S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programmes (PEMP)
Application of QFD and Value Engineering Concepts in Product Development of Commercial Ventilation System Exhaust Hood
M.Sc [Engg.] Dissertation in Engineering and Manufacturing Management
N.A.Mohan
Envirotech Engineering & Systems, Pondicherry
March-2011
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Certificate
This is to certify that the M.Sc (Engg) Project Dissertation titled Application of QFD and Value engineering concepts in product development of commercial ventilation system exhaust hood is a bonafide record of the Project work carried out by Mr.A.Pranava Audithan Reg.No. BUB0908001 in partial fulfilment of requirements for the award of M.Sc (Engg) Degree of Coventry University in Engineering and Manufacturing Management. March-2011 Mr.N.Sandeep Assistant Professor Academic Supervisor
MSRSAS
Dr.N.S.Mahesh
HOD (MME) MSRSAS
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
ii
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Declaration
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
The Project Dissertation is submitted in partial fulfilment of academic requirements for M.Sc (Engg) Degree of Coventry University in Engineering and Manufacturing Management. This dissertation is a result of my own investigation. All sections of the text and results, which has been obtained from other sources, are fully referenced. I understand that cheating and plagiarism constitute a breach of University regulations and will be dealt with accordingly.
Registration No:
BUB0908001
Date:
30-03-2011
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
iii
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Acknowledgement
I would like to first acknowledge Envirotech for their support to accomplish this work. My experience was richly rewarding, fun and insightful and I owe a lot to the people who made my project possible. I want to especially thank Mr.N.A.Mohan (Proprietor, Envirotech Engineering and Systems) for creating the project and giving me an opportunity to work for Envirotech.
My highest regard of appreciation and deepest gratitude to Mr. N.Sandeep Assistant Professor, MSRSAS for his continuous motivation and guidance not only during the project but throughout the entire academic semesters. His dedication, keenness and thought provocations pushed me to put my level best into the project. I wish to extend my whole hearted thankfulness to Dr.N.S.Mahesh, HOD - MME, MSRSAS for his timely reviews, monitoring and guidance throughout the project. I wish to extend my sincere gratitude to all the faculty members of Centre for Manufacturing, MSRSAS: Dr.K.Gnanamurthy, Professor.V.G.S Mani, Professor.B.S.Ajithkumar,
Professor.Ramadas Chandrasekhar, Assistant Professor Ganapathi and Mr. Vijay Kumar for the valuable and effective teachings imparted during the academic modules.
Finally, none of this would have been possible without the love and support of my family. I thank them for their never ending encouragement, patience and sacrifices.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
iv
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Abstract
In an increasingly intense competitive environment, it is of paramount importance for organizations to achieve highly efficient products, low costs and high customer service level to survive. Value engineering provides an organization with the tools that improves its ability to plan, implement and control its activities as well as the ways in which organization uses its resources in an effective and productive manner. In this project, attempt has been made to apply the concepts of Value engineering and Quality function deployment, in product development of Commercial Ventilation Exhaust hood. The selected product datas were gathered and studied in the information phase. Brainstorming and Quality function deployment were carried out to identify the problems. The selected ventilation principles were applied in the new concept of the Capture jet Kitchen Exhaust hood and Cyclonic grease filters. The newly designed concepts were modelled in 3 dimension using CATIA and the meshing was carried out using Star CCM commercial CFD solver. For inlet, four mass flow rates (0.5, 1, 3, 5 kg/s) were imposed using the fixed mass inlet boundary condition. The value of density (1.2 kg/m ), total pressure (1 atm) and turbulence intensity (5%) were specified at the inlet boundary. For outlet, outflow boundary condition was imposed with Pressure outlet (3bar). No slip boundary condition was applied on all wall surfaces. For main filter media, porous media boundary was imposed with pi = 2500 and pv= 3000. Whole domain was considered at 1 atm and at 298K as initial condition. Based on the Capture and containment analysis done for the Exhaust only hood and Capture jet model hoods, the capture jet model was 50% more efficient and air flow rates are 30% lower than those of an exhaust-only hood system. The need for replacement air is reduced as well. The capture jet model is not only saving energy but also improves productivity by providing a comfortable thermal environment.
3
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Table of Contents
Certificate...........................................................................................................................ii Declaration........................................................................................................................ iii Acknowledgement .............................................................................................................iv Abstract ...............................................................................................................................v Table of Contents ..............................................................................................................vi List of Figures ....................................................................................................................ix 1 Introduction ..................................................................................................................1 1.1 Commercial Kitchen Ventilation Systems .................................................................1 1.2 Company background .................................................................................................2 2 Background Theory .....................................................................................................4 2.1 Commercial Kitchen Ventilation System...................................................................4 2.2 Value engineering/ Value analysis ..............................................................................5 2.3 Computational Fluid Dynamics ..................................................................................6 3 Literature Review ........................................................................................................8 3.1 Quality function deployment ......................................................................................8 3.2 Value engineering.........................................................................................................9 3.3 Kitchen Ventilation ....................................................................................................10 3.4 Summary of Literature Review ................................................................................12 4 Problem Definition .....................................................................................................13 4.1 Problem Statement.....................................................................................................13 4.2 Objectives....................................................................................................................13 4.3 Methodology ...............................................................................................................14 5 Data Collection and Analysis ....................................................................................15 5.1 Flow Chart ..................................................................................................................15 5.1.1 Pre- workshop study ...............................................................................................15 5.1.2 Workshop Study......................................................................................................16
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
vi
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
5.1.3 Post Workshop Study .............................................................................................16 5.2 Information phase ......................................................................................................16 5.2.1 Product Data............................................................................................................16 5.2.2 House of Quality......................................................................................................17 5.3 Functional analysis.....................................................................................................17 5.3.1 Ventilation Principle Mixing Ventilation system ..............................................17 5.3.2 Exhaust Hood ..........................................................................................................19 5.3.3 Baffle filters .............................................................................................................20 5.4 Creative phase ............................................................................................................21 5.4.1 Ventilation principle Thermal Displacement Ventilation ................................ 21 5.4.2 Combined Exhaust Hoods and Supply Inlets .......................................................22 5.4.3 Air jets ......................................................................................................................24 5.4.4 Cyclone filters ..........................................................................................................24 5.5 Evaluation Phase ........................................................................................................26 6 Problem solving ..........................................................................................................27 6.1. Development Phase ...................................................................................................27 6.2 Concept generation ....................................................................................................27 6.2 Working of Capture jet hood Concept ....................................................................28 6.3 Working of Cyclonic grease filter concept ..............................................................29 7 Results and Discussions .............................................................................................30 7.1. GEOMETRY MODEL.............................................................................................30 7.1.1 CFD MESHING ......................................................................................................31 7.1.2 CFD MODEL DESCRIPTION .............................................................................32 7.1.3. GOVERNING EQUATIONS ...............................................................................33 7.1.4 BOUNDARY CONDITIONS .................................................................................34 7.2 Results and discussions ..............................................................................................34 7.2.1 Residual plot ............................................................................................................41 7.2.2 Capture efficiency vs. inlet airflow ........................................................................43 7.2.2 Heat gain vs. air flow ..............................................................................................43
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
vii
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
viii
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
List of Figures
Figure 1. 1 kitchen ventilation system ................................................................................. 2 Figure 1. 2 various kitchen equipments ............................................................................... 3
Figure 2. 1 styles of commercial kitchen exhaust hoods [7]................................................ 5 Figure 2. 2- examples of CFD applications [10].................................................................. 7
Figure 5. 1 flow chart of value engineering ....................................................................... 15 Figure 5. 2 house of quality (QFD) .................................................................................... 17 Figure 5. 3 typical mixing ventilation [13] ........................................................................ 18 Figure 5. 4 Wall mounted canopy[7] ................................................................................. 20 Figure 5. 5 Baffle filter ...................................................................................................... 21 Figure 5. 6 Displacement Ventilation[13] ......................................................................... 22 Figure 5. 7 Schematic diagram of trajectories[13]............................................................. 25 Figure 5. 8 collection efficiency curve of a cyclone[13] ................................................... 25 Figure 6. 1 capture jet exhaust hood .................................................................................. 27 Figure 6. 2 capture jet exhaust hood concept ..................................................................... 27 Figure 6. 3 Working of Capture jet exhaust hood concept ................................................ 28 Figure 6. 4 Working of Cyclonic grease filter concept ...................................................... 29 Figure 7. 1 Capture jet hood model ................................................................................... 30 Figure 7. 2 Normal exhaust hood model. ........................................................................... 30 Figure 7. 3 Filter in Capture jet .......................................................................................... 31 Figure 7. 4 Filter in Normal Exhaust Hood ....................................................................... 31 Figure 7. 5 Volume Tetrahedral mesh ............................................................................... 32 Figure 7. 6 Volume Polyhedral Mesh ................................................................................ 32 Figure 7. 7 Velocity at outlet section ................................................................................. 34 Figure 7. 8 Velocity at inlet section (circulations @inlet) ................................................. 35
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
ix
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Figure 7. 9 velocity vector plot .......................................................................................... 35 Figure 7. 10 Pressure contour of Whole hood ................................................................... 36 Figure 7. 11 Pressure contour of filter ............................................................................... 36 Figure 7. 12 Pressure contour of exhaust section .............................................................. 37 Figure 7. 13 Pressure contour of intake section ................................................................. 37 Figure 7. 14 Pressure contour of hood ............................................................................... 38 Figure 7. 15 Pressure contour of section ............................................................................ 38 Figure 7. 16 Temperature contour of section ..................................................................... 39 Figure 7. 17 Vortices contours ........................................................................................... 39 Figure 7. 18 Temperature contour of exahust section........................................................ 40 Figure 7. 19 Conduction heat flux contours....................................................................... 41 Figure 7. 20 Residual plot of Capture jet model ................................................................ 41 Figure 7. 21 Residual plot of Exhaust hood model............................................................ 42 Figure 7. 22 Capture efficiency vs inlet airflow ................................................................ 43 Figure 7. 23 heat gain vs air flow ...................................................................................... 44
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programmes (PEMP)
1 Introduction
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Figure 1.1 displays a typical wall mounted exhaust hood with baffle filters.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
2 Background Theory
2.1 Commercial Kitchen Ventilation System
Kitchen ventilation is a complex application of HVAC systems. System design includes aspects of air conditioning, fire safety, ventilation, building pressurization, refrigeration, air distribution, and food service equipment. Kitchens are in many buildings, including restaurants, hotels, hospitals, retail malls, single- and multifamily dwellings, and correctional facilities. Each building type has special requirements for its kitchens, but many basic needs are common to all. Kitchen ventilation has at least two purposes: To provide a comfortable environment in the kitchen and To enhance the safety of personnel working in the kitchen and of other building occupants. Comfort criteria often depend on the local climate, because some kitchens are not air conditioned. The ventilation system can also affect the acoustics of a kitchen. Kitchen ventilation enhances safety by removing combustion products from gas- or solid-fuelled equipment. The centrepiece of almost any kitchen ventilation system is an exhaust hood, used primarily to remove cooking effluent from kitchens. Effluent includes gaseous, liquid, and solid contaminants produced by the cooking process, and may also include products of fuel and even food combustion. These contaminants must be removed for both comfort and safety; effluent can be potentially life-threatening and, under certain conditions, flammable. The arrangement of food service equipment and its coordination with the hood(s) greatly affect kitchen operating costs. HVAC system designers are most frequently involved in commercial kitchen applications, in which cooking effluent contains large amounts of grease or water vapour. Residential kitchens typically use a totally different type of hood. The amount of grease
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
produced in residential applications is significantly less than in commercial applications, so the health and fire hazard is much lower. [7]
Figure 2.1 shows the various styles of commercial kitchen exhaust hoods.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
is unnecessary. This unintentional cost is the result of habits, attitudes, and all other human factors. Value engineering originated at General Electric Company in 1947. Harry Erlicher, Vice-President of Purchases, noted that during wartime, it was frequently necessary to make substitutions for critical materials that not only satisfied the required functions but also had better performance and lower cost. He reasoned that if it was possible to do this in wartime, it might be possible to develop a system that could be applied to normal operations to increase the companys efficiency and profit. L. D. Miles was assigned to study the possibility, and the result was a systematic approach to problem solving based on functional performance, which he called value analysis. Value analysis, value engineering, value management, value assurance, and value control are all the same in that they make use of the same set of techniques developed by Miles in 1947. In many cases, the title tends to describe how the system is being applied. Value analysis is applied to remove cost from a product. Value engineering and value assurance are applied in the development phase to keep cost out of a product. Value management and value control are overall programs that apply value techniques in business operations. Value engineering was first applied in product development, manufacturing, and the construction industry, and in the 1970s, value engineering began to be applied in the service industry. David Reeves case study (1974, 1978) on youth service bureaus was among the first successful case studies in a service organization. Since then, successful value engineering service case studies have been reported in retail, finance, health care, photo shops, and many other areas. [11]
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Stokes equations, have been known for over 150 years. However, the development of reduced forms of these equations is still an active area of research, in particular, the turbulent closure problem of the Reynolds- averaged Navier- Stokes equations. For nonNewtonian fluid dynamics, chemically reacting flows and two phase flows, the theoretical development is at less advanced stage. Experimental methods has played an important role in validating and exploring the limits of the various approximations to the governing equations, particularly wind tunnel and rig tests that provide a cost-effective alternative to full-scale testing. The flow governing equations are extremely complicated such that analytic solutions cannot be obtained for most practical applications. Computational techniques replace the governing partial differential equations with systems of algebraic equations that are much easier to solving using computers. The steady improvement in computing power, since the 1950s, thus has led to emergence of CFD. This branch of fluid dynamics complements experimental and theoretical fluid dynamics by providing alternative potentially cheaper means of testing fluid flow systems. It also can allow for the testing of conditions which are not possible or extremely difficult to measure experimentally and are not amenable to analytic solutions. [12] Figure 2.2 shows a few examples of aerodynamic applications of CFD.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Lin Chih cheng (2003) interpreted the QFD methodological characteristics in a structured manner and he further offers a guide for intervention in product development systems in organisations. This paper is a product of an action research program on implementing the QFD method into product development systems in Brazilian industrial organisations. This work on application of QFD in product development is encapsulated by the conciliation of the binomial theory practice, through bi-directional movement of reinforcing one another good understanding of methodological theory leading to effective practice and concurrently, good understanding of methodological theory leading to effective practice continuously generating or refining existing methodological theory. The author believes that the accumulation of knowledge of QFD comes in three interrelated forms: 1. Refinement of its methodological basis 2. Refinement of operating guides, procedures and rules 3. Construction of models of reference applications. This paper aims at the first two forms. [2]
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Biren Prasad (1998) has extended the initial idea of combining market research data with QFD to include value engineering. By integrating Technical importance ratings (TIR) and Customer importance ratings (CIR) with value engineering and value graphs, product designers can obtain priorities (relative preferences) on QC functions. The author has developed a template which can be used for carrying out the following value-based synthesis: 1. Assess how an organisation perceives its product ranks relative to competitor (technical competitive assessment). 2. Prioritize ratings that identify relative importance of each of the product solutions (quality characteristics). 3. Prioritize how a competitors product performs relative to each of the chosen quality characteristics (benchmark data).
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
4. Compute weighed sum of QCS with respect to both the customer preferences and those based on value engineering. [4]
Fabio et.al (2004), evaluated the integrated use of the QFD and VA tools by employing a structured methodology in a survey that was carried out to reveal consumers requirements concerning a sports bicycle. The quality function deployment with value analysis (QFVA) is the new tool obtained from the fusion of the QFD and the VA. The QFVA aims at fulfilling consumer requirements and supplying financial decision parameters that are based on company formal engineering terms. First this method quantifies and qualifies each one of the implicit and explicit requirements acquired. Then it arranges them as unique engineering requirements with their interrelationship, fulfilling all the consumer requirements according to their ranking. This kind of analysis is more appropriate when a consumer of a certain product becomes more exigent and critical of the products. That is when the differentiation level of a product matters to the consumer. [5]
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
10
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Delivering untempered makeup air into a kitchen on a hot summer day may result in temperature rise in a kitchen 10F (5.5C) and higher above the comfort level. Such a high temperature may result in 30% productivity loss of kitchen personnel. Thermal Displacement Ventilation cooled the kitchen space more effectively than the mixing ventilation system. The CFD simulation results demonstrate up to 10F (5.5C) lower temperature in the kitchen when the mixing air distribution system was replaced with a Thermal Displacement Ventilation system having the same cooling capacity. [8]
Risto et.al (2003) has evaluated the influence of a capture jet in a ventilated ceiling and has found that it is possible to improve the total effectiveness of the ventilation system. This means better indoor air quality and thermal comfort. In addition, the energy consumption of a capture jet ceiling is lower than that of a traditional ceiling concept. This paper demonstrates that the supply air distribution strategy has a remarkable influence on pollution removal effectiveness and the thermal environment in kitchens. For a ventilated ceiling, the capture jet could improve the total effectiveness of the ventilation system by reducing the average contaminant level in the occupied zone by 40 %. In addition the estimated energy saving potential can be as much as 23 %. Based on this study, the capture efficiency is not improved after a certain level of exhaust air flow rate, even if flow rates are increased. Therefore, the main point is to optimise the requested exhaust air flow rate and to adjust it for the existing convective load of kitchen appliances. The amount of air carried in a convective plume should be theoretically calculated and adjusted by matching the exhaust air flow rate. [9]
Risto et.al (2003) has derived a capture efficiency model and it is used to estimate the efficiency of a ventilated ceiling. This paper demonstrates that a simple equation that includes the average contaminant level in the occupied zone and the exhaust concentration could be a suitable platform for capture efficiency analysis in both measurements and simulations. With a ceiling height of 2.3 m, the capture and containment efficiency can be as high as 85 - 90 %; with a 2.6 m ceiling height it is 80
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
11
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
85 %. These values are quite reasonable compared with the capture efficiency of a default hood in the German code of practice (VDI, 1984). [10]
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
12
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
4 Problem Definition
In an increasingly intense competitive environment, it is of paramount importance for organizations to achieve quality products, low costs and high customer service level to survive. The aim of both value analysis (VA) and quality function deployment (QFD) is to reduce waste by avoiding redesign and providing optimal location of costs in general. To satisfy the consumers most important needs, the VA prioritizes the increase in the cost of the product and not the subsequent price rise. QFD aims at generating clear engineering needs from consumer requirements thus, minimizing the re-projecting cost (cost should read waste) and changes in the products. [5] In Envirotech there is tremendous pressure to relook at designs, engineering practices and processes which are decades older. Globalisation has enabled customers to access any product in the world without any barriers. So it has become extremely important to provide products with the best quality at lowest cost and after sales service. Envirotech is facing lots of difficulties as new companies are entering into commercial ventilation business. Increasing competition and increasing raw material costs, higher taxes and higher wages are increasing price so it is of ultimate necessity to innovate in order to stand out of the crowd.
4.2 Objectives
Survey the literature on implementation of QFD and VE concepts in product development and manufacturing industries.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
13
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Analyze current design techniques and manufacturing processes of the selected product. Identify the benefits of implementing QFD and VE techniques in terms of functioncost-worth with regards to the selected product. Propose modifications based on the outcomes. Implement the outcomes in the selected product development and measure the benefits in new design (Prototype).
4.3 Methodology
Literature survey on QFD and Value engineering concepts and various methods for successful implementation. Understanding how the VE concepts can be applied to product development process by referring journals, books, manuals and related documents Collecting information regarding materials, functionality and processes involved in the selected product. Plotted the VE job plan to schedule selection of product, identifying problem, setting goals etc. Used QFD, brainstorming techniques to identify the opportunities for improvements. CFD analysis was carried out to identify the benefits. Prototype exhaust hoods were fabricated to check for desired function Measuring the benefits in terms of functional quality and cost.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
14
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
15
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
5.1.2 Workshop Study Workshop study is the phase where value addition will be very high as compared to any other phases. This phase is systematically divided into 6 parts as following. Information: All possible data needed to proceed with the project is collected Functional analysis: Product or process is analysed for its function, cost and performance Creative: This stage provides a major contribution to the project where actual work is done in several iterations until the desired result is achieved. Evaluation: Affect of ideas on project cost of performance, selection and prioritization of ideas for developments. Development: Cost benefit analysis, develop action plan for implementing steps. Presentation: Prepare presentation and supportive documents; give the comparison of costs, functions and benefits of new VE model. 5.1.3 Post Workshop Study This stage is more related to the implementation activity where action plans are established, continuous follow up is done to monitor the status of the project, track achievements etc.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
16
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Figure 5.2 shows the house of quality built based on the Quality function deployment carried out to analyse the voice of the customer. Based on the House of quality the functionality tops the priority of the customers followed by reliability and serviceability.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
17
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
it mixes with the warmer air at the ceiling. Figure 5.3 shows typical mixing ventilation. [13]
Advantages of Mixing Ventilation: This type of ventilation allows heat recovery and preheating of supply air. Supply air is targeted to occupied zones, while air is extracted room polluted zone Absence of high suction pressures reduces the risk of backdraughting as well as the entry of radon or soil gas. Filtration of the incoming air is possible. Disadvantages of Mixing Ventilation: Two systems are present, thus doubling installation and operational costs. The systems have been shown to require regular long term maintenance. For correct operation, these systems must be installed in airtight enclosures. This reduces safety margins if the system fails to operate correctly or if the occupant unwittingly introduces high polluting sources into the building. [13]
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
18
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
5.3.2 Exhaust Hood The centrepiece of almost any kitchen ventilation system is an exhaust hood, used primarily to remove cooking effluent from kitchens. Effluent includes gaseous, liquid, and solid contaminants produced by the cooking process, and may also include products of fuel and even food combustion. These contaminants must be removed for both comfort and safety; effluent can be potentially life-threatening and, under certain conditions, flammable. The arrangement of food service equipment and its coordination with the hood(s) greatly affect kitchen operating costs. Hood Types Many types, categories, and styles of hoods are available, and selection depends on many factors. Hoods are classified by whether they are designed to handle grease; Type I hoods are designed for removing grease and smoke, and Type II are not. Model codes distinguish between grease-handling and non-grease-handling hoods, but not all model codes use Type I/Type II terminology. A Type I hood may be used where a Type II hood is required, but the reverse is not allowed. However, characteristics of the equipment and processes under the hood, and not necessarily the hood type, determine the requirements for the entire exhaust system, including the hood. A Type I hood is used for collecting and removing grease particulate, condensable vapour, and smoke. It includes (1) listed grease filters, baffles, or extractors for removing the grease and (2) fire-suppression system. Type I hoods are required over cooking equipment, such as ranges, fryers, griddles, broilers, and ovens, that produce smoke or grease-laden vapours. A Type II hood collects and removes steam and heat where grease or smoke is not present. It may or may not have grease filters or baffles and typically does not have a firesuppression system. It is usually used over dishwashers. A Type II hood is sometimes used over ovens, steamers, or kettles if they do not produce smoke or grease-laden vapour and if the AHJ allows it. [7] Figure 5.3 shows a typical Wall-mounted canopy, used for all types of cooking equipment located against a wall.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
19
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
5.3.3 Baffle filters Baffle filters (Fig 5.5) have a series of vertical baffles designed to capture grease and drain it into a container. The filters are arranged in a channel or bracket for easy insertion and removal for cleaning. Each hood usually has two or more baffle filters, which are typically constructed of aluminium, steel, or stainless steel and come in various standard sizes. Filters are cleaned by running them through a dishwasher or by soaking and rinsing. NFPA Standard 96 requires that grease filters be listed. Listed grease filters are tested and certified by a nationally recognized test laboratory under UL Standard 1046.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
20
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
ceiling level. This approach is designed to avoid the mixing of air; instead, it displaces the air already present within the space. It therefore has high air change efficiency. Air supply diffusers are usually either free standing or located in the floor. A large total area of diffuser over which the air is uniformly discharge is needed to accomplish the required volume low rate at low supply velocity. Figure 5.5 shows a typical displacement ventilation system. [13]
5.4.2 Combined Exhaust Hoods and Supply Inlets These systems can be inside large halls and may have no fixed limits for their influence, except for some parts of the system (inlet device surface, etc.) They can also be situated inside small rooms, where walls, floors, and ceilings are the natural boundaries. The systems usually consist of one exhaust hood and one supply inlet, which interact. There
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
22
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
are also special combinations, as two or more inlets and one exhaust hood, or one supply inlet and two or more exhausts. All of these combinations need careful design and an accurate relation between supply and exhaust flow rates and velocities. Some systems also need stable temperature conditions to function properly. All combinations are dependent on having a defined contaminant concentration in the inlet air. This usually implies clean supply air, but some systems may use recirculated air with or without cleaning. There are many possible combinations of supply and exhaust air. For example, a line jet could be used as a shield in an opening, as a stripping system on surfaces, for blowing contaminants into an exhaust, etc. An enclosure could be designed with a line jet in the opening, with a wall jet inside to increase efficiency, or with a low-momentum jet inside or outside the opening to replace the room air supply. In this section, only some basic combinations are described. All rooms need both supply and exhaust air. The combined systems described in this section are unique in that they must be chosen and designed simultaneously, since the aim is to get a specific flow fielddependent on the exhaust and the supply simultaneously inside the specified volume. The flow rates are usually not the same in the supply and the exhaust parts of the system. This means that the same flow difference must exist in the room's ventilation system, if the combined system takes its air from outside the room and disposes of the air to the same place. There is no general rule for how to choose between the systems, except what has been specified for exhaust hoods and supply inlets, respectively. Usually, the choice is made by tradition or the equipment available. This should not prevent the designer from exploring the relative advantages and disadvantages of these systems (which are described for each system) and applying and designing a system that suits his or her demands for a specific process. Similar to supply inlets, no measurements exist for evaluating the inlets' specific influence on contaminant concentration. The available measurements for the combinations are the same as for exhaust hoods, i.e., capture efficiencies and similar
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
23
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
measures. Sometimes the performance of a combined system can be approximated from the performance of the incoming supply inlet and exhaust hood. For a combined system it is always important to consider how the person working with a process and the contaminant source are placed in relation to the inlet and outlet. Exactly what their relative positions should be to get the highest efficiency depends on the specific system. [13] 5.4.3 Air jets Air jets are used for many purposes. Some of these are described in other parts of this chapter, but it is not possible to describe all the possible types and uses. When jets are used inside rooms, they do not need to have any corresponding exhaust air. Exhausted air is needed for supply jets in general ventilation, but if the jet's air is taken from the room and blown into the room again, no exhaust is need for supply jets in general ventilation, but if the jet's air is taken from the room and blown into the room again, no exhaust is needed. If the air is taken from the outside the room, it is necessary to the same flow rate exhausted from the room. [13] 5.4.4 Cyclone filters: Cyclone collectors are popularly used both for particle removal and for particle sampling. The separation process of a cyclone relies on the centrifugal accelerations that are produced when particle- laden fluid experiences a rapidly swirling motion in the cyclone. The larger the particle, the stronger the centripetal acceleration it acquires and, therefore, the easier it is for the particle to be collected. Figure5.6 is a schematic diagram of the trajectories for small and large particles in a typical cyclone. A particle of small diameter penetrates the cyclone, whereas a particle of large diameter finds its way to the side wall of the cylindrical portion of the cyclone and is then collected at the apex of the cyclone via the boundary layer flow. The collection efficiency curve is usually employed to demonstrate the performance of a cyclone. Figure 5.7 shows a typical collection efficiency curve for a cyclone at a particular airflow rate. The size of particles that have a collection efficiency of 50% is usually employed as a simple indication of the separation efficiency of the cyclone, and is
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
24
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
known as the cut-off particle size d<ft. Particles larger than the cut-off size d$Q are more likely to be separated by the cyclone, and particles smaller than the cut-off size are more likely to penetrate the cyclone. Pressure loss through the cyclone is also a key performance parameter, and this depends mainly on the design of the cyclone. In general, the pressure drop across the cyclone collector is small compared with most other dust collectors, but the higher the collection efficiency, the larger the pressure drop and hence the energy consumption required. [13]
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
25
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
26
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Figure 6.1 shows the capture jet exhaust hood concept generated in CATIA. The new concept has addressed the issues faced by the older exhaust only hoods. Fig 6.2 shows the parts of newly generated concept.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
27
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
The kitchen hood above cooking appliances contains the rising warm air and contaminants
2 3
The capture air jets direct the contaminated air toward the KSA grease filters Where grease particles and other impurities are separated from the exhaust air using the cyclone separation principle. The extracted grease and other air contaminants flow into a drain channel and toward the collection tray.
Make up air is distributed into the space at low velocity through the front plenum of the hood.
The vertical capture air improves efficiency, and allows the hood to operate at lower exhaust airflows.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
28
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Capture Jet air is used to increase air velocity in the working zone near the cooking equipment in order to compensate for the effects of radiant heat emitted by the cooking equipment.
Figure 6.4 shows the working of the newly designed cyclonic grease filter. The working is as follows: 1. Air enter through a slot in the filter face 2. Air spins through the filter, impinging grease on the filter walls. 3. The cleaner air exits the top and bottom of the filter.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
29
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
30
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
31
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
32
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
was valid for the current application. The near-wall cell thickness was calculated to satisfy the logarithmic law of the wall boundary. Other fluid properties were taken as constants. Filter media of intake system is modelled as porous media using coefficients. In the porous region, the pressure drop per unit length can be determined using the equation p/L= (Pi v + Pv)v Where v is the superficial velocity through the medium and Pi, Pv are coefficients defining the porous resistance, known as the inertial resistance and viscous resistance, respectively. Values for the resistance coefficients can be measured experimentally or derived using various empirical relationships, depending on the exact nature of the problem. In this case, Pi = 2500kg/m4 and Pv = 3000 kg/m3s. These values are roughly what we would expect from an isotropic porous filter.
Momentum:
Where is density, u is jth Cartesian velocity, p is static pressure, is viscous stress tensor
j ij
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
33
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
34
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
The above fig shows the velocity vector plot at outlet section. Velocities are high in Capture jet model because of extra jet of air. Due to high velocity there are large recirculation zones forming at inlet section also which intern increases the mixing and filtration of exhaust gases. The average velocity at outlet is high compared to standard model. Figure 7.9 shows the velocity vector plot of Normal exhaust model:
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
35
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Due to direct placing of filter in hood leads to less capturing efficiency and due to lack of driving force the velocities are pretty low. Hot gases remain in the kitchen.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
36
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Figure 7.10 shows the Pressure Contours of Capture jet model. Figure 7.11 shows the Pressure Contours of cyclonic filter. Due to lot of restriction to air flow in the Capture jet model in the form of filter material and small passages lot pressure is dropping in the Capture jet model. The above pressure contour indicates the lot of pressure variations, the red regions are high pressure regions. It can be observed mainly on filter core. Due to this high pressure drops we need to have fans and blowers to drive the air.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
37
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Figure 7.14 shows the Pressure Contours of exhaust hood model. Figure 7.15 shows the pressure contour of section.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
38
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
It is observed that the pressure variation is very less in standard model when compared to capture jet model. Due to less pressure drop across the hood, it is not required to install Fans and blowers. Figure 7.16 shows the Temperature Contours of section of Capture Jet model.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
39
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Due to high velocity and high turbalance lot of energy transaction will be happen between molcuels of the air, which intern increases the heat carring capacity of jet air. It is observed that exahust temperature of air in the capture is more when compared to standard exhaust model. The main purpose of these kitchen hoods are to carry away the heat generated in the kitchen and to filter the air which is going out. Figure 7.18 shows the Temperature Contours of exhaust only hood model.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
40
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
41
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
The above diagram (Figure 7.20) shows the convergence history of Capture jet model.It took around five itteration to converge.The convergence criteria is taken around 1e-5. Lot of up and downs shows the fluctuating flow in the capture jet.
The above diagram (figure 7.21) shows the convergence history of Capture jet model.It took around five itteration to converge.The coonvergence criteria is taken around 1e-6. There is no much flctuvations in residuals, which indicates smooth flow in standard exhaust model.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
42
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
The above plot (figure 7.22) shows the Capturing efficiency of both type of hood with respect to different flow conditions. It show clearly that for same flow rate capture jet efficiency is more efficient than the standard exhaust model.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
43
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
44
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
45
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
8.2 Recommendations
The application of CFD modelling is a very promising tool, and its use can be very helpful in a large number of applications but also requires some experience of the CFD engineer to produce accurate results. Usually, quite a number of parameter variations are needed, and different levels of simplification of the real situation have to be applied at different stages of the design process to draw the desired conclusions. It is greatly recommended that strong feedback between the designer who needs the results and the CFD engineer is maintained to improve the results. CFD results can only be as good as: 1. Quality of geometric modelling and spatial resolution of computational mesh 2. Models involved in CFD code 3. Knowledge of boundary conditions [13] This is not as simple as it sounds, as the boundary conditions are very often not well known. The number and distribution of heat sources and ventilation parameters, particularly in naturally ventilated surroundings, are very often not known or even vary. The CFD engineer has to cope with this situation and can do one of the following: Choose boundary conditions from his or her knowledge about the given information. Perform calculations with parameters varied to check their importance.
The CFD results can possibly turn out to be helpful more comparatively (qualitatively) than quantitatively.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
46
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)
References
[1] Mark A.Vonderembse et.al, Qualifying function deployments impact on product development, International Journal of Quality Science, Vol.2 no.4, 1997, pp.253-271. [2] Lin Chih Cheng, QFD in product development: methodological characteristics and a guide for intervention, International Journal of Quality & Reliability management, Vol.20 no.1, 2003, pp 107-122. [3] James R.Wixson, Improving product development with value analysis/ value engineering: A total management tool, SAVE conference proceedings, 1987, pp51-66. [4] Biren Prasad, Synthesis of market research data through a combined effort of QFD, value engineering and value graph techniques, Qualitative Market research: An International Journal, Vol.1 no.3, 1998, pp156-172. [5] Fabio et.al, Combined application of QFD & VA tools in the product design process, International Journal of Quality & Reliability Mgmt, Vol.21 No.2, 2004, pp231252. [6] Design Guide: Improving Commercial Kitchen Ventilation system performance, California Energy commission P-500-03-034F Rev.5.5.03, 2002. [7] ASHARE, ASHRAE HVAC Applications Handbook Chapter 31, Kitchen Ventilation, American Society of Heating, Refrigerating and Air-Conditioning Engineers, 2007 [8] Andrey et.al, The effect of supply air systems on kitchen thermal environment, ASHARE transactions: Symposia, Vol 111, Part 1, pp 748-754, 2005. [9] Risto et.al, The influence of a capture jet on the efficiency of a ventilated ceiling in a commercial kitchen, International Journal of Ventilation, Volume1, No.3, pp 189-199, 2003. [10] Risto et.al, Analysis of capture and containment efficiency of a ventilated ceiling, International Journal of Ventilation, Volume2, No.1, pp 33-43, 2003.
Application QFD and Value Engineering concepts in product development of commercial ventilation system exhaust hood
47
M.S Ramaiah School of Advanced Studies Postgraduate Engineering and Management Programme (PEMP)