AURORA FIRE PUMPS

VERTICAL TURBINE

Section 914 Page 201 Date April 2006


Supersedes Section 914 Page 201 Dated May 2004

Use the following table to determine which discharge head should be used on vertical turbine fire pumps. Both style discharge heads are shown on the setting plans where applicable.
Rated Capacity (GPM) 250 300 400 500 750 750 1000 1000 1250 1500 1500 2000 2000 2500 3000 3500 4000 4500 Discharge Head Design 100-175 PSI Working Pressure U.L. Listed FM Approved 16-1/2 x 6 SDC 16-1/2 x 6 SDC 16-1/2 x 6 SDC 16-1/2 x 6 SDC 16-1/2 x 6 SDC 16-1/2 x 6 SDC 16-1/2 x 6 LAD 16-1/2 x 6 LAD 16-1/2 x 6 LAD 16-1/2 x 6 LAD 16-1/2 x 8 SDC 16-1/2 x 8 SDC 16-1/2 x 6 LAD 16-1/2 x 6 LAD 16-1/2 x 8 SDC 16-1/2 x 8 SDC 16-1/2 x 8 SDC 16-1/2 x 8 SDC 16-1/2 x 8 SDC 16-1/2 x 8 SDC 20 x 10 LAD 20 x 10 LAD 20 x 10 LAD 20 x 10 LAD 20 x 10 LAD 20 x 10 LAD 20 x 10 LAD 20 x 10 LAD 24-1/2 x 12 SDH 24-1/2 x 12 SDH 24-1/2 x 12 SDH 24-1/2 x 12 SDH 24-1/2 x 12 SDH 24-1/2 x 12 SDH 24-1/2 x 12 SDH 24-1/2 x 12 SDH

Bowl Design 10 FEM 10 FEM 10 FEM 11 FGM 12 FCM 14 FGM 12 FCM 14 FGM 13 FGH 13 FGH 15 FGH 15 FGH 17 FGM 15 FGH 19 FGM 19 FGM 19 FGH 19 FGH

176-300 PSI Working Pressure U.L. Listed or FM Approved 16-1/2 x 6 LAD 16-1/2 x 6 LAD 16-1/2 x 6 LAD 16-1/2 x 6 LAD 16-1/2 x 6 LAD 16-1/2 x 8 LAD 16-1/2 x 6 LAD 16-1/2 x 8 LAD 16-1/2 x 8 LAD 16-1/2 x 8 LAD 20 x 10 LAD 20 x 10 LAD 20 x 10 LAD 20 x 10 LAD 24-1/2 x 12 SDH 24-1/2 x 12 SDH 24-1/2 x 12 SDH 24-1/2 x 12 SDH

2011 Pentair Pump Group, Inc.

Section 914 Page Date April 2006

202

AURORA FIRE PUMPS


ELECTRIC DRIVEN VERTICAL TURBINE
S T U DIA CL DISCH (4) H DIA HOLES BASEPLATE TOP VIEW 3/4" NPT DRAIN G NPT F

Supersedes Section 914 Page 202 Dated May 2004


T

B N A CL DISCHARGE C

(O.A.L.)

NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. Limited to maximum working pressure of 175 PSI. 5. For 250 GPM Z = 21. For 300 GPM and 400 GPM Z = 24.

NOMINAL COLUMN DIA

Z MIN WATER LEVEL

W Y 12 MIN

BOTTOM OF PIT

Size & Model 10 FEM 11 FGM 12 FCM

# of Stages 4 4 3

BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Lube Only Lube Only 6 6 41 41 6 10 Total Stages Add 8.25 for each additional stage over 4 stages 6 8 44-13/16 47-9/16 9 11-1/2 Total Stages Add 9-1/2 for each additional stage over 4 stages 8 8 40 42-3/4 7 13 Total Stages Add 10-3/4 for each additional stage over 3 stages

Z (5) 34 34

DISCHARGE HEADS & BASEPLATES Size BD 12 16-1/2 16-1/2 16-1/2 Customer: Job Name: Model: Motor Mfg.: Certified By: # Stages: HP: Frame: Date: GPM: Ph: DISCH 6 SDH 6 SDC 6 LAD 6 SDH A 20 23 23 20 B 11-1/2 11-3/8 10-1/4 11-1/2 C 7 10 10 7 F 1 1-1/2 1-1/2 1 G 3/4 1 1 3/4 P.O.#: UL FM CUL PSI: Hz: V: H 1 7/8 7/8 1 N 1-3/8 1-1/16 1-1/16 1-3/8 S 21-1/2 24 24 21-1/2 T 17-5/32 21 21 17-5/32 Dwg.# Flange Rating: Max. Lift: Encl.: 125# 250# U 14-1/2 17-1/8 17-1/8 14-1/2

(4)

2011 Pentair Pump Group, Inc.

AURORA FIRE PUMPS


ELECTRIC DRIVEN VERTICAL TURBINE
S T U DIA CL DISCH (4) H DIA HOLES BASEPLATE TOP VIEW 3/4" NPT DRAIN G NPT

Section 914 Page Date May 1, 2004

203

Supersedes Section 914 Page 203 Dated June 1, 2002

B N A CL DISCHARGE C

(O.A.L.)

NOMINAL COLUMN DIA

NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. Limited to maximum working pressure of 175 PSI.

Z MIN WATER LEVEL

W Y 12 MIN

BOTTOM OF PIT

Size & Model 13 FGH 14 FGM 15 FGH

# of Stages 4 3 3

BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Lube Only Lube Only 8 10 61-13/16 65-1/4 11 13 Total Stages Add 13-1/16 for each additional stage over 4 stages 8 10 44-15/16 49-1/4 13 14-3/4 Total Stages Add 12-3/16 for each additional stage over 3 stages 10 12 54-1/16 57-7/16 13 14-3/4 Total Stages Add 14-1/2 for each additional stage over 3 stages DISCHARGE HEADS & BASEPLATES

Z 34 30 34 - 2000 GPM 46 - 2500 GPM

Size BD 16-1/2 16-1/2 20 Customer: Job Name: Model: Motor Mfg.: Certified By: # Stages: HP: Frame: Date: GPM: Ph: DISCH 8 SDH 8 LAD 10 LAD A 23 23 23 B 11-3/8 11-3/8 13-7/8 C 10 10 10-1/2 F 1-1/2 1-1/2 1-1/2 G 1 1 1 H 7/8 7/8 7/8 P.O.#: UL FM CUL PSI: Hz: V: N 1-3/16 1-3/16 1-1/4 S 24 24 24 T 21 21 21 U 17-1/8 17-1/8 17-1/8 Dwg.# Flange Rating: Max. Lift: Encl.: 125# 250# (4)

2011 Pentair Pump Group, Inc.

Section 914 Page 204 Date May 1, 2004


Supersedes Section 914 Page 204 Dated June 1, 2002

AURORA FIRE PUMPS


ELECTRIC DRIVEN VERTICAL TURBINE
S T U DIA CL DISCH (4) H DIA HOLES BASEPLATE TOP VIEW 3/4" NPT DRAIN G NPT F

B N A CL DISCHARGE C

(O.A.L.)

NOMINAL COLUMN DIA

NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place.

Z MIN WATER LEVEL

W Y 12 MIN

BOTTOM OF PIT

Size & Model 17 FGM 19 FGM 19 FGH

# of Stages 3 2 2

BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Lube Only Lube Only 12 N/A 49-7/8 N/A 9 18 Total Stages Add 13-1/2 for each additional stage over 3 stages 12 N/A 47-5/8 N/A 12 23-1/2 Total Stages Add 17-5/8 for each additional stage over 2 stages 12 N/A 47-5/8 N/A 12 23-1/2 Total Stages Add 17-5/8 for each additional stage over 2 stages DISCHARGE HEADS & BASEPLATES

Z 28 32 32

Size BD 20 24-1/2 DISCH 10 LAD 12 SDH A 23 28 B 13-7/8 17 C 10-1/2 13-1/2 F 1-1/2 2 G 1 3/4 H 7/8 1-1/8 N 1-1/4 1-7/8 S 24 32-1/2 T 21 26-5/32 U 19 24-1/2

Customer: Job Name: Model: Motor Mfg.: Certified By: # Stages: HP: Frame:

P.O.#: UL GPM: Ph: Date: FM CUL PSI: Hz: V:

Dwg.# Flange Rating: Max. Lift: Encl.: 125# 250#

2011 Pentair Pump Group, Inc.

AURORA FIRE PUMPS


DIESEL DRIVEN VERTICAL TURBINE
S T U DIA CL DISCH HP (4) H DIA HOLES BASEPLATE TOP VIEW HD CD CS MAXIMUM VERTICAL OFFSET IS .25

Section 914 Page 205 Date September 2011


Supersedes Section 914 Page 205 Dated May 2004

FACE OF DRIVE DISK

T S

COUPLING GUARD

B N

A
1/2 4 AN DIA HOLES CE F

DISCHARGE C

AA

AB AB

CL OF ENGINE

Mfg.

GEAR Ratio

G NPT COOLING SUPPLY FOR ENG 3/4" NPT DRAIN NOMINAL COLUMN DIA

Model

AF CC CA

(O.A.L.)

NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. Reducers and/or increasers may be required to meet NFPA Pamphlet #20. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. Limited to maximum working pressure of 175 PSI 5. CD, CE & CS are dimensioned to face of drive disk. 6. For 250 GPM Z = 21. For 300 GPM and 400 GPM Z = 24.

Z MIN WATER LEVEL

W Y 12 MIN

BOTTOM OF PIT

Size & Model 10 FEM 11 FGM

# of Stages 4 4

BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Lube Only Lube Only 6 6 41 41 6 10 Total Stages Add 8-1/4 for each additional stage over 4 stages 6 8 44-13/16 47-9/16 9 11-1/2 Total Stages Add 9-1/2 for each additional stage over 4 stages DISCHARGE HEADS & BASEPLATES

Z (6) 34

Size BD 16-1/2 16-1/2 DISCH 6 SDC 6 LAD A 23 23 B 11-3/8 10-1/4 C 10 10 F 1-1/2 1-1/2 G 1 1 H 7/8 7/8 N 1-1/16 1-1/16 S 24 24 T 21 21 U 17-1/8 17-1/8 (4)

MODEL JU4HUF10 JU4HUF20 JU4HUF30 JU4HUF40 Customer: Job Name: Model: Engine Mfg.: Certified By:

AA 32 32 32 32

AB 15 15 15 15

AF 5 5 5 5

CLARKE JU4H DIESEL ENGINES AN CA CB CC 1x2 40 N/A 30 1x2 40 N/A 30 1x2 40 N/A 30 1x2 40 N/A 30 P.O.#:

CD 35.75 35.75 35.75 35.75

CE 2.26 2.26 2.26 2.26

CS 10 10 10.5 10.5

HD 20.25 20.25 20.25 20.25 Dwg.#

HP 40.5 40.5 45 45

UL # Stages: Engine Model: Date: GPM: RPM:

FM

CUL PSI:

Flange Rating: Max. Lift: HP:

125#

250#

2011 Pentair Pump Group, Inc.

Section 914 Page 206 Date September 2011


Supersedes Section 914 Page 206 Dated April 2006
S T

AURORA FIRE PUMPS


DIESEL DRIVEN VERTICAL TURBINE
CD CS MAXIMUM VERTICAL OFFSET IS .25 COUPLING GUARD U DIA CL DISCH HP (4) H DIA HOLES BASEPLATE TOP VIEW HD FACE OF DRIVE DISK

T S

B N

A
1/2 4 AN DIA HOLES CE F

DISCHARGE C

Mfg.

GEAR Ratio

AA

AB AB AF

CL OF ENGINE

Model

G NPT COOLING SUPPLY FOR ENG 3/4" NPT DRAIN NOMINAL COLUMN DIA

(O.A.L.)

NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. Reducers and/or increasers may be required to meet NFPA Pamphlet #20. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances.

CC CA

3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. Limited to maximum working pressure of 175 PSI 5. CD, CE & CS are dimensioned to face of drive disk.

Z MIN WATER LEVEL

Size & Model 12 FCM 13 FGH

# of Stages 3 4

BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Z Lube Only Lube Only 8 8 40 42-3/4 7 13 34 Total Stages Add 10-3/4 for each additional stage over 3 stages 8 10 61-13/16 65-1/4 11 13 34 Total Stages Add 13-1/16 for each additional stage over 4 stages

W Y 12 MIN

BOTTOM OF PIT

DISCHARGE HEADS & BASEPLATES Size BD 12 16-1/2 16-1/2 16-1/2 16-1/2 DISCH 6 SDH 8 SDC 8 LAD 6 LAD 6 SDH A 23 23 23 23 21-1/2 B 11-1/2 11-3/8 11-3/8 10-1/4 11-1/2 C 8-1/2 10 10 10 8-1/2 F 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 G 3/4 1 1 1 3/4 H 1 7/8 7/8 7/8 1 N 1-3/8 1-3/16 1-3/16 1-1/16 1-3/8 S 21-1/4 24 24 24 21-1/4 T 17-5/32 21 21 21 17-5/32 U 14-1/2 17-1/8 17-1/8 17-1/8 14-1/2

(4)

MODEL JU4HUF10 JU4HUF20 JU4HUF30 JU4HUF40 JU4HUF50 Customer: Job Name: Model: Engine Mfg.: Certified By:

AA 32 32 32 32 32

AB 15 15 15 15 15

AF 5 5 5 5 5

CLARKE JU4H DIESEL ENGINES AN CA CB CC 1x2 40 N/A 30 1x2 40 N/A 30 1x2 40 N/A 30 1x2 40 N/A 30 1x2 40 N/A 30 P.O.#:

CD 35.75 35.75 35.75 35.75 35.75

CE 2.26 2.26 2.26 2.26 2.26

CS 10 10 10.5 10.5 15.2

HD 20.25 20.25 20.25 20.25 20.25 Dwg.#

HP 40.5 40.5 45 45 45

UL # Stages: Engine Model: Date: GPM: RPM:

FM

CUL PSI:

Flange Rating: Max. Lift: HP:

125#

250#

2011 Pentair Pump Group, Inc.

AURORA FIRE PUMPS


DIESEL DRIVEN VERTICAL TURBINE
S T U DIA CL DISCH HP (4) H DIA HOLES BASEPLATE TOP VIEW HD CD

Section 914 Page 207 Date September 2011


Supersedes Section 914 Page 207 Dated May 2004
CS MAXIMUM VERTICAL OFFSET IS .25 COUPLING GUARD

FACE OF DRIVE DISK

T S

B N

A
1/2 4 AN DIA HOLES CE F

DISCHARGE C

AA

AB AB AF

CL OF ENGINE

G NPT COOLING SUPPLY FOR ENG 3/4" NPT DRAIN NOMINAL COLUMN DIA

(O.A.L.)

GEAR Mfg. Ratio Model

CC CA

NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. Reducers and/or increasers may be required to meet NFPA Pamphlet #20. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances.

3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. Limited to maximum working pressure of 175 PSI 5. CD, CE & CS are dimensioned to face of drive disk.

Z MIN WATER LEVEL

W Y 12 MIN

Size & Model 14 FGM 15 FGH

# of Stages 3 3

BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Lube Only Lube Only 8 10 44-15/16 49-1/4 13 14-3/4 Total Stages Add 12-3/16 for each additional stage over 3 stages 10 12 54-1/16 57-7/16 13 14-3/4 Total Stages Add 14-1/2 for each additional stage over 3 stages DISCHARGE HEADS & BASEPLATES

Z 36 34 - 2000 GPM 46 - 2500 GPM


BOTTOM OF PIT

Size BD 16-1/2 16-1/2 20 DISCH 8 SDC 8 LAD 10 LAD A 23 23 23 B 11-3/8 11-3/8 13-7/8 C 10 10 10-1/2 F 1-1/2 1-1/2 1-1/2 G 1 1 1 H 7/8 7/8 7/8 N 1-3/16 1-3/16 1-1/4 S 24 24 24 T 21 21 21 U 17-1/8 17-1/8 17-1/8 (4)

MODEL JU4HUF40 JU4HUF50 Customer: Job Name: Model: Engine Mfg.: Certified By:

AA 32 32

AB 15 15

AF 5 5

CLARKE JU4H DIESEL ENGINES AN CA CB CC 1x2 40 N/A 30 1x2 40 N/A 30 P.O.#:

CD 35.75 35.75

CE 2.26 2.26

CS 10.5 15.2

HD 20.25 20.25 Dwg.#

HP 45 45

UL # Stages: Engine Model: Date: GPM: RPM:

FM

CUL PSI:

Flange Rating: Max. Lift: HP:

125#

250#

2011 Pentair Pump Group, Inc.

Section 914 Page 208 Date September 2011


Supersedes Section 914 Page 208 Dated April 2006
S T U DIA CL DISCH

AURORA FIRE PUMPS


DIESEL DRIVEN VERTICAL TURBINE
CD CS MAXIMUM VERTICAL OFFSET IS .35 COUPLING GUARD FACE OF DRIVE DISK

HP (4) H DIA HOLES BASEPLATE TOP VIEW HD

B N

A
1/2 4 AN DIA HOLES CE F

DISCHARGE C

Mfg.

GEAR Ratio

AA

AB AB

CL OF ENGINE

Model
AF CC CA

G NPT COOLING SUPPLY FOR ENG 3/4" NPT DRAIN NOMINAL COLUMN DIA

(O.A.L.)

NOTES 1. Flange ratings are either 125# or 250# and will be designated in the 3. All bases are designed to have full contact with either grout certification block below for each order submittal. Reducers and/or or a soleplate grouted in place. increasers may be required to meet NFPA Pamphlet #20. 4. CD,CD & CS are dimensioned to face of drive disk. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances.

Z MIN WATER LEVEL

Size & Model 11 FGM 12 FCM

# of Stages 4 3

BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Z Lube Only Lube Only 6 8 44-13/16 47-9/16 9 11-1/2 34 Total Stages Add 9-1/2 for each additional stage over 4 stages 8 8 40 42-3/4 7 13 34 Total Stages Add 10-3/4 for each additional stage over 3 stages DISCHARGE HEADS & BASEPLATES

W Y 12 MIN

BOTTOM OF PIT

Size BD 12 16-1/2 DISCH 6 SDH 6 LAD A 23 23 B 11-1/2 10-1/4 C 8-1/2 10 F 1-1/2 1-1/2 G 3/4 1 H 1 7/8 N 1-3/8 1-1/16 S 21-1/4 24 T 17-5/32 21 U 14-1/2 17-1/8

MODEL JU6HUF30 JU6HUF50 JU6HUF60 Customer: Job Name: Model: Engine Mfg.: Certified By:

AA 32 32 32

AB 15 15 15

AF 5 5 5

CLARKE JU6H DIESEL ENGINES AN CA CB CC 1x2 46 N/A 36 1x2 46 N/A 36 1x2 46 N/A 36 P.O.#:

CD 45.9 45.9 48

CE .88 .88 .88

CS 15.2 15.2 15.2

HD 20.35 20.35 20.35 Dwg.#

HP 45.8 45.8 45.8

UL # Stages: Engine Model: Date: GPM: RPM:

FM

CUL PSI:

Flange Rating: Max. Lift: HP:

125#

250#

2011 Pentair Pump Group, Inc.

AURORA FIRE PUMPS


DIESEL DRIVEN VERTICAL TURBINE
S T U DIA CL DISCH HP (4) H DIA HOLES BASEPLATE TOP VIEW HD CD FACE OF DRIVE DISK

Section 914 Page 209 Date September 2011


Supersedes Section 914 Page 209 Dated May 2004
CS MAXIMUM VERTICAL OFFSET IS .35 COUPLING GUARD

B N

A
1/2 4 AN DIA HOLES CE F

DISCHARGE C

AA

AB AB

CL OF ENGINE

G NPT COOLING SUPPLY FOR ENG 3/4" NPT DRAIN NOMINAL COLUMN DIA

Mfg.

GEAR Ratio

AF

(O.A.L.)

Model

CC CA

NOTES 1. Flange ratings are either 125# or 250# and will be designated in the 3. All bases are designed to have full contact with either grout certification block below for each order submittal. Reducers and/or or a soleplate grouted in place. increasers may be required to meet NFPA Pamphlet #20. 4. Limited to maximum working pressure of 175 PSI 2. Not for construction, installation, or application purposes unless certified. 5. CD, CE & CS are dimensioned to face of drive disk. Dimensions shown are typical and may vary due to various tolerances. BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Lube Only Lube Only 8 10 61-13/16 65-1/4 11 13 Total Stages Add 13-1/16 for each additional stage over 4 stages 10 12 54-1/16 57-7/16 13 14-3/4 Total Stages Add 14-1/2 for each additional stage over 3 stages DISCHARGE HEADS & BASEPLATES Size BD 16-1/2 16-1/2 20 DISCH 8 SDC 8 LAD 10 LAD A 23 23 23 B 11-3/8 11-3/8 13-7/8 C 10 10 10-1/2 F 1-1/2 1-1/2 1-1/2 G 1 1 1 H 7/8 7/8 7/8 N 1-3/16 1-3/16 1-1/4 S 24 24 24 T 21 21 21

Z MIN WATER LEVEL

W Y 12 MIN

Size & Model 13 FGH 15 FGH

# of Stages 4 3

Z 34 34 - 2000 GPM 46 - 2500 GPM

BOTTOM OF PIT

U 17-1/8 17-1/8 17-1/8

(4)

MODEL JU6HUF30 JU6HUF50 JU6HUF60

AA 32 32 32

AB 15 15 15

AF 5 5 5

CLARKE JU6H DIESEL ENGINES AN CA CB CC 1x2 46 N/A 36 1x2 46 N/A 36 1x2 46 N/A 36

CD 45.9 45.9 48

CE .88 .88 .88

CS 15.2 15.2 15.2

HD 20.35 20.35 20.35

HP 45.8 45.8 45.8

Customer: Job Name: Model: Engine Mfg.: Certified By: # Stages: Engine Model:

P.O.#: UL GPM: RPM: Date: FM CUL PSI:

Dwg.# Flange Rating: Max. Lift: HP: 125# 250#

2011 Pentair Pump Group, Inc.

Section 914 Page 210 Date September 2011


Supersedes Section 914 Page 210 Dated May 2004
S T

AURORA FIRE PUMPS


DIESEL DRIVEN VERTICAL TURBINE
CD CS MAXIMUM VERTICAL OFFSET IS .35 COUPLING GUARD

T S

U DIA CL DISCH HP (4) H DIA HOLES BASEPLATE TOP VIEW HD

BARE FLYWHEEL

B N

A
1/2 4 AN DIA HOLES CE F

DISCHARGE C

AA

AB AB

CL OF ENGINE

Mfg.

GEAR Ratio

G NPT COOLING SUPPLY FOR ENG 3/4" NPT DRAIN

Model

AF CC CA

(O.A.L.)

NOMINAL NOTES COLUMN DIA 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. CD,CE & CS are dimensioned to bare flywheel. Z MIN WATER LEVEL

Size & Model 11 FGM 12 FCM

# of Stages 4 3

BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Z Lube Only Lube Only 6 8 44-13/16 47-9/16 9 11-1/2 34 Total Stages Add 9-1/2 for each additional stage over 4 stages 8 8 40 42-3/4 7 13 34 Total Stages Add 10-3/4 for each additional stage over 3 stages DISCHARGE HEADS & BASEPLATES

W Y 12 MIN

BOTTOM OF PIT

Size BD 16-1/2 DISCH 6 LAD A 23 B 10-1/4 C 10 F 1-1/2 G 1 H 7/8 N 1-1/16 S 24 T 21 U 17-1/8

MODEL JW6HUF30 JW6HUF50 JW6HUF60 Customer: Job Name: Model: Engine Mfg.: Certified By:

AA 36 36 36

AB 17 17 17

AF 5 5 5

CLARKE JW6H DIESEL ENGINES AN CA CB CC 1x2 46 N/A 36 1x2 46 N/A 36 1x2 46 N/A 36 P.O.#:

CD 47.52 47.52 47.52

CE 2.9 2.9 2.9

CS 14.1 14.1 14.1

HD 24 24 24 Dwg.#

HP 50.11 50.11 50.11

UL # Stages: Engine Model: Date: GPM: RPM:

FM

CUL PSI:

Flange Rating: Max. Lift: HP:

125#

250#

2011 Pentair Pump Group, Inc.

AURORA FIRE PUMPS


DIESEL DRIVEN VERTICAL TURBINE
S T U DIA CL DISCH HP (4) H DIA HOLES BASEPLATE TOP VIEW HD CD CS BARE FLYWHEEL

Section 914 Page 211 Date September 2011


Supersedes Section 914 Page 211 Dated May 2004

T S

MAXIMUM VERTICAL OFFSET IS .35

COUPLING GUARD

B N

A
1/2 4 AN DIA HOLES CE F

DISCHARGE C

AA

AB AB

CL OF ENGINE

Mfg.

GEAR Ratio

G NPT COOLING SUPPLY FOR ENG 3/4" NPT DRAIN NOMINAL COLUMN DIA

Model

AF CC CA

(O.A.L.)

NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. Limited to maximum working pressure of 175 PSI 5. CD, CE & CS are dimensioned to bare flywheel. BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Lube Only Lube Only 8 10 61-13/16 65-1/4 11 13 Total Stages Add 13-1/16 for each additional stage over 4 stages 8 10 44-15/16 49-1/4 13 14-3/4 Total Stages Add 12-3/16 for each additional stage over 3 stages DISCHARGE HEADS & BASEPLATES Size BD 16-1/2 16-1/2 20 DISCH 8 SDC 8 LAD 10 LAD A 23 23 23 B 11-3/8 11-3/8 13-7/8 C 10 10 10-1/2 F 1-1/2 1-1/2 1-1/2 G 1 1 1 H 7/8 7/8 7/8 N 1-3/16 1-3/16 1-1/4 S 24 24 24 T 21 21 21

Z MIN WATER LEVEL

W Y 12 MIN

Size & Model 13 FGH 14 FGM

# of Stages 4 3

Z 34 36
BOTTOM OF PIT

U 17-1/8 17-1/8 17-1/8

(4)

MODEL JW6HUF30 JW6HUF40 JW6HUF50 JW6HUF60 Customer: Job Name: Model: Engine Mfg.: Certified By:

AA 36 36 36 36

AB 17 17 17 17

AF 5 5 5 5

CLARKE JW6H DIESEL ENGINES AN CA CB CC 1x2 46 N/A 36 1x2 46 N/A 36 1x2 46 N/A 36 1x2 46 N/A 36 P.O.#:

CD 49.4 49.4 49.4 49.4

CE 4.6 4.6 4.6 4.6

CS 19.7 19.7 19.7 19.7

HD 24 24 24 24 Dwg.#

HP 50.1 50.1 50.1 50.1

UL # Stages: Engine Model: Date: GPM: RPM:

FM

CUL PSI:

Flange Rating: Max. Lift: HP:

125#

250#

2011 Pentair Pump Group, Inc.

Section 914 Page 212 Date September 2011


Supersedes Section 914 Page 212 Dated May 2004
S T

AURORA FIRE PUMPS


DIESEL DRIVEN VERTICAL TURBINE
CD CS MAXIMUM VERTICAL OFFSET IS .35 COUPLING GUARD U DIA CL DISCH HP (4) H DIA HOLES BASEPLATE TOP VIEW HD BARE FLYWHEEL

T S

B N

A
1/2 4 AN DIA HOLES CE F

DISCHARGE C

Mfg.

GEAR Ratio

AA

AB AB AF

CL OF ENGINE

Model

G NPT COOLING SUPPLY FOR ENG 3/4" NPT DRAIN NOMINAL COLUMN DIA

(O.A.L.)

CC

NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. CD, CE & CS are dimensioned to bare flywheel.

CA

Z MIN WATER LEVEL

Size & Model 15 FGH

# of Stages 3 2

BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others Lube Only Lube Only 10 12 54-1/16 57-7/16 Total Stages 12 Total Stages N/A

12 MIN

W 13

Y 14-3/4

Z 34 - 2000 GPM 46 - 2500 GPM


BOTTOM OF PIT

19 FGM

Add 14-1/2 for each additional stage over 3 stages 47-5/8 N/A 12 23-1/2 32 Add 17-5/8 for each additional stage over 2 stages

DISCHARGE HEADS & BASEPLATES Size BD 20 24-1/2 DISCH 10 LAD 12 SDH A 23 28 B 13-7/8 17 C 10-1/2 13-1/2 F 1-1/2 2 G 1 3/4 H 7/8 1-1/8 N 1-1/4 1-7/8 S 24 32-1/4 T 21 26-5/32 U 17-1/8 24-1/2

MODEL JW6HUF30 JW6HUF40 JW6HUF50 JW6HUF60 Customer: Job Name: Model: Engine Mfg.: Certified By:

AA 36 36 36 36

AB 17 17 17 17

AF 5 5 5 5

CLARKE JW6H DIESEL ENGINES AN CA CB CC 1x2 46 N/A 36 1x2 46 N/A 36 1x2 46 N/A 36 1x2 46 N/A 36 P.O.#:

CD 49.4 49.4 49.4 49.4

CE 4.6 4.6 4.6 4.6

CS 19.7 19.7 19.7 19.7

HD 24 24 24 24 Dwg.#

HP 50.1 50.1 50.1 50.1

UL # Stages: Engine Model: Date: GPM: RPM:

FM

CUL PSI:

Flange Rating: Max. Lift: HP:

125#

250#

2011 Pentair Pump Group, Inc.

Section 914 Page 213 Date April 2006


Supersedes Section 914 Page 213 Dated May 2004

THIS PAGE LEFT INTENTIONALLY BLANK

2011 Pentair Pump Group, Inc.

Section 914 Page Date April 2006

214

Supersedes Section 914 Page 214 Dated May 2004

THIS PAGE LEFT INTENTIONALLY BLANK

2011 Pentair Pump Group, Inc.

Section 914 Page 215 Date April 2006


Supersedes Section 914 Page 215 Dated May 1, 2004

THIS PAGE LEFT INTENTIONALLY BLANK

2011 Pentair Pump Group, Inc.

Section 914 Page 216 Date April 2006


Supersedes Section 914 Page 216 Dated May 1, 2004

THIS PAGE LEFT INTENTIONALLY BLANK

2011 Pentair Pump Group, Inc.

Section 000 Page 217 Section 914 Page 217 XXXX Date Xxxxx 2006 Date April
Supersedes Section 000 Page 217 Supersedes Section 914 Page 217 Dated XXXXXXXXXXXXXXXXXX Dated May 1, 2004

THIS PAGE LEFT INTENTIONALLY BLANK

2011 Pentair Pump Group, Inc.

Section 914 Page 218 Date April 2006


Supersedes Section 914 Page 218 Dated May 1, 2004

THIS PAGE LEFT INTENTIONALLY BLANK

2011 Pentair Pump Group, Inc.

Section 914 Page 219 Date April 2006


Supersedes Section 914 Page 219 Dated May 2004

THIS PAGE LEFT INTENTIONALLY BLANK

2011 Pentair Pump Group, Inc.

Section 914 Page Date April 2006

220

Supersedes Section 914 Page 220 Dated May 2004

THIS PAGE LEFT INTENTIONALLY BLANK

2011 Pentair Pump Group, Inc.

Section 914 Page 221 Date April 2006


Supersedes Section 914 Page 221 Dated May 2004

THIS PAGE LEFT INTENTIONALLY BLANK

2011 Pentair Pump Group, Inc.

Section 914 Page 222 Date February 2008


Supersedes Section 914 Page 222 Dated May 2004
S T U DIA CL DISCH HP (4) H DIA HOLES BASEPLATE TOP VIEW HD

AURORA FIRE PUMPS


DIESEL DRIVEN VERTICAL TURBINE
CD

FACE OF DRIVE FLANGE MAINTAIN MINIMUM ANGLE OF 1 - 1-1/2 COUPLING GUARD

B N

A
1/2 6 (TYP) AB AB 8 AN DIA HOLES CE F

DISCHARGE C

AA

CL OF ENGINE

GEAR Mfg. Ratio Model


3

G NPT COOLING SUPPLY FOR ENG CB 3/4" NPT DRAIN NOMINAL COLUMN DIA

AF

CB

CC CA

(O.A.L.)

NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. Limited to maximim working pressure of 175 PSI. 5. CD, CD & shafting length are dimensioned to face of drive flange. BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Z Lube Only Lube Only 8 8 40 42-3/4 7 13 34 Total Stages Add 10-3/4 for each additional stage over 3 stages 8 10 61-13/16 65-1/4 11 13 34 Total Stages Add 13-1/16 for each additional stage over 4 stages DISCHARGE HEADS & BASEPLATES Size BD 16-1/2 16-1/2 16-1/2 DISCH 6 LAD 8 SDC 8 LAD A 23 23 23 B 10-1/4 11-3/8 11-3/8 C 10 10 10 F 1-1/2 1-1/2 1-1/2 G 1 1 1 H 7/8 7/8 7/8 N 1-1/16 1-3/16 1-3/16 S 24 24 24

Z MIN WATER LEVEL

W Y 12 MIN

Size & Model 12 FCM 13 FGH

# of Stages 3 4

BOTTOM OF PIT

T 21 21 21

U 17-1/8 17-1/8 17-1/8

(4)

MODEL 3406DIT Customer: Job Name: Model: Motor Mfg.: Certified By:

AA 28-1/2

AB 10-1/4

AF 10-3/4

CATERPILLAR DIESEL ENGINES AN CA CB 13/16 76 16-3/4

CC 16-3/4 P.O.#:

CD 78-5/8

CE 15-1/8

HD 19-1/2

HP 34-3/4 Dwg.#

UL # Stages: HP: Frame: Date: GPM: Ph:

FM

CUL PSI: Hz: V:

Flange Rating: Max. Lift: Encl.:

125#

250#

2011 Pentair Pump Group, Inc.

AURORA FIRE PUMPS


DIESEL DRIVEN VERTICAL TURBINE
S T U DIA CL DISCH HP (4) H DIA HOLES BASEPLATE TOP VIEW HD CD

Section 914 Page 223 Date February 2008


Supersedes Section 914 Page 223 Dated May 2004

FACE OF DRIVE FLANGE MAINTAIN MINIMUM ANGLE OF 1 - 1-1/2 COUPLING GUARD

B N

A
1/2 6 (TYP) AB AB 3 AF CB CC CA CB 8 AN DIA HOLES CE F

DISCHARGE C

Mfg.

GEAR Ratio

AA

CL OF ENGINE

Model

G NPT COOLING SUPPLY FOR ENG 3/4" NPT DRAIN NOMINAL COLUMN DIA

(O.A.L.)

NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. Limited to maximum working pressure of 175 PSI. 5. CD, CE & shafting length are dimensioned to face of drive flange. 6. When used with a 17FGM, U=19 (483). BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Lube Only Lube Only 8 10 44-15/16 49-1/4 13 14-3/4 Total Stages Add 12-3/16 for each additional stage over 3 stages 10 12 54-1/16 57-7/16 13 14-3/4 Total Stages 12 Total Stages N/A Add 14-1/2 for each additional stage over 3 stages 49-7/8 N/A 9 18 Add 13-1/2 for each additional stage over 3 stages

Z MIN WATER LEVEL

W Y 12 MIN

Size & Model 14 FGM 15 FGH

# of Stages 3 3 3

Z 30 34 - 2000 GPM 46 - 2500 GPM 28


BOTTOM OF PIT

17 FGM

DISCHARGE HEADS & BASEPLATES Size BD 16-1/2 16-1/2 20 DISCH 8 SDC 8 LAD 10 LAD A 23 23 23 B 11-3/8 11-3/8 13-7/8 C 10 10 10-1/2 F 1-1/2 1-1/2 1-1/2 G 1 1 1 H 7/8 7/8 7/8 N 1-3/16 1-3/16 1-1/4 S 24 24 24 T 21 21 21 U 17-1/8 17-1/8 17-1/8 (4) (6)

MODEL 3406DIT 3406DITA Customer: Job Name: Model: Motor Mfg.: Certified By:

AA 28-1/2 28-1/2

AB 10-1/4 10-1/4

AF 10-3/4 10-3/4

CATERPILLAR DIESEL ENGINES AN CA CB 13/16 76 16-3/4 13/16 76 16-3/4

CC 16-3/4 16-3/4 P.O.#:

CD 78-5/8 78-5/8

CE 15-1/8 15-1/8

HD 19-1/2 19-1/2

HP 32-3/4 35-1/8 Dwg.#

UL # Stages: HP: Frame: Date: GPM: Ph:

FM

CUL PSI: Hz: V:

Flange Rating: Max. Lift: Encl.:

125#

250#

2011 Pentair Pump Group, Inc.

Section 914 Page 224 Date February 2008


Supersedes Section 914 Page 224 Dated May 2004
S T U DIA CL DISCH

AURORA FIRE PUMPS


DIESEL DRIVEN VERTICAL TURBINE
CD FACE OF DRIVE FLANGE MAINTAIN MINIMUM ANGLE OF 1 - 1-1/2 COUPLING GUARD

HP (4) H DIA HOLES BASEPLATE TOP VIEW HD

B N

A
1/2 6 (TYP) AB AB 8 AN DIA HOLES CE F

DISCHARGE C

Mfg.

GEAR Ratio

AA

CL OF ENGINE

Model
3 AF CB CC CA CB

G NPT COOLING SUPPLY FOR ENG 3/4" NPT DRAIN NOMINAL COLUMN DIA

(O.A.L.)

NOTES 1. Flange ratings are either 125# or 250# and will be designated in the certification block below for each order submittal. 2. Not for construction, installation, or application purposes unless certified. Dimensions shown are typical and may vary due to various tolerances. 3. All bases are designed to have full contact with either grout or a soleplate grouted in place. 4. CD, CD & shafting length are dimensioned to face of drive flange.

Z MIN WATER LEVEL

Size & Model 19 FGM 19 FGH

# of Stages 2 2

BOWL ASSEMBLY, COLUMN & SHAFTING Nominal Column Dia. V UL & FM Water All Others UL & FM Water All Others W Y Z Lube Only Lube Only 12 N/A 47-5/8 N/A 12 23-1/2 32 Total Stages Add 17-5/8 for each additional stage over 2 stages 12 N/A 47-5/8 N/A 12 23-1/2 32 Total Stages Add 17-5/8 for each additional stage over 2 stages DISCHARGE HEADS & BASEPLATES

W Y 12 MIN

BOTTOM OF PIT

Size BD 24-1/2 DISCH 12 SDH A 28 B 17 C 13-1/2 F 2 G 3/4 H 1-1/8 N 1-7/8 S 32-1/2 T 26-5/32 U 24-1/2

MODEL 3406DITA 3408DITA 3412DIT 3412DITA Customer: Job Name: Model: Motor Mfg.: Certified By:

AA 28-1/2 RTF RTF RTF

AB 10-1/4 RTF RTF RTF

AF 10-3/4 RTF RTF RTF

CATERPILLAR DIESEL ENGINES AN CA CB 13/16 76 16-3/4 RTF RTF RTF RTF RTF RTF RTF RTF RTF

CC 16-3/4 RTF RTF RTF P.O.#:

CD 78-5/8 RTF RTF RTF

CE 15-1/8 RTF RTF RTF

HD 19-1/2 RTF RTF RTF

HP 35-1/8 RTF RTF RTF Dwg.#

UL # Stages: HP: Frame: Date: GPM: Ph:

FM

CUL PSI: Hz: V:

Flange Rating: Max. Lift: Encl.:

125#

250#

2011 Pentair Pump Group, Inc.