 4.23 4.32 4.32 4.32 4.41 4.51

TC 5.3 5.5 6.0 6.4 6.6 6.7 7.4 8.0 7.5 7.8 8.5 9.0 9.4 9.5 10.4 11.1 9.2 9.8 10.4 11.2 11.5 11.7 12.9 13.6

PI 2.58 2.58 2.67 2.67 2.75 2.75 2.75 2.83 3.70 3.70 3.79 3.79 3.89 3.89 3.98 4.08 4.41 4.51 4.60 4.70 4.79 4.79 4.88 4.98

TC 4.9 5.3 5.5 6.0 6.2 6.3 6.8 7.4 6.9 7.5 7.8 8.4 8.7 8.8 9.6 10.3 8.6 9.2 9.7 10.4 10.8 11.0 12.0 12.9

PI 2.83 2.83 2.92 3.00 3.00 3.00 3.08 3.17 4.08 4.08 4.17 4.27 4.36 4.36 4.36 4.46 5.07 5.07 5.17 5.17 5.26 5.26 5.45 5.54

3TW25142-15

SYMBOLS
EWB: EDB: TC: PI o: PI corr1: Entering wet bulb temp. (CWB) Entering dry bulb temp. (CDB) Total capacity cooling (kW) Power input of outdoor unit (kW) Correction factor for Pi depending on voltage of outdoor (kW) PI corr2: Correction factor for Pi depending used indoor units (kW) PI: Total power input (kW) PI = PI o + PI corr1 + PI corr2 e.g. RYP100L7V1 + FHYBP71B7V1 + FHYP35B7V1 PI = 3.5 + 0.23 + 0.21 + 0.14 = 4.08 kW Caution: TC and SHC are shown by kW

NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. Shows nominal capacities 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on following conditions: Corresponding refrigerant piping length: 7.5 m Level difference: 0m 5. Add the following correction to the power input for the different outdoor units (PI corr1)

Outdoor model RYP71 RYP100

Power supply V1 W1 0.07 0 0.23 0

6. Add the following correction to the power input for each connected indoor unit (PI corr2)

Indoor model 35 45 60 71

FHYBP 0.12 0.16 0.21 0.21

FH(Y)P 0.14 0.14 0.14 0.14

FHYCP 0.14 0.14 0.16 0.16

Indoor types FHYKP 0.046 0.069 0.12 0.12

FAYP

FUYP

0.069

0.16

FDYMP 0.12 0.16 0.21 0.21

NOTE: The total capacity does not change with different combination of indoor units.

Split - Sky Air Outdoor Units

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

Capacity tables

1
4

Simultaneous operation RYP71-100-125L7 Heating capacity V1: 1230V [50Hz] W1: 3400V [50Hz]

Outdoor

RYP71

RYP100

RYP125

Indoor EDB (C) 16.0 18.0 20.0 22.0 24.0 16.0 18.0 20.0 22.0 24.0 16.0 18.0 20.0 22.0 24.0

TC 6.3 6.3 6.3 6.3 6.3 8.5 8.4 8.4 8.4 8.3 11.1 11.1 11.1 11.1 10.9

-10

PI 2.25 2.25 2.41 2.41 2.50 3.01 3.11 3.30 3.39 3.49 3.99 4.09 4.29 4.39 4.49

TC 6.7 6.7 6.7 6.7 6.7 9.3 9.2 9.1 9.1 9.1 12.0 12.0 11.8 11.8 11.8

-5

PI 2.33 2.33 2.41 2.50 2.58 3.11 3.20 3.39 3.49 3.58 4.19 4.29 4.49 4.59 4.69

TC 7.4 7.4 7.3 7.3 7.3 10.1 10.1 10.0 10.0 9.8 12.9 12.9 12.8 12.8 12.7

Outdoor temperature (CDB) PI 2.33 2.41 2.50 2.58 2.66 3.20 3.30 3.49 3.58 3.67 4.29 4.39 4.69 4.69 4.89 TC 8.1 8.0 8.0 8.0 7.9 11.2 11.1 11.0 11.0 10.8 14.1 14.0 14.0 14.0 13.9

PI 2.41 2.50 2.58 2.66 2.75 3.30 3.39 3.58 3.67 3.77 4.39 4.59 4.79 4.89 4.99

TC 8.6 8.6 8.6 8.6 8.6 11.9 11.9 11.7 11.7 11.5 15.0 14.9 14.8 14.8 14.8

10

PI 2.41 2.50 2.66 2.66 2.75 3.39 3.49 3.67 3.77 3.86 4.59 4.69 4.89 4.99 5.19

TC 9.3 9.1 9.1 12.7 12.6 12.6 16.0 16.0 15.8

15

PI 2.75 2.75 2.83 3.77 3.86 3.96 5.09 5.19 5.39

3TW25142-16

SYMBOLS
EWB: EDB: TC: PI o: PI corr1: Entering wet bulb temp. (CWB) Entering dry bulb temp. (CDB) Total capacity cooling (kW) Power input of outdoor unit (kW) Correction factor for Pi depending on voltage of outdoor (kW) PI corr2: Correction factor for Pi depending used indoor units (kW) PI: Total power input (kW) PI = PI o + PI corr1 + PI corr2 e.g. RYP100L7V1 + FHYBP71B7V1 + FHYP35B7V1 PI = 3.6 + 0.23 + 0.21 + 0.14 = 4.18 kW Caution: TC and SHC are shown by kW

NOTES
1. Ratings shown are net capacities. Influence of fan motor heat is included. 2. Shows nominal capacities 3. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7 CDB/6 CWB (heating) Corresponding refrigerant piping length: 7.5 m Level difference: 0m 4. Direct interpolation is permissible. Do not extrapolate. 5. Add the following correction to the power input for the different outdoor units (PI corr1)

Outdoor model RYP71 RYP100

Power supply V1 W1 0.07 0 0.23 0

6. Add the following correction to the power input for each connected indoor unit (PI corr2)

Indoor model 35 45 60 71

FHYBP 0.12 0.16 0.21 0.21

FH(Y)P 0.14 0.14 0.14 0.14

FHYCP 0.14 0.14 0.16 0.16

Indoor types FHYKP 0.046 0.069 0.12 0.12

FAYP

FUYP

0.069

0.16

FDYMP 0.12 0.16 0.21 0.21

NOTE: The total capacity does not change with different combination of indoor units.

Split - Sky Air Outdoor Units

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

Capacity tables

Simultaneous operation RYP200-250B7W1 Cooling capacity W1: 400V [50Hz]

1
4
TC 16.8 17.9 19.2 20.4 21.1 23.2 24.6 21.5 23.0 24.6 26.2 27.0 29.7 31.6 25 PI o 5.81 5.92 6.02 6.13 6.24 6.45 6.56 7.01 7.11 7.22 7.33 7.44 7.66 7.77 TC 15.8 16.9 18.1 19.3 20.0 22.0 23.4 20.2 21.7 23.2 24.8 25.6 28.2 30.0 Outdoor temperature (CDB) 32 35 PI o TC 6.67 15.4 6.78 16.5 6.88 17.7 6.99 18.9 7.10 19.5 7.31 21.5 7.42 22.9 7.98 19.7 8.09 21.2 8.20 22.7 8.42 24.2 8.42 25.0 8.74 27.6 8.85 29.4 PI o 7.10 7.21 7.31 7.42 7.53 7.75 7.96 8.42 8.53 8.74 8.85 8.96 9.29 9.39 TC 14.8 15.9 17.0 18.2 18.8 20.7 22.1 18.9 20.3 21.8 23.3 24.1 26.5 28.3 40 PI o 7.85 7.96 8.07 8.28 8.28 8.61 8.71 9.39 9.50 9.61 9.83 9.94 10.15 10.37 TC 14.1 15.1 16.2 17.4 17.9 19.8 21.1 18.0 19.4 20.8 22.3 23.0 25.4 27.1 46 PI o 8.93 9.04 9.14 9.36 9.47 9.68 9.90 10.59 10.81 10.91 11.13 11.24 11.57 11.78

Outdoor

RYP200

RYP250

EWB (C) 12 14 16 18 19 22 24 12 14 16 18 19 22 24

Indoor

EDB (C) 18 20 22 25 27 30 32 18 20 22 25 27 30 32

TC 17.5 18.7 20.0 21.3 21.9 24.1 25.6 22.4 24.0 25.6 27.2 28.1 30.9 32.8

20

PI o 5.38 5.49 5.59 5.70 5.70 5.92 6.02 6.35 6.46 6.57 6.68 6.79 7.01 7.11

3TW23612-2B

SYMBOLS
EWB: EDB: TC: PI o: PI corr: PI: Entering wet bulb temp. Entering dry bulb temp. Total capacity cooling Power input of outdoor unit Correction factor for Pi depending used indoor units Total power input PI = PI o + PI corr e.g. RYP200B7W1 + FHYP100 + FHYCP100 PI = 7.43 + 0.16 + 0.2 = 7.79 kW (CWB) (CDB) (kW) (kW) (kW) (kW)

NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. Shows nominal capacities 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on following conditions: Corresponding refrigerant piping length: 7.5 m Level difference: 0m 5. Add the following correction to the power input for the different outdoor units (PI corr1)

Caution: TC and SHC are shown by kW

Indoor model 35 45 60 71 100 125

FHYBP 0.13 0.14 0.17 0.18 0.22 0.29

FHYP 0.09 0.09 0.1 0.1 0.16 0.18

FHYCP 0.14 0.14 0.16 0.16 0.2 0.24

Indoor types FHYKP 0.08 0.08 0.105 0.105

FAYP

FDYP

FUYP

0.05 0.06

0.7

0.14 0.23 0.23

Split - Sky Air Outdoor Units

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

Capacity tables

1
4

Simultaneous operation RYP200-250B7W1 Heating capacity W1: 400V [50Hz]

Outdoor

RYP200

RYP250

EWB (C) 9 11 12 13 14 15 9 11 12 13 14 15

Indoor

EDB (C) 16 18 20 21 22 24 16 18 20 21 22 24

TC 15.0 14.8 14.6 14.5 14.4 14.2 17.6 17.3 17.1 16.9 16.8 16.6

-10

PI o 5.34 5.45 5.67 5.67 5.78 5.99 6.22 6.33 6.55 6.65 6.76 6.98

TC 16.7 16.6 16.3 16.2 16.0 15.8 19.5 19.4 19.1 18.9 18.7 18.4

-5

PI o 5.34 5.56 5.67 5.78 5.89 6.10 6.22 6.44 6.65 6.76 6.87 7.09

TC 19.5 19.4 19.3 19.3 19.3 19.3 22.9 22.7 22.6 22.6 22.5 22.5

Outdoor temperature (CDB) PI o 5.67 5.78 5.99 6.10 6.21 6.43 6.55 6.76 6.98 7.09 7.30 7.52 TC 23.4 23.2 23.1 23.0 23.0 22.9 27.3 27.1 27.0 26.9 26.9 26.8

PI o 5.99 6.21 6.43 6.54 6.65 6.87 6.98 7.30 7.52 7.63 7.74 8.06

TC 26.4 26.2 26.0 26.0 25.9 25.8 30.8 30.6 30.4 30.3 30.3 30.2

10

PI o 6.32 6.54 6.76 6.87 7.08 7.30 7.41 7.63 7.95 8.06 8.28 8.49

TC 30.0 29.9 29.8 29.7 35.0 34.9 34.9 34.8

15

PI o 7.30 7.41 7.52 7.85 8.60 8.71 8.82 9.25

3TW23612-3B

SYMBOLS
EWB: EDB: TC: PI o: PI corr: PI: Entering wet bulb temp. Entering dry bulb temp. Total capacity cooling Power input of outdoor unit Correction factor for Pi depending used indoor units Total power input PI = PI o + PI corr e.g. RYP200B7W1 + FHYP100 + FHYCP100 PI = 6.43 + 0.16 + 0.2 = 6.79 kW (CWB) (CDB) (kW) (kW) (kW) (kW)

NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. Shows nominal capacities 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on following conditions: Corresponding refrigerant piping length: 7.5 m Level difference: 0m 5. Add the following correction to the power input for the different outdoor units (PI corr1)

Caution: TC and SHC are shown by kW

Indoor model 35 45 60 71 100 125

FHYBP 0.13 0.14 0.17 0.18 0.22 0.29

FHYP 0.09 0.09 0.1 0.1 0.16 0.18

FHYCP 0.14 0.14 0.16 0.16 0.2 0.24

Indoor types FHYKP 0.08 0.08 0.105 0.105

FAYP

FDYP

FUYP

0.05 0.06

0.7

0.14 0.23 0.23

Dimensional drawings
See chapter RYP-L7/B7 for the dimensional drawings of RYP71-100-125L7V1/W1RYP200-250B7W1

Operation range
See chapter RYP-L7/B7 for the operation range of RYP71-100-125L7V1/W1RYP200-250B7W1

10

Split - Sky Air Outdoor Units

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

Piping diagrams
See chapter RYP-L7/B7 for the piping diagrams of RYP71-100-125L7V1/W1RYP200-250B7W1

1
7
Electronic expansion valve

Twin application RYP71-125L7


Indoor heat exchanger Solenoid valve

One way valve

One way valve

Filter

Filter One way valve Fan Strainer One way valve

Heat exchanger

Field piping Field piping Indoor unit

Receiver Service port 1/4 One way valve

Indoor heat exchanger

4-way valve

Filter

Low pressure switch

High pressure switch

Muffler

branch pipe (option) Fan

Field piping JA C12207-0 Field piping JB C1220T-0 Compressor


Service port 1/4 flare

Field piping Field piping Indoor unit Stop valve (with service port 1/4 flare)

Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.

Outdoor unit

Heating Cooling

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

A 9.5 9.5

B 15.9 19.1

Model RYP71 RYP100,125

3TW25155-2

Twin application RYP200-250B7W1


Indoor heat exchanger One way valve One way valve Outdoor heat exchanger

One way valve

One way valve

Propeller fan Solenoid valve Fan Field piping Field piping Electronic expansion valve Filter Receiver

One way valve

Indoor unit Indoor heat exchanger Field piping JA branch pipe (option) Field piping JB Low pressure switch High pressure switch Muffler Filter

Service port 1/4 flare

Compressor Fan Field piping Field piping Indoor unit Stop valve (with service port 1/4 flare) Outdoor unit

A 12.7 15.9

B 28.6 28.6

Model RYP200 RYP250

Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

3TW23635-2

Split - Sky Air Outdoor Units

11

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

Piping diagrams
See chapter RYP-L7/B7 for the piping diagrams of RYP71-100-125L7V1/W1RYP200-250B7W1

1
7

Triple application RYP100-125L7


Indoor heat exchanger Indoor unit Solenoid valve Electronic expansion valve

One way valve

One way valve

Filter

Fan

Stop valve Field piping Field piping Indoor unit (with service port 1/4 flare)

Filter One way valve One way valve

Heat exchanger

Strainer

Indoor heat exchanger

Receiver Service port 1/4 One way valve

Field piping J9.5 Fan C12207-0 Field piping Field piping Field piping J19.1 C1220T-0 Filter

4-way valve Low pressure switch High pressure switch

Muffler

Indoor heat exchanger

Indoor unit branch pipe (option)

Service port 1/4 flare

Compressor

Outdoor unit

Heating Cooling

Fan

Field piping Field piping

Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

3TW25155-3

Triple application RYP200-250B7W1


Indoor heat exchanger Indoor unit One way valve One way valve Outdoor heat exchanger

One way valve Fan Field piping Field piping Indoor unit Solenoid valve

One way valve

Propeller fan

Receiver

Indoor heat exchanger

Filter

Electronic expansion valve

Filter

One way valve Service port 1/4 flare

Fan

Field piping Field piping Field piping JA Indoor heat exchanger branch pipe (option) Field piping JB

Filter Low pressure switch

Muffler

High pressure switch

Compressor Stop valve (with service port 1/4 flare) Fan Field piping Field piping Indoor unit Outdoor unit

A 12.7 15.9

B 28.6 28.6

Model RYP200 RYP250

Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

3TW23635-3

12

Split - Sky Air Outdoor Units

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

Piping diagrams
See chapter RYP-L7/B7 for the piping diagrams of RYP71-100-125L7V1/W1RYP200-250B7W1

1
7
One way valve One way valve Outdoor heat exchanger

Double twin application RYP200-250B7

Indoor heat exchanger

Indoor unit

Field piping JC Fan Indoor heat exchanger Field piping JA Indoor unit One way valve One way valve

Field piping J9.5

Solenoid valve Receiver Filter Electronic expansion valve Field piping JA

Propeller fan

Field piping J19.1

Field piping JC Fan Indoor heat exchanger Field piping JA Indoor unit branch pipe (option) Field piping JB

Filter One way valve Service port 1/4 flare

Filter Low pressure switch

Muffler High pressure switch

Field piping JC Fan Indoor heat exchanger Field piping JA Indoor unit Field piping J9.5 Field piping J19.1 Stop valve

(with service port 1/4 flare)

Compressor Outdoor unit

Field piping JC Fan Field piping JA

A 12.7 15.9

B 28.6 28.6

C 6.4 9.5

Model RYP200 RYP250

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

3TW23635-4

Split - Sky Air Outdoor Units

13

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

Wiring diagrams
See chapter RYP-L7/B7 for the wiring diagrams of RYP71-100-125L7V1/W1RYP200-250B7W1

1
8

9 10 11 12

Sound level
See chapter RYP-L7/B7 for the sound levels ofRYP71-100-125L7V1/W1RYP200-250B7W1

Accessories
See chapter RYP-L7/B7 for the accessories of RYP71-100-125L7V1/W1RYP200-250B7W1

Center of gravity
See chapter RYP-L7/B7 for the centre of gravity of RYP71-100-125L7V1/W1RYP200-250B7W1

Safety device settings


See chapter RYP-L7/B7 for the safety device settings of RYP71-100-125L7V1/W1RYP200-250B7W1

14

Split - Sky Air Outdoor Units

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

13

Installation
(B) In case obstacles exist only in front of outlet side

RYP71-125L7
The numerical figures used here represent the dimensions for the models RYP71 to RYP25. The figures inside () indicate the dimensions for the models RYP100 and RY125. (Unit: mm) The figures inside < > indicate the dimension of discharge grille when it is installed facing downward When installing multiple units in lateral connection, discharge grille cannot be set to discharge air in Left/Right direction

13

+ Where there are no obstacles above the unit. 1 Installation of single unit + In case obstacles exist only in front of outlet side.

(A) In case obstacles exist in front of the air inlet + Where there are no obstacles above the unit 1 Installation of single unit + In case obstacles exist only in front of the air inlet. + In case obstacles exist in front of the air inlet and on both sides of the unit.
100 or more 100 or more

Installation of multiple units in lateral connection (2 units or more).

150 or more 20 mm or more 20 mm or more

50 or more (100)

+ Where there are obstacles above the unit. 1 Installation of single unit + In case obstacles exist only in front of outlet side.

1000 mm or more

500 or less

100 or more

2 Installation of multiple units in lateral connection (2 units or more).

100 or more

20 mm or more 20 mm or more

+ In case obstacles exist in front of the air inlet and on both sides of the unit.

1000 mm or more

Installation of multiple units in lateral connection (2 units or more).


20 mm or more

500 mm or more

500 or less 20 mm or more 200 or more (300) 1000 mm or more

+ Where there are obstacles above the unit. 1 Installation of single unit + In case obstacles exist only in front of the air inlet.

500 or less 1000 mm or more 100 or more 500 or less 1000 mm or more

+ In case obstacles exist only in front of outlet side.


20 mm or more

1000 mm or more

+ In case obstacles exist in front of the air inlet and on both sides of the unit.

(C) In case obstacles exist in front of both the air inlet and outlet sides. Where obstacle in front of the air outlet is higher than the unit.
50 or more (100) 500 or more (1000)

Pattern 1
150 or more

150 or more

150 or more

2 Installation of multiple units in lateral connection (2 units or more).

500 or less 20 mm or more

+ Where there are no obstacles above the unit. 1 Installation of single unit. Installation of multiple units in lateral connection (2 units or more).
1000 mm or more

20 mm or more 20 mm or more

1000 mm or more

2
20 mm or more 200 or more (300) 200 mm or more

+ In case obstacles exist in front of the air inlet and on both sides of the unit.

200 or more (300) 1000 or more (1500)

DU427-826

Split - Sky Air Outdoor Units

15

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

13
13

Installation
2
500 or less

+ Where there are obstacles above the unit.

Installation of multiple units in lateral connection (2units or less).


500 or less 1000 mm or more

Installation of single unit.

Relation of dimensions of H, A, and L are shown in the table below.


LH H<L L A 0 < L 1/2 H 150 (250) 1/2 H < L 200 (300) Set the frame to be L<=H
20 mm or more

1000 mm or more

Relation of dimensions of H, A, and L are shown in the table below.


LH H<L L A 0 < L 1/2 H 750<1250> 1/2 H < L 1000<1500> Set the frame to be L<=H

150 or more (250)

Get the lower part of the frame sealed so that air from the outlet does not bypass Do not install more than 2 units (D) In case of stacked installation 1 In case obstacles exist in front of the outlet side. Do not stack more than one unit.. About 100mm is required as the dimension for laying the upper outdoor units drain pipe.. Get the portion A sealed so that air from the outlet does not bypass..

1000 or more (1500)

Get the lower part of the frame sealed so that air from the outlet does not bypass 2 Installation of multiple units in lateral connection (2 units or more).
500 or less

20 mm or more

100 or more

Relation of dimensions of H, A, and L are shown in the table below.


LH H<L L A 0 < L 1/2 H 1000<1500> 1/2 H < L 1250<1750> Set the frame to be L<=H

20 mm or more

1000 mm or more

200 or more (300)

Get the lower part of the frame sealed so that air from the outlet does not bypass Do not install more than 2 units Where obstacle in front of the air outlet is lower than the unit.

In case obstacles exist in front of the air inlet.

20 mm or more

Do not stack more than one unit.. About 100mm is required as the dimension for laying the upper outdoor units drain pipe.. Get the portion A sealed so that air from the outlet does not bypass..
200 or more (300)

Pattern 2

+ Where there are no obstacles above the unit. 1 Installation of single unit.
50 or more (100)

(E) In case of multiple-low installation (for roof top use, etc.).

Installation of multiple units in lateral connection (2 units or more).

500 or more (1000)

1 Relation of dimensions of H, A, and L are shown in the table below.


L 0 < L 1/2 H 1/2 H < L A 150 (250) 200 (300)
20 mm or more 20 mm or more

In case of installing one unit per row.

50 or more (100) 1000 or more (2000)

100 or more (200) 500 or more (1000)

+ Where there are obstacles above the unit. 1 Installation of single unit.

In case of installing multiple units (2 units or more) in lateral connection per row.

20 mm or more 20 mm or more

1000 or more (1500)

500 or less 1000 mm or more

Relation of dimensions of H, A, and L are shown in the table below.


LH H<L L A 0 < L 1/2 H 50 (100) 1/2 H < L 100 (200) Set the frame to be L<=H
500 or more (1000)

2000 or more (3000)

400 or more (600) 1000 or more (1500)

Relation of dimensions of H, A, and L are shown in the table below.


LH H<L L A 0 < L 1/2 H 150 (250) 1/2 H < L 200 (300) Installation impossible
DU427-826

Get the lower part of the frame sealed so that air from the outlet does not bypass

16

Split - Sky Air Outdoor Units

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

13

Installation

Single installation Case 1

Installation in a row Case 1

Conentrated installation Case 1

13 Installation

suction side

front side

Split - Sky Air Outdoor Units

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

Case 2

Case 2

Case 2

Case 3

Case 3

2 3 4

Case 1and case 2 + Front wall height is 1500mm + Suction wall height is 500mm + Side wall height has no limit + Case 3 wall height has no limit If the wall is higher than mentioned in note 1: ADO h2/2 (front side) and ANO h1/2 (suction side) to the mentioned values for installation. (h1 and h2: see figure to the left) Before installing, please check the passage of humans and air at the side, and select a place which is suitable for the case. (If there are a lot of units to be installed, take care that there is no shortcircuit of air) Please install considering piping installation at the front side.

3TW23619-4

13

17
Split - Sky Air Outdoor Units

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

13
13

Installation

R(Y)(E)P-L
A. Non stacked installation

Legend
= mm SSO Suction side obstacle DSO Discharge side obstacle LSO Left side obstacle RSO Right side obstacle TSO Top side obstacle  Obstacle is present In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125 class models.

x ( )

B. Stacked installation
1. Obstacles exist in front of the outlet side

C. Stacked installation
1. Installation of one unit per row

2. Obstacles exist in front of the air inlet

2. Installing multiple units (2 units or more) in lateral connection per row

Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor units drain pipe. Get the portion A sealed so that air from the outlet does not bypass.

Relation of dimensions of H, A, and L are shown in the table below.


LH H<L L A 0 < L 0.5 H 150 (250) 0.5 H < L 200 (300) Installation impossible

3TW25149-4A

18

Split - Sky Air Outdoor Units

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

13

Installation
Charging refrigerant
This unit requires additional charging of refrigerant according to the length of pipe connected at the site. Charge the refrigerant to the liquid pipe in its liquid state. Since R-407C is a mixed refrigerant, its composition changes if charged in a state of gas and normal system operation would no longer be assured.

RYP71-125L7
Refrigerant pipe size
Pair system

13

Model Class 71 100, 125 Gas pipe J15.9xt1.0 J19.1xt1.0

Piping length Liquid pipe J9.5xt0.8

On this model it is not necessary to charge additionaly if the piping length 30 m. On twin/triple application, piping length means sum of main pipe and branch pipe. Piping length is the 1 way length, gas or liquid. Over 30 m or for complete recharging, please charge based as shown in the figures, where the pipe length is respectively L1+L2+L3 and L1+L2+L3+L4.

The pipes between the outdoor unit and the branch (L1) should have the same size as the outdoor connections. The pipes between the branch and the indoor units (L2-L4) should have the same size as the indoor connections.

Allowable pipe length and height difference


See the table below concerning lengths and heights. Refer to the figures. Assume that the longest line in the figure corresponds with the actual longest pipe, and the highest unit in the figure corresponds with the actual highest unit.

Additional charging of refrigerant


Over 30 m please, add refrigerant quantity according to following table. For future servicing, mark with a circle the selected amount on the tables below.

Pair

Pair system
Table 1: Additional charging amount <unit: kg>

Model Class H/P


Twin

Piping length 3040m +0.50 +0.75 +0.25 4050m +1.00 +1.50 0.50 5060m +1.50 +2.25 +1.75 6070m +2.00 +3.00 +1.00

71 100-125 71-100-125

C/O
Triple

For twin/triple system


Please charge additionaly according to the following calculation. (Additional amount is R1+ R2) 1. G1: total length of J9.5 mm liquid piping G2: total length of J6.4 mm liquid piping 2. a G1 > 30 m calculate length over 30 m (+ G1 - 30 m) Based on this length decide R1, R2 in the table b G 30 m and G1 + G2 > 30 m calculate total length over 30 m (= G1 + G2 - 30 m) Total additional charge amount 3. Total additional charge amount R = R1 + R2 (kg) Table 2: Additional charging amount <unit: kg>

Allowable pipe length Maximum allowable pipe length (figures between parenthesis represent equivalent length) Maximum total one-way pipe length Maximum branch pipe length Maximum difference between branch lengths Maximum height between indoor and outdoor Chargeless length Pair Twin/Triple Twin Triple Twin/Triple Twin Triple All All L1 L1+L2 L1+L2+L3 L1+L2+L3+L4 L2 L2-L3 L2-L4 H1 H2 L1+L2+L3+L4 70 m (90 m) 80 m 20 m 10 m 30 m 0.5 m 30 m

Model Class 71 100-125 H/P 71 100-125 71-100-125 Main C/O 71-100-125 Branch Branch Piping Main J 9.5 9.5 9.5 9.5 6.4 9.5 9.5 6.4

Length exceeding 30 m 0-10 0.50 0.75 0.30 0.75 0.30 0.25 0.25 0.15 10-20 20-30 30-40 40-50 1.00 1.50 1.00 1.50 0.60 0.50 0.50 0.30 1.50 2.25 1.50 2.25 0.90 0.75 0.75 0.45 2.00 3.00 2.00 3.00 1.20 1.00 1.00 0.60 2.50 3.75 2.50 3.75 1.50 1.25 1.25 0.75 R1 R1 R2 R1 R2

Maximum height between indoors Twin/Triple

The minimal piping length should be 5 m. If installation is performed with less field piping, the system will be overcharged (abnormal HP, etc.). If the distance between indoor and outdoor unit is less than 5 m, please make sure that the piping length is 5 m by additional bending of the pipes.

Split - Sky Air Outdoor Units

19

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

13
13

Installation

Example 1
L1 = 35 (J9.5)

L2 = 7 (J9.5)

71 type Indoor

100 type outdoor heat pump

L3 = 5 (J6.4)

35 type

1. G1 = L1 + L2 = 35 + 7 = 42 m G2 = L3 = 5 2. Over 30 m a G1 - 30 = 12 m J9.5 R1 = 1.50 kg b G2 = 5 m J6.4 R2 = 0.30 kg 3. Refrigerant charge amount= R = R1 + R2 = 1.50 + 0.30 = 1.80 kg Example 2

L2 = 17 (J6.4)

45 type Indoor

125 type outdoor heat pump

L1 = 5 (J9.5)

L3 = 17 (J6.4)

45 type Indoor

L4 = 20 (J6.4)

45 type

1. G1 = L1 = 5 m G2 = L2 + L3 + L4 = 17 + 17 + 20 = 54 2. Over 30 m a G1 = 5 m R1 = 0.0 kg b (G1 + G2) - 30 = (5 + 54) - 30 = 29 J6.4 R2 = 0.90 kg 3. Refrigerant charge amount= R = R1 + R2 = 0.0 + 0.9 = 0.9 kg In case of complete recharge of the refrigerant, please first execute vacuuming. Execute this vacuuming from the service port. Do not use the port of the stop valve for vacuuming. Vacuuming can not be executed completely using such port. Position of service port: Heat pump: On the piping between the heat exchanger and the 4-way valve. Cooling only: On the discharge pipe.

Complete charging of the refrigerant (after a leak, etc.)


When the entire refrigerant pipe length is within 30 meters, charge the refrigerant in accordance with the amount mentioned in the nameplate, and when the pipe length exceeds 30 meters, the charging amount mentioned in the nameplate and that required for additional charging are to be totalled as the net charging amount.

20

Split - Sky Air Outdoor Units

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

13

Installation
Additional charge
The units require additional charging of refrigerant, according to the length of pipe connected at the size. The correct amount of refrigerant to charge G (kg) can be lound by using the following formulas (If G<O: no addition is required).

RYP200-250B7 Refrigerant pipe size 1. Pair system (fig. 1)


Outdoor unit RYP200 RYP250 Refrigerant pipe size Gas pipe J 28.8 J 28.8 Liquid pipe J 12.7 J 15.9

13

1. Pair system
L1 (m) One way length of liquid pipe

RP200 RP250 RYP200 RYP250

G = (L1-30) * 0.06 G = (L1-30) * 0.09 G = (L1-30) * 0.10 G = (L1-30) * 0.14

2. Simultaneous operation system


Twin and triple operation system (fig. 2 / fig. 3) The pipes between the outdoor unit and the branch (L1) should have the same size as the outdoor connections. The pipes between the branch and the indoor units (L2-L4) should have the same size as the indoor connections. Branch: see marking Q on the figures.Double twin operation system (fig. 4) The pipes between the outdoor unit and the branch (L1) should have the same size as the outdoor connections. The pipes between the branch and the indoor units (L2-L4) should have the same size as the indoor connections. Branch: see marking Q on the figures.

2. Simultaneous operation system


L1 (m) One way length of main liquid pipe L2-L7 (m) One way length of branched liquid pipes

RP200 RP250 RYP200 RYP250

G = (L1-30) * 0.06+L2*A+L3*A+L4*A+L5*A+L6*A+L7*A G = (L1-30) * 0.09+L2*A+L3*A+L4*A+L5*A+L6*A+L7*A G = (L1-30) * 0.10+L2*A+L3*A+L4*A+L5*A+L6*A+L7*A G = (L1-30) * 0.14+L2*A+L3*A+L4*A+L5*A+L6*A+L7*A Branched pipe J 9.5 J 6.4 J 9.5 A 0.03 kg/m 0.03 kg/m 0.05 kg/m

Outdoor unit RYP200,250

Refrigerant pipe size Gas pipe J 19.1 Liquid pipe J 9.5

Outdoor unit RP200,250 RYP200,250

Allowable pipe length

See the table below concerning lengths and heights. Refer to the figures. Assume that the longest line in the figure corresponds with the actual longest pipe, and the highest unit in the figure corresponds with the actual highest unit.

Pair Maximum allowable pipe length (figures between parenthesis represent equivalent length) Twin/triple Double twin Twin Maximum total one-way pipe length Triple Double twin Maximum branch pipe length Twin/triple Double twin Twin Maximum difference between branch lengths Maximum difference between each 1st branch Maximum difference between each 2nd branch Maximum height between indoor and outdoor Maximum height between indoors
3TW23619-3

L1 L1+L2 L1+L2+L4 L1+L2+L3 L1+L2+L3+L4 L1+L2+L3+L4+L5+L6+L7 L2 L2+L4 L2-L3 L2-L4 (L2+L4)-(L3+L7) L2-L3 L4-L5, L6-L7 H1 H2
fig. 2: Twin

50m (70m)

60m

20m

Triple Double twin Double twin Double twin All Twin / triple / double twin
fig. 1: Pair

10m 10m 10m 30m 0.5m

fig. 3: Triple

fig. 4: Double twin

Split - Sky Air Outdoor Units

21

Twin/triple/double twin application R-407C RYP71-125L7V1/W1-RYP200-250B7W1

13
13

Installation

RYP71-125L7 Oil trap

Indoor unit

Oil trap

Gas piping Outdoor unit Liquid piping Install trap at each difference in eight of 15m

NOTE: Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and causing liquid compression phenomenon, or cases of deterioration of oil return, it well be necessary to provide a trap at an appropriate place in A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit.

4TW25149-8

22