Air System Sizing Summary for Reception

Project Name: Coca - Cola Plant at Bangaluru Prepared by: ANA Design Consultancy 09-22-2012 04:23PM

Air System Information


Air System Name Equipment Class Air System Type Reception SPLT AHU SZCAV Number of zones Floor Area Location 1 500.0 ft Bangalore, India

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Sum of space airflow rates Space CFM Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Central Cooling Coil Sizing Data


Total coil load Total coil load Sensible coil load Coil CFM at Jun 1700 Max block CFM Sum of peak zone CFM Sensible heat ratio ft/Ton BTU/(hr-ft) Water flow @ 10.0 F rise 4.5 54.5 44.2 2129 2293 2293 0.810 110.1 109.0 N/A Tons MBH MBH CFM CFM CFM Load occurs at OA DB / WB Entering DB / WB Leaving DB / WB Coil ADP Bypass Factor Resulting RH Design supply temp. Zone T-stat Check Max zone temperature deviation Jun 1700 97.5 / 82.6 74.6 / 60.3 53.2 / 50.5 47.5 0.210 44 56.0 1 of 1 0.0 F F F F % F OK F

Supply Fan Sizing Data


Actual max CFM Standard CFM Actual max CFM/ft 2293 CFM 2053 CFM 4.59 CFM/ft Fan motor BHP Fan motor kW n/a 1.84 kW

Outdoor Ventilation Air Data


Design airflow CFM CFM/ft 113 CFM 0.23 CFM/ft CFM/person 6.80 CFM/person

Hourly Analysis Program v4.51

Page 1 of 4

System Psychrometrics for Reception


Project Name: Coca - Cola Plant at Bangaluru Prepared by: ANA Design Consultancy 09-22-2012 04:23PM

June DESIGN COOLING DAY, 1700

TABLE 1:

SYSTEM DATA
Dry-Bulb Temp (F) 97.5 74.6 53.2 56.0 56.0 73.0 73.4 Specific Humidity (lb/lb) 0.02367 0.00919 0.00805 0.00805 0.00805 0.00844 0.00844 Sensible Heat (BTU/hr) 2445 44184 5821 34967 1024 Latent Heat (BTU/hr) 6813 10336 3519 -

Component Ventilation Air Vent - Return Mixing Central Cooling Coil Supply Fan Cold Supply Duct Zone Air Return Plenum

Location Inlet Outlet Outlet Outlet Outlet Outlet

Airflow (CFM) 105 2129 2129 2129 2129 2129 2129

CO2 Level (ppm) 400 1696 1696 1696 1696 1763 1763

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.967 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4250.8 BTU/(hr-CFM) Site Altitude = 3021.0 ft

TABLE 2:

ZONE DATA
Zone Sensible Load (BTU/hr) 34594 Zone T-stat Cond Mode (BTU/hr) Cooling 34967 Zone Temp (F) 73.0 Zone Airflow (CFM) 2129 CO2 Level (ppm) 1763 Terminal Heating Coil (BTU/hr) 0 Zone Heating Unit (BTU/hr) 0

Zone Name Zone 1

Hourly Analysis Program v4.51

Page 2 of 4

System Psychrometrics for Reception


Project Name: Coca - Cola Plant at Bangaluru Prepared by: ANA Design Consultancy 09-22-2012 04:23PM

WINTER DESIGN HEATING

TABLE 1:

SYSTEM DATA
Dry-Bulb Temp (F) 59.0 0.0 0.0 0.0 0.0 79.0 Specific Humidity (lb/lb) 0.00588 0.00000 0.00000 0.00000 0.00000 0.00000 Airflow (CFM) 0 0 0 0 0 0 CO2 Level (ppm) 400 0 0 0 0 0 Sensible Heat (BTU/hr) 0 0 0 0 0 Latent Heat (BTU/hr) 0 0 0 -

Component Ventilation Air Vent - Return Mixing Central Cooling Coil Supply Fan Zone Air Return Plenum

Location Inlet Outlet Outlet Outlet Outlet

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.967 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4250.8 BTU/(hr-CFM) Site Altitude = 3021.0 ft

TABLE 2:

ZONE DATA
Zone Sensible Load (BTU/hr) -157 Zone T-stat Cond Mode (BTU/hr) Deadband 0 Zone Temp (F) 59.7 Zone Airflow (CFM) 0 CO2 Level (ppm) 0 Terminal Heating Coil (BTU/hr) 0 Zone Heating Unit (BTU/hr) 0

Zone Name Zone 1

Hourly Analysis Program v4.51

Page 3 of 4

Psychrometric Analysis for Reception


Project Name: Coca - Cola Plant at Bangaluru Prepared by: ANA Design Consultancy 09-22-2012 04:23PM

Location: Bangalore, India Altitude: 3021.0 ft. Data for: June DESIGN COOLING DAY, 1700
1. Outdoor Air 2. Mixed Air 3. Central Cooling Coil Outlet 4. Supply Fan Outlet 5. Room Air 6. Return Plenum Outlet 1

0.024 0.022 0.020 0.018 0.016 0.014 0.012

2 56

0.010 0.008 0.006 0.004 0.002 0.000

Specific Humidity ( lb/lb )

30

40

50

60

70 80 Temperature ( F )

90

100

Hourly Analysis Program v4.51