ABB s. r. o.

, PPMV Brno Vdesk 117 619 00 B R N O Czech Republic

Document No.: Page number: Number of pages:

1VL 8413732 1 15

ABB

MV SWITCHGEAR Erbil - Dohuk, Stage 5 KRG-MOE/EDS5- 08/2008

CT and VT Calculation

5 October 2011 rev.A 30.1.2012 Keller

Elaborated: Karel Keller

ABB s. r. o., PPMV Brno Vdesk 117 619 00 B R N O Czech Republic

Document No.: Page number: Number of pages:

1VL 8413732 2 15

CT Overcurrent Protection Feeder: Outgoing/Capac.

CT core parameters: TPU 40.23 5P20 Primary ratio IaN: Secondary ratio IbN: Rated burden Sn: Accuracy limit factor n: Current transformer resistance Rct: Protection relay parameters: Relay type: REX 521 Relay burden Sp: Holmgreems conection of measuring S0: Lead parameters: Lead lenght l: Cross-section of lead S: Cooper rezistance : Maximum allowable temperature Tmax: Real max. short circuit current I"kmax:

150 5 7,5 20 0,4

A A VA

0,5 0,5

VA VA

5 m mm2 4 2 -1 0,0178571 .mm .m 75 C 31,5 kA

Calculated values: Loop resistance: Rl=2**l/S*(1+*(Tmax-20)) Internal burden of CT: Sin=Rct*IbN


2 2

Rl= Sin=

0,054 10,000 2,357 28,323 4248

VA VA A

Real burden: Sa=Sp+S0+Rl*IbN Sa= Real accuracy limit factor: nr=n*(Sin+Sn)/(Sin+Sa) nr= Maximum short circuit current without CT saturation: Imax=IaN*nr Imax=

Condition Real accuracy limit factor has to be higher than 20. nr 28,323 > > n 20 Result: OK

Current transformers are sufficient for

REX 521

requirements Overcurrent protection function.

ABB s. r. o., PPMV Brno Vdesk 117 619 00 B R N O Czech Republic

Document No.: Page number: Number of pages:

1VL 8413732 3 15

CT Overcurrent Protection Feeder: Outgoing/Capac.

CT core parameters: TPU 40.23 5P20 Primary ratio IaN: Secondary ratio IbN: Rated burden Sn: Accuracy limit factor n: Current transformer resistance Rct: Protection relay parameters: Relay type: REX 521 Relay burden Sp: Holmgreems conection of measuring S0: Lead parameters: Lead lenght l: Cross-section of lead S: Cooper rezistance : Maximum allowable temperature Tmax: Real max. short circuit current I"kmax:

300 5 15 20 0,8

A A VA

0,5 0,5

VA VA

5 m mm2 4 2 -1 0,0178571 .mm .m 75 C 31,5 kA

Calculated values: Loop resistance: Rl=2**l/S*(1+*(Tmax-20)) Internal burden of CT: Sin=Rct*IbN


2 2

Rl= Sin=

0,054 20,000 2,357 31,310 9393

VA VA A

Real burden: Sa=Sp+S0+Rl*IbN Sa= Real accuracy limit factor: nr=n*(Sin+Sn)/(Sin+Sa) nr= Maximum short circuit current without CT saturation: Imax=IaN*nr Imax=

Condition Real accuracy limit factor has to be higher than 20. nr 31,310 > > n 20 Result: OK

Current transformers are sufficient for

REX 521

requirements Overcurrent protection function.

ABB s. r. o., PPMV Brno Vdesk 117 619 00 B R N O Czech Republic

Document No.: Page number: Number of pages:

1VL 8413732 4 15

CT Overcurrent Protection Feeder: Incomer feeder

CT core parameters: TPU 46.43 5P20 Primary ratio IaN: Secondary ratio IbN: Rated burden Sn: Accuracy limit factor n: Current transformer resistance Rct: Protection relay parameters: Relay type: REX 521 Relay burden Sp: Holmgreems conection of measuring S0: Lead parameters: Lead lenght l: Cross-section of lead S: Cooper rezistance : Maximum allowable temperature Tmax: Real max. short circuit current I"kmax:

1250 5 15 20 0,6

A A VA

0,5 0,5

VA VA

5 m mm2 4 2 -1 0,0178571 .mm .m 75 C 31,5 kA

Calculated values: Loop resistance: Rl=2**l/S*(1+*(Tmax-20)) Internal burden of CT: Sin=Rct*IbN


2 2

Rl= Sin=

0,054 15,000 2,357 34,568 43209

VA VA A

Real burden: Sa=Sp+S0+Rl*IbN Sa= Real accuracy limit factor: nr=n*(Sin+Sn)/(Sin+Sa) nr= Maximum short circuit current without CT saturation: Imax=IaN*nr Imax=

Condition Real accuracy limit factor has to be higher than 20. nr 34,568 > > n 20 Result: OK

Current transformers are sufficient for

REX 521

requirements Overcurrent protection function.

ABB s. r. o., PPMV Brno Vdesk 117 619 00 B R N O Czech Republic

Document No.: Page number: Number of pages:

1VL 8413732 5 15

CT Overcurrent Protection Feeder: Incomer feeder

CT core parameters: TPU 46.43 5P20 Primary ratio IaN: Secondary ratio IbN: Rated burden Sn: Accuracy limit factor n: Current transformer resistance Rct: Protection relay parameters: Relay type: REX 521 Relay burden Sp: Holmgreems conection of measuring S0: Lead parameters: Lead lenght l: Cross-section of lead S: Cooper rezistance : Maximum allowable temperature Tmax: Real max. short circuit current I"kmax:

2500 5 15 20 1,2

A A VA

0,5 0,5

VA VA

5 m mm2 4 2 -1 0,0178571 .mm .m 75 C 31,5 kA

Calculated values: Loop resistance: Rl=2**l/S*(1+*(Tmax-20)) Internal burden of CT: Sin=Rct*IbN


2 2

Rl= Sin=

0,054 30,000 2,357 27,814 69536

VA VA A

Real burden: Sa=Sp+S0+Rl*IbN Sa= Real accuracy limit factor: nr=n*(Sin+Sn)/(Sin+Sa) nr= Maximum short circuit current without CT saturation: Imax=IaN*nr Imax=

Condition Real accuracy limit factor has to be higher than 20. nr 27,814 > > n 20 Result: OK

Current transformers are sufficient for

REX 521

requirements Overcurrent protection function.

ABB s. r. o., PPMV Brno Vdesk 117 619 00 B R N O Czech Republic

Document No.: Page number: Number of pages:

1VL 8413732 6 15

CT Overcurrent Protection Feeder: Auxiliary transf.

CT core parameters: TPU 40.23 5P20 Primary ratio IaN: Secondary ratio IbN: Rated burden Sn: Accuracy limit factor n: Current transformer resistance Rct: Protection relay parameters: Relay type: REX 521 Relay burden Sp: Holmgreems conection of measuring S0: Lead parameters: Lead lenght l: Cross-section of lead S: Cooper rezistance : Maximum allowable temperature Tmax: Real max. short circuit current I"kmax:

300 5 10 20 1

A A VA

0,5 0,5

VA VA

5 m mm2 4 2 -1 0,0178571 .mm .m 75 C 31,5 kA

Calculated values: Loop resistance: Rl=2**l/S*(1+*(Tmax-20)) Internal burden of CT: Sin=Rct*IbN


2 2

Rl= Sin=

0,054 25,000 2,357 25,587 7676

VA VA A

Real burden: Sa=Sp+S0+Rl*IbN Sa= Real accuracy limit factor: nr=n*(Sin+Sn)/(Sin+Sa) nr= Maximum short circuit current without CT saturation: Imax=IaN*nr Imax=

Condition Real accuracy limit factor has to be higher than 20. nr 25,587 > > n 20 Result: OK

Current transformers are sufficient for

REX 521

requirements Overcurrent protection function.

ABB s. r. o., PPMV Brno Vdesk 117 619 00 B R N O Czech Republic

Document No.: Page number: Number of pages:

1VL 8413732 7 15

CT Overcurrent Protection Feeder: Bus coupler

CT core parameters: TPU 46.33 5P20 Primary ratio IaN: Secondary ratio IbN: Rated burden Sn: Accuracy limit factor n: Current transformer resistance Rct: Protection relay parameters: Relay type: REX 521 Relay burden Sp: Holmgreems conection of measuring S0: Lead parameters: Lead lenght l: Cross-section of lead S: Cooper rezistance : Maximum allowable temperature Tmax: Real max. short circuit current I"kmax:

2500 5 15 20 1

A A VA

0,5 0,5

VA VA

5 m mm2 4 2 -1 0,0178571 .mm .m 75 C 31,5 kA

Calculated values: Loop resistance: Rl=2**l/S*(1+*(Tmax-20)) Internal burden of CT: Sin=Rct*IbN


2 2

Rl= Sin=

0,054 25,000 2,357 29,243 73107

VA VA A

Real burden: Sa=Sp+S0+Rl*IbN Sa= Real accuracy limit factor: nr=n*(Sin+Sn)/(Sin+Sa) nr= Maximum short circuit current without CT saturation: Imax=IaN*nr Imax=

Condition Real accuracy limit factor has to be higher than 20. nr 29,243 > > n 20 Result: OK

Current transformers are sufficient for

REX 521

requirements Overcurrent protection function.

ABB s. r. o., PPMV Brno Vdesk 117 619 00 B R N O Czech Republic

Document No.: Page number: Number of pages:

1VL 8413732 8 15

CT Overcurrent Protection Feeder: BC/Incomer

CT core parameters: TPU 46.43 5P20 Primary ratio IaN: Secondary ratio IbN: Rated burden Sn: Accuracy limit factor n: Current transformer resistance Rct: Protection relay parameters: Relay type: REX 521 Relay burden Sp: Holmgreems conection of measuring S0: Lead parameters: Lead lenght l: Cross-section of lead S: Cooper rezistance : Maximum allowable temperature Tmax: Real max. short circuit current I"kmax:

1000 5 15 20 0,6

A A VA

0,5 0,5

VA VA

5 m mm2 4 2 -1 0,0178571 .mm .m 75 C 31,5 kA

Calculated values: Loop resistance: Rl=2**l/S*(1+*(Tmax-20)) Internal burden of CT: Sin=Rct*IbN


2 2

Rl= Sin=

0,054 15,000 2,357 34,568 34568

VA VA A

Real burden: Sa=Sp+S0+Rl*IbN Sa= Real accuracy limit factor: nr=n*(Sin+Sn)/(Sin+Sa) nr= Maximum short circuit current without CT saturation: Imax=IaN*nr Imax=

Condition Real accuracy limit factor has to be higher than 20. nr 34,568 > > n 20 Result: OK

Current transformers are sufficient for

REX 521

requirements Overcurrent protection function.

ABB s. r. o., PPMV Brno Vdesk 117 619 00 B R N O Czech Republic

Document No.: Page number: Number of pages:

1VL 8413732 9 15

CT Overcurrent Protection Feeder: BC/Incomer

CT core parameters: TPU 46.43 5P20 Primary ratio IaN: Secondary ratio IbN: Rated burden Sn: Accuracy limit factor n: Current transformer resistance Rct: Protection relay parameters: Relay type: REX 521 Relay burden Sp: Holmgreems conection of measuring S0: Lead parameters: Lead lenght l: Cross-section of lead S: Cooper rezistance : Maximum allowable temperature Tmax: Real max. short circuit current I"kmax:

2000 5 15 20 1,2

A A VA

0,5 0,5

VA VA

5 m mm2 4 2 -1 0,0178571 .mm .m 75 C 31,5 kA

Calculated values: Loop resistance: Rl=2**l/S*(1+*(Tmax-20)) Internal burden of CT: Sin=Rct*IbN


2 2

Rl= Sin=

0,054 30,000 2,357 27,814 55629

VA VA A

Real burden: Sa=Sp+S0+Rl*IbN Sa= Real accuracy limit factor: nr=n*(Sin+Sn)/(Sin+Sa) nr= Maximum short circuit current without CT saturation: Imax=IaN*nr Imax=

Condition Real accuracy limit factor has to be higher than 20. nr 27,814 > > n 20 Result: OK

Current transformers are sufficient for

REX 521

requirements Overcurrent protection function.

ABB s. r. o., PPMV Brno Vdesk 117 619 00 B R N O Czech Republic

Document No.: Page number: Number of pages:

1VL 8413732 10 15

CT Metering Units Feeder: Outgoing feeder

CT core parameters: TPU 40.23 0.5Fs5 Primary ratio IaN: Secondary ratio IbN: Rated burden Sn:

150-300 5 15

A A VA

Lead parameters: Lead lenght l: Cross-section of lead S: Cooper rezistance : Maximum allowable temperature Tmax:

5 m mm2 4 2 -1 0,0178571 .mm .m 75 C

Other burden: Transducer Sineax I 538 Transducer Sineax P 530 Transducer Sineax Q 531

0,025 0,025 0,025

VA VA VA

Calculated values: Loop resistance: Rl=2**l/S*(1+*(Tmax-20)) Lead burden: Sa=Rl*IbN Sum other burden
2

Rl= Sa= So=

0,054 1,357 0,175 1,532

VA VA VA

Total burden: St=Sa+So

Condition Rated burden has to be higher than total burden. Sn 15 > > St 1,532 Result: OK

Current transformers are sufficient for metering circuit.

ABB s. r. o., PPMV Brno Vdesk 117 619 00 B R N O Czech Republic

Document No.: Page number: Number of pages:

1VL 8413732 11 15

CT Metering Units Feeder: Incomer feeder

CT core parameters: TPU 46.43 0.5Fs5 Primary ratio IaN: Secondary ratio IbN: Rated burden Sn:

1250-2500 5 15

A A VA

Lead parameters: Lead lenght l: Cross-section of lead S: Cooper rezistance : Maximum allowable temperature Tmax:

5 m mm2 4 2 -1 0,0178571 .mm .m 75 C

Other burden: Transducer Sineax I 538 Transducer Sineax P 530 Transducer Sineax Q 531 Multifunction meter

0,025 0,025 0,025 0,1

VA VA VA VA

Calculated values: Loop resistance: Rl=2**l/S*(1+*(Tmax-20)) Lead burden: Sa=Rl*IbN Sum other burden
2

Rl= Sa= So=

0,054 1,357 0,175 1,532

VA VA VA

Total burden: St=Sa+So

Condition Rated burden has to be higher than total burden. Sn 15 > > St 1,532 Result: OK

Current transformers are sufficient for metering circuit.

ABB s. r. o., PPMV Brno Vdesk 117 619 00 B R N O Czech Republic

Document No.: Page number: Number of pages:

1VL 8413732 12 15

CT Metering Units Feeder: Auxiliary transf.

CT core parameters: TPU 40.23 0.5Fs5 Primary ratio IaN: Secondary ratio IbN: Rated burden Sn:

150 5 15

A A VA

Lead parameters: Lead lenght l: Cross-section of lead S: Cooper rezistance : Maximum allowable temperature Tmax:

5 m mm2 4 2 -1 0,0178571 .mm .m 75 C

Other burden: Transducer Sineax I 538 Transducer Sineax P 530

0,025 0,025

VA VA

Calculated values: Loop resistance: Rl=2**l/S*(1+*(Tmax-20)) Lead burden: Sa=Rl*IbN Sum other burden
2

Rl= Sa= So=

0,054 1,357 0,175 1,532

VA VA VA

Total burden: St=Sa+So

Condition Rated burden has to be higher than total burden. Sn 15 > > St 1,532 Result: OK

Current transformers are sufficient for metering circuit.

ABB s. r. o., PPMV Brno Vdesk 117 619 00 B R N O Czech Republic

Document No.: Page number: Number of pages:

1VL 8413732 13 15

CT Metering Units Feeder: Bus Coupler

CT core parameters: TPU 46.33 0.5Fs5 Primary ratio IaN: Secondary ratio IbN: Rated burden Sn:

2500 5 15

A A VA

Lead parameters: Lead lenght l: Cross-section of lead S: Cooper rezistance : Maximum allowable temperature Tmax:

5 m mm2 4 2 -1 0,0178571 .mm .m 75 C

Other burden: Transducer Sineax I 538 Multifunction meter

0,025 0,1

VA VA

Calculated values: Loop resistance: Rl=2**l/S*(1+*(Tmax-20)) Lead burden: Sa=Rl*IbN Sum other burden
2

Rl= Sa= So=

0,054 1,357 0,125 1,482

VA VA VA

Total burden: St=Sa+So

Condition Rated burden has to be higher than total burden. Sn 15 > > St 1,482 Result: OK

Current transformers are sufficient for metering circuit.

ABB s. r. o., PPMV Brno Vdesk 117 619 00 B R N O Czech Republic

Document No.: Page number: Number of pages:

1VL 8413732 14 15

VT Measuring winding Feeder: All feeders

CT core parameters: TJP 4.0 0.5/3P Primary ratio UaN: Secondary ratio UbN: Rated burden Sn: Lead parameters: Lead lenght l: Cross-section of lead S: Cooper rezistance : Maximum allowable temperature Tmax: Other burden: REX 521 Voltmeter Fb96 Transducer Sineax U 539

11/3 0.11/3 30

A A VA

10 m mm2 2,5 2 -1 0,0178571 .mm .m 75 C

0,5 0,5 0,006

VA VA VA

Calculated values: Loop resistance: Rl=2**l/S*(1+*(Tmax-20)) Lead burden: Sa=Rl*Im Sum other burden
2

Rl= Sa= So=

0,087 0,002 1,006 1,008

VA VA VA

Im~150mA

Total burden: St=Sa+So

Condition Rated burden has to be higher than total burden. Sn 30 > > St 1,008 Result: OK

Voltage transformers are sufficient for metering circuit.

ABB s. r. o., PPMV Brno Vdesk 117 619 00 B R N O Czech Republic

Document No.: Page number: Number of pages:

1VL 8413732 15 15

VT Protection winding Feeder: All feeders

CT core parameters: TJP 4.0 3P Primary ratio UaN: Secondary ratio UbN: Rated burden Sn: Lead parameters: Lead lenght l: Cross-section of lead S: Cooper rezistance : Maximum allowable temperature Tmax: Other burden: REX 521

11/3 0.11/3 30

A A VA

10 m mm2 2,5 2 -1 0,0178571 .mm .m 75 C

0,5

VA

Calculated values: Loop resistance: Rl=2**l/S*(1+*(Tmax-20)) Lead burden: Sa=Rl*Im Sum other burden
2

Rl= Sa= So=

0,087 0,002 0,500 0,502

VA VA VA

Im~150mA

Total burden: St=Sa+So

Condition Rated burden has to be higher than total burden. Sn 30 > > St 0,502 Result: OK

Voltage transformers are sufficient for protection circuit.