You are on page 1of 7

HELAIAN TUGASAN

(Assignment Sheet)

NAMA KURSUS TAJUK MODUL TAJUK SUB MODUL

SIJIL TEKNOLOGI ELEKTRIK AKTA BEKALAN, PERATURAN-PERATURAN ELEKTRIK DAN PIAWAIAN MS IEC 60364 Electrical Installation of Building-Paiwaian MS IEC 60364 Guide To MS IEC 60364 Menerangkan mengenai Peraturan Electrical Installation of Building berpandukan Paiwaian MS IEC 60364 supaya kerja-kerja pepasangan elektrik mengikut standard yang ditetapkan. MUKA: NO. K/P 1 DRP: 6

OBJEKTIF PRESTASI / Performance Objective (PO) KOD RUJUKAN NAMA

TAJUK : TUJUAN :

Perbezaan MS IEC 60364 Dengan I.E.E

Helaian tugasan ini adalah bertujuan untuk memantapkan kefahaman dan meningkatkan kemahiran pelatih tentang perbezaan peraturan MS IEC 60364 dan Peraturan I.E.E.

ARAHAN : Pelatih dikehendaki menjawab semua soalan didalam helaian tugasan ini.

KOD RUJUKAN Soalan 1 Berikan maksud MS IEC 60364 dan I.E.E ?

MUKA:

DRP:

i. ii.

...................................................................................... ......................................................................................
( 2 MARKAH)

Soalan 2 Isikan tempat kosong di bawah berpandukan perbezaan MS IEC 60364 dan I.E.E ? N o Subject Latest Revision MSIEC60364 BS7671 (IEE 16th Edition)

Scope

Exclusion list

Voltage ranges

( 8 Markah )

KOD RUJUKAN Soalan 3.

MUKA:

DRP:

Isikan tempat kosong di bawah berpandukan perbezaan MS IEC 60364 dan I.E.E ? No Subject K MSIEC60364 BS7671 (IEE 16th Edition)

Selection And Erection of Equipment Isolation, Switching and Control

Emergency switching

Earthing Arrengement Part Water pipes Part 5-54 Part 5 Chaper %4

Alum as protective bonding

Protective conductors

Insulation for protective conductors

( 10 Markah )

KOD RUJUKAN

MUKA:

DRP:

KOD RUJUKAN

MUKA:

DRP:

Jawapan no 1

The IEE 16th Edition is a familiar standards with Malaysian Engineers. IEE 16th Edition is known as BS 7671 Wiring Installation for Buildings Jawapan no 2 N o Subject Latest Revision MSIEC60364 2002 BS7671 (IEE 16th Edition) 1992, 2002 (Amd), 2005 (Draft)

Scope

Residential, industrial, commercial agricultural, horticultural premises, pre-fab buildings, construction sites, marinas etc. External consumber installation, extension, alteration etc.

Covers all installation not in exclusion list. Similar listing of coverage as per MSIEC60364.

Exclusion list Traction equip., motor vehicles, Traction equip., moto vehicles, Ship, aircraft, street lightings, Ship, aircraft, ships, motor vehicles, off mines, RF suppressor, electric shore installations, aircraft, mines, fence, lightning etc. Public lightning lifts. distribution system, generation, transmission

Voltage ranges

Up to 1kVa.c. or 1.5Vd.c.

Extra low voltage & low voltage

KOD RUJUKAN

MUKA:

DRP:

Jawapan no 3 No Subject K MSIEC60364 BS7671 (IEE 16th Edition)

Selection And Erection of Equipment Isolation, Switching and Control

Emergency switching

No specific prohibition.

Plug & socket as means of emergency switching is prohibited.

Earthing Arrengement Part Water pipes Part 5-54 Use of water pipes as earth electrode are left to the discretion of national committees Part 5 Chaper %4 Water pipes are not allowed to be used as earth electrodes.

Alum as protective bonding

No specific restriction (left to the discretion of national committees.

Prohibits the use of aluminum or copper clad aluminum as protective bonding conductors.

Protective conductors

Allows aluminium of appropriate cross sectional area.

Protectice conductor of 10mm or less shall be exclusively copper.

Insulation for No specific prescription. protective conductors

Protective conductor of up to and including 6mm shall be protected by insulation.