ACE 5000 type 5.1 Technical Document Three Phase Time Switch Static Meter

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 1 of 43

ACTARIS

CONFIDENTIAL

GENERAL_____________________________________________________________________ 4
1.1 1.2 1.3 Scope ______________________________________________________________________ 5 Lifetime ____________________________________________________________________ 6 Meter overview_______________________________________________________________ 6
Main Assemblies Identification __________________________________________________________6 Main Dimensions & Fixing Triangle ______________________________________________________7 Direct Connected Terminal & Connections _________________________________________________8 Current Transformer connected Terminal & Connections ______________________________________8 Envelope Material ____________________________________________________________________8 Functions on Cover ___________________________________________________________________9 External / Internal IP Link _____________________________________________________________ 10 Auxiliary terminals __________________________________________________________________ 10 Opening Cover Detector_______________________________________________________________ 10 Protection _________________________________________________________________________ 10 Temperature range ___________________________________________________________________ 10 Humidity range _____________________________________________________________________ 11 Variants ___________________________________________________________________________ 11

1.3.1 1.3.2 1.3.3 1.3.4 1.3.5 1.3.6 1.3.7 1.3.8 1.3.9

1.4

Enclosure protection & Climate _________________________________________________ 10

1.4.1 1.4.2 1.4.3

1.5

Standards __________________________________________________________________ 11

1.5.1

HARDWARE FUNCTIONAL SPECIFICATIONS ___________________________________ 12


2.1 2.2 2.3 2.4 Power Supply Unit ___________________________________________________________ 12 LV/DC Current ranges________________________________________________________ 12 LV/CT Current ranges________________________________________________________ 12 Real Time clock (acc. to IEC 61038) _____________________________________________ 12
Battery ____________________________________________________________________________ 13 Super Capacitor _____________________________________________________________________ 13 LCD overview ______________________________________________________________________ 14 LCD modes ________________________________________________________________________ 17 Metrology LED _____________________________________________________________________ 22

2.4.1 2.4.2

2.5

Human Machine Interface _____________________________________________________ 14

2.5.1 2.5.2 2.5.3

METROLOGY_________________________________________________________________ 23
3.1 Metrology Indications ________________________________________________________ 23
Metrology principle __________________________________________________________________ 23 Metrology modes ____________________________________________________________________ 23 Metrology LED constant and duration ____________________________________________________ 25 Pulse Output _______________________________________________________________________ 25 Instantaneous values _________________________________________________________________ 25 Energy Registers ____________________________________________________________________ 26 Maximum Demand Registers ___________________________________________________________ 28 Maximum Registers __________________________________________________________________ 29 3.1.1 3.1.2 3.1.3 3.1.4 3.1.5

3.2

Exploitation data ____________________________________________________________ 26

3.2.1 3.2.2 3.2.3

TARIFFS_____________________________________________________________________ 30
4.1 Definition & ACE 5.1 Time Switch: ______________________________________________ 30
Power-Up _________________________________________________________________________ 30 Power-Down _______________________________________________________________________ 30 Precision on RTC setting ______________________________________________________________ 30 4.1.1 4.1.2 4.1.3

4.2 4.3 4.4

Contract change _____________________________________________________________ 30 End of Billing (E.O.B.) ________________________________________________________ 31 Load Management ___________________________________________________________ 31
ParameterSetChecksum _______________________________________________________________ 33 ProgrammingCounter_________________________________________________________________ 33
Page 2 of 43

Diagnostic and Survey __________________________________________________________ 33


5.1.1 5.1.2

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

ACTARIS

CONFIDENTIAL

5.1.3 5.1.4 5.1.5 5.1.6 5.1.7 5.1.8

ReverseFlowCounter _________________________________________________________________ 33 BillingPeriodCounter_________________________________________________________________ 33 Terminal Cover Opening Counter________________________________________________________ 33 CutOffCounter______________________________________________________________________ 33 StatusWord ________________________________________________________________________ 33 Check Reading register _______________________________________________________________ 33

COMMUNICATIONs___________________________________________________________ 34
6.1 IR communication port : ______________________________________________________ 34
Flag (IEC 61107) Read-out ____________________________________________________________ 34 COSEM Reading and Programming _____________________________________________________ 34 DATA BUS OUTPUT ________________________________________________________________ 35 Principle __________________________________________________________________________ 35 Data Format ________________________________________________________________________ 36 Remote Reading_____________________________________________________________________ 36 6.1.1 6.1.2 6.1.3

6.2

Local Reading ______________________________________________________________ 35

6.2.1 6.2.2 6.2.3

IMPORTANT:___________________________________________________________________ 36

Installation ___________________________________________________________________ 37
7.1 7.2 7.3 7.4 Preliminary verifications before the meter is powered up _____________________________ 37 Battery connection [optional] ___________________________________________________ 37 LCD testing and Date and Time Setting ___________________________________________ 37 Battery replacement [Optional] _________________________________________________ 37 Installation_________________________________________________________________ 38 Setup _____________________________________________________________________ 38 User and permissions management ______________________________________________ 38 Meter management __________________________________________________________ 38 Configuration_______________________________________________________________ 38 Cosem Connection ___________________________________________________________ 38 Configuration programming ___________________________________________________ 39 Data reading________________________________________________________________ 39 Specific actions ______________________________________________________________ 39 Norms_____________________________________________________________________ 40 Configuration and Exploitation data _____________________________________________ 41

Reading and configuration tool / "AIMS 5000" ______________________________________ 38


8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9

Annexes ______________________________________________________________________ 40
9.1 9.2

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 3 of 43

ACTARIS

CONFIDENTIAL

1 GENERAL
Meter Type LifeTime Enclosure Protection Degree

ACE 5000 type 5.1 3ph TSW


15 years (<0.5% drop-out rate/year) Overall Terminal Block Specified Operating Range Limit Range of Operation Storage & Transport Specified Operating+C22 Range Limit Range of Operation Storage & Transport 3phases 3 wires or 4 wires Active Energy Reactive Energy 1000 pulses / kWh DIN 46 857 part2 Vn (Un) = 3x230 (400)V / 3x400V or Vn (Un) = 3x127 (220)V / 3x220V Fully Redundant Power Supply (Un) 0V to 500 V 5A 80A, 120A 1A 10A Starting current Limit max current Withstands : 50, 60 Hz + 10% < 2.5s 0.5s @ [ 0.7 Vn .. 1.25 Vn ] Lithium Battery Super-Capacitor 2W and 4VA capacitive at Vn + 0.5s/day @ 23C with Main Power and + 0.1s/day/C for Specified Operating Range + 1s/day @ 23C with Back-Up Power Clock accuracy According to IEC 61038 typically < 9s/month and < 3min/year for Specified Operating Range 0.2s if only two wires [ 0.9 Vn .. 1.25 Vn ] Ib/250 1.2 Imax 30.Imax for cycle nominal frequency (Other Ib currents available for commercial purposes) IP 54 IP xxB -25C to 60C -40C to 70C -40C to 80C 45% to 90%RH < 95% RH over 95% RH non condensing Internal or External IP Link Class 1 IEC 61036 Class 2 IEC 61268 In Test mode 5000 pulses available per kWh or kvarh (asymmetric connection) From -30% up to +25% ( Operation without loss of accuracy with only two wires connected ) (Withstands neutral rupture) (Other Ib currents available for commercial purposes)

Temperature Range

Humidity Range Connection Type Metrology Accuracy LED Constant Terminal Connection Voltage Operating Range Limit Voltage Ranges LV/DC Nominal Current (Ib) LV/DC Maximum Current (Imax) LV/CTNominal Current (Ib) LV/CT Maximum Current (Imax)

Limit Current Ranges

Frequency Metrology Start Up Continue Operation on V drops Back-Up Power Supply Unit Overall Consumption

3 years / 23C ; Rated shelf life of 10years 7 days capacity; recharge less than 12hours

Real Time Clock

Time Switch & Registers Energy Registers


NR = non resetable [1..n] registers per Rate n = 8 for TSW only 3 energies possible, either P+, Q+, Por P+, Q+, Q-

4 Seasons with 4 Day Profiles & up to 8 Rates 12 End of Billing dates 72 Special Days P+ [1..n] (NR) P+Total (NR) Q+ [1..n] (NR) Q+ Total (NR) P- or Q- [1..n] (NR) P- or Q-Total (NR)
MDI. P+

Leap year and Day-light Saving Time management One historical Billing data Bill.P+ [1..n] Bill.P+Total Bill.Q+ [1..n] Bill.Q+ Total Bill.P- or Q-[1..n] Bill.P- or Q-Total Hist.Bill.P+ [1..n] Hist.Bill.P+Total Hist.Bill.Q+ [1..n] Hist.Bill.Q+Total Hist.Bill.P- or Q-[1..n] Hist.Bill.P- or Q-Total
( W or VA) ( W or VA)

( kWh ) ( kvarh ) ( kWh or kvarh )

or S+ or S+ [1..n]

( W or VA ) ( W or VA)

Hist.MDI.P+ Hist.MDI.P+

or S+ or S+ [1..n]

Maximum Demand Registers

MDI. P+

Number of Sub-intervals N = 1 to 5, 10 and 15 Sub-Interval Duration in minutes T = 1, 3, 5, 10, 15, 20, 30, 60 Block or sliding operation

Max.I 1/2/3

Maximum Registers

Max.I1/2/3 [1..n] Max. P+ Max U 1/2/3

( A ) filtered ( A ) filtered ( W ) filtered ( V ) not filtered (A) (V)

Filter Time Constant = 20s, 5 or 10 minutes

Instantaneous Values

RMS Current per phase RMS Voltage per phase

Active Power Apparent Power Power Factor

(W) ( VA )

Display

Energy Resolution : 6+0 , 6+1 , 5+2 Digit size : 6mm x 8mm LCD display IEC 61107 sealable optical port Communication : 9600 bps

Optical Port Communication Speed

Displaying Information : 2 Push Buttons : Normal and Autoscrolling mode A: Scrolling button Special Function mode B: Reset button - sealable Test mode Readout (all data) according to IEC 61107 Read/Write (single data values) according to DLMS/COSEM (IEC 62056) (MDI and EOB are reset automatically or manually through the push buttons)

Data Bus Output or Pulse Output

Serial unidirectional Data Bus Ouput with information of Readout @ 1200 bps (set by default) Pulse Output S0 (DIN 43 864 & IEC 62053-31 type A) Programmable constant for 500, 1000 and 2000 pulses / kWh or kvarh and programmable pulse length from 10ms up to 150ms 0, 1 or 2 Relay out-puts 5 A 250 V 4 kV 50Hz for 1 min Mains connections Output connections 30 V/m < 2 GHz 218 x 179 x 106 (without Terminal Cover) 1.7 kg Optical port password protection Number of times in programming mode Number of reverse energy detections Check read index AIMS+ 5000 with Cripkey protection Number of power outages Working time (total & by rate) Detection Terminal Cover Opening 272 x 179 x 106 (with Terminal Cover) 10 kV 12 kV Relays can be controlled directly, by rate change or by current threshold.

Load Management Insulation Strength Impulse Voltage Insulation Strength Immunity to HF Fields Size ( W x H x D ) Weight

Anti-fraud devices

Configuration Tool

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 4 of 43

ACTARIS

CONFIDENTIAL

1.1

Scope

The meter is designed within the ACE 5000 family and is identified as 5.1 type.

The ACE 5.1 is an asymmetrical direct connected 3 phase 4 wire static meter for low voltage applications. The meter covers current ranges from 5A up to 120A providing active and reactive energy measurements according to class 1 IEC 61036 and class 2 IEC 61268 respectively and showing either one or the other through the calibration LED. The meter measures active and reactive energies, maximum consumed energies, power, currents and voltages. The meter integrates a Maximum Demand Register as well as an internal Real Time Clock managing a Time Switch up to 8 rates for 3 different energy types over 4 seasons with 4 different Day Profiles through 72 special days, plus the capability of automatically changing between Summer and Winter time. The ACE 5.1 carries Load Management features through up to two relay outputs, has permanent electrical readout output feature or the traditional DIN S0 pulse-output facility. It is designed with a back-up power supply carrying a super capacitor or a replaceable lithium battery. Automatic or manual End Of Billing holding one or more historical billing data. All meter data is stored in an Electrically Erasable Programmable Read Only Memory (EEPROM), which remains intact even in the event of long total power losses (over 10 years). The meter carries a LCD where the information displayed obeys to DLMS/COSEM identification code table or to codes set by the customer. An optical port communicating at 9600bps with the capability of being sealed is available allowing IEC61107 readout and DLMS/COSEM read/write. The meters are fully programmable through a dedicated Windows software application.

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 5 of 43

ACTARIS

CONFIDENTIAL

1.2

Lifetime

The meter is designed to cope with a 15 years life-time with a maximum drop-out rate of 0.5% / year

1.3
1.3.1

Meter overview
Main Assemblies Identification

ACE 5.1 is made of: 1 base 1 LCD and its holder 1 cover with Output terminals 1 Optical port and 1 metrology LED 1 replaceable battery and 2 push buttons (variant dependent) 1 top PCB with microcontroler & all metrology components 1 bottom PCB with power supply, I/O components & relays 1 terminal cover that protects the connection terminals against fraud. 1 terminal block with all associated connections and 1 retainer
Metrological LED Infrared Optical port Push Buttons D (Display) Push Buttons S (Sealable) Battery Holder

Cover

LCD

Top PCB Bottom PCB 1 Pulse output or Data Bus Output

2 Relays

Opcode

Termin al Cover

Base

ITerminal Block + current sensors

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 6 of 43

ACTARIS

CONFIDENTIAL

1.3.2

Main Dimensions & Fixing Triangle

External Dimensions 3Ph TSW

Meter Fixing

The meter is designed to be mounted vertically, directly hooked on a metering board using a DIN three triangular arrangement points. The meter is removable from its mounting board only after breaking the terminal cover seal(s). Fixation Triangle

Tv

Th
Meter ACE 5.1 Th (mm) 150 Tv (mm) 186, 201 and 230

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 7 of 43

ACTARIS

CONFIDENTIAL

1.3.3

Direct Connected Terminal & Connections

Terminals

ACE 5.1s carries a VDE connection arrangement (asymmetrical terminals) of 120A or 80A of maximum current, with an internal or external IP link (common-point).

3 Phase 4 Wire meter connections

The main terminals accept wiring of 16mm, 35mm and use 2 screws.

Note : This 120A VDE DC meter variant is not fully compliant with DIN 43-857 specification (non compliance stands for the neutral terminals pitch of 10 mm instead of 9 mm and terminal bores is greater than 6.5 mm). The reason comes from the DIN standard itself, specified for a 60A meter.

Cables The meter can withstand a permanent maximum current of : Copper TERMINALS 120 A (Copper) 80 A (tinned) Cables Aluminium Cables

1.3.4

Current Transformer connected Terminal & Connections

1.3.5

Envelope Material

Meter case has been designed and arranged so that any non-permanent deformation cannot prevent satisfactory meter operation. All plastic components are able to be recycled as expressed by their recycling markings. Parts color Standard colour: light grey RAL 7035 Push buttons: blue PANTONE 300. Terminal Cover is grey or transparent

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 8 of 43

ACTARIS

CONFIDENTIAL

The overall range of meters has been designed and constructed in order to avoid introducing any danger in normal use and under normal conditions ensuring: personal safety against electric shock personal safety against effects of excessive temperature protection against spread of fire protection against penetration of solid objects, dust and water protection against projecting particles in case of internal default. All parts, which are subjected to corrosion under normal working conditions, are effectively protected. The material of which the meter is made passes the Glow Wire test given by IEC 695-2-1 : Base and Terminal Block - 960C 15C @ 30s 1s Terminal cover and Cover - 650C 10C @ 30s 1s

1.3.6

Functions on Cover

Without having to remove the meter cover, it is possible to carry out the following operations: visually read the display unit and operate the buttons visually read the nameplate or scan the serial number bar-code read and program the meter through the optical port with a PC

reset max current, status word using the push buttons on the front of the meter cover or through the optical port start EOB, test relays, test LCD test active or reactive energy meter accuracy by picking up LED pulse signals replace battery set date & time

Meter is marked by the following information Type of meter The constructors identification Utilitys name and logo Legal approval identification Meter accuracy class and Metrology Modes (See 3.1.2) Distribution system : kind of current, number of wires Meter constant Reference voltage Basic and maximum current Reference frequency for double insulation Serial number Bar-code Outputs identification

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 9 of 43

ACTARIS

CONFIDENTIAL

1.3.7

External / Inte rnal IP Link

According to the following pictures it is possible to select either external or internal IP Link which is provided by a transparent plastic part maintained by the sealed cover and allows or does not allows access to the common point screws.

External IP Link

Internal IP Link

1.3.8

Auxiliary terminals

Access to ACE 5.1 output terminals will only be possible after removing the terminal cover : Function Relay 1: Load management Relay 2: Load management PO/DBO (Data Bus Output) Reference 20/21 22/23 30/31 32 / 33 34/35 Bore size 4.4x4.2 4.4x4.2 4.4x4.2 Screw M3 M3 M3 Characteristics 5A 250V 5 A 250V Blank I=10mA 240V Blank

1.3.9

Opening Cover Detector

As an extended antifraud feature, the OPCODE (OPening COver DEtector) detects the opening of the sealed terminal cover at any time, i.e., even if the meter is completely powered down. When the mains are powered after a tamper event, while it was not powered, the meter will detect the tamper and increase the internal counter with 1 opening cover event. While powered, the device detects the number of times the terminal cover has been opened keeping a 1 second reset gap between two frauds. The OPCODE device is checked every 200ms and in case of fraud detection it is confirmed 200ms later. T he "OPCODE tamper index" is increased and the device is reset. The "OPCODE tamper index" registers up to 255 events setting an overflow bit in the status word if the index rolls over to 0. This bit can be reset using the push buttons or the IR communication port.

1.4
1.4.1

Enclosure protection & Climate


Protection

ACE 5.1 has been designed to be an indoor meter carrying the following protection degrees: IP51 and IP54

1.4.2

Temperature range

ACE 5.1 has been designed to withstand the most severe climate conditions Operating Temperature Range: -25C to +60C

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 10 of 43

ACTARIS

CONFIDENTIAL

Limit Range of Operation: Storage & Transport:

-40C to +70C -40C to +80C

1.4.3

Humidity range
45% to 90% relative humidity 95% relative humidity withstands over 95% relative humidity non condensing

Operating Humidity Range: Limit Range of Operation: Storage & Transport:

1.5

Standards

ACE 5.1 complies with the following standards: Active energy, class 1.0 according to IEC 61036 Reactive energy, class 2.0 according to IEC 61268 Real Time Clock accuracy, according to IEC 61038 All versions of the meter comply with IEC 61107 Metering Communication Standard optical port. Data available through IEC 61107 for complete data readout and read and write according to DLMS/COSEM (IEC 62056). Please refer to Annexes section for complete norm list.

1.5.1

Variants

Based on the following options several variants are available CT 10A or DC 80A or DC120A Removable battery or Super Capacitor External or Internal IP LINK With or Without Opcode No, one or two Relays Active Energy Class 1 or Class 2 Metrology Modes (See 3.1.2) No or One or Two Pulse Output Standard or Specific Marking Default or Specific Configuration

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 11 of 43

ACTARIS

CONFIDENTIAL

2 HARDWARE FUNCTIONAL SPECIFICATIONS


2.1 Power Supply Unit
The ACE 5.1 meter is designed with a fully redundant 3 phase 4 wire power supply, for 50, 60Hz 10% network frequency with nominal voltage of 127V up to 230V in 3 or 4 wires connection types. Withstands the inversion of one phase and neutral. 2 wires from the 4 possible are mandatory for product operation. Design Note : The meter has 3 different qualified network voltages (220, 230 and 240V), however the reference network voltage used in all calculations dimensioning the meter is 230 V (Vn). Power consumption: The maximum overall consumption per phase of the apparatus under the reference conditions is : 2 W and 4 VA inductive. Typical per phase power consumption are: Current circuit DC(Ib=10A, Un=230V) 50mVA CT(Ib=5A, Un=230V) 250mVA

Voltage circuit 0.5W_0.8VA 0.5W_0.8VA

2.2

LV/DC Current ranges

Nominal Operating Current Range Basic Current (Ib): 5A Max Currents: 80A for 80A variant or 120A for 120A variant Limit Current Operating Range Starting Current : 20mA Maximum current: 1.2 Imax , i.e, 96 A for Imax 1 and 144 A for Imax 2 The meter withstands 30 times Imax for cycle at nominal frequency range Meter Variants 80 A 120 A 30 times Imax 2 400 A 3 600 A

2.3

LV/CT Current ranges

Nominal Operating Current Range Basic Current (Ib): 1A Max Currents: 10A

2.4

Real Time clock (acc. to IEC 61038)

All real timing functions within the meter, like rate changes or special day management, among others, are derived from the integrated real time clock (RTC). Its source is internal and based on a 32.768 kHz crystal. This meter is equipped with a small back-up power supply, and optionally either a lithium battery or a supercapacitor. Without the extra energy sources the auxiliary power circuit holds the RTC working for at least 15 minutes. In case of the super-capacitor, the RTC is maintained at least 7days of continuous total supply outage. If the lithium battery is chosen, it will maintain the RTC up to 3 years. Characteristics of Time accuracy: 0,5s per day at 23C when meter is powered by main

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 12 of 43

ACTARIS

CONFIDENTIAL

1s per day when RTC is powered by backup power 0.1s per day per C: temperature deviation for operating scope = -25C to 60C in accordance with Operating range

As the crystal drift is not linear over the temperature range and time, the internal clock source accuracy is better than 15 seconds per month at 23C, and 6 minutes per year over the full temperature range. Time is possible to be set (re-synchronised) with 1 second accuracy [hh,mm,ss], by a programming operation using the IR port or directly using the sealed push-button on the meter cover. The meter verifies the consistency of Date & Time programmed in the meter and rejects not valid ones.

2.4.1

Battery

The meter may be equipped with a replaceable lithium battery, which is accessed by a battery holder placed on the front of the meter. This battery holder can be sealed and therefore its access possible only after breaking it. The battery carries the following characteristics : Standard size Lithium battery CR2450, Rated shelf life of 10 years (20 years typically), The battery is modified into an assembly to fit meters battery holder. The battery holder provides a space to put a sticker to indicate battery date of change. also indicates a printed forecasted date for its replacement. A battery failure indication is shown in the display when the battery capacity decreased by about 10% or when it is absent.

2.4.2

Super Capacitor

The Super capacitor is placed on the meters bottom board and not replaceable. It assures a minimum capacity of 7 days in case of continuous total supply outage with a recharging time no more than 12 hours.

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 13 of 43

ACTARIS

CONFIDENTIAL

2.5

Human Machine Interface

The Human Machine Interface is the communication mean between the end user and the meter without interposed devices. The User Interface is made of two push buttons and one LCD Display.

2.5.1

LCD overview

As described earlier the meter carries a Liquid Crystal Display, which is organised in 3 different areas with a total of 60x20mm viewing surface. Area 1 Main digits Area 2 Code digits Area 3 Units information (the 5 bottom icons are printed on the meter nameplate)

R1

R2

The information displayed is shown on an auto-scrolling mode, which can be interrupted at any time by the use of the push buttons shifting to a manual scrolling. The display can be read at a 3 m distance of and its contrast value is greater than 0.90. 2.5.1.1 Main Digits

Decimal dot position is configurable (no, one or two decimal points, i.e. format "6.0" "6.1" or " 5.2"). 2.5.1.2 Code Digits area

NB: The code is blinking when the value correspond to an active tariff. For each parameter, the following letters can be displayed in the Code Digits area when the OBIS codes are not used.

Letter A, a B, b C, c D, d E, e

LCD Code

Letter N, n O, o P, p Q, q R, r

LCD Code

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 14 of 43

ACTARIS

CONFIDENTIAL

F, f G, g H, h I, i J, j L, l M, m K,k v W,w X,x


ATTENTION:

S, s T, t U, u V, v Y, y Z, z -, _
All stay blank

Several letters must be used with care due to possible misunderstandings. They are : Capital "i" Small "L" Capital "O" Capital and Small "Q" Capital and Small "S" Capital "V" Capital "Z" Can be 1, capital "i" or small "L" Can be 1, capital "i" or small "L" Can be number 0 Can be number 9 Can be Number 5 Equal to capital letter "U" Can be number 2

Should also pay attention the space left by the symbols "1", capital "I" and small "L". Although two letters ensue each other, by optical effect the user may read a space. Examples: MDI6 (Max Demand Register) We can either read Max Demand value for 16 rate ! or we can read Max Demand Register for 6 rate ! Ul1 (Voltage Phase 1) HIST (Historical)
th th

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 15 of 43

ACTARIS

CONFIDENTIAL

2.5.1.3

Units and Icons area

Cursors: when lightened above the following ideograms, means R1 R2 Communication in progress Excess Demand above a treshold Relay 1 closed Relay 2 closed Battery failure

Arrows icons: P+ Import Aggregate Active Energy flowing P- Export Aggregate Active Energy flowing Q+ Import Aggregate Reactive Energy flowing Q- Export Aggregate Reactive Energy flowing When there is no energy flowing through the meter (meter blocked) the arrows are unlightened. Units: Depending on the value, the following units are displayable kWh, kW, A , V, VA, kVarh, Var Phase icons: Lx: continuously lightened when voltage on Lx Lx: unlightened when no voltage on Lx L1 & L2 & L3: blinking at 2Hz in case of wrong connection (order, inversion) or overvoltage Lx : blinking at 2Hz in case of overvoltage on Lx

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 16 of 43

ACTARIS

CONFIDENTIAL

2.5.2

LCD modes

There are two push buttons (A and B) situated on the top right hand corner of the meter cover. Their role consists on giving user access to 3 main different LCD modes which allows the user either to read the data "Reading mode", or to perform specific actions "Special Function Mode" or to configure Energy retransmitted on the metrological Led "Test Mode". The following state chart present the procedure to switch between each mode.

Alarm mode
No overvoltage during 10 s.

Overvoltage

Reading Mode

Short Pressure on B AND current diplay different than Metrological pulses

Display mode

Special Function Mode


Short Press on A and B Long Pressure on B

Long Pressure on A OR Short Pressure on A 5 min. time out

Test Mode
Short Pressure on A

Auto scrolling mode

Long Pressure on A

60 min. time out (if authorized)

Long Pressure on B or Time Out

Blank mode

2.5.2.1 2.5.2.1.1

Reading Mode / Available data Sub mode Display

In normal mode, most of the exploitation data are configurable with AIMS, the list of these data is given in annex 9.2. The data itself and the associated parameter code (by default OBIS codes Ref[8]) are configurable with AIMS. Used Push buttons: A only to go from one parameter to the next one. 2.5.2.1.2 Sub mode Auto Scrolling

Each parameter is displayed every 5 seconds.

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 17 of 43

ACTARIS

CONFIDENTIAL

2.5.2.2

Special function mode / Available data and action

IMPORTANT: This mode is not accessible when there is a communication in progress


Special Function Main State Chart Actions sub-State Chart Principle

Normal Mode
Short Press B

Value n
XXX.n
Special Function Mode
A pressed

Value n+1 Sequence 1


A&B pressed A pressed A pressed

XXX.n+1
A pressed (Action canceled)

Sequence 2 Value m
A&B pressed

XXX.m
A pressed

Sequence n
A and B pressed

Proposed Action

B pressed (Action confirmed)

Values

are one of these: billing energy registers per tariff; status word; maximum currents per phase and per tariff. be one of these: generate End Of Billing; erase Status Word. erase Max Currents.

Execution Report

Proposed Action can bill , to rESEt , to rESEt , to

At these step, user can either: execute proposed action by pushing S button; cancel action and restart the sequence by pushing D button.

Execution Report can be one of these: Eob , to indicate End Of Billing is done; St = 0 , to indicate Status Word is erased; MC = 0 , to indicate Max Current is erased.

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 18 of 43

ACTARIS

CONFIDENTIAL

Once entered in Special Function Mode the following sequences could be used (Hypothesis: all the possible actions chose by the customer) Sequence 1: LCD Test : All segments displayed (Good repair to check the Special Function Mode enter because of the limited Human Interface Ergonomy) Sequence 2: Reset Maximum current per tariff and per phase (depending on the contract) Sequence 3: Reset Status Words Sequence 4: Test of output relays. Sequence 5: End Of Billing Sequence 6: Set the date and time Because Sequence 4 and 6 does not strictly follow the State-Chart above, the two next State-Chart describes the procedure to follow.

Relays test sub-State Chart

tESt
relay(s) icon()s D pressed

tESt 1
1 or 2 relays opened A pressed (only 1 relay) D pressed

NOTE 1: this sequence is accessible if the meter has at least 1 relay. Otherwise, it will be bypassed by the meter. NOTE 2: if there is only 1 relay, the 2 last states are bypassed.
A pressed

tESt 2
1 or 2 relays closed D pressed (2 relays)

tESt 3
left relays opened - right relay closed D pressed

tESt 4
left relays closed - right relay opened

A&B pressed

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 19 of 43

ACTARIS

CONFIDENTIAL

Date and time setting sub-State Chart

A & B pressed

DD:MM:YY
Date setting code A or B pressed

A & B pressed

HH:MM:SS
Time setting code A or B pressed

A & B pressed

A pressed increase Year

DD:MM:YY
Date setting code A&B pressed

B pressed decrease Year

A pressed increase Hour

HH:MM:SS
Time setting code A&B pressed

B pressed decrease Hour

NOTE 1: if the time format is AM/ PM, a dot is used to indicate AM/PM information. Dot lightened means PM. This dot is located just after SS field. NOTE 2: even if the date format is MM:DD:YY, day setting comes after month setting.

A pressed increase Month

DD:MM:YY
Date setting code A&B pressed

B pressed decrease Month

A pressed increase Minute

HH:MM:SS
Time setting code A&B pressed

B pressed decrease Minute

A pressed increase Day

DD:MM:YY
Date setting code

B pressed decrease Day

A pressed increase Second

HH:MM:SS
Time setting code A&B pressed

B pressed decrease Second

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 20 of 43

ACTARIS

CONFIDENTIAL

2.5.2.3

Test Mode / Available data and actions

This mode allows to change the energy type retransmitted on the metrological Led (Active or Reactive), to increase the Led constant Pulse / kwh or kvarh and to read the active or reactive energy register in 5.2 format (2 decimals). Note: In order to allow a customer to stay in test mode in their Laboratory for example, the Exit Time Out of this mode is configurable in days and independent from power down/up.

Test Mode
Reminder: Long Press on B to enter in test mode fromReading Mode 2 Exit Conditions, either Long Press on B or continuous x days test mode time-out (configurable). In case of power down in test mode, test mode is recovered at Power up. P is the Led pulse constant (configurable) IR communication (COSEM or 1107) are authorised in this mode.

Reading Mode

Metrological Led
Ph1

LCD
123456
kWh
Ph2 Ph3

LED Active P pulses / kWh

LONG press B

Ph1

LED Active P pulses / kWh

LEd

kWh

Short press A Short PressA

23456.78

kWh

Ph2 Ph3

Short Press B

Current active (or reactive) index. Phase icons are lighting if blocked or unlighting if started. Ph1

LED Active 5000 pulses / kWh

LEd 5

kWh

Short press A Short PressA

23456.78

kWh

Ph2 Ph3

Short Press B and Reactive Register visible

Ph1

LED Ractive P pulses / kvarh

LEd

kvarh

Short press A Short press A

06875.42

kvarh

Ph2 Ph3

Short Press B and Reactive Register visible

Ph1

LED Ractive 5000 pulses / kvarh

LEd 5
Short Press B AND Reactive Registers NOT visible

kvarh

Short press A Short press A

06875.42

kvarh

Ph2 Ph3

Long Press B or Time Out

Test Mode Metrological LED

Ph1

LED Active P pulses / kWh

123456

kWh

Ph2 Ph3

Reading mode

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 21 of 43

ACTARIS

CONFIDENTIAL

2.5.2.4

Alarm Mode

If an overvoltage is detected on RMS Voltages per phase (overvoltage threshold configurable), the message "ALArM V" is displayed. 10 second after the overvoltage disappears, the LCD comes back to the previous state in Display mode.

2.5.3

Metrology LED

The LED designed to emit the metrology pulses is visible from outside, with the meter in operating position. The nominal characteristics of this LED are as follows: luminance (10 mCd) red colour Angle of vision 15. Convergence is obtained for a distance between 0 and 5 mm from the front panel. A metallic part on the meter case is used to hold a reading cell by magnetic attraction. Pre-centering exists on the meter.

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 22 of 43

ACTARIS

CONFIDENTIAL

3 METROLOGY
3.1 Metrology Indications
The ACE 5.1 is a Class1 Active energy meter according to IEC61036 and a Class2 Reactive energy meter according to IEC61268.

3.1.1

Metrology principle

The apparatus is equipped with 3 special design current transformers, internally called MCT (Mutual Current Transformer), providing the AD converter with an analogue current ratio. Samples read on the meter elements, which are not modified by calculation, are (V1, V2, V3, I1, I2, I3) and permit, among others, the calculation of active, reactive and apparent energy quantities, as well as the power factor and RMS values. Voltage and current signals are sampled and processed to be compensated, equalised, calibrated and phase corrected in order to give final filtered voltage and current values.

3.1.2

Metrology modes

Two different energy measurement modes are available in the meter. Bi-directional Mode - concerns (P+, P-, Q+) and is represented by the symbol

Unidirectional Mode - concerns (P+, Q+, Q-) and is represented by the symbol Note: These 2 energy measurement modes are factory programmable only Within each mode there are three available aggregate energy calculation mode: Ferraris, Static, Anti-fraud. Note: These 3 aggregate energy calculation modes are customer programmable Description of Bi-directional Mode: (P+, P-, Q+)
"n" is the phase number

Ferraris

Static

Anti-fraud

Metrology LED

LED

Active

| |

Pn |

LED Reactive PO Active

Qn | Pn+ Qn+ Pn+ | Pn-| Qn+


+ |

Pulse Output PO Reactive P+ Register Energy Registers P- Register Q+ Register

Pn if P > 0
n

Pn+ Pn+

Pn- |

Qn if Q > 0
n

Pn if P > 0
n

+ |

Pn- |

Pn if P

<0
n

Qn if Q > 0

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 23 of 43

ACTARIS

CONFIDENTIAL

Description of Unidirectional Mode: (P+, Q+, Q-)

"n" is the phase number

Ferraris

Static

Anti-fraud

Metrology LED

LED

Active

| |

Pn |

LED Reactive PO Active

Qn | Pn+ Qn+ Pn+ Qn+ | Qn-|


+ |

Pulse Output PO Reactive P+ Register Energy Registers Q+ Register Q- Register

Pn if P > 0
n

Pn+ Pn+

Pn- |

Qn if Q > 0
n

Pn if P

>0
n

+ |

Pn- |

Qn if Q > 0 Qn if Q < 0
n

Example depending on the measurement mode chosen above, after 1 second of measurement period
Measured Active Energy (wh) Status of Active Energy Measured Reactive Energy (varh)

Phase

I II III

+2 -5 +1

Import Export Import

+7 -5 +1

The metrology outputs and the different registers will then be distributed the way described below :

Ferraris

Static

Anti-Fraud

Metrology pulses Active Metrology pulses Reactive Pulses in PO Active Pulses in PO Reactive Energy register P+ Energy register PEnergy register Q+

|2 -5+1|=2 |7 -5+1|=3 2 - 5 + 1 = -2 => 0 2+1=3 7+1=8 2 - 5 + 1 = -2 => 0 2 - 5 + 1 = -2 => 2 2+1=3 5 7+1=8 2+5+1=8 5 2+5+1=8

Ferraris

Static

Anti-Fraud

Metrology pulses Active Metrology pulses Reactive Pulses in PO Active Pulses in PO Reactive Energy register P+ Energy register Q+ Energy register Q-

|2 -5+1|=2 |7-5+1|=3 2 - 5 + 1 = -2 => 0 2+1=3 7-5+1=3 2 - 5 + 1 = -2 => 0 2+1=3 7-5+1=3 7 - 5 + 1 = 3 => 0 2+5+1=8 2+5+1=8

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 24 of 43

ACTARIS

CONFIDENTIAL

IMPORTANT : As shown above, although the export reactive energy is selected, leaving only one active energy register, the meter still measures the export active energy but this value is saved only when in anti-fraud mode.

3.1.3

Metrology LED constant and duration

The metrology LED has been designed to display metrology luminous pulses (blinks) for active or reactive energy, visible from outside, with the meter in operating position. The LED transmits active or reactive energy pulses depending on configuration. The led is mainly used for meter calibration. And its nominal pulse length is 10 ms for ON state and 10 ms for OFF. Meter constant corresponds to the electrical energy measured between two consecutive pulses. No problem of saturation exists with the pulses, even in case of heavy consumption. ( Over 3ph @ 1.2 Imax (144A) & 1.25x240V ) 3.1.3.1 LV/DC Metrological Led constant

Standard pulse rates: 500 - 1000 2000 pulses/kWh (Configurable with AIMS) In LCD Test mode the pulse rate could be increased to 5000 pulses/kWh 3.1.3.2 LV/CT Metrological Led constant

Standard pulse rates: 50 - 100 200 pulses/kWh (Configurable with AIMS) In LCD Test mode the pulse rate could be increased to 500 pulses/kWh

3.1.4

Pulse Output

During a cut -off, a saving into the EEPROM of pulses which have to be emitted is done, in order to retransmit it just after power-up. In case of saturation, the LED pulses and the pulse of the pulse output device will no longer be synchronised. The Pulse emitter device can be active or inactive. The selection of pulse transmission (active or not) is carried out via IR communication. The pulse output device is exclusive with the Data Output (see 6.1.3). (Recall of definition under DIN 43-864 and IEC 62053-31 type A) max voltage : U = 27 V DC max current : I = 27 mA DC max wire length : l = 0.5 m (for a standard DIN S0 pulse emitter connection) 3.1.4.1 LV/DC Metrological Led constant

Standard pulse rates: 500 - 1000 2000 pulses/kWh (Configurable with AIMS) 3.1.4.2 LV/CT Metrological Led constant

Standard pulse rates: 50 * CT ratio - 100 * CT ratio 200 * CT ratio pulses/kWh (Configurable with AIMS)

3.1.5

Instantaneous values

Rms currents and voltages

Rms Current per phase and Rms Voltage per phase are calculated from an accumulation of squared Current and Voltage samples between 1 second tops, being square-rooted during the same time period. Active Power

The meter calculates every second the instantaneous Active Power quantity W. The Active Energy calculated at the sampling frequency (USAMPLE * ISAMPLE) is accumulated in the Active Power register every second providing an average instantaneous Active Power every second once divided by the number of samples over

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 25 of 43

ACTARIS

CONFIDENTIAL

the period. Its sign is used to determine the active energy direction (import or export) and its absolute value is used to determine if the energy status is BLOCKED or STARTED. Average Apparent Power

Measurement of the RMS Apparent Power is carried out every second using the RMS arithmetic method : the Apparent Power VA comes from the multiplication between Urms and Irms. Power Factor (P / S )

The power factor is calculated every second per phase and aggregate. Pfagg = kWagg / kVAagg The resolution of the calculation is 0,01. The calculation uses active power signed and apparent power unsigned. The sign of the Power Factor is the sign of Active Power. Phase sequence (V 1/V2, V1/V3, V2/V3) This function returns the voltage to voltage angle according to the different connection types. From these angles are deduce the phase sequence. When the phase sequence is wrong, a bit is raised in the status word. As soon as the right connection is restored, the bit is reset .

3.2

Exploitation data
Design Note : all energy registers are calculated and saved with the precision of one unit ( 1x100).

3.2.1

Energy Registers
*1 *1

Nota: Internal energy register resolution is Wh and Varh respectively for Active and Reactive energy. P+ [1..n] P+Total (NR) (NR) Active Energy Import, data registered per tariff. No reset possible. Active Energy Import Total, sum-up of all Active Energy Import tariff registers. No reset possible. This register is tariff independent. Billing Active Energy Import, data registered per tariff during a billing period. Registers reset to zero at End Of Billing (EOB) Billing Active Energy Import Total, sum-up of all Active Energy Import tariff registers during a billing period. Register reset to zero at End Of Billing (EOB). This register is tariff independent. Historical Billing Active Energy Import, data registered per tariff during the previous billing period. Registers reset with respective tariff Billing Active Energy Import registers value at End Of Billing (EOB) Billing Active Energy Import Total, sum-up of all Active Energy Import tariff registers during a billing period. Register refreshed at End Of Billing (EOB). This register is tariff independent.

Bill.P+ [1..n] Bill.P+Total

Hist.Bill.P+ [1..n]

Hist.Bill.P+Total

*1

These are described as Import registers but they cumulate Export energy as well as when Absolute Value Mode is selected

P- [1..n] P-Total

*2 *2

(NR) (NR)

Active Energy Export, data registered per tariff. No reset possible. Active Energy Export Total, sum-up of all Active Energy Export tariff registers. No reset possible. This register is tariff independent. Billing Active Energy Export, data registered per tariff during a billing period. Registers reset to zero at End Of Billing (EOB)

Bill.P- [1..n]

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 26 of 43

ACTARIS

CONFIDENTIAL

Bill.P-Total

Billing Active Energy Export Total, sum-up of all Active Energy Export tariff registers during a billing period. Register reset to zero at End Of Billing (EOB). This register is tariff independent. Historical Billing Active Energy Export, data registered per tariff during the previous billing period. Registers reset with respective tariff Billing Active Energy Export registers value at End Of Billing (EOB) Billing Active Energy Export Total, sum-up of all Active Energy Export tariff registers during a billing period. Register refreshed at End Of Billing (EOB). This register is tariff independent.

Hist.Bill.P- [1..n]

Hist.Bill.P-Total

*2

These are described as Export registers but they cumulate export energy only when this energy is selected

Q+ [1..n] Q+Total Bill.Q+ [1..n] Bill.Q+Total

(NR) (NR)

Import Reactive Energy, data registered per tariff. No reset possible. Import Reactive Energy Total, sum-up of all import Reactive Energy tariff registers. No reset possible. This register is tariff independent. Import Billing Reactive Energy, data registered per tariff during a billing period. Registers reset to zero at End Of Billing (EOB) Import Billing Reactive Energy Total, sum-up of all import Reactive Energy tariff registers during a billing period. Register reset to zero at End Of Billing (EOB). This register is tariff independent. Historical Import Billing Reactive Energy, data registered per tariff during the previous billing period. Registers reset with respective tariff import Billing Reactive Energy registers value at End Of Billing (EOB) Import Historical Billing Reactive Energy Total, sum-up of all import historical Reactive Energy tariff registers during a billing period. Register refreshed at End Of Billing (EOB). This register is tariff independent.

Hist.Bill.Q+ [1..n]

Hist.Bill.Q+Total

Q- [1..n] Q-Total Bill.Q- [1..n] Bill.Q-Total

(NR) (NR)

Export Reactive Energy, data registered per tariff. No reset possible. Export Reactive Energy Total, sum-up of all export Reactive Energy tariff registers. No reset possible. This register is tariff independent. Export Billing Reactive Energy, data registered per tariff during a billing period. Registers reset to zero at End Of Billing (EOB) Export Billing Reactive Energy Total, sum-up of all export Reactive Energy tariff registers during a billing period. Register reset to zero at End Of Billing (EOB). This register is tariff independent. Historical Export Billing Reactive Energy, data registered per tariff during the previous billing period. Registers reset with respective tariff export Billing Reactive Energy registers value at End Of Billing (EOB) Export Historical Billing Reactive Energy Total, sum-up of all export historical Reactive Energy tariff registers during a billing period. Register refreshed at End Of Billing (EOB). This register is tariff independent.

Hist.Bill.Q- [1..n]

Hist.Bill.Q-Total

*3

These are export reactive energy registers, used only when this energy is selected.

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 27 of 43

ACTARIS

CONFIDENTIAL

3.2.2

Maximum Demand Registers

The values measured by the Maximum Demand Registers are power averages determined over a chosen number of Sub-Intervals with a selected time duration: Number of Sub-intervals: N = 1 to 5, 10 and 15. Sub-Interval Duration in minutes: DT = 1, 3, 5, 10, 15, 20, 30, 60.

The calculation of the MDR is synchronised on the RTC, i.e. the time of an end of integration period is a multiple of the programmed sub-interval duration.

Sub intervals duration (min.)

Time of end of integration period Minutes 0, 1, 2, 3, 4, 5, 6, 7, .., 58, 59 of an hour. Minutes 0, 3, 6, 9, 12, 15, 18, 21, 24, 27, 30, ., 54, 57 of an hour. Minutes 0, 5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55 of an hour. Minutes 0, 10, 20, 30, 40, 50 of an hour. Minutes 0, 15, 30, 45 of an hour. Minutes 0, 20, 40 of an hour. Minutes 0, 30 of an hour. Minute 0 of an hour.

1 3 5 10 15 20 30 60

In case of exceptional events (tariff change, end of billing, contract change, power down or clock setting (except DST event)), the ongoing integration period is stopped. Depending on a choice made by a programmed parameter through the IR communication port, the calculation of the last integration period can be neglected or computed theoretically as if the integration period was complete. After these events (power up instead of power down), a new integration period begins: the time between the event and the end of the integration period synchronised on the RTC is considered as a complete integration period.

One of two maximum energy types could be managed depending of the customer order (once the type defined, it is not possible to change afterwards either with Push buttons or with AIMS). The possible types are Active Import (P+) or Apparent Import (S+).

MDI.P+ [1..n] (respectively S+)

W (resp. VA) - Maximum Demand Register of Active Power Import per tariff. Average maximum power per tariff over the predefined number and duration of Sub-intervals. Reset to zero at End Of Billing (EOB). (respectively Apparent Import)

MDI.P+ (respectively S+)

W (resp. VA) - Maximum Demand Register of Active Power Import. This register is tariff independent and represent the maximum of the MDI.P+ [1..n]. Reset to zero at End Of Billing (EOB). (respectively Apparent Import)

Hist.MDI.P+ [1..n] (respectively S+) W (resp. VA) - Historical Maximum Demand Register of Active Power Import per tariff. Registers refreshed with respective Maximum Demand Indicator of Active Power Import per tariff registers value at End Of Billing (EOB). (respectively Apparent Import)

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 28 of 43

ACTARIS

CONFIDENTIAL

Hist.MDI.P+ (respectively S+)

W (resp. VA) - Historical Maximum Demand Register of Active Power Import. Register refreshed with Maximum Demand Indicator of Active Power Import registers value at End Of Billing (EOB). (respectively Apparent Import)

3.2.3

Maximum Registers

The maximum registers report the maximum values over an averaged sliding period of time, this period of time is called Filter Time Constant and can take the following values: 20 seconds, 5 or 10 minutes. The averaged Current values per tariff are used for Load Management ( see 4.4). The aim of this sliding window is to simulate the thermal behaviour of a circuit-breaker allowing the detection of fraud to the subscribed currents. These values are reset to zero via the IR communication port or using the push buttons. The meter is also equipped with a special memory case where the maximum voltage values per phase are saved.. Max.I1/2/3 Max.I1/2/3 [1..n] Max.P+ A - Maximum current per phase measured selected time window. A - Maximum current per phase and per tariff measured the selected time window. W - Maximum Active Power Import measured for the selected time window

In addition maximum voltages are not filtered in order to detect over-voltage events. Max U1/2/3 V - Maximum voltage per phase (non resettable)

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 29 of 43

ACTARIS

CONFIDENTIAL

4 TARIFFS
4.1 Definition & ACE 5.1 Time Switch:
A tariff, or rate, is a well-determined period of time during which a set of registers is enabled and used for billing purposes. The meter carries only one living tariff at a time, applicable to all billing registers, being able to change it 8 times every 24-hour period. The ACE 5.1 is equipped with 8 tariffs that can be used to set 4 different day profiles. Each day profile will then be used to define the meter's behaviour through 7-week days, defining a week profile. There are 4-week profiles available, one for each season (therefore 4 seasons). 72 special days are available which are defined through the set of generic dates. These dates are defined either by a year less fixed date (ex: 01_MAY) or by a generic sliding date (ex: First Sunday of November). The group of Timse Switch options is defined as a calendar. Able to support a calendar from 01_JAN_2000 to 31_DEC_2099, the apparatus carries the following functions: Leap year every year that can be divided by 4 is a leap year. When internal time of the meter is 31_DEC_2099 at 23h59mn59sec, then Date & Time restart from 01_JAN_2000 at 0h0mn0sec and corresponding bit in the RTC Status word is set. Leap year Management is not configurable. Day Light Saving Time a total of 16 years could be handled with 32 programmed dates. It is also possible to define generic dates. 2 DST adjustments can be defined each year; one advance & one reverse in any order. In the same configuration, for each year, advance & reverse DST adjustment shall be always in the same order and contains therefore a total of 32 DST adjustments. Current and Latent calendar the future calendar allows a change of time switch behaviour after a configurable date. (This feature is particularly useful when an utility wants to programme a simultaneous calendar change over a wide meter population)

Each tariff can have a different subscribed current. These subscribed current per tariff can be used by the utilities for billing purposes as it establishes a current threshold. This threshold is responsible for the Load Management, i.e., the control of up two relay outputs (see 4.4 Load Management). Besides the control by current threshold, the relays could also be controlled by the daily tariff changes (maximum 8 per day).

4.1.1

Power-Up

In case of a mains failure the meter re-synchronises the calendar at power-up with the current Date & Time and sets the state of the meter (Tariff rate, Relays & Excess Demand Flag) according to the current Date & Time. At power-up, if Date & Time is lost, the RTC restart 01 January 2000, in addition a flag is set, allowing blinking of time displayed on LCD.

4.1.2

Power-Down

While power is down the meter continues to count Date & Time, within its auxiliary power supply limits. No other actions are performed. (See 2.3 for definition on Real Time Clock)

4.1.3

Precision on RTC setting

Depending on the configuration, the format of the available RTC information on the Display, will be either on a 24h or 12h format (plus AM/PM).

4.2

Contract change

A contract is the name given to the set of up to 8 tariffs, or rates, agreed between the utility and the final client. A contract change can only be performed through the IR communication port using AIMS 5000. It allows for a given pre-programmed Time Switch to limit or extend the tariffs used. When the contract change is processed, an automatic EOB is performed.

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 30 of 43

ACTARIS

CONFIDENTIAL

4.3

End of Billing (E.O.B.)

The End Of Billing orders are given either by the IR communication port, using the push button or through the pre-programmed internal calendar. Two types of EOB could be performed (configurable by the customer with AIMS 5000) "Cumulative" mode: Copy of the billing registers per tariff and total into the corresponding registers "Hybrid" mode: Copy of the billing registers per tariff and total into the corresponding registers and reset of the billing registers per tariff.

The internal calendar carries up to 12 year-less End Of Billing dates (day / month) permitting yearly roll-over and it occurs by default at 00:00:00 hours. Note: If a power-off masks more than one End of Billing event, only one End of Billing will be generated at power-up.
Note: For a matter of security, specially thinking on manual meter reading events, the meter prevents two End Of Billing orders within the same half-hour (30 minutes). If by any chance two successive EOB orders were given too close, and no energy had been registered, the data of at least one historical set of registers would have been lost.

4.4

Load Management

Load Management (dynamic load management or load shedding) is a functionality that generates actions directly on the output circuits (relays). As soon as averaged RMS current (see 3.2.3) of one of the 3 phases is above the subscribed current in use (the current threshold chosen per tariff - 4.1), an excess of consumption is detected. The relays are then switched to a pre-defined position (configurable with AIMS). The meter has two output circuits delivered as options. The output circuits are equipped with single direction, single-pole electric-control cut-off equipment. These controls lead to stable states able to support currents up to 5A and 250V. The actions over the relays are made through the tariff change and through the control of the consumed current by the load connected to the meter As well as to the hysteresis control values, explained below. The hysteresis avoids the relays to switch on & off too many times when the averaged current value is around the subscribed current. The management of the load through the evaluation of its current threshold is prior to the tariff. An icon is set and erased on the display depending of the status of the over-current. The hysteresis values are defined in the Configuration programme and loaded into the meter through the optical port. The example below represents the averaged current of a phase and the state of a relay when the hysteresis values are crossed.

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 31 of 43

ACTARIS

CONFIDENTIAL

Hysteresis High Value

Subscribed current

Hysteresis Low Value

Relay ON

Relay OFF

Relay ON

Electrical requirement: Breaking power of the enclosed output circuits Each output circuit is able to carry out 60 000 operations (30 000 closings and 30 000 openings) under the following conditions: * Imax under 250 V, 50 Hz on a resistive circuit with constant value, * Imax/2 under 250 V, 50 Hz, on an inductive circuit with a power factor equal to 0.4. Undervoltage The output circuits do not cause faulty operation under the sole effect of the disappearance of the network voltage, or upon its re-establishment.

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 32 of 43

ACTARIS

CONFIDENTIAL

5 DIAGNOSTIC AND SURVEY


The following exploitation data are intended to provide information to ease ACE 5000 maintenance and exploitation and failure diagnostic.

5.1.1

ParameterSetChecksum

This register contains a 16bit checksum of all the customer configuration data set. It avoids reading the whole configuration set to check if it is the correct one programmed in the meter.

5.1.2

ProgrammingCounter

This register counts the number of programming attempts from IR port and from the user interface. The maximum capacity of the register is 65500. When it reaches this limit, it stays at this value even if another programming action happens. This register cannot be reset.

5.1.3

ReverseFlowCounter

The number of export transits is registered in a register with a maximum capacity of 65500. This register cannot be reset and when it reaches its maximum value, it stays there even if a new reverse flow occurs.

5.1.4

BillingPeriodCounter

The number of billing periods is registered with a maximum capacity of 255. This register cannot be reset and when it reaches its maximum value, it stays there even if new billing period occurs.

5.1.5

Terminal Cover Opening Counter

This register counts the opening number of the sealed terminal cover. The maximum capacity of the register is 255 (1 byte), After it reaches this values, the next opening cover event brings this register back to 0, and a fraud register overflow bit (erasable) is indicated on the status word. This register cannot be reset.

5.1.6

CutOffCounter

This register counts the cut off numbers. The maximum capacity of the register is 255 (1 byte), After it reaches this values, the next cut off brings this register back to 0, and a fraud register overflow bit (erasable) is indicated on the status word. This register cannot be reset.

5.1.7

StatusWord

The standard status word provides the following information Incorrect Phase sequence Cut off overflow flag Frauds overflow flag.. Overvoltage flag. . Phase loss flag per phase Memory test flag

5.1.8

Check Reading register

This data available on LCD is a signature of the active import energy register used in the current contract, which allows the utility to prevent billing tampering in case or "manual" reading.

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 33 of 43

ACTARIS

CONFIDENTIAL

6 COMMUNICATIONS
6.1 IR communication port :
The communication is the mean, which gives access both to the meters exploitation data and to its configuration data. The meter carries one full communication protocol, DLMS/COSEM (IEC 62056) with connection mode E of IEC61107, and a Flag (IEC 61107) data read-out capacity. The remote access to the meter is made through an infrared optical port based on the flag protocol IEC 61107. This port is situated beneath the liquid crystal display on the left hand side. It is equipped with a metallic part to hold a reading cell by magnetic attraction (pre-centering exists). All of the technical and functional characteristics of the local communication link are according to [6]. COSEM is a multi layered protocol, including physical, data-link, application layer. COSEM by a formal definition of data type (COSEM objects) and a non-ambiguous data identification (OBIS Code) guarantee interoperability on a lot of metering data.

Flag- Connection Mode C and E


Client / ? Device address ! CR LF HHU

Server Tariff Device

/ XXXZ \W Ident CR LF

300 bd. 7E1

Data Readout
ACK 0 Z 0 CR LF

Mode E-HDLC
ACK 2 Z 2 CR LF

STX Data ! CR LF ETX BCC

NACK

ACK 2 Z 2 CR LF

Z bd. 7E1
End

METERING HDLC protocol

Z bd. 8N1

6.1.1

Flag (IEC 61107) Read-out

Communication speed: After connection at 300bauds, ACE 5000 proposes 9600 bauds The data readout content is configurable in the same manner than Data Bus Output (see 6.2).

6.1.2

COSEM Reading and Programming

Communication speed: After connection at 300bauds, ACE 5000 proposes 9600 bauds Authentification mechanism: Password (no encryption) Client type: one client type (Utility) allowed to read, program, execute some scripts depending on access rights given by configuration in factory according to the utility needs. NOTA: For the exhaustive list of Configuration and Exploitation data please refer to Annex 9.2.

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 34 of 43

ACTARIS

CONFIDENTIAL

6.1.3

DATA BUS OUTPUT

The Data Bus Output is situated on the right hand side of the meter cover and is exclusively set by the programming software (AIMS 5000) as a Pulse Output or a Serial Data Output. This feature allows to read locally or remotely a configurable set of data (Via AIMS). Indeed once configured in D.B.O. mode the meter send always the data refreshed as soon as their content changed without any costly system.

6.2

Local Reading

PC

Meter ACE 5000

PC DBO Interface

6.2.1

Principle

The Data Bus Output allows to get meter data from the RS232 port of a PC. The connection is done through a simple interface (PC DBO Interface) using a twisted pair, screwed in terminals on the meter side, and ended by a SubD9 connector including hardware adaptor. The data can be simply read using Hyperterminal, such as shown below or by a specific application for post processing .

Frame format: According to the configuration, the data readout set is composed by x lines, each line contents the data identifier on 4 ASCII characters followed by the data value between brackets; the data value includes the numerical value and the corresponding unit if significant). Speed: 1200 bps

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 35 of 43

ACTARIS

CONFIDENTIAL

Data: Parity: Stop bit:

7 Even 1 25ms 25ms

Average Time out inter line: Average Time out inter frame (set of lines):

NOTA: For the exhaustive list of the data available and configurable on DBO and Readout please refer to Annex 9.2.

6.2.2

Data Format

One data per line: "Data ID" ("Value" [*] "Unit") [YY-MM-DD HH:MM:SS] Field Data ID: OBIS Code Field * optional separator in case of unit Field Unit: V, A

IMPORTANT: The Data Identification (OBIS Code) string is not configurable.

6.2.3

Remote Reading

PC

Modem

PSTN Modem Meter ACE 5000

IMPORTANT: A specific Interface cable must be used to connect the meter to the Modem. The Modem connected to the meter must be powered independently. All the other characteristics remains the same than for local reading (Format, Data).

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 36 of 43

ACTARIS

CONFIDENTIAL

7 INSTALLATION
The following procedure is recommended in case of a first installation of ACE 5000.

7.1

Preliminary verifications before the meter is powered up

Warning : the ACE 5000 measurement circuit wiring diagram is non-symetrical VDE. It is important to verify that the measurement circuits are correctly wired to the meters terminal block. NON-SYMETRICAL

1 +I1

2 U1

5 U2

6 -I2

7 +I3

11 UN

-I1 +I2

U3 -I3

The pulse outputs is a "low level" type and so it is important to verify that no voltage greater than 30 Volts is connected to these terminals.

7.2

Battery connection [optional]

The battery has an equivalent life time of three years accumulated power interruptions. The battery is disconnected in all new meters. The battery must be connected just before the first power up sequence but not prematurely since this will unnecessarily reduce the batterys life time.

7.3

LCD testing and Date and Time Setting

According to 2.5.2.2

7.4

Battery replacement [Optional]

The battery has an equivalent life time of three years accumulated power interruptions and a natural life time of 10 years. Th e non-fatal battery error is displayed when 80% of the equivalent life time has been used or when the natural life time end date has been exceeded or when the terminal voltage falls below 2V. It is possible to change the battery without altering the meter data. Once the battery has been changed then the battery natural life time end date must updated under the battery gate.

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 37 of 43

ACTARIS

CONFIDENTIAL

8 READING AND CONFIGURATION TOOL / "AIMS 5000"


Note 1: The purpose of this section is not to describe in details AIMS+ which is self "documented" (Help on line) but to present the main features. Note 2: Two main type of access are provided: Administrator (able to manage the others users permissions) and the others.

8.1

Installation

Follow the installation procedure provided in the CD ROM.

8.2

Setup

This menu allows to configure general items on the PC (Com port, )

8.3

User and permissions management

In order to facilitate the management of the users . The administrator could create and modify 4 differents user profiles group which gives access to specific functions sub-sets.

8.4

Meter management

AIMS 5000+ is able to manage meter database which contains a few data such as Serial number Utility passwords Customer Field

8.5

Configuration

This main function provides creation, modification and storage of the configurations. A configuration is a set of configuration parameters (See 0). In addition it is possible to export or import configuration files to exchange between different users on different PC.

8.6

Cosem Connection

This specific item allow to establish a COSEM connexion with the ACE 5000 with an optical head.

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 38 of 43

ACTARIS

CONFIDENTIAL

8.7

Configuration programming

Once configuration defined and Cosem connection established with a meter, it is possible to program (write) whole or part of configuration.

8.8

Data reading

As per programming, it is possible to read whole or part of exploitation data (see Error! No se encuentra el origen de la referencia.) stored in the meter. Once read the data are stored in directory organised by meter serial number. The data could be also exported in exel file format for further processing.

8.9

Specific actions
Clock setting Relay testing Metrological Led testing

This item group specific actions such as

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 39 of 43

ACTARIS

CONFIDENTIAL

9 ANNEXES
9.1 Norms

General applicable Standards: 1. IEC 61036 Second Edition:1996-09 + Amendment 1 2. 3. 4. IEC 61268 IEC 61038 DIN 43857 First Edition: 1995-09 Edition 1.2: 1998-11 Part 2: 1978-09 Part 4: 1974-12 5. DIN 43859 1977-06 Draft Standard: 1990-03 Electronic a.c. watt-hour meters; (Accuracy class 1 and 2)

Electronic a.c. reactive volt-ampere-hour meters (Accuracy classes 2 and 3) Time switches for tariff control Electricity meters housed in insulation material for direct connection up to 60 A limit current; Electricity meters for instrument transformer connection; main dimensions for three-phase meters

Nota: NMI approval tests were also passed agains the new version of the general standards IEC 62052-11 : Electricity metering equipment (a.c) - General Requirements, Tests and test Conditions Part 11 : Metering equipment IEC 62053-21 : Electricity metering equipment (a.c) - Particular Requirements - Part 21 : Static meters for active energy (classes 1 and 2) IEC 62053-22 : Electricity metering equipment (a.c) - Particular Requirements - Part 21 : Static meters for active energy (classes 0.2 S and 0.5 S) IEC 62053-23 : Electricity metering equipment (a.c) - Particular Requirements - Part 21 : Static meters for reactive energy (classes 2 and 3)

Communication Standards: 6. 7. 8. 9. IEC 62056-21 IEC 62056-42 IEC 62056-46 IEC 62056-53 Edition 1.0: 2002-05 Edition 1.0: 2002-02 Edition 1.0: 2002-02 Edition 1.0: 2002-02 Edition 1.0: 2002-02 Edition 1.0: 2002-02

Direct Local Data Exchange (3rd edition of IEC 61107) Physical layer services and procedures for connection oriented asynchronous data exchange Data Link Layer using HDLC-Protocol COSEM Application Layer OBIS Object Identification System Interface Objects

10. IEC 62056-61 11. IEC 62056-62

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 40 of 43

ACTARIS

CONFIDENTIAL

9.2

Configuration and Exploitation data


A B Meaning Indicates which accesses are allowed when the meter is in customer mode. -> Get: reading -> Set: programming -> Get/Set: reading and programming Some Customer mode access rights are programmable. A star ( * ) indicates that Get (resp. Set) can be allowed or not. If there is no star, then the corresponding access right is fixed. Indicates if corresponding data can be available on DBO and Readout. -> Y: available -> N: never available TS -> Y* : available and Time Stamped, depending on Readout And DBO Configuration object. Indicates if corresponding data can be displayed depending on Display Configuration -> Y: available -> N: never available

Column Cust. Mod.

3 Configurable access 4 DBO (Y/N) 5 Display (Y/N) 6

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 41 of 43

ACTARIS Configuration data

CONFIDENTIAL

A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64

D E Logical Name B C D

G H

I Cust. Mode

K L

Configurable Access

M N O DBO Display Y/N

Get Set

A light green background indicates which codes are showed when the object is displayed 96, 97, 98 and 99 can be displayed as C, F, L and P (respectively), as allowed by IEC 62056-61

Metrology Metrol reading parameters Metrol output control 1 Metrol output control 2 Constants LED Active Constant LED Reactive Constant PULSE Active Constant PULSE Reactive Constant Metrol calibration date and time Measurement parameters Measurement modes (Aggregate energy calculation mode) Current transformers ratio numerator Current transformers ratio denominator Response times Maximum current response time Maximum power response time Maximum demand parameters Real Time Clock Clock Daylight saving time Time switch Activity calendar Special day table Logical device Current Association Logical Device Name Utility association Public client association Utility access rights Billing Period End of Billing parameters Status Meter Status Register and contract parameters Demand management parameters Readout And DBO Configuration Subscribed currents Subscribed current Auxiliary Output configuration Config contract parameters Contract number Meter identification Firmware identification Customer serial number Customer serial number, left part Customer serial number, right part Factory data Diagnostic Standard diagnostic Status word Display Display configuration parameters Customer field Customer field, left part Customer field, right part Script tables User script (US)

1 1 1 1 1 1 1 0 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 1 0 1 0 1

1 160 1 160 1 160 1 1 1 1 0 0 0 0 0 96

4 2 5 3 3 3 3 2 3 4 4 1 8 8 0 1 0 0 0 0 0 0 1 0 1 1 50 35 1 50 50 1 1 1 1 1 0 5 1 1 1 1

0 255 0 255 0 255 0 1 3 4 5 255 255 255 255 255

Get Get/Set Get/Set Get Get Get/Set Get/Set Get Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get Get Get/Set Get Get Get/Set Get Get/Set Get/Set Get/Set Get/Set Get/Set

N N N N N N N N N Y* Y* N N N Y N N N N N N N N N N N N Y* N N Y Y* Y

N N N N N N N N N Y Y N N N N N N N N N N N N N N N N Y N N Y Y Y

* *

* *

1 160 1 0 1 0 1 167 1 0 1 0 0 1 0 161 0 0 13 11

0 255 2 255 5 255 0 255 1 255 0 255 0 255 0 255 0 255 0 255 0 0 1 2 0 255 255 255 255 255

* * *

* * *

0 40 0 42 0 40 0 40 0 164 0 15

0 255 0 255 0 255 0 255 n 255 0 255 1 255 2 0 0 0 0 1 255 255 128 129 255

0 162 1 163 0 96 1 11 0 168 1 96 96 0 169 0 96 0 96 0 96 0 169 1 140 0 96 0 165 0 96 0 96 0 96 0 10

0 0 0 0 0 1 0 0 0 0 0 0

Get Get

Get Get

N N Y N Y*

N N Y

1 255 0 255 0 1 1 1 255 255 128 129

Get/Set Get/Set

1 101 255

Execute

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 42 of 43

ACTARIS

CONFIDENTIAL

Exploitation data
C D E 65 Logical 66 Name 67 A B C D 68 A light green background indicates which codes are showed when the object is displayed 69 96, 97, 98 and 99 can be displayed as C, F, L and P (respectively), as allowed by IEC 62056-61 70 RMS quantities 71 Instantaneous Voltage Phase 1 1 1 32 7 1 1 52 7 72 Instantaneous Voltage Phase 2 73 Instantaneous Voltage Phase 3 1 1 72 7 74 Maximum Voltage Phase 1 1 1 32 26 75 Maximum Voltage Phase 2 1 1 52 26 76 Maximum Voltage Phase 3 1 1 72 26 77 Instantaneous Current Phase 1 1 1 31 7 1 1 51 7 78 Instantaneous Current Phase 2 79 Instantaneous Current Phase 3 1 1 71 7 80 Power quantities 81 82 Instantaneous Active Power 1 1 15 7 83 Maximum Active Power 1 1 1 16 84 Instantaneous Apparent Power 1 1 9 7 85 Average Apparent Power 1 1 9 14 86 Power factor 1 1 13 7 87 88 Energy quantities 89 Total Import Active Energy (Ferraris or static) 1 1 1 8 90 Total Import Active Energy (anti-fraud) 1 1 15 8 1 1 1 8 91 Tariff Import Active Energy (Ferraris or static) 92 Tariff Import Active Energy anti-fraud 1 1 15 8 93 Total Export Active Energy 1 1 2 8 1 1 2 8 94 Tariff Export Active Energy 95 Total Import Reactive Energy 1 1 3 8 96 Tariff Import Reactive Energy 1 1 3 8 1 1 4 8 97 Total Export Reactive Energy 98 Tariff Export Reactive Energy 1 1 4 8 99 100 Billing Total Import Active Energy (Ferraris or static) 1 1 1 8 1 1 15 8 101 Billing Total Import Active Energy (anti-fraud) 102 Billing Tariff Import Active Energy (Ferraris or static) 1 1 1 8 103 Billing Tariff Import Active Energy (anti-fraud) 1 1 15 8 1 1 2 8 104 Billing Total Export Active Energy 105 Billing Tariff Export Active Energy 1 1 2 8 106 Billing Total Import Reactive Energy 1 1 3 8 1 1 3 8 107 Billing Tariff Import Reactive Energy 108 Billing Total Export Reactive Energy 1 1 4 8 109 Billing Tariff Export Reactive Energy 1 1 4 8 110 111 Billing Maximum Demand Active Energy Register 1 1 1 6 112 Billing Tariff Max Demand Active Energy Register 1 1 1 6 1 1 9 6 113 Billing Maximum Demand Apparent Energy Register 114 Billing Tariff Max Demand Apparent+A87 Energy Register 1 1 9 6 115 116 Historical Billing Total Import Active Energy (Ferraris or static) 1 1 1 8 117 Historical Billing Total Import Active Energy (anti-fraud) 1 1 15 8 118 Historical Billing Tariff Import Active Energy (Ferraris or static) 1 1 1 8 119 Historical Billing Tariff Import Active Energy anti-fraud 1 1 15 8 120 Historical Billing Total Export Active Energy 1 1 2 8 121 Historical Billing Tariff Export Active Energy 1 1 2 8 122 Historical Billing Total Import Reactive Energy 1 1 3 8 123 Historical Billing Tariff Import Reactive Energy 1 1 3 8 124 Historical Billing Total Export Reactive Energy 1 1 4 8 125 Historical Billing Tariff Export Reactive Energy 1 1 4 8 126 127 Historical Max. Demand Active Energy Register 1 1 1 6 128 Historical Tariff Max Demand Active Energy Register 1 1 1 6 129 Historical Max. Demand Apparent Energy Register 1 1 9 6 130 Historical Tariff Max Demand Apparent Energy Register 1 1 9 6 131 132 Total Working Time 0 0 96 8 0 0 96 8 133 Tariff Working Time 134 135 Maximum Overall Current phase 1 1 1 31 6 136 Maximum Overall Current phase 2 1 1 51 6 137 Maximum Overall Current phase 3 1 1 71 6 138 Tariff Maximum Current Phase 1 1 1 31 6 A B F G H I Cust. Mode J K L
Configurable Access

M N O DBO Display Y/N

Get Set

0 255 0 255 0 255 0 255 0 255 0 0 0 0 255 255 255 255

Get Get Get Get Get Get Get Get Get

Y Y Y TS Y TS Y TS Y Y Y
Y

Y Y Y Y Y Y Y Y
Y

0 0 0 0 0

255 255 255 255 255

Get Get Get Get Get

Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y TS Y TS Y TS Y TS Y TS Y TS Y TS Y TS Y TS Y Y TS Y TS Y TS Y Y Y Y TS Y TS Y TS Y
TS TS TS

Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y

0 0 n n 0 n 0 n 0 n 0 0 n n 0 n 0 n 0 n 0 n 0 n 0 0 n n 0 n 0 n 0 n 0 n 0 n

255 255 255 255 255 255 255 255 255 255 255 255 255 255 255 255 255 255 255 255 255 255 255 255 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get

0 255 n 255 0 255 0 255 0 255 n 255

D0216713 Technical Guide ACE 5000 Type 5.1 Release B 03/07/25

Page 43 of 43