ta (Ik min) 5 s
The resulting current-breaking time of the selected protective equipment must ensure that the calculated minimum short-circuit current Ik min at the end of the transmission line or protected line is automatically cleared within 5 s at the most. Overload and short-circuit protection need not necessarily be provided by one and the same device. If required, these two protection targets may be realized by a device combination. The use of separate switching protective devices could also be considered, i.e., at the start and end of a cable route. As a rule, devices applied at the end of a cable route can ensure overload protection for that line only. Final circuits The method for coordinating overload and short-circuit protection is practically identical for distribution and nal circuits. Besides overload and short-circuit protection, the protection of human life is also important for all circuits. Protection against electric shock