50LJS/TJS007-014 (60Hz)

Single- Package
Rooftop Units
6 to
12.5 Nominal Tons

Product Data

Single package rooftop cooling units with electric heat option. Compact, horizontal
discharge units (vertical discharge option), combining installation flexibility with efficient
performance.

Features / Benefits
Higher Cooling Capacity.
Standard cooling operation at outdoor ambient
temperature as high as 50 C (122 F).
Galvanized steel cabinet with powder paint coat.
2-inch (51 mm) return-air filters.
Commercial strength base rails (full perimeter).
Corrosion-resistant sloped condensate pan.
Single power entry to the unit.
Commercial duty motors with permanently
lubricated bearings.
All units feature sloped condensate drain pans in
accordance with ASHRAE Standard 62. Also, the new
sloped condensate pan permits either an external drain
(outside the roof curb) or an internal bottom drain (inside
the roof curb). Both options require an external, fieldsupplied disconnect, if desired.
In addition, these units have a standard filter access door,
which permits tool less changes and provides an opening
for outdoor air options and accessories (models 007-014).
Field installed electrical heaters are available in a wide
range of capacities. Singe point wiring kit makes
installation simple.
Simple electrical connections: Terminal boards, located in
the base unit control box, facilitate connections to room
thermostat, outdoor thermostat (s), economizer, and
electrical heat permitting easy servicing.
Thru-the-curb service connections accessory allow power
and control wiring to be routed through the curb,
minimizing roof penetrations. Both power and control
connections are made on the same side of the unit to
simplify installation.
Quite and efficient operation is provided by belt-driven
evaporator fans. The belt-driven evaporator fan with
variable pitch pulleys allows adjustment to available static
pressure to meet the job requirements of even the most
demanding applications.

50TJS-03 PD 60HZ

2008

Model Number Nomenclature


50 TJ S 008 5

50LJS/TJS

50Cooling Only/Cooling
with Optional Electric Heat
(Field Installed)
LJConstant Volume, Size 007.
TJConstant Volume, size 008-014.

3 1 SR _

L Horizontal Discharge
B Vertical Discharge
NE Standard Unit, Size 007.

SR Standard Unit, Size 008-014.

S - SAMCO
Nominal Capacity in Tons (kW)
007 - 6 Tons (21 kW)
008 - 7 1/2 Tons (26 kW)
009 - 8 1/2 Tons (30 kW)
012 - 10 Tons (35 kW)
014 - 12 Tons (44 kW)
Coil Fin Option

AL Evaporator, AL Condenser.

P Pre-Coated Condenser Coil ( Aluminum Fins ).

Packaging
1Standard.
3 Export.
Design Series

3 With Fixed Orifice Expantion.

Voltage
2 380360
5 208/230360

LEGEND
AL Aluminum

Table of Contents
Model Number Nomenclature. ..
ARI Capacity Rating.
Physical Data.
Performance Data.
Base Unit Dimensions.
Fan Performance Data.
Electrical Data
Typical Piping and Wiring..
Typical Wiring Schematic..
Controls
Guide Specifications

Page
2
3
4
6
8
10
21
23
24
29
30

UNIT

NOMINAL STANDARD
NET COOLING
TOTAL
TONS
CFM
CAPACITY (Btuh)
kw

EER

SOUND
RATING (Bels)

50LJS007

2100

73,600

7.8

9.0

8.4

50TJS008

7 1/2

2800

86,000

9.4

9.2

8.6

50TJS009

8 1/2

3000

98,600

10.6

9.3

8.6

50TJS012

10

4000

115,000

12.8

9.0

8.8

50TJS014

12 1/2

4500

147,800

15.2

9.7

8.8

Bels
db
EER

50LJS/TJS

ARI Capacity Rating*

- Sound Levels (1 bel = 10 decibels)


- dry bulb
- Energy Efficiency Ratio

*ARI - Air Conditioning and Refrigeration Institute.

1.
2.
3.

Rated in accordance with ARI Standards 210/240-89 or 360-86 and 270-84.


Ratings are net values, reflecting the effects of circulating fan heat.
Ratings are based on:

Cooling Standard: 80 F db, 67 wb indoor entering-air temperature and 95 F db air entering outdoor
unit, Horizontal Discharge, 0.4 iwg External Static. .

Physical data (60Hz) English


UNIT MODEL 50 SERIES
Electrical Configuration
Nominal Cooling Capacity

LJS007

TJS008

009

012

014

460,380,208 / 230 - 3 - 60

V-PH-Hz
TR

7.5

8.5

10

12.5

Kbtu/hr

72

90

102

120

150

Unit

lbs

520

755

760

915

930

Economizer

lbs

34

44

44

44

44

Roof Curb

lbs

115

143

143

143

143

COMPRESSOR

type

Scroll

Quantity

no.

Oil (per compressor)

oz

77

47

52

52

77

5 - 14

8- 10

50LJS/TJS

OPERATING WEIGHT

REFRIGERANT
Operating Charge / Circuit
CONDENSER FAN
Quantity . Diameter
Nominal CFM
Motor hp rpm
CONDENSER COIL
Rows Fins/inch

Hermetic, Reciprocating

type

R -22

lbs-oz

9-0

4 - 14

6 - 14

type

Propellar

no.in.

1 . 26

2 . 22

2 . 22

2 . 22

2 . 22

CFM

4100

7150

7150

7700

7700

hprpm

1/3 .850

1/4 . 1100

1/4 . 1100

1/4 . 1100

1/4 . 1100

type

Enhanced Copper Tubes, Aluminum Double-Wavy Fins

no.per in.

2 17

1 17

2 17

2 17

2 17

Total Face Area

sq. ft

12.25

20.5

18

17.42

25

EVAPORATOR FAN

type

1 . 15 x15

1 . 15 x15

Quantity . Size

no.in.

Centrifugal Type
1 10 x 10

1 . 15 x15

1 . 15 x15

Drive Type

type

Nominal CFM

CFM

2100

2800

3000

4000

4500

hp, rpm

1.7 , 1725

2.9 , 1725

2.9 , 1725

2.9 , 1725

3.7 , 1725

Nominal Motor hp, rpm


HIGH PRESSURE SWITCH

Belt Driven

Psig
400 - 500

Standard Compressor IPRV setting


Cutout

Cutout

4 10

17 27

14

Rows Fins / inch

20 - 30

F
25 - 35

Closes

EVAPORATOR COIL

300 - 340

Psig

Resest (Manual)

FREEZE-PROTECTION SWITCH
Opens

463 - 477

Resest (Auto)

LOW PRESSURE SWITCH

type

/ 40 - 50

Enhanced Copper Tubes, Aluminum Double-Wavy Fins

noper in.

4 15

3 .15

3 ..15

3 . 15

4 . 15

Total Face Area

sq. ft

5.5

10

11.1

OUTDOOR AIR INLET SCREENS

type

Quantity . Size
RETURN AIR FILTERS
Quantity . Size

Scroll

no.in.

Cleanable
1 .20x24x1

type
no.in.

1 20x25x1 + 1 .16x25x1
Throw away

2 .16x25x2

4 . 16x20x2

4 20x20x2

Physical data (60 Hz) SI


UNIT MODEL 50 SERIES

LJS007

TJS008

012

014

TR

7.5

8.5

10

12.5

KW

21.1

26.3

29.9

35.17

43.9

Unit

Kg

236.3

343.1

345.4

415.9

422.7

Economizer

kg

15.45

20

20

20

20

Roof Curb

kg

52.2

65

65

65

65

COMPRESSOR

type

Scroll

Quantity

no.

Oil (per compressor)

ml

2277

1390

1538

1538

2277

2.67

3.92

Electrical Configuration
Nominal Cooling Capacity

V-PH-Hz

009
208 / 230 - 3 - 60

REFRIGERANT
Operating Charge / Circuit
CONDENSER FAN
Quantity . Diameter

Hermetic, Reciprocating

type
kg

Scroll

R -22
4.09

2.18

3.12

type

Propellar

no mm

1 . 660.4

2 . 558.8

2 . 558.8

2 . 558.8

2 . 558.8

Nominal Airlflow

L/s

1934.8

3374

3374

3634

3634

Motor KW rps

KW rps

0.25 .14.16

0.18 . 18.33

0.18 . 18.33

CONDENSER COIL
Rows Fins/inch
Total Face Area
EVAPORATOR FAN
Quantity . Size
Drive Type

type

0.18 . 18.33 0.18 . 18.33

Enhanced Copper Tubes, Aluminum Double-Wavy Fins

no .per 25 mm

2 17

1 17

2 17

2 17

2 17

sq. m

1.14

1.9

1.67

1.61

2.32

type
no.mm x mm

Centrifugal Type
1 254 x 254

1 . 381 x381 1 . 381 x381 1 . 381 x381 1 . 381 x381

type

Nominal Airflow
Nominal Motor Kw, rps

HIGH PRESSURE SWITCH

Belt Driven

L/s

991

Kw, rps

1.26 , 28.75

1321

1416

2.16 , 28.75

Cutout

Opens

3192 - 3289

Rows Fins / inch

28 69 / 117 186

97

(-)4
type

to 1.66

3 .15

Total Face Area

sq. m

0.51

0.74

OUTDOOR AIR INLET SCREENS

type

Quantity . Size

138 - 207

no.mm

4.44 to 10

3 ..15

3 . 15

4 . 15

0.74

0.929

1.03

Cleanable
1 .508x609.6x25.4

type
no.mm

Enhanced Copper Tubes, Aluminum Double-Wavy Fins


4 15

RETURN AIR FILTERS

noper 25 mm

Quantity . Size

2068 - 2344

Closes

EVAPORATOR COIL

2124
2.76 , 28.75

kPa

Resest (Manual)

FREEZE-PROTECTION SWITCH

2.16 , 28.75

2758 - 3448

Resest (Auto)

LOW PRESSURE SWITCH

1887

2.16 , 28.75

kPa

Standard Compressor IPRV setting


Cutout

50LJS/TJS

OPERATING WEIGHT

1 508x635x25.4 + 1 .406.4x635x25.4
Throw away

2 .406.4x635x50.8

4 . 406.4x508x50.8

4 508x508x50.8

Performance data (cont)


COOLING CAPACITIES
50LJ007 (6 TONS)
Temp (F)
Air Entering
Condenser
(Edb)
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

50LJS/TJS

75

85

95

105

115

72
88.7
44.4
5.5
86.0
43.5
6.2
83.2
42.6
6.9
80.0
41.5
7.7
76.6
40.2
8.4

Evaporator Air Quantity Cfm/BF


2100/0.08
2400/0.09
Evaporator Air Ewb (F)
67
62
72
67
82.1
75.4
90.8
84.1
56.0
66.9
46.5
59.6
5.4
5.3
5.6
5.4
79.3
72.8
87.8
81.2
55.0
65.7
45.5
58.6
6.1
5.9
6.3
6.1
76.5
70.2
84.8
78.2
54.0
64.6
44.6
57.6
6.7
6.5
7.0
6.8
73.4
67.3
81.6
74.9
52.8
63.1
43.5
56.4
7.4
7.3
7.7
7.5
70.1
64.3
78.0
71.5
51.5
61.4
42.3
55.1
8.2
8.0
8.5
8.3

Evaporator Air Quantity Cfm/BF


2800/0.09
3000/0.10
Evaporator Air Ewb (F)
67
62
72
67

1800/0.06
72
86.6
42.2
5.5
84.1
41.4
6.2
81.6
40.6
6.9
78.4
39.4
7.6
75.1
38.1
8.4

67
80.0
52.3
5.3
77.4
51.3
6.0
74.7
50.3
6.7
71.8
49.2
7.4
68.7
47.9
8.1

62
73.6
62.2
5.2
71.0
61.1
5.9
68.5
60.0
6.5
65.6
58.7
7.2
62.5
57.2
7.9

3000/0.11
62
77.2
71.6
5.3
74.5
70.3
5.9
71.8
69.1
6.6
68.9
67.4
7.3
66.1
65.5
8.1

72
93.2
50.1
5.7
90.1
49.4
6.4
87.0
48.7
7.0
83.3
47.4
7.8
79.5
46.3
8.6

67
86.6
66.4
5.5
83.5
65.4
6.2
80.4
64.5
6.9
76.9
63.1
7.6
73.3
61.6
8.3

62
79.7
78.7
5.4
77.3
76.7
6.0
74.8
74.7
6.7
72.1
72.0
7.4
69.3
69.2
8.2

50TJ008 (7.5 TONS)


Temp (F)
Air Entering
Condenser
(Edb)

2250/0.07

3750/0.12

72

67

62

72

62

72

67

62

75

TC
SHC
kW

105.9
50.9
7.14

97.6
63.7
6.82

88.8
75.4
6.5

109.0
54.2
7.28

101.1
69.8
6.98

92.7
84.0
6.68

109.6
55.2
7.32

102.0
71.9
7.04

93.5
86.5
6.72

112.5
59.9
7.46

104.6
79.7
7.18

96.4
95.0
6.86

85

TC
SHC
kW

101.1
49.4
7.66

92.9
62.0
7.34

84.0
73.3
7

104.9
53.1
7.82

96.4
68.4
7.5

87.8
82.0
7.18

105.7
54.4
7.86

97.2
70.7
7.54

88.6
84.5
7.22

107.7
58.5
7.98

99.7
78.3
7.68

92.3
92.1
7.4

95

TC
SHC
kW

96.6
47.8
8.18

87.8
59.9
7.84

78.9
70.9
7.48

99.9
51.7
8.36

91.1
66.5
8

82.4
79.5
7.64

100.5
52.9
8.4

91.7
68.8
8.04

83.6
81.4
7.7

102.4
57.3
8.5

93.9
76.6
8.16

87.8
87.8
7.92

105

TC
SHC
kW

91.1
45.9
8.68

82.2
57.9
8.3

72.9
68.0
7.98

93.7
49.6
8.8

85.3
64.5
8.46

76.8
76.4
8.14

94.3
50.9
8.86

85.9
66.7
8.5

78.3
77.9
8.2

96.6
55.8
8.98

88.0
74.6
8.64

83.0
83.0
8.42

115

TC
SHC
kW

85.3
43.9
9.16

76.0
55.4
8.78

68.0
65.1
8.42

87.8
47.8
9.3

79.1
62.2
8.92

71.7
71.7
8.64

88.2
49.2
9.34

79.7
64.5
8.96

73.1
73.1
8.72

90.2
54.4
9.48

81.8
72.5
9.1

78.3
78.1
8.94

50TJ009 (8.5 TONS)


Temp (F)
Air Entering
Condenser
(Edb)

2550/0.08

Evaporator Air Quantity Cfm/BF


3000/0.10
3400/0.11
Evaporator Air Ewb (F)
67
62
72
67

4250/0.135

72

67

62

72

62

72

67

62

75

TC
SHC
kW

120.1
74.1
7.77

111.7
63.8
7.57

102.0
78.2
7.38

122.8
77.5
7.86

114.6
67.1
10.68

104.9
83.8
7.44

123.7
82.9
7.89

116.2
70.0
6.72

106.7
88.2
7.51

126.0
33.7
7.97

118.2
76.1
7.8

109.5
97.2
7.6

85

TC
SHC
kW

116.7
55.6
8.46

107.3
69.7
8.22

96.8
82.8
7.96

119.2
58.0
5.54

110.1
74.7
8.31

99.9
89.7
8.04

120.7
59.9
8.6

112.0
78.7
8.38

101.8
95.3
8.12

123.7
64.8
8.72

114.3
86.7
8.48

104.9
104.0
8.23

95

TC
SHC
kW

112.4
54.2
8.9

102.3
67.9
8.97

89.9
79.7
8.68

114.5
56.7
8.99

105.1
73.0
9.06

94.1
87.4
8.79

115.9
58.8
9.06

106.7
77.4
9.12

96.5
93.0
8.86

118.8
64.1
4.76

109.0
85.7
9.24

110.6
100.2
9

105

TC
SHC
kW

106.4
52.0
9.74

96.8
55.6
9.43

83.8
76.7
9.08

109.1
55.1
9.85

99.2
71.2
9.54

87.1
83.8
9.21

110.6
57.5
9.92

100.6
75.3
9.6

90.5
89.2
9.29

112.7
62.2
10.03

102.9
83.8
9.72

95.6
95.6
9.48

115

TC
SHC
kW

100.6
50.2
10.33

90.5
63.6
9.97

78.2
74.1
9.61

102.9
53.4
10.46

93.1
68.9
10.1

81.2
80.4
9.75

104.3
55.6
10.54

94.6
73.3
10.18

84.9
84.8
9.88

106.0
60.3
10.61

96.6
81.8
10.3

90.9
90.8
10.1

Performance data (cont)

COOLING CAPACITIES (cont)


50TJ012 (10 TONS)
Evaporator Air Quantity Cfm/BF
4000/0.125
Evaporator Air Ewb (F)
72
67
62

3000/0.095

5000/0.15

72

67

62

72

67

62

75

TC
SHC
kW

139.9
68.8
9.76

128.5
85.1
9.41

115.4
100.3
9.1

146.7
75.4
10

146.7
75.4
10

123.4
116.1
9.27

150.9
82.1
10.17

148.2
107.5
9.75

127.4
126.8
9.41

85

TC
SHC
kW

133.9
66.2
10.41

123.2
82.9
10.07

107.1
96.6
9.74

140.1
73.2
10.67

140.1
73.2
10.67

117.9
113.5
9.94

144.2
79.8
10.84

141.7
104.9
10.41

122.4
122.3
10.09

95

TC
SHC
kW

127.8
64.1
11.13

117.1
80.8
10.78

99.6
92.7
10.4

133.4
71.2
11.38

133.4
71.2
11.38

110.1
109.1
10.63

136.8
77.1
11.52

135.7
103.1
11.14

117.5
117.4
10.83

105

TC
SHC
kW

121.6
62.2
11.93

107.7
77.1
11.52

90.5
87.8
11.1

126.4
68.9
12.13

126.4
68.9
12.13

101.5
101.5
11.41

129.8
75.3
12.27

128.6
101.2
11.89

111.2
111.2
11.65

115

TC
SHC
kW

118.5
61.2
12.26

100.9
74.6
11.82

86.7
85.9
11.4

123.6
68.4
12.48

123.6
68.4
12.48

96.2
96.2
11.78

126.3
75.0
12.6

124.0
99.5
12.2

105.9
105.9
12

50TJ014 (12 1/2 TONS)


Temp (F
Air Entering
Condenser
(Edb)
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

75

85

95

105

115

Boldface
BF
Edb
Ewb
kW
Ldb
Lwb
SHC
TC

3750/0.08
72
175.6
85.7
11.16
169.3
83.9
12.15
161.9
81.4
13.12
154.9
79.0
14.16
146.2
76.1
15.09

67
162.2
107.3
10.85
155.7
104.8
11.78
148.9
102.0
12.72
141.3
99.2
13.66
132.2
95.7
14.57

62
149.2
128.0
10.57
140.6
124.0
11.42
132.0
119.8
12.28
123.0
115.5
13.17
113.1
110.3
14.07

72
181.0
91.4
11.32
174.2
89.6
12.31
166.8
87.0
13.30
158.8
84.5
14.31
150.5
81.7
15.30

Air Entering Evaporator Cfm/BF


4500/0.09
5000/0.10
Air Entering Evaporator Ewb (F)
67
62
72
67
167.5
154.2
182.9
170.2
116.2
140.3
94.2
122.2
11.00
10.69
11.37
11.07
160.7
147.0
176.9
163.0
113.9
137.0
92.7
119.7
11.94
11.58
12.39
12.01
153.5
139.1
169.5
155.7
111.1
133.2
90.7
117.3
12.89
12.46
13.40
12.97
145.4
130.2
160.9
147.6
108.2
128.1
87.8
114.3
13.82
13.35
14.38
13.91
137.0
122.4
152.3
139.4
105.2
122.3
85.0
111.6
14.76
14.25
15.37
14.87

- Standard Ratings

LEGEND
Bypass Factor

Entering Dry-Bulb

Entering Wet-Bulb

Compressor Motor Power Input

Leaving Dry-Bulb

Leaving Wet-Bulb

Sensible Heat Capacity (1000 Btuh) Gross

Total Capacity (1000 Btuh) Gross

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)

t ldb = t edb

1.10 x cfm

6250/0.12
62
156.4
146.5
10.73
149.7
143.6
11.63
142.8
140.2
12.56
135.0
134.9
13.48
127.8
127.7
14.43

72
187.2
102.1
11.49
181.5
100.9
12.53
173.2
98.3
13.54
165.3
96.6
14.58
155.2
92.9
15.49

67
174.7
135.3
11.19
167.3
133.4
12.14
159.5
130.8
13.11
151.2
127.8
14.07
142.7
125.0
15.02

62
161.8
160.7
10.87
155.8
155.6
11.82
149.6
149.6
12.78
143.2
143.1
13.77
136.0
135.8
14.73

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.


Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

BYPASS
FACTOR
(BF)

79
81

.05
.10
.20
.30

1.04
.98
.87
.76

ENTERING AIR DRY-BULB TEMP (F)


78
77
76
75
under 75
82
83
84
85
over 85
Correction Factor
2.07
3.11
4.14
5.18
1.96
2.94
3.92
4.90
Use formula
1.74
2.62
3.49
4.36
shown below.
1.53
2.29
3.05
3.82

Interpolation is permissible.

Correction Factor = 1.10 x (1 - BF) x (edb - 80).

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapora


tor coil (hlwb )
hlwb =h ewb

total capacity (Btuh)

4.5 x cfm

Where: hewb = Enthalpy of air entering evaporator coil

50LJS/TJS

Temp (F)
Air Entering
Condenser
(Edb)

50LJS/TJS

Base unit dimensions 50LJS007

50LJS/TJS

Base unit dimensions 50TJS008-014

Performance data (cont)


FAN PERFORMANCE HORIZONTAL DISCHARGE UNITS
50LJS007 (6 TONS)
Airflow
(Cfm)

50LJS/TJS

1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000

Rpm
765
802
840
878
916
954
993
1031
1070
1109
1148
1188
1227

50LJS007 (6 TONS)
Airflow
(Cfm)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
Bhp
FIOP
Watts

Rpm
1178
1201
1226
1252
1280
1309
1336
1363
1390
1418
1446
1476
1506

STANDARD MOTOR (BELT DRIVE)*


0.1
Bhp
0.45
0.45
0.60
0.69
0.78
0.89
1.00
1.13
1.26
1.41
1.57
1.74
1.92

Watts
487
539
600
669
739
827
916
1022
1131
1258
1396
1543
1700

Rpm
821
854
888
923
958
993
1029
1066
1103
1140
1177
1215
1253

0.2
Bhp
0.51
0.58
0.66
0.75
0.85
0.96
1.07
1.20
1.34
1.48
1.64
1.81
2.00

External Static Pressure (in. wg)


0.4
Watts
Rpm
Bhp
Watts
Rpm
532
923
0.65
638
1019
585
953
0.73
700
1046
646
984
0.82
771
1073
716
1015
0.91
843
1101
795
1046
1.01
924
1129
883
1079
1.13
1022
1160
973
1112
1.25
1123
1190
1081
1145
1.39
1241
1220
1199
1179
1.52
1353
1251
1318
1212
1.67
1482
1283
1456
1246
1.83
1621
1316
1604
1281
2.00
1770
1349
1382
1770
1316
2.19
1936

STANDARD MOTOR (BELT DRIVE)* (cont)


External Static Pressure (in. wg)
1.0
1.2
1.4
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
1.14
1031
1249
1.32
1182
1316
1.52
1.23
1106
1274
1.43
1275
1338
1.62
1.33
1990
1297
1.53
1361
1363
1.73
1.45
1292
1320
1.64
1456
1388
1.85
1.58
1404
1345
1.77
1569
1410
1.97
1.71
1517
1372
1.91
1691
1434
2.11
1.85
1639
1400
2.06
1823
1459
2.26
1486
2.43
2.00
1770
1428
2.22
1962
2.15
1901
1456
2.38
2102
1514
2.61
1483
2.56
2257
1543
2.80
2.31
2041
2.48
2188
1510
2.73
2403

2.67
2352
1537
2.92
2562

2.88
2529

LEGEND
Brake Horsepower Input to Fan
Factory-Installed Option
Input Watts to Motor

*Motor drive range: 1070 to 1460 rpm. All other rpms require fieldsupplied drive.
NOTES:
1. Boldface Out of Drive Package or Motor range .

Watts
1353
1439
1534
1639
1744
1866
1997
2145
2300
2462

Rpm
1382
1402
1424
1448
1473
1496
1519
1543
1569

0.6
Bhp
0.81
0.90
0.99
1.08
1.19
1.31
1.43
1.57
1.71
1.87
2.04
2.22
2.42

1.6
Bhp
1.72
1.83
1.94
2.07
2.20
2.34
2.48
2.65
2.83

Watts
843
835
907
981
1072
1173
1275
1396
1517
1656
1805
1962
2136

Rpm
1099
1126
1154
1182
1209
1237
1264
1292
1322
1352
1383
1413
1444

0.8
Bhp
0.96
1.06
1.16
1.27
1.39
1.51
1.63
1.77
1.92
2.09
2.26
2.44
2.63

Watts
883
965
1047
1140
1241
1344
1447
1569
1700
1849
1997
2154
2317

Watts
1526
1621
1718
1831
1945
2067
2188
2335
2487

2. Maximum usable watts input is 2120 and maximum continuous bhp


is 2.40. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confi
dence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit war
ranty will not be affected.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
5. Interpolation is permissible. Do not extrapolate.

10

Performance data (cont)


FAN PERFORMANCE HORIZONTAL DISCHARGE UNITS
External Static Pressure (in. wg)
0.6
Watts
Rpm
Bhp
Watts
Rpm
630
630
0.86
803
695
646
635
0.89
827
699
684
645
0.95
875
708
723
654
1.01
924
717
747
659
1.05
956
722
771
663
1.08
981
727
827
672
1.14
1031
737
875
683
1.20
1081
747
932
693
1.27
1140
756
989
704
1.35
1207
765
1056
715
1.43
1275
775
1114
727
1.52
1353
785
1182
739
1.62
1439
795
1258
750
1.72
1526
806
1335
761
1.82
1613
817
1422
772
1.93
1709
828
1517
783
2.03
1796
840
1569
789
2.09
1849
846

0.8
Bhp
1.09
1.12
1.18
1.25
1.29
1.32
1.40
1.49
1.57
1.66
1.74
1.83
1.91
2.01
2.11
2.23
2.35
2.42

Watts
989
1014
1064
1123
1156
1182
1250
1327
1396
1473
1543
1321
1691
1779
1866
1971
2076
2136

Rpm
757
760
768
776
780
784
793
802
813
823
832
841
851
860
870
880
890
896

1.0
Bhp
1.34
1.37
1.44
1.51
1.55
1.58
1.66
1.75
1.84
1.94
2.05
2.15
2.26
2.36
2.47
2.57
2.69
2.75

Watts
1199
1224
1284
1344
1378
1404
1473
1552
1630
1718
1814
1901
1997
2084
2180
2266
2369
2420

50TJS008 (712/TONS STANDARD MOTOR (BELT DRIVE)* (cont)


External Static Pressure (in. wg)
Airflow
1.2
1.4
1.6
(Cfm)
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
2250
883
810
1.62
1439
850
1.91
1691
873
2.20
1945
2300
816
1.65
1465
859
1.94
1718
888
2.24
1980
903
2400
931
824
1.72
1526
872
2.01
1779
909
2.32
2050
2500
832
1.79
1587
882
2.09
1849
925
2.40
2119
955
2550
931
2.45
2162
964
836
1.83
1621
887
2.13
1884
2660
839
1.87
1656
891
2.17
1919
936
2.49
2197
973
2700
946
2.58
2275
987
846
1.95
1726
898
2.26
1997
2800
855
2.04
1805
906
2.35
2076
954
2.67
2352
997
2900
913
2.44
2154
961
2.77
2436
1006
863
2.13
1884
921
2.54
2240
969
2.88
2529
1014
3000
872
2.22
1962
3100
930
2.65
2335
976
2.99
2620
1021
882
2.33
2058
3200
892
2.45
2162
939
2.76
2428
984
3.10
2710

3300
902
2.57
2266
948
2.88
2529
993
3.21
2799

3400
912
2.69
2369
958
3.01
2637
1002
3.34
2902

3500
921
2.82
2479
968
3.15
2751

3600
930
2.95
2587
978
3.29
2862

3700
940
3.07
2686

3750
945
3.14
2743

1.8
Bhp
2.50
2.55
2.64
2.72
2.77
2.82
2.91
3.01
3.12
3.22
3.34

Watts
2206
2249
2326
2394
2436
2479
2554
2637
2727
2807
2902

Rpm
895
911
935
972
986
999
1019
1034

2.0
Bhp
2.78
2.85
2.96
3.06
3.11
3.16
3.26
3.36

Watts
2445
2504
2595
2678
2718
2759
2839
2917

Airflow
(Cfm)
2250
2300
2400
2500
2550
2660
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750

Bhp
FIOP
Watts

Rpm
465
471
482
494
501
507
520
533
546
559
572
585
598
610
623
636
649
655

0.2
Bhp
0.43
0.45
0.50
0.54
0.57
0.59
0.65
0.71
0.77
0.83
0.90
0.96
1.03
1.10
1.17
1.25
1.33
1.37

Watts
473
487
524
554
577
592
638
684
731
779
835
883
940
998
1056
1123
1190
1224

Rpm
554
559
569
581
587
592
604
615
626
637
648
660
671
682
694
707
720
727

0.4
Bhp
0.64
0.66
0.71
0.76
0.79
0.82
0.89
0.95
1.02
1.09
1.17
1.24
1.32
1.41
1.50
1.60
1.71
1.77

LEGEND
Brake Horsepower Input to Fan
Factory-Installed Option
Input Watts to Motor

*Motor drive range: 590 to 840 rpm.


All other rpms require field-supplied drive.
NOTES:
1. Boldface Out of Drive Package or Motor range .

2. Maximum usable watts input is 2120 and maximum continuous bhp


is 2.90. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confi
dence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit war
ranty will not be affected.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
5. Interpolation is permissible. Do not extrapolate.

11

50LJS/TJS

50TJS008 (712/TONS) STANDARD (BELT DRIVE)*

Performance data (cont)


FAN PERFORMANCE HORIZONTAL DISCHARGE UNITS
50TJS009 (8 1/2 TONS) STANDARD MOTOR (BELT
Airflow
(Cfm)

50LJS/TJS

2550
2660
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
3800
3900
4000
4100
4200
4250

Rpm
501
507
520
533
546
559
572
585
598
610
623
636
649
655
661
674
687
699
712
719

0.2
Bhp
0.57
0.59
0.65
0.71
0.77
0.83
0.90
0.96
1.03
1.10
1.17
1.25
1.33
1.37
1.41
1.49
1.57
1.60
1.75
1.80

Watts
577
592
638
684
731
779
835
883
940
998
1056
1123
1190
1224
1258
1327
1396
1473
1552
1595

Rpm
587
592
604
615
626
637
648
660
671
682
694
707
720
727
733
746
759
772
785
792

0.4
Bhp
0.79
0.82
0.89
0.95
1.02
1.09
1.17
1.24
1.32
1.41
1.50
1.60
1.71
1.77
1.82
1.93
2.05
2.17
2.30
2.37

50TJS009 (8 1/2 TONS) STANDARD MOTOR (BELT


Airflow
(Cfm)
2550
2660
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
3800
3900
4000
4100
4200
4250
Bhp
FIOP
Watts

Rpm
836
839
846
855
863
872
882
892
902
912
921
930
940
945
949
959

1.2
Bhp
1.83
1.87
1.95
2.04
2.13
2.22
2.33
2.45
2.57
2.69
2.82
2.95
3.07
3.14
3.20
3.33

Watts
1621
1656
1726
1805
1884
1962
2058
2162
2266
2369
2479
2587
2686
2743
2781
2894

Rpm
887
891
898
906
913
921
930
939
948
958
968
978

1.4
Bhp
2.13
2.17
2.26
2.35
2.44
2.54
2.65
2.76
2.88
3.01
3.15
3.29

DRIVE)*

Rpm
722
727
737
747
756
765
775
785
795
806
817
828
840
846
852
863
874
885
897
903

0.8
Bhp
1.29
1.32
1.40
1.49
1.57
1.66
1.74
1.83
1.91
2.01
2.11
2.23
2.35
2.42
2.48
2.61
2.75
2.88
3.03
3.10

Watts
1156
1182
1250
1327
1396
1473
1543
1321
1691
1779
1866
1971
2076
2136
2188
2300
2420
2529
2653
2710

Rpm
780
784
793
802
813
823
832
841
851
860
870
880
890
896
901
912
923
935
947

1.0
Bhp
1.55
1.58
1.66
1.75
1.84
1.94
2.05
2.15
2.26
2.36
2.47
2.57
2.69
2.75
2.80
2.93
3.08
3.23
3.39

Watts
1378
1404
1473
1552
1630
1718
1814
1901
1997
2084
2180
2266
2369
2420
2462
2571
2694
2815
2940

DRIVE)* (cont)
External Static Pressure (in. wg)
1.6
Watts
Rpm
Bhp
Watts
Rpm
931
2.45
2162
964
1884
1919
936
2.49
2197
973
946
2.58
2275
987
1997
2076
954
2.67
2352
997
2154
961
2.77
2436
1006
2240
969
2.88
2529
1014
2335
976
2.99
2620
1021
2428
984
3.10
2710

2529
993
3.21
2799

2637
1002
3.34
2902

2751

2862

1.8
Bhp
2.77
2.82
2.91
3.01
3.12
3.22
3.34

Watts
2436
2479
2554
2637
2727
2807
2902

Rpm
986
999
1019
1034

2.0
Bhp
3.11
3.16
3.26
3.36

Watts
2718
2759
2839
2917

Watts
747
771
827
875
932
989
1056
1114
1182
1258
1335
1422
1517
1569
1613
1709
1814
1919
2032
2093

Rpm
659
663
672
683
693
704
715
727
739
750
761
772
783
789
795
806
817
828
840
846

LEGEND
Brake Horsepower Input to Fan
Factory-Installed Option
Input Watts to Motor

*Motor drive range: 685 to 935 rpm. All other rpms require fieldsupplied drive.
NOTES:
1. Boldface Out of Drive Package or Motor range .

0.6
Bhp
1.05
1.08
1.14
1.20
1.27
1.35
1.43
1.52
1.62
1.72
1.82
1.93
2.03
2.09
2.15
2.26
2.38
2.50
2.64
2.71

Watts
956
981
1031
1081
1140
1207
1275
1353
1439
1526
1613
1709
1796
1849
1901
1997
2102
2206
2326
2386

2. Maximum usable watts input is 2120 and maximum continuous bhp


is 2.90. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confi
dence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit war
ranty will not be affected.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
5. Interpolation is permissible. Do not extrapolate.

12

Performance data (cont)


FAN PERFORMANCE HORIZONTAL DISCHARGE UNITS
External Static Pressure (in. wg)
0.6
Watts
Rpm
Bhp
Watts
Rpm
677
631
0.87
810
690
723
638
0.92
851
699
763
646
0.98
899
708
810
655
1.05
956
717
859
664
1.11
1006
724
907
672
1.18
1064
731
956
680
1.24
1114
738
1014
688
1.31
1173
747
1072
698
1.39
1241
756
1140
708
1.47
1310
764
1207
717
1.56
1387
773
1284
727
1.65
1465
781
1361
737
1.74
1543
789
1447
747
1.83
1621
798
1534
757
1.92
1700
807
1630
767
2.02
1788
817
1726
777
2.13
1884
827
1831
787
2.24
1980
836
1945
797
2.36
2084
846
2058
808
2.48
2238
856
2230
818
2.61
2353
866

0.8
Bhp
1.03
1.10
1.16
1.23
1.30
1.36
1.43
1.51
1.60
1.69
1.78
1.86
1.95
2.05
2.16
2.27
2.38
2.50
2.62
2.73
2.86

Watts
940
998
1047
1106
1165
1216
1275
1344
1422
1499
1578
1648
1726
1814
1910
2006
2102
2256
2362
2460
2578

Rpm
747
755
761
767
775
784
794
802
810
816
823
832
841
849
858
866
874
882
891
900
910

1.0
Bhp
1.20
1.27
1.34
1.40
1.48
1.56
1.64
1.73
1.81
1.89
1.98
2.08
2.18
2.30
2.41
2.51
2.62
2.73
2.85
2.99
3.12

Watts
1081
1140
1199
1250
1318
1387
1456
1534
1604
1674
1753
1840
1927
2032
2177
2265
2362
2460
2569
2698
2819

50TJS012 (10 TONS)-STANDARD MOTOR (BELT DRIVE)* (cont)


External Static Pressure (in. wg)
Airflow
1.2
1.4
1.6
(Cfm)
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
3000
800
1.38
1233
850
1.52
1353
879
1.38
1233
925
3100
805
1.44
1284
857
1.63
1447
896
1.66
1473
935
3200
812
1.51
1344
862
1.71
1517
908
1.85
1639
944
3300
819
1.59
1413
867
1.78
1578
915
1.98
1753
952
3400
827
1.67
1482
873
1.85
1639
920
2.07
1831
963
3500
833
1.75
1552
880
1.94
1718
926
2.15
1901
970
3600
840
1.83
1621
888
2.04
1805
931
2.23
1971
976
3700
847
1.92
1700
895
2.13
1884
938
2.33
2108
981
3800
856
2.02
1788
901
2.23
1971
945
2.44
2203
986
3900
865
2.12
1875
908
2.32
2050
953
2.55
2300
993
4000
875
2.22
1962
915
2.42
2186
960
2.65
2389
1000
4100
1008
883
2.32
2050
924
2.54
2291
966
2.76
2487
4200
889
2.41
2177
934
2.65
2389
972
2.87
2587
1015
4300
980
2.99
2698
1021
896
2.51
2265
943
2.77
2406
4400
903
2.62
2362
951
2.89
2603
990
3.12
2819
1028
4500
958
3.00
2707
999
3.26
2982
1035
912
2.74
2469
4600
921
2.87
2587
965
3.11
2810
1008
3.39
3078
1041
4700
930
3.00
2707
972
3.23
2923
1017
3.45
3224
1048
4800
938
3.14
2838
980
3.37
3058
1025
3.55
3362
1055
4900
946
3.27
2962
990
3.51
3149
1034
3.71
3505
1062
5000
954
3.39
3078
998
3.62
3271
1042
3.85
3654
1068

1.8
Bhp
1.81
1.93
2.01
2.11
2.21
2.41
2.47
2.56
2.65
2.75
2.87
2.99
3.12
3.23
3.36
3.51
3.68
3.80
3.85
3.98
4.08

Watts
1604
1709
1836
1920
2005
2134
2230
2309
2389
2478
2587
2698
2819
2923
3049
3161
3295
3436
3584
3741
3907

Rpm
964
975
984
993
1001
1007
1017
1024
1029
1034
1039
1046
1053
1061
1068
1074
1081
1088
1095
1101
1108

2.0
Bhp
1.92
1.98
2.09
2.22
2.31
2.46
2.62
2.77
2.89
3.00
3.10
3.21
3.34
3.48
3.61
3.74
3.90
4.13
4.30
4.45
4.59

Watts
1761
1811
1903
2014
2091
2221
2362
2496
2605
2707
2800
2904
3029
3166
3241
3346
3450
3552
3653
3753
3851

Airflow
(Cfm)
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000

Bhp
FIOP
Watts

Rpm
484
495
505
516
527
537
548
560
571
582
593
605
616
628
639
651
662
674
686
698
710

0.2
Bhp
0.55
0.61
0.66
0.72
0.78
0.85
0.92
1.00
1.08
1.16
1.25
1.35
1.45
1.56
1.67
1.78
1.91
2.03
2.17
2.31
2.45

Watts
562
607
646
692
739
795
851
916
981
1047
1123
1207
1292
1387
1482
1578
1691
1796
1919
2041
2212

Rpm
560
570
579
589
599
609
619
629
639
649
659
670
680
690
701
712
722
733
744
755
766

0.4
Bhp
0.70
0.76
0.81
0.87
0.93
0.99
1.05
1.12
1.19
1.27
1.35
1.44
1.53
1.63
1.73
1.84
1.95
2.07
2.20
2.33
2.47

LEGEND
Brake Horsepower Input to Fan
Factory-Installed Option
Input Watts to Motor

*Standard motor drive range: 685 to 935 rpm.


All other rpms require field-supplied drive.
NOTES:
1. Boldface Out of Drive Package or Motor range .

2. Maximum usable watts input is 2120 with standard motor,


Extensive motor and electrical testing on these units ensures that
the full range ofthe motor can be utilized with confidence.
Using your fan motors up to the wattage ratings shown will not
result in nuisance tripping or premature motor failure.
Unit warranty will not be affected.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
5. Interpolation is permissible. Do not extrapolate.

13

50LJS/TJS

50TJS012 (10 TONS)-STANDARD MOTOR (BELT DRIVE)*

Performance data (cont)


FAN PERFORMANCE HORIZONTAL DISCHARGE UNITS
50TJS014 (121 /2 TONS)-STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg)
0.6
Watts
Rpm
Bhp
Watts
Rpm
1113
732
1.37
1267
782
1170
742
1.45
1332
795
1226
751
1.53
1398
808
1291
761
1.61
1464
819
1357
772
1.71
1548
830
1431
783
1.81
1632
839
1506
794
1.91
1717
848
1582
805
2.02
1811
857
1666
817
2.12
1897
867
1759
828
2.23
1992
877
1854
840
2.34
2088
888
1948
852
2.46
2193
899
2053
863
2.57
2290
910
2166
875
2.70
2405
921
2290
887
2.83
2521
932
2414
898
2.96
2638
943
2539
909
3.09
2755
955
2683
920
3.24
2891
967
2828
932
3.38
3019
978
2973
943
3.54
3166
990
3129
956
3.70
3313
1002
3294
968
3.87
3470
1013
3470
981
4.05
3637
1025
3646
995
4.23
3804
1037
3832
1008
4.42
3981
1042
4018
1022
4.62
4167
1058
4223
1036
4.83
4363
1070

0.8
Bhp
1.56
1.66
1.76
1.86
1.96
2.05
2.14
2.24
2.35
2.46
2.59
2.72
2.86
2.99
3.13
3.28
3.42
3.57
3.72
3.87
4.03
4.20
4.37
4.55
4.73
4.91
5.11

Watts
1423
1506
1590
1674
1759
1836
1914
2000
2096
2193
2307
2423
2548
2665
2792
2928
3056
3193
3331
3470
3618
3775
3934
4102
4270
4437
4624

Rpm
833
842
851
861
871
883
896
908
919
929
938
947
957
966
976
987
998
1009
1029
1031
1042
1053
1065
1076
1088

1.0
Bhp
1.73
1.82
1.92
2.02
2.13
2.25
2.38
2.51
2.63
2.75
2.87
2.98
3.11
3.24
3.38
3.53
3.69
3.86
4.03
4.20
4.38
4.56
4.74
4.92
5.10

Watts
1565
1641
1725
1811
1905
2009
2123
2237
2343
2450
2557
2656
2773
2891
3019
3157
3304
3461
3618
3775
3943
4111
4279
4447
4614

50TJS014 (121 /2 TONS)-STANDARD MOTOR (BELT DRIVE)* (cont)


External Static Pressure (in. wg)
Airflow
1.2
1.4
1.6
(Cfm)
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
3700
879
1.95
1751
927
2.17
1940
973
2.38
2123
1013
3800
889
2.03
1819
934
2.26
2018
980
2.48
2210
1022
3900
898
2.12
1897
942
2.36
2105
987
2.59
2307
1030
4000
908
2.21
1974
950
2.46
2193
994
2.70
2405
1037
4100
917
2.32
2070
960
2.55
2272
1001
2.81
2503
1045
4200
925
2.44
2175
969
2.65
2370
1009
2.92
2602
1051
4300
935
2.56
2281
979
2.77
2468
1018
3.03
2701
1058
4400
945
2.68
2387
988
2.89
2575
1028
3.14
2801
1066
4500
955
2.82
2512
996
3.02
2692
1037
3.25
2901
1074
4600
967
2.96
2638
1005
3.16
2819
1046
3.38
3019
1084
4700
980
3.11
2773
1015
3.30
2946
1056
3.52
3147
1093
4800
992
3.26
2910
1025
3.45
3083
1064
3.67
3285
1103
4900
1003
3.41
3047
1036
3.61
3230
1073
3.83
3433
1112
5000
1014
3.56
3184
1049
3.79
3396
1083
4.00
3590
1121
5100
1024
3.71
3322
1061
3.96
3553
1093
4.17
3748
1129
5200
1033
3.84
3442
1073
4.14
3720
1103
4.34
3906
1138
5300
1042
3.98
3572
1084
4.31
3878
1115
4.53
4157
1148
5400
1051
4.14
3720
1095
4.49
4046
1128
4.74
4279
1158
5500
1061
4.30
3818
1105
4.66
4204
1140
4.94
4465
1168
5600
1071
4.46
4018
1114
4.81
4344
1152
5.14
4652

5700
1081
4.64
4186
1123
4.98
4503

5800
1092
4.84
4372
1132
5.15
4661

5900
1103
5.04
4558

6000
1114
5.24
4745

6100

6200

6300

1.8
Bhp
2.57
2.69
2.81
2.92
3.04
3.17
3.29
3.41
3.54
3.66
3.79
3.92
4.07
4.23
4.40
4.58
4.76
4.95
5.15

Watts
2290
2396
2503
2602
2710
2828
2937
3047
3166
3276
3396
3516
3655
3804
3962
4130
4326
4475
4661

Rpm
1046
1058
1068
1077
1085
1092
1100
1106
1113
1121
1129
1137
1147
1157
1166
1175
1184
1193

2.0
Bhp
2.73
2.87
3.01
3.14
3.21
3.40
3.53
3.67
3.81
3.95
4.09
4.22
4.36
4.50
4.66
4.82
5.01
5.20

Watts
2432
2557
2683
2801
2919
3037
3157
3285
3414
3544
3674
3795
3925
4055
4202
4354
4531
4707

Airflow
(Cfm)

50LJS/TJS

3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300

Bhp

FIOP
Watts

Rpm
607
621
636
650
665
680
696
711
727
742
758
773
789
805
821
837
853
869
885
901
917
933
949
965
981
997
1014

0.2
Bhp
0.97
1.05
1.13
1.21
1.30
1.39
1.49
1.60
1.70
1.82
1.94
2.06
2.19
2.32
2.47
2.61
2.76
2.92
3.09
3.26
3.44
3.62
3.81
4.01
4.21
4.42
4.64

Watts
947
1010
1073
1137
1210
1283
1365
1456
1540
1641
1742
1845
1957
2070
2202
2325
2459
2602
2755
2910
3074
3239
3414
3600
3785
3981
4186

Rpm
670
681
693
705
717
728
739
750
762
774
786
799
812
826
840
854
868
882
897
911
926
941
956
972
987
1002
1018

0.4
Bhp
1.18
1.25
1.32
1.40
1.48
1.57
1.66
1.75
1.85
1.96
2.07
2.18
2.30
2.43
2.57
2.71
2.85
3.01
3.17
3.33
3.50
3.68
3.87
4.06
4.26
4.46
4.68

LEGEND
Brake Horsepower Input to Fan
Factory-Installed Option
Input Watts to Motor

*Standard motor drive range: 860 to 1080 rpm. Alternate motor drive range:
900 to 1260 rpm. All other rpms require field-supplied drive.
NOTES:
1. Boldface Out of Drive Package or Motor range .

2. Maximum usable watts input is 3313 with standard motor.


Maximum continuous bhp is 3.70 with standard motor.
Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence.
Using your fan motors up to the wattage ratings shown will not result
in nuisance tripping or premature motor failure. Unit warranty
will not be affected.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative for details.
5. Interpolation is permissible. Do not extrapolate.

14

Performance data
FAN PERFORMANCE VERTICAL DISCHARGE UNITS (Optional)

Airflow
(Cfm)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000

Rpm
852
894
936
978
1021
1064
1107
1150
1193
1237
1280
1324
1368

STANDARD MOTOR (BELT DRIVE)

0.1
Bhp
0.55
0.64
0.74
0.85
0.97
1.10
1.24
1.39
1.56
1.74
1.94
2.15
2.37

Watts
562
630
708
795
891
998
1114
1241
1387
1543
1718
1901
2093

Rpm
905
945
984
1024
1064
1104
1145
1186
1228
1269
1311
1354
1396

0.2
Bhp
0.62
0.72
0.82
0.93
1.05
1.18
1.32
1.48
1.65
1.83
2.03
2.24
2.46

External Static Pressure (in. wg)


0.4
Watts
Rpm
Bhp
Watts
Rpm
615
1002
0.78
739
1084
692
1037
0.88
818
1119
771
1072
0.98
899
1154
859
1108
1.10
998
1190
956
1145
1.22
1097
1225
1064
1183
1.36
1216
1260
1182
1222
1.52
1353
1296
1318
1262
1.68
1491
1331
1465
1301
1.86
1648
1367
1621
1341
2.05
1814
1404
1442
1796
1381
2.25
1989
1980
1420
2.47
2180
1481
2171
1460
2.69
2369
1521

Watts
859
948
1047
1156
1275
1396
1534
1674
1831
1997
2180
2369
2571

1.6
Bhp
1.90
2.03
2.16
2.31
2.46
2.64
2.84

Watts
1638
1796
1910
2041
2171
2326
2459

Rpm
1163
1194
1226
1259
1294
1330
1365
1400
1435
1471
1506
1542

0.8
Bhp
1.10
1.21
1.33
1.47
1.62
1.78
1.94
2.12
2.31
2.51
2.72
2.94

Watts
998
1089
1190
1310
1439
1578
1718
1875
2041
2214
2394
2579

50TJS007 (6 TONS)*
Airflow
(Cfm)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
Bhp

FIOP
Watts

Rpm
1235
1266
1297
1327
1359
1392
1426
1461
1497
1532

STANDARD MOTOR (BELT DRIVE) (cont)


External Static Pressure (in. wg)
1.0
1.2
1.4
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
1.29
1156
1303
1.48
1318
1371
1.69
1.40
1250
1330
1.59
1413
1396
1.81
1.53
1361
1362
1.73
1534
1422
1.94
1.66
1473
1393
1.87
1656
1452
2.08
1483
2.24
1.81
1604
1423
2.02
1779
1515
2.41
1.97
1744
1454
2.18
1927
1485
2.36
2084
2.15
1901
1544
2.59
2.34
2067
1518
2.55
2249
1575
2.78
2.54
2240
1552
2.76
2428

2.75
2420

0.6
Bhp
0.93
1.04
1.16
1.29
1.43
1.57
1.73
1.89
2.07
2.26
2.47
2.69
2.93

50LJS/TJS

50LJS007 (6 TONS)*

LEGEND
Brake Horsepower Input to Fan
Factory-Installed Option
Input Watts to Motor

*Motor drive range: 1070 to 1460 rpm. All other rpms require fieldsupplied drive.
NOTES:
1. Boldface Out of Drive Package or Motor range .

Watts
1499
1604
1718
1840
1980
2128
2283
2445

Rpm
1433
1460
1485
1510
1538
1569
1601

2. Maximum usable watts input is 2120 and maximum continuous


bhp is 2.40. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confi
dence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit war
ranty will not be affected.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
5. Interpolation is permissible. Do not extrapolate.

15

Performance data (cont)


FAN PERFORMANCE VERTICAL DISCHARGE UNITS (Optional)
50TJS008 (712/TONS)* STANDARD MOTOR (BELT DRIVE)
Airflow
(Cfm)

50LJS/TJS

2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750

Rpm
511
518
534
549
557
565
581
597
613
629
646
662
679
696
712
729
746
755

0.2
Bhp
0.52
0.55
0.61
0.67
0.71
0.74
0.81
0.89
0.97
1.06
1.15
1.25
1.35
1.46
1.57
1.69
1.85
1.89

Watts Rpm
539 592
562 599
607 613
653 627
684 633
708 639
763 652
827 665
891 679
965 694
1039 709
1123 724
1207 740
1301 756
1396 771
1499 787
1613 803
1674 811

0.4
Bhp
0.74
0.77
0.84
0.90
0.94
0.97
1.04
1.12
1.20
1.29
1.39
1.50
1.61
1.73
1.85
1.98
2.12
2.20

External Static Pressure (in. wg)


0.6
0.8
Watts Rpm Bhp Watts Rpm Bhp Watts Rpm
708 659 0.95
875 722 1.19 1072 778
731 665 0.98
899 727 1.22 1097 783
787 677 1.06
965 738 1.30 1165 794
835 690 1.14 1031 750 1.38 1233 805
867 697 1.18 1064 756 1.42 1267 811
891 703 1.22 1097 761 1.46 1301 816
948 717 1.31 1173 773 1.55 1378 827
1014 733 1.40 1250 786 1.66 1473 839
1081 745 1.50 1335 799 1.76 1560 850
1156 759 1.59 1413 812 1.88 1665 862
1241 772 1.70 1508 825 1.99 1761 875
1335 785 1.80 1595 840 2.11 1866 887
1430 798 1.91 1691 854 2.24 1980 900
1534 811 2.02 1788 868 2.37 2093 914
1639 824 2.14 1892 881 2.50 2206 928
1753 839 2.21 2006 894 2.64 2326 942
1875 854 2.42 2136 907 2.78 2445 956
1945 862 2.49 2197 914 2.85 2504 963

50TJS008 (712/TONS)* STANDARD MOTOR(BELT DRIVE) (cont)


External Static Pressure (in. wg)
Airflow
1.4
1.6
1.8
(Cfm)
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
2250
937 2.33
2058
884 1.97
1744
947 2.66
2343
2300
939 2.36
2084
885 2.00
1770
979 2.69
2369
2400
944 2.40
2119
892 2.08
1840
987 2.76
2428
2500
902 2.18
1927
949 2.48
2188 1002 2.84
2495
2550
908 2.24
1980
953 2.53
2232 1003 2.87
2521
2600
913 2.29
2023
957 2.58
2275 1004 2.91
2554
2700
924 2.40
2120
967 2.70
2377 1010 3.01
2637
2800
935 2.52
2223
978 2.62
2479 1019 3.13
2735
2900
946 2.65
2335
989 2.96
2595 1030 3.27 2847
3000
957 2.78
2445 1000 3.09
2702 1040 3.41
2956
3100
968 2.91
2554 1011 3.24
2832

2933

3200
980 3.04
2661 1022 3.38
3300
991 3.18
2775

3400
1003 3.32
2886

3500
3009

1014 3.48
3600

3700

3750

Bhp

FIOP
Watts

LEGEND
Brake Horsepower Input to Fan
Factory-Installed Option
Input Watts to Motor

*Standard motor drive range: 590 to 840 rpm.


All other rpms require field-supplied drive.
NOTES:
1. Boldface Out of Drive Package or Motor range .

16

Rpm
1022
1025
1039
1041
1045
1050
1056
1061

2.0
Bhp
3.10
3.12
3.20
3.25
3.28
3.31
3.37
3.47

1.0
Bhp
1.43
1.47
1.55
1.64
1.69
1.74
1.83
1.93
2.04
2.15
2.28
2.41
2.54
2.69
2.84
2.99
3.15
3.23

Watts Rpm
1275 829
1310 834
1378 844
1456 855
1499 861
1543 866
1621 878
1709 889
1805 900
1901 911
2015 923
2128 934
2240 946
2369 959
2495 971
2620 984
2751 997
2815

1.2
Bhp
1.68
1.72
1.81
1.91
1.96
2.01
2.12
2.23
2.34
2.46
2.58
2.71
2.85
3.00
3.16
3.22
3.49

Watts
1491
1526
1604
1691
1735
1779
1875
1971
2067
2171
2275
2386
2504
2629
2759
2886
3017

Watts
2710
2727
2791
2831
2854
2878
2925
3002

2. Maximum usable watts input is 2120 and maximum continuous


bhp is 2.90. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit war
ranty will not be affected.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
5. Interpolation is permissible. Do not extrapolate.

Performance data (cont)


FAN PERFORMANCE VERTICAL DISCHARGE UNITS (Optional)

50TJS009 (8 1/2 TONS)* STANDARD MOTOR (BELT DRIVE) (cont)


External Static Pressure (in. wg)
Airflow
1.4
1.6
1.8
(Cfm)
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
2550
908 2.24 1980
953 2.53 2232 1003 2.87 2521
2600
913 2.29 2023
957 2.58 2275 1004 2.91 2554
2700
924 2.40 2120
967 2.70 2377 1010 3.01 2637
2800
935 2.52 2223
978 2.62 2479 1019 3.13 2735
2900
946 2.65 2335
989 2.96 2595 1030 3.27 2847
3000
957 2.78 2445 1000 3.09 2702 1040 3.41 2956
3100
968 2.91 2554 1011 3.24 2832

3200
980 3.04 2661 1022 3.38 2933

3300
991 3.18 2775

3400
1003 3.52 2886

3500

1014 3.48 3009


3600

3700

3750

3800

3900

4000

4100

4200

4250

Bhp

FIOP
Watts

LEGEND
Brake Horsepower Input to Fan
Factory-Installed Option
Input Watts to Motor

*Motor drive range: 685 to 935 rpm. All other rpms require fieldsupplied drive.
NOTES:
1. Boldface Out of Drive Package or Motor range .

Rpm
1045
1050
1056
1061

2.0
Bhp
3.28
3.31
3.37
3.41

1.0
Bhp
1.69
1.74
1.83
1.93
2.04
2.15
2.28
2.41
2.54
2.69
2.84
2.99
3.15
3.23
3.31
3.48

Watts
1499
1543
1621
1709
1805
1901
2015
2128
2240
2369
2495
2620
2751
2815
2878
3009

Rpm
861
866
878
889
900
911
923
934
946
959
971
984
997

1.2
Bhp
1.96
2.01
2.12
2.23
2.34
2.46
2.58
2.71
2.85
3.00
3.16
3.32
3.49

Watts
1735
1779
1875
1971
2067
2171
2275
2386
2504
2629
2759
2886
3017

50LJS/TJS

50TJS009 (8 1/2 TONS)* STANDARD MOTOR (BELT DRIVE)


External Static Pressure (in. wg)
Airflow
0.2
0.4
0.6
0.8
(Cfm)
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm
2550
557
0.71
684
633
0.94
867
697
1.18 1064
756
1.42 1267
811
2600
565
0.74
708
639
0.97
891
703
1.22 1097
761
1.46 1301
816
2700
581
0.81
763
652
1.04
948
717
1.31 1173
773
1.55 1378
827
2800
597
0.89
827
665
1.12 1014
733
1.40 1250
786
1.66 1473
839
2900
613
0.97
891
679
1.20 1081
745
1.50 1335
799
1.76 1560
850
3000
629
1.06
965
694
1.29 1156
759
1.59 1413
812
1.88 1665
862
3100
646
1.15 1039
709
1.39 1241
772
1.70 1508
825
1.99 1761
875
3200
662
1.25 1123
724
1.50 1335
785
1.80 1595
840
2.11 1866
887
3300
679
1.35 1207
900
740
1.61 1430
798
1.91 1691
854
2.24 1980
3400
696
1.46 1301
756
1.73 1534
811
2.02 1788
868
2.37 2093 914
3500
881
2.50 2206
928
712
1.57 1396
771
1.85 1639
824
2.14 1892
3600
729
1.69 1499
787
1.98 1753
839
2.27 2006
894
2.64 2326
942
3700
854
2.42 2136
907
2.78 2445
956
746
1.82 1613
803
2.12 1875
3750
755
1.89 1674
811
2.20 1945
862
2.49 2197
914
2.85 2504
963
3800
763
1.95 1726
819
2.27 2006
869
2.56 2257
920
2.92 2562
970
3900
780
2.09 1849
835
2.42 2136
884
2.72 2394
933
3.07 2686
983
4000
796
2.23 1971
851
2.56 2257
900
2.89 2537
946
3.23 2815

4100
813
2.39 2110
867
2.74 2411
915
3.06 2678
960
3.40 2948

4200
830
2.55 2249
883
2.91 2554
931
3.24 2823

4250
839
2.63 2317
892
3.00 2629
939
3.34 2902

Watts
2854
2878
2925
3002

2. Maximum usable watts input is 2120 and maximum continuous


bhp is 2.90. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confi
dence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit war
ranty will not be affected.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative to verify.
5. Interpolation is permissible. Do not extrapolate.

17

Performance data (cont)


FAN PERFORMANCE VERTICAL DISCHARGE UNITS (Optional)
50TJS012 (10 TONS)-STANDARD MOTOR (BELT DRIVE)*

50LJS/TJS

Airflow
(Cfm
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000

Rpm
532
544
557
570
583
596
609
622
635
649
662
675
689
702
715
729
742
756
770
783
797

0.2
Bhp
0.64
0.70
0.75
0.81
0.88
0.94
1.01
1.09
1.16
1.25
1.33
1.42
1.52
1.61
1.72
1.83
1.94
2.06
2.18
2.31
2.44

Watts
630
677
716
763
818
867
924
989
1047
1123
1190
1267
1353
1430
1526
1621
1718
1823
1927
2041
2203

Rpm
605
616
628
639
651
663
674
686
698
713
722
734
746
759
772
785
797
810
823
836
849

0.4
Bhp
0.81
0.86
0.93
0.99
1.06
1.14
1.22
1.30
1.39
1.48
1.57
1.67
1.77
1.88
1.99
2.10
2.22
2.34
2.46
2.60
2.73

Watts
763
803
859
907
965
1031
1097
1165
1241
1318
1396
1482
1569
1665
1761
1858
1962
2067
2221
2344
2460

External Static Pressure (in. wg)


0.6
0.8
Rpm Bhp Watts Rpm Bhp Watts
670
0.97
891
725
1.12 1014
680
1.03
940
735
1.20 1081
690
1.10
998
746
1.28 1148
700
1.18 1064
757
1.36 1216
711
1.25 1123
767
1.44 1284
721
1.33 1190
777
1.52 1353
732
1.42 1267
787
1.61 1430
744
1.50 1335
797
1.70 1508
755
1.59 1413
808
1.80 1595
767
1.68 1491
818
1.90 1683
778
1.78 1578
829
2.01 1779
790
1.89 1674
839
2.12 1875
801
1.99 1761
851
2.23 1971
813
2.11 1866
862
2.34 2067
825
2.22 1962
873
2.46 2221
837
2.35 2076
885
2.59 2335
848
2.48 2238
896
2.72 2451
860
2.61 2353
908
2.86 2578
919
3.00 2707
872
2.75 2505
931
3.14 2838
884
2.89 2605
897
3.04 2661
943
3.30 2870

50TJS012 (10 TONS)-STANDARD MOTOR (BELT DRIVE)* (cont)


External Static Pressure (in. wg)
Airflow
1.4
1.6
1.8
(Cfm)
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
3000
874 1.60 1422
926 1.82 1613
974 2.11 1920
3100
880 1.68 1491
933 1.87 1656
983 2.16 1963
3200
888 1.77 1569
934 1.94 1718
988 2.18 1980
3300
897 1.86 1648
940 2.03 1853
989 2.24 2031
3400
907 1.97 1744
947 2.14 1946
991 2.32 2099
3500
916 2.07 1831
956 2.25 2039
997 2.43 2195
3600
926 2.18 1927
966 2.41 2134 1004 2.54 2291
3700
934 2.28 2015
976 2.48 2238 1013 2.66 2397
3800
943 2.41 2160
985 2.60 2334 1023 2.79 2514
3900
952 2.51 2265
994 2.72 2451 1032 2.92 2633
4000
962 2.63 2371 1003 2.84 2560 1042 3.06 2763
4100
973 2.77 2496 1011 2.97 2679 1051 3.20 2895
4200
983 2.91 2624 1021 3.11 2810 1060 3.34 3029
4300
994 3.05 2754 1031 3.25 2943 1068 3.48 3166
4400
1004 3.19 2885 1042 3.41 3097 1080 3.63 3388
4500
1015 3.33 2020 1051 3.45 3218 1090 3.75 3493
4600
1025 3.48 3166 1060 3.61 3369 1100 3.92 3655
4700
1037 3.58 3335 1070 3.84 3325 1111 4.10 3822
4800
1048 3.75 3494 1080 3.95 3686 1121 4.28 3995
4900
1060 3.92 3659 1089 4.13 3854 1132 4.48 4174
5000
1072 4.11 3830 1099 4.32 4027 1144 4.67 4359
LEGEND

*Standard motor drive range: 685 to 935 rpm.


All other rpms require field-supplied drive.
NOTES:
1. Boldface Out of Motor and Drive Package range.
2. Maximum usable watts input is 2120 with standard motor,

Maximum continuous bhp is 2.90 with standard motor.

18

Rpm
1012
1017
1025
1032
1038
1043
1045
1051
1059
1068
1078
1087
1090
1097
1105
1112
1119
1126
1133
1140

2.0
Bhp
2.41
2.44
2.47
2.53
2.57
2.64
2.74
2.85
2.98
3.12
3.26
3.41
3.51
3.70
3.91
4.12
4.35
4.59
4.85
5.12

Rpm
778
787
796
805
815
826
836
847
857
867
878
888
898
908
919
929
940
951
963
974
984

1.0
Bhp
1.28
1.36
1.44
1.52
1.61
1.71
1.80
1.91
2.01
2.11
2.22
2.33
2.45
2.58
2.71
2.85
2.98
3.12
3.27
3.41
3.44

Watts
1148
1216
1284
1353
1430
1517
1595
1691
1779
1866
1962
2058
2212
2326
2442
2569
2688
2727
2847
2956
3211

Rpm
825
835
844
854
863
871
880
890
901
912
922
933
943
953
963
973
984
994
1003
1013
1023

1.2
Bhp
1.43
1.52
1.61
1.70
1.79
1.88
1.98
2.09
2.20
2.32
2.44
2.56
2.69
2.81
2.94
3.08
3.22
3.38
3.43
3.59
3.75

Watts
1275
1353
1430
1508
1587
1665
1753
1849
1945
2050
2203
2309
2424
2533
2651
2782
2914
3068
3202
3349
3501

Watts
2134
2177
2230
2282
2318
2380
2478
2569
2688
2819
2952
3097
3276
3453
3642
3843
4057
4284
4523
4775

electrical testing on these units ensures that the full range of the
motor can be utilized with confidence. Using your fan motors up to
the wattage ratings shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected.
3. Values include losses for filters, unit casings, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
5. Interpolation is permissible. Do not extrapolate.

Performance data (cont)


FAN PERFORMANCE VERTICAL DISCHARGE UNITS (Optional)

Airflow
(Cfm)
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300

Rpm
654
668
683
697
711
726
741
755
770
784
799
814
829
843
858
873
888
903
918
933
948
963
978
993
1008
1023
1038

0.2
Bhp
1.12
1.20
1.28
1.37
1.46
1.56
1.66
1.77
1.89
2.00
2.13
2.25
2.39
2.52
2.67
2.82
2.97
3.13
3.30
3.47
3.65
3.83
4.00
4.22
4.42
4.63
4.85

Watts
1065
1129
1194
1267
1340
1423
1506
1598
1700
1794
1905
2009
2131
2246
2378
2512
2647
2792
2946
3101
3267
3433
3590
3795
3981
4176
4382

Rpm
714
727
741
754
767
780
794
808
821
835
849
863
877
892
906
920
934
949
963
978
992
1006
1021
1035
1050
1065
1079

0.4
Bhp
1.31
1.40
1.49
1.59
1.69
1.80
1.91
2.03
2.15
2.27
2.40
2.53
2.67
2.81
2.95
3.10
3.26
3.43
3.59
3.77
3.95
4.14
4.34
4.54
4.75
4.96
5.19

Watts
1218
1291
1365
1448
1531
1624
1717
1819
1923
2027
2140
2254
2378
2503
2629
2764
2910
3065
3212
3377
3544
3720
3906
4093
4288
4484
4698

External Static Pressure (in. wg)


0.6
0.8
Rpm Bhp Watts Rpm Bhp Watts
767 1.50 1373
815 1.67 1514
780 1.60 1456
827 1.77 1598
793 1.70 1540
839 1.88 1691
806 1.80 1624
851 1.99 1785
819 1.90 1708
864 2.10 1879
832 2.01 1802
877 2.22 1983
845 2.12 1897
889 2.35 2096
858 2.24 2000
902 2.48 2210
871 2.37 2114
915 2.61 2325
884 2.49 2219
928 2.75 2450
897 2.63 2343
941 2.88 2566
910 2.77 2468
954 3.02 2692
923 2.92 2602
967 3.17 2828
937 3.08 2746
980 3.32 2964
950 3.24 2891
993 3.48 3111
963 3.40 3037 1006 3.65 3267
977 3.57 3193 1019 3.82 3424
991 3.75 3359 1032 4.00 3590
1004 3.92 3516 1045 4.18 3757
1018 4.11 3692 1058 4.38 3943
1032 4.30 3869 1072 4.58 4130
1046 4.50 4055 1085 4.79 4326
1060 4.69 4232 1098 5.01 4531
1074 4.91 4419 1112 5.23 4735
1089 5.10 4616

50TJS014 (12 TONS)-STANDARD MOTOR (BELT DRIVE)* (cont)


External Static Pressure (in. wg)
Airflow
1.4
1.6
1.8
(Cfm)
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
3700
950 2.27 2027
991 2.47 2202 1030 2.65 2361
3800
959 2.38 2123 1001 2.58 2299 1040 2.78 2476
3900
969 2.50 2228 1010 2.70 2405 1049 2.91 2593
4000
979 2.62 2334 1020 2.83 2521 1059 3.04 2710
4100
989 2.74 2441 1029 2.96 2638 1068 3.18 2837
4200
1000 2.86 2548 1039 3.10 2764 1077 3.31 2955
4300
1011 2.97 2647 1049 3.23 2882 1087 3.46 3092
4400
1022 3.10 2764 1059 3.37 3010 1097 3.61 3230
4500
1033 3.23 2882 1070 3.51 3138 1107 3.76 3368
4600
1044 3.37 3010 1081 3.64 3258 1117 3.92 3516
4700
1056 3.52 3147 1092 3.78 3387 1127 4.07 3655
4800
1057 3.69 3304 1103 3.93 3525 1138 4.23 3804
4900
1079 3.87 3470 1114 4.09 3674 1149 4.37 3934
5000
1091 4.05 3637 1126 4.25 3822 1160 4.53 4083
5100
1103 4.23 3804 1137 4.45 4009 1171 4.70 4242
5200
1115 4.42 3981 1149 4.65 4195 1182 4.91 4409
5300
1127 4.62 4167 1161 4.85 4382 1194 5.07 4586
5400
1139 4.82 4354 1173 5.06 4577

5500
1152 5.03 4549

5600
1165 5.24 4746

5700

5800

5900

6000

6100

6200

6300

Bhp

FIOP
Watts

LEGEND
Brake Horsepower Input to Fan
Factory-Installed Option
Input Watts to Motor

*Standard motor drive range: 860 to 1080 rpm.


All other rpms require field-supplied drive.
NOTES:
1. Boldface Out of Motor and Drive Package range.
2. Maximum usable watts input is 3313 with standard motor.

Maximum continuous bhp is 3.70 with standard motor.

Extensive motor and electrical testing on these units

ensures that the full range of

Rpm
1064
1075
1085
1095
1105
1114
1124
1133
1143
1152
1162
1172
1182
1193
1204
1215

2.0
Bhp
2.82
2.96
3.11
3.25
3.39
3.54
3.69
3.84
4.00
4.17
4.33
4.50
4.68
4.85
5.01
5.18

Rpm
861
873
884
895
907
919
931
943
955
968
981
993
1006
1019
1032
1045
1058
1071
1084
1097
1110
1123

1.0
Bhp
1.85
1.95
2.05
2.16
2.28
2.41
2.54
2.68
2.82
2.96
3.11
3.27
3.43
3.60
3.76
3.93
4.11
4.29
4.47
4.66
4.86
5.07

Watts
1666
1751
1836
1931
2035
2149
2263
2387
2512
2638
2773
2919
3065
3221
3368
3525
3692
3860
4027
4204
4391
4586

Rpm
906
916
927
938
949
960
971
983
995
1006
1018
1030
1043
1055
1068
1081
1094
1106
1119
1132
1145

1.2
Bhp
2.08
2.18
2.28
2.38
2.49
2.60
2.72
2.86
3.01
3.17
3.32
3.48
3.65
3.82
4.00
4.19
4.38
4.57
4.77
4.97
5.18

Watts
1862
1948
2035
2123
2219
2316
2433
2548
2683
2828
2964
3111
3267
3424
3590
3767
3943
4120
4307
4493
4689

Watts
2512
2638
2773
2901
3028
3166
3304
3442
3590
3748
3897
4055
4223
4382
4531
4689

the motor can be utilized with confidence. Using your fan motors
up to the wattage ratings shown will not result in nuisance tripping
or premature motor failure. Unit warranty will not be affected. For
additional information on motor performance.
3. Values include losses for filters, unit casings, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
5. Interpolation is permissible. Do not extrapolate.

19

50LJS/TJS

50TJS014 (12 TONS)-STANDARD MOTOR (BELT DRIVE)*

Performance data (cont)

FAN RPM AT MOTOR PULLEY SETTINGS* 60 Hz


MOTOR PULLEY TURNS OPEN

50LJS/TJS

UNIT

1/2

1 1/2

2 1/2

3 1/2

4 1/2

50LJS007

1300

1262

1224

1186

1148

1110

1072

1034

996

958

920

50TJS008

820

798

776

755

733

711

690

668

647

625

604

50TJS009

935

910

885

860

835

810

785

760

735

710

685

50TJS012

935

910

885

860

835

810

785

760

735

710

685

50TJS014

1080

1060

1035

1015

990

970

950

925

905

880

860

OUTDOORS SOUND POWER


UNIT

SOUND
RATING
(Bels)

OCTAVE BANDS
63

125

250

500

1000

2000

4000

8000

78.5

84

77.5

73

70.5

72

65

58.5

82.8

83

77.7

71.8

67

84.8

83.9

77.5

71.3

65.8

83

77.7

71.8

67

50LJS007

8.2

50TJS008,009

8.6

83.2

87.4

83.5

50TJS012

8.8

97.6

90.4

85.7

50TJS014

8.8

83.7

87.2

83.4

82.8

DURABLADE ECONOMIZER BAROMETRIC RELIEF


DAMPER CHARACTERISTICS

20

Electrical Data 50LJS007, 50TJS008 014 ( 60 Hz )

208/230-3
60

VOLTAGE COMPRESSOR
OFM (ea)
IFM
ELECTRIC HEAT*
RANGE
(ea)
MIN MAX RLA
LRA Qty Hp FLA FLA NOMINAL KW**
FLA

187

254

20

146

1/3

1.9

460-3-60

414

508

8.4

73

--

1.8

208/230-3
60

187

254

11.7

78

1/4

1.4

7.5

460-3-60

414

508

6.6

53

1/2

1.8

3.4

208/230-3
60

187

254

13.7

106

1/4

1.4

7.5

460-3-60

414

508

7.5

62

1/2

1.8

3.4

208/230-3
60

187

254

15

114

1/4

1.4

7.5

460-3-60

414

508

8.8

79

1/2

1.8

3.4

208/230-3
60

187

254

20

146

1/4

1.4

10.6

414

508

8.4

73

1/2

1.8

4.8

50LJS
007

STD

50TJS
008

STD

50TJS
009

STD

50TJS
012

STD

50TJS
014

STD

460-3-60

4.9/6.5
7.6/10.5
12.0/16.0
15.8/21.0
19.9/26.5
6
11.5
14
23
25.5
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.9/39.0
12.8
15.2
25.6
30.4
38.4
7.8/9.6
12.0/14.7
18.6/22.8
24.0/29.4
31.9/39.0
12.8
15.2
25.6
30.4
38.4
7.8/9.6
12.0/14.7
24.0/29.4
31.9/39.0
37.5/46.0
15.2
25.6
30.4
38.4
46
7.8/9.6
12.0/14.7
24.0/29.4
31.9/39.0
37.5/46.0
15.2
25.6
30.4
38.4
46

13.8/15.7
22.2/25.3
33.6/38.4
44.4/50.4
55.8/63.7
7
13.8
16.8
27.8
30.7
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
16.7
19.8
33.4
39.7
50.2
21.7/25.0
33.4/38.5
51.7/59.7
66.7/77.0
88.4/102.0
16.7
19.8
33.4
39.7
50.2
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
19.8
33.4
39.7
50.2
60.1
21.7/25.0
33.4/38.5
66.7/77.0
88.4/102.0
104.2/120.3
19.8
33.4
39.7
50.2
60.1

POWER SUPPLY
MCA

MOCP

34.7/34.7
34.7/34.7
34.7/38
48.1/54.4
61.6/69.4
75.9/86
15.8
15.8
19.5
23.3
36.9
40.6
40.1/40.1
40.1/40.1
48.9/55.4
71.9/81.8
90.6/103.5
117.7/134.8
18.4
26.9
28.1
45
52.9
65.9
44.6/44.6
44.6/44.6
48.9/55.4
71.9/81.8
90.6/103.5
117.7/134.8
22.7
24.1
28.1
45
52.9
65.9
44.6/44.6
44.6/44.6
48.9/55.4
90.6/103.5
117.7/134.8
137.5/157.6
21.8
28.1
45
52.9
65.9
63.4
65.2/65.2
65.2/65.2
65.2/65.2
96.6/109.5
123.7/140.8
143.5/163.6
29.6
30.8
47.8
55.6
68.7
66.1

42/42
42/42
42/42
50/60
70/80
80/90
20
20
20
25
40
45
45/45
45/45
50/60
80/90
100/1110
125/150
20
30
30
50
60
70
50/50
50/50
50/60
80/90
100/110
125/150
25
25
30
50
60
70
50/50
50/50
60/60
100/110
125/150
150/175
25
30
50
60
70
70
80/80
80/80
70/70
100/110
125/150
150/175
40
40
50
60
70
80

DISCONNECT
SIZE
FLA
LRA
32/32
32/32
32/34
43/49
56/63
69/78
15
15
18
21
34
37
42/42
42/42
45/51
66/75
83/95
108/124
19
25
26
41
49
61
47/47
47/47
47/51
66/75
83/95
108/124
24
24
26
41
49
61
47/47
47/47
47/51
83/95
108/124
127/147
24
26
41
49
61
72
68/68
68/68
68/68
89/101
114/129
132/151
31
31
44
51
63
75

173/173

50LJS/TJS

UNIT NOMINAL IFM


MODEL V-Ph-Hz TYPE

92

260/260

153

351/351

176

337/337

167

383/383

192

21

Electrical Data 50LJS007, 50TJS008 014 ( 60 Hz Cont.)

UNIT NOMINAL IFM


MODEL V-Ph-Hz TYPE

50LJS/TJS

50LJS
007
50TJS
008
50TJS
009
50TJS
012
50TJS
014

VOLTAGE COMPRESSOR
OFM (ea)
IFM
ELECTRIC HEAT*
RANGE
(ea)
MIN MAX RLA
LRA Qty Hp FLA FLA NOMINAL KW** FLA

POWER SUPPLY

DISCONNECT
SIZE
FLA
LRA

MCA

MOCP

380-3-60

STD

342

418

10.7

70

1/3

0.8

2.5

17.1

22

18.5

100

380-3-60

STD

342

418

5.8

54

1/4

0.8

4.3

19.01

26

20

145

380-3-60

STD

342

418

8.2

42

1/4

0.8

4.3

24.38

27.01

25

127

380-3-60

STD

342

418

10.4

55

1/4

0.8

4.3

29.3

32.5

26

155

380-3-60

STD

342

418

10.7

70

1/4

0.8

6.1

32

36

30

193

LEGEND AND NOTES FOR ELECTRICAL DATA TABLES


FLA
HACR
IFM
LRA
MCA
MOCP
NEC
OFM
RLA

LEGEND
Full Load Amps
Heating, Air Conditioning and Refrigeration
Indoor (Evaporator) Fan Motor
Locked Rotor Amps
Minimum Circuit Amps
Maximum Overcurrent Protection
National Electrical Code
Outdoor (Condenser) Fan Motor
Rated Load Amps

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v,


480 v, and 600 v. Heaters are rated at 240 v, 480 v, or 600 v. If power
distribution voltage to unit varies from rated heater voltage, heater kW
will vary accordingly. To determine heater capacity at actual unit volt
age, multiply 240 v, 480 v, or 600 v capacity by multipliers found in
table on page 51.
Used to determine minimum disconnect size per NEC.

**Heaters are field installed only.

Fuse or HACR circuit breaker.


||Fusing in single point box provides the required branch circuit
protection.
NOTES:
1. In compliance with NEC requirements for multimotor and combina
tion load equipment (refer to NEC Articles 430 and 440), the overcur
rent protective device for the unit shall be fuse or HACR breaker. The
Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent
of voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage

22

Example: Supply voltage is 460-3-60.


AB = 452 v

BC = 464 v

AC = 455 v

Average Voltage =
=

452 + 464 + 455


3
1371
3

= 457
Determine maximum deviation from average voltage.
(AB) 457 452 = 5 v
(BC) 464 457 = 7 v
(AC) 457 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.

Typical piping and wiring 50LJS007


(50TJS 008-014 shown)

50LJS/TJS

VERTICAL DISCHARGE DUCTING

HORIZONTAL DISCHARGE DUCTING

LEGEND
NEC National Electrical Code

23

50LJS/TJS

Typical wiring schematic 50LJS007

24

50LJS/TJS

Typical wiring schematic 50LJS007

25

50LJS/TJS

Typical
wiring schematic 50TJS008-014

26

50LJS/TJS

Typical wiring schematic 50TJS008-014 (Cont.)

27

50LJS/TJS

Typical wiring schematic 50TJS008-014 (Cont.)

28

Operating sequence
Cooling, units without economizer
When thermostat calls for cooling, terminal
G and Y1 are energized.
The indoor
(evaporator) fan contactor (IFC), and
compressor contactor no 1 (C1) are
energized and evaporator-fan motor,
compressor no. 1 (50TJS008-014), and
condenser fans start. The condenser-fan
motor runs continuously while unit is cooling.
On 50TJS008 014 units, if the thermostat
calls for a secondary stage of cooling by
energizing Y2, compressor contactor no.2
(C2) is energized and compressor no. 2
starts.

Heating, units without economizer


(If Accessory or Optional Heater is
Installed) Upon a call for heating through terminal W1,
IFC and heater contactor no. 1 (HC1) are
energized. On units equipped for 2 stages of
heat, when additional heat is needed, HC2
is energized through W2.

Cooling, units with economizer


(50TJS008 014)
When the outdoor-air temperature is above
the outdoor-air thermostat (OAT) setting and
the room thermostat calls for cooling,
compressor contactor no.1 is energized to
start compressor no. 1and the condenserfan motor. The evaporator-fan motor is
energized and the economizer damper
moves to the minimum position. Upon a
further call for cooling, compressor contactor
no. 2 will be energized (50TJS008 014),
starting compressor no. 2. After the
thermostat is satisfied, the damper moves to
the fully closed position.
When the outdoor-air temperature is below
the OAT setting and the thermostats call for
cooling, the economizer damper moves to

the minimum position. If the supply air


temperature is above 57 F, the damper
continues to open until it reaches the fully
open position or until the supply-air
temperature drops below 57 F.
When the supply-air temperature falls to
between 57 F and 52 F, the damper will
remain at an intermediate open position. If
the supply air temperature falls below 52
F, the damper will modulate closed until it
reaches the minimum position or until the
supply-air temperature is above 52 F. when
the thermostat is satisfied, the damper will
move to the fully closed position.
If the outdoor air alone can not satisfy the
cooling requirements of the conditioned
space, economizer cooling is integrated with
mechanical cooling, providing second-stage
cooling. Compressor no. 1 and the
condenser fan will be energized and the
position of the economizer damper will be
determined by the supply-air temperature.
Compressor no. 2 (50TJS008 014) is
locked out.
When the second stage of cooling is
satisfied, the compressor and condenser-fan
motor will be deenergized. The damper
position will be determined by the supply-air
temperature.
When the first stage of cooling is satisfied,
the damper will move to fully closed position.

Heating, units with economizer


(50TJS008-014) (If Accessory or
Optional Heater is Installed) When the room thermostat calls for heat
through terminal W1, the evaporator-fan
contactor and heater contactor no. 1are
energized. On units equipped with 2 stages
of heat, when additional heat is needed,
heater contactor no. 2 is energized through
W2. The economizer damper moves to the
minimum position during heating. When the
thermostat is satisfied, the damper moves to
the fully closed position.

29

50LJS/TJS

Controls

Guide specifications
Packaged Rooftop Cooling Unit
with Electric
Heat Option Constant Volume
Application
50LJS/TJS

HVAC Guide Specifications


Carrier Model Number: 50TJS008 - 014
Part 1 General
1.01 SYSTEM DESCRIPTION
Outdoor rooftop- or slab-mounted, electrically
controlled cooling unit with optional heat
utilizing a hermetic compressor for cooling
duty and electric resistance coils for heating
duty. Unit shall discharge supply air vertically
or horizontally as shown on contract
drawings. Unit shall have TXV for refrigerant
control.
1.02 QUALITY ASSURANCE
A. Insulation and adhesive shall meet NFPA
90A requirements for flame spread and
smoke generation.
B. Unit casing shall be capable of
withstanding
500-hour salt spray exposure per ASTM
B117
(scribed specimen).
1.03
DELIVERY,
STORAGE,
AND
HANDLING Unit(s) shall be stored and
handled
as
per
manufacturers
recommendations.
Part 2 Products
2.01 EQUIPMENT (STANDARD)
A. General:
Factory-assembled, single-piece cooling unit
with optional heat. Contained within the unit
enclosure shall be all factory wiring, piping,
controls, refrigerant charge (R-22), and
special features required prior to field start
up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of
galvanized steel, shall be bonderized and
coated with a baked enamel finish on all
externally exposed surfaces.
2. Evaporator fan cabinet interior shall be
insulated with a minimum 1/2-in. thick, 1-lb

30

density Aluminum faced, flexible fiberglass


insulation.
3. Cabinet panels shall be easily removable
for servicing.
4. Holes shall be provided in the base rails for
rigging shackles to facilitate overhead rigging,
and forklift slots shall be provided to facilitate
maneuvering.
5. Unit shall have a factory-installed, sloped
condensate drain pan made of a non
corrosive plastic material, providing a
minimum 3/4-in. connection with both vertical
and horizontal drains and shall comply with
ASHRAE 62.
6. Unit shall have factory-installed filter
access panel to provide filter access with
tool-less removal.
C. Fans:
1. Indoor blower (evaporator fan) shall be of
the belt-driven, double inlet, forward curved,
centrifugal type. Belt drive shall include an
adjustable-pitch motor pulley.
2. Indoor blower (evaporator fan) shall be
made from steel with a corrosion-resistant
finish and shall be dynamically balanced.
3. Bearings shall be of the sealed,
permanently lubricated, ball-bearing type for
longer life and lower maintenance.
4. Condenser fan shall be of the direct-driven
propeller type and shall discharge air
vertically.
5. Condenser fan shall have aluminum
blades riveted to corrosion-resistant steel
spiders and shall be dynamically balanced.
D. Compressor(s):
1. Reciprocating or scroll type, fully hermetic
type, internally protected.
2. Factory mounted on rubber grommets and
internally spring mounted for vibration
isolation.
3. On independent circuits (TJ 008-014).
E. Coils:
1. Condenser coils shall have aluminum plate
fins mechanically bonded to enhanced
copper tubes with all joints brazed.
2. Tube sheet openings shall be belled to
prevent tube wear.
3. Evaporator coil shall be of the full face
active design.

F. Refrigerant Components:

Refrigerant circuit components shall include:

1. Thermostatic Expansion Valve (TXV).

2. Refrigerant filter.

3. Service gage connections on suction,

discharge, and liquid line.

50LJS/TJS

G. Filter Section:

1. Standard filter section shall consist of


factory installed low-velocity, throwaway 2-in.
thick fiberglass filters of commercially
available sizes.

2. Filter face velocity shall not exceed 320


fpm at nominal airflows.

3. Filter section shall use only one size filter.

4. Filters shall be accessible through an


access panel with no-tool removal.

and shall have line break thermal and current


overload protection.
2. Indoor blower (evaporator fan) motor shall
have permanently lubricated bearings and
inherent automatic-reset thermal overload
protection.
3. Totally enclosed condenser-fan motor shall
have permanently lubricated bearings, and
inherent automatic-reset thermal overload
protection.

H. Controls and Safeties:

1. Unit Controls:

Unit shall be complete with self-contained low

voltage control circuit.

2. Standard Safeties:

a. Unit shall incorporate compressor over

temperature and over current safety devices

to shut off compressor.

b. Contain high pressure as well as loss of

charge/low pressure and freeze protection

switches.

c. For models with Scroll compressors, unit

shall have phase monitor to prevent reverse

rotation.

d. Compressor Cycle Delay:

Unit shall be prevented from restarting for a

minimum of 5 minutes after shutdown.

L. Special Features:
1. High-Static Motor(s) and Drive(s)
(50TJS008-014): High-static motor(s) and
drive(s) shall be factory- installed to provide
an additional
performance range.
2. Condenser coil shall pre-coated
aluminum-fin coils shall have a
durable epoxy-phenolic coating to
provide protection in mildly corrosive
coastal environments. Coating shall
be applied to the aluminum fin stock
prior to the fin stamping process to
create an inert barrier between the
aluminum fin and copper tube.
Epoxy-phenolic barrier shall minimize
galvanic action between dissimilar
metals.

I. Operating Characteristics:

1. Unit shall be capable of starting and

running at 115 F ambient outdoor

temperature, meeting maximum load criteria

of ARI Standard 210/ 240 or 360 at 10%

voltage.

2. Compressor with standard controls shall

be capable of operation down to 25 F

ambient outdoor temperature.

3. Optional crankcase heater should be

0
installed where temperature falls below 45 F

and cooling operation is required.

J. Electrical Requirements:

All unit power wiring shall enter unit cabinet

at a single factory-predrilled location.

K. Motors:

1. Compressor motors shall be cooled by

refrigerant passing through motor windings

31

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations

2008

Form: 50TJS- 03PD -60HZ