A) B) C) D) E) F) G) H) I) Description of item INSTALLATION OF CHILLER PUMPS: COOLING TOWERS: SUPPLY OF AIR HANDLING UNITS/FAN COIL UNITS: VENTILATION FANS: DUCTING: PIPING: INSULATION: ELECTRICAL WORKS FOR HVAC SYSTEM: with EPCG Benefit without EPCG Benefit Unit Qty. Rate

GRAND TOTAL 1.0 1.1 PREAMBLE TO BOQ: Tendered Rates all Inclusive:

or for all items1.1.1 work shall be all inclusive and shall apply to all heights, lifts, leads and depths, in all positions of the building. of the

testing and to1.1.2 put there in working conditions and all other requirements as called for in all the parts of these Tender Documents.

gements, supports, nuts, bolts, hangers as are a standard part of the particular item except where specially mentioned otherwise. 1.1.3

Rates are inclusive of holes, sleeves, recesses in the concrete and masonry work as the Work proceeds except foundation work. 1.1.4

1.1.5 1.1.6

All rates quoted shall include marking of grills/diffusers. Nothing extra shall be payable to Contractor on account of any of the above factors.

Q. For all such items, if desired by the Owner, installation, testing and commissioning shall be the responsibility of the Contractor. 1.1.7

1.1.8

All the equipment /material shall be only from one of the I-preference of approved makes as per tender documents.

1.1.9

Making and closing of all HVAC associated openings in walls shall form part of HVAC works. All quoted prices should be

1.1.10 Wooden frame work for mounting grills on walls shall be in the scope of HVAC works and nothing shall be paid extra for

1.1.11 The grills/diffusers shall be measured and charged on actual area basis and 0.1m2 shall not be accepted as the minimu

1.1.12 The bidder should quote all imported equipment with price breakup in Foreign exchange and Indian Rupees. 1.1.13 The bidder should quote as per the equipment/ materials given in BOQ. Any suggested deviations can only be given as

1.1.14 The quoted price shall include all labelling and identification of various equipment/piping as per relevant IS colour coding

1.1.15 The water balancing is to be done using digital differential manometer. The data is to be accessed by online computer. C

DETAILED COST ESTIMATE S.No. A) Description of item INSTALLATION OF CHILLER Unit Qty. Rate

Receiving at site, unloading, storing, handling hoisting, installing in position, effecting connections, anchoring, grouting te

The chillers shall be installed over a reinforced cement concrete platform on flooring and shall be adequately isolated as

1.1

200 TR- Screw Chiller

Nos.

216000

Note: Supplier shall provide foundation details accordingly with their offer. Total of Sub-head C/F to Summary PUMPS: Primary Chilled Water Pump

B) 1.1

Supply, loading, unloading, packing, installation, testing and commissioning of end suction centrifugal pump sets with s

a)

480 USGPM x 12m head Under EPCG benefit 480 USGPM x 12m head (Manufacturer shall quote the taxes and duties components separately in case of EPCG benefit.) Secondary Chilled Water Pump Supply, loading, unloading, packing, installation, testing and commissioning of Secondary variable speed pumping system, end suction type. 1 No. dedicated microprocessor based pump controller housed with in the enclosure of one of the A.F.D., with pumping software duly downloaded. Adjustable frequency drives for each pump and differential pressure sensor/transmitters as necessary and as described in the specifications. The system shall be complete in all respects including thermal insulation, antivibration pads, channels base, cabling, Tyre coupling & guard, Pressure Gauges, flexible expansion bellows at both ends etc. and suitable for following ratings :-

Nos.

68000

a)

Nos.

1.2

a)

480 USGPM x 24m head Under EPCG benefit 480 USGPM x 24m head (Manufacturer shall quote the taxes and duties components separately in case of EPCG benefit.) Total Static pressure given below is minimum required for the system. Actual static pressure shall be calculated and confirmed by the vendor at the time of bidding for primary,secondary and condenser water pumps. Condenser Water Pump: Supply, loading, unloading, packing, installation, testing and commissioning of End Suction type Condenser Water Pumps, each capable of delivering specified flow rate, complete with bronze impeller, TEFC motor of 415 + 10% volts, 3 Phase, 50 Hz along with Tyre coupling & guard, Pressure Gauges, flexible expansion bellows at both ends etc complete mounted on common base frame with ribbed vibration isolators duly grouted to masonary foundation.

Nos.

508000

a) Note:

Nos.

2.0

a)

800 USGPM x 26m head Under EPCG benefit 800 USGPM x 26m head (Manufacturer shall quote the taxes and duties components separately in case of EPCG benefit.) Hot Water Pumps:

Nos.

105000

a)

Nos.

3.0

Supply, loading, unloading, packing, insurance upto install of monoblock type hot water pump set of following capacity, in

90 USGPM against x 18 m head (1W+1S) 4.0 Hot Water Generator: HOT WATER GENERATORS : 1.0

Nos.

15000

Supply, installing, testing and commissioning of Hot Water Generator of following capacity conforming to BIS Standards

a) Matching electrical immersion heater bank. Heater shall be seamless copper sheeted sheath electrically resistant U tube

b) All automatic and safety control such as safety valve, purge filling valves for descaling filled at inlet and outlet. High limit

c) Electrical panel mounted on generator frame complete with internal wiring, contactor, switches etc.

d) Interconnecting cables between panel and heater. Hot Water IN Temp. : 45 OC Hot Water OUT Temp. : 55 OC Heating Capacity : 90 kW (Each)

Nos.

225000

eplacement of the heaters are possible without disturbing the functioing of the Generator)

Note: All outgoings shall be provided with Stop/ Manual/ Auto selector switch to facilitate operation through BMS. All starters shall be provided with potential free contacts for connection to BMS. Total of Sub-head C/F to Summary (without EPCG Benefit) Total of Sub-head C/F to Summary (with EPCG Benefit) COOLING TOWERS:

C)

Supply, loading, unloading, packing, installation, testing and commissioning of FRP induced draught type cooling towers each complete with FRP basin having and auxiliary rectangular suction tank at the bottom. The basin shall be complete with connections for drain, overflow, makeup water, quick fill and float valve, plus hot dipped galvanised suction strainer FRP body, of sufficient strength to with stand wind velocities upto 60 m/s, vibrations and earth quakes, fan and motor assembly conforming to IP-55, protection for outdoor operation fill media of honeycomb design arranged in the suitable pattern for ease of replacement, distribution pipes consisting of PVC sprinkler pipes mounted on top of the main supply standby, sprinkler head mounted on ball bearings designed to take both radial and vertical thrust overflow pipe, ladder, vibration isolation pads, cables, controls etc. As per specifications and drawing. a) 240 T.R. Total of Sub-head C/F to Summary SUPPLY OF AIR HANDLING UNITS/FAN COIL UNITS: AIR HANDLING UNITS (AHU/TFA) Nos. 2 216000

D) 1.0

on isolators etc., complete as per specifications and drawing for the following capacities:

e provided with potential free contacts for connection to BMS and for Fire Alarm system.

1) a)

Basement - 01 5500 CFM - TFA for Corridor [1.02m2 coil area, 4 row deep cooiling coil, S.P 30mmWG] 2000 CFM - TFA Laundry (0.37m2 coil area, 6 row deep cooiling coil, S.P 30mmWG] 1600 CFM - Bakery[0.29m2 coil area, 4 row deep cooiling coil, S.P 30mmWG] 1500 CFM - Linen Room & Uniform room [0.27m2 coil area, 4 row deep cooiling coil, S.P 30mmWG] 2000 CFM - Male Locker [0.37m2 coil area, 4 row deep cooiling coil, S.P 30mmWG]

No.

86250

b)

No.

40500

c)

No.

31050

d)

No.

31050

e)

No.

34500

2) a)

Ground Floor 17500 CFM with 3.25 Sqm. Coil area, 6 row deep cooling coil , 2 row deep heating coil with 65 mm WG static pressure. (For Indian Grille) 7000 CFM with 1.3 Sqm. Coil area, 6 row deep cooling coil, 2 row deep heating coil with 50 mmmmWG static pressure. (For Entrance Lobby) 5000 CFM with 0.93 Sqm. Coil area, 4 row deep cooling coil, 2 row deep heating coil with 50 mmmmWG static pressure. (For Entrance Lobby) 3000 CFM with 0.55 Sqm. Coil area, 6 row deep cooling coil 30 mmWG static pressure. (For Kitchen) 9500 CFM with 1.76 Sqm. Coil area, 4 row deep cooling coil, 2 row deep heating coil with 50 mmmmWG static pressure. (For Bar) First Floor 6000 CFM with 1.12 Sqm. Coil area, 4 row deep cooling coil, 2 row deep heating coil with 40 mm mmWG static pressure. (For Meeting Room-1) 5800 CFM with 1.07 Sqm. Coil area, 4 row deep cooling coil 2 row deep heating coil with 40 mm mmWG static pressure. (For Meeting Room-2) 3200 CFM with 0.59 Sqm. Coil area, 4 row deep cooling coil 2 row deep heating coil with 40 mmmmWG static pressure. (For Meeting Room-3)

No.

350000

b)

No.

95000

c)

No.

74000

d)

No.

48300

e)

No.

130000

3) a)

No.

98500

b)

Nos.

105000

b)

Nos.

57960

c)

3300 CFM with 0.61 Sqm. Coil area, 4 row deep cooling coil 2 row deep heating coil with 35 mmmmWG static pressure. (For Prefunction & Lobby) Service Floor 1600 CFM -Staff Cafeteria [0.46m2 coil area, 4 row deep cooiling coil, S.P 30mmWG]. TFA Typical Floor 1600 CFM - TFA [6 row deep cooiling coil, S.P 30mmWG] FAN COIL UNITS (FCU)

No.

58960

4) a)

No.

31050

5) a) 2.0

Nos.

16

48000

ecifications and drawings. The unit shall be designed with acoustic performance in mind. 2.1

a)

For Guest Floors 1.5 TR with electric strip heater For BOH Area 1.0 TR 1.5 TR 2.0 TR 2.5 TR 3.0 TR

Nos.

206

12035

c) d) e) f) g)

Nos. Nos. Nos. Nos. Nos.

21 10 5 4 1

10500 11750 15000 19000 21000

Supply & fixing of following ball valves, without 'Y' strainer for the FCUs (PN-10) 2.2

a) b)

25 mm dia valve 32 mm dia valve

Nos. Nos.

242 5

350 400

Supply & fixing of following ball valves, with strainer for the F.C.Us (PN-10) 2.3

a) b) 3.0

25 mm dia valve 32 mm dia valve AIR COOLED SPLIT UNITS

Nos. Nos.

242 5

400 450

thermostat, wiring, control cooling and earthing. The unit capacities shall be as follows :

a) b)

1.5 TR Air Cooled Split Unit 2.0 TR Air Cooled Split Unit Total of Sub-head C/F to Summary VENTILATION FANS:

No. No.

1 5

37500 50000

E)

mplete as per specification. (The bidder shall submit fan performance curves for all fans). 1.0

a) b) c)

37000 CFM DIDW fan (40mm Static Pressure)- Basement-1 27000 CFM DIDW fan for DG Room (40mm Static Pressure) 6500 CFM SISW fan for Toilet (50mm Static Pressure)

Nos. Nos. No.

2 2 1

296000 243000 58500

17000 CFM SISW Fan for Corridor Smoke Exhaust (40mm Static Pressure) d) No. 9000 CFM SISW Fan for Corridor Smoke Exhaust (40mm Static Pressure) e) No. 1 72000 1 153000

5.0

Axial Flow Fans

air performance & sound ratings and the fan should be selected for maximum efficiency.

a) b)

28000 CFM Basement (in case of fire) (45mm Static Pressure) 12000 CFM Public Area Smoke Extraction(25mm Static Pressure)

Nos. Nos.

4 1

115000

35000 c) d) e) f) g) 10.0 6000 CFM Meeting & Public Area (25mm Static Pressure) 4800 CFM Boiler Room (25mm Static Pressure) 2740 CFM (B.O.H Area) (25mm Static Pressure) 3000 CFM Prefunction & Public Area(25mm Static Pressure) 1500 CFM Prefunction & Public Area(25mm Static Pressure) In-line Fan Supply, installation, testing and commissioning of Inline Centrifugal fan of following capacities: a) b) c) 2.0 1500 CFM 5000 CFM 600 CFM Air Washer Nos. Nos. Nos. 1 1 1 18000 60000 10800 Nos. Nos. Nos. Nos. Nos. 4 1 1 2 17 26000 28000 13700 21000 7500

omplete in all respects as per specifications and drawings. Capacity of coolers as under:

a) b) c) d) e) f) g) 3.0

67500 CFM for DG Set (40mm Static Pressure) 12200 CFM for Laundry (35mm Static Pressure) 6500 CFM for Bakery (35mm Static Pressure) 22000 CFM for Ground Floor Kitchen (40mm Static Pressure) 14000 CFM for First Floor Kitchen (40mm Static Pressure) 5500 CFM for Basement Boiler Room (25mm Static Pressure) 5700 CFM for Laundry (25mm Static Pressure) Scrubber :

Nos. Nos. Nos. Nos. Nos. Nos. Nos.

1 1 1 1 1 1 1

810000 140000 105000 250000 195000 102000 95000

ency down to 30 micron and complete as per specifications and approved shop drawing.

a)

57100 CFM for Ground & First Floor Kitchen (75mm Static Pressure) Nos. 1 1 685000 102000

b)

6750 CFM for Laundry (25mm Static Pressure) Total of Sub-head C/F to Summary DUCTING: Sheet Metal Duct:

Nos.

F)

c. as required 1.0 per specifications and approved shop drawing complete as required. & as

1.1 a) b) c) d) e) f) 1.2 a) b) c) d) e)

GSS Ducting (Air-conditioning ): B-26 C-26 D-26 E-24 F-22 I-20 GSS Ducting (Ventilation ): C-26 D-26 E-24 F-22 I-20 Sqm Sqm Sqm Sqm Sqm 150 100 300 200 200 550 550 555 650 825 Sqm Sqm Sqm Sqm Sqm Sqm 700 1100 800 1100 400 100 550 550 555 650 825 950

specifications 1.3 approved shop drawing complete as required. (For Kitchen Exhaust). and

a) b) c) d) e) 2.0

C-26 D-26 E-24 F-22 I-20 Flexible Connection:

Sqm Sqm Sqm Sqm Sqm

300 200 750 600 775

650 650 790 990 1200

exible connection constructed of fire resistant material as per the drawings/specifications. Nos. 4.0 Supply/Return Air Grills: 250 550

ow through the collar and register and removable key-operated volume control dampers.

a)

Powder Coated linear Aluminium grilles with volume control damper: Sqm 40 5500

b)Powder Coated linear Aluminium grilles without volume control damper: Sqm 4.0 Supply /Return Air Diffuser 40 3500

ow through the collar and register and removable key-operated volume control dampers.

a) Powder Coated Aluminium square diffuser with volume control damper Sqm Powder Coated Aluminium square diffuser without volume control damper b) Sqm 5.0 Supply /Return Slot Air Diffuser 10 5000 10 5500

diffuser complete with nuts,bolts,screw etc. as per approved drawings and specification.

a) b) 6.0

Supply air slot diffuser with volume control damper. Return air slot diffuser without volume control damper. Exhaust Air Grilles (Without Damper):

Sqm Sqm

20 20

10000 9000

esting of exhaust air Al. grilles with bird screen complete as per specification & drawings.

a) 7.0

Exhaust Air Grilles: Exhaust Air Louvers (Without Damper):

Sqm

25

3000

sting of exhaust air Al. louvers with bird screen complete as per specification & drawings. Sqm 8.0 Fresh Air Grilles: 12 3400

ng of fresh air Al. intake grilles with bird screen complete as per specification & drawings. Sqm 9.0 Fresh Air Louvers: 7 3400

g of fresh air Al. intake louvers with bird screen complete as per specification & drawings.

a 10.0

With Damper Smoke cum Fire Damper

Sqm

21

3400

re dampers hooked up with fire alarm system) complete as per specification & drawings.

11.1

Smoke and fire damper

Sqm

20

5500

11.2 otorized actuators spring return, control panel & temperature sensors. M Set Total of Sub-head C/F to Summary PIPING: Condenser Water Piping: 40 3000

G) 1.0

hall be visibly marked with identifying arrows complete as per specifications & drawings.

a) b) 2.0

250 mm dia MS pipes 200 mm dia MS pipes Chilled Water Piping:

RM RM

400 60

3000 1900

s such as clamps, anti-vibration hangers etc. complete as per specifications & drawings.

a) b) c) d) e) f) g) h) i) j)

200 mm dia MS pipes 150 mm dia MS pipes 125 mm dia MS pipes 100 mm dia MS pipes 80 mm dia MS pipes 65 mm dia MS pipes 50 mm dia MS pipes 40 mm dia MS pipes 32 mm dia MS pipes 25 mm dia MS pipes

RM RM RM RM RM RM RM RM RM RM

125 100 200 90 120 60 650 250 200 1300

2000 1300 1150 910 700 570 400 300 270 200

k) 3.0

20 mm dia MS pipes Hot Water Piping:

RM

R.O

190

s such as clamps, anti-vibration hangers etc. complete as per specifications & drawings.

a) b) c) d) e) 4.0

100 mm dia MS pipes 80 mm dia MS pipes 65 mm dia MS pipes 50 mm dia MS pipes 40 mm dia MS pipes Condensate Drain Piping

RM RM RM RM RM

275 20 30 135 290

850 700 570 400 300

ducers etc and supports such as clamps etc. complete as per specifications & drawings.

a) b) c) d)

40 mm dia GI pipes 32 mm dia GI pipes 25 mm dia GI pipes 20 mm dia GI pipes

RM RM RM RM

350 250 850 R.O

280 240 200 190

Providing and fixing in position the following butterfly valves (PN-10). 5.0

a) b) c) d) e) f) g)

250 mm dia (Un-insulated) 200 mm dia (Un-insulated) 200 mm dia (Insulated) 150 mm dia (Insulated) 100 mm dia (Insulated) 80 mm dia (Insulated) 65 mm dia (Insulated)

Nos. Nos. Nos. Nos. Nos. Nos. Nos.

R.O. 14 R.O. 16 12 5 4

9500 7800 8000 4500 3000 . 2600 2200

h) i) j)

50 mm dia (Insulated) 40 mm dia (Insulated) 32 mm dia (Insulated)

Nos. Nos. Nos.

42 18 12

1625 1400 1300

oviding and fixing in position the following balancing valves as per specifications: 6.0

a) b) c) d) e) f) g) h) 7.0 a) b) c) 8.0 a) b) c) d) e) f) g) 9.0

200 mm dia (Un-insulated) 200 mm dia (Insulated) 150 mm dia (Insulated) 80 mm dia (Insulated) 65 mm dia (Insulated) 50 mm dia (Insulated) 40 mm dia (Insulated) 32 mm dia (Insulated) Providing and fixing in position the following NRV (PN-10). 200 mm dia (Un-insulated) 150 mm dia (insulated) 150 mm dia (insulated) Providing and fixing in position the following Y-strainers. 200 mm dia (Insulated) 150 mm dia (Insulated) 80 mm dia (Insulated) 65 mm dia (Insulated) 50 mm dia (Insulated) 40 mm dia (Insulated) 32 mm dia (Insulated) Pressure Gauges & Thermometers:

Nos. Nos. Nos. Nos. Nos. Nos. Nos. Nos.

3 R.O. 2 1 2 21 6 4

25000 25200 17500 15500 4700 3500 2600 2500

Nos. Nos. Nos.

3 6 2

7200 6500 6650

Nos. Nos. Nos. Nos. Nos. Nos. Nos.

3 6 1 2 21 6 4

11000 7000 4500 2800 2350 1900 1800

ng ball valves in both the scales (metric & British units) complete as per specifications.

a) b) 10.0

Pressure Gauge Thermometer Air Purging Valve

Nos. Nos.

142 142

300 400

ding, fixing, testing and commissioning of mechanical air purging valves with ball valves.

25mm dia 11.0 Flow Switch

Nos.

25

800

Providing and fixing in position of approved make flow switch complete with copper control wiring at condenser and chille Nos. 12.0 2-Way Motorized Valves for AHUs: 4 1200

erging valve with motor/with out motor as required. The size of the valves are as follows:

a) b) c) d) e) 13.0

80 mm dia 65 mm dia 50 mm dia 40 mm dia 32 mm dia Expansion Tank

Nos. Nos. Nos. Nos. Nos.

1 2 21 6 4

18000 15000 13500 11500 10500

duly insulated and plastered fabricatedout of 3mm M.S. sheet as per the specifications.

a 14.0

1000 x 1000 x 1000mm Pot Strainer Providing and fixing in position the following pot strainers :

Nos.

15000

a) H) 1.0

250mm dia (Un-insulated) Total of Sub-head C/F to Summary INSULATION: Acoustic Lining of Ducts:

No.

25000

gs shall be provided with acoustic lining of fibre glass insulation as per the specifications.

a) b) 1.1

50mm thick acoustic lining 32 kg/cum. 25mm thick acoustic lining 32 kg/cum. Acoustic Lining of AHU Room:

Sqm Sqm

R.O 750

570 405

upply, installation & testing of acoustic lining of AHU room as per technical specifications.

a)50 mm thick acoustic lining (32 kg/cum.) (Wall & Ceiling of AHU Room) Sqm 2.0 Thermal Insulation: 300 680

cell nitrile rubber duct insulation with density 32 Kg/ Cum complete as per specifications.

a) b)
3.0

19 mm thick insulation. 9 mm thick insulation. Chilled Water Pipe Insulation:

Sqm Sqm

100 3500

350 375

espects as per specifications and drawings on chilled water pipes of the following sizes:

50mm thick a) b) c) d) e) f) 200 mm dia MS pipes 150 mm dia MS pipes 125 mm dia MS pipes 100 mm dia MS pipes 80 mm dia MS pipes 65 mm dia MS pipes 32mm thick 50 mm dia MS pipes 40 mm dia MS pipes 32 mm dia MS pipes RM RM RM RM RM RM 125 225 110 90 60 60 450 390 360 335 310 300

g) h) i)

RM RM RM

500 400 220

250 245 235

j) l)

25 mm dia MS pipes 20 mm dia MS pipes 25mm thick

RM RM

1200 R.O

185 190

l) m) n) 4.0

40 mm dia GI pipes 32 mm dia GI pipes 25 mm dia GI pipes Nitrile rubber insulation

RM RM RM

350 250 750

210 205 170

espects as per specifications and drawings on chilled water pipes of the following sizes:

a) 5.0

19mm thick 25 mm dia MS pipes (for Guest room) Hot Water Pipe Insulation:

RM

300

350

espects as per specifications and drawings on chilled water pipes of the following sizes:

50mm thick a) b) c) 100 mm dia MS pipes 80 mm dia MS pipes 65 mm dia MS pipes 32mm thick 50 mm dia MS pipes 40 mm dia MS pipes Total of Sub-head C/F to Summary ELECTRICAL WORKS FOR HVAC SYSTEM: RM RM RM 275 20 30 335 310 300

e) e)

RM RM

135 290

250 245

I)

1.0

Design, fabrication, loading, unloading at store as directed by Engineer-in-Charge, supply, installation, testing and commissioning of LT Panels fabricated out of 2mm thick for structural members (Load bearing members) and 1.6mm thick for door and covers (Non load bearing members) CRCA sheet in cubicle compartmentalize free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel 'T' irons and / or flats wherever necessary, 16 gauge CRCA sheet steel shall be used for final distribution panels. Cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before painting as per specifications with 2 coats of zinc chromate primer and final approved shade of enamelled paint. 2 Nos. earthing terminals shall be provided for all distribution panels. Panels shall be suitable for 415V, 3-phase, 4wire, 50Hz supply system and with 15% spare space, lifting hooks shall also be provided in case of large panels.

Approval shall be taken for each panel before fabrication. Galvanized hardwares with zinc passivation shall be used in fabrication of panels.

General Notes: 1.0 ACB: LSI (Microprocessor Based) releases shall be used for incoming ACB feeders..

2.0

MCCB: All MCCB's shall be provided with door interlocked rotary handle with ON/TRIP/OFF position indicator, continious variable thermal magnetic O/C and S/C releases. The MCCB above 250A rating shall be provided with microprocessor based releases (settable at site). i/c MCCB shall be provided with E/F release also. All MCCB used in starter feeder shall be suitable for motor duty application. (curve 'X' type) All motor circuit MCB shall be motor duty with 'C' curve. All switchgears used in starter feeder shall be type-2 co-ordinated. Manufacturer is required to submit manufacturers type-2 coordination chart for the make used. Capacitor shall be heavy duty type (MPP technology). Breaking capacity mentioned is Ics value. All CT, PT shall be cast resin. All meters shall be digital type. All indicating light shall be LED type .

3.0

4.0 5.0

6.0 7.0 8.0 9.0 10.0

11.0

All starters shall be provided with Auto/ Manual selector switch, MPCB/ MCCB/MCB, over load relay, single phasing preventor, ON/OFF/ Trip indication lamps, ON/OFF push Buttons, contractor and suitable No. of Potential free contacts for remote / local operations, indication, interlocking and Building Management system. The BOQ shall be read in conjunction with general notes, specification and Single Line Diagram (attached for Ref.). Incase of any discrepancy between specification, BOQ and SLD, the same shall be brought to the notice of Client/Consultant before quoting the rates, otherwise stringent condition shall be deemed to have been considered. Current density for bus bar shall not be more than 0.8A/Sqmm. Rating of Bus bar is after considering all derating factors. (Bus bar sizing calculation to be submitted for approval.) All bus bar shall be insulated with coloured PVC Sleeve i.e. R, Y, B, BK as per colour code. All internal control wiring shall be heat resistant type. All TP/TPN feeders shall have solid isolable neutral link. Bus bar chamber shall be provided at top only. Incoming and outgoing cable entry shall be from top/bottom as required. Bus couplers shall be provided with ON & OFF indicating lights but without releases. All feeders shall be provided with door interlocked with door defeat, pad lock facility. Live parts shall not be accessible after opening the door, Transparent acrylic sheet to be provided to cover the same. Spare contacts of Relays/Contactor etc. shall be wired upto terminal block. All outgoing feeders shall have ON/OFF indication lamps with 2A control MCB. Degree of protection for following type of distribution panel enclosure shall be as per IS:13947-1993. IP 43 for indoor panels. IP 55 for outdoor panels. All electrical panels and circuits must be labeled and manufacturers shall submit the CPRI approved certificate with their quote.

12.0

13.0

14.0

15.0 16.0 17.0

18.0

19.0

20.0

21.0

22.0

23.0 a) b) 24.0

1.1

AC Plant Room Panel

Incomer (2 Nos.): Each shall have following: 1600A, 4-pole, EDO type ACB (35KA) (microprocessor based with all releases). Metering (0-500) volts digital voltmeter with selector switch protected by 2A control MCB's

(0-800A) Digital ammeter with Selector Switch and suitable ratio, CL1, 10VA CT's Phase indicating lamps and shall be protected by 2Amps MCBs.

Bus Coupler (2 Nos.): 800Amps 4P EDO ACB (35KA) type with necessary potential free contacts for interlockings and with breaker control switch, ON/OFF/Trip indicating lamps with control MCBs. Bus Bar: 1000A TPN aluminium , colour coded bus bars suitable for 415V, 50Hz. (after deration) Outgoings: Section- 1 Three (3) Nos. 630A TP+N MCCB (25 KA) Two (2) Nos. 125A TP+N MCCB (25 KA) Four (4) Nos. 63A TP+N MCCB (25 KA) One (1) No. 40A TP+N MCCB (25 KA) Section- 2 Two (2) Nos. 630A TP+N MCCB (25 KA) Two (2) Nos. 125A TP+N MCCB (25 KA) Two (2) Nos. 63A TP+N MCCB (25 KA) One (1) No. 40A TP+N MCCB (25 KA) Section- 3 Three (3) Nos. 630A TP+N MCCB (25 KA) Two (2) Nos. 125A TP+N MCCB (25 KA) Four (4) Nos. 63A TP+N MCCB (25 KA) One (1) No. 40A TP+N MCCB (25 KA) Starters:

n each feeder and Auto Manual Selector Switch as required. (Condenser Water Pumps)

ach feeder and Auto Manual Selector Switch as required. (Primary Chilled Water Pumps)

ation in each feeder and Auto Manual Selector Switch as required. (Cooling Tower Fans)

ntacts for remote operation in each feeder and Auto Manual Selector Switch as required.

Set 1.2 Guest Floor Smoke Extraction Panel Incoming (1 No.): 125Amp TP+N MCCB, 25kA Metering & Indication: (0-500) volts digital voltmeter with selector switch protected by 2A control MCB's

1 ######

(0-125A) Digital ammeter with Selector Switch and suitable ratio, Cl1, 10VA CT's Set of Phase indicating lamps. Each backed up with 2 Amps Control MCB.

Bus Bars: 200A, TPN aluminium , colour coded bus bars suitable for 415V, 50Hz. (after deration) Outgoings ON/OFF indicating lamps with 2A Control MCB shall be provided on each outgoing. Eighteen (18) Nos. 40A 4P MCB (10KA) 1.3 Basement Ventilation Panel Set 1 105000

Incoming (1 No.): 250Amp TP+N MCCB, 25kA Metering & Indication: (0-500) volts digital voltmeter with selector switch protected by 2A control MCB's

(0-250A) Digital ammeter with Selector Switch and suitable ratio, Cl1, 10VA CT's Set of Phase indicating lamps. Each backed up with 2 Amps Control MCB.

Bus Bars: 350A, TPN aluminium , colour coded bus bars suitable for 415V, 50Hz. (after deration) Outgoings ON/OFF indicating lamps with 2A Control MCB shall be provided on each outgoing. Six (6) Nos. 40A 4P MCB (10KA) Seven (7) Nos. 63A TP+N MCCB (15KA) 1.4 Smoke Extraction Panel (Basement + BOH area) Incoming (1 No.): 125Amp TP+N MCCB, 25kA Metering & Indication: (0-500) volts digital voltmeter with selector switch protected by 2A control MCB's

Set

250000

(0-125A) Digital ammeter with Selector Switch and suitable ratio, Cl1, 10VA CT's Set of Phase indicating lamps. Each backed up with 2 Amps Control MCB.

Bus Bars: 200A, TPN aluminium , colour coded bus bars suitable for 415V, 50Hz. (after deration) Outgoings ON/OFF indicating lamps with 2A Control MCB shall be provided on each outgoing.

Three (3) Nos. 63A TP+N MCCB (15KA) Five (5) Nos. 40A 4P MCB (10KA) 2.0 2.1 Cabling:

Set

115000

Supplying & laying of following 1100 volt grade XLPE insulated PVC sheathed aluminium conductor armoured cables

a) 3.5C x 240 Sq.mm cable b) 4C x 25 Sq.mm cable c) 4C x 16 Sq.mm cable d) 4C x 10 Sq.mm cable e) 3.5C x 35 Sq.mm cable f) 3C x 70 Sq.mm cable g) 3C x 35 Sq.mm cable h) 3C x 25 Sq.mm cable i) 3C x 16 Sq.mm cable j) 3C x 10 Sq.mm cable k) 3C x 6 Sq.mm cable l) 3C x 4 Sq.mm cable 2.1.1 Copper Conductor Armoured Cables: a) b) 2.2 3C x 1.5 Sq mm PVC insulated, multi stranded 3C x 2.5 Sq mm PVC insulated, multi stranded Cable termination :

RM RM RM RM RM RM RM RM RM RM RM RM

200 2500 1000 1200 200 100 100 200 250 500 1000 200

1140 215 145 115 175 345 205 150 140 115 110 100

RM RM

20 10

65 80

Supplying of all materials and making terminations of 1.1 KV grade aluminium multicore cables of the following sizes. T

a) 3.5C x 240 Sq.mm b) 4C x 25 Sq.mm c) 4C x 16 Sq.mm d) 4C x 10 Sq.mm e) 3.5C x 35 Sq.mm f) 3C x 70 Sq.mm

Nos. Nos. Nos. Nos. Nos. Nos.

12 36 24 90 10 8

1500 390 340 270 490 650

g) 3C x 35 Sq.mm h) 3C x 25 Sq.mm i) 3C x 16 Sq.mm j) 3C x 10 Sq.mm k) 3C x 6 Sq.mm l) 3C x 4 Sq.mm 2.2.2 Copper Conductor Cables: (Single compression glands suitable for following armoured cables). a) 3C 1.5 Sq mm PVC insulated b) 3C 2.5 Sq mm PVC insulated 2.3 Control Cables:

Nos. Nos. Nos. Nos. Nos. Nos.

8 10 20 50 30 30

420 375 350 300 250 180

Nos. Nos.

4 4

100 120

Supplying, receiving, storing, laying, effecting proper connections, testing and commissioning of the following sizes of 1.1

a) b) c) d) 2.4

2 C x 2.5 Sq.mm Cable 4 C x 2.5 Sq.mm Cable 7 Core x 2.5 Sq.mm Cable 10 Core x 2.5 Sq.mm Cable Control Cable Termination

RM RM RM RM

150 50 300 700

130 190 250 390

Supply, installation, testing and commissioning of Control Cable end termination of the following PVC insulated copper c

a) b) c) d) 3.0

2 C x 2.5 Sq.mm Cable 4 C x 2.5 Sq.mm Cable 7 Core x 2.5 Sq.mm Cable 10 Core x 2.5 Sq.mm Cable Supply and drawing of following sizes of PVC insulated multi stranded copper conductor wires 1100V grade in existing conduits, pipes, raceways including connection/termination etc. as required.

Nos. Nos. Nos. Nos.

4 4 4 16

180 220 290 350

a) b) 4.0

3 x 2.5 Sq.mm 3 x 4 + 2 x 2.5 Sq.mm Cable Tray:

RM RM

250 150

180 110

Supply, fabricating and installing following sizes of painted 2mm thick MS ladder/perforated type Cable tray including ho

4.1 a) b) c) d) 4.2

Perforated Type 1000mm(W) x 40 mm (Deep) 450 mm wide x 40 mm (Deep) 300 mm wide x 40 mm (Deep) 150 mm wide x 40 mm (Deep) Cable Tray Support: Supply, fabrication and installation of cable support structure as per drawings/ specification/ site requirement and the direction of Construction manager/ Consultant comprising of ISMCS, ISAs flats rods, tumbuckles etc for supporting cable trays in multitier formation. The rate shall include painting with 2 primer coats of red oxide and two finishing coats of approved enameled paint. Earthing System: Providing and laying of 600 x 600 x 6 mm GI plate with 1 No. 75 x 6 mm GI tape form earth electrode to inspection chamber, 20mm dia medium class GI pipe, CI funnel with 20 gauge GI wire mesh, masonry chamber 300 x 300 x 300 mm with concrete base CI manhole cover having locking (the chamber shall be of dissconnection type link for testig of earthing pit) arrangement with frame painted with bitumastic paint and packing with mixtures of charcoal and common salt around plate electrode including digging of pit upto permanent moisture level but not less than 3 meter and black filling as required. G.I. Earthing Strip/Wire:

RM RM RM RM

50 50 100 200

1200 700 325 275

Kg.

500

50

5.0 5.1

Nos.

6500

5.2

Supply, installation, testing and commissioning of following sizes of G.I. strip/wire clamped to walls, cable trays, bus

a) 25 x 6 mm strip b) 8 SWG wire c) 6 SWG wire 6.0 Supply & installation of following size of black enamelled MS conduit on surface/concealed including all accessories, GI fish wire, fixing hardware etc including chasing the wall/floor and plastering the chased portion and making good the damages including fitting e.g. bends, tee, GI flexible pipe, inspection bends etc as required.

RM RM RM

600 2000 800

125 13 16

a) 25 mm dia b) 32 mm dia 7.0 Supply & installation of following size of heavy duty (FRLS) PVC conduit on surface/concealed including all accessories, GI fish wire, fixing hardware etc including chasing the wall/floor and plastering the chased portion and making good the damages including fitting e.g. bends, tee, GI flexible pipe, inspection bends etc as required.

RM RM

50 50

85 130

a) 25 mm dia b) 32 mm dia 8.0 Starter for AHUs/TFAs:

RM RM

50 50

50 75

Supply, installation, testing & commissioning of the following starters in a sheet metal enclosure complete as required an

nd push buttons, potential free contacts for remote operation in each feeder as required . 8.1

i) ii)

10.0 HP Auto Star Delta Starter 7.5 HP Auto DOL Starter

No. No.

1 1

14850 11250

nd push buttons, potential free contacts for remote operation in each feeder as required . 8.2

i) ii) iii) iv) v) 9.0

5.0 HP DOL Starter 3.0 HP DOL Starter 2.0 HP DOL Starter 1.5 HP DOL Starter 1.0 HP DOL Starter Starter for Ventilation Fan:

Nos. Nos. Nos. Nos. Nos.

5 2 3 2 4

10350 9450 9000 8550 8550

Supply, installation, testing & commissioning of the following starters in a sheet metal enclosure complete as required an

nd push buttons, potential free contacts for remote operation in each feeder as required . 9.1

i) Auto Star Delta Starter for 25 HP fan with 100A TP+N MCCB.

No.

R.O

27000

ii) Auto Star Delta Starter for 20 HP fan with 100A TP+N MCCB. iii) Auto Star Delta Starter for 15 HP fan with 63A TPN MCB. iv) Auto DOL Starter for 10.0 HP fan with 63A TPN MCB. v) Auto DOL Starter for 7.5 HP fan with 63A TPN MCB. vii) Auto DOL Starter for 5.0 HP with 40A TPN MCB. viii) Auto DOL Starter for 3.0 HP fan with 40A TPN MCB. ix) Auto DOL Starter for 2.0 HP fan with 32A TPN MCB. x) Auto DOL Starter for 1.5 HP fan with 25A TPN MCB. 10.0 ISOLATORS:

Nos. Nos. No. Nos. Nos. Nos. Nos. No.

6 5 1 2 4 4 4 1

22500 21150 13500 11250 10350 9000 8100 7650

Supply, installation, testing and commissioning of following isolator in MS box with all material and as per site requireme

10.1 100A TPN MCCB 10.2 63A TPN MCB Total of Sub-head C/F to Summary

Set Set

R.O 4

15000 2500

Amount 648,000 2,523,000 432,000 5,533,630 4,744,500 7,038,000 4,922,650 3,171,675 4871000

######### PREAMBLE TO BOQ: ered Rates all Inclusive: positions of the building.

hese Tender Documents.

ally mentioned otherwise.

except foundation work.

marking of grills/diffusers.

any of the above factors.

nsibility of the Contractor.

akes as per tender documents.

C works. All quoted prices should be inclusive of this aspect.

s and nothing shall be paid extra for this. However, frame work for mounting grills/diffusers on false ceiling shall be provided by other agenci

shall not be accepted as the minimum chargeable area.

ange and Indian Rupees.

ted deviations can only be given as an option with proper justification.

ping as per relevant IS colour coding. In the absence of IS colour coding for any equipment, the labelling and identification shall be carried ou

o be accessed by online computer. Contractor must submit computerized printout of each valve indicating design flow, differential pressure,

Amount

g connections, anchoring, grouting testing and commissioning including supplying & installing all necessary indigenous accessories as requi

g and shall be adequately isolated as per manufacturers recommendations against transmission of vibration to the building structure & compl

648000

648,000

suction centrifugal pump sets with suitable electric motor for circulation of chilled water for central air-conditioning system. All pumps shall b

204000

1524000

315000

ater pump set of following capacity, including GA drawing for foundation for pumps etc. complete as per specifications.

30000

apacity conforming to BIS Standards at specified flow rate and hot water temperature complete as per specification with following accessorie

ed sheath electrically resistant U tube type suitable for 3 phase 415 Volts with flange ends in 3 banks.

ng filled at inlet and outlet. High limit cut-out, automatic and manual reset, low level cut out step controller and recycling relay, thermostats pil

r, switches etc.

450000

2,523,000 -

432000 432,000

86250

40500

31050

62100

34500

350000

95000

74000

48300

130000

98500

105000

57960

58960

31050

768000

2479210

220500 117500 75000 76000 21000

84700 2000

96800 2250

37500 250000 5,533,630

592000 486000 58500

153000

72000

460000

35000 104000 28000 13700 42000 127500

18000 60000 10800

810000 140000 105000 250000 195000 102000 95000

685000 102000 4,744,500

385000 605000 444000 715000 330000 95000

82500 55000 166500 130000 165000

195000 130000 592500 594000 930000

137500

220000

140000

55000 50000

200000 180000

75000

40800

23800

71400

110000

120000 7,038,000

1200000 114000

250000 130000 230000 81900 84000 34200 260000 75000 54000 260000

---

233750 14000 17100 54000 87000

98000 60000 170000 ----

--109200 --72000 36000 13000 8800

68250 25200 15600

75000 --35000 15500 9400 73500 15600 10000

21600 39000 13300

33000 42000 4500 5600 49350 11400 7200

42600 56800

20000

4800

18000 30000 283500 69000 42000

15000

25000 4,922,650

--303750

204000

35000 1312500

56250 87750 39600 30150 18600 18000

125000 98000 51700

222000 ---

73500 51250 127500

105000

92125 6200 9000

33750 71050 3,171,675

1500000

105000

250000

115000

minium conductor armoured cables as per specification in existing trenches, cable trays, ducts, clamped to wall with suitable clamps includin

228000 537500 145000 138000 35000 34500 20500 30000 35000 57500 110000 20000

1300 800

core cables of the following sizes. The work includes cable glanding using brass plated double compression glands, sizing the core leads, re

18000 14040 8160 24300 4900 5200

3360 3750 7000 15000 7500 5400

400 480

missioning of the following sizes of 1.1 KV grade PVC insulated copper conductor armoured stranded control cable complete as required.

19500 9500 75000 273000

he following PVC insulated copper conductor armoured stranded control cable including supplying and fixing of bimettalic crimping lugs, dou

720 880 1160 5600

45000 16500

forated type Cable tray including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly s

60000 35000 32500 55000

25000

26000

clamped to walls, cable trays, bus ducts, cables in recess or surface etc for equipment/ System / Lightning protection earthing complete

75000 26000 12800

4250 6500

2500 3750

al enclosure complete as required and as per site conditions:

14850 11250

51750 18900 27000 17100 34200

al enclosure complete as required and as per site conditions:

135000 105750 13500 22500 41400 36000 32400 7650

ll material and as per site requiremet.

10000 4871000

indigenous accessories as required to complete the installation of Water Cooled Screw Chiller complete as required and as per site conditio

to the building structure & complete as per site conditions, drawings and co-ordination with supply vendor.

ioning system. All pumps shall be fixed on M.S. frame structure with base plate of pumps. The pump motor shall be suitable for 415 10% v

ication with following accessories.

d recycling relay, thermostats pilot light (for individual heating circuit and alarm, poor interlock switches, flow switch and other control).

wall with suitable clamps including providing and fixing of all fixing accessories, connecting, testing and commissioning.

n glands, sizing the core leads, removing insulation, fixing suitable crimping type aluminium lugs/thimbles by using hydraulic crimping tools w

cable complete as required.

g of bimettalic crimping lugs, double compression glands with earthing facility and cable sockets etc. complete as required.

ccessories as required and duly suspended from the ceiling with MS suspenders and including painting etc. (Cost of support of Cable Tray s

ing protection earthing complete as required including inter connection between length at joints, all fixing accessories saddles, clamps

d and as per site conditions.

e suitable for 415 10% volts, 50 cycles, 3 phase power supply. The price of pump shall also include the cost of thermal insulation, anti-vibra

and other control).

ydraulic crimping tools with correct size of the dies, shaping the leads and neatly connecting the same to the equipment terminals.

f support of Cable Tray shall not include the item). Colour of paint to be approved by the client/consultant.

sories saddles, clamps etc. and other fixing hardware material as required for proper installation.

rmal insulation, anti-vibration pads, channels base, cabling, Tyre coupling & guard, Pressure Gauges, flexible expansion bellows at both end

ment terminals.

nsion bellows at both ends etc. and suitable for following ratings as per specifications. Pump performance characteristics shall be suitable fo

ristics shall be suitable for parallel operation as follows:-

Chiller S.pump P.pump C.Pump H.W.Pump

QTY. 3 3 3 3 2

6 6 6 6 4