You are on page 1of 125

Its our pleasure present our Company Cable Factory FKN Negotino from Republic of Macedonia.

Cable Factory Negotino is establishment in 1968 year. Our motive is: traditional, quality and safely. Cable Factory Negotino is one of the biggest factories (within 1500 tons of production capacity), and is a leading cable producing company at the Balkan markets. A strategic goal of our factory is maintaining a leading position at the mentioned markets, as well as expanding business activities, especially to western and new markets. Constant dynamic growth is, and will be the result of our activities towards the needs of our customers. Over the years we built a strong reputation for clearly understanding and fulfilling the needs of each individual customer. We have more then 300 satisfy employments. Since the beginning of its establishment CF Negotino have endeavored to include all these new achievements in their own assortment climbing at large and faster development of them. Cable Factory Negotino is working with the International Certification Network ISO 9001:2008, ISO 14001:2004 and OHSAS 18001:2007. Production program of the Cable Factory Negotino comprising: Flexible cable Cables for stationary installation Power cables for rated voltages of 1 kV, 10 kV, 20 kV and 36 kV Armored cables with insulation from PVC or XLPE Self supporting bunch cables Date, telephone, coaxial and control cables, etc. Cables according to customer specification

We want and it is our desire to start and make a good cooperation if your needs are part of our production assortment. Our comprehensive range of products is approved to International Standard (like VDE, BS, JUS, NF, GOST, IEC, BDS, HD, and EN). What we can promise you is the following: *competitive price *on time delivery *quality *good cooperation If you looking for this, please do not hesitate to contact us! If you are interested yes we are also interested to be your supplier!!!! We will be welcome to hear from you!

Flame retardant compounds Weather resistance

UV irradiation resistance The product is in conformity with DIRECTIVE 2006/95/EC

Flame retardant compounds Oil resistance Can be laid in water Can be laid in air (outdoors)

Longitudinal water tightness Mechanical damage resistance Radial water-tightness


< VDE >

Flexible cable VDE approved product

EM V

Screened cable
- Packing
- Fire propagation acc. IEC 60332-3 cat. - Hydrocarbon resistant outer sheath - Termite and rodents protected outer - Oil resistant outer sheath
Fl Cl Br

Low smoke compounds

Can be laid in earth Halogen free compounds

- Protected against direct sun irradiation

- RF - super-fine wire stranded (class 6) - RM - mutliwire round shaped conductor (class 2) - RE - solid round conductor (class 1) - RF - fine wire stranded conductor (class 5)
- RM - mutliwire round shaped
Copper: 1.5mm - 630mm Copper: 35mm - 300mm Copper: 1.5mm - 16mm Aluminium: 50mm - 630mm Aluminium: 50mm - 240mm

- SM - mutliwire sector shaped - RE - solid round conductor

Aluminium: 25mm - 50mm

Acc. to IEC 60228 and VDE 0295

CONDUCTOR FOR ELECTRICAL APPLIANCE and ELECTRIC INSTALLATIONS H03VH-H H03VV-F, H03VVH2-F H05VV-F, H05VVH2-F H05V-U, K;H07V-U, R, K NYM NYM-T NYIFY NYM(St)

TELECOMMUNICATION AND CONROL CABLES J-Y(St)Y ..Lg J-YY ..Lg TK-33-U Coaxial cables UTP cat. 5 FTP cat. 5 S-FTP cat. 5 LiYY, LiYCY LiYY-TP, LiYCY-TP NYSLY OIL, NYSLYCY-OIL SPZ, SEZ YV

LOW VOLTAGE POWER CABLES WITH (PVC, PE and XLPE, HFFR) INSULATION NYY, NAYY NYBY, NAYBY NYCY, NAYCY NYCWY, NAYCWY NYRY, NAYRY NY2Y, NAY2Y (E-AY2Y) N2XY, NA2XY; N2X2Y, NA2X2Y N2XYRY, NA2XYRY N2XCY; NA2XCY N2XBY; NAXBY

MIDDLE VOLTAGE POWER CABLES N2XSY, NA2XSY; N2XS2Y, NA2XS2Y N2XSEY, N2XSE2Y; NA2XSEY, NA2XSE2Y XHP 48; XHP48-A XHE 49; XHE 49-A N2XS(F)2Y, NA2XS(F)2Y N2XS(FL)2Y, NA2XS(FL)2Y; N2XS(FB)2Y, NA2XS(FB)2Y-so CU/KO traka N2XSYRY, NA2XSYRY; N2XSEYRY, NA2XSEYRY; N2XSYBY, NA2XSYBY; N2XSEYBY, NA2XSEYBY AASC-XLPE 20KV (PAS) FR-N(10)XA8E-AR; FR-N(20)XA8E-AR N2XS(F)2YY, NA2XS(F)2YY

CABLES ACCORDING TO BDS SVT; SAVT SVTT; SAVTT SAVBT; SVBT SVBT; SAVBT 6kV A; AC; ACO SHemT-ET; SAHemT-ET PVO PVU-A1 PVU-A2 PVV-MB1

POWER CABLES FOR OVERHEAD LINES 0.6/1 kV, BARE COPPER CONDUCTORS N1XD4-AR; X00-A N1XD9-AR; AL/R; X00/0-A NFA2X Bare copper conductors ACSR Aluminium Alloy rope Steel rope Bare Al conductors Al1-ST1
- BARE ALUMINIUM CONDUCTORS AND ALUMINIUM CONDUCTORS, STEEL-REINFORCED FOR OVERHEAD LINES

MULTIWIRE CONDUCTORS Multi wire copper and aluminium conductors class 2 Multi wire copper conductors class 5

TECHNICAL DATA

Conductors (for Electrical Appliance and Electrical Installation)

H03VH-H
PVC insulated flexible cord, parallel twin Rated Voltage: U0/U - 300/300 V Standard: DIN VDE 0281-302; HD 21.5.S3
< VDE >

for Electrical Appliances

Application H03VH-H cable types are especially suited to use on small appliances with low mechanical stress and for connecting for light household appliances, e.g. kitchen utensils, desk lamps, floor lamps, vacuum cleaners, office machines, radios, etc. These cables are not permitted to use with cooking or heating apparatus. These cables are not suitable for outdoor use or use of industrial or farmer machineries.

Conductors

Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 Core temperature, max: 70oC in operation Max. short circuit temperature: 160 oC , not more than 5 sec Rated voltage - U0 /U: 300/300 V Test voltage: AC - 2 kV; 50 Hz Temperature Range Fixed installation: -40C to +70C Flexible Installation: -5C to +70C Bending radius, min. 6xDcable Specific insulation resistance at 70C: min, 1010 x cm

Cable Structure:
Conductor: Bare copper, fine wire conductor, bunch stranded as per VDE 0295 cl.5 or cl.6 (HD 383) The conductors shall be laid parallel, and are sheathed together with insulation.

Insulation: PVC core insulation YI2 as per VDE 0207 part 4 (HD 21.1 TI2) Core arrangement:

Color of insulation: white, grey, black, green, red, blue or the customers request.

Note
The in design (flat profile) is constructed to enable the cores to be separated without causing damage to the insulation.

Constructive and electrical data: H03VH-H


Number of Cores and Nominal Cross Section Number of wire and Diameter Thickness of insulation Approx. Overall Diameter Conductor DC Resistance Approx, total Weight Max. Current Carrging N x mm N x mm mm max. mm /km kg/km Pipe A Air A 2x0.5 2x0.75 28 x 0.15 39 x 0.15 0.8 0.8 3.0 x 6.0 3.2 x 6.4 39 26 24 29 / / 3 6

*other dimensions available on request

Packing
Standard packing length on cable coils: [ 50 m; 100 m ];

Cable Factory FKN | 2012

H03VV-F, H03VVH2-F
Ordinary PVC insulated and sheathed flexible cable Rated Voltage: U0/U - 300/300 V Standard: DIN VDE 0281-5; HD 21.5.S3
< VDE >

Conductors

Application The cables are suitable for connection of light small duty appliances, i. e. desk-instructions of the lamps, fairy-lamps, house vacuum cleaners, radio sets etc. as far as this is allowed in the instructions of the electrical appliances. The cables with cross-section 0.5 and 0.75 mm are not suitable for use in industrial electrical equipment, in agriculture and in open spaces.

for Electrical Appliances

Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 class 5 Core temperature, max: 70 C in operation Max. short circuit temperature: 160 oC , not more than 5 sec Working voltage - U0 /U: 300/300 V Max. permissible operating voltage: in three-phases AC system Uo /U = 330/330V in DC system Uo /U = 495/495V Test voltage: AC - 2 kV; 50 Hz Temperature Range Fixed installation: -40C to +70C Flexible Installation: -5C to +70C Bending radius, min. 6xDcable Specific insulation resistance at 70C: min, 1010 x cm
o

Cable Structure:
Conductor:

Bare copper, fine wire conductor,


bunch stranded as per VDE 0295 cl.5 (HD 383)

Insulation: PVC core insulation YI2 as per VDE 0207 part 4 (HD 21.1 TI2) Color code: Cores colour coded to DIN VDE 0293 . (HD 27) Core arrangement: Cores layed up by H03VV-F, and laid parallel byH03VVH2-F Outer jacket:

PVC outer jacket YM2 as per DIN VDE 0207/5(HD21.1 TM2),

available in black, white or as per requirement

Packing
Standard packing length on cable coils: [ 50 m; 100 m ];
Overall Diameter (Approx.) max.mm H03VV-F 5.04 5.5 5.4 5.8 6.0 6.5 H03VVH2-F 5.1x3.1 5.5x3.4 Conductor DC Resistance at 20C /km 39 26 39 26 39 26 39 26 Total Weight (Approx.) kg/km 40 48 47 57.8 56 70 28 35 Max. Current Carrying Capacity at 30 C A 3 6 3 6 3 6 3 6

Constructive and electrical data for H03VV-F; H03VVH2-F U0/U - 300/300V


Num. of Cores and Nominal Cross Section No x mm 2 x 0.5 2 x 0.75 3 x 0.5 3 x 0.75 4 x 0.5 4 x 0.75 2 x 0.5 2 x 0.75 Number of Wires and Diameter No x mm 15x0.2 22x0.2 15x0.2 22x0.2 15x0.2 22x0.2 15x0.2 22x0.2 Nominal Thickness Nominal Thickness of of Insulation Sheath mm mm 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 Copper weight (Approx.) kg/km 9.6 14.4 14.4 21.6 19.2 29 9.6 14.4

* other dimensions available on request.

On Request:
Fire propagation acc. IEC 60332-1 cat. A, B, C Hydrocarbon resistant outer sheath (RH). Termite and rodents protected outer sheath Oil resistant outer sheath.

Cable Factory FKN | 2012

H05VV-F, H05VVH2-F
Ordinary PVC insulated and sheathed flexible cable Rated Voltage: U0/U - 300/500 V Standard: DIN VDE 0281-5; HD 21.5.S3
< VDE >

for Electrical Appliances

Conductors

Application H05VV-F, H05VVH2-F cable types are especially suited to use for the appliances with medium mechanical stress in households, kitchens end offices also for household appliances in damp and wet areas , e.g. refrigerators, washing machines, spin - driver, etc. As far as this cable is admitted to the relevant specifications of the equipment. These cable are suited to be use for cooking and heating apparatus under the condition that cable does not come in direct contact with hot parts of the apparatus and no other influences of heat. The cable are suitable for fixed installation in furniture, partition walls, decoration covering and in hollow spaces of prefabricated building parts.
Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 Core temperature, max: 70oC in operation Max. short circuit temperature: 160 oC , not more than 5 sec Working voltage - U0 /U: 300/500 V Max. permissible operating voltage: in three-phases AC system Uo /U = 330/550V in DC system Uo /U = 495/825V Test voltage: AC - 2 kV; 50 Hz Temperature Range Fixed installation: -40C to +70C Flexible Installation: -5C to +70C Bending radius, min. 6xDcable Specific insulation resistance at 70C: min, 1010 x cm

Cable Structure:
Conductor: Bare copper, fine wire conductor, bunch stranded as per VDE 0295 cl.5 (HD 383)

Insulation: PVC core insulation YI2 as per VDE 0207 part 4 (HD 21.1 TI2) Color code: Cores colour coded to DIN VDE 0293 . (HD 27) Core arrangement: Cores layed up by H05VV-F, and laid parallel by H05VVH2-F Outer jacket : PVC outer jacket YM2 as per VDE 0207 part 5 (HD21.1 TM2), available in black, white or as per requirement

On Request:
Fire propagation acc. IEC 60332-1 cat. A, B, C Hydrocarbon resistant outer sheath Termite and rodents protected outer sheath

Construction data H05VV-F


Num. of Cores Overall and Nominal Shape Diameter (Approx.) Cross Section No x mm max.mm 2 x 0.75 3 G 0.75 4 G 0,75 5 G 0.75 2x1 3G1 4G1 5G1 2 x 1.5 3 G 1.5
Num. of Cores and Nominal Cross Section No x mm 4 G 1.5 5 G 1.5 2 x 2.5 3 G 2.5 4 G 2.5 5 G 2.5 2x4 3G4 4G4 5G4 2 x 0.75 2x1

U0/U - 300/500V
Total Weight (Approx.) kg/km 65 75 89 103 75 87 109 128 96 118 Packing: Cable coil or Drum m or N/m 100 100 100 100 100 100 100 100 100 100

Copper weight (Approx. ) kg/km 14,4 21,6 29 36 19 29 38 48 29 43

RF RF RF RF RF RF RF RF RF RF

6,5 6,7 7,2 8 7 7,3 8 8,6 7,5 8,3

Construction data H05VV-F


Shape

U0/U - 300/500V
Total Weight (Approx.) kg/km 148 178 149 183 220 266 207 257 312 370 43 50 Packing: Cable coil or Drum m or N/m 100 100 100 100 100 100 100 100 100 100 100 100

Overall Copper weight (Approx.) Diameter (Approx.) max.mm kg/km 58 72 48 72 96 120 76 115 154 192 HO5VVH2-F 14,4 19

RF RF RF RF RF RF RF RF RF RF RF RF

9 10 9,5 10 11 12 11 11,5 12,5 13,8 6,3x4,0 6,6x4,2

*other dimensions available on request

RF - fine wire stranded conductor (class 5)

Cable Factory FKN | 2012

H05V-U-K, H07V-U/-R/-K
Single core, Non Sheathed PVC cable Rated Voltage: U0/U - 450/750 V Standard: DIN VDE: 0281-3 (HD 21.3)
< VDE >

Conductors

Application H07V-U/-R/-K PVC-insulated single-core cable according to VDE 0281 part 3,HD 21.3 S3 and IEC 227-3. These PVC-insulated singlecore cables are used for the internal wiring of equipment switching systems and distributors as well as for the protected installation in and to lighting fixtures with a rated voltage up to 1000 V alternating current or a direct voltage up to 750 V, earthed.These cables are suitable for installation in dry rooms, switching and distribution systems,in conduit, on, in and under plaster as well as in closed installation ducts. Note (for H07V): These single-core cables may not be used for direct installation on flatbed bodies, ducts or tanks. Approved for use as potential-compensating cable directly on, in and underneath plaster as well as on flatbed bodies or similar.
Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 Core temperature, max: 70oC in operation Max. short circuit temperature: 160 oC , not more than 5 sec Working voltage - U0 /U: for H05V up to 1mm2 Uo /U = 300/500V for H07V from 1.5mm2 and above Uo /U = 450/750V Test voltage: AC - 2.5 kV; 50 Hz Temperature Range Fixed installation: -40C to +70C Flexible Installation: -5C to +70C Bending radius, min. from 12.5 to 15xDcable Radiation resistance: up to 80 x 106 cJ/kg (up to 80 Mrad) Specific insulation resistance at 70C: min, 10 M x km

for Electrical Instalation

Cable Structure:
The conductor is made of copper wires as follows: bare copper at H07V-U, class 1 Conductor: wire stranded at H07V-R, class 2 fine wire stranded at H07V-K, class 5, according to VDE 0295 (IEC 60228) Insulation: PVC, compound Type YI1 accordingto VDE 0207 part 4 black, red, blue, pink, gray, yellow, Color of insulaion: green, brown, white, violet, orange or on request.

Two-color combinations are not


permitted except for green/yellow.

Packing
Up to 35sq.mm standard packing length in cable coils: (50m; 100m) From 50sq.mm and above standard packing length on cable drums:(500m; 1000m)

On Request:
Fire propagation acc. IEC 60332-1 cat. A, B, C Hydrocarbon resistant outer sheath (RH) Termite and rodents protected outer sheath Oil resistant outer sheath.

Protected against direct sun irradiation

Cable Factory FKN | 2012

H05V-U-K, H07V-U/-R/-K
Single core, Non Sheathed PVC cable Rated Voltage: U0/U - 450/750 V Standard: DIN VDE: 0281-3 (HD 21.3)
< VDE >

for Electrical Instalations

Construction data H07V-U/R/K


NominalCross Section No x mm 1,5 2,5 4 6 10 1,5 2,5 4 6 10 16 25 35 50 70 95 120 150 185 240 1,5 2,5 4 6 10 16 25 35 50 70 95 120 150 185 240 RE RE RE RE RE RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RM RM RM RM RM RM RM RM RM RM RM RM RM RM RM max.mm H07V-U 2,75 3,35 3,8 4,3 5,5 H07V-K 3,0 3,6 4,2 5,3 7,0 8,1 10,0 11,4 13,6 15,7 18,0 19,8 22,5 24,7 28,1 H07V-R 3,0 3,7 4,2 4,8 6,1 7,2 9,0 10,0 11,6 13,7 16,0 18,0 19,5 21,6 24,6 14,4 24,0 38,0 58,0 96,0 145,0 240,0 336,0 480,0 672,0 912,0 1152,0 1440,0 1776,0 2304,0 14,4 24,0 38,0 58,0 96,0 154,0 240,0 336,0 480,0 672,0 912,0 1152,0 1440,0 1776,0 2304,0 14,4 24 38,0 58,0 96,0 kg/km

U0/U - 450/750V
Total Packing: Cable coil or Drum Weight (Approx.) kg/km m or N/m 20 31 46,0 65,2 107,0 20,07 32,0 48,5 68,0 118,5 172,8 270,6 375,8 524,3 714,8 984,5 1203,0 1514,6 1877,0 2409,4 22,0 35,0 51,1 72,0 118,0 178,2 282,0 369,6 560,0 723,0 974,0 1272,0 1483,0 1873,0 2430,6 100 100 100 100 100 100 100 100 100 100 100 100 9/1000 9/1000 9/500 9/500 10/500 12/500 12/500 12/500 100 100 100 100 100 100 100 8/1000 9/1000 10/1000 9/500 9/500 10/500 14/1000 12/500

Shape Overall Diameter (Approx.) Copper weight (Approx.)

Conductors

*other construction, sizes and packing length are available on request. RM - multiwire round shaped conductor RE - solid round conductor (class 1) RF - fine wire stranded conductor

Cable Factory FKN | 2012

NYM-J, NYM-O
Single core, Non Sheathed PVC cable Rated Voltage: U0/U - 450/750 V Standard: DIN VDE: 0281-3 (HD 21.3)
< VDE >

Conductors

Application NYM is used as power and control cable in static installations for indoor installations, on, in and under plaster and in the air where mechanical damage is not anticipated.

for Electrical Instalation

Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 Core temperature, max: 70oC in operation Max. short circuit temperature: 160 oC , not more than 5 sec Rated voltage - U0 /U: 300/500 V Test voltage: AC - 2 kV; 50 Hz Temperature Range: -20C to +70C Bending radius, min. 6xDcable Specific insulation resistance at 70C: min, 1010 x cm Max. permissible tensile stress with cable grip: For Cu conductor = 50 N/mm2

Cable Structure:
Conductor: solid or multi-strand Cu wires class 1, 2 or 5 acc. VDE 0295(IEC 60228) Insulation: PVC type YI1 acc. DIN VDE 0207/4 according to DIN VDE 0293, Core identification: construction with 7 or more cores are numbered coded (for J-type one of them is yellow-green) Cores assembly: cores stranded concentrically (cores stranded in concentric layers, for signal) Inner sheath: rubber mass or PVC Sheath: PVC type YM1 acc. DIN VDE 0207/5

Packing
Standard packing length on wooden drums: (500m; 1000m) Length Tolerance per drum 5% Standard packing length on cable coils: (50m; 100m)
Construction data NYM-J/O U0/U - 300/500V
Num. of Cores Overall Total and Nominal Shape Copper weight (Approx.) Packing: Cable coil or Drum Diameter (Approx.) Weight (Approx.) Cross Section No x mm max.mm kg/km kg/km m or N/m 1 x 1.5 1 x 2.5 1x4 1x6 1 x 10 1 x 16 2 x 1.5 2 x 2.5 2x4 2x6 2 x 10 2 x 16 2 x 25 RE RE RE RE RE RM RE RE RE RE RE RM RM 5.4 6.0 6.7 7.2 8.4 10.0 8.8 10 11.5 12.5 15.5 18.5 22.2 14.4 24 38 58 96 154 29 48 76 116 192 308 480 77.4 61 82.4 105 158.5 242 123 166 225 284 470 712 1085 100 100 100 100 100 100 100 100 50 50 50 9/500 10/500

On Request:
Fire propagation acc. IEC 60332-1 cat. A, B, C Hydrocarbon resistant outer sheath (RH) Termite and rodents protected outer sheath

Oil resistant outer sheath.


Protected against direct sun irradiation

RF - fine wire stranded conductor (class 5)

Construction data NYM-J/O

U0/U - 300/500V

Num. of Cores Overall Total and Nominal Shape Copper weight (Approx.) Packing: Cable coil or Drum Diameter (Approx.) Weight (Approx.) Cross Section No x mm max.mm kg/km kg/km m or N/m 2 x 35 3 x 1.5 3 x 2.5 3x4 3x6 3 x 10 3 x 16 3 x 25 3 x 35 4 x 1.5 4 x 2.5 4x4 4x6 RM RE RE RE RE RE RM RM RM RE RE RE RE 25 9.2 10.5 12 13 16.5 19.5 24 26.4 9.8 11.2 13.3 15.2 647 43 72 115 173 290 462 720 975 58 96 154 230 1400 142.2 195,5 270.5 359 573 903 1372.5 1750 167.5 233 338 453 14/1000 100 100 50 50 9/500 12/1000 14/1000 14/1000 100 100 50 50

*other dimensions and packing length are available on request

Cable Factory FKN | 2012

NYMT-J, NYMT-O
Electric power and lighting PVC insulated and sheathed self supporting cable Rated Voltage: U0/U - 300/500 V Standard: DIN VDE 0250/206

for Electrical Appliances

Application NYMT is used in open air for public illuminations, domestic wiring connections on constructions sites and the similar. They are installed on the poles, brackets next to facades of buildings or seel structures.

Conductors

Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 Core temperature, max: 70oC in operation Max. short circuit temperature: 160 oC , not more than 5 sec

Cable Structure:
Conductor: solid or multi-strand Cu wires class 1, 2 or 5 acc. VDE 0295(IEC 60228) according to DIN VDE 0293, construction

Insulation: PVC type YI1 acc. DIN VDE 0207/4 Core identification: with 7 or more cores are numbered coded (for J-type one of them is yellow-green) Cores assembly: cores stranded concentrically (cores stranded in concentric layers, for signal) strand of galvanized steel wires, with breaking strength of least 1300 N/mm2

Rated voltage - U0 /U: 300/500 V Test voltage: AC - 2 kV; 50 Hz Temperature Range: -20C to +70C Bending radius, min. 6xDcable Specific insulation resistance at 70C: min, 1010 x cm Max. permissible tensile stress with cable grip: For Cu conductor = 50 N/mm2

Inner sheath: rubber mass or PVC Support:

Sheath: PVC type YM1 acc. DIN VDE 0207/5, black


Construction data NYMT-J/O
Num. of Cores and Nominal Cross Section No x mm 2 x 1.5 2 x 2.5 2x4 2x6 2 x 10 2 x 16 2 x 25 2 x 35 3 x 1.5 3 x 2.5 3x4 3x6 3 x 10 3 x 16 3 x 25 3 x 35

U0/U - 300/500V

Construction data NYMT-J/O


Num. of Cores and Nominal Cross Section No x mm 4 x 1.5 4 x 2.5 4x4 2x6 4 x 10 4 x 16 4 x 25 4 x 35 5 x 1.5 5 x 2.5 5x4 5x6 5 x 10 5 x 16 5 x 25 5 x 35

U0/U - 300/500V

Shape Copper weight (Approx.) Total Weight (Approx.) Min. breaking load kg/km RE RE RE RE RE RM RM RM RE RE RE RE RE RM RM RM 27 44 70 105 178 288 450 630 40 65 105 157 267 432 675 944 kg/km 200 242 302 366 596 792 1105 1510 218 270 346 446 700 950 1430 1845 kN 6 6 6 6 10,5 10,5 10,5 16 6 6 6 6 10,5 10,5 16 16

Shape Copper weight (Approx.) Total Weight (Approx.) Min. breaking load kg/km RE RE RE RE RE RM RM RM RE RE RE RE RE RM RM RM 53 87 140 209 356 576 899 1259 66 108 174 261 445 720 1124 1573 kg/km 243 308 423 540 826 1163 1757 2300 273 354 508 674 976 1472 2163 2803 kN 6 6 6 6 10,5 10,5 16 23,5 6 6 6 10,5 10,5 16 23,5 23,5

*other dimensions available on request

On Request:
Fire propagation acc. IEC 60332-1 cat. A, B, C

Packing Standard packing length on wooden drums: (500m; 1000m) Length Tolerance per drum 5%

Cable Factory FKN | 2012

NYiFY, NYiFY-O
Flat webbed house wires Rated Voltage: U0/U - 230/400 V Standard: DIN VDE 0250/201

Application For installation in dry environments only, both in and beneath plaster. The cables must be covered by plaster along their entire length. Installation in cavities of concrete, stone or non-inflammable building materials is allowed. Installations notes: - The cables cannot be installed on flammable building materials, immediately next to or under wire mesh or similar materials. - For mounting, only materials and procedure shall be used which preclude a deformation or damage of the insulation, e. g. gypsum plaster, adhesives, nails with insulating washers. - Flat house wire cables may only be installed beneath gypsum board if these are subsequently fixed using gypsum plaster. The cables may not be bundled together. Bunching flat webbed building wires to insertion points for electrical equipments is not considered as bunching.
Technical Data: Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 Core temperature, max: 70oC in operation Max. short circuit temperature: 160 oC , not more than 5 sec Rated voltage - U0 /U: 230/400 V Test voltage: AC - 2 kV; 50 Hz Temperature Range: -20C to +70C Bending radius, min. 6xDcable Specific insulation resistance at 70C: min, 10 x cm
10

Conductors

for Electrical Instalation

Cable Structure:
Conductor: Wire of soft annealed copper as per VDE 0295(IEC 60228) class 1. Insulation: PVC type YI1 acc. DIN VDE 0207/4 Core identification: according to DIN VDE 0293 Cores assembly: Parallel placed cores in a plane PVC sealess layer type YM1 acc. DIN VDE 0207/5. Sheath: Between the cores the sheath is in the shape of a path with wedge shaped groove in the middle, enabling provisional fixing of conductors.

Color of sheath: white, black, gray

On Request:

Packing Standard packing length on cable coils: (50m; 100m) On request: Fire propagation acc. IEC 60332-3 cat. A or cat.C Oil resistant outer sheath.

Construction data NYiFY-J/O


Num. of Cores Approx. and Nominal Shape Overall Approx. Copper weight Cross Section Diameter No x mm max.mm kg/km 2 x 1.5 2 x 2.5 2x4 3 x 1.5 3 x 2.5 3x4 4 x 1.5 4 x 2.5 5 x 1.5 5 x 2.5 RE RE RE RE RE RE RE RE RE RE 3.8x11.2 4,6x12.8 5.2x14.4 3.8x18.7 4.5x21 5.2x23.7 3.8x32.8 4.5x29 3.8x32.8 4.5x36.7 29 48 76 43 72 115 58 96 72 120

U0/U - 230/400V
Approx. Total Weight kg/km 65 95 135 100 145 206 135 196 170 246 Packing: Cable coil or Drum m or N/m 100 100 100 100 100 100 100 100 100 100

*other dimensions and packing length are available on request

Cable Factory FKN | 2012

(N)YM(St)-J, (N)YM(St)-O
PVC sheathed cable for fixing wiring Rated Voltage: U0/U - 300/500 V Standard: acc. DIN VDE 0250/204
EMV

for Electrical Appliances

Conductors

Application This cable has a static foil screen for limiting its irradiated electromagnetic field in areas with high requirements to EMC as computer rooms, hospitals as well as in living rooms with high sensitivity to electrical and/or magnetical fields. For installation on and under plaster in dry and wet rooms, as well as inside of walls or in concrete. Also for outdoor use, if the cable is protected against direct sun irradiation.
Cable Structure:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 Core temperature, max: 70oC in operation Max. short circuit temperature: 160 oC , not more than 5 sec Rated voltage - U0 /U: 300/500 V Test voltage: AC - 2 kV; 50 Hz Temperature Range: -20C to +70C Bending radius, min. 6xDcable Specific insulation resistance at 70C: min, 10 x cm Max. permessible tensile stress with cable grip: For Cu conductor = 50 N/mm
2 10

Technical Data:

Conductor: solid or multi-strand Cu wires class 1, 2 or 5 acc. VDE 0295(IEC 60228) Insulation: PVC type YI1 acc. DIN VDE 0207/4 according to DIN VDE 0293, construction Core identification: with 7 or more cores are numbered coded (for J-type one of them is yellow-green) Cores assembly: cores stranded concentrically (cores stranded in concentric layers, for signal)

Inner sheath: rubber filling compound or PVC Screen: Coated aluminium foil shielding and solid copper drain-wire, tinned Sheath: PVC type YM1 acc. DIN VDE 0207/5, color gray RAL7035

Construction data NYM-J/O

U0/U - 300/500V

Construction data NYM-J/O

U0/U - 300/500V

Num. of Cores Approx. Approx. Num. of Cores Approx. Approx. and Nominal Shape Overall Approx. Copper weight Total Packing: Cable coil or Drum and Nominal Shape Overall Approx. Copper weight Total Packing Cable coil or Drum Cross Section Diameter Weight Cross Section Diameter Weight No x mm max.mm kg/km kg/km m or N/m No x mm max.mm kg/km kg/km m or N/m 1 x 1.5 RE 5.2 13 45 100 2 x 35 RM 24 615 1230 N14/1000 1 x 2.5 RE 5.8 22 60 100 3 x 1.5 RE 8.5 40 125 100 1x4 RE 6.5 34 80 100 3 x 2.5 RE 10 66 178 100 1x6 RE 7.1 52 102 100 3x4 RE 11.5 105 248 50 1 x 10 RE 8.2 85 155 100 3x6 RE 13 155 335 50 1 x 16 2 x 1.5 2 x 2.5 2x4 2x6 2 x 10 2 x 16 2 x 25 RM RE RE RE RE RE RM RM 9.5 8.2 9.5 10.7 11.8 15 17.5 21 143 27 44 70 105 170 285 445 223 108 150 205 265 420 625 917 100 100 100 50 50 50 N9/500 N10/500

3 x 10 3 x 16 3 x 25 3 x 35 4 x 1.5 4 x 2.5 4x4 4x6

RE RM RM RM RE RE RE RE

15.5 18.5 22.5 25 9.5 11 13 14

260 425 665 920 55 90 140 210

520 780 1165 1535 150 215 310 418

N9/500 N12/1000 N14/1000 N14/1000 100 100 50 50

Packing
Standard packing length on wooden drums: (500m; 1000m) Length Tolerance per drum 5% Standard packing length on cable coils: (50m; 100m)

On request:
Fire propagation acc. IEC 60332-3 cat. A, B, C Termite and rodents protected outer sheath. Protected against direct sun irradiation

Cable Factory FKN | 2012

Telecommunication and Control Cables

J-Y(St)Y...Lg
Wiring cable for telecommunication and data processing systems Standard: DIN VDE 0815
EMV

Telecommunication and Control Cables

Application These cables are suitable for telephone stations and sub-extensions, for signal and data transmission. This cable type with electrostatic screening (St) protects the transmission circuits against extern electrical interferences. Installation cables laid up in pairs are preferably used for indoor telecommunication installation in dry and damp places, but also in the open for fixed installation on outer walls of buildings. The use of this cable is not allowed in energetic purposes.

Technical Data:
Conductor diameter: 0.6mm Loop resistance at 20C - max. 130 /km Insulation resistance value at 20C min. 100 M/km Nominal voltage, max. 300 V Mutual capacitance at 800 Hz, max. 100 nF/km Capacitance unbalances at 800 Hz, max. 300 pF/100m Line attenuation 800 Hz, max 1,7dB/km Test voltage: core/core: 800 V core/screen: 800 V Temperature Range: Fixed installation: -30C to +70C Flexible Installation: -5C to +50C Bending radius, min. during delivery: 7.5xDcable single Packing bending without tension: 2.5xDcable repeated bending under tension: 7.5xDcable 100 nF/km 300 pF/100m 1,1dB/km 0.8mm 73.2 /km 100 M/km

Cable Structure:
Conductor: Insulation: Color code: Core arrangement: Bare copper conductor, solid, 0,6 and 0,8mm according DIN VDE 0295 PVC core insulation, compound type YI1, as per DIN VDE 0207/4 Insulation colour and pair identification as per DIN VDE 0815 Insulated cores are twisted in pairs and the pairs are stranded in concentric layers Electrostatic screen (St) of plastic coated aluminium foil and drain wire PVC outer jacket grey RAL 7032, compound type YM1 as per DIN VDE 0207 part 5.

Wrapping: Core wrapping with plastic tape Screen: Outer jacket:

Note
Outer jacket is Red for fire signalisation systems. The cable can be made in the same constructions but with thermoplastic polyethylene insulation and sheath and than is marked as: J-2Y(St)2Y ...Lg.

Construction data: J-Y(St)Y ...Lg


Number of pairs No x mm 1x2x0.6 2x2x0.6 3x2x0.6 4x2x0.6 5x2x0.6 6x2x0.6 10x2x0.6 16x2x0.6 20x2x0.6 24x2x0.6 30x2x0.6 RE RE RE RE RE RE RE RE RE RE RE Shape Overall Copper Total Diameter weight Weight (Approx.) (Approx.) (Approx.) max.mm kg/km kg/km 4,2 4,6 6,0 6,5 7,0 7,4 9,0 10,0 11,0 11,5 13,0 6,0 13,0 18,0 24,0 30,0 35,0 58,0 93,0 116,0 139,0 172,0 26,0 36,0 48,0 58,0 66,0 75,0 108,0 156,0 188,0 219,0 279,0

Construction data: J-Y(St)Y ...Lg


Number of pairs No x mm 1x2x0.8 2x2x0.8 3x2x0.8 4x2x0.8 5x2x0.8 6x2x0.8 10x2x0.8 16x2x0.8 20x2x0.8 24x2x0.8 RE RE RE RE RE RE RE RE RE RE Shape Overall Copper Total Diameter weight Weight (Approx.) (Approx.) (Approx.) max.mm kg/km kg/km 5,5 6,2 8,0 9,0 9,5 10,5 13,0 15,0 16,0 18,0 10,0 21,0 31,0 41,0 52,0 62,0 102,0 164,0 204,0 244,0 22,0 60,0 83,0 100,0 115,5 134,0 213,0 310,0 375,0 440,0

*other construction and sizes are available on request. Hydrocarbon resistant outer sheath (RH).

30x2x0.8 RE 20,0 304,0 554,0 *other construction and sizes are available on request.

Cable Factory FKN | 2012

J-YY...Lg
Wiring cable for telecommunication and data processing systems Standard: DIN VDE 0815

Telecommunication and Control Cables

Application In communication technology, the following connections can be installed: telephone, telex as well as standard modems of postal services, burglar and fire alarm systems (cf. fire alarm cables), communication and paging systems, access control, time and data control systems Can be used in dry and wet interiors for fixed installation on and under plaster.

Technical Data:
Conductor diameter: 0.6mm Loop resistance at 20C - max. 130 /km Insulation resistance value at 20C min. 100 Mxkm Nominal voltage, max. 300 V Mutual capacitance at 800 Hz, max. 100 nF/km Capacitance unbalances at 800 Hz, max. 300 pF/100m Line attenuation 800 Hz, max 1.5dB/km Test voltage, core/core: 800 V Temperature Range: Fixed installation: -30C to +70C Flexible Installation: -5C to +50C Bending radius, min. during delivery: 7.5xDcable single bending without tension: 2.5xDcable repeated bending under tension: 7.5xDcable 100 nF/km 300 pF/100m 0.8mm 73.2 /km 100 Mxkm

Cable Structure:
Conductor: Insulation: Color code: Bare copper conductor, solid, 0,6 and 0,8mm according DIN VDE 0295 PVC core insulation, compound type YI1, as per DIN VDE 0207/4 Insulation colour and pair identification as per DIN VDE 0815 the pairs are stranded in concentric layers Wrapping: Core wrapping with plastic tape Outer jacket: PVC outer jacket grey RAL 7032, compound type YM1 as per DIN VDE 0207 part 5.

Core arrangement: Insulated cores are twisted in pairs and

Pairs available: 1 up to 100

Note
Outer jacket is Red for fire signalisation systems.

Packing
Hydrocarbon resistant outer sheath (RH). Protected against direct sun irradiation

Standard Packing length on cable coils: [ 50 m; 100 m ];

Construction data: J-YY ...Lg


Number of pairs No x mm 1x2x0.6 2x2x0.6 3x2x0.6 4x2x0.6 5x2x0.6 6x2x0.6 10x2x0.6 16x2x0.6 20x2x0.6 24x2x0.6 30x2x0.6 RE RE RE RE RE RE RE RE RE RE RE Shape Overall Copper Total Diameter weight Weight (Approx.) (Approx.) (Approx.) max.mm kg/km kg/km 4,0 4,2 5,7 6,2 6,7 7,1 8,8 9,9 10,7 11,2 12,8 6,0 13,0 18,0 24,0 30,0 35,0 58,0 93,0 116,0 139,0 172,0 23,0 33,0 45,0 56,0 64,0 74,0 105,0 155,0 183,0 215,0 273,0

Construction data: J-YY ...Lg


Number of pairs No x mm 1x2x0.8 2x2x0.8 3x2x0.8 4x2x0.8 5x2x0.8 6x2x0.8 10x2x0.8 16x2x0.8 20x2x0.8 24x2x0.8 30x2x0.8 RE RE RE RE RE RE RE RE RE RE RE Shape Overall Copper Total Diameter weight Weight (Approx.) (Approx.) (Approx.) max.mm kg/km kg/km 5,3 6,0 7,7 8,8 9,3 10,2 13,0 12,7 15,8 17,8 19,8 10,0 21,0 31,0 41,0 52,0 62,0 102,0 164,0 204,0 244,0 304,0 21,0 58,0 80,0 98,0 112,0 130,0 210,0 306,0 365,0 430,0 545,0

*other construction and sizes are available on request. Packing type and length is available on request.

Cable Factory FKN | 2012

TK-33 U
Self-supporting subscriber telephone cable with supporting strand Standard: ZJPTT LNVIII/B.4.

Telecommunication and Control Cables

Application Self-supporting telephone local cables with supporting rope are used only in the secondary telephone network. They are suitable for stringing along poles and other supports.

Technical Data:
Conductor diameter: 0.6mm 0.8mm 72 /km Loop resistance at 20C - max. 130 /km 73.2 /km Loop resistance mean value at 20C - max. 126 /km Insulation resistance value at 20C min. Permitted voltage, max. at AC: at DC: Mutual capacitance at 800 Hz, max. cable with one quad: cable with several quads: Capacitance unbalances at 800 Hz, max. K1 for 100% values: K1 for 98% values: K9 -1 2 : Planned attenuation at 800 Hz cable with one quad: 120 mN/km 95 mN/km cable with several quads: 110 mN/km 85 mN/km Test voltage (2 sec, DC),core/core: Temperature Range: before and after after installation: during operation: Bending radius, min. -30C to +50C +5C to +50C 15xDcable 6 kV 8 kV 2700 pF/km 1350 pF/km 1000 pF/km 52 nF/km 42 nF/km 150 V 210 V 10000 Mkm

Cable Structure:
Conductor: Bare copper conductor, solid, 0,6 and 0,8mm Insulation: Core arrangement: Core wrapping: solid polyethylene insulation type ETI1, according MKS N.CO.195 four insulated wires are twisted in a star quad, quad group cable core is made in form of concentric layers or two polyester bands with orange thread under them as the mark of FKN.

Supporting element: strand made of zinc-plated steel wire. Outer sheath: black PE, type ETP1 as per MKS N.CO.195

Concentric twisting
Quads in layer marker direction odd even a-wire b-wire c-wire d-wire

Construction data: TK 33-U


Overall Total Packing: Sheath Supporting Height Construction Diameter Weight Cable coil Thickness strand (Approx.) (Approx.) (Approx.) or Drum No x mm mm mm max.mm mm kg/km m or N/m 1x2x0.6 1x4x0.6 3x4x0.6 5x4x0.6 10x4x0.6 15x4x0.6 20x4x0.6 25x4x0.6 1,0 1,0 1,6 1,6 1,8 1,8 1,8 1,8 2,0 2,0 2,0 1,0 1,6 1,8 1,8 1,8 2,0 2,0 2,0 3x1 3x1 7x1 7x1 12x1 19x1 19x1 19x1 19x1 19x1.2 19x1.2 3x1 7x1 12x1 19x1 19x1 19x1 19x1.2 19x1.2 4,5 5,5 10,0 12,5 16,5 19,0 20,5 22,5 25,5 29,0 31,0 6,5 13,0 15,0 19,0 22,0 25,5 28,0 30,5 9,0 11,0 17,5 20,0 25,0 28,5 31,0 32,5 35,5 40,0 42,0 11,5 20,0 24,0 28,5 32,0 35,5 39,0 41,5 50,0 72,0 180,0 220,0 370,0 520,0 610,0 695,0 810,0 1045,0 1215,0 86,0 230,0 350,0 560,0 710,0 890,0 1100,0 1240,0 7/1000 7/1000 9/1000 10/1000 12/1000 14/1000 14/1000 14/1000 16/1000 16/1000 18/1000 8/1000 10/1000 12/1000 14/1000 16/1000 16/1000 16/1000 18/1000

Group Twisting
Quads in the basic groyup first second third fourth fifth
H
2+1

a-wire

b-wire

c-wire

d-wire

30x4x0.6 40x4x0.6 50x4x0.6 1x4x0.8 3x4x0.8


H

5x4x0.8
2+1

10x4x0.8 15x4x0.8 20x4x0.8

25x4x0.8 30x4x0.8

- sheath thickness H - height B - diameter

*other dimensions and packing length are available on request. *values mentioned above are for concentrical twisted star quads.

Cable Factory FKN | 2012

RG-6, RG-58, RG-59


Coaxial cables Standard: acc. to MIL C 17; MKS.N.C6.051

Telecommunication and Control Cables

Application Coaxialcables are used in high frequency transmission, especially for transmitters and receivers,computers, radio and TV transmissions. The varied mechanical, thermal and electronic properties of Coaxialcables mean that they can be used up into the GHz levels,as per cable type.

Cable Structure and Electrical characteristics:


RG-Type. . . /U Cable structure Inner conductor, d[mm] Cu-bare, 1.01mm Cu-tinned, 19 x 0.18mm Cu-bare, 0.584mm Insulation, thickness [mm]: foam PE, 4.65mm Outer conductor, braid: Outer jacket: Min. bending radius, approx. [mm]: Temperature range, C: Cu weight, [kg/km]; Approx. outer D cable, [mm]: Approx. weight, [kg/km]: Electrical characteristics Impedance, [Ohm]: Frequency range f (max), [GHz]: Propagation velocity, v/c Attenuation at 20C, [dB/100m] 100MHz 200MHz 500MHz 800MHz 1000MHz Approx. capacitance, [pF/m] Insulation resistance [MOhmx km] Loop resistance max. [Ohm/km] Nominal peak voltage [kV] 6.9 9.7 16.0 21.0 22.9 54 min. 5000 110 2.8 16 24 39 51 56 100 min. 5000 53 2.5 12.8 16.0 27.4 35.0 41.0 67 min. 5000 171 3.5 753 3 0.83 503 3 0.66 753 3 0.66 Al/PS+CuSn PVC 40 -35 to +80 16 6.87 50 PE, 3.0mm CuSn PVC 25 -35 to +80 23 5.15 45 PE, 3.7mm Cu-bare, 0.584mm PVC 30 -35 to +80 25 6.1 56 RG-6 RG-58 RG-59

Cable Factory FKN | 2012

UTP Cat. 5 Cables


LAN cables for computer network Standard: EIA/TIA 568-A; ISO IEC 11 801

Telecommunication and Control Cables

Application Used in data communication networks in transmission of analog or digital signals , has a maximum working transmission speed of 100 Mbit/s at frequency 100MHz.

Technical Data:
Impedance: 100 % 6 Ohm 1-100 Mhz Mutual Capacitance at 1 KHz: Max. 56 nf /km Loop resistance at 20 C: max. 19.2 Ohm/km Insulation resistance at 20 C, min: 150 Mohmkm Working Voltage, max: 250V Test Voltage: 500V Temperature Range: Fixed installation: -20C to +60C Flexible Installation: 0C to +50C Bending radius, min. 10xDcable Time delay: up to 5.7ns/m at 10MHz
2 Tensile Strength: Max.50 N/mm

Cable Structure:
Conductor: Bare copper conductor, solid, 0.51mm Insulation: Polyethylene insulation (PE high density). Core arrangement: Insulated cores are twisted in pairs with small lay and the pairs are stranded layer pair 1: blue and white Pairs color code : pair 2: orange and white pair 3: green and white pair 4: brown and white Wrapping: Core wrapping with plastic tape Outer jacket: PVC outer jacket grey RAL 7035 Cable outer diameter: 5.27 mm Cable weight: 34 kg/km

On Request Oil Resistant outer sheath (O) Protected against direct sun irradiation

Packing
Standard packing length on cable coils: (100m)

Electrical Properties
Frequency Structural Return Loss SRL (dB) (dB) 23 23 23 23 23 23 23 22 21.06 12.5 16 Attenuation Max. (dB/100m) 1.8 2.2 5.2 6.8 8.6 9.2 11.2 12.5 15.8 22.4 26 NEXT (Near and Crosstalk) Min. (dB) 64 62 53 48 47 44 42 41 39 35 32

(MHz) 0.772 1 4 8 10 16 20 25 31.25 65.5 100

Cable Factory FKN | 2012

FTP Cat. 5 Cables


LAN cables for computer network Standard: ANSI/EIA/TIA 568-A; EN 50 173

Telecommunication and Control Cables

Application Used in data communication networks in transmission of analog or digital signals , has a maximum working transmission speed of 100 Mbit/s at frequency 100MHz.

Technical Data:
Impedance: 100 % 6 Ohm 1-100 Mhz Mutual Capacitance at 1 KHz: Max. 56 nf /km Loop resistance at 20 C: max. 19.2 Ohm/km Insulation resistance at 20 C, min: 150 MOhmkm Working Voltage, max: 250V Test Voltage: 500V Temperature Range: Fixed installation: -20C to +60C Flexible Installation: 0C to +50C Bending radius, min. 10xDcable Time delay: up to 5.7ns/m at 10MHz
2 Tensile Strength: Max.50 N/mm

Cable Structure:
Conductor: Bare copper conductor, solid, 0.51mm2 Insulation: Polyethylene insulation (PE high density). Core arrangement: Insulated cores are twisted in pairs with small lay and the pairs are stranded in layer pair 1: blue and white Pairs color code : pair 2: orange and white pair 3: green and white pair 4: brown and white Wrapping: Core wrapping with plastic tape Screen: Electrostatic screen (St) of plastic coated aluminium foil with drain tinned copper earth wire.

Outer jacket: PVC outer jacket grey RAL 7035 Cable outer diameter: 5.35 mm Cable weight: 36 kg/km

On Request Oil Resistant outer sheath (O) Protected against direct sun irradiation

Packing
Standard packing length on cable coils: (100m)

Electrical Properties
Frequency (MHz) 0.772 1 4 8 10 16 20 25 31.25 65.5 100 Structural Return Loss SRL (dB) (dB) 23 23 23 23 23 23 23 22 21.06 12.5 16 Attenuation Max. (dB/100m) 1.8 2.2 5.2 6.8 8.6 9.2 11.2 12.5 15.8 22.4 26 NEXT (Near and Crosstalk) Min. (dB) 64 62 53 48 47 44 42 41 39 35 32

Cable Factory FKN | 2012

S-FTP Cat. 5 Cables


LAN cables for computer network Standard: ANSI/EIA/TIA 568-A; EN 50 173

Telecommunication and Control Cables

Application Used in data communication networks in transmission of analog or digital signals , has a maximum working transmission speed of 100 Mbit/s at frequency 100MHz.

Technical Data:
Impedance: 100 % 6 Ohm 1-100 Mhz Mutual Capacitance at 1 KHz: Max. 56 nf /km Loop resistance at 20 C: max. 19.2 Ohm/km Insulation resistance at 20 C, min: 150 Mohmkm Working Voltage, max: 250V Test Voltage: 500V Temperature Range: Fixed installation: -20C to +60C Flexible Installation: 0C to +50C Bending radius, min. 10xDcable Time delay: up to 5.7ns/m at 10MHz
2 Tensile Strength: Max.50 N/mm

Cable Structure:
Conductor: Bare copper conductor, solid, 0.51mm Insulation: Polyethylene insulation (PE high density). Core arrangement: Insulated cores are twisted in pairs with small lay and the pairs are stranded layer pair 1: blue and white Pairs color code : pair 2: orange and white pair 3: green and white pair 4: brown and white Wrapping: Core wrapping with plastic tape PVC outer jacket grey RAL 7035 Outer jacket: Screen: Electrostatic screen (St) of plastic coated aluminium foil and braid of tin coated Cu wires over the foil Cable outer diameter: 5.27 mm

On Request Oil Resistant outer sheath (O) Protected against direct sun irradiation

Cable weight: 34 kg/km

Packing
Standard packing length on cable coils: (100m)

Electrical Properties
Frequency Structural Return Loss SRL (dB) (dB) 23 23 23 23 23 23 23 22 21.06 12.5 16 Attenuation Max. NEXT (Near and Crosstalk) Min. (dB) 64 62 53 48 47 44 42 41 39 35 32

(MHz) 0.772 1 4 8 10 16 20 25 31.25 65.5 100

(dB/100m) 1.8 2.2 5.2 6.8 8.6 9.2 11.2 12.5 15.8 22.4 26

Cable Factory FKN | 2012

LiYY, LiYCY
Multiconductor signal and control cable with or without overall braid, PVC sheath Standard: DIN VDE 0812
EMV

Telecommunication and Control Cables

Application These screened and non-screened flexible control and interconnecting cables are used in instrumentation and control engineering where low current consumption are required, e.g. in industrial electronics, information and transmission systems, office machines and precision mechanics. These cables are ideal for voice communication in telecommunications systems. These cables are also suitable for flexible and permanent installation for unimpeded movement, without tensile load and without forced movement in dry rooms.
Technical Data:
Conductor cross sections mm2 : 0.14 0.25 0.34 0.5 0,75 1.0 1.5 Cond. resistance at 20 C, /km: - max. 78 57 39 25.5 19.1 13 Capacitance (core/core), pF/m (for LiYCY) Capacitance (core/screen), pF/m (for LiYCY) Capacitance (core/core), pF/m (for LiYY) Nominal voltage, pick value up to 0.25mm2 from 0.25mm2 Test voltage, core/core: up to 0.25mm2 from 0.25mm2 Insulation resistance min. 20 Mxkm Radiation resistance: 8 x 10 cJ/kg Temperature Range: Fixed installation: -30 C to +70 C Flexible Installation: -5 C to +70 C Bending radius, min. Fixed installation: 5xDcable Free movement: 10xDcable
7

Cable Structure:
Conductor: Multiwire stranded tinned or untined electrolytic copper conductor class 5, according to DIN VDE 0295

110 110 120 130 130 130 220 250 260 320 350 360 120 120 150 150 150 150 350V 500V 800V 1200V

Insulation: PVC insulation type YI2 according toVDE 0207,part 4 Color code: color coded with different colours according to DIN 47 100 Core arrangement: Insulated cores are stranded in concentric layers Wrapping: Core wrapping with plastic tape Screen: Outer jacket: braid of tinned copper wires, coverage approx. 85% (only for LiYCY) PVC outer jacket grey RAL 7032, compound type YM1 as per DIN VDE 0207 part 5.

On Request Hydrocarbon resistant outer sheath (RH). Termite and rodents protected outer sheath Protected against direct sun irradiation Oil resistant outer sheath.

Packing
C o n s t r u ct io n d a t a : L iY Y
Nu m b e r o f w ir e s No x m m 2 x0 .2 5 3 x0 .2 5 4 x0 .2 5 5 x0 .2 5 6 x0 .2 5 7 x0 .2 5 8 x0 .2 5 9 x0 .2 5 1 0 x0 .2 5 2 x0 .3 4 3 x0 .3 4 4 x0 .3 4 5 x0 .3 4 6 x0 .3 4 7 x0 .3 4 8 x0 .3 4 9 x0 .3 4 1 0 x0 .3 4 2 x0 .5 3 x0 .5 4 x0 .5 5 x0 .5 6 x0 .5 7 x0 .5 8 x0 .5 9 x0 .5 1 0 x0 .5 RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF S hape O ve r a ll Dia m e te r (A p p r o x.) m a x.m m 3 ,7 3 ,9 4 ,2 4 ,5 4 ,9 4 ,9 5 ,4 5 ,7 6 ,2 3 ,9 4 ,1 4 ,4 4 ,8 5 ,2 5 ,2 5 ,7 6 ,0 6 ,6 4 ,7 4 ,9 5 ,4 5 ,9 6 ,4 6 ,4 7 ,1 7 ,5 8 ,2 C opper w e ig h t (A p p r o x.) kg /km 4 ,5 7 ,0 9 ,3 1 1 ,8 1 4 ,0 1 6 ,5 1 9 ,0 2 1 ,0 2 3 ,5 6 ,5 9 ,8 1 3 ,1 1 6 ,3 2 0 ,0 2 3 ,0 2 6 ,1 3 0 ,0 3 2 ,6 8 ,8 1 3 ,2 1 8 ,0 2 2 ,0 2 6 ,0 3 2 ,0 3 6 ,0 4 0 ,0 4 5 ,0 T o ta l W e ig h t (A p p r o x.) kg /km 1 6 ,0 2 0 ,0 2 5 ,0 3 0 ,0 3 5 ,0 3 9 ,0 4 5 ,0 4 8 ,0 5 3 ,0 1 9 ,0 2 5 ,0 3 0 ,0 3 5 ,0 4 2 ,0 4 7 ,0 5 3 ,0 5 7 ,0 6 5 ,0 2 6 ,0 3 5 ,0 4 2 ,0 5 0 ,0 5 8 ,0 6 5 ,0 7 5 ,0 8 2 ,0 9 0 ,0 Nu m b e r o f w ir e s No x m m 2 x0 .7 5 3 x0 .7 5 4 x0 .7 5 5 x0 .7 5 6 x0 .7 5 7 x0 .7 5 8 x0 .7 5 9 x0 .7 5 1 0 x0 .7 5 2 x1 .0 3 x1 .0 4 x1 .0 5 x1 .0 6 x1 .0 7 x1 .0 8 x1 .0 9 x1 .0 1 0 x1 .0 2 x1 .5 3 x1 .5 4 x1 .5 5 x1 .5 6 x1 .5 7 x1 .5 8 x1 .5 9 x1 .5 1 0 x1 .5

Standard packing length on cable coils: ( 50m, 100m)


C o n s t r u ct io n d a t a : L iY Y
S hape O ve r a ll Dia m e te r (A p p r o x.) m a x.m m 5 ,1 5 ,3 5 ,8 6 ,4 7 ,0 7 ,0 7 ,8 8 ,2 1 0 ,0 5 ,4 5 ,7 6 ,3 6 ,9 7 ,5 7 ,5 8 ,4 9 ,8 1 0 ,5 6 ,4 6 ,7 7 ,4 8 ,2 1 0 ,0 1 0 ,0 1 1 ,0 1 1 ,5 1 2 ,6 C opper w e ig h t (A p p r o x.) kg /km 1 4 ,3 2 2 ,0 2 8 ,5 3 5 ,5 4 2 ,5 5 0 ,0 5 7 ,0 6 4 ,0 7 1 ,0 1 9 ,0 2 8 ,5 3 8 ,0 4 7 ,5 5 6 ,0 6 6 ,0 7 5 ,0 8 5 ,0 9 5 ,0 2 8 ,0 4 2 ,0 5 5 ,0 6 9 ,1 8 3 ,0 9 7 ,0 1 1 1 ,0 1 2 5 ,0 1 3 9 ,0 T o ta l W e ig h t (A p p r o x.) kg /km 3 2 ,0 4 3 ,0 5 4 ,0 6 6 ,0 7 7 ,0 8 8 ,0 9 9 ,0 1 1 0 ,0 1 3 5 ,0 3 9 ,0 5 2 ,0 6 6 ,0 8 0 ,0 9 5 ,0 1 0 7 ,0 1 2 2 ,0 1 5 8 ,0 1 7 5 ,0 5 3 ,0 7 3 ,0 9 3 ,0 1 1 4 ,0 1 5 8 ,0 1 7 6 ,0 2 0 0 ,0 2 2 1 ,0 2 4 5 ,0

RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF

Cable Factory FKN | 2012

LiYY, LiYCY
Multiconductor signal and control cable with or without overall braid, PVC sheath Standard: DIN VDE 0812
EMV

Telecommunication and Control Cables

Construction data: LiYCY


Number of wires No x mm 2x0.25 3x0.25 4x0.25 5x0.25 6x0.25 7x0.25 8x0.25 9x0.25 10x0.25 2x0.34 3x0.34 4x0.34 5x0.34 6x0.34 7x0.34 8x0.34 9x0.34 10x0.34 2x0.5 3x0.5 4x0.5 5x0.5 6x0.5 7x0.5 8x0.5 9x0.5 10x0.5 RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF Shape Overall Diameter (Approx.) max.mm 3,9 4,1 4,4 4,8 5,2 5,2 5,7 6,0 6,6 4,1 4,3 4,6 5,0 5,3 5,3 6,0 6,3 6,8 5,1 5,3 6,0 6,5 7,0 7,0 7,7 8,1 9,8 Copper weight (Approx.) kg/km 14,0 16,0 20,0 23,0 25,0 29,0 39,0 44,0 47,0 17,0 22,0 25,0 30,0 38,0 42,0 50,0 55,0 62,0 22 26,0 35,0 46,0 52,0 55,0 65,0 72,0 77,0 Total Weight (Approx.) kg/km 26,0 32,0 37,0 42,0 49,0 52,0 68,0 76,0 78,0 34,0 43,0 52,0 62,0 73,0 83,0 101,0 112,0 120,0 38,0 46,0 60,0 75,0 86,0 90,0 110,0 125,0 148,0 Number of wires No x mm 2x0.75 3x0.75 4x0.75 5x0.75 6x0.75 7x0.75 8x0.75 9x0.75 10x0.75 2x1.0 3x1.0 4x1.0 5x1.0 6x1.0 7x1.0 8x1.0 9x1.0 10x1.0 2x1.5 3x1.5 4x1.5 5x1.5 6x1.5 7x1.5 8x1.5 9x1.5 10x1.5

Construction data: LiYCY


Shape Overall Diameter (Approx.) max.mm 5,7 5,9 6,4 7,0 7,6 7,6 8,4 9,8 10,6 5,4 5,7 6,3 6,9 7,5 7,5 9,4 9,8 10,6 5,6 5,9 6,5 7,1 7,8 7,8 9,7 10,2 11,0 Copper weight (Approx.) kg/km 35,0 42,0 52,0 60,0 75,0 80,0 89,0 97,0 108,0 35,0 45,0 52,0 64,0 75,0 83,0 93,0 101,0 112,0 45,0 55,0 65,0 75,0 85,0 90,0 105,0 112,0 124,0 Total Weight (Approx.) kg/km 55,0 65,0 79,0 92,0 112,0 117,0 142,0 180,0 185,0 56,0 70,0 83,0 100,0 120,0 125,0 174,0 190,0 196,0 65,0 85,0 95,0 115,0 134,0 140,0 190,0 205,0 215,0

RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF

*other construction and sizes are available on request. Packing type and length is available on request.

Cable Factory FKN | 2012

LiYY-TP, LiYCY-TP
Paired PVC data cables with or without overall braid and PVC sheath Standard: DIN VDE 0812 and 0814
EMV

Telecommunication and Control Cables

Application These screened and non-screened flexible control and interconnecting cables are ideal for voice communication in telecommunication systems, for pulse, signal and data transmission applications. The twisted pairs with optimum pair and layer pitch prevent mutual interaction from neighboring conductor circuits. The overall braided screen, consisting of tinned copper wires with a visible coverage of approx. 85% provides protection against external pulses. These cables are also suitable for flexible and permanent installation in dry and moist rooms.
Technical Data:
Conductor cross sections mm2 : 0.14 0.25 0.34 0.5 0,75 1.0 1.5 Cond. resistance at 20 C, /km: - max. 78 57 39 25.5 19.1 13 Capacitance (core/core), pF/m (for LiYCY) Capacitance (core/screen), pF/m (for LiYCY) Capacitance (core/core), pF/m (for LiYY) Mutual capacitance at 800Hz-max. Capacitance unbalances at 800Hz; K1 max. Nominal voltage, pick value up to 0.25mm2 from 0.25mm2 Test voltage, core/core: up to 0.25mm2 from 0.25mm2 Insulation resistance min. 20 Mxkm Radiation resistance: 8 x 107 cJ/kg Temperature Range: Fixed installation: -30 C to +70 C Flexible Installation: -5 C to +70 C Bending radius, min. Fixed installation: 5xDcable Free movement: 10xDcable 350V 500V 800V 1200V 110 110 120 130 130 130 220 250 260 320 350 360 120 120 150 150 150 150 150pF/m 300pF/100m

Cable Structure:
Conductor: Multiwire stranded tinned or untined electrolytic copper conductor class 5, according to DIN VDE 0295

Insulation: PVC insulation type YI2 according toVDE 0207,part 4 Pairs: each 2 wires are twisted to a pair Color code: color coded with different colours according to DIN 47 100 Core arrangement: the pairs are stranded into layer Wrapping: Core wrapping with plastic tape Screen: Outer jacket: braid of tinned copper wires, coverage approx. 85% (only for LiYCY) PVC outer jacket grey (RAL 7001/7032), compound type YM1 as per DIN VDE 0207 part 5.

On Request

Hydrocarbon resistant outer sheath (RH). Termite and rodents protected outer sheath Protected against direct sun irradiation Oil resistant outer sheath.

Packing

Standard packing length on cable coils: ( 50m, 100m)

Construction data: LiYY-TP


Number of pairs No x mm 1x2x0.25 2x2x0.25 3x2x0.25 4x2x0.25 5x2x0.25 1x2x0.34 2x2x0.34 3x2x0.34 4x2x0.34 5x2x0.34 1x2x0.5 2x2x0.5 3x2x0.5 4x2x0.5 5x2x0.5 RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF Shape Overall Copper Total Diameter weight Weight (Approx.) (Approx.) (Approx.) max.mm kg/km kg/km 3,7 5,4 5,7 6,3 6,9 3,9 5,7 6,1 6,7 7,4 4,7 7,1 7,5 9,3 10,2 4,8 9,5 14,0 18,8 23,5 2,9 5,6 8,8 11,0 14,0 8,7 17,5 26,2 35,0 44,0 28 36,0 45,0 54,0 65,0 15 26,0 32,0 39,0 47,0 25 45,0 60,0 98,0 116,0

Construction data: LiYY-TP


Number of pairs No x mm 1x2x0.75 2x2x0.75 3x2x0.75 4x2x0.75 5x2x0.75 1x2x1.0 2x2x1.0 3x2x1.0 4x2x1.0 5x2x1.0 1x2x1.5 2x2x1.5 3x2x1.5 4x2x1.5 5x2x1.5 RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF Shape Overall Copper Total Diameter weight Weight (Approx.) (Approx.) (Approx.) max.mm kg/km kg/km 5,1 7,8 9,3 10,1 11,1 6,4 9,4 9,9 10,8 11,9 6,4 11,0 11,6 12,8 14,1 14,2 28,4 42,6 56,9 71,0 19 38,0 56,0 76,0 95,0 28 55,5 83,3 111,1 139,0 32 60,0 102,0 127,0 152,0 39 94,0 122,0 152,0 182,0 53 126,0 167,0 210,0 254,0

Cable Factory FKN | 2012

LiYY-TP, LiYCY-TP
Paired PVC data cables with or without overall braid and PVC sheath Standard: DIN VDE 0812 and 0814
EMV

Telecommunication and Control Cables

Construction data: LiYCY-TP


Number of pairs No x mm 1x2x0.25 2x2x0.25 3x2x0.25 4x2x0.25 5x2x0.25 1x2x0.5 2x2x0.5 3x2x0.5 4x2x0.5 5x2x0.5 1x2x0.75 2x2x0.75 3x2x0.75 4x2x0.75 5x2x0.75 RF RF RF RF RF RF RF RF RF RF RF RF RF RF RF Shape Overall Copper Total Diameter weight Weight (Approx.) (Approx.) (Approx.) max.mm kg/km kg/km 4,1 6,0 6,3 6,9 7,5 4,7 7,1 7,5 9,3 10,2 5,1 8,8 9,3 10,1 11,1 15,0 29,0 38,0 44,0 55,0 35,0 62,0 75,0 95,0 115,0 35,0 62,0 75,0 95,0 115,0 35,0 49,0 60,0 72,0 85,0 40,0 80,0 100,0 133,0 155,0 55,0 115,0 138,0 165,0 195,0

Construction data: LiYY-TP


Number of pairs No x mm 1x2x1.0 2x2x1.0 3x2x1.0 4x2x1.0 5x2x1.0 1x2x1.5 2x2x1.5 3x2x1.5 4x2x1.5 5x2x1.5 RF RF RF RF RF RF RF RF RF RF Shape Overall Copper Total Diameter weight Weight (Approx.) (Approx.) (Approx.) max.mm kg/km kg/km 5,4 9,4 9,9 10,8 11,9 6,4 11,0 11,6 12,8 14,1 38,0 72,0 95,0 117,0 140,0 52,0 98,0 130,0 160,0 195,0 58,0 130,0 160,0 198,0 230,0 79,0 170,0 215,0 265,0 310,0

RF - fine wire stranded conductor (class 5)

*other construction and sizes are available on request. Packing type and length is available on request.

Cable Factory FKN | 2012

NYSLY, NYSLYCY - OIL


Special PVC flexible control cables with oil-resistance outer sheath Rated Voltage: U0/U - 300/500 V Standard: DIN VDE 0281/part 5 and part 13
EMV

Telecommunication and Control Cables

Application In dry and wet conditions as supply cable or remote control and signal cable in assembling lines, machine tools, automatics, etc., at medium mechanical strains. Not designed for laying in the open air. Due to his chemical characteristics suitable for usage in brewaries and washing plants.

Technical Data:
Conductor resistance: acc. to DIN VDE 0295 and IEC 60228 for class 5 Permissable conductor temperature: in constant operation: 70C in short circuit (max 5s): 150C Working Voltage: 300/500 V Insulation resistance, min. 20 Mxkm Test voltage: wire/wire: 2 kV, wire/screen: 2 kV, Temperature Range: Fixed installation: -40C to +70C Flexible Installation: +5C to +70C Radiation resisance: 80x106 cJ/kg (up to 80 Mrad) Bending radius, min. 7.5xDcable Oil resistance: research according to VDE 0207 and VDE 0473.

Cable Structure:
Conductor: Multiwire stranded electrolytic copper conductor class 5, according to DIN VDE 0295 and IEC 60228 The cores are black, marked with numbers, according to DIN VDE 0293. When green/yellow core exists (type code: -JZ), it is laid in outer layer.

Insulation: Special PVC compound, type TI 2, according to DIN VDE 0281 Teil 1 Color code:

Core arrangement: Cores stranded in layer, without streched central core Wrapping: Core wrapping with plastic tape Screen: braid of tinned copperwires, coverage approx. 85% (only for NYSLYCO) Outer jacket: Special PVC compound layer, oil-resistant, complying to type TM 5 requirements according to DIN VDE 0281 Teil 1

Color: Standard colour of the sheath: gray

On Request Protected against direct sun irradiation Oil resistant outer sheath.

RF - fine wire stranded conductor (class 5)

Packing

Standard packing length on cable coils: ( 50m, 100m)

Construction data NYSLYC U0/U - 300/500V


Num. of Cores and Nominal Cross Section No x mm 3x0.5 4x0.5 5x0.5 7x0.5 12x0.5 19x0.5 25x0.5 27x0.5 34x0.5 37x0.5 44x0.5 50x0.5 61x0.5 Shape

Construction data: NYSLYC


Shape

U0/U - 300/500V
Packing: Cable coil or Drum m or N/m 100 100 100 9/1000 10/1000 12/1000 14/1000 14/1000 14/1000 14/1000 16/1000 16/1000 16/1000

Num. of Cores Overall Copper Total Packing: Diameter weight Weight Cable coil and Nominal Cross (Approx.) (Approx.) (Approx.) or Drum Section max.mm kg/km kg/km m or N/m No x mm 8,6 9,3 10,4 11,0 13,9 16,8 19,5 18,6 21,1 21,1 24,3 25,4 27,2 35,0 43,0 49,0 61,0 107,0 150,0 189,0 200,0 238,0 256,0 301,0 354,0 417,0 99,0 118,0 141,0 166,0 263,0 382,0 505,0 473,0 599,0 608,0 772,0 877,0 1003,0 100 100 100 100 10/1000 12/1000 12/1000 12/1000 14/1000 14/1000 14/1000 14/1000 16/1000 3x0.75 4x0.75 5x0.75 7x0.75 12x0.75 19x0.75 25x0.75 27x0.75 34x0.75 37x0.75 44x0.75 50x0.75 61x0.75

Overall Copper Total Diameter weight Weight (Approx.) (Approx.) (Approx.) max.mm kg/km 44,0 54,0 63,0 80,0 139,0 200,0 254,0 270,0 328,0 353,0 414,0 483,0 576,0 kg/km 113,0 144,0 163,0 194,0 310,0 453,0 600,0 596,0 742,0 788,0 930,0 1054,0 1242,0

RF RF RF RF RF RF RF RF RF RF RF RF RF

RF RF RF RF RF RF RF RF RF RF RF RF RF

9,0 10,2 10,9 11,6 14,7 17,8 20,7 20,5 22,8 23,5 25,9 27,1 29,5

Cable Factory FKN | 2012

NYSLY, NYSLYCY - OIL


Special PVC flexible control cables with oil-resistance outer sheath Rated Voltage: U0/U - 300/500 V Standard: DIN VDE 0281/part 5 and part 13
EMV

Telecommunication and Control Cables

Construction data NYSLYC U0/U - 300/500V


Num. of Cores and Nominal Cross Section No x mm 3x1 4x1 5x1 7x1 12x1 19x1 25x1 27x1 34x1 37x1 44x1 50x1 61x1 Shape Overall Copper Total Packing: Diameter weight Weight Cable coil (Approx.) (Approx.) (Approx.) or Drum max.mm RF RF RF RF RF RF RF RF RF RF RF RF RF 9,6 10,7 11,4 12,2 16,6 19,4 22,3 22,7 24,8 24,9 27,5 29,1 31,9 kg/km 53,0 65,0 77,0 99,0 174,0 250,0 321,0 342,0 415,0 448,0 526,0 615,0 732,0 kg/km 133,0 162,0 185,0 222,0 394,0 548,0 716,0 744,0 895,0 919,0 1088,0 1260,0 1485,0 m or N/m 100 100 10/100 10/100 12/1000 12/1000 14/1000 14/1000 14/1000 14/1000 16/1000 16/1000 14/500

Construction data: NYSLYC


Num. of Cores and Nominal Cross Section No x mm 3x1.5 4x1.5 5x1.5 7x1.5 12x1.5 19x1.5 25x1.5 27x1.5 34x1.5 37x1.5 44x1.5 50x1.5 61x1.5 RF RF RF RF RF RF RF RF RF RF RF RF RF Shape

U0/U - 300/500V

Overall Copper Total Packing: Diameter weight Weight Cable coil (Approx.) (Approx.) (Approx.) or Drum max.mm 12,2 13,3 14,6 15,6 21,4 25,5 29,6 30,2 32,8 33,2 37,8 39,2 42,0 kg/km 104,0 131,0 172,0 225,0 365,0 548,0 738,0 789,0 968,0 1045,0 1235,0 1419,0 1663,0 kg/km 228,0 275,0 332,0 409,0 710,0 1031,0 1380,0 1439,0 1733,0 1807,0 2233,0 2499,0 2869,0 m or N/m 100 100 10/1000 10/1000 14/1000 14/1000 16/1000 16/1000 14/500 14/500 16/500 16/500 16/500

Cable Factory FKN | 2012

SPZ, SEZ
Copper conductors, PVC insulation, steel tape armour Standard: JS S2.011 : 2008

Telecommunication and Control Cables

Application For connecting remote safety control and signal devices at electrificated railways. For laying in earth, in ducts.

Technical Data:
Conductor diameter, mm 0.9 1.4 Conductor resistance at 200 C - max. 28.9 /km 11.9 /km Max. operating temperature of Conductor: 70C 70C Insulation resistance, min: for SPZ: 5 M .km Mutual capacitance, max: for SPZ: 180 nF/km 210 nF/km for SEZ: 100 nF/km 120 nF/km Dialectic strenght, wire/wire: 2000 V 2000 V Temperature range: -5C to +50C Minimum bending radius approx. 15xDcable 5 M .km for SEZ: 10 G .km 10 G .km

Cable Structure:
Conductor: Annealed copper wire 0.9 mm diameter and 1.4 mm diameter Insulation: for SPZ: PVC compound for SEZ: PE compound Core arrangement: The cores are stranded, concentric laid Inner covering: thermoplastic tape Inner sheath: PVC compound Armour: Wrapped steel tape Outer sheath: PVC compound Color: Standard colour of the sheath: black

Packing Packing length on wooden drums: ( 500m; 1000m )

Construction data: SPZ


Number of pairs No x mm 2x0.9 4x0.9 5x0.9 8x0.9 12x0.9 16x0.9 21x0.9 27x0.9 33x0.9 40x0.9 48x0.9 2x0.9 4x0.9 5x0.9 8x0.9 12x0.9 16x0.9 21x0.9 27x0.9 33x0.9 40x0.9 48x0.9 RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE Shape Overall Copper Total Diameter weight Weight (Approx.) (Approx.) (Approx.) max.mm kg/km kg/km 9,0 11,0 12,0 13,0 14,5 16,0 17,5 18,5 19,5 22,0 23,5 9,0 10,5 11,0 12,5 14,5 15,5 16,5 18,0 19,5 21,5 23,5 12,2 24,0 31,0 49,0 73,0 98,0 128,0 165,0 201,0 244,0 293,0 12,2 24,0 31,0 49,0 73,0 98,0 128,0 165,0 201,0 244,0 293,0 155,0 174,0 196,0 242,0 321,0 385,0 460,0 530,0 610,0 762,0 869,0 153,0 160,0 181,0 224,0 304,0 360,0 423,0 500,0 606,0 721,0 821,0 Number of pairs No x mm 2x1.4 4x1.4 5x1.4 8x1.4 12x1.4 16x1.4 21x1.4 27x1.4 33x1.4 40x1.4 48x1.4 2x1.4 4x1.4 5x1.4 8x1.4 12x1.4 16x1.4 21x1.4 27x1.4 33x1.4 40x1.4 48x1.4

Construction data: SPZ


Shape Overall Copper Total Diameter weight Weight (Approx.) (Approx.) (Approx.) max.mm kg/km kg/km 10,5 12,5 13,5 15,0 17,5 19,0 21,0 24,0 25,3 27,5 29,5 10,5 13,0 13,5 15,5 17,5 18,0 21,0 24,0 26,5 28,0 29,0 29,6 59,0 74,0 118,0 177,0 237,0 310,0 399,0 488,0 591,0 710,0 29,6 59,0 74,0 118,0 177,0 237,0 310,0 399,0 488,0 591,0 710,0 205,0 236,0 271,0 359,0 505,0 618,0 770,0 980,0 1141,0 1318,0 1524,0 200,0 224,0 268,0 350,0 480,0 584,0 724,0 922,0 1150,0 1260,0 1419,0

RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE

Construction data: SEZ

Construction data: SEZ

* Other constructions are available on request

Cable Factory FKN | 2012

YV x 0.4/0.8, YV x 0.5/0.9
Tinned copper conductor, PVC insulation, single or stranded Standard: VDE 0812

Telecommunication and Control Cables

The jumper wire is used for wiring telephone and signal distributors. Tinned copper conductor with a diameter of 0.4, and 0.5mm PVC insulating cover. The operating voltages of the cables are 500 V.

Technical Data:
Conductor diameter, mm 0.4
0

Cable Structure:
0.5 C - ma 92.2 95.0 200 500V
Conductor: Conductor: Cable core: solid tinned copper conductor diameter: 0.4mm and 0.5mm PVC insulation typeYI3 according to VDE 0207, part4 the wires are stranded

Conductor resistanceat 20 -single wire 144 -multi-wire 148 Insulation resistancemin., M .km 200 Nominal voltage peak value 500V Temperature range:

Test voltage 50Hz, 1 min 1200V 1200V

into pairs, triples, quads and quintuples

mobile: -30C to +50C fixed: -5C to +60C Minimum bending radius approx. 10xDcable

Color coding:
number of wires 1 2 3 4 5 Wire color brown, red, yellow, green, blue, gray, white, black white/brown, white/green, white/blue white/black/green white/yellow/black/green white/yellow/black/green/gray

Constriction Data:
Number of wires Outer diameter approx. mm x mm Copper weight approx. kg/km YV x 0.4/0.8 1 2 3 4 5 1 2 3 4 5 0.8 1.6 1.7 1.9 2.2 0.9 1.8 1.9 2.2 2.4 1.1 2.2 3.3 4.4 5.5 YV x 0.5/0.9 1.7 3,5 5.2 7.0 8.7 2.3 4.8 7.0 9.2 11.6 1.6 3.2 4.8 6.4 8.0 Wire weight approx. kg/km

Type Codes
V - tinned copper conductor Y - insulating cover of PVC

Packing
Packing length in cable coils: ( on request )

Cable Factory FKN | 2012

Low Voltage Power Cables

NYY, NAYY
Power cable with PVC insulation and PVC sheath Rated Voltage: U0/U - 0.6/1 kV Standard: DIN VDE 0276/HD603 type 3G-2-power; DIN VDE 0276/HD627 type 4H1 - signal
< VDE >

Low Voltage Power Cables

Application NYY, NAYY is used in power plants industrial and switching installations, in secondary distribution networks and other. These cables are preferentially used in outdoor applications, for indoor installations, in the open air, underground and in water where mechanical damage is not anticipated.

Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 Core temperature, max: 70oC in operation Max. short circuit temperature: 160 oC , not more than 5 sec Rated voltage - U0 /U (Umax ): 0.6/1(1.2) kV Test voltage: AC - 4 kV; 50 Hz Temperature Range Fixed installation: -30C to +70C Flexible Installation: -5C to +50C Bending radius, min. single core: 15xDcable multi core: 12xDcable Specific insulation resistance at 70C: min, 1010 x cm For Cu conducor = 50 N/mm2 Max. permessible tensile stress with cable grip: For Al conducor = 30 N/mm2

Cable Structure:
Conductor: solid or multi-strand Cu or Al wires class 1, 2 or 5 acc. VDE 0295(IEC 60228)

Insulation: PVC type DIV4 acc. VDE0207 Core identification: according to VDE 0293 Signal-command copper core: Cores assembly: Additional, cross section 2,5mm2, red coloured (black coloured 1,5mm2 on request) cores stranded concentrically (cores stranded in concentric layers, for signal)

Inner sheath: rubber filling compound or tape Sheath: PVC type DMV5 acc. VDE 0207 Color of sheath: black

RM - mutliwire round shaped


Copper: 1.5mm - 630mm Copper: 35mm - 300mm Aluminium: 50mm - 630mm Aluminium: 50mm - 240mm

SM - mutliwire sector shaped

Additional information and technical data


Available conductor sizes for power distribution:
Number of cores size of Cu conductors 1 core: 4mm2 - 630mm2 2 cores: 1.5mm2 - 120mm2 3 cores: 1.5mm2 - 300mm2

RE - solid round conductor


size of Al conductors 25mm2 - 630mm2 25mm2 - 120mm2 25mm2 - 240mm2 25mm2 - 240mm2 25mm2 - 240mm2 / + 25mm2 - 120mm2 25mm2 - 300mm2 size of Al conductors / / /

4 cores: 1.5mm - 300mm 3 cores+1 earth core: 25mm2 - 300mm2 / + 16mm2 - 150mm2 5 cores: 1.5mm2 - 300mm2 Available conductor sizes for signalling and control Number of cores size of Cu conductors over 7 cores (class 5) (1.5 - 2.5 )mm2 7 -19 cores: (1.5 - 4 ) RE; RM over 19 cores (1.5 - 2.5 ) RE; RM

On request:
Fire propagation acc. IEC 60332-3 cat. A, B, C Hydrocarbon resistant outer sheath (RH). Termite and rodents protected outer sheath. Oil resistant outer sheath.

Packing

*other dimensions available on request.

Standard packing length on wooden drums: (500m; 1000m) Length Tolerance per drum 5%
C o n s t r u ct io n d a t a : N A Y Y
Num be r of core s x N o m in a l C r o s s S e c tio n No x m m 4 x 2 5 +1 .5 4 x 3 5 +1 .5 4 x 5 0 +1 .5 4 x 7 0 +1 .5 4 x 9 5 +1 .5 4 x 1 2 0 +1 .5 4 x 1 5 0 +1 .5 4 x 1 8 5 +1 .5 4 x 2 4 0 +1 .5 S hape O v e r a ll D ia m e te r ( A p p r o x .) m a x .m m 2 7 ,5 3 0 ,0 3 1 ,0 3 5 ,0 4 0 ,0 4 3 ,0 4 8 ,0 5 3 ,0 5 9 ,0

U 0 / U - 0 .6 / 1 k V
T o ta l W e ig h t ( A p p r o x .) kg /km 1 0 8 1 ,0 1 2 9 3 ,5 1 3 4 0 ,0 1 7 5 5 ,0 2 2 6 2 ,0 2 7 0 2 ,0 3 3 7 0 ,5 4 0 8 6 ,5 5 1 4 2 ,0 P a c k in g : C a b le c o il o r Drum m o r N/m 1 2 /5 0 0 1 4 /5 0 0 1 4 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 8 /5 0 0 2 0 /5 0 0 2 2 /5 0 0

A l. w e ig h t ( A p p r o x .) kg /km 2 9 0 ,0 4 0 6 ,0 5 8 0 ,0 8 1 2 ,0 1 1 0 2 ,0 1 3 9 2 ,0 1 7 4 0 ,0 2 1 4 6 ,0 2 7 8 4 ,0

R M +R E R M +R E S M +R E S M +R E S M +R E S M +R E S M +R E S M +R E S M +R E

Cable Factory FKN | 2012

NYY, NAYY
Power cable with PVC insulation and PVC sheath Rated Voltage: U0/U - 0.6/1 kV Standard: DIN VDE 0276/HD603 type 3G-2-power; DIN VDE 0276/HD627 type 4H1 - signal
< VDE >

Low Voltage Power Cables

Construction data: NYY U0/U - 0.6/1kV


Number of cores x Nominal Cross Section No x mm
1x4 1x6 1x10 1x16 1x25 1x35 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 3x1.5 3x2.5 3x4 3x6 3x10 3x16 3x25/16 3x35/16 3x50/25 3x70/35 3x95/50 3x120/70 3x150/70 3x185/95 3x240/120 4x1.5 4x2.5 4x4 4x6 4x10 4x16 4x25 4x35 4x50 4x70 4x95 4x120 4x150 4x185 4x240 5x1.5 5x2.5 5x4 5x6 5x10 5x16 5x25 7x1.5 10x1.5 12x1.5 14x1.5 19x1.5
2 4 x1 .5 3 0 x1 .5 4 0 x1 .5 7 x2 .5 1 0 x2 .5 1 2 x2 .5 1 4 x2 .5 1 9 x2 .5 2 4 x2 .5 3 0 x2 .5 4 0 x2 .5

Shape

Overall Diameter (Approx.) max.mm

Copper weight (Approx.) kg/km


38,0 58,0 96,0 154,0 240,0 336,0 480,0 672,0 912,0 1150,0 1440,0 1776,0 2304,0 2880,0 3840,0 43,0 72,0 115,0 173,0 288,0 461,0 874,0 1162,0 1680,0 2352,0 3216,0 4128,0 4992,0 6240,0 8064,0 58,0 96,0 154,0 230,0 384,0 614,0 960,0 1344,0 1920,0 2688,0 3648,0 4608,0 5760,0 7104,0 9210,0 72,0 120,0 192,0 288,0 480,0 768,0 1200,0 101,0 144,0 173,0 202,0 274,0
3 4 6 ,0 4 3 2 ,0 5 7 6 ,0 1 6 8 ,0 2 4 0 ,0 2 8 8 ,0 3 3 6 ,0 4 5 6 ,0 5 7 6 ,0 7 2 0 ,0 9 6 0 ,0

Total Weight (Approx.) kg/km


104,0 128,0 176,0 239,0 380,0 477,0 650,0 864,0 1132,0 1405,0 1710,0 2086,0 2669,0 3305,0 4337,0 223,0 272,0 373,0 466,0 629,0 850,0 1595,0 1718,0 2383,0 3196,0 4271,0 5281,0 6408,0 7909,0 10162,0 256,0 316,0 439,0 547,0 743,0 1039,0 1620,0 1916,0 2639,0 3576,0 4746,0 5813,0 7263,0 8905,0 11430,0 292,0 363,0 510,0 640,0 899,0 1240,0 1957,0 350,0 476,0 523,0 578,0 716,0
8 8 5 ,0 1 0 4 5 ,0 1 3 1 0 ,0 4 4 5 ,0 6 1 0 ,0 6 8 0 ,0 7 5 5 ,0 9 5 0 ,0 1 1 7 3 ,0 1 3 9 8 ,0 1 7 7 8 ,0

Packing: Cable coil or Drum m or N/m


100 100 100 9/1000 9/1000 10/1000 10/1000 12/1000 12/1000 14/1000 14/1000 14/1000 16/1000 16/1000 18/1000 9/1000 9/1000 10/1000 12/1000 12/1000 12/1000 14/1000 16/1000 14/500 14/500 16/500 16/500 18/500 20/500 22/500 9/1000 10/1000 10/1000 12/1000 12/1000 14/1000 16/1000 16/1000 14/500 14/500 16/500 16/500 18/500 20/500 24/500 10/1000 10/1000 12/1000 12/1000 14/1000 14/1000 16/1000 10/1000 12/1000 12/1000 12/1000 14/1000
1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0

RE RE RE RE RM RM RM RM RM RM RM RM RM RM RM RE RE RE RE RE RE RM /RM S M /RM S M /RM S M /S M S M /S M S M /S M S M /S M S M /S M S M /S M RE RE RE RE RE RE RM SM SM SM SM SM SM SM SM RE RE RE RE RE RE RM RE RE RE RE RE


RE RE RE RE RE RE RE RE RE RE RE

8,0 9,0 10,0 11,0 13,0 14,0 15,0 17,0 19,0 21,0 22,0 24,0 27,0 30,0 34,0 12,0 13,0 15,0 16,0 18,0 20,0 25,0 27,0 30,5 33,0 38,0 41,0 45,5 50,0 57,0 13,0 14,0 15,0 17,0 19,0 22,0 26,5 27,0 31,0 35,0 40,0 43,0 48,0 53,0 60,0 14,0 15,0 17,0 18,5 21,0 23,0 30,0 15,0 17.5 18,0 18,7 20,5
2 3 ,5 2 5 ,0 2 7 ,0 1 6 ,0 1 9 ,0 1 9 ,5 2 0 ,5 2 2 ,5 2 6 ,0 2 7 ,2 3 0 ,0

*other dimensions and packing length are available on request.

Cable Factory FKN | 2012

NYBY, NAYBY
Power Cable PVC insulated and armoured with two steel tapes Rated Voltage: U0/U - 0.6/1 kV Standard: IEC 60502-1(DIN VDE 0271)

Low Voltage Power Cables

Application NYBY is used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other. These cables are also used as control cables for transmission of measured values control and regulation pulses. These cables are preferentially used for underground application as well as for interior installation in room and cable ducts and for outdoor and applications, for indoor installations, in the open air, underground and in wet ambient where greater mechanical protection an protection against accidental contact is required if damaged.
Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 Core temperature, max: 70oC in operation Max. short circuit temperature: 160 oC , not more than 5 sec Rated voltage - U0 /U (Umax ): 0.6/1 (1.2) kV Test voltage: AC - 3.5 kV; 50 Hz Temperature Range Fixed installation: -30C to +70C Flexible Installation: -5C to +50C Bending radius, min. single core: 15xDcable multi core: 12xDcable Specific insulation resistance at 70C: min. 1010xcm Max. permissible tensile stress with cable grip: P = D2 3 N/mm2 D = Cable diameter (mm)
Armour: for multi-core cable: two steel tapes for single-core cable: two Aluminium tapes Sheat: PVC type ST1 acc. IEC 60502 Color: black

Cable Structure:
Conductor: solid or multi-strand Cu or Al wires class 1, 2 or 5 acc. VDE 0295(IEC 60228) single core-black, multiple core according to VDE 0293 (HD 308) cores stranded concentrically (cores stranded in concentric layers, for signal)

Insulation: PVC acc. to IEC 60502 Core identification: Cores assembly:

Inner sheath: PVC filling compound

RM - mutliwire round shaped


Copper: 1.5mm - 630mm Copper: 35mm - 300mm Aluminium: 50mm - 630mm Aluminium: 50mm - 240mm

SM - mutliwire sector shaped

Additional information and technical data


A v a ila b le co n d u ct o r siz e s fo r p o w e r d ist ib u t io n :
Nu mb e r o f c o r e s s iz e o f Cu c o n d u c t o r s 1 core : 4m m 2 - 630m m 2 2 c o r e s : 1 .5 m m 2 - 1 2 0 m m 2 3 c o r e s : 1 .5 m m 2 - 3 0 0 m m 2 4 c o r e s : 1 .5 m m 2 - 2 4 0 m m 2 3 core s+ 1 e a rt h core : 25m m 2 - 300m m 2 / + 16m m 2 - 150m m 2 5 c o r e s : 1 .5 m m 2 - 2 4 0 m m 2 Nu mb e r o f c o r e s s iz e o f Cu c o n d u c t o r s o v e r 7 c o r e s ( c la s s 5 ) (1 .5 - 2 .5 )m m 2 7 - 1 9 c o r e s : (1 .5 - 4 ) R E; R M o v e r 1 9 c o r e s (1 .5 - 2 .5 ) R E; R M s iz e o f A l c o n d u c t o r s 16m m 2 - 630m m 2 25m m 2 - 120m m 2 25m m 2 - 240m m 2 25m m 2 - 240m m 2

RE - solid round conductor

25m m 2 - 240m m 2 / + 25m m 2 - 120m m 2 25m m 2 - 240m m 2 s iz e o f A l c o n d u c t o r s / / /

A v a ila b le co n d u ct o r siz e s fo r sig n a lin g a n d co n t ro l

On request:
Fire propagation acc. IEC 60332-3 cat. A, B, C Hydrocarbon resistant outer sheath (RH). Termite and rodents protected outer sheath. Oil resistant outer sheath.

Packing
Standard packing length on wooden drums: (500m; 1000m) Length Tolerance per drum 5%

Cable Factory FKN | 2012

NYBY, NAYBY
Power Cable PVC insulated and armoured with two steel tapes Rated Voltage: U0/U - 0.6/1 kV Standard: IEC 60502-1(DIN VDE 0271)

Low Voltage Power Cables

C onstruction da ta : NY BY , NA Y BY
Num ber of cores x Nom inal C ross S ection No x m m 2 x 1.5 2 x 2.5 2 x4 2 x6 2x10 2x16 2x25 3 x 1.5 3 x 2.5 3 x4 3 x6 3 x 10 3 x 16 3x25/16 3x35/16 3x50/25 3x70/35 3x95/50 3x120/70 3x150/70 3x185/95 3x240/120 4x1.5 4x2.5 4x4 4x6 4x10 4x16 4x25 4x35 4x50 4x70 4x95 4x120 4x150 4x185 5x1.5 5x2.5 5x4 5x6
Number of cores x Nominal Cross Section No x mm 4x25+1.5 4x35+1.5 4x50+1.5 4x70+1.5 4x95+1.5 4x120+1.5 4x150+1.5 4x185+1.5 4x240+1.5

U 0/U - 0.6/1k V
T otal W eight (A pprox.) kg/km 270,0 315,0 390,0 465,0 590,0 790,0 1215,0 280,0 340,0 440,0 540,0 710,0 970,0 1740,0 2340,0 2765,0 3590,0 4700,0 5720,0 6880,0 8440,0 10880,0 313,0 380,0 520,0 640,0 860,0 1170,0 1810,0 2630,0 2940,0 3860,0 5100,0 6150,0 7510,0 9170,0 360,0 436,0 600,0 750,0
Total Weight (Approx.) kg/km 1233,0 1730,0 1940,0 2310,0 2970,0 3600,0 4230,0 5010,0 6250,0

S hape

Overall Diam eter (A pprox.) m ax.m m NY BY 12,4 13,1 14,9 15,9 17,5 19,4 24,4 13,0 14,0 16,0 17,0 19,0 21,0 28,0 32,0 33,0 36,0 41,0 43,0 49,0 53,0 60,0 14,0 15,0 17,0 18,0 20,0 22,0 28,0 32,0 33,0 37,0 42,0 44,0 49,0 53,0 14,5 15,5 18,0 20,0
NA YBY Overall Diameter (Approx.) max.mm 28,5 31,0 33,0 37,0 42,0 46,0 50,0 55,0 61,0

C opper w eight (A pprox.) kg/km 29,0 48,0 77,0 116,0 192,0 308,0 480,0 43,0 72,0 115,0 173,0 288,0 461,0 874,0 1162,0 1680,0 2352,0 3216,0 4128,0 4992,0 6240,0 8064,0 58,0 96,0 154,0 230,0 384,0 614,0 960,0 1344,0 1920,0 2688,0 3648,0 4608,0 5760,0 7104,0 72,0 120,0 192,0 288,0

Packing: C able coil or Drum m or N/m 9/1000 9/1000 10/1000 12/1000 12/1000 12/1000 14/1000 9/1000 10/1000 12/1000 12/1000 12/1000 12/1000 12/500 14/500 14/500 14/500 16/500 16/500 18/500 20/500 22/500 10/1000 10/1000 12/1000 12/1000 14/1000 14/1000 12/500 14/500 14/500 16/500 16/500 16/500 18/500 20/500 10/1000 10/1000 12/1000 12/1000

RE RE RE RE RE RM RM RE RE RE RE RE RM RM /RE RM /RE S M /RM S M /S M S M /S M S M /S M S M /S M S M /S M S M /S M RE RE RE RE RE RM RM RM SM SM SM SM SM SM RE RE RE RE

Shape

Al weight (Approx.) kg/km 290,0 406,0 580,0 812,0 1102,0 1392,0 1740,0 2146,0 2784,0

Packing: Cable coil or Drum m or N/m 16/1000 18/1000 18/1000 20/1000 16/500 18/500 18/500 20/500 24/500

RM+RE RM+RE SM+RE SM+RE SM+RE SM+RE SM+RE SM+RE SM+RE

*other dimensions and packing length are available on request.

Cable Factory FKN | 2012

NYCY, NAYCY
Power Cable with concentric copper conductor Rated Voltage: U0/U - 0.6/1 kV Standard:DIN VDE 0276/HD603 - power ; DIN VDE 0276/HD627 type 4H1 - signal
< VDE >

Low Voltage Power Cables

Application NYCY, NAYCY is used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other. These cables are preferentially used for underground application as well as for interior installation in room and cable ducts and for outdoor and applications, for indoor installations, in the open air, underground and in wet ambient where greater mechanical protection and protection against accidental contact is required if damaged.
Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 Core temperature, max: 70oC in operation Max. short circuit temperature: 160 oC , not more than 5 sec Rated voltage - U0 /U (Umax ): 0.6/1(1.2) kV Test voltage: AC - 4 kV; 50 Hz Temperature Range Fixed installation: -30C to +70C Flexible Installation: -5C to +50C Bending radius, min. 12xDcable Specific insulation resistance at 70C: min, 10 max Permessible tensile stress with cable grip:
10

Cable Structure:
Conductor: solid or multi-strand Cu or Al wires class 1, 2 or 5 acc. VDE 0295(IEC 60228)

Insulation: PVC type DIV4 acc. VDE0207 Core identification: according to VDE 0293 (HD 308) Cores assembly cores stranded concentrically (cores stranded in concentric layers, for signal) helicoidally copper wires and one copper tape around inner covering

Inner sheath: rubber filling compaund Concentric copper conductor:


2

x cm

For Cu conductor = 50 N/mm For Al conductor = 30 N/mm2

Sheat: PVC type DMV5 acc. VDE 0207, black color

RM - mutliwire round shaped


Copper: 1.5mm - 630mm Copper: 35mm - 300mm Aluminium: 50mm - 630mm Aluminium: 50mm - 240mm

SM - mutliwire sector shaped

Additional information and technical data


A vailable conductor sizes for power distibution:
Number of cores size of Cu conductors 1 core: 4mm2 - 500mm2 2 cores: 1.5mm2 - 300mm2 3 cores: 1.5mm2 - 300mm2 4 cores: 1.5mm2 - 300mm2 3 cores+1 earth core: 25mm2 - 300mm2 / + 16mm2 - 150mm2 5 cores: 1.5mm2 - 120mm2 nominal cross-section 1,5mm 2 - 240mm 2 Number of cores size of Cu conductors over 7 cores (class 5) (1.5 - 2.5 )mm 2 7 -19 cores: (1.5 - 4 ) RE; RM over 19 cores (1.5 - 2.5 ) RE; RM size of Al conductors 25mm2 - 500mm2 25mm2 - 240mm2 25mm2 - 240mm2 25mm2 - 240mm2

RE - solid round conductor

25mm2 - 240mm2 / + 16mm2 - 120mm2 25mm2 - 120mm2 1,5mm 2 - 240mm 2 size of A l conductors / / /

A vailable sizes for concentric copper conductor: A vailable conductor sizes for signalling and control:

*other dimensions and packing length are available on request.

On request:
Fire propagation acc. IEC 60332-3 cat. A, B, C Hydrocarbon resistant outer sheath (RH). Termite and rodents protected outer sheath. Oil resistant outer sheath.

Packing
Standard packing length on wooden drums: (500m; 1000m)

Cable Factory FKN | 2012

NYCY, NAYCY
Power Cable with concentric copper conductor Rated Voltage: U0/U - 0.6/1 kV Standard:DIN VDE 0276/HD603 - power ; DIN VDE 0276/HD627 type 4H1 - signal
< VDE >

Low Voltage Power Cables

Construction data: NYCY


Number of cores x Nominal Cross Section No x mm 2 x 1.5/1.5 2 x 2.5/2.5 2 x 4/4 3x1.5/1.5 3x2.5/2.5 3x4/4 3x6/6 3x10/10 3x16/16 3x25/16 3x35/35 3x50/50 3x70/70 3x95/95 3x120/120 3x150/150 4x1.5/1.5 4x2.5/2.5 4x4/4 4x6/6 4x10/10 4x16/16 4x25/16 4x35/16 4x50/25 4x70/35 4x95/50 4x120/70 4x150/70 4x185/95 5x1.5/2.5 5x2.5/2.5 5x4/4 5x6/6 5x10/10 5x16/16 7x1.5/2.5 8x1.5/2.5 10x1.5/2.5 12x1.5/2.5 14x1.5/2.5 19x1.5/4 24x1.5/6 30x1.5/6 7x2.5/2.5 8x2.5/4 10x2.5/4 12x2.5/4 14x2.5/6 19x2.5/6 24x2.5/10 30x2.5/10 Shape Overall Diameter (Approx.) max.mm 14 14 16,0 14,0 15,0 17,0 18,0 20,0 22,0 25,0 27,0 31,0 35,0 40,0 43,0 48,0 15,0 16,0 18,0 19,0 21,0 23,0 28,0 30,0 34,0 38,0 43,0 48,0 53,0 58,0 16,0 17,0 19,0 20,0 23,0 25,0 17,0 17,0 20,0 20,0 21,0 23,0 26,0 27,0 18,0 19,0 21,0 22,0 23,0 25,0 28,0 30,0

U0/U - 0.6/1kV
Total Weight (Approx.) kg/km 245,0 285,0 360,0 280,0 316 423,0 530,0 730,0 970,0 1340,0 1820,0 2490,0 3350,0 4490,0 5500,0 6950,0 302,0 360,0 485,0 616,0 850,0 1160,0 1630,0 2080,0 2775,0 3910,0 5180,0 6400,0 8075,0 9710,0 344,0 412,0 560,0 690,0 965,0 1355,0 395,0 440,0 510,0 585,0 640,0 780,0 950,0 1105,0 490,0 550,0 670,0 730,0 825,0 1000,0 1270,0 1495,0 Packing: Cable coil or Drum m or N/m 10/1000 10/1000 12/1000 10/1000 10/1000 12/1000 12/1000 12/1000 14/1000 14/1000 16/1000 12/500 16/500 16/500 16/500 18/500 10/1000 12/1000 12/1000 12/1000 14/1000 14/1000 16/1000 16/1000 14/500 16/500 16/500 18/500 20/500 22/500 12/1000 12/1000 12/1000 12/1000 14/1000 14/1000 12/1000 12/1000 12/1000 12/1000 14/1000 14/1000 16/1000 16/1000 12/1000 12/1000 14/1000 14/1000 14/1000 14/1000 16/1000 16/1000

Copper weight (Approx.) kg/km 60,0 85,0 125,0 80,0 109,0 155,0 240,0 384,0 610,0 870,0 1340,0 1980,0 2680,0 3650,0 4610,0 5750,0 94,0 133,0 195,0 299,0 480,0 766,0 1112,0 1515,0 2156,0 3070,0 4200,0 5275,0 6690,0 8030,0 109,0 158,0 259,0 355,0 575,0 940,0 141,0 155,0 188,0 223,0 253,0 325,0 407,0 494,0 209,0 233,0 291,0 339,0 397,0 516,0 673,0 820,0

RE RE RE RE RE RE RE RE RE RM SM SM SM SM SM SM RE RE RE RE RE RE RM SM SM SM SM SM SM SM RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE RE

*other dimensions and packing length are available on request.

Cable Factory FKN | 2012

NYCWY, NAYCWY
Power Cable with concentric copper conductor Rated Voltage: U0/U - 0.6/1 kV Standard:DIN VDE 0276/HD603 type 3G-1 - power ; DIN VDE 0276/HD627 - signal
< VDE >

Low Voltage Power Cables

Application Power cables for energy supply, preferably used for underground laying, especially in subscriber networks, power station as well as control impulses and test data. Overall, where increased electrical and also mechanical protection are required. These cables are installed in open air, in underground, in water, indoors and in cable ducts. The corrugated concentric conductor (CW) is allowed to use as neutral, protective or earth conductor. Simultaneously, this also is permitted to apply as a screen for example earthed-connected protection against contact. Due to the typical construction of corrugated concentric conductors (Ceander), are possible to obtain many more cable joints, without cutting any conductor. In that way the operating reliability is guaranteed.
Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 Core temperature, max: 70oC in operation Max. short circuit temperature: 160 oC , not more than 5 sec Rated voltage - U0 /U (Umax ): 0.6/1(1.2) kV Test voltage: AC - 4 kV; 50 Hz Temperature Range Fixed installation: -30C to +70C Flexible Installation: -5C to +50C Bending radius, min. 12xDcable pecific insulation resistance at 70C: min, 1010 x cm essible tensile stress with cable grip: For Cu conductor = 50 N/mm2 For Al conductor = 30 N/mm2
Concentric copper conductor:

Cable Structure:
Conductor: solid or multi-strand Cu or Al wires class 1, 2 or 5 acc. VDE 0295(IEC 60228)

Insulation: PVC type DIV4 acc. VDE0207 Core identification: according to VDE 0293 (HD 308) Cores assembly: cores stranded concentrically (cores stranded in concentric layers, for signal) Waveconal outer conductor copper wires and contrahelical copper tape (reverse lay copper tape)

Inner sheath: rubber filling compaund

Sheath: PVC type DMV5 acc. VDE 0207 Color: black

RM - mutliwire round shaped


Copper: 1.5mm - 630mm Copper: 35mm - 300mm Aluminium: 50mm - 630mm Aluminium: 50mm - 240mm

SM - mutliwire sector shaped

Additional information and technical data


Available conductor sizes for power distribution:
Number of cores size of Cu conductors 1 core: 4mm2 - 300mm2 2 cores: 1.5mm2 - 120mm2 3 cores: 1.5mm2 - 300mm2 4 cores: 1.5mm - 240mm 3 cores+1 earth core: 25mm2 - 300mm2 / + 16mm2 - 150mm2 5 cores: 1.5mm2 - 185mm2
2 2

RE - solid round conductor

size of Al conductors 25mm2 - 300mm2 25mm2 - 120mm2 25mm2 - 240mm2 25mm2 - 240mm2 25mm2 - 240mm2 / + 16mm2 - 120mm2 25mm2 - 185mm2 1,5mm2 - 185mm2 size of Al conductors / / /

Available sizes for concentric copper conductor


nominal cross-section 1,5mm2 - 185mm2 Number of cores size of Cu conductors over 7 cores (class 5) (1.5 - 2.5 )mm2 7 -19 cores: (1.5 - 4 ) RE; RM over 19 cores (1.5 - 2.5 ) RE; RM

Available conductor sizes for signalling and control

*other dimensions and packing length are available on request.

On request:
Fire propagation acc. IEC 60332-3 cat. A, B, C Hydrocarbon resistant outer sheath (RH). Termite and rodents protected outer sheath. Oil resistant outer sheath.

Packing
Standard packing length on wooden drums: (500m; 1000m)

Cable Factory FKN | 2012

NYCWY, NAYCWY
Power Cable with concentric copper conductor Rated Voltage: U0/U - 0.6/1 kV Standard:DIN VDE 0276/HD603 type 3G-1 - power ; DIN VDE 0276/HD627 - signal
< VDE >

Low Voltage Power Cables

Construction data: NYCWY U0/U - 0.6/1kV


Number of cores x Nominal Cross Section No x mm 3x10/10 3x16/16 3x25/16 3x35/16 3x50/25 3x70/35 3x95/50 3x120/70 3x150/70 3x185/95 3x240/120 4x10/10 4x16/16 4x25/16 4x35/16 4x50/25 4x70/35 4x95/50 4x120/70 4x150/70 4x185/95 Shape Overall Diameter (Approx.) max.mm 20 22,0 26,0 28 30,0 33,0 38,0 41,0 45,0 50,0 56,0 21,0 24,0 28,0 29,0 33,0 38,0 43,0 46,0 51,0 57,0 Copper weight (Approx.) kg/km 394,0 630,0 895,0 1190,0 1722,0 2411,0 3296,0 4231,0 5117,0 6396,0 8265,0 492,0 787,0 1141,0 1535,0 2214,0 3100,0 4231,0 5412,0 6592,0 8216,0 Total Weight (Approx.) kg/km 775,0 1066,0 1584,0 1710,0 2368,0 3174 4256,0 5314,0 6344,0 8054,0 10274,0 897,0 1250,0 1822,0 2140,0 3031,0 4056,0 5364,0 6748,0 8159,0 10198,0 Packing: Cable coil or Drum m or N/m 12/1000 14/1000 16/1000 16/1000 14/500 14/500 16/500 16/500 18/500 20/500 22/500 14/1000 14/1000 16/1000 16/1000 14/500 16/500 16/500 18/500 20/500 22/500

RE RE RM SM SM SM SM SM SM SM SM RE RE RM SM SM SM SM SM SM SM

*other dimensions and packing length are available on request.

Cable Factory FKN | 2012

NYRY, NAYRY
Power Cable PVC insulation armored with steel wire armour Rated Voltage: U0/U - 0.6/1 kV Standard: IEC 60502-1; DIN VDE 0271 (acc. to BS 6346)

Low Voltage Power Cables

Application These cables are used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other.These cables are preferentially used for underground application as well as for interior installation in room and cableducts and for outdoor and applications, for indoor installations, in the open air, underground and in wet ambient where greater mechanical protection an protection against accidental contact is required if damaged.
Technical Data: Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 and BS 6360 Core temperature, max: 70oC in operation Max. short circuit temperature: 160 oC , not more than 5 sec Rated voltage U0/U(Umax): 0.6/1(1.2) kV Test voltage, AC(50 Hz): 4kV (3.5kV by IEC) Min. temp. during installation: -5C Operating temperature: -30C to +70C Bending radius, min. single core: 15xDcable multi core: 12xDcable Spec. insulation resisance at 70C: min, 1010xcm 2 2 Max. permissible tensile stress with cable grip: P = D 9 N/mm D = Cable diameter (mm)
Core identification:

Cable Structure:
Conductor: Insulation: solid or multi-strand Cu or Al wires class 1, 2 or 5 acc. VDE 0295(IEC 60228) and BS 6360 PVC compound, type PVC/A acc. to IEC 60502 (PVC type TI-1 acc. to BS 7655) single core-black, multiple core according to VDE 0293 (HD 308) or according to BS 7655

Inner sheath: PVC filling compound Armour: for single-core: aluminium round wires : NYR(AL)Y for multi-core: galvanized round steel wires Optional armour: Sheath: Armour of galvanized flat steel wires and optional contra spiral galvanized steel tape PVC compound, type PVC/ST1 acc. to IEC 60502 (PVC compound type TM-1 acc. to BS 7655), black color

Additional information and technical data


Available conductor sizes for power distribution:
Number of cores size of Cu conductors 1 core: 10mm2 - 630mm2 2 cores: 1.5mm2 - 120mm2 3 cores: 1.5mm2 - 300mm2 4 cores: 1.5mm - 240mm 3 cores+1 earth core: 25mm2 - 240mm2 / + 16mm2 - 120mm2 5 cores: 1.5mm2 - 185mm2 Number of cores size of Cu conductors over 7 cores (class 5) (1.5 - 2.5 )mm2 7 -19 cores: (1.5 - 4 ) RE; RM over 19 cores (1.5 - 2.5 ) RE; RM
2 2

size of Al conductors 25mm2 - 630mm2 25mm2 - 120mm2 25mm2 - 240mm2 25mm2 - 240mm2 25mm2 - 240mm2 / + 25mm2 - 120mm2 25mm2 - 185mm2 size of Al conductors / / /

Available conductor sizes for signalling and control:

*other dimensions and packing length are available on request.

On request:
Fire propagation acc. IEC 60332-3 cat. A, B, C Hydrocarbon resistant outer sheath (RH). Termite and rodents protected outer sheath. Oil resistant outer sheath.

Packing
Standard packing length on wooden drums: (500m; 1000m)

RM - mutliwire round shaped


Copper: 1.5mm - 630mm Copper: 35mm - 300mm Aluminium: 50mm - 630mm Aluminium: 50mm - 240mm

SM - mutliwire sector shaped

RE - solid round conductor

Cable Factory FKN | 2012

NYRY, NAYRY
Power Cable PVC insulation armored with steel wire armour Rated Voltage: U0/U - 0.6/1 kV Standard: IEC 60502-1; DIN VDE 0271 (acc. to BS 6346)

Low Voltage Power Cables

C o n s t r u ct io n d a t a : N Y R Y
N u mb e r o f co re s x N o m in a l C r o s s S e c t io n N o x mm Shape O v e r a ll D ia m e t e r ( A p p r o x . ) ma x . mm

U 0 / U - 0 .6 / 1 k V
Tota l W e ig h t (A p p ro x . ) kg /km P a c k in g : C a b le c o il o r D ru m m o r N /m

C o p p e r w e ig h t (A p p ro x . ) kg /km

N Y R ( A L ) Y - a r m o u r w it h a lu m in iu m r o o u n d w ir e s 1x10 1x16 1x25 1x35 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 RE RE RM RM RM RM RM RM RM RM RM RM RM RM RM 14,4 15,4 17,2 18,3 20,5 22,5 24,5 26,5 28,5 31,0 34,0 38,0 42,0 46,5 51,0 96,0 154,0 240,0 336,0 480,0 672,0 912,0 1152,0 1440,0 1776,0 2304,0 2880,0 3840,0 4800,0 6048,0 326,0 402,0 541,0 658,0 841,0 1070,0 1365,0 1662,0 1967,0 2406,0 3071,0 3781,0 4764,0 5968,0 7538,0 1 0 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0 1 8 /1 0 0 0 1 8 /1 0 0 0 1 6 /5 0 0 1 6 /5 0 0 1 8 /5 0 0 2 0 /5 0 0

N Y R Y - a r m o u r w it h g a lv a n iz e d s t e ll w ir e s 2x1.5 2x2.5 2x4.0 2x6.0 2x10 2x16 2x25 2x35 2x50 2x70 2x95 2x120 2x150 2x185 RE RE RE RE RE RE RM RM RM RM RM RM RM RM 14,0 15,0 16,9 18,8 21,0 23,0 27,0 29,0 32,5 37,0 42,0 45,0 50,5 55,5 28,8 48,0 76,8 115,2 192,0 308,0 480,0 672,0 960,0 1344,0 1824,0 2304,0 2880,0 3552,0 347,0 403,0 516,0 701,0 874,0 1082,0 1565,0 1893,0 2293,0 3150,0 4037,0 4725,0 6041,0 7253,0 1 0 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0 1 8 /1 0 0 0 1 6 /5 0 0 1 6 /5 0 0 1 8 /5 0 0 2 0 /5 0 0 2 2 /5 0 0

N Y R Y - a r m o u r w it h g a lv a n iz e d s t e ll w ir e s 3x1.5 3x2.5 3x4.0 3x6.0 3x10 3x16 3x25 3x35 3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300 RE RE RE RE RE RE RM RM SM SM SM SM SM SM SM SM 14,5 15,5 18,4 19,6 22,0 24,0 28,0 30,5 33,5 38,5 42,5 45,5 51,5 56,5 62,5 68,0 43,2 72,0 115,2 172,8 288,0 462,0 720,0 1008,0 1440,0 2016,0 2736,0 3456,0 4320,0 5328,0 6912,0 8640,0 382,0 448,0 678,0 783,0 1006,0 1276,0 1863,0 2279,0 2644,0 3664,0 4661,0 5478,0 7040,0 8457,0 10579,0 12683,0 1 0 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 4 /5 0 0 1 4 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 8 /5 0 0 2 0 /5 0 0 2 2 /5 0 0 2 4 /5 0 0 2 4 /5 0 0

N Y R Y - a r m o u r w it h g a lv a n iz e d s t e ll w ir e s 4x1.5 4x2.5 4x4.0 4x6.0 4x10 4x16 4x25 4x35 RE RE RE RE RE RE RM RM 15,4 16,5 19,6 21,0 23,5 27,0 30,5 33,5 57,6 96,0 153,6 230,4 384,0 616,0 960,0 1344,0 425,0 509,0 767,0 904,0 1179,0 1657,0 2236,0 2768,0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0 1 4 /5 0 0

4x50 4x70 4x95 4x120 4x150 4x185 4x240 4x300

SM SM SM SM SM SM SM SM

40,0 43,0 50,0 54,0 60,5 65,0 72,0 78,0

1920,0 2688,0 3648,0 4608,0 5760,0 7104,0 9216,0 11520,0

3639,0 4592,0 6338,0 7547,0 9073,0 10835,0 13543,0 16333,0

1 6 /5 0 0 1 6 /5 0 0 2 0 /5 0 0 2 0 /5 0 0 2 4 /5 0 0 2 4 /5 0 0 2 4 /4 5 0 2 4 /4 0 0

*other dimensions and packing length are available on request.

Cable Factory FKN | 2012

NY2Y, NAY2Y
Power Cable PVC insulation and PE sheath Rated Voltage: U0/U - 0.6/1 kV Standard:DIN VDE 0276/HD603; IEC 60502-1

Low Voltage Power Cables

Application Power cable suitable for laying in air, soil, water, concrete, in enclosed locations, cable ducts, in Power Plants, Industrial Applications, City Power Grids where mechanical damages are not expected and cables are not exposed to excessive pulling.

Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 Core temperature, max: 70oC in operation Max. short circuit temperature: 160 oC , not more than 5 sec Rated voltage: 0.6/1 kV Test voltage: AC - 4 kV (3.5kV by IEC); 50 Hz Temperature Range Fixed installation: -30C to +70C Flexible Installation: -5C to +50C Bending radius, min. single core: 15xDcable multi core: 12xDcable Specific insulation resisance at 70C: min, 1010xcm For Cu conducor = 50 N/mm2 Max. permissible tensile stress with cable grip:

Cable Structure:
Conductor:

solid or multi-strand Cu or Al wires class 1, 2 or (5) acc. VDE 0295(IEC 60228) single core-black, multiple core according to VDE 0293 (HD 308) Additional, cross section 2,5mm2, red coloured (black coloured 1,5mm2 on request) cores stranded concentrically (cores stranded in concentric layers, for signal) HDPE outer jacket, black, type DMP2 according DIN VDE 0276-603 (HD603.1)

Insulation: PVC acc. to IEC 60502 or PVC type DIV4 acc. VDE0276 Core identification:

Signal-command copper core:

Cores assembly:

Inner covering: rubber filling compound Sheath:

For Al conducor = 30 N/mm2

Color: black

Additional information and technical data Available conductor sizes for power distribution:
Number of cores size of Cu conductors 1 core: 4mm2 - 630mm2 2 cores: 1.5mm2 - 120mm2 3 cores: 1.5mm2 - 300mm2 4 cores: 1.5mm2 - 240mm2 3 cores+1 earth core: 25mm2 - 300mm2 / + 16mm2 - 150mm2 5 cores: 1.5mm2 - 240mm2 Number of cores size of Cu conductors over 7 cores (class 5) (1.5 - 2.5 )mm2 7 -19 cores: (1.5 - 4 ) RE; RM over 19 cores (1.5 - 2.5 ) RE; RM size of Al conductors 25mm2 - 630mm2 25mm2 - 120mm2 25mm2 - 240mm2 25mm2 - 240mm2 25mm2 - 240mm2 / + 25mm2 - 120mm2 25mm2 - 240mm2 size of Al conductors / / /

Available conductor sizes for signalling and control

*other dimensions and packing length are available on request.

Packing
Standard packing length on wooden drums: (500m; 1000m)

RM - mutliwire round shaped


Copper: 1.5mm - 630mm Copper: 35mm - 300mm Aluminium: 50mm - 630mm Aluminium: 50mm - 240mm

SM - mutliwire sector shaped

RE - solid round conductor

Cable Factory FKN | 2012

NY2Y, NAY2Y
Power Cable PVC insulation and PE sheath Rated Voltage: U0/U - 0.6/1 kV Standard:DIN VDE 0276/HD603; IEC 60502-1

Low Voltage Power Cables

Construction data: NAY2Y


Nominal Cross Section No x mm Shape Overall Diameter (Approx.) max.mm

U0/U - 0.6/1kV
Total Weight (Approx.) kg/km
2

Al weight (Approx.) kg/km

Packing: Cable coil or Drum m or N/m

with signal wire - 2.5 mm . 4x16+2,5 4x25+2,5 4x35+2,5 4x50+2,5 4x70+2,5 4x95+2,5 4x120+2,5 4x150+2,5 4x185+2,5 4x240+2,5 RM+RE RM+RE RM+RE SM+RE SM+RE SM+RE SM+RE SM+RE SM+RE SM+RE 23,0 27,0 29,0 32,0 36,0 40,0 44,0 49,0 54,0 61,0 186,0 290,0 406,0 580,0 812,0 1102,0 1392,0 1740,0 2146,0 2784,0 665,0 1325,0 1164,0 1290,0 1740,0 2220 2700,0 3315,0 3960,0 5065,0 14/1000 16/1000 16/1000 18/1000 16/500 16/500 18/500 20/500 20/500 24/500

without signal wire 4x16 4x25 4x35 4x50 4x70 4x95 4x120 4x150 4x185 4x240 RM RM RM SM SM SM SM SM SM SM 23,0 27,0 29,0 32,0 36,0 40,0 44,0 49,0 54,0 61,0 186,0 290,0 406,0 580,0 812,0 1102,0 1392,0 1740,0 2146,0 2784,0 645,0 1295,0 1132,0 1270,0 1720,0 2190,0 2665,0 3295,0 3930,0 5035,0 14/1000 16/1000 16/1000 18/1000 16/500 16/500 18/500 20/500 20/500 24/500

*other dimensions and packing length are available on request.

Cable Factory FKN | 2012

N2XY, NA2XY, N2X2Y, NA2X2Y


Power cable with XLPE insulation and PVC or PE sheath Rated Voltage: U0/U - 0.6/1 kV Standard: VDE 0276/HD603 tip 5G-2; IEC 60502-1

Low Voltage Power Cables

Application The power cables with insulation of cross-linked polyethylene (XLPE) are designed for distribution and supply of consumers with nominal voltage 0.6/1 kV and frequency 50 Hz in industrial installations and urban networks. They are suitable for fixed indoor assembly in cable ducts and conduits, over shelves and grilles, directly underground in ditch and outdoor under shelters providing the conditions determined for the type of cable.
Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 Core temperature, max: 90oC in operation Max. short circuit temperature: 250 oC , not more than 5 sec Rated voltage U0 /U(Umax ): 0.6/1(1.2) kV Test voltage: AC - 4 kV (3.5kV by IEC); 50 Hz Temperature range: flexing: -5C to +50C stationary: -30C to +90C Bending radius, min. for single-core: 15xDcable for multi-core: 12xDcable Specific insulation resistance at 90C: min, 1014 x cm Max. permessible tensile stress with cable grip: For Cu conducor = 50 N/mm For Al conducor = 30 N/mm2
2

Cable Structure:
Conductor: solid or multi-strand Cu or Al wires class 1, 2 or (5) acc. VDE 0295 (IEC 60228)

Insulation: XLPE type DIX3 acc. to VDE 0276-603/5G Core identification: according to VDE 0293 (HD 308) Signal-command copper core: Cores assembly: Additional, cross section 2,5mm2, red coloured (black coloured 1,5mm2 on request) cores stranded concentrically (cores stranded in concentric layers, for signal)

Wrapping: paper tape Inner covering: rubber filling compound Sheath: PVC type DMV6 acc. to VDE 0276-603/sec.1 or PE HDPE mass, type DMP2 acc. DIN VDE 0276/HD603

Color of sheath: black

Additional information and technical data Available conductor sizes for power distibution:
Number of cores size of Cu conductors 1 core: 4mm2 - 630mm2 2 cores: 1.5mm2 - 120mm2 3 cores: 1.5mm2 - 300mm2 4 cores: 1.5mm2 - 300mm2 3 cores + 1 earth core: 25mm2 - 300mm2 / + 16mm2 - 150mm2 5 cores: 1.5mm2 - 300mm2 Number of cores size of Cu conductors 2 over 7 cores (class 5) (1.5 - 2.5 )mm 7 -19 cores: (1.5 - 4 ) RE; RM over 19 cores (1.5 - 2.5 ) RE; RM size of Al conductors 25mm2 - 630mm2 25mm2 - 120mm2 25mm2 - 240mm2 25mm2 - 240mm2 25mm2 - 240mm2 / + 16mm2 - 120mm2 25mm2 - 300mm2 size of Al conductors / / /

Available conductor sizes for signaling and control

*other dimensions and packing length are available on request.

Packing
Standard packing length on wooden drums: (500m; 1000m)

RM - mutliwire round shaped


Copper: 1.5mm - 630mm Copper: 35mm - 300mm Aluminium: 50mm - 630mm Aluminium: 50mm - 240mm

SM - mutliwire sector shaped

On request:
- Fire propagation acc. IEC 60332-3 - Hydrocarbon resistant outer sheath (RH). - Termite and rodents protected outer sheath. - Oil resistant outer sheath.

RE - solid round conductor

Cable Factory FKN | 2012

N2XY, NA2XY, N2X2Y, NA2X2Y


Power cable with XLPE insulation and PVC or PE sheath Rated Voltage: U0/U - 0.6/1 kV Standard: VDE 0276/HD603 tip 5G-2; IEC 60502-1

Low Voltage Power Cables

C o n s t r u c t io n
N u m b e r o f co re s x N o m in a l C r o s s S e c t io n N o x m m 1 x 4 1 x 6 1 x 1 0 1 x 1 6 1 x 2 5 1 x 3 5 1 x 5 0 1 x 7 0 1 x 9 5 1 x 1 2 0 1 x 1 5 0 1 x 1 8 5 1 x 2 4 0 1 x 3 0 0 R E R E R E R E R M R M R M R M R M R M R M R M R M R M S h a p e

d a ta : N 2 X Y

U 0 / U

- 0 .6 / 1 k V
To ta l W e ig h t (A p p ro x . ) kg /km 7 4 ,0 9 6 ,0 1 4 2 ,0 2 0 5 ,0 3 0 2 ,0 4 0 0 5 2 6 ,0 7 5 0 ,0 1 0 0 0 ,0 1 2 4 0 ,0 1 5 5 0 ,0 1 8 9 0 ,0 2 4 3 0 ,0 3 0 1 5 ,0 P a c k in g : C a b le c o il o r D r u m m o r N /m 1 0 0 1 0 0 1 0 0 8 /1 0 0 0 9 /1 0 0 0 9 /1 0 0 0 9 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0

O v e r a ll D ia m e t e r (A p p ro x . ) m a x .m m 6 ,5 7 ,0 8 ,0 9 ,0 1 1 ,0 1 2 ,0 1 3 ,0 1 6 ,0 1 7 ,0 1 8 ,5 2 1 ,0 2 3 ,0 2 6 ,0 2 8 ,0

C o p p e r ( o r A l) w e ig h t (A p p ro x . ) kg /km 3 8 ,0 5 8 ,0 9 6 ,0 1 5 4 ,0 2 4 0 ,0 3 3 6 ,0 4 8 0 ,0 6 7 2 ,0 9 1 2 ,0 1 1 5 0 ,0 1 4 4 0 ,0 1 7 7 6 ,0 2 3 0 4 ,0 2 8 8 0 ,0

3 x 1 .5 3 x 2 .5 3 x 4 3 x 6 3 x 1 0 3 x 1 6

R E R E R E R E R E R E

1 0 ,0 1 1 ,0 1 2 ,0 1 3 ,0 1 5 ,0 1 7 ,0

4 3 ,0 7 2 ,0 1 1 5 ,0 1 7 3 ,0 2 8 8 ,0 4 6 1 ,0

1 4 2 ,0 1 8 3 ,0 2 4 2 ,0 3 2 0 ,0 4 8 0 ,0 7 0 0 ,0

8 /1 0 0 0 9 /1 0 0 0 9 /1 0 0 0 9 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0

3 x 2 5 /1 6 3 x 3 5 /1 6 3 x 5 0 /2 5 3 x 7 0 /3 5 3 x 9 5 /5 0

R M /R M S M /R M S M /R M S M /S M S M /S M

2 1 ,0 2 6 ,0 2 9 3 1 ,0 3 7 ,0

8 7 4 ,0 1 1 6 2 ,0 1 6 8 0 ,0 2 3 5 2 ,0 3 2 1 6 ,0

1 2 3 0 ,0 1 4 5 0 ,0 1 9 5 5 ,0 2 7 2 0 ,0 3 7 5 6 ,0

1 4 /1 0 0 0 1 6 /1 0 0 0 1 4 /5 0 0 1 4 /5 0 0 1 6 /5 0 0

4 x 1 .5 4 x 2 .5 4 x 4 4 x 6 4 x 1 0 4 x 1 6 4 x 2 5 4 x 3 5 4 x 5 0 4 x 7 0 4 x 9 5 4 x 1 2 0 4 x 1 5 0 4 x 1 8 5 4 x 2 4 0

R E R E R E R E R E R E R M S M S M S M S M S M S M S M S M

1 1 ,0 1 2 ,0 1 3 ,0 1 4 ,0 1 6 ,0 1 9 ,0 2 2 2 7 ,0 3 0 ,0 3 4 ,0 3 8 ,0 4 3 ,0 4 7 ,0 5 2 ,0 5 8 ,0

5 8 ,0 9 6 ,0 1 5 4 ,0 2 3 0 ,0 3 8 4 ,0 6 1 4 ,0 9 6 0 ,0 1 3 4 4 ,0 1 9 2 0 ,0 2 6 8 8 ,0 3 6 4 8 ,0 4 6 0 8 ,0 5 7 6 0 ,0 7 1 0 4 ,0 9 2 1 0 ,0

1 6 5 ,0 2 1 6 ,0 2 9 0 ,0 3 8 5 ,0 5 9 0 ,0 8 6 4 ,0 1 2 9 3 ,0 1 7 5 0 ,0 2 3 0 0 ,0 3 2 8 0 ,0 4 3 0 0 ,0 5 4 1 6 ,0 6 7 0 0 ,0 8 2 0 0 ,0 1 0 5 6 0 ,0

9 /1 0 0 0 9 /1 0 0 0 9 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 4 /5 0 0 1 4 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 8 /5 0 0 2 0 /5 0 0 2 2 /5 0 0

5 x 1 .5 5 x 2 .5 5 x 4 5 x 6 5 x 1 0 5 x 1 6 5 x 2 5
C
4 x 1 6 + 4 x 2 5 + 4 x 3 5 + 4 x 5 0 + 4 x 7 0 + 4 x 9 5 + 4 x 1 2 0 + 4 x 1 5 0 + 4 x 1 8 5 + 4 x 2 4 0 + 4 x 1 6 4 x 2 5 4 x 3 5 4 x 5 0 4 x 7 0 4 x 9 5 4 x 1 2 0 4 x 1 5 0 4 x 1 8 5 4 x 2 4 0 1 . 5 1 . 5 1 . 5 1 . 5 1 . 5 1 . 5 1 . 5 1 . 5 1 . 5 1 . 5

R E R E R E R E R E R E R M
o
R R R

1 2 ,0 1 2 ,5 1 4 ,0 1 5 ,0 1 8 ,0 2 1 ,0 2 5 ,0
c t i o n d
2 4 2 7 , 0 3 0 , 0 3 5 , 0 3 9 , 0 4 3 , 0 4 7 , 0 5 2 , 0 5 8 , 0 2 1 , 0 2 4 2 7 , 0 3 0 , 0 3 5 , 0 3 9 , 0 4 3 , 0 4 7 , 0 5 2 , 0 5 8 , 0

7 2 ,0 1 2 0 ,0 1 9 2 ,0 2 8 8 ,0 4 8 0 ,0 7 6 8 ,0 1 2 0 0 ,0
t a : N A 2 X Y
1 8 6 , 0 2 9 0 , 0 4 0 6 , 0 5 8 0 , 0 8 1 2 , 0 1 1 0 2 , 0 1 3 9 2 , 0 1 7 4 0 , 0 2 1 4 6 , 0 2 7 8 4 , 0 1 8 6 , 0 2 9 0 , 0 4 0 6 , 0 5 8 0 , 0 8 1 2 , 0 1 1 0 2 , 0 1 3 9 2 , 0 1 7 4 0 , 0 2 1 4 6 , 0 2 7 8 4 , 0

1 9 3 ,0 2 5 2 ,0 3 4 0 ,0 4 6 0 ,0 8 4 0 ,0 1 0 4 0 ,0 1 5 6 0 ,0
U 0 / U 0 . 6 / 1 k V
5 9 6 , 0 8 2 0 , 0 1 0 3 3 , 0 1 1 3 7 , 0 1 5 6 8 , 0 1 9 4 6 , 0 2 4 3 6 2 9 7 3 , 0 3 5 9 2 , 0 4 5 7 3 , 0 5 7 0 , 0 7 9 4 , 0 8 7 4 , 0 1 1 1 0 , 0 1 5 4 0 , 0 1 9 2 0 , 0 2 4 1 0 , 0 2 9 4 6 , 0 3 5 6 5 , 0 4 5 4 5 , 0

9 /1 0 0 0 9 /1 0 0 0 1 0 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0
1 4 / 1 0 0 0 1 4 / 1 0 0 0 1 6 / 1 0 0 0 1 4 / 5 0 0 1 6 / 5 0 0 1 6 / 5 0 0 1 6 / 5 0 0 1 8 / 5 0 0 2 0 / 5 0 0 2 2 / 5 0 0 1 4 / 1 0 0 0 1 4 / 1 0 0 0 1 6 / 1 0 0 0 1 4 / 5 0 0 1 6 / 5 0 0 1 6 / 5 0 0 1 6 / 5 0 0 1 8 / 5 0 0 2 0 / 5 0 0 2 2 / 5 0 0

n
M M

s t r u
R R R R R R R R R R E M E E E E E E E E E E + + + + + + + + + R R

E +

2 1 , 0

S M S M S M S M S M S M S M

S M S M S M S M S M S M S M S M

*other dimensions and packing length are available on request.

Cable Factory FKN | 2012

N2XYRY, NA2XYRY
Power cable with XLPE insulation, steel wire armor, PVC sheath Rated Voltage: U0/U - 0.6/1 kV Standard: IEC 60502-1; BS 5467

Low Voltage Power Cables

Application These power and control armoured cables are designed for open air installation, for direct burrial underground, in wet ambient, in cable ducts, power stations, for industry and distribution boards or subscriber networks, where mechanical damages to the cable may occur.

Technical Data:
Conductor resistance at 20 C: according to IEC 60228 Core temperature, max: 90oC in operation Max. short circuit temperature: 250 oC , not more than 5 sec Rated voltage U0 /U(Umax ): 0.6/1(1.2)kV Test voltage: AC - 3.5 kV; 50 Hz Service temperature: -20C to +90C Temperature of exploitation: -30C to +50C Min. laying temperature: -5C Specific insulation resistance at 90C: min. 1014 x cm P = D2 9 N/mm2 Max. permessible tensile stress with cable grip: D = Cable diameter (mm) Bending radius, min. 8xDcable
o

Cable Structure:
Conductor: solid or multi-strand Cu or Al wires class 1 or class 2, in class 5 acc. IEC 60228

Insulation: XLPE Core identification: according to HD 308 Core assembly: cores stranded concentrically (cores stranded in concentric layers, for signal)

Inner sheat: extruded PVC A rmour: for single-core: aluminium round wires - N2XYR(AL)Y for multi-core: galvanized round steel wires Optional armour: Armour of galvanized flat steel wires and optional contra spiral galvanized steel tape

Sheath: PVC , black color

Additional information and technical data Available conductor sizes for power distibution:
Number of cores size of Cu conductors 1 core: 4mm2 - 630mm2 2 cores: 1.5mm2 - 120mm2 3 cores: 1.5mm2 - 300mm2 4 cores: 1.5mm - 300mm
2 2

size of Al conductors 25mm2 - 630mm2 25mm2 - 120mm2 25mm2 - 240mm2 25mm2 - 240mm2 25mm2 - 240mm2 / + 16mm2 - 120mm2 25mm2 - 185mm2 size of Al conductors / / /

3 cores / + 1 earth core: 25mm2 - 300mm2 / + 16mm2 - 150mm2 5 cores: 1.5mm2 - 185mm2

Available conductor sizes for signaling and control


Number of cores size of Cu conductors 2 over 7 cores (class 5) (1.5 - 2.5 )mm 7 -19 cores: (1.5 - 4 ) RE; RM over 19 cores (1.5 - 2.5 ) RE; RM

*other dimensions and packing length are available on request.

Packing
Standard packing length on wooden drums: (500m; 1000m)

RM - mutliwire round shaped


Copper: 1.5mm - 630mm Copper: 35mm - 300mm Aluminium: 50mm - 630mm Aluminium: 50mm - 240mm

SM - mutliwire sector shaped

On request:
- Fire propagation acc. IEC 60332-3 - Hydrocarbon resistant outer sheath (RH). - Termite and rodents protected outer sheath. - Oil resistant outer sheath.

RE - solid round conductor

Cable Factory FKN | 2012

N2XYRY, NA2XYRY
Power cable with XLPE insulation, steel wire armor, PVC sheath Rated Voltage: U0/U - 0.6/1 kV Standard: IEC 60502-1; BS 5467

Low Voltage Power Cables

C o n s t r u ct io n d a t a : N 2 X Y R Y
N u m b e r o f c o r e s x N o m in a l C r o s s S e c t io n No x mm Shape O v e r a ll D ia m e t e r ( A p p r o x . ) max .mm kg /km

U 0 / U - 0 .6 / 1 k V
Tota l W e ig h t ( A p p r o x . ) kg /km P a c k in g : C a b le c o il o r D r u m m o r N /m

C o p p e r w e ig h t ( A p p r o x . )

N 2 X Y R ( A L ) Y - a r m o u r w it h a lu m in iu m r o o u n d w ir e s 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 RM RM RM RM RM RM RM RM RM 17,5 19,0 21,0 23,0 24,5 26,2 30,0 32,3 37,0 480,0 672,0 912,0 1152,0 1440,0 1776,0 2304,0 2880,0 3840,0 742,0 975,0 1277,0 1547,0 1860,0 2268,0 2952,0 3434,0 4738,0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0 1 8 /1 0 0 0 2 0 /1 0 0 0

N 2 X Y R Y - a r m o u r w it h g a lv a n iz e d s t e ll w ir e s 2x 1.5 2x 2.5 2x 4.0 2x 6.0 2x10 2x16 2x25 RE RE RE RE RE RE RM 13,0 14,0 14,5 17,5 18,5 20,5 24,5 28,8 48,0 76,8 115,2 192,0 307,0 480,0 397,0 455,0 524,0 715,0 869,0 1102,0 1637,0 9 /1 0 0 0 1 0 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0

N 2 X Y R Y - a r m o u r w it h g a lv a n iz e d s t e ll w ir e s 3x 1.5 3x 2.5 3x 4.0 3x 6.0 3x10 3x16 3x25 3x35 3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300 RE RE RE RE RE RE RM RM SM SM SM SM SM SM SM SM 13,5 14,5 15,5 18,0 19,5 21,5 25,5 30,0 31,0 35,0 38,5 42,5 47,0 51,5 57,0 62,5 43,2 72,0 115,2 172,8 288,0 460,0 720,0 1008,0 1440,0 2016,0 2736,0 3456,0 4320,0 5328,0 6912,0 11520,0 429,0 498,0 583,0 800,0 996,0 1287,0 1918,0 2602,0 2771,0 3826,0 4849,0 6158,0 7356,0 8914,0 11082,0 13366,0 1 0 /1 0 0 0 1 0 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 4 /5 0 0 1 4 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 8 /5 0 0 2 0 /5 0 0 2 2 /5 0 0 2 4 /5 0 0

N 2 X Y R Y - a r m o u r w it h g a lv a n iz e d s t e ll w ir e s 3x25+ 16 3x35+ 16 3x50+ 25 3x70+ 35 3x95+ 50 3x120+ 70 3x150+ 70 3x185+ 95 3x240+ 120 3x300+ 150 R M /R M R M /R M S M /R M S M /S M S M /S M S M /S M S M /S M S M /S M S M /S M S M /S M 26,5 31,0 35,5 38,5 44,0 48,0 53,0 58,0 65,5 71,5 873,0 1161,0 1680,0 2352,0 3216,0 4128,0 4992,0 6240,0 8064,0 12960,0 2135,0 2793,0 3492,0 4414,0 6063,0 7298,0 8586,0 10409,0 12960,0 15497,0 1 6 /1 0 0 0 1 4 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 8 /5 0 0 1 8 /5 0 0 2 2 /5 0 0 2 4 /5 0 0 2 4 /5 0 0 2 4 /4 5 0

N 2 X Y R Y - a r m o u r w it h g a lv a n iz e d s t e ll w ir e s 4x 1.5 4x 2.5 4x 4.0 4x 6.0 4x10 4x16 4x25 4x35 4x50 4x70 4x95
4x120 4x150 4x185 4x240 4x300

RE RE RE RE RE RE RM RM SM SM SM
SM SM SM SM SM

14,0 15,0 16,0 19,0 21,0 23,5 27,5 33,0 35,5 38,5 44,0
48,0 53,0 58,0 65,5 74,0

57,6 96,0 153,6 230,4 384,0 614,0 960,0 1344,0 1920,0 2688,0 3648,0
4608,0 5760,0 7104,0 9216,0 11520,0

466,0 556,0 657,0 906,0 1160,0 1669,0 2289,0 3153,0 3725,0 4759,0 6550,0
7817,0 9386,0 11342,0 14230,0 18205,0

1 0 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 4 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 8 /5 0 0
1 8 /5 0 0 2 0 /5 0 0 2 2 /5 0 0 2 4 /5 0 0 2 4 /4 5 0

*other dimensions and packing length are available on request.

Cable Factory FKN | 2012

N2XCY, NA2XCY
Power cable with XLPE insulation. concentric conductor and PVC sheath Rated Voltage: U0/U - 0.6/1 kV Standard: VDE 0276/HD603; IEC 60502-1

Low Voltage Power Cables

Application The power cables with insulation of cross-linked polyethylene (XLPE) are designed for distribution and supply of consumers with nominal voltage 0.6/1 kV and frequency 50 Hz in industrial installations and urban networks. They are suitable for fixed indoor assembly in cable ducts and conduits, over shelves and grilles, directly underground in ditch and outdoor under shelters providing the conditions determined for the type of cable.
Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 Core temperature, max: 90oC in operation Max. short circuit temperature: 250 oC , not more than 5 sec Rated voltage U0 /U(Umax ): 0.6/1(1.2) kV Test voltage: AC - 4 kV (3.5kV by IEC); 50 Hz Temperature range: flexing: -5C to +50C stationary: -30C to +90C Bending radius, min. for single-core: 15xDcable for multi-core: 12xDcable Specific insulation resistance at 90C: min, 10 x cm For Cu conducor = 50 N/mm2 Max. permessible tensile stress with cable grip: For Al conducor = 30 N/mm2
14

Cable Structure:
Conductor: solid or multi-strand Cu or Al wires class 1, 2 or (5) acc. VDE 0295 (IEC 60228)

Insulation: XLPE type DIX3 acc. to VDE 0276-603/5G Core identification: according to VDE 0293 (HD 308) Signal-command copper core: Cores assembly: Additional, cross section 2,5mm2, red coloured (black coloured 1,5mm2 on request) cores stranded concentrically (cores stranded in concentric layers, for signal)

Wrapping: paper tape Inner covering: rubber filling compound Concentric conductor: helicoidaly copper wires and one copper tape around inner covering

Sheath: PVC type DMV6 acc. to VDE 0276-603/sec.1 Color of sheath: black

Additional information and technical data


Available conductor sizes for power distibution:
Number of cores size of Cu conductors 1 core: 4mm2 - 500mm2 2 cores: 1.5mm2 - 120mm2 3 cores: 1.5mm2 - 300mm2 4 cores: 1.5mm - 300mm 3 cores+1 earth core: 25mm2 - 300mm2 / + 16mm2 - 150mm2 5 cores: 1.5mm2 - 120mm2
2 2

size of Al conductors 25mm2 - 500mm2 25mm2 - 120mm2 25mm2 - 240mm2 25mm2 - 240mm2 25mm2 - 240mm2 / + 16mm2 - 120mm2 25mm2 - 120mm2 1,5mm2 - 240mm2 size of Al conductors / / /

Available sizes for concentric copper conductor:


nominal cross-section 1,5mm2 - 240mm2 Number of cores size of Cu conductors over 7 cores (class 5) (1.5 - 2.5 )mm2 7 -19 cores: (1.5 - 4 ) RE; RM over 19 cores (1.5 - 2.5 ) RE; RM

Available conductor sizes for signaling and control:

*other dimensions and packing length are available on request.

Packing
Standard packing length on wooden drums: (500m; 1000m)

RM - mutliwire round shaped


Copper: 1.5mm - 630mm Copper: 35mm - 300mm Aluminium: 50mm - 630mm Aluminium: 50mm - 240mm

SM - mutliwire sector shaped

On request:
- Fire propagation acc. IEC 60332-3 - Hydrocarbon resistant outer sheath (RH). - Termite and rodents protected outer sheath. - Oil resistant outer sheath.

RE - solid round conductor

Cable Factory FKN | 2012

N2XCY, NA2XCY
Power cable with XLPE insulation. concentric conductor and PVC sheath Rated Voltage: U0/U - 0.6/1 kV Standard: VDE 0276/HD603; IEC 60502-1

Low Voltage Power Cables

C o n st ru ct io n d a t a : N 2 X C Y
Num b e r o f c o r e s x No m ina l C r o s s S e ctio n No x m m 1 x1 .5 /1 .5 1 x2 .5 /2 .5 1 x4 /4 1 x6 /6 1 x1 0 /1 0 1 x1 6 /1 6 1 x2 5 /1 6 1 x3 5 /1 6 1 x5 0 /2 5 1 x7 0 /3 5 1 x9 5 /5 0 1 x1 2 0 /7 0 1 x1 5 0 /7 0 1 x1 8 5 /9 5 1 x2 4 0 /1 2 0 1 x3 0 0 /1 5 0 1 x4 0 0 /1 8 5 2 x1 .5 /1 .5 2 x2 .5 /2 .5 2 x4 .0 /4 .0 2 x6 .0 /6 .0 2 x1 0 /1 0 2 x1 6 /1 6 2 x2 5 /1 6 2 x3 5 /1 6 2 x5 0 /2 5 2 x7 0 /3 5 2 x9 5 /5 0 2 x1 2 0 /7 0 2 x1 5 0 /7 0 3 x1 .5 /1 .5 3 x2 .5 /2 .5 3 x4 .0 /4 .0 3 x6 .0 /6 .0 3 x1 0 /1 0 3 x1 6 /1 6 3 x2 5 /1 6 3 x3 5 /1 6 3 x5 0 /2 5 3 x7 0 /3 5 3 x9 5 /5 0 3 x1 2 0 /7 0 3 x1 5 0 /7 0 3 x1 8 5 /9 5 3 x2 4 0 /1 2 0 3 x3 0 0 /1 5 0 4 x1 .5 /1 .5 4 x2 .5 /2 .5 4 x4 .0 /4 .0 4 x6 .0 /6 .0 4 x1 0 /1 0 4 x1 6 /1 6 4 x2 5 /1 6 4 x3 5 /1 6 4 x5 0 /2 5 4 x7 0 /3 5 4 x9 5 /5 0
4 x1 2 0 /7 0 4 x1 5 0 /7 0 4 x1 8 5 /9 5 4 x2 4 0 /1 2 0 4 x3 0 0 /1 5 0

U 0 / U - 0 .6 / 1 k V
T o ta l W e ig ht (A p p r o x.) kg /km 1 2 0 ,0 1 4 3 ,0 1 8 0 ,0 2 2 6 ,0 3 2 2 ,0 4 5 6 ,0 5 8 0 ,0 6 8 9 ,0 9 4 5 ,0 1 2 7 9 ,0 1 6 9 6 ,0 2 1 6 7 ,0 2 4 5 9 ,0 3 1 1 8 ,0 3 9 8 6 ,0 4 8 6 6 ,0 6 1 7 9 ,0 2 0 9 ,0 2 5 3 ,0 3 2 2 ,0 4 0 7 ,0 5 7 8 ,0 8 1 1 ,0 1 0 9 1 ,0 1 3 5 9 ,0 1 7 2 8 ,0 2 3 8 1 ,0 3 2 0 9 ,0 4 0 4 6 ,0 4 7 9 7 ,0 2 3 1 ,0 2 8 6 ,0 3 6 8 ,0 4 7 2 ,0 6 8 3 ,0 9 7 0 ,0 1 3 3 5 ,0 1 6 9 2 ,0 2 0 3 4 ,0 2 8 5 8 ,0 3 8 2 4 ,0 4 8 0 2 ,0 5 7 8 6 ,0 7 2 2 9 ,0 9 3 6 4 ,0 1 1 5 5 2 ,0 2 6 5 ,0 3 3 3 ,0 4 3 0 ,0 5 5 4 ,0 8 1 8 ,0 1 1 6 6 ,0 1 6 3 3 ,0 2 0 9 4 ,0 2 5 7 3 ,0 3 6 2 3 ,0 4 8 5 7 ,0
6 1 5 5 ,0 7 4 1 1 ,0 9 2 2 6 ,0 1 1 9 5 0 ,0 1 4 7 5 5 ,0

S ha p e

O ve r a ll Dia m e te r (A p p r o x.) m a x.m m 9 ,7 1 0 ,2 1 0 ,8 1 1 ,3 1 2 ,4 1 3 ,8 1 5 ,5 1 6 ,6 1 8 ,8 2 1 ,0 2 3 ,5 2 6 ,0 2 8 ,0 3 0 ,5 3 4 ,0 3 7 ,0 4 1 ,0 1 3 ,0 1 3 ,9 1 5 ,0 1 6 ,2 1 8 ,1 2 1 ,0 2 4 ,0 2 6 ,0 2 9 ,5 3 3 ,0 3 7 ,5 4 2 ,0 4 6 ,0 1 3 ,5 1 4 ,5 1 5 ,7 1 6 ,9 1 9 ,0 2 2 ,0 2 5 ,0 2 7 ,5 3 0 ,0 3 4 ,0 3 7 ,5 4 1 ,5 4 6 ,5 5 1 ,0 5 7 ,5 6 2 ,5 1 4 ,3 1 5 ,4 1 6 ,8 1 8 ,1 2 0 ,5 2 3 ,5 2 7 ,5 3 0 ,0 3 3 ,5 3 8 ,5 4 2 ,5


4 8 ,0 5 4 ,0 5 8 ,5 6 5 ,5 7 1 ,5

C o p p e r w e ig h t (A p p r o x.) kg /km 4 4 ,0 6 1 ,0 8 6 ,0 1 2 4 ,0 2 0 1 ,0 3 0 7 ,0 3 9 3 ,6 4 8 9 ,6 7 2 0 ,0 1 0 0 8 ,0 1 3 9 2 ,0 1 8 2 4 ,0 2 1 1 2 ,0 2 6 8 8 ,0 3 4 5 6 ,0 4 3 2 0 ,0 5 6 1 6 ,0 6 0 ,0 8 5 ,0 1 2 5 ,0 1 8 2 ,0 2 9 2 ,0 4 6 1 ,0 6 3 3 ,0 8 2 5 ,0 1 2 0 0 ,0 1 6 8 0 ,0 2 3 0 4 ,0 2 9 7 6 ,0 3 5 5 2 ,0 8 0 ,0 1 0 9 ,0 1 5 5 ,0 2 4 0 ,0 3 8 4 ,0 6 1 0 ,0 8 7 0 ,0 1 1 6 2 ,0 1 6 8 0 ,0 2 3 5 2 ,0 3 2 1 6 ,0 4 1 2 8 ,0 4 9 9 2 ,0 6 2 4 0 ,0 8 0 6 4 ,0 1 0 0 8 0 ,0 9 4 ,0 1 3 3 ,0 1 9 5 ,0 2 9 9 ,0 4 8 0 ,0 7 6 6 ,0 1 1 1 2 ,0 1 5 1 5 ,0 2 1 5 6 ,0 3 0 7 0 ,0 4 2 0 0 ,0
5 2 7 5 ,0 6 6 9 0 ,0 8 0 3 0 ,0 1 0 3 6 8 ,0 1 2 9 6 0 ,0

P a c king : C a b le co il o r Dr um m o r N/m 8 /1 0 0 0 8 /1 0 0 0 9 /1 0 0 0 9 /1 0 0 0 9 /1 0 0 0 1 0 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0 1 8 /1 0 0 0 1 8 /1 0 0 0 1 6 /5 0 0 1 6 /5 0 0 9 /1 0 0 0 1 0 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0 1 4 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 8 /5 0 0 9 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0 1 4 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 8 /5 0 0 2 0 /5 0 0 2 2 /5 0 0 2 4 /5 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 4 /5 0 0 1 4 /5 0 0 1 6 /5 0 0 1 6 /5 0 0
1 8 /5 0 0 2 0 /5 0 0 2 2 /5 0 0 2 4 /5 0 0 2 4 /5 0 0

RE RE RE RE RE RM RM RM RM RM RM RM RM RM RM RM RM RE RE RE RE RE RM RM RM RM RM RM RM RM RE RE RE RE RE RM RM RM SM SM SM SM SM SM SM SM RE RE RE RE RE RE RM RM SM SM SM
SM SM SM SM SM

*other dimensions and packing length are available on request.

Cable Factory FKN | 2012

N2XBY, NA2XBY
Power cable with XLPE insulation, double steel tapes armoured, PVC sheath Rated Voltage: U0/U - 0.6/1 kV Standard: DIN VDE 0271; IEC 60502-1

Low Voltage Power Cables

Application These power and control armoured cables are designed for open air installation, for direct burrial underground, in wet ambient, in cable ducts, power stations, for industry and distribution boards or subscriber networks, where mechanical damages to the cable may occur.
Technical Data: Conductor resistance at 20o C: Core temperature, max: Max. short circuit temperature: Rated voltage U0 /U(Umax ): Test voltage: Service temperature: Temperature of exploitation: Min. laying temperature: according to IEC 60228 90 C in operation 250 C , not more than 5 sec 0.6/1(1.2)kV AC - 3.5 kV; 50 Hz -20C to +90C -30C to +50C -5C
2 2 o o

Cable Structure:
Conductor: solid or multi-strand Cu or Al wires class 1 or class 2, in same case class 5 acc. IEC 60228

Insulation: XLPE Core identification: according to HD 308 Core assembly: cores stranded concentrically (cores stranded in concentric layers, for signal)

Inner sheat: extruded PVC Armour: for multi-core: double steel tapes for single-core: doube aluminium tapes - N2XB(AL)Y Sheat: PVC, black color

Specific insulation resistance at 90C: in. 1014 x cm m P = D 3 N/mm Max. permessible tensile stress with cable grip: D = Cable diameter (mm) Bending radius, min. 8xDcable

Additional information and technical data Available conductor sizes for power distibution:
Number of cores size of Cu conductors 1 core: 4mm2 - 630mm2 2 cores: 1.5mm2 - 240mm2 3 cores: 1.5mm2 - 300mm2 4 cores: 1.5mm2 - 300mm2 3 cores /+ 1 earth core: 25mm2 - 300mm2 / + 16mm2 - 150mm2 5 cores: 1.5mm2 - 185mm2 size of Al conductors 25mm2 - 630mm2 25mm2 - 240mm2 25mm2 - 240mm2 25mm2 - 240mm2 25mm2 - 240mm2 / + 16mm2 - 120mm2 25mm2 - 185mm2 size of Al conductors / / /
RM - mutliwire round shaped
Copper: 1.5mm - 630mm Aluminium: 50mm - 630mm Aluminium: 50mm - 240mm

Available conductor sizes for signaling and control


Number of cores size of Cu conductors 2 over 7 cores (class 5) (1.5 - 2.5 )mm 7 -19 cores: (1.5 - 4 ) RE; RM over 19 cores (1.5 - 2.5 ) RE; RM *other dimensions and packing length are available on request.

Packing
Standard packing length on wooden drums: (500m; 1000m)

SM - mutliwire sector shaped


Copper: 35mm - 300mm

On request:
- Fire propagation acc. IEC 60332-3 - Hydrocarbon resistant outer sheath (RH). - Termite and rodents protected outer sheath. - Oil resistant outer sheath.

RE - solid round conductor

Cable Factory FKN | 2012

N2XBY, NA2XBY
Power cable with XLPE insulation, double steel tapes armoured, PVC sheath Rated Voltage: U0/U - 0.6/1 kV Standard: DIN VDE 0271; IEC 60502-1

Low Voltage Power Cables

C o n s t r u c t io n d a t a : N 2 X B Y
Num ber of cores x N o m in a l C r o s s S e c tio n No x m m 1 x1 6 1 x2 5 1 x3 5 1 x5 0 1 x7 0 1 x9 5 1 x1 2 0 1 x1 5 0 1 x1 8 5 1 x2 4 0 1 x3 0 0 1 x4 0 0 1 x5 0 0 1 x6 3 0 2 x1 .5 2 x2 .5 2 x4 .0 2 x6 .0 2 x1 0 2 x1 6 2 x2 5 2 x3 5 2 x5 0 2 x7 0 2 x9 5 2 x1 2 0 2 x1 5 0 3 x1 .5 3 x2 .5 3 x4 .0 3 x6 .0 3 x1 0 3 x1 6 3 x2 5 3 x3 5 3 x5 0 3 x7 0 3 x9 5 3 x1 2 0 3 x1 5 0 3 x1 8 5 3 x2 4 0 3 x3 0 0 4 x1 .5 4 x2 .5 4 x4 .0 4 x6 .0 4 x1 0 4 x1 6 4 x2 5 4 x3 5 4 x5 0 4 x7 0
4 x9 5 4 x1 2 0 4 x1 5 0 4 x1 8 5 4 x2 4 0 4 x3 0 0

U 0 / U - 0 .6 / 1 k V
T o ta l W e ig h t (A p p r o x.) kg /km 4 0 0 ,0 4 7 5 ,0 5 8 5 ,0 7 5 5 ,0 9 9 5 ,0 1 2 6 0 ,0 1 5 3 0 ,0 1 8 3 0 ,0 2 2 6 5 ,0 2 9 0 0 ,0 3 5 0 0 ,0 4 4 5 0 ,0 5 6 3 0 ,0 7 2 8 0 ,0 3 0 5 ,0 3 2 5 ,0 3 4 4 ,0 4 1 6 ,0 5 5 9 ,0 7 4 0 ,0 1 0 3 5 ,0 1 3 1 4 ,0 1 6 0 5 ,0 2 1 8 0 ,0 2 8 7 5 ,0 3 9 4 9 ,0 4 7 8 9 ,0 3 1 9 ,0 3 4 3 ,0 3 9 5 ,0 4 8 6 ,0 6 6 9 ,0 9 0 3 ,0 1 2 8 4 ,0 1 6 5 2 ,0 1 9 0 8 ,0 2 6 4 3 ,0 3 5 3 5 ,0 4 7 1 8 ,0 5 7 7 5 ,0 7 0 5 5 ,0 9 0 2 4 ,0 1 0 9 9 7 ,0 3 2 8 ,0 3 6 7 ,0 4 6 6 ,0 5 8 0 ,0 8 1 9 ,0 1 1 1 8 ,0 1 6 0 8 ,0 2 0 8 5 ,0 2 4 9 7 ,0 3 4 5 5 ,0
5 0 1 0 ,0 6 1 7 2 ,0 7 5 3 0 ,0 9 1 7 0 ,0 1 1 7 5 2 ,0 1 4 3 4 1 ,0

S hape

O v e r a ll D ia m e te r ( A p p r o x . ) m a x.m m

C o p p e r w e ig h t (A p p r o x.) kg /km 1 5 4 ,0 2 4 0 ,0 3 3 6 ,0 4 8 0 ,0 6 7 2 ,0 9 1 2 ,0 1 1 5 2 ,0 1 4 4 0 ,0 1 7 7 6 ,0 2 3 0 4 ,0 2 8 8 0 ,0 3 8 4 0 ,0 4 8 0 0 ,0 6 0 4 8 ,0 2 8 ,8 4 8 ,0 7 6 ,8 1 1 5 ,2 1 9 2 ,0 3 0 8 ,0 4 8 0 ,0 6 7 2 ,0 9 6 0 ,0 1 3 4 4 ,0 1 8 2 4 ,0 2 3 0 4 ,0 2 8 8 0 ,0 4 3 ,2 7 2 ,0 1 1 5 ,2 1 7 2 ,8 2 8 8 ,0 4 6 2 ,0 7 2 0 ,0 1 0 0 8 ,0 1 4 4 0 ,0 2 0 1 6 ,0 2 7 3 6 ,0 3 4 5 6 ,0 4 3 2 0 ,0 5 3 2 8 ,0 6 9 1 2 ,0 8 6 4 0 ,0 5 7 ,6 9 6 ,0 1 5 3 ,6 2 3 0 ,4 3 8 4 ,0 6 1 6 ,0 9 6 0 ,0 1 3 4 4 ,0 1 9 2 0 ,0 2 6 8 8 ,0
3 6 4 8 ,0 4 6 0 8 ,0 5 7 6 0 ,0 7 1 0 4 ,0 9 2 1 6 ,0 1 1 5 2 0 ,0

P a c k in g : C a b le c o il o r D r u m m o r N/m 1 0 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0 1 8 /1 0 0 0 1 4 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 8 /5 0 0 1 0 /1 0 0 0 1 0 /1 0 0 0 1 0 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 4 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 8 /5 0 0 1 0 /1 0 0 0 1 0 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 2 /5 0 0 1 4 /5 0 0 1 4 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 8 /5 0 0 2 0 /5 0 0 2 2 /5 0 0 2 4 /5 0 0 1 0 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 4 /5 0 0 1 4 /5 0 0 1 6 /5 0 0
1 6 /5 0 0 1 8 /5 0 0 2 0 /5 0 0 2 2 /5 0 0 2 4 /5 0 0 2 4 /5 0 0

N 2 X B(A L)Y (C u /X LP E/P V C /A T A /P V C ) RE RM RM RM RM RM RM RM RM RM RM RM RM RM RE RE RE RE RE RE RM RM RM RM RM RM RM RE RE RE RE RE RE RM RM SM SM SM SM SM SM SM SM RE RE RE RE RE RE RM RM SM SM


SM SM SM SM SM SM

a r m o u r w ith tw o a lu m in iu m ta p e s

1 5 ,4 1 5 ,6 1 6 ,7 1 8 ,5 2 0 ,5 2 2 ,5 2 4 ,0 2 6 ,0 2 8 ,5 3 1 ,5 3 4 ,5 3 8 ,0 4 2 ,5 4 7 ,5 1 4 ,4 1 4 ,4 1 4 ,4 1 5 ,4 1 7 ,4 1 9 ,4 2 2 ,5 2 5 ,0 2 8 ,0 3 2 ,0 3 5 ,5 4 0 ,5 4 5 ,0 1 4 ,4 1 4 ,4 1 5 ,0 1 6 ,2 1 8 ,2 2 0 ,5 2 4 ,0 2 6 ,5 2 8 ,5 3 2 ,5 3 6 ,0 4 1 ,0 4 5 ,5 5 0 ,0 5 6 ,0 6 1 ,0 1 4 ,4 1 4 ,7 1 6 ,0 1 7 ,4 1 9 ,7 2 2 ,5 2 6 ,0 2 9 ,0 3 2 ,5 3 7 ,0
4 2 ,5 4 7 ,5 5 3 ,5 5 7 ,5 6 4 ,0 6 9 ,5

N 2 X BY (C u /X LP E/P V C /S T A /P V C ) -

a r m o u r w ith tw o g a lv a n iz e d s te e l ta p e s

N 2 X BY (C u /X LP E/P V C /S T A /P V C ) -

a r m o u r w ith tw o g a lv a n iz e d s te e l ta p e s

N 2 X BY (C u /X LP E/P V C /S T A /P V C ) -

a r m o u r w ith tw o g a lv a n iz e d s te e l ta p e s

*other dimensions and packing length are available on request.

Cable Factory FKN | 2012

Middle Voltage Power Cables

N2XSY, NA2XSY, N2XS2Y, NA2XS2Y


Cu or Al single-core cables with insulation XLPE and PVC or PE sheath Rated Voltage: U0/U - 3.6/6; 6/10; 8.7/15; 12/20; 18/30; 20/35; 20.8/36kV; Standard:VDE 0276/HD620.S2; IEC 60502-2

Middle Voltage Power Cables

Application For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The good installation properties of this cable make installation easy, even on difficult routes.

Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 class 2 Core temperature, max: 90 C in continuous operation Max. short circuit temperature: 250 oC , not more than 5 sec Overload temperature: 130oC /100h per year max. 3.6/6 kV = max. 7.2 kV 6/10 kV = max. 12 kV 8.7/15 kV = max. 17.5 kV Highest system voltage, Umax 12/20 kV = max. 24 kV 18/30 kV = max. 36 kV 20/35 kV = max. 42kV 20.8/36 kV = max. 42 kV 3.6/6 kV = 12.6 kV 6/10 kV = 21kV Test voltage = 3.5Uo(IEC60502-2); 8.7/15 kV = 30.45 kV 3.5Uo(VDE 0276/HD620) 12/20 kV = 42 kV AC (50Hz) - 5 min 18/30 kV = 63 kV 20/35 kV = 70kV 20.8/36 kV = 72.8 kV Level of partial discharge at 2*Uo: no more than 2pC Bending radius, min 15xDcable Temperature of laying: no less than - 5 oC Dielectric factor of losses, 50 Hz: at 20C, (0.8-3)x10-4 Spec.volume insulation resistance at 20C, min 1015 x cm Intensity of electric field: max. 6.9-5.3 kV/mm Tests: according to IEC 60502-2 or DIN VDE 0276-620 Al cores - 30*S Force of strain in laying, N max. Cu cores - 50*S where: S is cross section of cores in mm2

Cable Structure: Conductor: Cu or Al stranded compacted, according to IEC 60228 and VDE 0295 class 2

Inner semi-conductive layer: semi-conductive XLPE compound around conductor Insulation: XLPE compoundDIX8 as per DIN VDE 0276-620 part 1. Outer semi-conductive layer: semi-conductive XLPE compound around insulation Warapping: Semi-conductive tape helicoidally wrapped Metal screen: Cu wires concentrically laid and one contact of Cu tape with min. thickness of 0.1mm. PE compound type ST7 according to IEC 60502-2 type DMP 2 according to VDE 0276, black color

Optional metal screen: overlapping one or two Cu tapes PE Sheath:

PVC Sheath: PVC mass type DMV6, red (or black) coloured

Available constructions:
Single Al core: 1x(25 - 630)mm2 Single Cu core: 1x(25 - 500)mm2 Standard Cross section of metallic screen for conductor sizes: from 25mm2 to 120 mm2 16mm2 from 150mm2 to 300mm2 25mm2 from 400mm2 to 630mm2 35mm2

Standard shape of conductor RM - class 2 conductor acc. to IEC 60228 and VDE 0295

On Request:
Fire propagation acc. IEC 60332-3 cat.

Packing

Standard packing length on wooden drums: [ 500 m; 1000 m ];

Cable Factory FKN | 2012

N2XSY, NA2XSY, N2XS2Y, NA2XS2Y


Cu or Al single-core cables with insulation XLPE and PVC or PE sheath Rated Voltage: U0/U - 3.6/6; 6/10; 8.7/15; 12/20; 18/30; 20/35; 20.8/36kV; Standard:VDE 0276/HD620.S2; IEC 60502-2

Middle Voltage Power Cables

Construction data: N2XSY, NA2XSY


Number of cores x Nominal Cross Section No x mm 1x25RM/16 1x35RM/16 1x50RM/16 1x70RM/16 1x95RM/16 1x120RM/16 1x150RM/25 1x185RM/25 1x240RM/25 1x300RM/25 1x35RM/16 1x50RM/16 1x70RM/16 1x95RM/16 1x120RM/16 1x150RM/25 1x185RM/25 1x240RM/25 1x300RM/25 1x35RM/16 1x50RM/16 1x70RM/16 1x95RM/16 1x120RM/16 1x150RM/25 1x185RM/25 1x240RM/25 1x300RM/25 1x35RM/16 1x50RM/16 1x70RM/16 1x95RM/16 1x120RM/16 1x150RM/25 1x185RM/25 1x240RM/25 1x300RM/25 1x35RM/16 1x50RM/16 1x70RM/16 1x95RM/16 1x120RM/16 1x150RM/25 1x185RM/25 1x240RM/25 1x300RM/25 1x35RM/16 1x50RM/16 1x70RM/16 1x95RM/16 1x120RM/16 Nominal insulation thickness mm 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 Nominal sheath thickness mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 Overall Diameter (Approx.) max.mm N2XSY 6/10kV 22.4 24.4 25 27 28.2 29.5 31.1 32.6 35.4 37.1 NA2XSY 6/10kV 24.4 25 27 28.2 29.5 31.1 32.6 35.4 37.1 N2XSY 12/20kV 27.8 29.3 31.2 32.5 33.7 35.4 37 40 41.3 NA2XSY 12/20kV 27.8 29.3 31.2 32.5 33.7 35.4 37 40 41.3 N2XSY 20/35kV 34.8 36.4 38.2 39.5 40.7 42.4 43.9 46.7 48.3 NA2XSY 20/35kV 34.8 36.4 38.2 39.5 40.7 182 182 182 182 182 101 145 203 276 348 1230 1340 1480 1610 1730 20/1000 20/1000 20/1000 22/1000 22/1000 518 662 854 1094 1334 1723 2059 2587 3163 1460 1660 1930 2220 2500 2930 3310 3950 4580 20/1000 20/1000 20/1000 22/1000 22/1000 24/1000 24/1000 18/500 20/500 182 182 182 182 182 283 283 283 283 101 145 203 276 348 435 537 696 870 880 970 1090 1200 1310 1530 1680 1920 2150 16/1000 16/1000 18/1000 18/1000 18/1000 20/1000 20/1000 20/1000 22/1000 518 662 854 1094 1334 1723 2059 2587 3163 1100 1290 1540 1810 2080 2500 2870 3470 4080 16/1000 16/1000 18/1000 18/1000 18/1000 20/1000 20/1000 20/1000 22/1000 182 182 182 182 182 283 283 283 283 101 145 203 276 348 435 537 696 870 700 780 890 990 1100 1300 1440 1680 1890 14/1000 16/1000 16/1000 18/1000 9/1000 9/1000 10/1000 12/1000 12/1000 408 518 662 854 1094 1334 1723 2059 2587 3163 800 960 1160 1360 1600 1870 2270 2640 3210 3800 14/1000 14/1000 14/1000 16/1000 16/1000 16/1000 16/1000 18/1000 20/1000 20/1000 Copper weight (Approx.) kg/km Al weight (Approx.) kg/km Total Weight (Approx.) kg/km Packing: Cable coil or Drum m or N/m

* other dimensions for conductor, metallic screen and packing length are available on request.

Cable Factory FKN | 2012

N2XSEY, NA2XSEY, N2XSE2Y, NA2XSE2Y


Cu or Al triple-core cables with insulation XLPE and PVC or PE sheath Rated Voltage: U0/U - 3.6/6; 6/10; 8.7/15; 12/20; 18/30; 20/35; 20.8/36kV; Standard:VDE 0276/HD620.S2; IEC 60502-2

Middle Voltage Power Cables

Application For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The good installation properties of this cable make installation easy, even on difficult routes. Acc. to VDE 0276-603 cables with PVC sheath must be protected against direct sun irradiation and cables with PE sheath with high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation.

Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 class 2 Core temperature, max: 90 C in continuous operation Max. short circuit temperature: 250 C , not more than 5 sec Overload temperature: 130oC /100h per year max. 3.6/6 kV = max. 7.2 kV 6/10 kV = max. 12 kV 8.7/15 kV = max. 17.5 kV Highest system voltage, Umax 12/20 kV = max. 24 kV 18/30 kV = max. 36 kV 20/35 kV = max. 42kV 20.8/36 kV = max. 42 kV 3.6/6 kV = 12.6 kV 6/10 kV = 21kV Test voltage = 3.5Uo(IEC60502-2); 8.7/15 kV = 30.45 kV 3.5Uo(VDE 0276/HD620) 12/20 kV = 42 kV AC (50Hz) - 5 min 18/30 kV = 63 kV 20/35 kV = 70kV 20.8/36 kV = 72.8 kV Level of partial discharge at 2*Uo: no more than 2pC Bending radius, min 15xDcable Temperature of laying: no less than - 5 oC Dielectric factor of losses, 50 Hz: at 20C, (0.8-3)x10-4 Spec.volume insulation resistance at 20C, min 1015 x cm Intensity of electric field: max. 6.9-5.3 kV/mm Tests: according to IEC 60502-2 orDIN VDE 0276-620 Al cores - 30*S*n Force of strain in laying, N max. Cu cores - 50*S*n
o

Cable Structure:
Conductor: Cu or Al stranded compacted, according to IEC 60228 and VDE 0295 class 2

Inner semi-conductive layer: semi-conductive XLPE compound around conductor Insulation: XLPE compoundDIX8 as per DIN VDE 0276-620 part 1. Outer semi-conductive layer: semi-conductive XLPE compound around insulation Warapping: Semi-conductive tape helicoidally wrapped Cu wires concentrically laid and Metal screen: one contact of Cu tape with min. thickness of 0.15mm over each core Optional metal screen: Overlapping one or two Cu tapes Core arrangment: screened cores are laid-up Inner sheath: PVC applied around the laid-up cores PE Sheath: PE compound type ST7 according to IEC 60502-2 type DMP 2 according to VDE 0276, black color PVC Sheath: PVC mass type DMV6, red (or black) color

Available constructions:
Cu cores
6/10 kV 3x(35 -300)mm2

Al cores 3x(35 - 300)mm2

12/20 kV 3x(35 - 185)mm2 3x(35 - 185)mm2 18/30 kV 3x(35 - 120)mm2 3x(35 - 120)mm2 20/35 kV 3x(35 - 120)mm2 3x(35 - 120)mm2 Standard Cross section of metallic screen for conductor sizes: from 25mm 2 to 120 mm 2 from 150mm 2 to 300mm 2 from 400mm 2 to 630mm 2

where: S is cross section of cores in mm2 n - cross section of cores

16mm2 25mm2 35mm2


Pa cking: C a ble coil or Drum m or N/m 24/1000 20/500 22/500 24/500 24/500 24/500 22/250 24/250 24/1000 20/500 22/500 24/500 24/500 24/500 22/250 24/250

C o nstructio n d a ta : N 2X SE Y , N A 2X SE Y
Num be r of core s x Nom ina l C ross S e ction No x m m 3x50RM /16 3x70RM /16 3x95RM /16 3x120RM /16 3x150RM /25 3x185RM /25 3x240RM /25 3x300RM /25 3x50RM /16 3x70RM /16 3x95RM /16 3x120RM /16 3x150RM /25 3x185RM /25 3x240RM /25 3x300RM /25 Nom ina l insula tion thickne ss mm 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 Nom ina l she a th thickne ss mm 2.5 2.7 2.8 2.9 3.0 3.2 3.4 3.4 2.5 2.7 2.8 2.9 3.0 3.2 3.4 3.4 O ve ra ll Dia m e te r (A pprox.) m a x.m m N2X S EY 6/10kV 48 53 57 60 63 67 74 77 NA 2X S EY 6/10kV 48 53 57 60 63 67 74 77 297 330 357 378 406 428 474 502 435 609 827 1044 1305 1610 2038 2610 2680 3270 3730 4200 4840 5440 6550 7500 1774 2380 3132 3877 4768 5808 7424 9203 3650 4640 5580 6540 7720 9040 11290 13340 C u w e ight (A pprox.) kg/km A l w e ight (A pprox.) kg/km T ota l W e ight (A pprox.) kg/km

Standard shape of conductor RM - class 2 conductor acc. to IEC 60228 and VDE 0295

Cable Factory FKN | 2012

A2XSYT, A2XS2YT XHE 48/0-A, XHP 48/0-A


Aerial bundled cables for medium voltage Rated Voltage: U0/U - 6/10kV; 12/20kV; 20/35 kV Standard: HD620.S2, SRPS N.C5.231

Middle Voltage Power Cables

Application
For middle voltage power distribution in distribution networks (6/10(12);12/20(24);20/35(40)) kV. May be put on on the overhead lines in old and residential areas. Provides a shortcut to electrification without affecting the townscape and its environs. This cables can be strung safeluy on the same poles with low-voltage and telecomunication cables.

Technical Data:
Conductor resistance at 20o C: according to N.60.228 class 2 Core temperature, max: 90 C in continuous operation Max. short circuit temperature: 250 oC , not more than 5 sec Overload temperature: 130oC /100h per year max. Nominal voltage Uo/U: 6/10; 12/20; 20/35 kV 6/10 kV = max. 12 kV Highest system voltage, Umax 12/20 kV = max. 24 kV 20/35 kV = max. 40 kV Test voltage = 2.5Uo(HD.620.S2), 6/10 kV = 15 kV AC (50Hz) - 5 min: 12/20 kV = 30 kV 20/35 kV = 50 kV Level of partial discharge: no more than 2pC Bending radius, min: 15xDcable Temperature of laying: no less than - 5 oC Dielectric factor of losses, 50 Hz: at 20C, (0.8-3)x10-4 Spec.volume insulation resistance: at 20C, min 1015 x cm Intensity of electric field: max. 6.9-5.3 kV/mm Tests for cable: according to HD620.S2 Test for messanger: according to HD620.S2 Tensile force during the laying must not exceed: Breaking load of messenger, min: for Cu conductors - 50 N/mm2 for Al conductors - 30 N/mm2 for 50 mm2 = 60 kN for 70 mm2 = 82kN

Cable Structure:
Conductor: Round, stranded and compacted aluminium conductors cl.2, according to EN.60.228

Inner semi-conductive layer: semi-conductive XLPE compound around conductor Insulation: XLPE type XI 1 Outer semi-conductive layer: semi-conductive XLPE compound around insulation Wrapping: Layer of semi-conductive tape helicoidally wrapped. Cu wires concentrically laid and Metal screen: one contact of Cu tape with thickness of 0.1mm. one or more overlapping Cu tapes Optional metal screen: with min.thickness of 0.1mm Separator: Polyester tape helicoidally wrapped. PE sheath (A2XS2YT): PE compound, black color for each phase conductor and steel PVC sheath (A2XS2YT): PVC compaund type, Black Color for each phase conductor and steel

Messenger (for 10, 20 kV): Galvanized steel messenger 50 mm2. Mass of zink coated. Messenger (for 35 kV): Galvanized steel messenger 70 mm2 . Three single-phase cables twisted around Cores assembly: a steel messenger as an aerial bundled cable

Available constructions:
Single Al core: 1x(25 - 150)mm2 Standard Cross section of metallic screen for conductor sizes: from 25mm2 to 120 mm2 16mm2 from 150mm2 to 300mm2 25mm2 from 400mm2 to 630mm2 35mm2

Modulus of elasticity of messenger: 175 kN/mm2

* other dimensions for metallic screen are available on request.

Packing:
Standard packing length on wooden drums: Min. length on drum: 200m

Standard shape of conductor RM - class 2 conductor acc. to IEC 60228 and VDE 0295

Cable Factory FKN | 2012

A2XS(F) 2YT, XHE 49/0-A


Aerial bundled cables for medium voltage Rated Voltage: U0/U - 6/10kV; 12/20kV; 20/35 kV Standard: HD 620.S2; acc: IEC 60502-2; SRPS N.C5.231

Middle Voltage Power Cables

Application For middle voltage power distribution in distribution networks (6/10(12);12/20(24)) kV. May be put on the overhead lines in old and residential areas. Provides a shortcut to electrification without affecting the townscape and its environs. This cables can be strung safeluy on the same poles with low-voltage and telecomunication cables and water resistant.

Technical Data:
Conductor resistance at 20oC: according to EN.60.228 Core temperature, max: 90 C in continuous operation Max. short circuit temperature: 250 oC , not more than 5 sec Overload temperature: 130oC /100h per year max. Nominal voltage Uo/U: 6/10; 12/20; 20/35 kV 6/10 kV = max. 12 kV Highest system voltage, Umax 12/20 kV = max. 24 kV 20/35 kV = max. 40 kV 6/10 kV = 15 kV Test voltage = 2.5Uo(HD.620.S2), AC (50Hz) - 5 min 12/20 kV = 30 kV 20/35 kV = 50 kV Level of partial discharge: no more than 2pC Bending radius, min 15xDcable Temperature of laying: no less than - 5 oC Dielectric factor of losses, 50 Hz: at 20C, (0.8-3)x10-4 Spec.volume insulation resistance: at 20C, min 1015 x cm Intensity of electric field: max. 6.9-5.3 kV/mm Tests for cable: according to HD 620.S2 Test for messanger: according to HD 620.S2 Tests - water penetration in the region of metallic screen: Tensile force during the laying must not exceed: Breaking load of messenger, min: IEC 60502-2 annex F (125x4h, 90C) for Cu conductors - 50 N/mm2 for Al conductors - 30 N/mm2 for 50 mm2 = 60 kN for 70 mm2 = 82kN

Available constructions:
Single Al core: 1x(25 - 150)mm2 Standard Cross section of metallic screen for conductor sizes: from 25mm2 to 120 mm2 16mm2 from 150mm2 to 300mm2 25mm2 from 400mm2 to 630mm2 35mm2
* other dimensions for metallic screen are available on request.

Packing:
Standard packing length on wooden drums: Min. length on drum: 200m

Modulus of elasticity of messenger: 175 kN/mm2

Cable Structure:
Conductor: Round, stranded and compacted aluminium conductors cl.2, according to EN.60.228

Inner semi-conductive layer: semi-conductive XLPE compound around conductor Insulation: XLPE type XI 1 Outer semi-conductive layer: semi-conductive XLPE compound around insulation Water resisting element: Layer of semi-conductive water absorbing tape helicoidally wrapped. Metal screen: Cu wires concentrically laid and one contact of Cu tape with min. thickness of 0.1mm. PE compound type EP 1 acc.to N.C0.195, black color for each phase conductor and steel

Water resisting element: Layer of non-conductive water absorbing tape helicoidally wrapped. PE sheath

Messenger (for 10, 20 kV): Galvanized steel messenger 50 mm2. Mass of zink coated Messenger (for 35 kV): Galvanized steel messenger 70 mm2. Mass of zink coated Three single-phase cables twisted around Cores assembly: a steel messenger as an aerial bundled cable

Standard shape of conductor RM - class 2 conductor acc. to IEC 60228 and VDE 0295

Cable Factory FKN | 2012

A2XS(F) 2YT, XHE 49/0-A


Aerial bundled cables for medium voltage Rated Voltage: U0/U - 6/10kV; 12/20kV; 20/35 kV Standard: HD 620.S2; acc: IEC 60502-2; SRPS N.C5.231

Middle Voltage Power Cables

Construction data: XHE 49/0-A


Number of cores x Nominal Cross Section No x mm 3x35RM/16+50 3x50RM/16+50 3x70RM/16+50 3x95RM/16+50 3x120RM/16+50 3x150RM/25+50 3x35RM/16+50 3x50RM/16+50 3x70RM/16+50 3x95RM/16+50 3x120RM/16+50 3x150RM/25+50 Nominal insulation thickness mm 3.4 3.4 3.4 3.4 3.4 3.4 5.5 5.5 5.5 5.5 5.5 5.5 Nominal sheath thickness mm 1.8 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 Overall Diameter (Approx.) max.mm XHE 49/0-A 6/10kV 57.6 60.8 64.8 68.0 70.6 74.0 XHE 49/0-A 12/20kV 66.8 69.2 73.2 76.7 79.0 82.4 191 215 215 230 230 275 305 440 615 835 1055 1318 2555 2755 3105 3445 3750 4505 22/400 24/400 24/350 24/300 24/300 22/300 191 215 215 230 230 275 305 440 615 835 1055 1318 2060 2280 2590 2900 3185 3861 22/500 24/500 24/450 24/400 24/400 22/350 Cu weight (Approx.) kg/km Al weight (Approx.) kg/km Total Weight (Approx.) kg/km Packing: Cable coil or Drum m or N/m

* other dimensions for conductor, metallic and packing lenght are available on request.

Cable Factory FKN | 2012

N2XS(F)2Y, NA2XS(F)2Y
Cu or Al single-core cables with insulation XLPE, longitudinal water-tight and PE sheath Rated Voltage: U0/U - 6/10kV; 12/20kV; 20/35 kV Standard: VDE 0276/HD620, IEC 60502-2

Middle Voltage Power Cables

Application The single-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements are designed for transfer and distribution of electrical power in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 class 2

Core temperature, max: 90 C in continuous operation Max. short circuit temperature: 250 oC , not more than 5 sec Overload temperature: 130oC /100h per year max. Nominal voltage Uo/U: 6/10; 12/20; 20/35 kV 6/10 kV = max. 12 kV Highest system voltage, Umax 12/20kV = max. 24 kV 20/35 kV = max. 42kV 6/10 kV = 21kV Test voltage AC (50Hz): 12/20 kV = 42 kV 20/35 kV = 70kV Level of partial discharge at 2*Uo: no more than 2pC Bending radius, min 15xDcable Temperature of laying: no less than - 5 oC Dielectric factor of losses, 50 Hz: at 20C, (0.8-3)x10-4 Spec.internal volume resistivity: at 90C, min 1012 x m Intensity of electric field: max. 6.9-5.3 kV/mm Force of strain in laying, N max. Tests - water penetration in the region of metallic screen: 120 x D where: D is diameter od cable in (mm) IEC 60502-2 annex F (125x4h, 90C)

Standard shape of conducto RM - class 2 conductor acc. to IEC 60228 and VDE 0295

Cable Structure:
Conductor: Cu or Al stranded compacted acc. DIN VDE 0295 cl.2 (HD383). Inner semi-conductive layer: semi-conductive XLPE compound around conductor Insulation: XLPE compound Outer semi-conductive layer: semi-conductive XLPE compound around isolation Water resisting element: Layer of semi-conductive water absorbing tape helicoidally wrapped. Metal screen: Cu wires concentrically laid andone contact of Cu tape with min.thickness of 0.1mm Water resisting element: Layer of non-conductive water absorbing tape helicoidally wrapped. Color of sheath Black

Available constructions:
Al conductor 6/10 kV 12.7/22kV 20/35 kV Standard Cross section of metallic screen for conductor sizes: from 25mm2 to 120 mm2 from 150mm to 300mm from 400mm to 500mm
2 2 2 2

Cu conductor 25 - 300mm2 35 - 240mm2 50 - 240mm2

35 - 500mm2 50 - 500mm2 50 - 500mm


2

16mm2 25mm2 35mm2

Cable Factory FKN | 2012

N2XS(FL)2Y, NA2XS(FL)2Y
Single-core cables with insulation of cross-linked polyethylene (XLPE) longitudinal water-tight and PE sheath Rated Voltage: U0/U - 6/10; 12/20; 18/30 kV; Standard:VDE 0276/HD620.S2; IEC 60502-2 Similar as: XHE 49-A by standard: N.C5.230
$$$
! "

$$$

Middle Voltage Power Cables

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements are designed for transfer and distribution of electrical power in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 class 2 Core temperature, max: 90 C in continuous operation
o Max. short circuit temperature: 250 C , not more than 5 sec o Overload temperature: 130 C /100h per year max.

Nominal voltage Uo/U: 6/10; 12/20; 18/30 kV Highest system voltage 6/10; 12/20; 18/30 kV Uo/U, no more than: 12kV; 24kV; 36kV Test v olt age Uo/ U 6/10; 12/20; 18/30kV A C ( ) - 5 min 21kV; 42kV; 63kV DC (= ) - 15 min 67kV; 134kV; 201kV Lev el of par t ial dischar geat 2*Uo: max. 5 pC / 2 pC Bending radius, min 15xDcable o Temperature of laying: no less than - 5 C Temperature of exploitation: -30 to 50oC according to IEC 60502-2 or Tests: DIN VDE 0276-620 or HD620.S2 Al cores - 30*n*S core Force of strain in laying N max. Cu cores - 50*n*S core where: N is number of cores and S is cross section of cores in mm2 Tests - water penetration in the region of metallic screen: IEC 60502-2 annex F

Cable Structure:
Conductor: Cu and Al stranded compacted, according to IEC 60228 class 2 and VDE 0295 class 2

Inner semi-conductive layer: semi-conductive XLPE compound Insulation: XLPE compound Outer semi-conductive layer: semi-conductive XLPE compound Water resisting element: Layer of semi-conductive water absorbing tape Cu wires concentrically laid and Metal screen: one contact of Cu tape with thickness of 0.1mm. Water resisting element: Layer of non-conductive water absorbing tape Radial protection: Al foil with copolymer protectionfrom moisture ingress Sheath: PE compound type ST7 according to IEC 60502-2 type DMP 2 according to VDE 0276

Color: black

Standard shape of conducto RM - class 2 conductor acc. to IEC 60228 and VDE 0295

Cable Factory FKN | 2012

NA2XSYRY, NA2XSEYRY
One or three core XLPE-insulated cables with steel wire armour and PVC sheath Rated Voltage: U0/U - 3.6/6kV; 6/10kV; 8.7/15kV; 12/20kV; 18/30kV; Standard: IEC 60502-2

Middle Voltage Power Cables

Application The three-core armored cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U - 3.6/6kV; 6/10kV; 8.7/15kV; 12/20kV; 18/30kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 class 2 Core temperature, max: 90 C in continuous operation Max. short circuit temperature: 250 C , not more than 5 sec Overload temperature: 130oC /100h per year max. Nominal voltage Uo/U: 3.6/6; 6/10; 8.7/15; 12/20; 18/30 kV 3.6/6 kV = max. 7.2 kV 6/10 kV = max. 12 kV Highest system voltage, Umax 8.7/15 kV = max. 17.5 kV 12/20 kV = max. 24 kV 18/30 kV = max. 36 kV 3.6/6 kV = 12.5 kV Test voltage = 3.5Uo(IEC60502-2); 6/10 kV = 21 kV 3.5Uo(VDE 0276/HD620) 8.7/15 kV = 30.5 kV AC (50Hz) - 5 min 12/20 kV = 42 kV 18/30 kV = 63 kV Level of partial discharge at 2*Uo: no more than 2pC Bending radius, min 15xDcable Temperature of laying: no less than - 5 oC Dielectric factor of losses, 50 Hz: at 20C, (0.8-3)x10-4 Spec.volume insulation resistance at 20C, min 1015 x cm Intensity of electric field: max. 6.9-5.3 kV/mm Tests: according to IEC 60502-2 or DIN VDE 0276-620 Al cores - 30*S*n Force of strain in laying, N max. Cu cores - 50*S*n where: S is cross section of cores in mm2 n - cross section of cores
o

Cable Structure:
Conductor: Cu or Al stranded compacted, according to IEC 60228 and VDE 0295 class 2

Inner semi-conductive layer: semi-conductive XLPE compound around conductor Insulation: XLPE compound Outer semi-conductive layer: semi-conductive XLPE compound around isolation Warapping: Semi-conductive tape helicoidally wrapped Cu wires concentrically laid and Metal screen: one contact of Cu tape with min. thickness of 0.1mm over each core Optional metal screen: overlapping one or two Cu tape Core arrangment: screened cores are laid-up Inner sheath: PVC applied around the laid-up cores Armour: for single core: aluminium round wires for three-core: galvanized round steel wires Optional armour: Sheath: galvanized flat steel wires and optional contra spiral galvanized steel tape PVC compound type ST2 according to IEC 60502, red or black color

Optional sheath PE mass, black color

On request:
Fire propagation acc. IEC 60332-3 cat. A, B, C Hydrocarbon resistant outer sheath (RH). Termite and rodents protected outer sheath. Oil resistant outer sheath.

Standard shape of conducto RM - class 2 conductor acc. to IEC 60228 and VDE 0295

Cable Factory FKN | 2012

N2XSYBY, N2XSEYBY, NA2XSYBY, NA2XSEYBY


Single Core and Three-core Cables with insulation of cross-linked polyethylene (XLPE), alow steel wire armour and PVC sheath Rated Voltage: U0/U - 6/10; 12/20; 18/30 kV; Standard:VDE 0276/HD620.S2; IEC 60502-2 Similar as: XHE 49-A by standard: N.C5.230

Middle Voltage Power Cables

Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U - 3.6/6kV; 6/10kV; 8.7/15kV; 12/20kV; 18/30kV and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.

Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 class 2 Core temperature, max: 90 C in continuous operation Max. short circuit temperature: 250 oC , not more than 5 sec Overload temperature: 130oC /100h per year max. Nominal voltage Uo/U: 3.6/6; 6/10; 8.7/15; 12/20; 18/30 kV 3.6/6 kV = max. 7.2 kV 6/10 kV = max. 12 kV Highest system voltage, Umax 8.7/15 kV = max. 17.5 kV 12/20 kV = max. 24 kV 18/30 kV = max. 36 kV 3.6/6 kV = 12.5 kV Test voltage = 3.5Uo(IEC60502-2); 6/10 kV = 21 kV 3.5Uo(VDE 0276/HD620) 8.7/15 kV = 30.5 kV AC (50Hz) - 5 min 12/20 kV = 42 kV 18/30 kV = 63 kV Level of partial discharge at 2*Uo: no more than 2pC Bending radius, min 15xDcable Temperature of laying: no less than - 5 oC Dielectric factor of losses, 50 Hz: at 20C, (0.8-3)x10-4 Spec.volume insulation resistance at 20C, min 1015 x cm Intensity of electric field: max. 6.9-5.3 kV/mm Tests: according to IEC 60502-2 orDIN VDE 0276-620 Al cores - 30*S*n Force of strain in laying, N max. Cu cores - 50*S*n where: S is cross section of cores in mm2

Cable Structure:
Conductor: Cu or Al stranded compacted, according to IEC 60228 and VDE 0295 class 2

Inner semi-conductive layer: semi-conductive XLPE compound around conductor Insulation: XLPE compound Outer semi-conductive layer: semi-conductive XLPE compound around insulation Wrapping: Semi-conductive tape helicoidally wrapped Cu wires concentrically laid and Metal screen: one contact of Cu tape with min. thickness of 0.1mm over each core Optional metal screen: overlapping one or two Cu tapes Core arrangment: screened cores are laid-up Inner sheath: PVC applied around the laid-up cores Armour: for single-core: two aluminium tapes for three-cores: two galvanized steel tapes Sheath: PVC compound type ST2 according to IEC 60502, red or black color

Optional sheath: PE mass, Black color

On request:
Fire propagation acc. IEC 60332-3 Hydrocarbon resistant outer sheath (RH). Termite and rodents protected outer sheath. Oil resistant outer sheath.

n - cross section of cores

Standard shape of conducto RM - class 2 conductor acc. to IEC 60228 and VDE 0295

Cable Factory FKN | 2012

N2XSYBY, N2XSEYBY, NA2XSYBY, NA2XSEYBY


Single Core and Three-core Cables with insulation of cross-linked polyethylene (XLPE), alow steel wire armour and PVC sheath Rated Voltage: U0/U - 6/10; 12/20; 18/30 kV; Standard:VDE 0276/HD620.S2; IEC 60502-2 Similar as: XHE 49-A by standard: N.C5.230

Middle Voltage Power Cables

Construction data: N2XSEYBY


Number of cores x Nominal No x mm 3x25RM/16 3x35RM/16 3x50RM/16 3x70RM/16 3x95RM/16 3x120RM/16 3x150RM/25 3x185RM/25 3x240RM/25 3x300RM/25 3x25RM/16 3x35RM/16 3x50RM/16 3x70RM/16 3x95RM/16 3x120RM/16 3x150RM/25 3x185RM/25 3x25RM/16 3x35RM/16 3x50RM/16 3x70RM/16 3x95RM/16 3x120RM/16 3x150RM/25 3x185RM/25 3x50RM/16 3x70RM/16 3x95RM/16 Nominal insulation thickness mm 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 8.0 8.0 8.0 Nominal sheath thickness mm 2.5 2.5 2.6 2.7 2.8 2.9 3.1 3.2 3.4 3.5 2.6 2.7 2.8 2.9 3.0 3.1 3.3 3.4 2.8 2.8 2.9 3.0 3.2 3.3 3.4 3.5 3.3 3.4 3.6 Overall Copper weight Total Diameter (Approx.) (Approx.) Weight (Approx.) max.mm kg/km kg/km 46.0 49.0 52.0 56.0 61.0 64.0 68.0 71.5 77.5 83.0 51.5 54.5 57.0 61.5 65.5 69.0 72.5 77.5 58.5 59.0 61.5 66.0 70.0 74.0 77.0 82.0 72.5 77.0 82.5 910 1210 1670 2247 2994 3714 4640 5646 7272 9015 910 1210 1670 2247 2994 3714 4640 5646 910 1210 1670 2247 2994 3714 4640 5646 1670 2247 2994 3975 4600 5280 6340 7760 8880 10420 12115 14690 17360 4611 5180 5900 7134 8511 9858 11300 13015 5607 5925 6709 7844 9434 10663 12221 13910 8640 10070 12614 Packing: Cable coil or Drum m or N/m 18/500 18/500 20/500 22/500 24/500 24/500 24/500 24/450 24/400 24/350 20/500 20/500 22/500 24/500 24/500 24/500 24/450 24/400 22/500 22/500 24/500 24/500 24/500 24/450 24/400 24/350 24/450 24/400 24/350

N2XSEYBY 6/10kV (Umax=12kV)

N2XSEYBY 8.7/15kV (Umax=17.5kV)

N2XSEYBY 12/20kV (Umax=24kV)

N2XSEYBY 18/30kV (Umax=36kV)

*other dimensions for conductor, metallic screen and packing length are available on request.

Cable Factory FKN | 2012

AASC-XLPE 20kV (PAS)


XLPE insulated aluminium alloy conductors for MV overhead lines Rated Voltage: U0/U - 12/20kV Standard: AC SFS 5791

Middle Voltage Power Cables

Application
These power cables are used for overhead lines at specific environmental conditions like strong wind, ice, snow and when the route of the cables is placed over mountains and forests. Cable's construction enables smaller destination between two phases, opposites against strong wind and tolerates bigger mechanical and electrical loads provoked by fallen trees. The primary advantage of cross linked PE is despite the two conductors are close too much to each other because of the wind, the line isn't fallen out. The ice sheath over the cross linked PE sheath doesn't retain as long as over the bare conductor.

Technical Data:
Max. temperature of conductor: 80 C Working voltage: 12/20kV Test voltage in water: 4 kV Insulation resistance at 80C: 1014 x cm Max. permissible tensile stress: 100 N/mm2 Calculated breaking load: table 1 Max. electric. resistance, at 20C table 1 Permissible permanent current: table 2 Distance between phases: horizontal: 500 mm vertical: 600 mm

Cable Structure:
The conductor is rope according MKS N.C1.402 (DIN 48 201/6) Conductor: of wrapped wires of AlMgSi-E alloys according MKS N. C1.401(DIN 48 200/6) . The rope is compacted. XLPE outer jacket, black coloured, XI3, Insulation: according MKS N.C0.195(DIN VDE 0207/22), with content of carbon black at least 2%, low temperature and UV resistance.

Additional Information and technical data:


Nominal cross-section Max.electric resistance at 20C Calculated breaking load mm 2 35 50 70 95 120 150 /km 0.986 0.720 0.493 0.363 0.288 0.236 kN 9.65 14.20 20.60 27.90 35.20 43.40

Nominal cross-section Permissible permanent current S hort circuit current mm 2 35 50 70 95 120 150
mm2 35 50 70 95 120 150

A 200 245 310 370 430 485

kA 3.2 4.3 6.4 8.6 11.0 13.5


Outer diameter of cable mm 12 13 15 17 18 19

Note: Values given in tables at:


Environmental temperature - 20C Conductor temperature - 80C Wind velocity - 0,6 m/s Sun influence - 1000/m Short circuit temperature - 150 C Short circuit time - 1 s

Nominal cross-section Number of wires Outer diameter of conductor mm 7 7 19 19 19 19 7 8.3 9.8 11.6 12.8 14.2

Note: Nominal thickness of sheath - 2.3mm

Minimal thickness of sheath - 2.0mm Maximal thickness of sheath - 2.5mm

Cable Factory FKN | 2012

FRN-N10XA8E-AR, FR-N20XA8E-AR
Single-core XLPE-insulated cables with PE sheath, longitudinally and radially watertight Rated Voltage: U0/U - 6/10kV; 12/20kV Standard: HD620.S1; NF C33-223
! "

$$$
$$$

Middle Voltage Power Cables

Application

The single-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal and radial water-blocking elements are designed for transfer and distribution of electrical power in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 class 2 Core temperature, max: 90 C in continuous operation Max. short circuit temperature: 250 oC , not more than 5 sec Overload temperature: 130oC /100h per year max. Nominal voltage Uo/U: 6/10; 12/20; kV 6/10 kV = max. 12 kV Highest system voltage, Umax 12/20 kV = max. 24 kV Test voltage = 3.5Uo A C (50Hz) - 5 min Level of partial discharge at 1.73*Uo: no more than 5pC Bending radius, min 30xDcable Temperature of laying: no less than - 5 C Dielectric factor of losses, 50 Hz: at 20C, (0.8-3)x10-4 Spec.volume insulation resistance at 20C, min 1015 x cm Intensity of electric field: max. 6.9-5.3 kV/mm Tests: acc. to. HD626S2, NF C33-223 Force of strain in laying, N max. Al cores - 30*S where: S is cross section of cores in mm2
o

Cable Structure:
Conductor: Al stranded compacted acc. DIN VDE 0295 cl.2 (HD383). Inner semi-conductive layer: semi-conductive XLPE compound around conductor Insulation: XLPE compound Outer semi-conductive layer: semi-conductive XLPE compound around insulation Water resisting element: Layer of semi-conductive water absorbing tape helicoidally wrapped. Metallic screen : Al foil with copolymer layer tightly bonded to the PE sheath Sheath: PE compound - HDPE

6/10 kV = 21kV 12/20 kV = 42 kV

Standard shape of conductor:


RM - class 2 conductor acc. to IEC 60228 and VDE 0295

Packing:
- Standard packing length on wooden drums: (500m; 1000m)

Construction data: FR-N(10)XA8E-AR; FR-N(20)XA8E-AR


Number of Nominal Nominal Overall Al cond. Total Packing: cores x insulation sheath Diameter Weight Weight Cable coil or Nominal thickness thickness (Approx.) (Approx.) (Approx.) Drum Cross Section No x mm mm mm max.mm kg/km kg/km m or N/m FR-N(10)XA8E-AR 6/10 kV 1x185RM/16 1x185RM/25 1x50RM/16 1x95RM/16 1x120RM/16 1x150RM/16 1x185RM/16 1x185RM/25 3.4 3.4 5.5 5.5 5.5 5.5 5.5 5.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 32.5 33.0 29.0 32.5 34.0 35.5 37.0 37.5 540 540 145 280 350 435 540 540 1188 1214 765 1022 1134 1282 1410 1416 18/1000 18/1000 18/1000 18/1000 18/1000 20/1000 20/1000 20/1000

FR-N(20)XA8E-AR 12/20 kV

*other dimensions for conductor and metallic screen are available on request.

Cable Factory FKN | 2012

N2XS(F)2YY, NA2XS(F)2YY
Al or Cu single-core cables with insulation XLPE, longitudinal water-tight and PE+PVC sheath Rated Voltage: U0/U - 6/10kV; 12.7/22kV; 20/35 kV Standard: IEC 60502-2
! "

Middle Voltage Power Cables

Application
The single-core cables with insulation of cross-linked polyethylene (XLPE) and longitudinal water-blocking elements are designed for transfer and distribution of electrical power in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants. They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
Technical Data:
Conductor resistance at 20o C: according to VDE 0295 and IEC 60228 class 2 Core temperature, max: 90 C in continuous operation Max. short circuit temperature: 250 oC , not more than 5 sec Overload temperature: 130oC /100h per year max. Nominal voltage Uo/U: 6/10; 12.7/22; 20/35 kV 6/10 kV = max. 12 kV Highest system voltage, Umax 12.7/22kV = max. 25 kV 20/35 kV = max. 40.5kV 6/10 kV = 28kV Test voltage AC (50Hz): 12.7/22 kV = 50 kV 20/35 kV = 75kV Level of partial discharge at 2*Uo: no more than 2pC Bending radius, min 20xDcable Temperature of laying: no less than - 5 oC Dielectric factor of losses, 50 Hz: at 20C, (0.8-3)x10-4 Spec.internal volume resistivity: at 90C, min 1012 x m Intensity of electric field: max. 6.9-5.3 kV/mm Force of strain in laying, N max. Tests - water penetration in the region of metallic screen: 120 x D where: D is diameter od cable in (mm) IEC 60502-2 annex F (125x4h, 90C)

Available constructions:
Al conductor Cu conductor 6/10 kV 35 - 500mm2 25 - 300mm2 12.7/22kV 50 - 500mm2 35 - 240mm2 20/35 kV 50 - 500mm2 50 - 240mm2 Standard Cross section of metallic screen for conductor sizes: from 25mm2 to 120 mm2 from 150mm to 300mm
2 2

16mm2 25mm2 35mm2

from 400mm2 to 500mm2

On Request:
Fire propagation acc. IEC 60332-3 cat.

Cable Structure:
Conductor: Cu or Al stranded compacted acc. DIN VDE 0295 cl.2 (HD383). Inner semi-conductive layer: semi-conductive XLPE compound around conductor Insulation: XLPE compound Outer semi-conductive layer: semi-conductive XLPE compound around insulation Water resisting element: Layer of semi-conductive water absorbing tape helicoidally wrapped. Cu wires concentrically laid and Metal screen: one contact of Cu tape with min. thickness of 0.1mm Water resisting element: Layer of non-conductive water absorbing tape helicoidally wrapped. Sheath: combined PE+PVC sheath (two layers) with thickness 2.5+1.5 mm. PVC is stabilized against the sun irradiation.

Color of sheath Black or red

Standard shape of conductor:


RM - class 2 conductor acc. to IEC 60228 and VDE 0295

Packing:
Standard packing length on wooden drums: (500m; 1000m)

Cable Factory FKN | 2012

N2XS(F)2YY, NA2XS(F)2YY
Al or Cu single-core cables with insulation XLPE, longitudinal water-tight and PE+PVC sheath Rated Voltage: U0/U - 6/10kV; 12.7/22kV; 20/35 kV Standard: IEC 60502-2
! "

Middle Voltage Power Cables

C o n s t r u ct io n d a t a : N 2 X S (F )2 Y Y , N A 2 X S (F )2 Y Y
N u mb e r o f co re s x N o m in a l C r o s s S e c t io n N o m in a l in s u la t io n t h ic k n e s s N o m in a l s h e a t h t h ic k n e s s O v e r a ll D ia m e t e r (A p p ro x . ) C o p p e r w e ig h t (A p p ro x . ) A l w e ig h t (A p p ro x . ) Tota l W e ig h t (A p p ro x . ) P a c k in g : C a b le c o il o r D r u m

No x m m 1 x2 5 R M /1 6 1 x3 5 R M /1 6 1 x5 0 R M /1 6 1 x7 0 R M /1 6 1 x9 5 R M /1 6 1 x1 2 0 R M /1 6 1 x1 5 0 R M /2 5 1 x1 8 5 R M /2 5 1 x2 4 0 R M /2 5 1 x3 5 R M /1 6 1 x5 0 R M /1 6 1 x7 0 R M /1 6 1 x9 5 R M /1 6 1 x1 2 0 R M /1 6 1 x1 5 0 R M /2 5 1 x1 8 5 R M /2 5 1 x2 4 0 R M /2 5 1 x3 0 0 R M /2 5 1 x4 0 0 R M /3 5 1 x5 0 0 R M /3 5 1 x3 5 R M /1 6 1 x5 0 R M /1 6 1 x7 0 R M /1 6 1 x9 5 R M /1 6 1 x1 2 0 R M /1 6 1 x1 5 0 R M /2 5 1 x1 8 5 R M /2 5 1 x2 4 0 R M /2 5 1 x3 5 R M /1 6 1 x5 0 R M /1 6 1 x7 0 R M /1 6 1 x9 5 R M /1 6 1 x1 2 0 R M /1 6 1 x1 5 0 R M /2 5 1 x1 8 5 R M /2 5 1 x2 4 0 R M /2 5 1 x3 0 0 R M /2 5 1 x4 0 0 R M /3 5 1 x5 0 0 R M /3 5 1 x5 0 R M /1 6 1 x7 0 R M /1 6 1 x9 5 R M /1 6 1 x1 2 0 R M /1 6 1 x1 5 0 R M /2 5 1 x1 8 5 R M /2 5 1 x2 4 0 R M /2 5 1 x5 0 R M /1 6 1 x7 0 R M /1 6 1 x9 5 R M /1 6 1 x1 2 0 R M /1 6

mm 3 .4 3 .4 3 .4 3 .4 3 .4 3 .4 3 .4 3 .4 3 .4 3 .4 3 .4 3 .4 3 .4 3 .4 3 .4 3 .4 3 .4 3 .4 3 .4 3 .4 5 .5 5 .5 5 .5 5 .5 5 .5 5 .5 5 .5 5 .5 5 .5 5 .5 5 .5 5 .5 5 .5 5 .5 5 .5 5 .5 5 .5 5 .5 5 .5 9 .0 9 .0 9 .0 9 .0 9 .0 9 .0 9 .0 9 .0 9 .0 9 .0 9 .0

mm 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5 2 .5 +1 .5

m a x.m m 2 8 .0 2 9 .0 3 0 .0 3 2 .0 3 4 .0 3 5 .0 3 6 .0 3 8 .0 4 1 .0 2 9 .0 3 0 .0 3 2 .0 3 4 .0 3 5 .0 3 6 .0 3 8 .0 4 1 .0 4 3 .0 4 6 .0 4 9 .0 3 3 .0 3 4 .0 3 6 .0 3 7 .5 3 9 .0 4 0 .5 4 2 .5 4 4 .5 3 3 .0 3 4 .0 3 6 .0 3 7 .5 3 9 .0 4 0 .5 4 2 .5 4 4 .5 4 7 .0 5 0 .0 5 3 .5 4 1 .0 4 3 .0 4 4 .5 4 6 .0 4 7 .5 4 9 .5 5 1 .5 4 1 .0 4 3 .0 4 4 .5 4 6 .0

kg /km 408 518 662 854 1094 1334 1723 2059 2587 182 182 182 182 182 283 283 283 283 395 395 518 662 854 1094 1334 1723 2059 2587 182 182 182 182 182 283 283 283 283 395 395 662 854 1094 1334 1723 2059 2587 182 182 182 182

kg /km 101 145 203 276 348 435 537 696 870 1160 1450 101 145 203 276 348 435 537 696 870 1160 1450 145 203 276 348

kg /km 990 1070 1220 1460 1760 2000 2400 2770 3280 855 930 1040 1170 1270 1490 1650 1830 2090 2140 2890 1220 1410 1660 1970 2220 2610 2990 3530 1120 1230 1370 1490 1710 1860 2080 2350 2790 3190 1790 2050 2380 2640 2980 3370 3940 1500 1630 1790 1920

m o r N/m 1 6 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0 1 8 /1 0 0 0 2 0 /1 0 0 0 2 0 /1 0 0 0 2 0 /1 0 0 0 2 2 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0 1 8 /1 0 0 0 2 0 /1 0 0 0 2 0 /1 0 0 0 2 0 /1 0 0 0 2 2 /1 0 0 0 2 4 /1 0 0 0 2 4 /1 0 0 0 1 8 /1 0 0 0 1 8 /1 0 0 0 2 0 /1 0 0 0 2 0 /1 0 0 0 2 0 /1 0 0 0 2 2 /1 0 0 0 2 2 /1 0 0 0 2 4 /1 0 0 0 1 8 /1 0 0 0 1 8 /1 0 0 0 2 0 /1 0 0 0 2 0 /1 0 0 0 2 0 /1 0 0 0 2 2 /1 0 0 0 2 2 /1 0 0 0 2 4 /1 0 0 0 2 4 /1 0 0 0 2 0 /5 0 0 2 0 /5 0 0 2 2 /1 0 0 0 2 2 /1 0 0 0 2 4 /1 0 0 0 2 4 /1 0 0 0 2 4 /1 0 0 0 2 0 /5 0 0 2 0 /5 0 0 2 2 /1 0 0 0 2 2 /1 0 0 0 2 4 /1 0 0 0 2 4 /1 0 0 0

1 0 -C X EKV C EY (N 2 X S (F )2 YY) 6 /1 0 kV

1 0 -A X EKV C EY (N A 2 X S (F )2 YY) 6 /1 0 kV

2 2 -C X EKV C EY (N 2 X S (F )2 YY) 1 2 /2 0 kV

2 2 -A X EKV C EY (N A 2 X S (F )2 YY) 1 2 /2 0 kV

3 5 -C X EKV C EY (N 2 X S (F )2 YY) 2 0 /3 5 kV

3 5 -A X EKV C EY (N A 2 X S (F )2 YY) 2 0 /3 5 kV

*other dimensions for conductor, metallic screen and packing length are available on request.

Cable Factory FKN | 2012

Cables According to BDS

SVT, SAVT
Power cable with PVC insulation and PVC sheath Rated Voltage: U0/U - 0.6/1 kV Standard: BDS 16291-85

According to BDS

Application Used for transferring and distribution of electrical power for switching installations and outdoor installation or for interior installation in rooms, in canals, tunnels, shafts or pits, at rated voltage Uo/U to 0,6/1 kV with frequency 50 Hz.

Technical Data:
Conductor resistance at 20o C: According to BDS 904-84 Core temperature, max: 70oC in operation Max. short circuit temperature: 160 oC , not more than 5 sec Rated voltage - U0 /U (Umax ): 0.6/1(1.2) kV Test voltage: AC - 4 kV; 50 Hz Temperature Range Fixed installation: -30C to +70C Flexible Installation: -5C to +50C Min. temperaure of laying: -5C Bending radius, min. 10xDcable Specific insulation resistance at 70C: min, 1010 x cm For Cu conducor = 50 N/mm2 Max. permessible tensile stress with cable grip: For Al conducor = 30 N/mm2 Flame test: acc. to IEC 60332-1

Cable Structure:
Conductor: solid or twisted copper or Al wires, class 1 or 2 according to BDS 904-84 (IEC 60228). Insulation: PVC compaund Core identification: according to BDS 16291 Cores assembly: cores stranded concentrically (cores stranded in concentric layers, for signal)

Sheath: PVC compaund Colorof sheath: Gray or black

On Request:
Fire propagation acc. IEC 60332-3 cat. A, B, C (SVT-FR) Hydrocarbon resistant outer sheath (RH). Termite and rodents protected outer sheath. Protected against direct sun irradiation (SVT_c) Oil resistant outer sheath.

Standard shapes and size of conductors:


RM - mutliwire round shaped conductor
Copper: 1.5mm - 630mm Copper: 35mm - 300mm Aluminium: 50mm - 630mm Aluminium: 50mm - 240mm

SM - mutliwire sector shaped conductor

RE - solid round conductor

Additional information and technical data:


Available conductor sizes for power distibution:
Number of cores size of Cu conductors size of Al conductors 1 core: 4mm2 - 630mm2 2 cores: 1.5mm2 - 120mm2 3 cores: 1.5mm2 - 300mm2 4 cores: 1.5mm2 - 240mm2 25mm2 - 300mm2 3 cores+1 earth core: + 16mm2 - 150mm2 5 cores: 1.5mm2 - 240mm2 Available conductor sizes for signaling and control 25mm2 - 630mm2 25mm2 - 120mm2 25mm2 - 240mm2 25mm2 - 240mm2 25mm2 - 240mm2 + 25mm2 - 120mm2 25mm2 - 240mm2

Number of cores size of Cu conductors size of Al conductors 7 -19 cores: (1.5 - 10 ) RE / over 19 cores (1.5 - 2.5 ) RE /

* Other dimensions available on request.

Packing
Standard Packing length on wooden drums: [ 500 m; 1000 m ]; Length Tolerance per drum 5%

Cable Factory FKN | 2012

SVT, SAVT
Al conductors, XLPE insulation, twisted cable Rated Voltage: U0/U - 0.6/1 kV Standard:HD 626/part 4F

C o n st ru ct io n d a t a : S A V T
Num be r o f co r e s x No m ina l C r o s s S e ctio n No x m m 1 x4 1 x6 1 x1 0 1 x1 6 1 x2 5 1 x3 5 1 x5 0 1 x7 0 1 x9 5 1 x1 2 0 1 x1 5 0 1 x1 8 5 1 x2 4 0 1 x3 0 0 1 x4 0 0 1 x5 0 0 2 x2 .5 2 x4 .0 2 x6 .0 2 x1 0 2 x1 6 2 x2 5 3 x2 .5 3 x4 .0 3 x6 .0 3 x1 0 3 x1 6 3 x2 5 3 x3 5 3 x5 0 3 x7 0 3 x9 5 3 x1 2 0 3 x1 5 0 3 x1 8 5 3 x2 4 0 3 x4 .0 +2 .5 3 x6 .0 +4 .0 3 x1 0 +6 .0 3 x1 6 +1 0 3 x2 5 +1 6 3 x3 5 +1 6 3 x5 0 +2 5 3 x7 0 +3 5 3 x9 5 +5 0 3 x1 2 0 +7 0 3 x1 5 0 +7 0 3 x1 8 5 +9 5 3 x2 4 0 +1 2 0 S ha pe O ve r a ll Dia m e te r (A ppr o x.) m a x.m m 8 ,0 8 ,5 9 ,3 1 0 ,8 1 1 ,9 1 3 ,0 1 4 ,2 1 6 ,7 1 8 ,4 1 9 ,9 2 1 ,9 2 4 ,3 2 7 ,2 3 0 ,3 3 3 ,8 3 7 ,9 1 0 ,6 1 2 ,1 1 3 ,2 1 5 ,2 1 7 ,8 2 1 ,5 1 1 ,0 1 2 ,8 1 4 ,0 1 6 ,0 1 8 ,9 2 2 ,8 2 5 ,3 2 8 ,9 2 8 ,8 3 3 ,1 3 5 ,9 3 9 ,3 4 3 ,4 4 8 ,9 1 3 ,4 1 4 ,4 1 6 ,7 1 9 ,5 2 4 ,4 2 7 ,1 3 0 ,8 3 1 ,8 3 6 ,8 4 0 ,1 4 4 ,3 4 9 ,3 5 5 ,4

U 0 /U - 0 .6 /1 k V

According to BDS

A l w e ight (A ppr o x.) kg/km 1 2 ,0 1 7 ,0 2 8 ,0 4 5 ,0 6 8 ,0 9 5 ,0 1 2 7 ,0 1 9 0 ,0 2 6 0 ,0 3 2 5 ,0 4 0 5 ,0 5 1 0 ,0 6 6 5 ,0 8 3 0 ,0 1 0 6 0 ,0 1 4 1 0 ,0 1 4 ,0 2 3 ,0 3 4 ,0 5 6 ,0 9 0 ,0 1 3 7 ,0 2 1 ,0 3 6 ,0 5 1 ,0 8 5 ,0 1 3 5 ,0 2 1 0 ,0 2 9 0 ,0 3 8 5 ,0 5 8 5 ,0 8 1 0 ,0 1 0 2 0 ,0 1 2 5 5 ,0 1 5 6 0 ,0 2 0 3 5 ,0 4 2 ,0 6 3 ,0 1 0 1 ,0 1 6 5 ,0 2 5 5 ,0 3 4 0 ,0 4 8 0 ,0 6 7 0 ,0 9 1 0 ,0 1 1 8 0 ,0 1 4 0 5 ,0 1 7 8 0 ,0 2 3 1 0 ,0

T o ta l W e ight (A ppr o x.) kg/km 7 8 ,0 9 1 ,0 1 1 5 ,0 1 5 0 ,0 1 8 7 ,0 2 2 5 ,0 2 6 5 ,0 3 6 0 ,0 4 6 5 ,0 5 5 0 ,0 6 8 0 ,0 8 3 0 ,0 1 0 6 5 ,0 1 3 0 5 ,0 1 5 9 5 ,0 2 0 7 0 ,0 1 2 0 ,0 1 6 0 ,0 1 8 5 ,0 2 4 5 ,0 3 4 0 ,0 4 7 0 ,0 1 3 0 ,0 1 8 5 ,0 2 2 5 ,0 2 9 0 ,0 3 8 0 ,0 6 1 0 ,0 7 4 0 ,0 9 5 0 ,0 1 0 9 0 ,0 1 4 9 0 ,0 1 7 1 0 ,0 2 0 6 0 ,0 2 6 1 0 ,0 3 3 2 0 ,0 2 0 5 ,0 2 4 0 ,0 3 2 0 ,0 4 7 5 ,0 6 3 0 ,0 8 2 5 ,0 1 0 2 5 ,0 1 2 5 0 ,0 1 6 8 0 ,0 2 0 1 0 ,0 2 4 1 5 ,0 2 9 7 5 ,0 3 8 0 5 ,0

Pa cking: C a ble co il o r Dr um m o r N/m 100 100 100 100 9 /1 0 0 0 9 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0 1 8 /1 0 0 0 2 0 /1 0 0 0 100 100 100 100 1 2 /1 0 0 0 1 4 /1 0 0 0 1 0 0 ,0 1 0 0 ,0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 4 /5 0 0 1 4 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 2 0 /5 0 0 9 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 4 /5 0 0 1 4 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 8 /5 0 0 2 0 /5 0 0 2 2 /5 0 0

RE RE RE RM RM RM RM RM RM RM RM RM RM RM RM RM RE RE RE RE RM RM RE RE RE RE RE RM RM RM SM SM SM SM SM SM R E/R E R E/R E R E/R E R E/R E R M /R E R M /R E R M /R M S M /R M S M /S M S M /S M S M /S M S M /S M S M /S M

* Other dimensions and packing length are available on request.

Cable Factory FKN | 2012

SVT, SAVT
Power cable with PVC insulation and PVC sheath Rated Voltage: U0/U - 0.6/1 kV Standard: BDS 16291-85

According to BDS

Construction data: SAVT


Number of cores x Nominal Cross Section No x mm 4x2.5 4x4.0 4x6.0 4x10 4x16 4x25 4x35 4x50 4x70 4x95 4x120 4x150 4x185 4x240 RE RE RE RE RE RM RM RM SM SM SM SM SM SM Shape Overall Diameter (Approx.) max.mm 11,9 13,6 14,4 16,8 19,2 25,2 28,0 32,0 33,0 37,3 41,2 45,2 49,5 56,4

U0/U - 0.6/1kV
Total Weight (Approx.) kg/km 152,0 216,0 260,0 340,0 460,0 670,0 905,0 1180,0 1390,0 1860,0 2210,0 2710,0 3320,0 4110,0 Packing: Cable coil or Drum m or N/m 9/1000 10/1000 10/1000 12/1000 12/1000 14/1000 16/1000 14/500 14/500 16/500 16/500 18/500 20/500 22/500

Al weight (Approx.) kg/km 28,0 46,0 68,0 112,0 180,0 270,0 390,0 520,0 760,0 1060,0 1340,0 1650,0 2100,0 2720,0

5x2.5 5x4.0 5x6.0 5x10 5x16 5x25 5x35 5x50 5x70

RE RE RE RE RE RM RM RM RM

12,8 15,5 16,8 19,2 23,2 27,9 32,4 36,9 42,0

35,0 58,0 85,0 140,0 225,0 345,0 480,0 650,0 965,0

180,0 270,0 320,0 430,0 580,0 855,0 1210,0 1470,0 1955,0

9/1000 10/1000 12/1000 12/1000 14/1000 16/1000 18/1000 16/500 16/500

* Other dimensions and packing length are available on request.

Cable Factory FKN | 2012

SVTT, SAVTT
Power cable with PVC insulation and PVC sheath Rated Voltage: U0/U - 0.6/1 kV Standard:BDS 16291-85

Application Used for transferring and distribution of electrical power for switching installations and outdoor installation or for interior installation in rooms, in canals, tunnels, shafts or pits, at rated voltage Uo/U to 0,6/1 kV with frequency 50 Hz.

According to BDS

Technical Data:
Conductor resistance at 20o C: According to BDS 904-84 Core temperature, max: 70oC in operation Max. short circuit temperature: 160 oC , not more than 5 sec Rated voltage - U0 /U (Umax ): 0.6/1(1.2) kV Test voltage: AC - 4 kV; 50 Hz Temperature Range Fixed installation: -30C to +70C Flexible Installation: -5C to +50C Min. temperature of laying: -5C Bending radius, min. 10xDcable Specific insulation resistance at 70C: min, 1010 x cm For Cu conducor = 50 N/mm2 Max. permessible tensile stress with cable grip: For Al conducor = 30 N/mm2 Flame test: acc. to IEC 60332-1

Cable Structure:
Conductor: solid or twisted copper or Al wires, class 1 or 2 according to BDS 904-84 (IEC 60228).

Insulation: PVC compaund Core identification: according to BDS 16291 Cores assembly: cores stranded concentrically (cores stranded in concentric layers, for signal)

Inner sheath: PVC compaund Outer sheath: PVC compaund Color: Gray or black

On Request:
Fire propagation acc. IEC 60332-3 cat. A, B, C (SVT-FR) Hydrocarbon resistant outer sheath (RH). Termite and rodents protected outer sheath. Protected against direct sun irradiation (SVT_c) Oil resistant outer sheath.

Standard shapes and size of conductors:


RM - mutliwire round shaped conductor
Copper: 1.5mm - 630mm Aluminium: 50mm - 630mm

SM - mutliwire sector shaped conductor


Copper: Aluminium: 35mm - 300mm 50mm - 240mm RE - Solid Round Conductor

Available conductor sizes for power distibution:


Number of cores size of Cu conductors 1 core: 4mm2 - 630mm2 2 cores: 1.5mm2 - 120mm2 3 cores: 1.5mm2 - 300mm2 4 cores: 1.5mm - 300mm 3 cores+1 earth core: 25mm2 - 300mm2
2 2 2

size of Al conductors 25mm2 - 630mm2 25mm2 - 120mm2 25mm2 - 240mm2 25mm2 - 240mm2

+ 16mm - 150mm
2

25mm2 - 240mm2 25mm - 240mm


2 2

+ 25mm2 - 120mm2

5 cores: 1.5mm - 240mm Available conductor sizes for signaling and control

Number of cores: size of Cu conductors 7 -19 cores: (1.5 - 10 ) RE over 19 cores (1.5 - 2.5 ) RE

size of Al conductors / /

Packing
Standard Packing length on wooden drums: [ 500 m; 1000 m ]; Length Tolerance per drum 5%

Cable Factory FKN | 2012

SVTT, SAVTT
Power cable with PVC insulation and PVC sheath Rated Voltage: U0/U - 0.6/1 kV Standard:BDS 16291-85

According to BDS

C o n s t r u ct io n d a t a : S V T T U 0 / U - 0 .6 / 1 k V
Nu m b e r o f c o r e s x No m in a l C r o s s S e c tio n No x m m 1 x1 .5 1 x2 .5 1 x4 1 x6 1 x1 0 1 x1 6 1 x1 6 1 x2 5 1 x3 5 1 x5 0 1 x7 0 1 x9 5 1 x1 2 0 1 x1 5 0 1 x1 8 5 1 x2 4 0 1 x3 0 0 1 x4 0 0 1 x5 0 0 2 x1 .0 2 x1 .5 2 x2 .5 2 x4 .0 2 x6 .0 2 x1 0 2 x1 6 2 x2 5 2 x3 5 2 x5 0 3 x1 .0 3 x1 .5 3 x2 .5 3 x4 .0 3 x6 .0 3 x1 0 3 x1 6 3 x2 5 3 x3 5 3 x5 0 3 x7 0 3 x9 5 3 x1 2 0 3 x1 5 0 3 x1 8 5 3 x2 4 0 3 x2 .5 +1 .5 3 x4 .0 +2 .5 3 x6 .0 +4 .0 3 x1 0 +6 .0 3 x1 6 +1 0 3 x2 5 +1 6 3 x3 5 +1 6 3 x5 0 +2 5 3 x7 0 +3 5 S ha pe O ve r a ll Dia m e te r (A p p r o x.) m a x.m m 9 ,5 9 ,9 1 0 ,3 1 0 ,8 1 1 ,6 1 3 ,2 1 3 ,2 1 4 ,3 1 5 ,4 1 6 ,6 1 8 ,4 2 0 ,4 2 2 ,0 2 3 ,9 2 6 ,2 2 9 ,3 3 2 ,0 3 5 ,6 3 9 ,9 1 0 ,3 1 0 ,8 1 1 ,5 1 3 ,4 1 4 ,2 1 6 ,1 1 9 ,1 2 2 ,2 2 4 ,2 2 7 ,6 1 0 ,7 1 1 ,2 1 2 ,0 1 4 ,0 1 5 ,0 1 6 ,9 2 0 ,2 2 3 ,2 2 5 ,6 2 9 ,1 3 0 ,0 3 4 ,5 3 7 ,3 4 0 ,9 4 5 ,4 5 1 ,0 1 2 ,5 1 4 ,6 1 5 ,7 1 7 ,5 1 9 ,6 2 4 ,9 2 7 ,1 3 0 ,8 3 3 ,2 C o p p e r w e ig h t (A p p r o x.) kg /km 1 4 ,0 2 3 ,0 3 7 ,0 5 5 ,0 9 3 ,0 1 4 8 ,0 1 4 8 ,0 2 2 9 ,0 3 2 5 ,0 4 5 8 ,0 6 4 8 ,0 8 8 5 ,0 1 1 2 0 ,0 1 3 7 8 ,0 1 7 0 3 ,0 2 2 0 8 ,0 2 7 6 5 ,0 3 6 8 0 ,0 4 6 0 0 ,0 2 0 ,0 2 8 ,0 4 6 ,0 7 5 ,0 1 1 0 ,0 1 8 2 ,0 3 0 3 ,0 4 7 0 ,0 6 5 2 ,0 9 2 8 ,0 2 8 ,0 4 2 ,0 6 9 ,0 1 1 0 ,0 1 6 5 ,0 2 7 5 ,0 4 5 0 ,0 7 0 0 ,0 9 8 0 ,0 1 3 9 0 ,0 1 9 5 0 ,0 2 6 5 0 ,0 3 3 5 0 ,0 4 1 8 5 ,0 5 1 6 0 ,0 6 7 2 0 ,0 8 2 ,0 1 3 2 ,0 2 0 2 ,0 3 3 0 ,0 5 4 0 ,0 8 5 0 ,0 1 1 3 0 ,0 1 6 3 0 ,0 2 2 8 0 ,0 T o ta l W e ig h t (A p p r o x.) kg /km 1 0 8 ,0 1 2 4 ,0 1 4 3 ,0 1 7 0 ,0 2 2 1 ,0 3 0 8 ,0 3 0 8 ,0 4 1 2 ,0 5 2 4 ,0 6 5 9 ,0 8 8 0 ,0 1 1 6 1 ,0 1 4 3 0 ,0 1 7 5 2 ,0 2 1 5 6 ,0 2 7 3 5 ,0 3 4 1 2 ,0 4 3 2 4 ,0 5 4 3 2 ,0 1 3 2 ,0 1 5 8 ,0 1 8 2 ,0 2 5 0 ,0 3 0 5 ,0 4 1 8 ,0 5 8 7 ,0 8 7 5 ,0 1 2 3 5 ,0 1 5 1 0 ,0 1 4 5 ,0 1 7 0 ,0 2 1 4 ,0 2 9 5 ,0 3 7 4 ,0 5 2 0 ,0 7 6 5 ,0 1 1 2 5 ,0 1 4 6 5 ,0 1 9 6 0 ,0 2 4 5 0 ,0 3 3 1 0 ,0 4 0 6 5 ,0 4 9 5 0 ,0 6 1 6 0 ,0 7 9 5 0 ,0 2 3 0 ,0 3 3 0 ,0 3 9 0 ,0 5 9 0 ,0 8 9 5 ,0 1 3 0 3 ,0 1 6 6 1 ,0 2 2 2 8 ,0 2 8 5 9 ,0 P a c kin g : C a b le c o il o r Dr u m m o r N/m 100 100 100 100 100 100 100 1 0 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0 1 8 /1 0 0 0 2 0 /1 0 0 0 2 2 /1 0 0 0 100 100 100 100 100 100 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 0 0 ,0 1 0 0 ,0 1 0 0 ,0 1 0 0 ,0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 4 /5 0 0 1 4 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 8 /5 0 0 2 0 /5 0 0 9 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 4 /5 0 0 1 4 /5 0 0

RE RE RE RE RE RE RM RM RM RM RM RM RM RM RM RM RM RM RM RE RE RE RE RE RE RE RM RM RM RE RE RE RE RE RE RE RM RM RM SM SM SM SM SM SM R E /R E R E /R E R E /R E R E /R E R E /R E R M /R E R M /R E R M /R M S M /R M

* Other dimensions and packing length are available on request.

Cable Factory FKN | 2012

SVBT, SAVBT
Power cable with PVC insulation, armored with two steel tapes and PVC sheath Rated Voltage: U0/U - 0.6/1 kV Standard: BDS 16291-85

Application Used for transfer and distribution of electrical power for switching installation and in static installations, at rated voltage Uo/U to 0,6/1 kV with frequency 50 Hz. These cables are used for indoor installations, in the open air, in ditches, tunnels,canals and shafts.

According to BDS

Technical Data:
Conductor resistance at 20o C: According to BDS 904-84 Core temperature, max: 70oC in operation Max. short circuit temperature: 160 oC , not more than 5 sec Rated voltage - U0 /U (Umax ): 0.6/1 (1.2) kV Test voltage: AC - 4 kV; 50 Hz Temperature Range Fixed installation: -30C to +70C Flexible Installation: -5C to +50C Min. temperature of laying: -5C Bending radius, min. 15xDcable Specific insulation resisance at 70C: min. 1010xcm Max. permessible tensile stress with cable grip: P = D 3 N/mm D = Cable diameter (mm)
2 2

Cable Structure:
Conductor: solid or twisted copper or Al wires, class 1 or 2, acc.to BDS 904-84

Insulation: PVC compound Core identification: according BDS 16291 Cores assembly: cores stranded concentrically (cores stranded in concentric layers, for signal)

Inner sheat: PVC filling compound Armour: for multi-core cable: two steel tapes for single-core cable: two Aluminium tapes Sheath: PVC compound Color of sheath: black or gray

Standard shapes and size of conductors:


RM - mutliwire round shaped conductor
Copper: 1.5mm - 630mm Aluminium: 50mm - 630mm

On Request:
Fire propagation acc. IEC 60332-3 cat. A, B, C (SVT-FR) Hydrocarbon resistant outer sheath (RH). Termite and rodents protected outer sheath. Oil resistant outer sheath.

SM - mutliwire sector shaped conductor


Copper: Aluminium: 35mm - 300mm 50mm - 240mm RE - Solid Round Conductor

Available conductor sizes for power distibution:


Number of cores size of Cu conductors 1 core: 4mm2 - 630mm2 2 cores: 1.5mm2 - 120mm2 3 cores: 1.5mm2 - 300mm2 4 cores: 1.5mm - 240mm 3 cores+1 earth core: 25mm2 - 240mm2
2 2 2

size of Al conductors 25mm2 - 630mm2 25mm2 - 120mm2 25mm2 - 240mm2 25mm2 - 240mm2

+ 16mm - 150mm
2

25mm2 - 240mm2 25mm - 240mm


2 2

+ 25mm2 - 120mm2

5 cores: 1.5mm - 240mm Available conductor sizes for signaling and control

Number of cores size of Cu conductors over 7 cores (class 5) (1.5 - 2.5 )mm2 7 -19 cores: (1.5 - 4 ) RE; RM over 19 cores (1.5 - 2.5 ) RE; RM

size of Al conductors / / /

Packing
Standard Packing length on wooden drums: [ 500 m; 1000 m ]; Length Tolerance per drum 5%

Cable Factory FKN | 2012

SVBT, SAVBT
Power cable with PVC insulation, armored with two steel tapes and PVC sheath Rated Voltage: U0/U - 0.6/1 kV Standard: BDS 16291-85

According to BDS

C o n s t r u ct io n d a t a : S V B T
Num be r of core s x N o m in a l C r o s s S e c tio n No x m m 1 x1 0 1 x1 6 1 x2 5 1 x3 5 1 x5 0 1 x7 0 1 x9 5 1 x1 2 0 1 x1 5 0 1 x1 8 5 1 x2 4 0 2 x2 .5 2 x4 .0 2 x6 .0 2 x1 0 2 x1 6 2 x2 5 2 x3 5 2 x5 0 3 x1 .5 3 x2 .5 3 x4 .0 3 x6 .0 3 x1 0 3 x1 6 3 x2 5 3 x3 5 3 x5 0 3 x7 0 3 x9 5 3 x1 2 0 3 x1 5 0 3 x1 8 5 3 x2 4 0 3 x2 .5 +1 .5 3 x4 .0 +2 .5 3 x6 .0 +4 .0 3 x1 0 +6 .0 3 x1 6 +1 0 3 x2 5 +1 6 3 x3 5 +1 6 3 x5 0 +2 5 3 x7 0 +3 5 3 x9 5 +5 0 3 x1 2 0 +7 0 3 x1 5 0 +7 0 3 x1 8 5 +9 5 3 x2 4 0 +1 2 0 S hape O ve r a ll Dia m e te r (A p p r o x.) m a x.m m 1 2 ,5 1 3 ,5 1 5 ,3 1 6 ,4 1 7 ,6 1 9 ,9 2 1 ,6 2 3 ,3 2 5 ,1 2 7 ,7 3 0 ,6 1 2 ,7 1 4 ,6 1 5 ,7 1 7 ,3 1 9 ,3 2 3 ,7 2 5 ,9 2 9 ,4 1 2 ,4 1 3 ,2 1 5 ,4 1 6 ,4 1 8 ,3 2 0 ,3 2 5 ,0 2 7 ,5 3 1 ,3 3 2 ,2 3 6 ,7 3 9 ,5 4 3 ,1 4 7 ,6 5 3 ,4 1 3 ,7 1 6 ,0 1 7 ,1 1 9 ,1 2 1 ,2 2 6 ,3 2 9 ,1 3 3 ,0 3 5 ,4 4 0 ,2 4 3 ,7 4 8 ,1 5 3 ,3 5 9 ,6

U 0 / U - 0 .6 / 1 k V
T o ta l W e ig h t (A p p r o x.) kg / km 3 0 2 ,0 3 8 1 ,0 5 1 5 ,0 6 2 4 ,0 7 7 1 ,0 1 0 2 5 ,0 1 3 0 5 ,0 1 5 7 5 ,0 1 8 9 0 ,0 2 3 0 7 ,0 2 9 3 5 ,0 2 6 1 ,0 3 4 6 ,0 4 1 5 ,0 5 3 8 ,0 7 1 1 ,0 1 0 3 8 ,0 1 3 1 5 ,0 1 7 0 6 ,0 2 5 2 ,0 2 9 7 ,0 4 1 0 ,0 4 9 0 ,0 6 6 0 ,0 8 8 0 ,0 1 3 2 6 ,0 1 6 8 5 ,0 2 2 1 0 ,0 2 7 5 4 ,0 3 6 7 0 ,0 4 4 5 2 ,0 5 3 6 8 ,0 6 6 3 5 ,0 8 5 0 1 ,0 2 9 5 ,0 4 5 0 ,0 5 4 5 ,0 7 3 6 ,0 9 9 6 ,0 1 5 1 4 ,0 1 8 9 0 ,0 2 4 9 9 ,0 3 2 1 2 ,0 4 1 8 0 ,0 5 2 6 0 ,0 6 2 2 0 ,0 7 7 8 6 ,0 9 9 1 0 ,0 P a c kin g : C a b le c o il o r Dr u m m o r N/m 9 /1 0 0 0 9 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 8 /1 0 0 0 9 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0 9 /1 0 0 0 9 /1 0 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 4 /5 0 0 1 4 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 8 /5 0 0 2 0 /5 0 0 1 0 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 2 /1 0 0 0 1 4 /1 0 0 0 1 6 /1 0 0 0 1 6 /1 0 0 0 1 4 /5 0 0 1 6 /5 0 0 1 6 /5 0 0 1 8 /5 0 0 1 8 /5 0 0 2 0 /5 0 0 2 2 /5 0 0

C o p p e r w e ig h t (A p p r o x.) kg / km 9 3 ,0 1 4 8 ,0 2 2 9 ,0 3 2 5 ,0 4 5 8 ,0 6 4 8 ,0 8 8 5 ,0 1 1 2 0 ,0 1 3 7 8 ,0 1 7 0 3 ,0 2 2 0 8 ,0 4 6 ,0 7 5 ,0 1 1 0 ,0 1 8 2 ,0 3 0 3 ,0 4 7 0 ,0 6 5 2 ,0 9 2 8 ,0 4 2 ,0 6 9 ,0 1 1 0 ,0 1 6 5 ,0 2 7 5 ,0 4 5 0 ,0 7 0 0 ,0 9 8 0 ,0 1 3 9 0 ,0 1 9 5 0 ,0 2 6 5 0 ,0 3 3 5 0 ,0 4 1 8 5 ,0 5 1 6 0 ,0 6 7 2 0 ,0 8 2 ,0 1 3 2 ,0 2 0 2 ,0 3 3 0 ,0 5 4 0 ,0 8 5 0 ,0 1 1 3 0 ,0 1 6 3 0 ,0 2 2 8 0 ,0 3 1 2 0 ,0 4 0 1 0 ,0 4 8 5 0 ,0 6 0 7 0 ,0 7 8 4 0 ,0

RE RM RM RM RM RM RM RM RM RM RM RE RE RE RE RE RM RM RM RE RE RE RE RE RE RM RM RM SM SM SM SM SM SM R E /R E R E /R E R E /R E R E /R E R E /R E R M /R E R M /R E R M /R M S M /R M S M /S M S M /S M S M /S M S M /S M S M /S M

* Other dimensions and packing length are available on request.

Cable Factory FKN | 2012

SVBT, SAVBT
Power cable with PVC insulation, armored with two steel tapes and PVC sheath Rated Voltage: U0/U - 0.6/1 kV Standard: BDS 16291-85

C onstruction da ta : SVBT
Number of cores x Nominal C ross Section No x mm 4x 1. 5 4x 2. 5 4x 4. 0 4x 6. 0 4x 10 4x 16 4x 25 4x 35 4x 50 4x 70 4x 95 4x 120 4x 150 4x 185 4x 240 RE RE RE RE RE RE RM RM RM SM SM SM SM SM SM Shape O v erall Diameter (A pprox . ) max . mm 13, 2 14, 1 16, 5 17, 6 19, 8 22, 0 27, 4 30, 4 34, 4 36, 6 42, 0 45, 4 50, 0 55, 2 62, 2

U 0/U - 0.6/1k V
Total W eight (A pprox . ) kg/km 286, 0 350, 0 480, 0 580, 0 800, 0 1080, 0 1642, 0 2175, 0 2762, 0 3478, 0 4791, 0 5800, 0 7975, 0 8117, 0 10080, 0

According to BDS

C opper weight (A pprox . ) kg/km 55, 0 92, 0 146, 0 218, 0 363, 0 582, 0 925, 0 1303, 0 1857, 0 2601, 0 3540, 0 4460, 0 5575, 0 6880, 0 8928, 0

Packing: C able coil or Drum m or N/m 9/1000 10/1000 12/1000 12/1000 12/1000 14/1000 16/1000 14/500 14/500 16/500 16/500 18/500 20/500 22/500 24/500

5x 1. 5 5x 2. 5 5x 4. 0 5x 6. 0 5x 10 5x 16 5x 25 5x 35 5x 50 5x 70

RE RE RE RE RE RE RM RM RM RM

14, 0 15, 2 17, 7 19, 2 21, 4 24, 0 30, 7 33, 4 38, 7 43, 7

69, 0 114, 0 182, 0 257, 0 455, 0 745, 0 1165, 0 1640, 0 2330, 0 3260, 0

331, 0 413, 0 567, 0 708, 0 970, 0 1324, 0 2048, 0 2758, 0 3840, 0 5128, 0

10/1000 10/1000 12/1000 12/1000 14/1000 14/1000 18/1000 18/1000 16/500 18/500

7x 1. 5 8x 1. 5 10x 1. 5 12x 1. 5 14x 1. 5 16x 1. 5 19x 1. 5 24x 1. 5 30x 1. 5 37x 1. 5

RE RE RE RE RE RE RE RE RE RE

15, 2 16, 2 18, 3 18, 8 19, 5 20, 5 21, 3 24, 5 25, 7 27, 7

96, 0 110, 0 140, 0 165, 0 195, 0 220, 0 260, 0 330, 0 410, 0 506, 0

421, 0 465, 0 571, 0 610, 0 675, 0 740, 0 814, 0 1042, 0 1180, 0 1370, 0

10/1000 12/1000 12/1000 12/1000 12/1000 14/1000 14/1000 14/1000 16/1000 16/1000

7x 2. 5 8x 2. 5 10x 2. 5 12x 2. 5 14x 2. 5 16x 2. 5 19x 2. 5 24x 2. 5 30x 2. 5 37x 2. 5

RE RE RE RE RE RE RE RE RE RE

16, 3 17, 3 19, 9 20, 4 21, 4 22, 6 23, 5 27, 0 28, 4 30, 8

160, 0 182, 0 228, 0 275, 0 320, 0 365, 0 435, 0 546, 0 685, 0 845, 0

508, 0 570, 0 719, 0 778, 0 838, 0 941, 0 1050, 0 1354, 0 1551, 0 1820, 0

12/1000 12/1000 12/1000 12/1000 14/1000 14/1000 14/1000 16/1000 16/1000 18/1000

Cable Factory FKN | 2012

SVBT, SAVBT - 6kV


PVC-insulated cables with PVC sheath and steel tape armour Rated Voltage: U0/U - 3.6/6 kV Standard: BDS 16291-85

According to BDS

Application
The one-core and three-core cables with insulation of polyvinylchloride (PVC) are designed for distribution of electrical power and for electrical supply of consumers with nominal voltage Uo/U 3.6/6 kV and frequency 50 Hz. They are suitable for distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, for indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
Technical Data:
Conductor resistance at 20o C: (IEC60228) class 2 According to BDS904

Cable Structure:
Conductor: Cu and Al stranded compacted, according to BDS 904 (IEC60228) class 2 Insulation: PVC compound Color of insulation: natural Cores assembly: insulated cores are twisting together Inner sheat: PVC filling compound Armour: for one-core cable: two aluminium tapes for three-core cable: two galvanized steel tapes Sheath: PVC compound type P-1 Color of sheath: black or gray

Core temperature, max: 70oC in operation Max. short circuit temperature: for cross-section up to 300mm2 160 oC , not more than 5 sec for cross-section above 300mm2 140 oC , not more than 5 sec Rated voltage - U0 /U (Umax ): 3.6/6(7.2) kV Test voltage: AC - 11 kV; 50 Hz Temperature Range: -30C to +70C Min. temperature for laying and manipulation with cables: -5C Bending radius, min. 15xDcable max Permessible tensile stress with cable grip: P = D2 3 N/mm2 D = Cable diameter (mm)

Additional information and technical data:


Available conductor sizes for power distibution: Number of cores size of Cu conductors size of Al conductors 1 core: 3 cores: 35mm2 - 500mm2 35mm - 185mm
2 2

On Request:
Fire propagation acc. IEC 60332-3 Hydrocarbon resistant outer sheath (RH). Termite and rodents protected outer sheath. Oil resistant outer sheath.

35mm2 - 630mm2 35mm - 185mm


2 2

RM - Multiwire conductor round shape class 2 SM - Multiwire sector shaped conductor class 2

Packing
Standard Packing length on wooden drums: [ 500 m; 1000 m ];
Construction data: SVBT, SAVBT U0/U - 3.6/6kV
Number of cores x Nominal Cross Section No x mm 3x25RM/6 3x35RM/6 3x50SM/6 3x70SM/6 3x95SM/6 3x120SM/6 3x150SM/6 3x185SM/6 3x240SM/6 Nonminal insulation Thickness mm 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 Armour section equivalent to copper mm2 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 Overall Diameter (Approx.) max.mm 37,7 40,0 43,2 44,6 45,6 48,6 51,6 55,1 60,0 Copper weight SVBT (Approx.) kg/km 700,0 630,0 1390,0 1950,0 2650,0 3350,0 4185,0 5160,0 6720,0 Total Weight -SVBT (Approx.) kg/km 2685,0 3155,0 3600,0 4170,0 5080,0 5980,0 6920,0 8175,0 10110,0 AL weight SAVBT (Approx.) kg/km 210,0 290,0 385,0 585,0 810,0 1020,0 1255,0 1560,0 2035,0 Total Weight -SAVBT (Approx.) kg/km 2150,0 2535,0 2700,0 2945,0 3380,0 3818,0 4250,0 4830,0 5660,0 Packing: Cable coil or Drum m or N/m 16/500 16/500 16/500 18/500 18/500 20/500 20/500 22/500 24/500

* Other dimensions and packing length are available on request.

Cable Factory FKN | 2012

A, AC, ACO
Bare Aluminium conductors and aluminium conductors, steel reinforced Standards: BDS 1133-89

Application For overhead electric power transmission

According to BDS

Construction data
Nominal Cross Section mm 16 25 35 50 70 95 120 150 185 240 300 400 500 630 Number of Wires and Diameter No x mm 7x1.70 7x2.12 7x2.50 7x3.0 7x3.55 7x4.12 19x2.8 19x3.15 19x3.5 19x4.0 37x3.2 37x3.69 37x4.15 61x3.55 Cable diameer mm Type A 5.1 6.36 7.5 9.0 10.65 12.36 14.0 15.75 17.5 20.0 22.4 25.83 29.05 31.95 2.838 4.249 5.778 7.944 10.663 14.185 18.783 23.351 28.48 36.292 46.927 60.895 76.073 88.031 1.804 1.16 0.834 0.579 0.414 0.307 0.246 0.195 0.158 0.121 0.097 0.073 0.058 0.048 44 68 94 136 190 256 322 407 503 657 820 1091 1380 1668 Breaking load min kN Electrical resistance at 20C max /km Net weight aprox. kg/km

Construction data
Nominal Cross Section mm Number of Wires and Diameter No x mm Al 16 25 35 50 70 95 120 150 185 240 300 400 150 185 240 300 400 500 630 St 5.4 6.6 8.4 9.6 11.4 13.5 15.16 16.96 18.98 21.56 24.24 27.96 16.60 18.40 21.56 23.52 27.24 30.22 33.14 5.83 8.652 13.386 17.02 23.59 32.986 46.582 57.19 70.47 89.038 110.776 149.204 Type ACO 24x2.8+7x1.8 24x3.1+7x2.0 24x3.59+7x2.4 54x2.62+7x2.6 54x3.04+7x3.0 54x3.37+19x2.0 54x3.69+19x2.2 46.172 56.293 77039,00 93.477 120.481 150.024 179.5 0.195 0.159 0.119 0.099 0.074 0.060 0.050 408 500 607 805 1083 1332 1596 139 172 248 291 388 469 568 547 672 918 1096 1471 1801 2164 1.882 1.26 0.778 0.595 0.422 0.301 0.251 0.196 0.16 0.121 0.098 0.073 42 62 101 132 187 262 319 407 500 657 814 1092 20 30 48 63 88 124 172 209 269 338 441 568 62 92 149 195 275 386 491 616 796 995 1255 1660 Cable diameter mm Breaking load min kN Type AC 6x1.8+1x1.8 6x2.2+1x2.2 6x2.8+1x2.8 6x3.2+1x3.2 6x3.8+1x3.8 6x4.5+1x4.5 28x2.29+7x2.0 28x2.59+7x2.2 28x2.87+7x2.5 28x3.29+7x2.8 28x3.66+7x3.2 28x4.24+19x2.2 Electrical resistance at 20C max /km Net weight of Al aprox. kg/km Net weight of St aprox. kg/km Net weight of AC rope kg/km

Cable Factory FKN | 2012

SHEmT-et, SAHEmT-et
Al or Cu conductor, XLPE insulation, Cu screen, PVC sheath Rated Voltage: U0/U(AC) - 0.6/1kV; U(DC) - 3kV Standard: BDS 2581-86

According to BDS

Application
The single-core cables with cross-linked polyethylene (XLPE) insulation Cu screen are used mainly for electrical systems with nominal voltage 3 kV and are applicable for electrical public and metropolitan transportation. They can be used for transfer, distribution and electrical power supply with nominal voltage Uo/U 0.6/1 kV and frequency of 50Hz. The cables are for fixed assembly in lines with unlimited difference levels, underground, in cable ducts, tunnels and conduits, over shelves and grilles outdoor under shelter.

Technical Data:
Conductor resistance at 20o C:

Cable Structure:
(IEC60228) class 2
According to BDS904
Conductor: Al or Cu solid round multi cores acc.to BDS 2581-86( IEC 60228 ) class2

Core temperature, max: 90 C in continuous operation Max. short circuit temperature: 250 oC , not more than 5 sec Overload temperature: 130oC /100h per year max. Nominal voltage Uo/U (Umax): alternating: 0.6/1(1.2) kV constant: 3 kV Test voltage, AC (50Hz) - 5 min Between core and screen - 3.5kV Bending radius, min 15xDcable Temperature of laying: no less than - 5 oC Temperature of exploitation: -30 to 50 oC Al cores - 30*S Force of strain in laying, N max. Cu cores - 50*S where: S is cross section of cores in mm2

Insulation: XLPE compound Metal screen: copper tapes Sheath: PVC compound type P-5 Color of sheath: red

Standard shape of conductor:


RM - class 2 conductor acc. to BDS 904

Packing
Standard Packing length on wooden drums: [ 500 m; 1000 m ];
Additional information and technical data:
Construction data: SAHEmT-et U0/U - 0.6/1kV, U(=) - 3kV
Number of cores x Nominal Cross Section No x mm 1x95RM 1x120RM 1x150RM 1x185RM 1x240RM 1x300RM 1x400RM 1x500RM Nonminal insulation Thickness mm 2,5 2,5 2,5 2,5 2,5 3,0 3,0 3,0 Nominal cross section of screen, min. mm2 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 Nonminal Sheath Thickness mm 2,5 2,5 2,5 2,5 2,5 3,0 3,0 3,0 Overall Diameter (Approx.) max.mm 22,9 24,3 25,8 27,5 29,9 34,2 39,9 42,0 Al weight (Approx.) kg/km 260,0 325,0 405,0 510,0 665,0 830,0 1060,0 1410,0 Total Weight (Approx.) kg/km 735,0 855,0 943,0 1084,0 1287,0 1628,0 1920,0 2323,0 Packing: Cable coil or Drum m or N/m 14/1000 14/1000 16/1000 16/1000 16/1000 18/1000 22/1000 22/1000

* Other dimensions and packing length are available on request.

Cable Factory FKN | 2012

PVO
Copper conductor and PVC insulation Nominal Volage: Uo/U - 0.6/1kV Standard: FN KI 06 003-06

Application For Connecting home and other electrical installations to open air electrical distribution network.

According to BDS

T echnical Data:
Conductor resistance: according to BDS 904-84 class1 Permissable conductor temperature: 70C Working Voltage U0 / U: 0.6/1kV Test Voltage A C (50Hz): 4kV Temperature of exploitation: - 30 o C to + 50 o C Minimum bending radius: 6 x cable diameter

C a b le S t r u ct u r e :
c o p p e r w ir e s a c c o r d in g to Co nduct o r: B D S 9 0 4 - 8 4 ( IE C 6 0 2 2 8 ) c la s s 1 - 6 m m 2 a n d 1 0 m m 2 c la s s 2 - 1 6 m m 2 to 7 0 m m 2 In s u la t io n : P V C c o m p o u n d , ty p e Ia c c o r d in g to B D S 5 7 9 2 - 8 4 In s u la t io n c o lo r : b la c k

Constriction Data:
Nominal cross section Outer diameter approx. Copper weight approx. Cable weightapprox. mm x mm kg/km kg/km mm2 6 10 16 25 35 50 70 4.8 6.0 7.5 9.3 10.4 12.1 13.9 55 91 152 225 315 420 620 73 120 191 300 400 530 745

Packing
Packing length in cable coils and wooden drums: [ on request ];

Cable Factory FKN | 2012

PVU-A1
Copper conductor, PVC insulation, stranded wires Nominal Volage: Uo/U - 300/500 V; Uo/U - 450/750 V Standard: BDS 4305-90

According to BDS

Application
Installation in lighting installations, power and distribution systems, machines, apparatus and other.

T echnical Data:
Conductor resistance: according to BDS 904-84 class1 Permissable conductor temperature: 70C Working Voltage U0 / U: 0.35 mm2 to 1 mm2 300/500 V 1.5 mm2 to 4 mm2 450/750 V Test Voltage A C (50Hz): 0.35 mm2 to 1 mm2 2000 V 1.5 mm2 to 4 mm2 2500 V Temperature of exploitation: - 25 o C to + 50 o C Minimum bending radius: 6 x cable diameter Testing: BDS 4305-90

Cable Structure:
Conductor: copper wires according toBDS 904-84, class 1 (IEC 60228) Insulation: PVC compound, type I-2according to BDS 5792-84 Cores assembly: Insulated cores are twisted

Color coding:
number of cores 2 core 3 core With yellow/green yellow/green , blue , brown Without yellow/green Blue, brown brown ,black , gray

Constriction Data:
N x mm Outer diameter approx. Copper weight approx. Wire weight approx. mm x mm kg/km kg/km 4.0 4.2 4.5 4.8 5.8 7.0 7.8 4.3 4.6 5.0 5.2 6.2 7.5 8.4 6.6 9.2 13.4 18.4 27.6 44.0 71 11 13.8 20.1 27.6 41.4 66 106.5 16 19 24 31 45 70 100 23 28 39 49 75 115 157

PVU-A1 300/500V 2x0.35 2x0.5 2x0.75 2x1.0 2x1.5 2x2.5 2x4 PVU-A1 450/750V 3x0.35 3x0.5 3x0.75 3x1.0 3x1.5 3x2.5 1x4

Packing
Packing length in cable coils: [ on request ];

Cable Factory FKN | 2012

PVU-A2
Copper conductor, PVC insulation, stranded wires Nominal Volage: Uo/U - 300/500 V; Uo/U - 450/750 V Standard: BDS 4305-90

Application Installation in lighting installations, power and distribution systems, machines, apparatus and other.

According to BDS

Technical Data:
Conductor resistance: according to BDS 904-84 class1 Permissable conductor temperature: 70C Working Voltage U0 /U: 0.35 mm2 to 1 mm2 300/500 V 1.5 mm2 to 4 mm2 450/750 V Test Voltage AC (50Hz): 0.35 mm2 to 1 mm2 2000 V 1.5 mm2 to 4 mm2 2500 V Temperature of exploitation: - 25oC to + 50oC Minimum bending radius: 6 x cable diameter

Cable Structure:
Conductor: copper wires according toBDS 904-84, class 5 (IEC 60228) Insulation: PVC compound, type I-2according to BDS 5792-84 Cores assembly: Insulated cores are twisted

Color coding:
number of cores 2 core 3 core With yellow/green yellow/green , blue , brown Without yellow/green Blue, brown brown ,black , gray
N x mm PVU-A1 300/500V 2x0.35 2x0.5 2x0.75 2x1.0 2x1.5 2x2.5 2x4 PVU-A1 450/750V 3x0.35 3x0.5 3x0.75 3x1.0 3x1.5 3x2.5

Constriction Data:
Outer diameter approx. Copper weight approx. Wire weight approx. mm x mm kg/km kg/km 4.1 4.5 4.8 5.1 6.2 7.3 8.4 4.5 4.9 5.2 5.6 6.7 7.9 9.1 7.0 9.2 15 19.2 28.0 48.0 76.0 10.0 14.0 20.5 27.6 41.4 66 107 15.5 18 25 29 44 68 100 23 28 39 49 75 115 157

Packing

1x4

Packing length in cable coils and wooden drums: [ on request ];

Cable Factory FKN | 2012

PVV-MB1
Flat webbed house wires Rated Voltage: U0/U - 220/380 V Standard: BDS 4305-90

According to BDS

Application
For installation in dry environments only, both in and beneath plaster. The cables must be covered by plaster along their entire length. Installation in cavities of concrete, stone or non-inflammable building materials is allowed. Installations notes: - The cables cannot be installed on flammable building materials, immediately next to or under wire mesh or similar materials.For mounting, only materials and procedure shall be used which preclude a deformation or damage of the insulation, e. g. gypsum plaster, adhesives, nails with insulating washers. - Flat house wire cables may only be installed beneath gypsum board if these are subsequently fixed using gypsum plaster. The cables may not be bundled together. Bunching flat webbed building wires to insertion points for electrical equipments is not considered as bunching.
Te c hnic a l Da t a : Co nduc t o r r e s is t a nc e a t 20 o C: a ccording to BDS 904-84 cla ss 1 Co r e t e mpe r a t ur e , ma x: 70 o C in ope ra tion Ma x. s ho r t c ir c uit t e mpe r a t ur e : 160 o C , not m ore tha n 5 se c Ra t e d v o lt a ge - U0 / U: 220/380 V Te s t v o lt a ge : A C - 2 kV ; 50 Hz Te mpe r a t ur e Ra nge : -20C to +70C Be nding r a dius , min. 6xDca ble Spe c ific ins ula t io n r e s is t a nc e a t 70 C: m in, 10 1 0 x cm

Cable Structure:
Conductor: copper wires according to BDS 904-84,class 1 (IEC 60228) Insulation: PVC compound, type I-2according to BDS 5792-84 Core identification: according to DIN VDE 0293 Cores assembly: Insulated cores are parallel in between in a unified sheath Sheath: PVS compound, type P-1according to BDS 5792-84 Color of sheath: white, gray, black

Color coding:
number of cores 2 core 3 core 4 core 5 core With yellow/green yellow/green , blue , brown yellow/green , brown ,black , gray yellow/green , blue , brown , black, gray Without yellow/green Blue, brown brown, black, gray blue, brown, black, gray black , blue , brown , black , gray

Construction data PVV-MB1


Num. of Cores and Nominal Cross Section No x mm 2 x 1.5 2 x 2.5 2x4 3 x 1.5 3 x 2.5 3x4 4 x 1.5 4 x 2.5 5 x 1.5 5 x 2.5 Shape Overall Diameter (Approx.) max.mm 3.8x11.2 4,6x12.8 5.2x14.4 3.8x18.7 4.5x21 5.2x23.7 3.8x32.8 4.5x29 3.8x32.8 4.5x36.7

U0/U - 220/380V
Total Weight (Approx.) kg/km 65 95 135 100 145 206 135 196 170 246 Packing: Cable coil or Drum m or N/m 100 100 100 100 100 100 100 100 100 100

Copper weight (Approx. ) kg/km 29 48 76 43 72 115 58 96 72 120

RE RE RE RE RE RE RE RE RE RE

Cable Factory FKN | 2012

Overhead cables

N1XD4-AR, X00-A, AL/R


XLPE insulated cable bunch without supporting neutral conductor Rated voltage: Uo/U - 0,6/1 kV Standard: HD 626/part 4E; N.C5.250; NF C 33-209

Overhead Cables

Application The power cables with XLPE insulation for overhead lines - self-supporting type are designed for transfer, distribution and supply with electrical power in networks with or without Public Lighting (between Pole to Pole) for low voltage Uo/U-0.6/1 kV. In constructions for distribution networks these cable permit suspension on facades and trees. They allow crossing of forest areas without cutting and maintenance of openings in the wood. The suspension and support of the whole bundle is carried out by the phase (basic) insulated current-conductive.

Technical Data:
Operating temperature: 90 C Short-circuit temperature: 250 C (5 s. maximum duration) Nominal voltage : 0.6/1 kV Highest system voltage AC, not more than: 1.2 kV Test voltage AC - 50 Hz: 4 kV (3 kV acc. To N.C5.250) Temperature of using: -20C to +90C Temperature of laying, min: -20C Bending radius, min:
o o

Cable Structure:
Phases Conductors: Compacted round shaped aluminium rope Neutral conductor: Compacted round shaped aluminium rope Pilot cores (optional): Copper solid wires Insulation: XLPE Color: Black

Cores twisted into a bundle include:


Cable lay up:

Phase cores Neutral core Two additional pilot cores Phase cores are identified by numbers:

for cable - 14xDcable for one core - 6xDcore 16mm2- 1.91 /m

Standard identification of cores: Cores for street lighting are identified by letters: R1 and R2

Neutral core is identified by longitudinal convexity an insulation.

Conductor resistance at 20 C: 25mm2 - 1.20 /m

Breaking force min.

1.5mm2 - 12.1 /m (pilot core) 16mm2- 1.9kN 25mm2 - 3.0kN

Packing
Standard Packing length on wooden drums: [ 500 m; 1000 m ];
X00-A; N1XD4-AR; AL/R
Num. of Cores and Nominal Cross Section No x mm 2 x 16 (SP) 2 x 25 (SP) 4 x 16 (TP) 4 x 25 (TP) 2 x 16 + 2 x 1.5 (SP) 2 x 25 + 2 x 1.5 (SP) 4 x 16 + 2 x 1.5 (TP) 4 x 25 + 2 x 1.5 (TP) Average tickness Approx. external of insulating diameter sheath mm mm 1,2 1,4 1,2 1,4 1,2/1,2 1,4/1,2 1,2/1,2 1,4/1,2 15 18 18 22 16 19,5 20 24 Approx. Total Weight kg/km 140 213 280 426 191 270 330 476

U0/U - 0.6/1 kV
Voltage drop with cos=0.8 (V/A/km) Phase conductor 3,98 2,54 3,44 2,2 3,98 2,54 3,44 2,2 Packing on wooden drum N x m 1000 1000 1000 1000 1000 1000 1000 1000

Max. continuous current-carring capacity in phases conductors. Conductors temperature: 90C (A) In duct through walls 72 95 63 83 72 95 63 83 In Air at 30C 93 122 83 111 93 122 83 111 Along house fronts 83 109 74 100 83 110 74 100

(SP) - Single-Phase System (TP) - Three-Phase System

Cable Factory FKN | 2012

N1XD9-AR, X00/0-A, AL/R


XLPE insulated cable bunch with supporting neutral conductor Rated Voltage: U0/U - 0.6/1 kV Standard: HD 626/part 6E; N.C5.250; N.C5.251; NF C 33-209

Overhead Cables

Application The power cables with XLPE insulation for overhead lines - self-supporting type are designed for transfer, distribution and supply with electrical power in networks low voltage Uo/U-0.6/1 kV. In constructions for distribution networks these cable permit suspension on fasades and trees.They allow crossing of forest areas without cutting and maintenance of openings in the wood.The suspension and support of the whole bundle is carried out by a supporting insulated neutral wire of aluminium steel conductor or of aluminium alloy.
Cable Structure:
Phases Conductors: compacted round shaped aluminium rope compacted round shaped rope of aluminium alloy AlMgSi of 95mm2, Neutral conductor-Self Supporing: 70mm2 or 54.6mm2 nominal cross-sectio, or aluminium alloy AlMg 1 (1% magnesium) of 71.5mm2 nominal cross-sectio, or Al/Fe core of 50/8mm2 or 61/10mm2 Public lighting, optional: compacted round shaped aluminium rope, 16 and 25mm2 Pilot cores, optional: copper solid wire, 1.5 mm2 Insulation: XLPE for all elements of cable Color: black Phase core and cores for street lighting twisted Cable lay up: in a bunch around supporting neutral core. Phase cores are identified by numbers: 1,2,3 Standard identification of cores: Cores for street lighting are identified by letters: R1 and R2 Neutral core is identified by longitudinal convexity an insulation.

T e ch n ica l D a t a :
O pe r a ting te m pe r a tur e : 9 0 o C S ho r t- cir cuit te m p. o n pha s e co r e s : 2 5 0 o C (5 s . m a xim um dur a tio n) S ho r t- cir cuit te m p. o n ne utr a l co r e : 1 3 0 o C (5 s . m a xim um dur a tio n) No m ina l vo lta ge : 0 .6 /1 kV Highe s t s ys te m vo lta ge , A C : 1 .2 kV T e s t vo lta ge A C - 5 0 Hz : 4 kV (3 kV a cc. T o N.C 5 .2 5 0 ) T e m pe r a tur e o f us ing: - 2 0 C to +9 0 C T e m pe r a tur e o f la ying, m in: - 2 0 C Be nding r a dius , m in: fo r ca ble - 1 4 xDca ble fo r o ne co r e - 6 xDco r e

S pe cific vo lum e r e s is ta nce a t 9 0 C : m in, 1 0 1 4 x cm

Packing
Standard Packing length on wooden drums: [ 500 m; 1000 m ];
X00/O-A; N1XD9-AR; AL/R
Type Nominal Cross Section mm2 16 25 35 Phase conductor 50 70 95 120 150 54.6 70 Neutral conductor 95 71.5 50/8 61/10 Pilot core 1.5 Min. number of wires 7 7 7 7 12 19 19 19 7 7 19 7 6+1 6+1 1 Max.electrical resistance /km 1,91 1,2 0,868 0,641 0,443 0,32 0,253 0,206 0,63 0,5 0,343 0,47 0,59 0,51 Diameter od conductors min. (mm) 4,6 5,8 6,8 7,9 9,7 11 12 13,7 9,2 10 12,2 9,8 9,2 10,5 / max. (mm) 5,1 6,3 7,3 8,4 10,2 12 13,1 15 9,6 10,2 12,9 10.6 9,7 / 1,5

U0/U - 0.6/1 kV
Breaking Insulation Force, thickness min kN / / / / / / / / 16,6 20,5 27,5 15,5 17 17 mm 1,2 1,4 1,6 1,6 1,8 1,8 1,8 1,8 1,6 1,5 1,6 1,8 1,5(1,6) 1,8 1,2 Outside diameter min. (mm) 7 8,6 10 11,1 13,3 14,6 15,6 17,3 12,3 12,9 15,3 14,2 12,7 14 3,7 max. (mm) 7,8 9,4 10,9 12 14,2 15,7 16,7 18,6 13 13,6 16,3 14,6 12,9 15 4,2

X00/O-A; N1XD9-AR; AL/R


Num. of Cores and Nominal Cross Section No x mm 3x25+54.6(TP) 3x35+Kx16+54.6(TP) 3x50+Kx16+54.6(TP) 3x70+Kx16+54.6(TP) 3x70+Kx25+54.6(TP) 3x70+Kx16+70(TP) 3x95+Kx16+70(TP) 3x120+Kx16+70(TP) 3x120+Kx16+95(TP) 3x150+Kx16+70(TP) 3x150+Kx16+95(TP) 3x70+71.5(TP) 3x70+Kx16+71.5(TP) 3x70+Kx16+50/8(TP) 3x70+Kx16+61/10(TP)

U0/U - 0.6/1 kV

Max. continuous current-carrying capacity in phase conductors and in Public lighting conducor at temp. 90C: in Air at 30C stretched between in air at poles 30C 112 / 138 168 213 213 213 258 300 300 344 344 213 213 213 213 83 83 83 111 83 83 83 83 83 83 / 83 83 83

*Natural conductors: 71.5 mm; 61/10; 50/8 - only for type X00/0-A

(TP) - Three-Phase

Cable Factory FKN | 2012

NFA2X
Al conductors, XLPE insulation, twisted cable Rated Voltage: U0/U - 0.6/1 kV Standard:HD 626/part 4F

Overhead Cables

Application The power cables with XLPE insulation for overhead lines - self-supporting type are designed for transfer, distribution and supply with electrical power in networks with or without Public Lighting (between Pole to Pole) for low voltage Uo/U-0.6/1 kV. In constructions for distribution networks these cable permit suspension on facades and trees. They allow crossing of forest areas without cutting and maintenance of openings in the wood. The suspension and support of the whole bundle is carried out by the phase (basic) insulated currentconductive.
Technical Data:
Operating temperature: 80oC Short-circuit temperature: 130oC Nominal voltage : 0.6/1 kV Highest system voltage AC, not more than: 1.2 kV Test voltage C - 5 min: 4 kV Max. operating temperature, fixed: 20 C to 80 C Temperature of laying: no less than - 10 C, recommended 15 C Bending radius: 18xDcable 16 - 1.91 /m; 50 - 0.641/m Conductor resistance at 20 C: 25 - 1.20 /m; 70 - 0.443 /m 35 - 0.868/m; 95 - 0.320/m 16 - 2.84 kN; 50 - 8.45 N Breaking force min.: 25 -4.17 kN; 70 -11.32 N 35 - 5.78 kN; 95 - 15.68 kN
o o

Cable Structure:
Phases Conductors: (M): compacted round shaped aluminium rope Neural conductor: (N): compacted round shaped aluminium rope Conductors for lighting: (R) : compacted round shaped aluminium rope Insulation: XLPE with min. 2% carbon blackcontent type TIX-2 black Color: constructions twisted into a bundle include: phase cores () neutral (N) Cable lay up (cable constructions): one, two, or three additional reduced insulated cores for lighting ( R )

Cores identification: with color printing or with longitudinal ribs acc. To HD 626 S1

Packing
Standard Packing length on wooden drums: [ 500 m; 1000 m ];

Standard constructions and currents:


One core: 1x(16 - 95)mm2 Two cores: 2x(16 - 95)mm2 Four cores: 4x(16 - 95)mm2 Four cores with one lighting conductor: 4x(16 - 95)mm2+1x(16 - 35)mm2 Four cores with two lighting conductors: 4x(16 - 95)mm2+2x(16 - 35)mm2 nominal cross section: Allowed current in power supply networks 16mm2 81 A 25mm2 107 A 35mm2 132 A 50mm2 162 A 70mm2 205 A 95mm2 245 A

Cable Factory FKN | 2012

Bare Copper Conductors


Standard: DIN 48201 part 1

Overhead Cables

Application

For overhead electric power transmission systems.

Construction data Cu class 2


Nominal Cross Section mm 10 16 25 35 50 50 70 95 120 150 185 240 300 400 500 Number of Wires and Diameter No x mm 7x1.35 7x1.70 7x2.1 7x2.50 7x3.0 19x1.8 19x2.1 19x2.5 19x2.8 37x2.25 37x2.5 61x2.25 61x2.5 61x2.89 61x3.23
1 number of wires in the rope 2

Cable diameer mm 4.1 5.1 6.3 7.5 9.0 9.0 10.5 12.5 14.0 15.8 17.5 20.3 22.5 26.0 29.1
3 4

Breaking load min kN 4.02 6.37 9.72 13.77 19.84 19.38 26.38 37.39 46.90 58.98 72.81 97.23 120.04 160.42 200.38

Electrical resistance at 20C max /km 1.806 1.139 0.746 0.527 0.376 0.376 0.276 0.195 0.155 0.124 0.1 0.075 0.061 0.042 0.036
6 7 8

Net weight of copper aprox. kg/km 90 143 218 310 446 437 596 845 1060 1337 1649 2209 2725 3640 4545
9

Continuous current carring capacity A 90 125 160 200 250 250 310 380 440 510 585 700 800 960 1110

Lay Ratio (Table 2)


5

6-wire layer min. 10 10 10 10 max. 14 16 17 17

12-wire layer min. 10 10 10 max. 14 16 16

18-wire layer min. 10 10 max. 14 15

24-wire layer min. 10 max. 14

7 19 37 61

Note
Copper wire is accordance with DIN 48 200 Part 1 Conductor weights are calculated with a density of 8.9 kg/dm and the average lay ratio. The arithmetical mean of the relevant min. and max. values given in the Table 2 for the lay ratio is taken as the average lay ratio. The calculated breaking load is determinated in according with DIN 48 203 Part 1. Values for current carrying capacity are applicable up to 60 Hz at a wind velocity of 0.6m/s and solar effects for an original ambient temperature of 35 C and a final conductor e temperature of 70 C . The values must be reduced by an average of approx. 30% in case of special location in still air.

Packing
Standard Packing length on wooden drums: [ 500 m; 1000 m ];

Cable Factory FKN | 2012

Bare AL Conductor Steel Reinforced


Standard:48204

Overhead Cables

Application For overhead electric power transmission systems

Construction and Technical data


Nominal Cross Section mm 16/2.5 25/4 35/6 44/32 50/8 50/30 70/12 95/15 95/55 105/75 120/20 120/70 125/30 150/25 170/40 185/30 210/35 210/50 230/30 240/40 265/35 300/50 305/40 340/30 380/50 385/35 435/55 450/40 490/65 495/35 510/45 550/70 560/50 570/40 632/45 680/85 Number of Wires and Diameter No x mm Al St 5.4 6.8 8.1 11.2 '9.6 11.7 11.7 13.6 16 17.5 15.5 18 16.1 17.1 18.9 19 20.3 21 21 21.9 22.4 24.5 24.1 25 27 26.7 28.8 28.7 30.6 29.9 30.7 32.4 32.2 32.2 34 36 5.95 9.2 12.65 45 '17.1 43.8 26.8 35.75 79.35 108.45 45.65 100 57.6 55.25 76.75 66.2 74.9 93.9 73.1 86.4 83.05 107 99.4 92.9 123.1 104.8 136.45 120.75 153.1 121.80 136.65 170.6 148.95 139 155.8 210.4 1.8793 1.2028 0.8353 0.6573 0.5946 0.5644 0.4130 0.3058 0.2992 0.2736 0.2374 0.2364 0.2259 0.1939 0.1682 0.1571 0.1380 0.1363 0.1249 0.1188 0.1094 0.0949 0.0949 0.0851 0.0757 0.0748 0.0666 0.0644 0.0590 0.0584 0.0566 0.0526 0.0514 0.0506 62 97 140 372 196 378 284 383 712 891 494 901 591 605 794 746 850 981 877 987 1002 1236 1160 1180 1453 1344 1653 1561 1866 1646 1778 2092 1954 1888 2118 2570 90 125 145 170 290 350 410 425 470 520 535 590 610 630 645 680 740 790 740 840 850 900 920 960 985 995 1020 1040 1050 1120 1150 6x1.8+1x1.8 6x2.25+1x2.25 6x2.7+1x2.7 14x2+7x2.4 6x3.2+1x3.2 12x2.33+7x2.33 26x1.85+7x1.44 26x2.15+7x1.67 12x3.2+7x3.2 14x3.1+19x2.25 26x2.44+7x1.9 12x3.6+7x3.6 30x2.33+7x2.33 26x2.7+7x2.1 30x2.7+7x2.7 26x3+7x2.33 26x3.2+7x2.49 30x3+7x3 24x3.5+7x2.33 26x3.45+7x2.68 24x3.74+7x2.49 26x3.86+7x3 54x2.68+7x2.68 48x3+7x2.33 54x3+7x3 48x3.2+7x2.49 54x3.2+7x3.2 48x3.45+7x2.68 54x3.4+7x3.4 45x3.74+7x2.49 48x3.68+7x2.87 54x3.6+7x3.6 48x3.86+7x2.87 45x4+7x2.68 45x4.23+7x2.87 54x4+19x2.4 Cable diameer mm Breaking load min kN Electrical resistance at 20C max /km Net weight approx. kg/km Continuous current carring capacity A

Cable Factory FKN | 2012

ALMgSi Stranded Conductors


Standard: DIN 48201 part 6

Overhead Cables

Application

For overhead electric power transmission systems.

Construction data
Nominal Cross Section mm 16 25 35 50 50 70 95 120 150 185 240 300 400 500 Number of Wires and Diameter No x mm 7x1.70 7x2.1 7x2.50 7x3.0 19x1.8 19x2.1 19x2.5 19x2.8 37x2.25 37x2.5 61x2.25 61x2.5 61x2.89 61x3.23 Cable diameer mm 5.1 6.3 7.5 9.0 9.0 10.5 12.5 14.0 15.8 17.5 20.3 22.5 26.0 29.1 Breaking load min kN 4.44 6.77 9.6 13.82 13.5 18.38 26.05 32.68 41.09 50.73 67.74 83.63 111.76 139.60 Net weight aprox. kg/km 43 66 94 135 133 181 256 322 406 500 670 827 1104 1379 Continuous current carring capacity A 105 135 170 210 210 255 320 365 425 490 585 670 810 930

Lay Ratio (Table 2)


1 number of wires in the rope 7 19 37 61 2 3 4 5 6 7 8 9 6-wire layer min. 10 10 10 10 max. 14 16 17 17 12-wire layer min. 10 10 10 max. 14 16 16 18-wire layer min. 10 10 max. 14 15 24-wire layer min. 10 max. 14

Note AlMgSi wire is accordance with DIN 48 200 Part 6 Conductor weights are calculated with a density of 2.7 kg/dm and the average lay ratio. The arithmetical mean of the relevant min. and max. values given in the Table 2 for the lay ratio is taken as the average lay ratio. The calculated breaking load is determinated in according with DIN 48 203 Part 6. Values for current carrying capacity are applicable up to 60 Hz at a wind velocity of 0.6m/s and solar effects for an original ambient temperature of 35 C and a final conductor e temperature of 80 C . The values must be reduced by an average of approx. 30% in case of special location in still air.

Packing
Standard packing length on wooden drums: (500m; 1000m; 1500m; 2000m)

Cable Factory FKN | 2012

Steel Ropes
Standard:N.C1.702

Overhead Cables

Application For overhead electric power transmission systems

Construction data
Nominal Cross Section Number of Wires and Diameter Cable diameer Net weight aprox. Breaking Force for steel class I Breaking Force for steel class II Breaking Force for steel class III Breaking Force for steel class IV

mm
16 25

No x mm
7x1.70 7x2.1 12x1.6 7x2.5

mm
5.1 6.3 6.6 7.5 7.9 8.1 7.8 9.0 9.5 9.0 10.8 11.2 10.5 10.9 13.1 12.5 12.6 14.9 14.0 14.0 15.8 15.8 15.8 17.5 17.5 17.6 20.3 20.3 22.4 22.5

kg/km
126 192 193 272 271 289 285 391 396 384 563 548 523 556 745 741 749 973 929 925 1176 1170 1183 1451 1445 1467 1944 1933 2367 2387

daN
589,0 898,5 893,5 1 273,0 1 260,0 1 341,0 1 327,5 1 833,0 1 846 1 790,5 2 638,5 2 544,0 2 438,5 2 585,5 3 463,0 3 455,5 3 487,0 4 524 4 335 4 305 5 483,0 5 446,5 5 205,5 6 769,0 6 724,5 6 458,5 9 051,5 8 508,5 11 018,5 10 505,5

daN
1 041,5 1 589,0 1 581,0 2 252,5 2 229,5 2 372,5 2 348,5 3 243,5 3 266,5 3 167,5 4 668,5 4 501,5 4 314,5 4 574,0 6 127,0 6 114,0 6 169,0 8 003,5 7 669,5 7 617,0 9 701,5 9 639,0 9 209,5 11 967,0 11 897,5 11 426,5 16 014,0 15 053,0 19 494,5 18 586,5

daN
1 977,5 3 018,0 3 002,0 4 276,0 4 232,5 4 504,0 4 459,0 6 158,0 6 201,5 6 013,5 8 863,5 8 546,0 8 192,0 8 684,0 11 632,5 11 607,5 11 720,0 15 195,5 14 560,5 14 461,0 18 418,5 18 284,0 17 484,5 22 737,0 22 587,5 21 693,5 30 403,0 28 579 37 011,5 35 287,5

daN
245,5 3 156,0 3 139,0 4 472,0 4 426,5 4 710,0 4 663,5 6 440,0 6 485,5 6 289,0 9 269,5 8 937,4 8 566,5 9 082,0 12 165,0 12 139,0 12 248,5 15 891,5 15 227,5 15 123,5 19 262,0 19 132,0 20 995,0 23 778,5 23 622,0 25 999,0 31 795,5 34 251 38 706,5 42 291,0

35

12x1.9 12x1.96 19x1.55 7x3

50

12x2.3 19x1.8 7x3.6

70

12x2.7 19x2.1 37x1.55 12x3.15

95

19x2.5 37x1.8 12x3.6

120

19x2.8 37x2 19x3.15

150

37x2.25 61x1.76 19x3.5

185

37x2.5 61x1.96

240

37x2.9 61x2.25

300

37x3.2 61x2.5

Lay Ratio (Table 2)


1 number of wires in the rope 2 3 4 5 6 7 8 9

6-wire layer min. 10 10 10 10 max. 14 16 17 17

12-wire layer min. 10 10 10 max. 14 16 16

18-wire layer min. 10 10 max. 14 15

24-wire layer min. 10 max. 14

Galvanized steel wire is accordance with N.C1.701. Conductor weights are calculated with a density of 7.8 kg/dm and the average lay ratio. The arithmetical mean of the relevant min. and max. values given in the Table 2 for the lay ratio is taken as the average lay ratio. The calculated breaking load is determinated in according with standard.

7 19 37 61

Cable Factory FKN | 2012

Bare Aluminium Cond.


Standard: DIN 48201 part 5

Overhead Cables

Application

For overhead electric power transmission systems.


Construction data
Nominal Cross Section mm 16 25 35 50 50 70 95 120 150 185 240 300 400 500 Number of Wires and Diameter No x mm 7x1.70 7x2.1 7x2.50 7x3.0 19x1.8 19x2.1 19x2.5 19x2.8 37x2.25 37x2.5 61x2.25 61x2.5 61x2.89 61x3.23 Cable diameer mm 5.1 6.3 7.5 9.0 9.0 10.5 12.5 14.0 15.8 17.5 20.3 22.5 26.0 29.1 Breaking load min kN 2.84 4.17 5.78 7.94 8.45 11.32 15.68 18.78 25.3 30.54 39.51 47.7 60.86 74.67 Electrical resistance at 20C max /km 1.802 1.181 0.833 0.579 0.635 0.437 0.309 0.246 0.196 0.1587 0.1194 0.0965 0.0722 0.0578 Net weight aprox. kg/km 43 66 94 135 133 181 256 322 406 500 670 827 1104 1379 Continuous current carring capacity

A
110 145 180 225 225 270 340 390 455 520 625 710 855 990

Lay Ratio (Table 2)


1 number of wires in the rope 2 3 4 5 6 7 8 9

6-wire layer min. 10 10 10 10 max. 14 16 17 17

12-wire layer min. 10 10 10 max. 14 16 16

18-wire layer min. 10 10 max. 14 15

24-wire layer min. 10 max. 14

7 19 37 61

Note Aluminium wire is accordance with DIN 48 201 Part 5 Conductor weights are calculated with a density of 2.7 kg/dm and the average lay ratio. The arithmetical mean of the relevant min. and max. values given in the Table 2 for the lay ratio is taken as the average lay ratio. The calculated breaking load is determinated in according with DIN 48 203 Part 5. Values for current carrying capacity are applicable up to 60 Hz at a wind velocity of 0.6m/s and solar effects for an original ambient temperature of 35 C and a final conductore temperature of 80 C . The values must be reduced by an average of approx. 30% in case of special location in still air.

Packing
Standard packing length on wooden drums: (500m; 1000m; 1500m; 2000m)

Cable Factory FKN | 2012

AL1-ST1
Standard: EN 50182

Overhead Cables

Application For overhead electric power transmission systems

Construction data
Nominal Cross Section mm Number of Wires and Diameter No x mm Al 15-AL1/3-St1A 24-AL1/4-St1A 34-AL1/6-St1A 44-AL1/32-St1A 48-AL1/8-St1A 51-AL1/30-St1A 70-AL1/11-St1A 94-AL1/15-St1A 97-AL1/56-St1A 106-AL1/76-St1A 122-AL1/20-St1A 122-AL1/71-St1A 128-AL1/30-St1A 149-AL1/24-St1A 172-AL1/40-St1A 184-AL1/30-St1A 209-AL1/34-St1A 212-AL1/49-St1A 231-AL1/30-St1A 243-AL1/39-St1A 264-AL1/34-St1A 304-AL1/49-St1A 305-AL1/39-St1A 339-AL1/30-St1A 382-AL1/49-St1A 386-AL1/34-St1A 434-AL1/56-St1A 449-AL1/39-St1A 490-AL1/64-St1A 494-AL1/34-St1A 511-AL1/45-St1A 550-AL1/71-St1A 562-AL1/49-St1A 571-AL1/39-St1A St AL Cable diameer mm St 5,4 6,75 8,1 11,2 9,6 11,7 11,7 13,6 16 17,5 15,5 18 16,3 17,1 18,9 19 20,3 21 21 21,8 22,4 24,4 24,1 25 27 26,7 28,8 28,7 30,6 29,9 30,7 32,4 32,2 32,2 5.80 8.95 12.37 44.24 16.81 42.98 26.27 34.93 77.85 105.82 44.50 97.92 56.41 53.67 74.89 65.27 73.36 92.46 72.13 85.12 81.04 105.09 96.80 91.71 121.30 102.56 133.59 119.05 150.81 117.96 133.31 166.32 146.28 136.40 1,8769 1,2012 0,8342 0,6574 0,5939 0,5644 0,4132 0,3060 0,2992 0,2742 0,2376 0,2364 0,2260 0,194 0,1683 0,1571 0,1381 0,1363 0,125 0,1188 0,1095 0,0949 0,0949 0,0852 0,0758 0,0749 0,0666 0,0644 0,059 0,0584 0,0566 0,0526 0,0515 0,0506 41.85 65.39 94.16 121.3 132.26 141.14 192.76 260.35 266.22 292.2 335.32 336.94 353.09 410.6 474.13 506.91 576.75 585.35 636.44 670.38 726.72 839.19 841.20 937.4 1054.1 1066.51 1199.3 1239.7 1353.92 1365.5 1410.47 1517.9 1551.8 1577.7 19.85 31.01 44.66 248.1 62.73 233.87 89.32 120.14 441.12 593.8 155.51 558.3 233.87 189.97 314.03 233.87 267.09 387.7 233.87 309.4 267.09 387.7 309.40 233.87 387.7 267.09 441.12 309.40 497.98 267.09 354.83 558.29 387.7 309.4 61.7 96.4 138.82 369.4 194.99 375.1 282.1 380.49 707.34 886 490.83 895.24 586.96 600.57 788.16 741.0 843.84 973.05 870.31 979.78 993.81 1226.89 1150.6 1171.2 1440.44 1333.6 1641.3 1549.1 1851.9 1632.6 1765.3 2076.2 1939.5 1887.1 Electrical Breaking load resistance at 20C min max kN /km Type AL1/St1A conductors 6x1,80+1x1,80 6x2,25+1x2,25 6x2,70+1x2,70 14x2,00+7x2,40 6x3,20+1x3,20 12x2,33+7x2,33 26x1,85+7x1,44 26x2,15+7x1,67 12x3,20+7x3,20 14x3,10+19x2,25 26x2,44+7x1,90 12x3,60+7x3,60 30x2,33+7x2,33 26x2,70+7x2,10 30x2,70+7x2,70 26x3,00+7x2,33 26x3,20+7x2,49 30x3,00+7x3,00 24x3,50+7x2,33 26x3,45+7x2,68 24x3,74+7x2,49 26x3,86+7x3,00 54x2,68+7x2,68 48x3,00+7x2,33 54x3,00+7x3,00 48x3,20+7x2,49 54x3,20+7x3,20 48x3,45+7x2,68 54x3,40+7x3,40 45x3,74+7x2,49 48x3,68+7x2,87 54x3,60+7x3,60 48x3,86+7x3,00 45x4,02+7x2,68 Weight Al kg/km Weight St kg/km Net weight aprox. kg/km

Cable Factory FKN | 2012

AL1-ST1
Standard: EN 50128

Overhead Cables

Construction data
Nominal Cross Section mm 16-AL1 24- AL1 34- AL1 49- AL1 48- AL1 66- AL1 93- AL1 117- AL1 147- AL1 182- AL1 243- AL1 299- AL1 400- AL1 500- AL1 Number of Wires and Diameter No x mm 7x1.70 7x2.10 7x2.50 7x3.00 19x1.80 19x2.10 19x2.50 19x2.80 37x2.25 37x2.50 61x2.25 61x2.50 61x2.89 61x3.23 Cable diameter mm 5.10 6.30 7.50 9.00 9.0 10.5 12.5 14.0 15.8 17.5 20.3 22.5 26.0 29.1 Breaking load min kN Type AL1 conductors 3.02 4.36 6.01 8.41 8.94 11.85 16.32 19.89 26.48 31.78 43.66 52.40 68.02 82.47 17.986 11.787 0.8317 0.5776 0.5944 0.4367 0.3081 0.2456 0.1960 0.1588 0.1193 0.0966 0.0723 0.0579 43.4 66.3 93.9 135.2 132.9 180.9 256.3 321.5 405.7 500.9 671.1 828.5 1107.1 1382.9 Electrical resistance at 20C max /km Net weight of rope kg/km

Packing
Standard packing length on wooden drums: (500m; 1000m; 1500m; 2000m)

Cable Factory FKN | 2012

Multiwire Cables

Multiwire Cu&Al Conductors class 2


Standards: IEC 60228; DIN VDE 0295; BS 6360

Multiwire Cables

Multiwire copper and aluminium conductors for cables and conductors


Construction Data: Cu/A l conductors class 2
Nominal Cross Section No x mm 0,5 0,75 1 1,5 2,5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 600 Number of Wires and Diametar No x mm 7 x 0,31 7 x 0,37 7 x 0,42 7 x 0,52 7 x 0,67 7 x 0,87 7 x 1,06 7 x 1,35 7 x 1,74 7 x 2,26 7 x 2,52 19 x 1,8 19 x 2,18 19 x 2,52 37 x 2,03 37 x 2,24 37 x 2,52 61 x 2,24 61 x 2,52 61 x 2,89 61 x 3,18 61 x 3,63 Electrical resistance at 20C max Copper conductors [ /km ] Aluminium conductors [ /km ] 36 24,5 18,1 12,1 7,41 4,61 3,08 1,83 1,15 0,727 0,524 0,387 0,268 0,193 0,153 0,124 0,0991 0,0754 0,0601 0,047 0,0366 0,0283 7,41 4,61 3,08 1,91 1,2 0,868 0,641 0,443 0,32 0,253 0,206 0,164 0,125 0,1 0,0778 0,0605 0,0469

* Other Dimensions and information available on request

Packing
Standard Packing length on wooden drums: [ 500 m; 1000 m ];

Cable Factory FKN | 2012

Multiwire Cu Conductors class 5


Standards: IEC 60228; DIN VDE 0295; BS 6360

Multiwire Cables

Flexible copper wires for cables and conductors


Construction Data: Cu conductors class 5
Nominal Cross Section No x mm 0,14 0,25 0,38 0,5 0,75 1 1,5 2,5 4 6 6 10 16 25 35 50 70 95 120 150 185 240 Number of Wires and Diametar No x mm 18 x 0,1 7 x 0,2 12 x 0,2 15 x 0,2 22 x 0,2 30 x 0,2 28 x 0,25 45 x 0,25 53 x 0,3 75 x 0,3 7 x 11 x 0,3 7 x 11 x 0,4 7 x 17 x 0,4 7 x 27 x 0,4 7 x 39 x 0,4 19 x 20 x 0,4 19 x 18 x 0,5 19 x 25 x 0,5 19 x 31 x 0,5 37 x 20 x 0,5 37 x 25 x 0,5 37 x 32 x 0,5 Electrical resistance at 20C max Copper conductors [ /km ] Aluminium conductors [ /km ] 39 26 19,5 13,3 7,98 4,95 3,3 3,3 1,91 1,21 0,78 0,55 0,39 0,27 0,206 0,161 0,129 0,106 0,0801 0,0641 0,0486 0,0384 -

300 400 500

61 x 25 x 0,5 61 x 33 x 0,5 61 x 29 x 0,6

* Other Dimensions and information available on request

Packing
Standard Packing length on wooden drums: [ 500 m; 1000 m ];

Cable Factory FKN | 2012

DESIGNATION CODE FOR POWER CABLES according to DIN VDE 0271/0276


C o n s tru c ti o n r e fe r e n c e
Iden N (N) ca on of Designa on DIN VDE standard similar to DIN VDE standard

Conductor Material A aluminium conductor copper conductor Insula ng Materials Y PVC 2X cross-linked PE (XLPE) Concentric conductor (screen) C concentric conductor of copper CE concentric conductor of copper over each individual core S screen of copper wires SE screen of copper wires over each individual core H conduc ve layers (F) longitudinally water-proof screen (FL) longitudinally and radial water-proof screen Armouring B steel tape armouring R armour of galvanized round steel wires Sheath Material Y PVC 2Y PE H halogen-free thermoplas c polymer Protec ve Conductor I with protec ve conductor O without protec ve conductor Number of Cores Conductor Cross Sec on in mm
2

Conductor Type r... circular conductor .. m stranded conductor s... sector conductor /V compact conductor ..e... circular, solid conductor Ra ng Voltage 0.6/1 kV 3.6/6 kV 6.0/10 kV 12/20 kV 18/30 kV

Examples: NYY-J 4x1.5 RE 0.6/1 kV - VDE 0276-603 Cable according to standard, PVC-insulated, sheath PVC, with green-yellow marked core, 4 cores with nominal cross-sec on 1.5 mm2, circular conductor, solid, ra ng voltage 0.6/1 kV. A2XS2Y 1x35 RM/16 6/10 kV - IEC 60502-2 Single core XLPE-insulated cable with PE-sheath according to standard, circular, stranded aluminium conductor with nominal cross-sec on 35 mm2, covered with copper-screen 16 mm2 and ra ng vpltage (Uo/U) 6/10 kV.

Current Carrying Capacity and Indica ons for Calcula on of Power Cables and Wires
The guidelines for current carrying capaci es of copper and aluminium are valid DIN VDE 0298 part 4 as well as DIN VDE 0276 part 603 and for the conversion factors DIN VDE 0276 part 1000. The current carrying capacity of a cable should be limited in such a degree that all loca ons in a cable system which causes the generated heats under given propor ons to lead safely in the environment. The heat ow depends on the inner heat-resistance between conductor and outer surface of the cable and as well as from the heat emission to the surroundings. The following recommended values are the current carrying capacity of cables for laying in earth and in air at normal opera ng condi ons. Hints for the deviated opera ng condi ons, see DIN VDE 0298 table 4 and DIN VDE 0276 part 603 and part 1000.

Indica ons for Calcula on


For Laying in Earth - Devia ng opera ng condi ons with both conversion factors are to be considered, as these depend on both of speci c heat resistance and the grade of load. - EVU-load (load grade) is the maximum load factor of 0.7. The conversion factors for the load grades 0.5, 0.6, 0.85 and 1.0 are to be taken in tables DIN VDE 0276 part 603 and part 1000. Intermediate values can be interpolate (1.0 used for permanent load). - Laying depth 0.7 m. The load capacity decreases with increasing of the laying depth. Usual depth of laying is 0.7 to 1.2 m. - As normal value of the speci c ground thermal resis vity in moist areas is selected with 1.0 K.m/W. For dry areas the chosen value is 2.5 K .m/W, under considera on of the applied usual bedding materials of sands. - For favourable ground condi ons or with thermal resisted bedding materials, lower value under well consolida on can be achieved. For individual case, the values and upon that the resulted current carrying loads are to be determined. For Laying in Air The values stated in the tables for outdoor laying in the air are de ned for permanent opera on. The arrangement of the cables is corresponded the presenta on in table 3, DIN VDE 0276 part 1000. Conversion factors for other laying condi ons and the heaping of cables are shown in tables 10 and 11, DIN VDE 0276 part 1000. The current carrying capaci es of mul -core cables can be calculated by using the current load value for 3-core cables accord table 13 with help of the conversion factors. By using the cable channels of cable board underlays, etc., the air temperature will be increased. In this case the conversioning to factors according to table 12 for devia ng air temperature should be used. For outdoor installa on in air, the ambient temperature is based on 30 oC. Radia on of heats and solar in uence must be taken into considera on, where a good air circula on is needed. A su cient large distance is to be retained between the cables and the hea ng elements, because badly insulated hea ng elements o en raise addi onally the temperature of the cable. Distance between the cable and the wall, oor or ceiling = 2 cm Distance between the cables being laid one above the other = 2 x D Distance between the cable systems being laid one above the other = 20 cm Distance between the cables being laid side by side = 2 x D Speci c Ground Thermal Resis vity - very moist area = 0.7 K .m/W - moist area = 1.0 K .m/W - dry area = 2.0 K .m/W - very dry area = 3.0 K .m/W

INSTALLATION METHODS AND OPERATING CONDITIONS - Power Cables and Insulated Wires for Fixed Installa on
Installa on method type A1
Single core cables in insula on tube in a thermally insulated wall.

Installa on method A2
Mul core cables or mul core plas c sheathed cables in the insula on tube in a thermally insulated wall, whereby the walls for the methods of installa on employed comprise an outer weatherproof board, thermal insula on and an inner board of wood or materials similar to wood, having a temperature lag of 0.1 m2.K/W. The plas c or metal insula on tube is mounted so that it is very close to the inner wall without actually being in conduct with the wall.

Installa on method B1
Single core cables in insula on tube on a wooden wall.

Installa on method B2
Mul core cables or mul core plas c sheath cables in insula on tube on a wooden wall. For both installa on methods, the insula on tube must be secured so that the space between conduit and the wall surface is less than 0.3 mes the diameter of the insula on tube. The plas c or metal insula on tube can be installed directly on the masonry construc on or plastered surface, whereby the current carrying capacity of the cables or wires can then be higher. This problem is s ll being inves gated by CENELEC.

Installa on method C
Single core or mul core cables, or single core or mul core plas c-sheathed cables on a wooden wall. The cables or insulated wires shall be mounted so that the space from the wall surface is less than 0.3 mes the outer diameter of the cable or insulated wire. The current carrying capacity can be increased when installed directly on or in the masonry construc on as well as underneath the plaster.

Installa on methods E, F and G


Single core or mul core cables, or single core or mul core plas c-sheathed cables, installed in the open air. The cable or insulated wire shall be installed so that the dissipa on of heat is not impeded, whereby allowance shall be made for hea ng by other sources and for irradia on by sunshine. Natural convec on shall not be obstructed. The space from the cable or insulated wire by each bordering surface shall be 0.3 mes the outside diameter. A space equal to the one of the outside diameter is su cient for single core cables and plas c-sheathed wires in order to meet the current carrying requirements for an installa on in the open air.

Laying Condi ons for Power Cables


As laying depth, the mathema cal distance to the cable axis - for triangular bunched laying, the distance of the bundle axis to the earth surface of 70 cm is chosen. With increased laying depth the load ra ngs will be mathema cally reduced. Hereby the same temperature and the same thermal earth resistances are to be presumed. Normal opera on condi ons and indica ons for devia ng opera on condi ons.

Normal Opera on Condi ons


L a id in E a rth 1 Multic o re c a b le 1 S ing le c o re c a b le in d ire c t c urre nts ys te m 3 S ing le c o re c a b le s in 3-p ha s e s ys te m , s id e b y s id e , with a s p a c e of 7 c m 3 S ing le c o re c a b le s in 3-p ha s e s ys te m , in bundle form 1) B e d d ing in s a nd o r e a rth s ho ve a nd if ne c e s s a ry c o ve ring with b ric k s , c e m e nt p la te s o r with fla t to lig ht c urve d thin c o ve ring o f p la s tic Ambient Condi ons - G ro und te m p e ra ture a t installa on depth: 20 oC - S o il-the rm a l re s is tivity of moist area: 1.0 K . m/W - Soil-thermal resis vity of dry area: 2.5 K . m/W Connec ng and earthing of metal sheaths or screens on both ends L a id in A ir 1 Multic o re c a b le 1 S ing le c o re c a b le in d ire c t c urre nts ys te m 3 S ing le c o re c a b le s in 3-p ha s e s ys te m , s id e b y s id e , with a s p a c e o f a c a b le 3 S ing le c o re c a b le s in 3-p ha s e s ys te m , in bundle form 1) - L a id in o p e n a ir, i.e . unhind e re d he a t ra d ia tio n will b e e ns ure d a t: D is ta nc e o f c a b le fro m wa ll, flo o r o r c e iling 2 c m - F o r c a b le s la ying s id e b y s id e : Space at least two mes of the cable - For cables laying one above the o the r: Ver cal space of the cable at least two mes of the cable cable length at least 30 cm - Considera on of thermal loss in cable, the incresed air temperature of su cient big and ven lated rooms - Protec on against direct heat radia on of sunlight, etc. - Air temperature 30 oC Adequate big or ven lated rooms, due to that the power loss of the cable not be no ceable increased Connec ng and earthing of metal sheaths or screens on both sides Conversion factors for la ying in e a rth: - c o ve ring ho o d with a ir c a vity = 0.9 la id in c o nd uit = 0.85 Conversion factors for laying in air: - a lte rna ting a m b ie nt temperatures - a s o f c o lle c ting la ying condi ons - for laying in conduits - see tables and indica ons according to DIN VDE 0298 In d ic a tio n s C o nve rs io n fa c to rs s e e the following tables a s o f c o lle c tive la ying c o nd itio ns s e e the fo llo wing ta b le s

7 cm

d d

1)

In "bunched" or triangle touching arrangement.

Current ra ngs for installa on A1, A2, B1 and B2 Cables for xed installa on within buildings
Opera ng temperature at conductor 70o C ;
Type designa on H07V-U, -R, -K H07V3-U, -R, -K

Ambient temperature 30 oC
H07V-U, -R, -K H07V3-U, -R, -K NYM, NYBUY H05VV-U, N05VV-R NHXMH 1) NYY NYCY

NYM, NYBUY H05VV-U, N05VV-R NHXMH 1) NYY NYCY

Installa on: * in thermally insulated walls * in insula ng tubes

Single core cables in insula ng tubes, in thermally insulated walls

Mul core sheathed cables in insula ng tubes, in a thermally insulated walls

Single core cables in insula ng tubes on a wall

Mul core cables or mul core shaethed cables in insula ng tubes on a wall

Installa on in thermally insulated walls

Installa on in insula ng tubes

Installa on method 2) Number of loaded cores Cross-sec on, mm 2 1.5 2.5 4 6 10 10 16 25 35 50 70 95 120 150 185 240 300

A1 2

A2 2

B1 2

B2 2

Current ra ngs in Ampere (A) 15.5 19.5 26 34 46 61 80 99 119 151 182 210 240 273 320 367
3)

13.5 18.0 24 31 42 56 73 89 108 136 164 188 216 245 286 328

15.5 18.5 25 32 43 57 75 92 110 139 167 192 219 248 291 334

13.0 17.5 23 29 39 52 68 83 99 125 150 172 196 223 261 298

17.5 24 32 41 57 76 101 125 151 192 232 269 -

15.5 21 28 36 50 68 89 110 134 171 207 239 -

16.5 23 30 38 52 69 90 111 133 168 201 232 -

15.0 20 27 34 46 47.17 62 80 99 118 149 179 206 -

4)

Conversion factors for devia ng ambient temperature. grouping. installa on under the ceiling. mul core cables and insulated wires - see DIN VDE 0298 part 4. 1) The current ra ngs are valid for cables with concentric conductor. only for versions. 2) For further installa on methods - see DIN VDE 0298 part 4. 3) See DIN VDE 0298 part 4. 4) Not permi ed for the installa on on a wooden wall and not for applica on of the conversion factors. see DIN VDE 0298 part 4.

Current ra ngs for installa on condi ons C, E, F and G


Cables for xed installa on within buildings Opera ng temperature at conductor 70o C ;
Type designa on
1) NYM, NYIF, NYIFY, NYBUY, H05W-U, N05W-R, NHXMH, NYY, NYCY

Ambient temperature 30 oC
NYY

Insula on: * directly *in open air

singlecore or mul core cables or single or mul core sheathed cables on a wall

Mul core cables or mul core sheathed cables with a space of minimum 3.0x diameter d to wall

single core cables or single core sheathed cables with a space of minimum 1x diameter to wall

with contact
or

with gap d

d
or

0,3d

d ire c t in s ta lla tio n Installa on method Number of loaded Cross-sec on, mm 2 1.5 2.5 4 4 6 10 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630
2)

in s ta lla tio n in o p e n a ir E 3 F 2 3 2 Current ra ngs in Ampere (A) 18.5 25 34 43 60 80 101 126 153 196 238 276 319 364 430 497 131 162 196 251 304 352 406 463 546 629 754 868 1005 114 143 174 225 275 321 372 427 507 587 689 789 905 G 3 110 137 167 216 264 308 356 409 485 561 656 749 855 146 181 219 281 341 396 456 521 615 709 852 982 1138 130 162 197 254 311 362 419 480 569 659 795 920 1070 wires - see DIN VDE

C 2 19.5 27 36 46 63 85 112 138 168 213 258 299 344 392 461 530 -

17.5 24 32 33.02 3) 41 57 59.43 3) 76 96 119 144 184 223 259 299 341 403 464 -

22 30 40 51 70 94 119 148 180 232 282 328 379 434 514 593 -

Conversion factors for devia ng ambient temperature. grouping. installa on under the ceiling. mul core cables and insulated 0298 part 4. The current ra ngs are valid for cables with concentric conductor. only for mul core versions. For further installa on method - see DIN VDE 0298 part 4. 3) See DIN VDE 0298 part 4.
1) 2)

Current ratings for installation conditions


Cables for fixed installation within buildings Opera ng temperature at conductor 70o C ;
Type designation H07V2-U, -K H07Z-U, -R, -K

A1, A2, B1 and B2

Ambient temperature 30 oC
H07V2-U, -K H07Z-U, -R, -K N12XY, N2XY, NHXHX N2X2Y, N2XH, N2XCH FE 180 NHXCHX FE 180 NHXH FE NHXCH FE 180 NHXHX, NHXCHX

N12XY, N2XY, NHXHX N2X2Y, N2XH, N2XCH FE 180 NHXCHX FE 180 NHXH FE NHXCH FE 180 NHXHX, NHXCHX

Installa on: * in thermally insulated walls * in insula ng tubes

Single core cables in insula ng tubes, in thermally insulated walls

Mul core sheathed cables in insula ng tubes, in a thermally insulated walls

Single core cables in insula ng tubes on a wall

Mul core cables or mul core shaethed cables in insula ng tubes on a wall

Installation in thermally insulated walls

Installation in insulating tubes

Installation method 1) Number of loaded cores


2 Cross-section, mm

A1 2

A2 2

B1 2

B2

Current ratings in Ampere (A) 19.0 26 35 45 61 81 106 131 158 200 241 278 318 362 424 486 17.0 23 31 40 54 73 95 117 141 179 216 249 285 324 380 435 18.5 25 33 42 57 76 99 121 145 183 220 253 290 329 386 442 16.5 22 30 38 51 68 89 109 130 164 197 227 259 295 346 396 23 31 42 54 75 100 133 164 198 253 306 354 20 28 37 48 66 88 117 144 175 222 269 312 22 30 40 51 69 91 119 146 175 221 265 305 19.5 26 35 44 60 80 105 128 154 194 233 268 -

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300

Conversion factors for deviating ambient temperature, grouping, installation under the ceiling, multucore cables and insulated - see DIN wires VDE 0298 part 4. 1) For further installation conditions - see DIN VDE 0298 part 4.

Current ra ngs for installa on condi ons C, E, F and G


Cables for xed installa on within buildings Opera ng temperature at conductor 70o C ;
Type designa on N12XY, N2XY,N2S2Y 1) N2XH, N2XCH , NHXHX FE 180 NHXH FE180, NHXCH FE180 1) 1) NHXHX FE180, NHXCHX FE 180 NHXHX, NHXCHX,1) NHXHX singlecore or mul core cables or single or mul core sheathed cables on a wall

Ambient temperature 30 oC
N12XY, N2XY, N2X2Y N2XH, NHXH FE 180

Insula on: * directly *in open air

Mul core cables or mul core sheathed cables with a space of minimum 3.0x diameter d to wall

single core cables or single core sheathed cables with a space of minimum 1x diameter to wall

or

d
or

0,3d

direct installation

installation in open air

Installa on method Number of loaded Cross-sec on, mm 2

2)

C
2 3 2

E
3 2

F
3 Current ra ngs in Ampere (A)

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630

24 33 45 58 80 107 138 171 209 269 328 382 441 506 599 693 -

22 30 40 52 71 96 119 147 179 229 278 322 371 424 500 576 -

26 36 49 63 86 115 149 185 225 289 352 410 473 542 641 741 -

23 32 42 54 75 110 127 158 192 246 298 346 399 456 538 621 -

161 200 242 310 377 437 504 575 679 783 940 1083 1254

141 176 216 279 342 400 464 533 634 736 868 998 1151

135 169 207 268 328 383 444 510 607 703 823 946 1088

182 226 275 353 430 500 577 661 781 902 1085 1253 1454

161 201 246 318 389 454 527 605 719 833 1008 1169 1362

Conversion factors for deviating ambient temperature, grouping, installation under the ceiling, multicore cables and insulated wires - see DIN VDE 0298 part 4. 1) The current ratings are valid for cables with concentric conductor, only for multicore versions. 2) For further installation methods - see DIN VDE 0298 part 4.

Current ra ngs for NYY, NAYY, NYCY, NAYCY 0,6/1 kV


Current carrying capacity in Ampere (A), laying in ground (20
N o m in a l cross-sec on mm 2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500
1)

C)
NAY C Y
1)

C o p p e r c o n d u c to r NY Y
1)

NY C Y

A l u m i n i u m c o n d u c to r NAY Y

30 39 50 62 83 107 138 164 195 238 286 325 365 413 479 541 614 693

27 36 47 59 79 102 133 159 188 232 280 318 359 406 473 535 613 687

41 55 71 90 124 160 208 250 296 365 438 501 563 639 746 848 975 1125

31 40 51 63 84 108 139 166 196 238 281 315 347 385 432 473 521 574

27 36 47 59 79 102 133 160 190 234 280 319 357 402 463 518 579 624

106 127 151 185 222 253 284 322 375 425 487 558

102 123 144 179 215 245 275 313 364 419 484 553

160 193 230 283 340 389 436 496 578 656 756 873

108 129 153 187 223 252 280 314 358 397 441 489

103 123 145 180 216 246 276 313 362 415 474 528

Rated current for direct current systems with a far-distanced return conductor

Current carrying capacity in Ampere (A), laying in air (30 o C)


N o m in a l cross-sec on mm 2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500
1)

C o p p e r c o n d u c to r NY Y
1)

NY C Y

A l u m i n i u m c o n d u c to r NAY Y
1)

NAY C Y

21 28 37 47 64 84 114 139 169 213 264 307 352 406 483 557 646 747

19.5 25 34 43 59 79 106 129 157 199 246 285 326 374 445 511 597 669

27 35 47 59 81 107 144 176 214 270 334 389 446 516 618 717 843 994

22 29 39 49 67 89 119 146 177 221 270 310 350 399 462 519 583 657

19,5 26 34 44 60 80 108 132 160 202 249 289 329 377 443 504 577 626

87 107 131 166 205 239 273 317 378 437 513 600

82 100 119 152 186 216 246 285 338 400 472 539

110 135 166 210 259 302 345 401 479 555 653 772

91 112 137 173 212 247 280 321 374 426 488 556

83 101 121 155 189 220 249 287 339 401 468 524

Rated current for direct systems with a far-distanced return conductor

Conversion factors for mul core cable (


N u m b e r o f l o a d e d c o re s n 5 7 10 14 19 24 40 61
2 Note: Valid for cross-sec on 1,5 to 10 mm .

5 cores)
L a y i n g i n g ro u n d f 0.70 0.60 0.50 0.45 0.40 0.35 0.30 0.25 L a y in g in a ir f 0.75 0.65 0.55 0.50 0.45 0.40 0.35 0.30

The conversion factors are to be used for laying the cables in ground or in air, to the values given in above tables.

Current ra ngs for N2XY, NA2XY; N2XCY; NA2XCY; N2X2Y; NA2X2Y; N2XC2Y, NA2XC2Y; N2XH, NA2XH; N2XCH; NA2XCH
Current carrying capacity in Ampere (A), laying in ground (20 o C)
Copper conductor
Nominal crosssec on mm 2

Aluminium conductor NA2XY; NA2X2Y


1)

N2XY;N2X2Y
1)

N2XCY; N2XC2Y

NA2XCY; NA2XC2Y

1,5 2,5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500

48 63 82 102 136 176 229 275 326 400 480 548 616 698 815 927 1064 1227

31 40 52 64 86 112 145 174 206 254 305 348 392 444 517 585 671 758

33 42 54 67 89 115 148 177 209 256 307 349 393 445 517 583 663 749

31 40 52 65 87 113 146 176 208 256 307 349 391 442 509 569 637 691

33 43 55 68 91 117 150 179 211 257 304 341 377 418 469 514 565 623

177 212 252 310 372 425 476 541 631 716 825 952

112 135 158 196 234 268 300 342 398 457 529 609

114 136 162 199 238 272 305 347 404 457 525 601

113 136 159 197 236 269 302 342 397 454 520 584

116 138 164 201 240 272 303 340 387 430 479 531

1)

Rated current for direct current systems witn a far-distanced retum conductor.

Current ra ngs - Conversion factors


for grouping of single core cables or cables on troughs and trays
Number of three-phase systems with single core cables Installa on method P e rfo ra te d c a b le tro u g h s with c o n ta c t T h re e -c o re s c a b le in horizontal-surface a rra n g e m e n t 1 2 3 0,98 0,96 0,95 0,91 0,87 0,85 0,87 0,81 0,78 Used as mul plier for ra ng value for Number of troughs or trays 1 2 Coversion factors 3

300 mm

20 mm

with c o n ta c t

T h re e -c o re s c a b le t ve rtic a l-s u rfa c e arrangemen

1 2

0,96 0,95

0,86 0,84

225 mm

Cable trays

with contact Three-cores cable in horizontale surface a rra n g e m e n t


300 mm

1 2 3

11,00 0,98 0,97

0,97 0,93 0,90

0,96 0,89 0,86

20 mm

P e rfo ra te d c a b le tro u g h s
300 mm

d 2d

1 2 3

1,00 0,97 0,96

0,98 0,93 0,92

0,96 0,89 0,86

20 mm

2d d 225 mm

Three-core cables in ve rtic a l-s u rfa c e tria n g le a rra n g e m e n t

1 2

1,00 1,00

0,91 0,90

0,89 0,86

C a b le tra y s
d
2d

1 2 3

1,00 0,97 0,96

1,00 0,95 0,94

1,00 0,93 0,90

300 mm

20 mm

Note: The conversion factors are used only for cables of one layer grouping arrangement. These are not valied when the cables are installed with contact one upon another or the given sprees between the cable toughs or cable trays, are not followed, in such cases the conversion factors can be reduced. To parallel current circuits each group of three conductors of the parallel circuit is regarded as single circuit.

Current ra ngs - conversion factors


N u m b e r o f m u ltic o re c a b le s In s ta lla tio n m e th o d

for grouping of mul core cables or cables on troughs and trays


1 2 N u m b e r o f tro u g h s or trays 3 4 6 C o n ve rs io n fa c to rs 9

300 mm

N o n -p e rfo ra te d c a b le tro u g h s

with c o n ta c t

1 2 3 6
20 mm

0,97 0,97 0,97 0,97

0,84 0,83 0,82 0,81

0,78 0,76 0,75 0,73

0,75 0,72 0,71 0,69

0,71 0,68 0,66 0,63

0,68 0,63 0,61 0,58

P e rfo ra te d c a b le tro u g h s

with c o n ta c t
300 mm

1 2 3 6
20 mm

1,00 1,00 1,00 1,00

0,88 0,87 0,86 0,84

0,82 0,80 0,79 0,77

0,79 0,77 0,76 0,73

0,76 0,73 0,71 0,68

0,73 0,68 0,66 0,64

with s p a c e
300 mm

1 2 3

1,00 1,00 1,00

1,00 0,99 0,98

0,98 0,96 0,95

0,95 0,92 0,91

0,91 0,87 0,85

20 mm

with c o n ta c t

1 2

1,00 1,00

0,88 0,88

0,82 0,81

0,78 0,76

0,73 0,71

0,72 0,70

225 mm

with s p a c e
d d

1 2

1,00 1,00

0,91 0,91

0,89 0,88

0,88 0,87

0,87 0,85

225 mm

C a b le tra y s

with c o n ta c t

300 mm

1 2 3 6

1,00 1,00 1,00 1,00

0,87 0,86 0,85 0,83

0,82 0,81 0,79 0,76

0,80 0,78 0,76 0,73

0,79 0,76 0,73 0,69

0,78 0,73 0,70 0,66

20 mm

with s p a c e 300 mm

1 2 3

1,00 1,00 1,00

1,00 0,99 0,98

1,00 0,98 0,97

1,00 0,97 0,96

1,00 0,9 0,93

20 mm

Note: The conversion factor are used for cables of one layer grouping arrangement. These are not valid when the cables are installed with contact one upon another or the given spaces between the cable troughs or cable trays can not meet in such cases the conversion factor can be reduced.

Power ra ngs for XLPE-insulated Medium Voltage Power Cables 6/10 kV, 12/20 kV, 18/30 20/35 kV
N2XSY NA2XSY N2XS2Y NA2XS2Y N2XS(F)2Y NA2XS(F)2Y Current carrying capacity in Amperes (A) in ground (20 C)
C o n d u c to r material Arrangement U 0 /U crosssec on mm 2 25 35 50 70 95 120 150 185 240 300 400 500 6/10 kV 157 187 220 268 320 363 405 456 526 591 662 744 179 212 249 302 359 405 442 493 563 626 675 748 12/20 kV 189 222 271 323 367 409 461 532 599 671 754 213 250 303 360 407 445 498 568 633 685 760 18/30 kV 225 274 327 371 414 466 539 606 680 765 6/10 kV 12/20 kV Current ra ngs in Ampere (A) 251 304 362 409 449 502 574 640 695 773 145 171 208 248 283 315 357 413 466 529 602 165 194 236 281 318 350 394 452 506 558 627 172 210 251 285 319 361 417 471 535 609 195 237 282 319 352 396 455 510 564 634 18/30 kV 174 213 254 289 322 364 422 476 541 616 195 238 283 321 354 399 458 514 570 642 C o p p e r c o n d u c to r A l u m i n i u m c o n d u c to r

This factors are also valid for longitudinally water- ght cable

Current carrying capacity* in Amperes (A) in air (30 C)


C o n d u c to r material Arrangement U 0 /U cross-sec on mm 2 25 35 50 70 95 120 150 185 240 300 400 500
*

C o p p e r c o n d u c to r

A l u m i n i u m c o n d u c to r

6/10 kV

12/20 kV

18/30 kV

6/10 kV

12/20 kV

18/30 kV

Current ra ngs in Ampere (A) 163 197 236 294 358 413 468 535 631 722 827 949 194 235 282 350 426 491 549 625 731 831 920 1043 200 239 297 361 416 470 538 634 724 829 953 235 282 351 426 491 549 625 731 830 923 1045 241 299 363 418 472 539 635 725 831 953 282 350 425 488 548 624 728 828 922 1045 153 183 228 278 321 364 418 494 568 660 767 182 219 273 333 384 432 496 583 666 755 868 185 231 280 323 366 420 496 569 660 766 219 273 332 384 432 494 581 663 753 866 187 232 282 325 367 421 496 568 650 764 219 273 331 382 429 492 578 659 750 861

This factors are also valid for longitudinally water- ght cable

Electrical characteris cs of XLPE-insulated


Medium Voltage Power Cables, 6 - 35 kV
Conductor resistance 20 C
maximum value c ro s s - s e c ti o n mm 2 25 35 50 70 95 120 150 185 240 300 400 500 C u - c o n d u c to r O h m /k m 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 A l u - c o n d u c to r O h m /k m 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605
o

Conversion factors for the conductor temperatures


Temperature at o C Cu-conductor Alu-conductor 60 1.157 1.161 65 1.177 1.181 70 1.196 1.202 80 1.236 1.242 90 1.275 1.282

Conversion formula:
R =R R =R
20

. 234.5 + 254.5 . 228 + 248

for Cu-conductor for Alu-conductor

20

Conductor temperature at oC = Conductor resistance at C in Ohm/km = R Conductor resistance at 20 oC in Ohm/km = R20

416

Electrical characteris cs of XLPE-insulated


Medium Voltage Power Cables, 6 - 35 kV
E ec ve resistance at 50 Hz (Alterna ng-current resistance)
Copper conductor
N o m i n a l v o l ta g e C r o s s - s e c ti o n mm 2 35 50 70 95 120 150 185 240 300 400 500 0.671 0.497 0.345 0.249 0.198 0.163 0.132 0.102 0.082 0.068 0.055 6 /1 0 k V 1 2 /2 0 k V 0 h m /k m 0.673 0.498 0.346 0.251 0.200 0.165 0.134 0.104 0.085 0.071 0.058 0.671 0.496 0.345 0.249 0.198 0.163 0.131 0.101 0.082 0.067 0.055 0.672 0.498 0.346 0.250 0.200 0.165 0.133 0.103 0.084 0.070 0.058 0.496 0.344 0.249 0.198 0.162 0.131 0.101 0.082 0.067 0.054 1 8 /3 0 k V

0.497 0.346 0.250 0.199 0.164 0.133 0.103 0.084 0.069 0.057

Aluminium conductor
N o m i n a l v o l ta g e C r o s s - s e c ti o n mm 2 35 50 70 95 120 150 185 240 300 400 500 1.12 0.825 0.571 0.413 0.327 0.269 0.215 0.165 0.133 0.106 0.085 6 /1 0 k V 1 2 /2 0 k V 0 h m /k m 1.12 0.826 0.572 0.415 0.329 0.271 0.217 0.167 0.135 0.109 0.088 1.12 0.825 0.571 0.413 0.327 0.268 0.215 0.165 0.133 0.106 0.084 1.12 0.826 0.572 0.414 0.329 0.270 0.217 0.167 0.135 0.109 0.087 0.824 0.571 0.413 0.327 0.268 0.214 0.164 0.133 0.106 0.084 1 8 /3 0 k V

0.826 0.572 0.414 0.328 0.270 0.216 0.166 0.135 0.108 0.087

Induc ve resistance at 50 Hz
N o m i n a l v o l ta g e C r o s s - s e c ti o n mm 2 35 50 70 95 120 150 185 240 300 400 500 0.144 0.136 0.129 0.123 0.118 0.114 0.110 0.105 0.102 0.097 0.094 6 /1 0 k V 1 2 /2 0 k V 0 h m /k m 0.158 0.150 0.143 0.137 0.132 0.128 0.124 0.120 0.116 0.111 0.108 0.153 0.145 0.138 0.131 0.126 0.121 0.117 0.112 0.108 0.103 0.100 0.168 0.159 0.152 0.145 0.140 0.135 0.131 0.126 0.123 0.117 0.114 0.154 0.147 0.139 0.134 0.129 0.125 0.120 0.115 0.110 0.106 1 8 /3 0 k V

0.169 0.161 0.154 0.148 0.143 0.139 0.134 0.130 0.124 0.120

Electrical characteris cs of XLPE-insulated


Medium Voltage Power Cables, 6 - 35 kV
Mutual capacitance
N o m i n a l v o l ta g e Cross-sec on mm 2 35 50 70 95 120 150 185 240 300 400 500 6 /1 0 k V F/km 0,22 0,25 0,28 0,31 0,23 0,37 0,40 0,44 0,48 0,55 0,60 1 2 /2 0 k V F/km 0,16 0,18 0,20 0,22 0,23 0,25 0,27 0,30 0,32 0,36 0,40 1 8 /3 0 k V F/km 0,14 0,15 0,17 0,23 0,19 0,20 0,22 0,24 0,27 0,29

Inductance
N o m i n a l v o l ta g e Cross-sec on mm 2 35 50 70 95 120 150 185 240 300 400 500 6 /1 0 k V 1 2 /2 0 k V 1 8 /3 0 k V

mH/km 0,45 0,42 0,39 0,38 0,36 0,35 0,34 0,32 0,31 0,30 0,29

mH/km 0,76 0,73 0,70 0,67 0,65 0,63 0,61 0,59 0,57 0,55 0,53

mH/km 0,48 0,45 0,43 0,41 0,39 0,38 0,36 0,35 0,33 0,33 0,31

mH/km 0,76 0,74 0,70 0,68 0,65 0,63 0,62 0,59 0,58 0,55 0,53

mH/km 0,48 0,45 0,43 0,42 0,41 0,39 0,37 0,36 0,34 0,33

mH/km 0,75 0,71 0,68 0,66 0,64 0,63 0,60 0,59 0,56 0,54

418

Electrical characteris cs of XLPE-insulated


Medium Voltage Power Cables, 6 - 35 kV
Short-circuit current carrying capacity up to 30 kV Conductor temperature: 90 o C Short-circuit temperature: 250 o C Cable with Cu-conductors
c ro s s sec on mm 2 0,1 0,2 0,3 0,4 0,5 s h o rt- c i r c u i t ti m e i n s ( s e c o n d s )

0,6

0,7

0,8

0,9

1,0

1,5

2,0

3,0

4,0

5,0

permissible short-circuit in kA 25 35 50 70 95 120 150 185 240 300 400 500 11,3 15,8 22,6 31,7 43,0 54,3 67,8 83,7 108,5 135,7 180,9 226,1 8,0 11,2 16,0 22,4 30,4 38,4 48,0 59,2 76,7 95,9 127,9 159,9 6,5 9,1 13,1 18,3 24,8 31,3 39,2 48,3 62,7 78,3 104,4 130,5 5,7 7,9 11,3 15,8 21,5 27,1 33,9 41,8 54,3 67,8 90,4 113,1 5,1 7,1 10,1 14,2 19,2 24,3 30,3 37,4 48,5 60,7 80,9 101,1 4,6 6,5 9,2 12,9 17,5 22,2 27,7 34,2 44,3 55,4 73,8 92,3 4,3 6,0 8,5 12,0 16,2 20,5 25,6 31,6 41,0 51,3 68,4 85,5 4,0 5,6 8,0 11,2 15,2 19,2 24,0 29,6 38,4 48,0 64,0 79,9 3,8 5,3 7,5 10,6 14,3 18,1 22,6 27,9 36,2 45,2 60,3 75,4 3,6 5,0 7,2 10,0 13,6 17,2 21,5 26,5 34,3 42,9 57,2 71,5 2,9 4,1 5,8 8,2 11,1 14,0 17,5 21,6 28,0 35,0 46,7 58,4 2,5 3,5 5,1 7,1 9,6 12,1 15,2 18,7 24,3 30,3 40,4 50,6 2,1 2,9 4,1 5,8 7,8 9,9 12,4 15,3 19,8 24,8 33,0 41,3 1,8 2,5 3,6 5,0 6,8 8,6 10,7 13,2 17,2 21,5 28,6 35,8 1,6 2,2 3,2 4,5 6,1 7,7 9,6 11,8 15,3 19,2 25,6 32,0

Cable with Alu-conductors


crosssec on mm 2 0,1 0,2 0,3 0,4 0,5 0,6

short-circuit me in s (seconds) 0,7 0,8 0,9 1,0 1,5 2,0 3,0 4,0 5,0

permissible short-circuit in kA 25 7,4 35 10,4 50 14,9 70 20,8 95 28,2 120 35,7 150 44,6 185 55,0 240 71,3 300 89,2 400 118,9 500 148,6 5,3 7,4 10,5 14,7 20,0 25,2 31,5 38,9 50,4 63,1 84,1 105,1 4,3 6,0 8,6 12,0 16,3 20,6 25,7 31,7 41,2 51,5 68,6 85,8 3,7 5,2 7,4 10,4 14,1 17,8 22,3 27,5 35,7 44,6 59,5 74,3 3,3 4,7 6,6 9,3 12,6 16,0 19,9 24,6 31,9 39,9 53,2 66,5 3,0 4,2 6,1 8,5 11,5 14,6 18,2 22,5 29,1 36,4 48,5 60,7 2,8 3,9 5,6 7,9 10,7 13,5 16,9 20,8 27,0 33,7 44,9 56,2 2,6 3,7 5,3 7,4 10,0 12,6 15,8 19,4 25,2 31,5 42,0 52,5 2,5 3,5 5,0 6,9 9,4 11,9 14,9 18,3 23,8 29,7 39,6 49,5 2,4 3,3 4,7 6,6 8,9 11,3 14,1 17,4 22,6 28,2 37,6 47,0 1,9 2,7 3,8 5,4 7,3 9,2 11,5 14,2 18,4 23,0 30,7 38,4 1,7 2,3 3,3 4,7 6,3 8,0 10,0 12,3 16,0 19,9 26,6 33,2 1,4 1,9 2,7 3,8 5,2 6,5 8,1 10,0 13,0 16,3 21,7 27,1 1,2 1,6 2,4 3,3 4,5 5,6 7,1 8,7 11,3 14,1 18,8 23,5 1,1 1,5 2,1 2,9 4,0 5,0 6,3 7,8 10,1 12,6 16,8 21,0

Electrical characteris cs of XLPE-insulated


Medium Voltage Power Cables, 6 - 35 kV
Short-circuit to ground
N o m i n a l v o l ta g e cross-sec on mm 2 35 50 70 95 120 150 185 240 300 400 500 6 /1 0 k V A /k m 1,2 1,4 1,5 1,7 1,9 2,0 2,2 2,4 2,6 3,0 3,3 1 2 /2 0 k V A /k m 1,7 1,9 2,1 2,4 2,6 2,7 3,0 3,3 3,5 4,0 4,3 1 8 /3 0 k V A /k m 2,3 2,5 2,7 2,9 3,1 3,3 3,7 4,0 4,4 4,8

Short-cirguit current carrying capacity of copper screens Short-circuit temperature: 350o C


S h o rt- c i r c u i t ti m e i n s e c o n d s s 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,5 2,0 3,0 4,0 5,0 bei 16 mm kA 9,7 6,9 5,7 5,0 4,5 4,2 3,9 3,5 3,4 3,3 2,7 2,3 1,9 1,7 1,5
2

L o a d o f s h o r t- c i r c u i t c u r r e n t i n k A 25 mm 2 kA 15,1 10,7 8,9 7,7 7,0 6,4 6,0 5,6 5,3 5,1 4,2 3,6 2,9 2,6 2,3 35 mm 2 kA 21,2 15,1 12,5 10,9 9,8 9,0 8,4 7,9 7,5 7,2 5,9 5,1 4,2 3,6 3,2

Coordina on of screen-cross-sec on
conductor cross-sec on mm 2 35 b is 120 150 b is 300 400 u n d 500 screen-cross-sec on mm 2 16 25 35

420

Conversion factor for Medium Voltage Power Cables, 6 - 35 kV


Load ra ng for cables laid in ground Load factor 0,7 and 1,0
Fundamental condi ons* G ro u n d te m p e ra tu re 20 oC T h e rm a l re s is tivity 1,0 K . m/W Distance between cables or systems 7 cm Single core cables laid in trefoil touching arrangement

Load factor 0,7


Type of Cable insula on design PVC Mul core cables Three core cables Single core cables Single core cables VPE Mul core cables Single core cables Nominal voltage 0,6/1 up to 3,6/6 kV up to 6/10 kV 0,6/1 up to 3.6/6 kV up to 6/10 kV 0,6/1 up to 18/30 kV 0,6/1 up to 18/30 kV Number of cables or systems 2 4 6 0,86 0,71 0,64 0,87 0,71 0,63 0,85 0,70 0,63 0,83 0,66 0,57 0,85 0,70 0,63 0,85 0,70 0,63

8 0,60 0,59 0,59 0,53 0,59 0,58

10 0,57 0,54 0,56 0,49 0,56 0,56

Load factor 1,0


Type of insula on PVC Cable design Mul coe cables Tree core cables Single core cables Single core cables Mul coe cables Single core cables Nominal voltage 0,6/1 up to 3,6/6 kV up to 6/10 kV 0,6/1 up to 3.6/6 kV up to 6/10 kV 0,6/1 up to 18/30 kV 0,6/1 up to 18/30 kV Number of cables or systems 2 4 6 0,66 0,67 0,65 0,62 0,67 0,66 0,52 0,51 0.51 0,47 0,53 0,52 0,46 0,45 0,46 0,40 0,47 0,47

1 0,81 0,82 0,79 0,78 0,83 0,81

8 0,43 0,41 0,42 0,36 0,44 0,43

10 0,40 0,40 0,41 0,41

VPE

Build-up of systems:
for single core cables 7 cm for mul core cables 7 cm

* Conversion factors for mul core cables (


N u m b e rs o f l o a d e d c o re s

5 cores), Conductor cross-sec on from 1,5 to 10 mm 2


C o n v e rs i o n fa c to rs fo r th e v a l u e s o f 1 ,5 to 1 0 m m 2 to the belonging table E a r th A ir
0,7 0,6 0,5 0,45 0,4 0,35 0,3 0,25 0,75 0,65 0,55 0,5 0,45 0,4 0,35 0,3

5 7 10 14 19 24 40 61

* For other condi ons e. g. ground, temperature grouping, load factor, thermal resistance, the ra ng factors should be calculated according to DIN VDE 0276 part 1000.

Ra ng conversion factors for installa on of Medium Voltage Cables, 6 - 35 kV


Ra ng conversion factors for laying in air*) Mul core cable and single core dirrect current cable
Arrangement of cables in laying condi on Number cables troughs or trays Without inter-contact Space = cable d Distance from wall 2 cm Number of cables Installa on method on the ground
d d

With inter-contact contact with wall

Number of cables 6 Installa on method 1 2 3 4 6 9

1
a 20 mm

0,97
a

0,96 0,94

0,93

0,90
a 20 mm

0,97
a

0,85

0,78 0,75

0,71 0,68

on nonperforated cable troughs (res tricted air circula on)

1 2 3 6

d d

0,97 0,97 0,97 0,97


a

0,96 0,95 0,94 0,93

0,94 0,92 0,91 0,90

0,93 0,90 0,89 0,88

0,90 0,86 0,84 0,83

0,97 0,97 0,97 0,97


a 20 mm

0,85 0,84 0,83 0,81

0,78 0,76 0,75 0,73

0,75 0,73 0,72 0,69

0,71 0,68 0,66 0,63

0,68 0,63 0,61 0,58

300 mm

300 mm

20 mm

2d 2d

300 mm

on perforated cable troughs

1 2 3 6
a 20 m m

1,00 1,00 1,00 1,00

1,00 0,99 0,98 0,97

0,98 0,96 0,95 0,94

0,95 0,92 0,91 0,90

0,90 0,87 0,85 0,84

1,00 1,00 1,00 1,00


a 20 m m

0,88 0,87 0,86 0,84

0,82 0,80 0,79 0,77

0,79 0,77 0,76 0,73

0,76 0,73 0,71 0,68

0,73 0,68 0,66 0,64

on cable trays or on cable ladders (unres tricted air circula on)

1 2 3 6

d d

1,00 1,00 1,00 1,00


a

1,00 0,99 0,98 0,97

1,00 0,98 0,97 0,96

1,00 0,97 0,96 0,94

1,00 0,96 0,93 0,91

1,00 1,00 1,00 1,00


a 20 mm

0,87 0,86 0,85 0,83

0,82 0,80 0,79 0,76

0,80 0,78 0,76 0,73

0,79 0,76 0,73 0,69

0,78 0,73 0,70 0,66

300 mm

300 mm

20 mm

on platform or on wall or on perforated cable tray

d d

1 2

1,00 1,00

0,91 0,89 0,91 0,88

0,88 0,87

0,87 0,85

1,00 1,00

0,88 0,88

0,82 0,78 0,81 0,76

0,73 0,72 0,71 0,70

225 mm

laid on pla orm or on the wall

225 mm

0,95

0,78

0,73 0,72

0,68 0,66

2 cm

1)In narrow rooms or for bigger grouping, the air temperature is increased due to energy losses of cable, so the addi onal conversion factors for devia ng air-temperatures are to be taken in the given table.

20 cm

Arrangements , for which a reduction 1 not necessary

Number of cable arranged one over another is optoinal

Number of cable arraanged s ide-by-s yde is optoinal

2 cm

2d d

d 2d

Ra ng conversion factors for installa on


of Medium Voltage Cables, 6 -35 kV
Ra ng conversion factors for laying in air*) Single core cables in 3-phase systems
Arrangement of cables in laying condi on Number of cables troughs or trays o n to p of ea c h other For laying on plain surface Space = cable d Distance from wall 2 cm N u m b e r o f s y s te m s 1 2 3 In s ta lla tio n m e th o d
d d

For installa on in grouping S p a c e = 2x c a b le d Distance from wall 2 cm N u m b e r o f s y s te m s 1 2 In s ta lla tio n m e th o d


2d 2d

on the ground on nonp e rfo ra te d c a b le tro u g h s (re s tric te d air circula on) on perforated c a b le tro u g h s

20 mm

0,92 0,89 0,88

20 mm
2d 2d

0,98 0,96 0,94

1 2 3 6

300 mm

d d

0,92 0,87 0,84 0,82


a

0,89 0,84 0,82 0,80

0,88 0,83 0,81 0,79

0,98 0,95 0,94 0,93 a 20 mm


2d 2d a

0,96 0,91 0,90 0,88

0,94 0,87 0,85 0,82

20 m m

300 mm

300 mm

1 2 3 6

d d

1,00 0,97 0,96 0,94

0,93 0,89 0,88 0,85

0,90 0,85 0,82 0,80

300 mm

1,00 0,97 0,96 0,95

0,98 0,93 0,92 0,90

0,96 0,89 0,85 0,83

20 m m

20 mm
2d 2d

o n c a b le tra y s o r o n c a b le la d d e rs (u n re s tric te d air circula on)

300 mm

d d

300 mm

1 2 3 6

1,00 0,97 0,96 0,94

0,97 0,94 0,93 0,91

0,96 0,93 0,92 0,90 a

1,00 0,97 0,96 0,95


a

1,00 0,95 0,94 0,93

1,00 0,93 0,90 0,87

20 mm

20 mm

d d

225 mm Arrangements, for which a reduc on not necessary For the installa on on plain surface with greather distance, the muntual hea ng, is lower for this occur the addi onal sheath or screen-losses. Because of that no par culars can be made for reduc on-free arrangements.

2d

o n p la tfo rm o r o n th e wa ll

0,94 0,91 0,89 0,94 0,90 0,86

1,00 0,91 0,89 1,00 0,90 0,86

225 mm

1)

* Conversion factors for devia ng ambient temperature


Temperature o C XLPE-cable PVC-cable
*1

10 1,15 1,22

15 1,12 1,17

20 1,08 1,12

25 1,04 1,06

30 1,0 1,0

35 0,96 0,94

40 0,91 0,87

45 0,87 0,79

50 0,82 0,71

) In narrow rooms or for bigger grouping, the air temperature is increased due to energy losses of cable, so the addi onal conversion factors for devia ng air-temperatures are to be taken in the given table.

Designa on Code for Harmonized Cables According to DIN VDE 0281/DIN VDE 0292
Construc on reference
Iden A H ca ons of Designa on Authorized na onal standards Harmonized standards

H 05 V

25 G 0.75

Nominal Voltage U 01 100 V 03 300/300 V 05 300/500 V 07 450/750 V Insula on Material B G N2 R S V V2 V3 V4 Z (EPR) Ethylene-Propylene Rubber (EVA) Ethylene-Vinylacetat Copolymer (CR) Chloroprene Rubber for welding cables (NR a./o. SR) Natural a./o. Synthe c Rubber (SiR) Silicone Rubber (PVC) Polyvinyl Chloride (PVC) Polyvinyl Chloride heat-resistant (PVC) Polyvinyl Chloride low-temperature (PVC) Polyvinyl Chloride cross-linked (PE) Polyethylene cross-linked

Structural Elements C Q4 T T6 Screen (PA) Addi onal polymide core jacket Addi onal tex le braiding over laid-up cores Addi onal tex le braiding over individual cores

Sheath/Jacket Material B J N N2 N4 Q R T T2 V V2 V3 V4 V5 (EPR) Ethylene-Propylene Rubber Glass Fibre Braid (CR) Chloroprene Rubber (CR) Chloroprene Rubber for welding cables (CR) Chloroprene Rubber heat-resistant (PUR) Polyurethane (NR a./o. SR) Natural a./o. Synthe c Rubber Tex le braid Tex le braid with ame retardant compound (PVC) Polyvinyl Chloride (PVC) Polyvinyl Chloride heat-resistant (PVC) Polyvinyl Chloride low-temperature (PVC) Polyvinyl Chloride cross-linked (PVC) Polyvinyl Chloride oil-resistant

Special Structural Features D3 D5 FM H H2 H6 H7 H8 Stress-relieving element (support wire) Centre core (no suppor ng elements) Telecommunica ons cores integrated in power cables Flat, separable cable (twin cable) Flat, non-separable cable (two-core sheathed cable) Flat, non-separable cable (mul -core and mul ple sheathed cable) Two-layer insula ng jacket Spiral cables

Conductor Type D E F H K R U Y Finely stranded, for welding cables (Very) nely stranded, for welding cables Finely stranded, for cables for xed installa on (Very) nely stranded, for exible cables Finely stranded, for cables for xed installa on Mul ple-wire, round, class 2 Single-wire, round, class 1 Tinsel wire, DIN 47104

Number of cores Earth Core G X With earth core Without earth core

Conductor Nominal Cross Sec on in mm 2


Examples: H07V-U 2.5 black (according to DIN VDE 0281) Harmonized PVC-insulated single-core sheathed cable, 2.5 mm, 2 single-core, nominal voltage 750 V H07RN-F 3G, 1,5 (according to DIN VDE 0282) Harmonized rubber-sheathed cable for medium tensile loads, three-core 1.5 mm , 2 nely stranded, green-yellow earth core, nominal voltage 750 V

Permissible Minimum Bending Radius

according to DIN VDE Speci ca ons

The indicated values for bending radius stated in the following table are not permi ed to fall below the value. For noncomplience of the values a short longevity is to be expected.

Permissible Minimum Bending Radius for Power Cables according to DIN 0298 - Part 3 - Nominal Votage 0.6/1 kV

Cables for Fixed Installa ons


Outer of Cables or Thickness of Flat Cable in mm (D) M e th o d o f L a y in g
- fo r p e rm a n e n t la y in g - to fo rm o u t

U p to 1 0 m m
4x D 1x D

> 1 0 to 2 5 m m
4x D 2x D

> 2 5 mm
4x D 3x D

For Flexible Cables


- fo r fix e d in s ta lla tio n - fo r fre e m o ve m e n t - to th e in le t - fo r fo rc e d g u id in g o p e ra tio n (such as trailing) - O p e ra tio n fo r tro lly c a b le - o p e ra tio n in p o we r d ra g c h a in - o p e ra tio n fo r re tu rn s h e a ve

up to 8 mm
3x D 3x D 3x D 5x D 3x D 4x D 7.5x D

> 8 mm to 12 mm
3x D 4x D 4x D 5x D 4x D 4x D 7.5x D

>12 to 20 mm
4x D 5x D 5x D 5x D 5x D 5x D 7.5x D

>20 mm
4x D 5x D 5x D 6x D 5x D 5x D 7.5x D

D = outer of cables or thickness of at table

DESIGNATION CODE FOR TELEPHONE CABLES, JUMPER WIRES AND STRANDED HOOK-UP WIRES according to DIN VDE 0271/0276
Construc on reference
Basic cable Type with addi onal Informa on A outdoor cable I installa on cable YV/Li ... jumper wires/hook-up wires Insula on P dry paper Y PVC (Polyvinylchloride) 2Y PE (Polyethylene) 02Y foamed PE (cellular) 02YS foam-skin insula on Screening C screen of braided nned copper wires F lling of cable core with petrol-jelly (St) screen of plas c coated metallic foil (L) aluminium tape Sheath Material L smooth aluminium sheath M lead sheath (L)2Y copolymer coated aluminium Mz lead alloy sheath moisture barrier sheath Protec ve Coa ng Y PVC sheath 2Y PE sheath Number of Stranding Elements ..x1x single core ..x2x pair (double core) ..x3x triple ..x4x quad ..x5x ve-core Conductor Diameter in mm Type of Stranding Components St I P PiMF St III star quad without phantom circuit twisted pair pair in metal foil star quad in local (Subscriber) cable

Stranding Layout Lg layer stranded concentric Bd unit stranding Armouring Wire b armouring B armouring of steel band for induc ve protec on 1B 0.3 1 layer steel tape, thickness 0.3 mm 2B 0.5 2 layers steel tape, thickness 0.5 mm

DESIGNATION CODE FOR MEDIUM VOLTAGE CABLES


According to 31.3-00214534-017-2003, IEC 60502-2:2005

3 Conductor Insula on

three stranded single-core cables, twisted together aluminium conductor copper conductor (without designa on) insula on of cross-linked polyethylene (XLPE) copper screen over the each core collec ve copper screen for three core cables

Screen

closure of common screen by alumpolyethylene band. longitudinal water-blocking of water swelling tapes longitudinal and radial water-blocking with water-swelling tapes and aluminium-copolymer bands armour of steel strips armour of steel round wires armour of aluminium round wires outer sheath of polyethylene (PE) or polyethylene copolymer

Armour

( )* Outer sheath HF (A)*

outer jacket made of polymer composi on, prevents spread of lre (category A for non-spread of lre in wisps according to IEC 60332-3). outer jacket of polymer halogen-free composi on (category A for non spread of lre in wisps). reinforced polyethylene (PE) sheath outer sheath of polyvinylchloride (PVC) compound outer sheath of lame retardant polyvinylchloride (PVC) compound outer sheath of lame retardant, low smoke of corrosive gases polyvinylchloride (PVC) compound U variant (UHL) (without marking) T variant (tropical)

Climate condi ons

nxS/ S ( )

number of cores, nominal cross-sec on in mm 2 /nominal cross-sec on of the screen in mm 2 single-wire cores

* in other cases the marking of category, corresponding to non-spread of re is not applied (cable corresponds to B category according to IEC 60332-3)
Example of designa on: Aluminium conductor XLPE insula on Screen of copper wires and with longitudinal water-blocking Outer sheath of PE Rated voltage, kV Number of cores Nominal conductor cross-sec onal area, mm Nominal screen cross-sec onal area, mm Standards and speci ca ons
2 2

-6 1 150/25

31.3-00214534-017-2003

Correspondence of XLPE-insulated medium voltage power cables

Ukraine

Russia

Germany With copper conductors


N2XSY, N2XSEY (2XSY, 2XSEY) N2XSY, N2XSEY (2XSY, 2XSEY) N2XS(F)2Y (2XS(F)2Y) N2XS(F)2Y (2XS(F)2Y) N2XS(FL)2Y (2XS(FL)2Y) N2XS(FL)2Y (2XS(FL)2Y) N2XSY, N2XSEY (2XSY, 2XSEY) N2XS(FL)2Y N2XS 2Y N2XS 2Y N2XS Y

Poland
YHKXS YnHKXS XUHKXS XUHKXS XRUHKXS XRUHKXS YnHKXS YnUHKXS YnRUHKXS

2 2 -LS

-HF -HF -HF

N2XS(F)H, N2XS (F)H N2XSBH N2XSRH

XnUHKXSxn NUHKXSn

With aluminium conductors


NA2XSY, NA2XSEY (A2XSY, A2XSEY) NA2XSY, NA2XSEY (A2XSY, A2XSEY) NA2XS(F)2Y (A2XS(F)2Y) NA2XS(F)2Y (A2XS(F)2Y) NA2XSF(L)2Y, NA2XS(FL)2Y NA2XSF(L)2Y, NA2XS(FL)2Y NA2XSY, NA2XSEY (A2XSY, A2XSEY) NA2XS(FL)2Y NA2XS 2Y NA2XS 2Y NA2XS Y N 2XS(F)H N 2XSBH N 2XSRH YHAKXS YnHAKXS XUHAKXS XUHAKXS XRUHAKXS XRUHAKXS YnHAKXS YnUHAKXS YnRUHAKXS

2 2

A A A A -HF -HF -HF

XnUHAKXSxn NUHAKXSn